Professional Documents
Culture Documents
Loaded Transformer
Loading the secondary winding with a current
I2 causes a magnetic flux of that winding. This
flux is linked also with the primary winding and
tends to reduce the total flux seen by the
primary winding. Therefore a compensating
current I1 will flow in the primary winding
producing a compensating flux. The ampere
turns of both windings are nearly equal:
I 1 w1 = I 2 w 2 and
Furnace Transformers
1. Mode of Functioning of a Transformer
F
I1
I2
U1
U2
Fx
F
d
dt
(Law of Induction)(1)
U 02
d
= w2
dt
After elimination of
(2)
d
from the formulae (1)
dt
U 01 w1
=
=
U 02 w 2
is the transformation ratio.
Furnace Transformers
U 2 = w2
U 01 = w1
I1 w2 1
=
=
I 2 w1
d ( x )
d
d
= w2
w2 x
dt
dt
dt
w2
U 01 U x 2
(3)
w1
d
= w 2 x is the short circuit voltage
dt
U2 =
U x2
ux =
U x2
%]
100[
U 02
w2/w1U01
I2
w2/w1U01
Ux2
U2
X2
U2
I2
X =
ux
U2
0 [
]
100 % S n
R=
PCu
[ ]
3 I 2
Transformatorenwerk Nrnberg
0,40
1,00
Secondary Voltage(p.u.)
Secondary current
Power
Short circuit voltage
Short circuit impedance related to U2
The high voltage winding can be star or delta connected. The low voltage winding can have a star-,
delta- or open-circuit connection.
Transformatorenwerk Nrnberg
This type of furnace transformer has the most economic design, as only one active part is required.
(see also 3.1.4). The range of application is limited
due to the maximum height of the primary voltage
as the transient over-voltages in the tapping winding increase considerably with higher system voltages.
The voltage regulation is normally done in unequal
steps due to the variable flux regulation. A coarse
equalisation can be achieved in some cases using
different numbers of turns per step.
3.1.3.Regulation With
Transformer
an
Auto
This type contains two active parts, an auto transformer with regulating winding and a furnace
transformer which are located normally in a common tank.
Furnace transformer
Mp
Auto transformer
mp
3.1.4.Comparison
Types
of
the
Three
transformer and by the chosen concept. The comparison is done based on the same tapping range
for all three types e.g.: Umax/Uconstant/Umin = 1 /
0,8 / 0,5. The ratio between built in power and rated
power for the given tapping range is as follows:
Variable flux regulation:
1,63
Intermediate circuit regulation:
1,44
Regulation with auto transformer: 1,56
The best ratio is achieved in the case of Intermediate circuit regulation, followed by the regulation
with auto transformer. As these types consist of
two active parts, the manufacturing effort is much
higher than in the case of the variable flux regulation. If the transformer is connected to the medium
voltage system, the variable flux regulation leads to
the most economical design. If the transformer is
connected to the high voltage system, the available
manufacturing facilities and the figures given above
will determine the chosen type.
3.1.5.Other Characteristics
Other characteristics of some special types of furnace transformers are given below:
No load star delta switchover of the high voltage
winding of furnace transformers with variable flux
voltage regulation is used to reduce the built in
power in cases where big tapping ranges are required. If for instance a voltage range Umax/Umin
= 1 / 0,33 is foreseen, the built in power is only 1,49
times the rated power if such a switchover connection is used. (compare also 3.1.4).
An individual regulation of each phase can be realised. In this case, a zero sequence flux can occur.
Special measures have to be taken in this case.
Furnace transformers for ac-furnaces can be built
also as single phase units. In the case of the so
called Knappsack-connection, three single phase
units are arranged symmetrically around the furnace. Due to the geometrical symmetry the impedance of the three phases is nearly the same. This
leads to a uniform load of the three phases. This
advantage is compensated by higher manufacturing cost and greater content of material of the single phase units compared with a three phase unit.
Transformatorenwerk Nrnberg
Transformatorenwerk Nrnberg
If clamps of copper are used, they can be connected in parallel and in series.
Furnace Transformers
Transformatorenwerk Nrnberg
4.4. Cooling
U2max=f(Sn)
1,6
4.6. Screening
The stray field of the windings and of the leads
which carry high currents can induce eddy currents
in metallic parts. These eddy currents can cause
high losses and temperatures. These losses and
temperatures can be controlled by the use of magnetic and nonmagnetic screens.
1,4
1,2
1
0,8
0,6
0,4
0,2
0
0
50
100
150
200
120,00
100,00
Resonant events are of major importance. If frequencies are generated which correspond to the
resonant frequencies of the transformer, high overvoltages can be generated inside the transformer.
Resonant events can be started by reignitions of
switches during load-switch-off or by arc interruptions in service.
The protection of transformers against resonant
overvoltages can be done as follows: choosing different resonant frequencies for the system and for
the transformer, using R-C damping elements,
Furnace Transformers
80,00
60,00
40,00
20,00
0,00
0
50
100
150
200
Transformatorenwerk Nrnberg
It is possible, from our point of view to build furnace transformers of higher rated power in the future.
The secondary current of furnace transformers is
limited due to the following factors:
The width of transformer windings is limited
due to the losses produced by the stray field.
Available space for the low voltage bushings
Current distribution in the low voltage bushings
A maximum secondary current of 120 kA can be
reached based on the limitations given above if a
conventional design is used.
The primary current is limited by the tap changers
which are available. Tap changers for furnace
transformers are available up to a maximum current of 3000 A. The rated power of furnace transformers is limited based on this consideration as
follows:
Primary Voltage [kV]
10
20
30
6.
Rated Power
constant up to
Vector group
Rated primary voltage
Secondary voltage
maximum
minimum
steps
Secondary current
Furnace Transformers
105 MVA
837 V
Dd0
30 kV
960 V
550 V
18
73 kA
7%
10,5%
18,2%
2
u k U 022
7% (0,96 kV )
X2
= 0,61m
100% S
100% 105 MVA
X 2 (Tap _ position _ 13)= 0,67 m
X 2 (Tap _ position _ 1)= 0,79m
R2 =
PCu
520 kW
=
= 0,044 m
2
2
3 I
3 (63kA)
The transformer is equipped with a reactor connected in series to the high voltage winding, with an
onload tap changer. The reactance of this reactor
related to the primary terminals as well as to the
secondary terminals(reduced by the square of the
transformation rate 2) is given in the table below:
Tap pos. reactor:
10
9
5
1
Primary side delta
0
0,56 2,63 4,93
Primary side, star
0
0,19 0,88 1,64
Secondary side
0,19
0,90
1,68
0
Tap position 18
m
m
m
Secondary side
0,064
0,29
0,55
0
Tap position 1
m
m
m
The effect of the reactor on the secondary side is
greater if the transformation ratio is lower, i.e. if the
secondary voltage is higher.
Bibliography
[1]
[2]
[3]
Timm, K.: Elektrotechnik des Lichtbogenofens, Seminar vom 19. Bis 22. Oktober 1999 in Saalfeld
Author:
Dipl.Ing.Univ. Egon Kirchenmayer
R&D Department
Siemens-Transformatorenwerk Nrnberg
Transformatorenwerk Nrnberg