Professional Documents
Culture Documents
6/4/02
1:02 am
Page 2
Merlin Gerin
VIP 300 protection relay
Operation, testing and
commissioning
version 003 / April 2002
6/4/02
1:03 am
Page 1
VIP 300
Contents
Content
page
Curve selection
Phase overcurrent
setting area
Other functions
(labels, LEDs, VAP6)
8-9
Testing and
Commissioning
Overview of VAP6 test unit
10
11
Commissioning Ringmaster
with VIP 300
12-15
6/4/02
1:03 am
Page 2
VIP 300
4
C B
phase
overcurrent
10
I>
sensors:
200/1 4509996A0
VIP300LH range: x2
I>>
DT only
EI
VI
RI
1.2
DT
0.15 0.2
0.3
0.1
0.07
0.4
0.05
warning
0.1
not time
multiplier
x1
20
(x Is) off
0.2
0.4
0.6
0.05
0.9
0.03
0.6
(s)
t>
Is
x10
15
(x Is)
12
2.7
curve selection
42 48 56
36
64
30
72
24
80
20 100 90
(A)
9
2.4
1.5
off
VIP300
2.1
1.8
SI
I>
trip
1.5
(s)
t>>
see table
reset
minimum operating
phase current: 20A
Io>
EI
1.8
SI
RI
DT
trip
2.1
1.2
1
9
2.4
1.5
off
t> to>
0.05
0.07
0.1
0.15
0.2
0.3
0.4
0.05
0.6
0.07
0.1
0.15
0.2
0.3
0.4
0.6
x1
x1
x1
x1
x1
x1
x1
x10
x1
x10
x10
x10
x10
x10
x10
x10
SI
VI
EI
0.02
0.02
0.03
0.05
0.07
0.10
0.13
0.17
0.20
0.24
0.34
0.50
0.67
1.01
1.35
2.02
0.03
0.05
0.07
0.10
0.13
0.20
0.27
0.33
0.40
0.47
0.67
1.00
1.33
2.0
2.67
4.00
0.06
0.09
0.12
0.19
0.25
0.37
0.50
0.62
0.74
0.87
1.24
1.86
2.48
3.71
4.95
7.43
Io>>
DT only
VI
15
2.7
3
warning
0.1
(x Ios)
12
20
off
(x Ios)
curve selection
16 24 32
12
40
8
50
4
60
2 80 70
(A)
Io>
0.15 0.2
0.07
x10
0.4
0.05 (s)
x1
0.6
not time
multiplier
0.2
0.4
0.6
0.05
0.9
0.03
to>
Ios
earth fault
0.3
0.1
to>>
see table
1.5
(s)
D
11 12
13
14
15
E
17
18
16
19
20
Other functions
1.
11.
A.
B.
2.
3.
4.
5.
6.
7.
8.
9.
10.
12.
13.
14.
15.
16.
17.
18.
19.
20.
C.
D.
E.
6/4/02
1:03 am
Page 3
VIP 300
Curve selection
G
SI, VI, EI RI
t>
K
t>>
1.2 Is
10 Is
I>>
DT curve selection
t
H
t>
DT
K
t>>
Is 1.2 Is
Operation
The high and low set elements
operate separately. The tripping order
results from the logical OR between
the two settings.
I>
I>>
6/4/02
1:03 am
Page 4
VIP 300
1.
Phase overcurrent
phase
overcurrent
sensors:
200/1 4509996A0
VIP300LH range: x2
I>
I>
EI
1.8
1.5
off
DT
1.2
42 48 56
36
64
30
72
24
80
20 100 90
(A)
Is
reset
0.05
t>
0.3
0.4
(s)
9
2.4
(x Is) 3
warning
0.15 0.2
0.1
0.07
x10
x1
VIP300
2.1
2.7
curve selection
trip
I>>
DT only
VI
SI
RI
not time
multiplier
15
(x Is) off
20
0.2
see table
t>>
0.4
0.6
0.1
0.05
0.03
0.6
12
0.9
(s)
1.5
t> to>
0.05
0.07
0.1
0.15
0.2
0.3
0.4
0.05
0.6
0.07
0.1
0.15
0.2
0.3
0.4
0.6
x1
x1
x1
x1
x1
x1
x1
x10
x1
x10
x10
x10
x10
x10
x10
x10
SI
VI
EI
0.02
0.02
0.03
0.05
0.07
0.10
0.13
0.17
0.20
0.24
0.34
0.50
0.67
1.01
1.35
2.02
0.03
0.05
0.07
0.10
0.13
0.20
0.27
0.33
0.40
0.47
0.67
1.00
1.33
2.0
2.67
4.00
0.06
0.09
0.12
0.19
0.25
0.37
0.50
0.62
0.74
0.87
1.24
1.86
2.48
3.71
4.95
7.43
Phase overcurrent
setting area
2.
Phase overcurrent
pick-up indicator
3.
SI
VI
EI
RI
6.
:
:
:
:
7.
8.
4.
9.
Setting current Is
Choice of low
set curve
5.
Multiplying factor
(low set)
6/4/02
1:03 am
Page 5
VIP 300
Earth fault
reset
minimum operating
phase current: 20A
Io>
EI
1.8
2.1
1.2
1
9
2.4
1.5
off
DT
Io>>
DT only
VI
SI
RI
trip
2.7
(x Ios)
12
15
6
4
20
(x Ios) off
curve selection
Io>
earth fault
16 24 32
12
40
8
50
4
60
2 80 70
(A)
Ios
0.15 0.2
0.1
0.07
0.05 (s)
to>
warning
0.3
0.4
0.6
x10
x1
not time
multiplier
0.2
0.03
see table
to>>
0.4
0.6
0.1
0.05
0.9
(s)
1.5
VAP6 test plug
6/4/02
1:03 am
Page 6
VIP 300
A.
Other functions
Reversible scale label for Ringmaster fitted with 200/1A CTs
sensor
200/1: 4509996A0
sensor
200/1: 4509996A0
VIP 300LHrange: x4
Is
Is
48
42
56
36
64
30
72
24
80
20 100 90
(A)
96
84
112
72
128
60
144
48
160
40 200 180
(A)
minimum operating
phase current: 20A
minimum operating
phase current: 40A
Ios
Ios
24
16
32
12
40
8
50
4
60
2 80 70
(A)
x 2 range
48
32
64
24
80
16
100
8
120
4 160 140
(A)
x 4 range
sensor
400/1: 451101200
sensor
400/1: 451101200
VIP 300LHrange: x4
B.
CT and range
indication
Is
Is
96
84
112
72
128
60
144
48
160
40 200 180
(A)
192
168
224
144
256
120
288
96
320
80 400 360
(A)
minimum operating
phase current: 40A
minimum operating
phase current: 80A
Ios
Ios
48
32
64
24
80
16
100
8
120
4 160 140
(A)
x 2 range
96
64
128
48
160
32
200
16
240
8 320 280
(A)
x 4 range
sensor
800/1: 4509169A0
sensor
800/1: 4509169A0
VIP 300LHrange: x4
Is
Is
192
336
448
288
512
240
576
192
640
160 800 720
(A)
(A)
minimum operating
phase current: 80A
minimum operating
phase current: 160A
Ios
Ios
(A)
x 2 range
Installation
384
168
224
144
256
120
288
96
320
80 400 360
96
64
128
48
160
32
200
16
240
8 320 280
192 256
128
96
320
64
400
32
480
16 640 560
(A)
x 4 range
6/4/02
1:03 am
Page 7
VIP 300
C.
D.
Minimum operating
current
E.
6/4/02
1:03 am
Page 8
VIP 300
D
external mitop
I>
on
test in progress
trip
battery test
phase overcurrent
earth fault
trip
inhibition
earth fault
test
phase
overcurrent
test
phase
overcurrent
VIP 30
VIP 35
VIP300
VIP50
VIP75
trip
trip
inhibition
external
mitop
Indicators
Push buttons:
C Trip:
Is used to test other relays in the
VIP range. It is not to be
considered for the VIP 300 test (it
lights up for a transient period
when the VIP 300 sends a tripping
order; whether or not the circuit
breaker is inhibited).
Battery test:
If the batteries are healthy, the
on indicator(A) lights up when
the button is pressed.
Phase overcurrent:
Sends the phase overcurrent test
stimulus, which is equivalent to
20 times the setting current Is.
circuit breaker
mitop
circuit breaker
mitop
VAP6
Earth fault:
Sends the earth fault test
stimulus, which is equivalent to
20 times the earth setting current
Ios.
Trip inhibition:
By pressing and holding this
button down the relay can be
tested with the VAP6 without
tripping the circuit breaker. This
facility will inhibit the circuit
breaker tripping even if a real
fault occurs during the test.
A On:
Indicates that the batteries are
operating. Also lights up when the
battery test is carried out by
pressing battery test.
B Test in progress:
Confirms sending of the test
stimulus to the VIP 300.
Batteries:
Technical characteristics:
Supply:
Weight:
Dimensions:
10
3 x 9V 6LR61
batteries
0.45KG
93 X 157 X 45mm
6/4/02
1:03 am
Page 9
VIP 300
11
6/4/02
1:03 am
Page 10
VIP 300
Factory tests:
Reduced commissioning:
Secondary injection:
Caution:
The injection set is connected to the VIP 300 relay without disconnecting the CTs.
This is done via the sockets on the terminal rail located in the pilot cable box, just
above the relay itself.
To test the overcurrent protection the connection should be made across two CTs
(terminal rails nos 4 to 5, 5 to 6 or 6 to 4).
Note: When using a secondary injection set with VIP 300 a filter (e.g. Foster SF30)
should be used to improve the wave form. If a filter is not used the operating time of
the relay may not follow the theoretical operating times.
52
7
x4 range
40A,80A or 160A
5 minimum
operating
3 current
1
P2
S1
P1
S1
P1
S2
S2
P2
S1
B
S2
P2
C11
C31
C31
C51
C51
x2 range
20A,40A or 80A
minimum
operating
4 current
C10
C70
C30
C50
C90
10
S2
C71
P1
CT1
C11
C70
11
12
13
14
MITOP - ITC
K8
K7
(-VE)
(+VE)
0v
15
16
12
CB auxiliary contact
(for timing purposes)
6/4/02
1:03 am
Page 11
VIP 300
Recommended test
procedure for
secondary injection:
The test procedure outlined here is only
a guide and may need modifying to suit
the different test sets available.
1.
Pick-up check
- Increase the current slowly until
the appropriate LED indicator
starts to blink.
2.
Setting check:
- Set the current to be injected
(a true RMS ammeter should be
used to measure the current).
- The CB should then be closed
and the counter/timer reset. The
current should then be applied.
- When the CB has operated, the
applied current should be turned
off if not done automatically.
- The time shown on the counter
display includes the operating
time of the circuit breaker
>80ms or <100ms. The actual
relay operating time can then be
calculated by subtracting this
time from the counter reading.
Note. - No connection should be made to the MITOP trip coil from the secondary
injection test set.
RN6c
CT ratio 400/1A
CE6, RN6c
CT ratio 800/1A
Range x 2
Range x 4
Range x 2
Range x 4
Range x 2
Range x 4
Minimum Operating
Current=20A
Minimum Operating
Current=40A
Minimum Operating
Current=40A
Minimum Operating
Current=80A
Minimum Operating
Current=80A
Minimum Operating
Current=160A
Secondary
injected current
Equivalent
primary current
Secondary
injected current
Equivalent
primary current
Secondary
injected current
Equivalent
primary current
Secondary
injected current
Equivalent
primary current
Secondary
injected current
Equivalent
primary current
Secondary
injected current
Equivalent
primary current
100mA
20A
200mA
40A
100mA
40A
200mA
80A
100mA
80A
200mA
160A
120mA
24A
240mA
48A
120mA
48A
240mA
96A
120mA
96A
240mA
192A
150mA
30A
300mA
60A
150mA
60A
300mA
120A
150mA
120A
300mA
240A
180mA
36A
360mA
72A
180mA
72A
360mA
144A
180mA
144A
360mA
288A
210mA
42A
420mA
84A
210mA
84A
420mA
168A
210mA
168A
420mA
336A
240mA
48A
480mA
96A
240mA
96A
480mA
192A
240mA
192A
480mA
384A
280mA
56A
560mA
112A
280mA
112A
560mA
224A
280mA
224A
560mA
448A
320mA
64A
640mA
128A
320mA
128A
640mA
256A
320mA
256A
640mA
512A
360mA
72A
720mA
144A
360mA
144A
720mA
288A
360mA
288A
720mA
576A
400mA
80A
800mA
160A
400mA
160A
800mA
320A
400mA
320A
800mA
640A
450mA
90A
900mA
180A
450mA
180A
900mA
360A
450mA
360A
900mA
720A
500mA
100A
1A
200A
500mA
200A
1A
400A
500mA
400A
1A
800A
13
6/4/02
1:03 am
Page 12
VIP 300
tick as appropriate
Customer
Site
Contact ref.
Panel
Relay type
Current transformers
200/1A
x2, 20A
x4, 40A
400/1A
x2, 40A
x4, 80A
800/1A
x2, 80A
x4, 160A
Note. Ensure connections on the rear of the relay are made to the appropriate
terminals for the x2 or x4 setting ranges and that the scale labels are inserted
correctly to match the range selected.
Indicate on the diagram below actual settings. Carry out tests and record the results
in the table provided.
200/1A
68
800/1A
sensor
200/1: 4509996A0
sensor
200/1: 4509996A0
sensor
400/1: 451101200
sensor
400/1: 451101200
sensor
800/1: 4509169A0
sensor
800/1: 4509169A0
VIP 300LHrange: x4
VIP 300LHrange: x4
VIP 300LHrange: x4
Is
Is
Is
Is
Is
48
42
56
36
64
30
72
24
80
20 100 90
(A)
96
84
112
72
128
60
144
48
160
40 200 180
(A)
96
84
112
72
128
60
144
48
160
40 200 180
(A)
192
168
224
144
256
120
288
96
320
80 400 360
(A)
192
168
224
144
256
120
288
96
320
80 400 360
minimum operating
phase current: 20A
minimum operating
phase current: 40A
minimum operating
phase current: 40A
minimum operating
phase current: 80A
minimum operating
phase current: 80A
minimum operating
phase current: 160A
Ios
Ios
Ios
Ios
Ios
Ios
24
16
32
12
40
8
50
4
60
2 80 70
48
32
64
24
80
16
100
8
120
4 160 140
48
32
64
24
80
16
100
8
120
4 160 140
(A)
(A)
400/1A
phase
overcurrent
I>
I>
EI
1.8
2.4
DT
(s)
curve selection
2.7
(x Is) 3
trip
warning
0.15 0.2
0.3
0.1
0.07
x10
0.4
0.05
not time
multiplier
x1
see table
t>
12
15
6
4
20
(x Is) off
0.2
0.4
0.6
0.1
0.05
0.9
0.03
0.6
1.5
(s)
t>>
reset
Io>
EI
1.8
RI
trip
DT
2.1
9
2.4
1.5
off
1.2
2.7
t> to>
0.05
0.07
0.1
0.15
0.2
0.3
0.4
0.05
0.6
0.07
0.1
0.15
0.2
0.3
0.4
0.6
x1
x1
x1
x1
x1
x1
x1
x10
x1
x10
x10
x10
x10
x10
x10
x10
SI
VI
EI
0.02
0.02
0.03
0.05
0.07
0.10
0.13
0.17
0.20
0.24
0.34
0.50
0.67
1.01
1.35
2.02
0.03
0.05
0.07
0.10
0.13
0.20
0.27
0.33
0.40
0.47
0.67
1.00
1.33
2.0
2.67
4.00
0.06
0.09
0.12
0.19
0.25
0.37
0.50
0.62
0.74
0.87
1.24
1.86
2.48
3.71
4.95
7.43
Io>>
DT only
VI
SI
(A)
VIP 300
9
1.2
192 256
128
96
320
64
400
32
480
16 640 560
(A)
2.1
1.5
off
RI
96
64
128
48
160
32
200
16
240
8 320 280
I>>
DT only
VI
SI
(A)
(A)
96
64
128
48
160
32
200
16
240
8 320 280
(A)
(A)
Is
384
336
448
288
512
240
576
192
640
160 800 720
(s)
12
15
6
4
warning
0.1
20
(x Ios) off
curve selection
0.15 0.2
Io>
0.1
0.07
0.05 (s)
earth fault
14
to>
0.3
0.4
0.6
x10
x1
not time
multiplier
0.2
see table
0.6
0.05
0.03
to>>
0.4
0.9
(s)
1.5
VAP6 test plug
6/4/02
1:02 am
Page 4
VIP 300
Commissioning test
record
1.
Pick up check.
Inject the test current into the
relay for each phase in turn and
note the current required to flash
the LED.
2.
3.
Curve...............
T..............
Phase A-B
Phase B-C
Curve........... T..............
Phase C-A
EF
Date
Customer witness
Date
15
6/4/02
1:02 am
Page 1
Merlin Gerin - Medium Voltage, 123 Jack Lane, Leeds LS10 1BS
Tel: 0113 290 3500 Fax: 0113 290 3710 Internet address: http://www.schneider.co.uk