Bulletin 150
SMC-50
200690V
90520 A
Features
Soft Start
Linear Acceleration/Deceleration
Torque Control
Kickstart
Pump Control
Current Limit
Full Voltage
Energy Saver
Soft Stop
Accu-Stop
S
NA
Single-phase Operation
DPI Communication
Metering
Network Communications
Inside-the-Delta Functionality
DeviceLogix
Product Selection
Page 15
S = Standard Feature
O = Optional Feature
The starter does not include a configuration device as standard.
With removable terminal block.
The starter ships with two 24V DC control inputs and two relay outputs as standard.
The SMC-50 Starter is fully solid-state (no integrated bypass). An external bypass contactor can be added as an option.
Accu-Stop is not included as a parameter/function like that of the SMC-Flex. However, the Accu-Stop function can be accomplished with the Stop Option and
Slow Speed with Braking functions.
Firmware rev. 4.XXX and higher.
Publication 150-SG010E-EN-P
Bulletin 150
Table of Contents
For updated certification status of controllers with 24V DC control power, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
Selection Guide
This selection guide/catalog provides minimum information needed to select the proper SMC-50 Smart Motor Controller according to the
motor ratings used in the application. For normal duty applications (e.g., pumps, compressors, and short conveyors), refer to the Normal Duty
Product Selection tables on page 15 and page 21. For high inertia, heavy duty applications (e.g., rock crushers, wood chippers, centrifugal
fans, and long conveyors), refer to the Heavy Duty Product Selection tables on page 18 and page 23. For best selection results in all cases,
especially where there is frequent starting and stopping or when it is unclear if the application is Normal Duty or Heavy Duty, it is highly
recommended that the free selection tools be used (available at http://www.rockwellautomation.com). For additional assistance, please visit
www.rockwellautomation.com or contact Industrial Controls Technical Support by email at raictechsupport@ra.rockwell.com or by phone at
440-646-5800.
Product Overview
Port 9
Bulletin 150
Selectable Kickstart
Soft Start
Current Limit
100%
Percent Voltage
Initial
Torque
Ramp Time
Start
Run
Time in Seconds
Current Limit
100%
Percent Speed
Linear
Acceleration
Linear
Deceleration
Stop Time
Ramp Time
Start
Run
Time in Seconds
Current Limit
100%
Torque
Ramp
Starting
Torque
Ramp Time
Start
Run
Time in Seconds
600%
Current Limit
50%
Start
Time in Seconds
Stop
Publication 150-SG010E-EN-P
Soft Stop
Bulletin 150
Kickstart
Level
Coast-to-Rest
Soft Stop
Kickstart
Time
Initial
Torque
Run
Start
Soft Stop
Time in Seconds
100%
Motor Speed
Pump Start
Ramp Time
Run
Time in Seconds
Pump Stop
Stop Time
Ramp #2
Initial
Torque #2
Ramp #1
Initial
Torque #1
Start #1
Start #2
Time in Seconds
Run #1
Run #2
Percent Voltage
Time in Seconds
Bulletin 150
Motor Speed
Forward
15% - High
1% - Low
Start
Run
Reverse
Time in Seconds
Stopping Modes
The SMC-50 Smart Motor Controller provides the following Stopping Modes of operation as standard:
Stopping Modes
Coast
Soft Stop
Pump Stop
Coast
Configuring the stop mode to coast sets the controller to perform a
motor coast-to-stop maneuver.
Soft Stop
100%
Kickstart
Time
Percent Voltage
Coast-to-Rest
Soft Stop
Soft Start
Inital
Torque
Ramp Time
Start
Stop Time
Run
Time in Seconds
Soft Stop
Linear
Acceleration
Linear
Deceleration
Stop Time
Ramp Time
Start
Publication 150-SG010E-EN-P
Run
Time in Seconds
Stop
Bulletin 150
Pump Start
Ramp Time
Pump Stop
Stop Time
Run
Time in Seconds
Accu-Stop
100%
Motor Speed
This mode provides motor braking for applications that require the
motor to stop faster than a coast-to-rest. Braking control with
automatic zero speed shutoff is fully integrated into the design of
the SMC-50. This design facilitates a clean, straight-forward
installation and eliminates the requirement for additional hardware
(e.g., braking contactors, resistors, timers, and speed sensors). The
micro-processor based braking system applies braking current to a
standard squirrel-cage induction motor. The strength of the braking
current is programmable from 0400% of full-load current.
Coast-to-Rest
Stop
Time
Start
Brake
Run
Time in Seconds
Automatic Zero
Speed Shut-Off
Coast-to-Rest
7 or 15 %
Slow
Speed
Start
Run
Stop
Time in Seconds
Accu-Stop
100%
Motor Speed
Braking
15%
15%
1%
1%
Start
Run
Slow Speed
Coast-toRest
Brake
Bulletin 150
Running Modes
The SMC-50 Smart Motor Controller provides the following running modes of operation as standard:
Running Modes
SCR Control Normal Run
Operation
Emergency Run
The SMC-50 uses its power section SCRs to start, run, and stop
(except for Coast-to-Stop) a squirrel-cage induction motor. The
basic operation of the SCRs is to switch on (conduct) for a certain
percentage of the 50/60 Hz AC sine wave, as directed by the SMC50, to control the amount of voltage applied to the motor. By using
special control algorithms and motor feedback to manage voltage
supplied, the SMC-50 provides the previously outlined motor
starting, stopping, and braking control modes. During the normal
run operation, the SMC-50 power section SCRs are conducting for
100% of the 50/60 Hz AC sine wave to provide the motor specified
full load current (FLA/FLC) voltage and the resulting torque.
Emergency Run
When one of the SMC-50's inputs is configured for Emergency Run
and that input is activated, all system faults are disabled. This
prevents the system from being shut down by a fault.
Publication 150-SG010E-EN-P
Bulletin 150
The SMC-50 also has user-configurable motor alarms and faults which can be used to indicate required or planned maintenance.
Planned Maintenance Hours
Planned Maintenance Starts
Bulletin 150
Metering System
Power and operational monitoring parameters include:
Current The RMS current value is provided for each phase, plus the average current of all three.
Voltage The RMS line-to-line and line-to-neutral voltage values are provided while the motor is running and when stopped. The average of
all three is also provided.
Line Frequency The SMC-50 measures and provides user access to the line frequency (Hz).
Power Real, reactive, and apparent power values are calculated for each phase plus the total for all 3 phases. In addition, the current
power demand and the maximum power demand is provided.
Power Factor The value of the power factor is provided for each phase and as a total of all three.
Peak Starting Current The SMC-50 stores the peak average RMS motor current consumed for the last 5 start cycles.
Total Harmonic Distortion (THD) The SMC-50 calculates and provides user access to the THD for the 3 line voltages and 3 motor
currents, along with the average value of each.
Voltage Unbalance The calculation of the voltage unbalance signal is provided.
Current Imbalance The calculation of the current imbalance signal is provided.
Energy Savings The SMC-50 provides the percentage of energy saved when it is running the motor in the Energy Savings mode.
Motor Torque Electromechanical motor torque is calculated based on current and voltage feedback from the motor.
Motor Speed The SMC-50 provides a calculated estimate of motor speed in percent of full speed when operating in the linear speed
acceleration starting or deceleration stopping mode.
Elapsed Time & Elapsed Time 2 An elapsed time meter is provided to account for the total accumulated hours the motor has been
running. The meter can be reset by the user. Elapsed Time 2 cannot be user reset and will hold after 50,000 hours have elapsed.
Running Time The running time meter accumulates time (in hours) from the point the motor start command is given up to the point the
motor stop command is issued. When a new start command is given, the meter resets to zero and begins accumulating time again.
Actual Start Time The unit stores the actual time it takes to complete a start cycle (motor start command issued until motor is up-tospeed). The last five start times are stored as parameters for user access and in the Alarm Buffer as events.
Total Starts The total starts counter increments on every successful start (no prestart fault occurred) and cannot be reset. The maximum
value is 65,635.
10
Publication 150-SG010E-EN-P
Bulletin 150
DPI Port 1
DPI Port 4
11
Bulletin 150
12
Publication 150-SG010E-EN-P
Bulletin 150
13
Bulletin 150
150-S
B1
D - 8B
Enclosure Type
Control Voltage
Code
Description
Code
Description
Code
Description
150-S
150B-S
Open
Line Voltage
Controller Ratings
Code
B1
90 A
B2
110 A
B3
140 A
B4
Open Type
Description
Code
Description
Code
Description
Code
Description
8L
8M
8B
180 A
C1
210 A
C2
260 A
C3
320 A
D1
361 A
D2
420 A
D3
520 A
152H-S
B1
a
Bulletin Number Product Type
Code
Description
152H-S
152B-S
153H-S
153B-S
b
Controller Ratings
Code
Description
B1
90 A, 60 Hp @ 460V AC
B2
110 A, 75 Hp @ 460V AC
B3
B4
C1
C2
C3
D1
D2
D3
BD - 41 - 8B
d
Line Voltage
Code
Description
HD
Code
Description
AD
8L
BD
8M
CD
8B
e
Horsepower
Code
Hp Rating
41
10
42
15
43
20
44
25
45
30
46
40
47
50
48
60
49
75
50
100
51
125
52
150
54
200
56
250
Enclosure Type
57
300
Code
Description
58
350
59
400
60
450
61
500
14
Publication 150-SG010E-EN-P
Bulletin 150
Motor Current
[A]
Motor kW,
50 Hz
3090
Motor Hp,
60 Hz
1025
37110
1530
47140
2040
60180
2560
70210
2560
200/208
87260
3075
107320
40100
120361
50125
140420
50150
174520
75150
Control Power
Cat. No.
150-SB1NBD
150-SB1FHD
24V DC
150-SB1NBR
150-SB2NBD
24V DC
150-SB2NBR
150-SB3NBD
24V DC
150-SB3NBR
150-SB4NBD
24V DC
150-SB4NBR
150-SC1NBD
24V DC
150-SC1NBR
150-SC2NBD
24V DC
150-SC2NBR
150-SC3NBD
24V DC
150-SC3NBR
150-SD1NBD
24V DC
150-SD1NBR
150-SD2NBD
24V DC
150-SD2NBR
150-SD3NBD
24V DC
150-SD3NBR
150-SB2FHD
150-SB3FHD
150-SB4FHD
150-SC1FHD
150-SC2FHD
150-SC3FHD
150-SD1FHD
150-SD2FHD
150-SD3FHD
Requires a bypass contactor. Add -BP or -NB to the end of the catalog number to denote an IEC or NEMA bypass contactor, respectively. Example, for a
NEMA bypass contactor, Cat. No. 150-SB2FHD becomes 150-SB2FHD-NB.
Rated
Utilization
Voltage
[V AC]
Motor Current
[A]
3090
37110
47140
60180
70210
Motor kW,
50 Hz
1025
1132
1545
18.555
2263
Motor Hp,
60 Hz
1530
1540
2050
2560
3075
230
87260
107320
120361
140420
174520
3080
37100
40110
45132
63160
40100
50125
50150
60150
75200
Control Power
Cat. No.
150-SB1NBD
150-SB1FAD
24V DC
150-SB1NBR
150-SB2NBD
24V DC
150-SB2NBR
150-SB3NBD
24V DC
150-SB3NBR
150-SB4NBD
24V DC
150-SB4NBR
150-SC1NBD
24V DC
150-SC1NBR
150-SC2NBD
24V DC
150-SC2NBR
150-SC3NBD
24V DC
150-SC3NBR
150-SD1NBD
24V DC
150-SD1NBR
150-SD2NBD
24V DC
150-SD2NBR
150-SD3NBD
24V DC
150-SD3NBR
150-SB2FAD
150-SB3FAD
150-SB4FAD
150-SC1FAD
150-SC2FAD
150-SC3FAD
150-SD1FAD
150-SD2FAD
150-SD3FAD
Requires a bypass contactor. Add -BP or -NB to the end of the catalog number to denote an IEC or NEMA bypass contactor, respectively. Example, for a
NEMA bypass contactor, Cat. No. 150-SB2FAD becomes 150-SB2FAD-NB.
15
Bulletin 150
Motor Current
[A]
3090
37110
47140
60180
70210
Motor kW,
50 Hz
1750
2055
3075
3790
40110
Motor Hp,
60 Hz
2560
3075
40100
50150
60150
400/415 (kW)
460 (Hp)
87260
107320
120361
140420
174520
50132
63160
75200
80220
100300
75200
100250
100300
125350
150450
Control Power
Cat. No.
150-SB1NBD
150-SB1FBD
24V DC
150-SB1NBR
150-SB2NBD
24V DC
150-SB2NBR
150-SB3NBD
24V DC
150-SB3NBR
150-SB4NBD
24V DC
150-SB4NBR
150-SC1NBD
24V DC
150-SC1NBR
150-SC2NBD
24V DC
150-SC2NBR
150-SC3NBD
24V DC
150-SC3NBR
150-SD1NBD
24V DC
150-SD1NBR
150-SD2NBD
24V DC
150-SD2NBR
150-SD3NBD
24V DC
150-SD3NBR
150-SB2FBD
150-SB3FBD
150-SB4FBD
150-SC1FBD
150-SC2FBD
150-SC3FBD
150-SD1FBD
150-SD2FBD
150-SD3FBD
Requires a bypass contactor. Add -BP or -NB to the end of the catalog number to denote an IEC or NEMA bypass contactor, respectively. Example, for a
NEMA bypass contactor, Cat. No. 150-SB2FBD becomes 150-SB2FBD-NB.
Rated
Utilization
Voltage
[V AC]
Motor Current
[A]
3090
37110
47140
60180
70210
Motor kW,
50 Hz
2063
2575
3290
45125
50150
Motor Hp,
60 Hz
3075
40100
50125
60150
75200
500 (kW)
575 (Hp)
87260
107320
120361
140420
174520
63185
75220
90250
100300
125375
100250
125300
125350
150450
200500
Control Power
Cat. No.
150-SB1NUD
150-SB1FCD
24V DC
150-SB1NUR
150-SB2NUD
24V DC
150-SB2NUR
150-SB3NUD
24V DC
150-SB3NUR
150-SB4NUD
24V DC
150-SB4NUR
150-SC1NUD
24V DC
150-SC1NUR
150-SC2NUD
24V DC
150-SC2NUR
150-SC3NUD
24V DC
150-SC3NUR
150-SD1NUD
24V DC
150-SD1NUR
150-SD2NUD
24V DC
150-SD2NUR
150-SD3NUD
24V DC
150-SD3NUR
150-SB2FCD
150-SB3FCD
150-SB4FCD
150-SC1FCD
150-SC2FCD
150-SC3FCD
150-SD1FCD
150-SD2FCD
150-SD3FCD
Requires a bypass contactor. Add -BP or -NB to the end of the catalog number to denote an IEC or NEMA bypass contactor, respectively. Example, for a
NEMA bypass contactor, Cat. No. 150-SB2FCD becomes 150-SB2FCD-NB.
16
Publication 150-SG010E-EN-P
Bulletin 150
Motor kW, 50 Hz
3080
37100
45132
63160
75200
Motor Hp, 60 Hz
3075
40100
50125
60150
75200
90250
110315
125355
160400
185500
100250
125300
125350
150450
200500
Control Power
Cat. No.
150-SB1NUD
24V DC
150-SB1NUR
150-SB2NUD
24V DC
150-SB2NUR
150-SB3NUD
24V DC
150-SB3NUR
150-SB4NUD
24V DC
150-SB4NUR
150-SC1NUD
24V DC
150-SC1NUR
150-SC2NUD
24V DC
150-SC2NUR
150-SC3NUD
24V DC
150-SC3NUR
150-SD1NUD
24V DC
150-SD1NUR
150-SD2NUD
24V DC
150-SD2NUR
150-SD3NUD
24V DC
150-SD3NUR
17
Bulletin 150
Motor Current
[A]
Motor kW,
50 Hz
3090
1025
37110
1530
47140
2040
60180
200/208
70210
Motor Hp,
60 Hz
2560
87260
2560
3075
107320
40100
120361
50125
140420
50150
Control Power
Cat. No.
150-SB2NBD
24V DC
150-SB2NBR
150-SB3NBD
24V DC
150-SB3NBR
150-SB4NBD
24V DC
150-SB4NBR
150-SC1NBD
24V DC
150-SC1NBR
150-SC2NBD
24V DC
150-SC2NBR
150-SC3NBD
24V DC
150-SC3NBR
150-SD1NBD
24V DC
150-SD1NBR
150-SD2NBD
24V DC
150-SD2NBR
150-SD3NBD
24V DC
150-SD3NBR
150-SB2FHD
150-SB3FHD
150-SB4FHD
150-SC1FHD
150-SC2FHD
150-SC3FHD
150-SD1FHD
150-SD2FHD
150-SD3FHD
Requires a bypass contactor. Add -BP or -NB to the end of the catalog number to denote an IEC or NEMA bypass contactor, respectively. Example, for a
NEMA bypass contactor, Cat. No. 150-SB2FHD becomes 150-SB2FHD-NB.
Rated
Utilization
Voltage
[V AC]
Motor Current
[A]
3090
37110
47140
60180
230
70210
87260
107320
120361
140420
Motor kW,
50 Hz
1025
1132
1545
18.555
2263
3080
37100
40110
45132
Motor Hp,
60 Hz
1530
1540
2050
2560
3075
40100
50125
50150
60150
Control Power
Cat. No.
150-SB2NBD
24V DC
150-SB2NBR
150-SB3NBD
24V DC
150-SB3NBR
150-SB4NBD
24V DC
150-SB4NBR
150-SC1NBD
24V DC
150-SC1NBR
150-SC2NBD
24V DC
150-SC2NBR
150-SC3NBD
24V DC
150-SC3NBR
150-SD1NBD
24V DC
150-SD1NBR
150-SD2NBD
24V DC
150-SD2NBR
150-SD3NBD
24V DC
150-SD3NBR
150-SB2FAD
150-SB3FAD
150-SB4FAD
150-SC1FAD
150-SC2FAD
150-SC3FAD
150-SD1FAD
150-SD2FAD
150-SD3FAD
Requires a bypass contactor. Add -BP or -NB to the end of the catalog number to denote an IEC or NEMA bypass contactor, respectively. Example, for a
NEMA bypass contactor, Cat. No. 150-SB2FAD becomes 150-SB2FAD-NB.
18
Publication 150-SG010E-EN-P
Bulletin 150
Motor Current
[A]
3090
37110
47140
60180
400/415 (kW)
460 (Hp)
70210
87260
107320
120361
140420
Motor kW,
50 Hz
1750
2055
3075
3790
40110
50132
63160
75200
80220
Motor Hp,
60 Hz
2560
3075
40100
50150
60150
75200
100250
100300
125350
Control Power
Cat. No.
150-SB2NBD
24V DC
150-SB2NBR
150-SB3NBD
24V DC
150-SB3NBR
150-SB4NBD
24V DC
150-SB4NBR
150-SC1NBD
24V DC
150-SC1NBR
150-SC2NBD
24V DC
150-SC2NBR
150-SC3NBD
24V DC
150-SC3NBR
150-SD1NBD
24V DC
150-SD1NBR
150-SD2NBD
24V DC
150-SD2NBR
150-SD3NBD
24V DC
150-SD3NBR
150-SB2FBD
150-SB3FBD
150-SB4FBD
150-SC1FBD
150-SC2FBD
150-SC3FBD
150-SD1FBD
150-SD2FBD
150-SD3FBD
Requires a bypass contactor. Add -BP or -NB to the end of the catalog number to denote an IEC or NEMA bypass contactor, respectively. Example, for a
NEMA bypass contactor, Cat. No. 150-SB2FBD becomes 150-SB2FBD-NB.
Rated
Utilization
Voltage
[V AC]
Motor Current
[A]
3090
37110
47140
60180
500 (kW)
575 (Hp)
70210
87260
107320
120361
140420
Motor kW,
50 Hz
2063
2575
3290
45125
50150
63185
75220
90250
100300
Motor Hp,
60 Hz
3075
40100
50125
60150
75200
100250
125300
125350
150450
Control Power
Cat. No.
150-SB2NUD
24V DC
150-SB2NUR
150-SB3NUD
24V DC
150-SB3NUR
150-SB4NUD
24V DC
150-SB4NUR
150-SC1NUD
24V DC
150-SC1NUR
150-SC2NUD
24V DC
150-SC2NUR
150-SC3NUD
24V DC
150-SC3NUR
150-SD1NUD
24V DC
150-SD1NUR
150-SD2NUD
24V DC
150-SD2NUR
150-SD3NUD
24V DC
150-SD3NUR
150-SB2FCD
150-SB3FCD
150-SB4FCD
150-SC1FCD
150-SC2FCD
150-SC3FCD
150-SD1FCD
150-SD2FCD
150-SD3FCD
Requires a bypass contactor. Add -BP or -NB to the end of the catalog number to denote an IEC or NEMA bypass contactor, respectively. Example, for a
NEMA bypass contactor, Cat. No. 150-SB2FCD becomes 150-SB2FCD-NB.
19
Bulletin 150
70210
87260
107320
120361
140420
Motor kW, 50 Hz
3080
37100
45132
63160
75200
90250
110315
125355
160400
Motor Hp, 60 Hz
3075
40100
50125
60150
75200
100250
125300
125350
150450
Control Power
Cat. No.
150-SB2NUD
24V DC
150-SB2NUR
150-SB3NUD
24V DC
150-SB3NUR
150-SB4NUD
24V DC
150-SB4NUR
150-SC1NUD
24V DC
150-SC1NUR
150-SC2NUD
24V DC
150-SC2NUR
150-SC3NUD
24V DC
150-SC3NUR
150-SD1NUD
24V DC
150-SD1NUR
150-SD2NUD
24V DC
150-SD2NUR
150-SD3NUD
24V DC
150-SD3NUR
20
Publication 150-SG010E-EN-P
Bulletin 150
Rated Utilization
Voltage
[V AC]
Motor kW, 50 Hz
52155
2050
65190
2560
82242
3075
104311
40100
122363
200/208
50125
151450
60150
186554
75200
210625
75200
243727
100250
302900
Rated Utilization
Voltage
[V AC]
Motor Hp, 60 Hz
125300
Motor kW, 50 Hz
1750
2055
3075
37100
40110
Motor Hp, 60 Hz
2060
2560
4075
40100
50125
230
151450
186554
210625
243727
302900
50132
63160
75200
80220
100300
60150
75200
100250
100300
125350
Control Power
Cat. No.
150-SB1NBD
24V DC
150-SB1NBR
150-SB2NBD
24V DC
150-SB2NBR
150-SB3NBD
24V DC
150-SB3NBR
150-SB4NBD
24V DC
150-SB4NBR
150-SC1NBD
24V DC
150-SC1NBR
150-SC2NBD
24V DC
150-SC2NBR
150-SC3NBD
24V DC
150-SC3NBR
150-SD1NBD
24V DC
150-SD1NBR
150-SD2NBD
24V DC
150-SD2NBR
150-SD3NBD
24V DC
150-SD3NBR
Control Power
Cat. No.
150-SB1NBD
24V DC
150-SB1NBR
150-SB2NBD
24V DC
150-SB2NBR
150-SB3NBD
24V DC
150-SB3NBR
150-SB4NBD
24V DC
150-SB4NBR
150-SC1NBD
24V DC
150-SC1NBR
150-SC2NBD
24V DC
150-SC2NBR
150-SC3NBD
24V DC
150-SC3NBR
150-SD1NBD
24V DC
150-SD1NBR
150-SD2NBD
24V DC
150-SD2NBR
150-SD3NBD
24V DC
150-SD3NBR
21
Bulletin 150
Motor kW, 50 Hz
3080
Motor Hp, 60 Hz
40100
37100
50150
50132
75200
63160
100250
75200
100300
400/415 (kW)
460 (Hp)
151450
186554
210625
243727
Rated Utilization
Voltage
[V AC]
90250
125350
110315
200450
125355
200500
150400
250600
302900
185530
250700
Motor kW, 50 Hz
Motor Hp, 60 Hz
52155
65190
82242
104311
122363
37100
50132
63160
75220
90250
50150
75150
100250
125300
125350
500 (kW)
575 (Hp)
151450
186554
210625
243727
302900
110315
132400
150450
185530
220670
200450
200500
250600
300700
350900
Control Power
Cat. No.
150-SB1NBD
24V DC
150-SB1NBR
150-SB2NBD
24V DC
150-SB2NBR
150-SB3NBD
24V DC
150-SB3NBR
150-SB4NBD
24V DC
150-SB4NBR
150-SC1NBD
24V DC
150-SC1NBR
150-SC2NBD
24V DC
150-SC2NBR
150-SC3NBD
24V DC
150-SC3NBR
150-SD1NBD
24V DC
150-SD1NBR
150-SD2NBD
24V DC
150-SD2NBR
150-SD3NBD
24V DC
150-SD3NBR
Control Power
Cat. No.
150-SB1NUD
24V DC
150-SB1NUR
150-SB2NUD
24V DC
150-SB2NUR
150-SB3NUD
24V DC
150-SB3NUR
150-SB4NUD
24V DC
150-SB4NUR
150-SC1NUD
24V DC
150-SC1NUR
150-SC2NUD
24V DC
150-SC2NUR
150-SC3NUD
24V DC
150-SC3NUR
150-SD1NUD
24V DC
150-SD1NUR
150-SD2NUD
24V DC
150-SD2NUR
150-SD3NUD
24V DC
150-SD3NUR
22
Publication 150-SG010E-EN-P
Bulletin 150
Motor kW, 50 Hz
52155
2050
65190
2560
82242
3075
104311
200/208
122363
40100
50125
151450
60150
186554
75200
210625
75200
243727
Rated Utilization
Voltage
[V AC]
230
122363
151450
186554
210625
243727
Motor Hp, 60 Hz
100250
Motor kW, 50 Hz
1750
2055
3075
37100
40110
50132
63160
75200
80220
Motor Hp, 60 Hz
2060
2560
4075
40100
50125
60150
75200
100250
100300
Control Power
Cat. No.
150-SB2NBD
24V DC
150-SB2NBR
150-SB3NBD
24V DC
150-SB3NBR
150-SB4NBD
24V DC
150-SB4NBR
150-SC1NBD
24V DC
150-SC1NBR
150-SC2NBD
24V DC
150-SC2NBR
150-SC3NBD
24V DC
150-SC3NBR
150-SD1NBD
24V DC
150-SD1NBR
150-SD2NBD
24V DC
150-SD2NBR
150-SD3NBD
24V DC
150-SD3NBR
Control Power
Cat. No.
150-SB2NBD
24V DC
150-SB2NBR
150-SB3NBD
24V DC
150-SB3NBR
150-SB4NBD
24V DC
150-SB4NBR
150-SC1NBD
24V DC
150-SC1NBR
150-SC2NBD
24V DC
150-SC2NBR
150-SC3NBD
24V DC
150-SC3NBR
150-SD1NBD
24V DC
150-SD1NBR
150-SD2NBD
24V DC
150-SD2NBR
150-SD3NBD
24V DC
150-SD3NBR
23
Bulletin 150
400/415 (kW)
460 (Hp)
122363
151450
186554
210625
Rated Utilization
Voltage
[V AC]
3080
Motor Hp, 60 Hz
40100
37100
50150
50132
75200
63160
100250
75200
100300
90250
125350
110315
200450
125355
200500
243727
150400
250600
Motor kW, 50 Hz
Motor Hp, 60 Hz
52155
65190
82242
104311
500 (kW)
575 (Hp)
Motor kW, 50 Hz
122363
151450
186554
210625
243727
37100
50132
63160
75220
90250
110315
132400
150450
185530
50150
75150
100250
125300
125350
200450
200500
250600
300700
Control Power
Cat. No.
150-SB2NBD
24V DC
150-SB2NBR
150-SB3NBD
24V DC
150-SB3NBR
150-SB4NBD
24V DC
150-SB4NBR
150-SC1NBD
24V DC
150-SC1NBR
150-SC2NBD
24V DC
150-SC2NBR
150-SC3NBD
24V DC
150-SC3NBR
150-SD1NBD
24V DC
150-SD1NBR
150-SD2NBD
24V DC
150-SD2NBR
150-SD3NBD
24V DC
150-SD3NBR
Control Power
Cat. No.
150-SB2NUD
24V DC
150-SB2NUR
150-SB3NUD
24V DC
150-SB3NUR
150-SB4NUD
24V DC
150-SB4NUR
150-SC1NUD
24V DC
150-SC1NUR
150-SC2NUD
24V DC
150-SC2NUR
150-SC3NUD
24V DC
150-SC3NUR
150-SD1NUD
24V DC
150-SD1NUR
150-SD2NUD
24V DC
150-SD2NUR
150-SD3NUD
24V DC
150-SD3NUR
24
Publication 150-SG010E-EN-P
Bulletin 150
Rated Voltage
[V AC]
200/208
230
Max. kW, 50 Hz
Max. Hp, 60 Hz
Controller Current
Rating [A]
10
90
152H-SB1FHD-41
153H-SB1FHD-41
15
90
152H-SB1FHD-42
153H-SB1FHD-42
20
90
152H-SB1FHD-43
153H-SB1FHD-43
25
90
152H-SB1FHD-44
30
110
152H-SB2FHD-45
153H-SB2FHD-45
40
140
152H-SB3FHD-46
153H-SB3FHD-46
50
180
152H-SB4FHD-47
153H-SB4FHD-47
60
180
152H-SB4FHD-48
153H-SC1FHD-48
60
210
152H-SC1FHD-48
153H-SC1FHD-48
75
260
152H-SC2FHD-49
153H-SC2FHD-49
100
320
152H-SC3FHD-50
153H-SC3FHD-50
125
361
152H-SD1JHD-51
153H-SD1JHD-51
150
420
152H-SD2JHD-52
153H-SD2JHD-52
150
520
152H-SD3JHD-52
15
90
152H-SB1FAD-42
153H-SB1FAD-42
20
90
152H-SB1FAD-43
153H-SB1FAD-43
25
90
152H-SB1FAD-44
153H-SB1FAD-44
30
90
152H-SB1FAD-45
40
110
152H-SB2FAD-46
153H-SB2FAD-46
50
140
152H-SB3FAD-47
153H-SB3FAD-47
60
180
152H-SB4FAD-48
153H-SB4FAD-48
75
210
152H-SC1FAD-49
153H-SC1FAD-49
100
260
152H-SC2FAD-50
153H-SC2FAD-50
125
320
152H-SC3FAD-51
153H-SC3FAD-51
150
361
152H-SD1JAD-52
153H-SD1JAD-52
150
420
152H-SD2JAD-52
153H-SD2JAD-52
200
520
152H-SD3JAD-54
153H-SD3JAD-54
153H-SB1FHD-44
153H-SD3JHD-52
153H-SB1FAD-45
These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the
appropriate option code to the catalog string.
Requires a bypass contactor. Add -BP or -NB to the end of the catalog number to denote an IEC or NEMA bypass contactor, respectively. Example, for a
NEMA bypass contactor, Cat. No. 152H-SB2FHD-45 becomes 152H-SB2FHD-45-NB.
25
Bulletin 150
Rated Voltage
[V AC]
460
500/575
Max. kW, 50 Hz
Max. Hp, 60 Hz
Controller Current
Rating [A]
25
90
152H-SB1FBD-44
153H-SB1FBD-44
30
90
152H-SB1FBD-45
153H-SB1FBD-45
40
90
152H-SB1FBD-46
153H-SB1FBD-46
50
90
152H-SB1FBD-47
153H-SB1FBD-47
60
90
152H-SB1FBD-48
75
110
152H-SB2FBD-49
153H-SB2FBD-49
100
140
152H-SB3FBD-50
153H-SB3FBD-50
125
180
152H-SB4FBD-51
153H-SB4FBD-51
150
180
152H-SB4FBD-52
153H-SB4FBD-52
150
210
152H-SC1FBD-52
153H-SC1FBD-52
200
260
152H-SC2FBD-54
153H-SC2FBD-54
250
320
152H-SC3FBD-56
153H-SC3FBD-56
300
361
152H-SD1JBD-57
153H-SD1JBD-57
350
420
152H-SD2JBD-58
153H-SD2JBD-58
400
520
152H-SD3JBD-59
153H-SD3JBD-59
450
520
152H-SD3JBD-60
30
90
152H-SB1FCD-45
153H-SB1FCD-45
40
90
152H-SB1FCD-46
153H-SB1FCD-46
50
90
152H-SB1FCD-47
153H-SB1FCD-47
60
90
152H-SB1FCD-48
153H-SB1FCD-48
75
90
152H-SB1FCD-49
100
110
152H-SB2FCD-50
153H-SB2FCD-50
125
140
152H-SB3FCD-51
153H-SB3FCD-51
150
180
152H-SB4FCD-52
153H-SB4FCD-52
200
210
152H-SC1FCD-54
153H-SC1FCD-54
250
260
152H-SC2FCD-56
153H-SC2FCD-56
300
320
152H-SC3FCD-57
153H-SC3FCD-57
350
361
152H-SD1JCD-58
153H-SD1JCD-58
400
420
152H-SD2JCD-59
153H-SD2JCD-59
450
520
152H-SD3JCD-60
153H-SD3JCD-60
500
520
152H-SD3JCD-61
153H-SD3JCD-61
153H-SB1FBD-48
153H-SD3JBD-60
153H-SB1FCD-49
Requires a bypass contactor. Add -BP or -NB to the end of the catalog number to denote an IEC or NEMA bypass contactor, respectively. Example, for a
NEMA bypass contactor, Cat. No. 152H-SB2FBD-49 becomes 152H-SB2FBD-49-NB.
26
Publication 150-SG010E-EN-P
Bulletin 150
Rated Voltage
[V AC]
200/208
230
Max. kW, 50 Hz
Max. Hp, 60 Hz
Controller Current
Rating [A]
10
90
152H-SB2FHD-41
153H-SB2FHD-41
15
90
152H-SB2FHD-42
153H-SB2FHD-42
20
90
152H-SB2FHD-43
153H-SB2FHD-43
25
90
152H-SB2FHD-44
153H-SB2FHD-44
30
110
152H-SB3FHD-45
153H-SB3FHD-45
40
140
152H-SB4FHD-46
153H-SB4FHD-46
50
180
152H-SC1FHD-47
153H-SC1FHD-47
60
180
152H-SC1FHD-48
153H-SC1FHD-48
60
210
152H-SC2FHD-49
153H-SC2FHD-49
75
260
152H-SC3FHD-49
153H-SC3FHD-49
100
320
152H-SD1JHD-50
153H-SD1JHD-50
125
361
152H-SD2JHD-51
153H-SD2JHD-51
150
420
152H-SD3JHD-52
153H-SD3JHD-52
15
90
152H-SB2FAD-42
153H-SB2FAD-42
20
90
152H-SB2FAD-43
153H-SB2FAD-43
25
90
152H-SB2FAD-44
153H-SB2FAD-44
30
90
152H-SB2FAD-45
153H-SB2FAD-45
40
110
152H-SB3FAD-46
153H-SB3FAD-46
50
140
152H-SB4FAD-47
153H-SB4FAD-47
60
180
152H-SC1FAD-48
153H-SC1FAD-48
75
210
152H-SC2FAD-49
153H-SC2FAD-49
100
260
152H-SC3FAD-50
153H-SC3FAD-50
125
320
152H-SD1JAD-51
153H-SD1JAD-51
150
361
152H-SD2JAD-52
153H-SD2JAD-52
150
420
152H-SD3JAD-52
153H-SD3JAD-52
Requires a bypass contactor. Add -BP or -NB to the end of the catalog number to denote an IEC or NEMA bypass contactor, respectively. Example, for a
NEMA bypass contactor, Cat. No. 152H-SB2FHD-41 becomes 152H-SB2FHD-41-NB.
27
Bulletin 150
Rated Voltage
[V AC]
460
500/575
Controller Current
Rating [A]
Max. kW, 50 Hz
Max. Hp, 60 Hz
25
90
152H-SB2FBD-44
153H-SB2FBD-44
30
90
152H-SB2FBD-45
153H-SB2FBD-45
40
90
152H-SB2FBD-46
153H-SB2FBD-46
50
90
152H-SB2FBD-47
153H-SB2FBD-47
60
90
152H-SB2FBD-48
153H-SB2FBD-48
75
110
152H-SB3FBD-49
153H-SB3FBD-49
100
140
152H-SB4FBD-50
153H-SB4FBD-50
125
180
152H-SC1FBD-51
153H-SC1FBD-51
150
180
152H-SC1FBD-52
153H-SC1FBD-52
150
210
152H-SC2FBD-52
153H-SC2FBD-52
200
260
152H-SC3FBD-54
153H-SC3FBD-54
250
320
152H-SD1JBD-56
153H-SD1JBD-56
300
361
152H-SD2JBD-57
153H-SD2JBD-57
350
420
152H-SD3JBD-58
153H-SD3JBD-58
30
90
152H-SB2FCD-45
153H-SB2FCD-45
40
90
152H-SB2FCD-46
153H-SB2FCD-46
50
90
152H-SB2FCD-47
153H-SB2FCD-47
60
90
152H-SB2FCD-48
153H-SB2FCD-48
75
90
152H-SB2FCD-49
153H-SB2FCD-49
100
110
152H-SB3FCD-50
153H-SB3FCD-50
125
140
152H-SB4FCD-51
153H-SB4FCD-51
150
180
152H-SC1FCD-52
153H-SC1FCD-52
200
210
152H-SC2FCD-54
153H-SC2FCD-54
250
260
152H-SC3FCD-56
153H-SC3FCD-56
300
320
152H-SD1JCD-57
153H-SD1JCD-57
350
361
152H-SD2JCD-58
153H-SD2JCD-58
400
420
152H-SD3JCD-59
153H-SD3JCD-59
450
420
152H-SD3JCD-60
153H-SD3JCD-60
Requires a bypass contactor. Add -BP or -NB to the end of the catalog number to denote an IEC or NEMA bypass contactor, respectively. Example, for a
NEMA bypass contactor, Cat. No. 152H-SB2FBD-44 becomes 152H-SB2FBD-44-NB.
28
Publication 150-SG010E-EN-P
Bulletin 150
Push Buttons
Selector Switch
Pilot Lights
Description
Start-Stop Push Button
-1
-1F
1XA
1XB
1XC
1XD
1XE
-3
-4G
-4R
-5R
-6PX
-6PK
-6PL
-6PM
Communication Module
Disconnect Auxiliary
Circuit Breaker Auxiliary
Contactors
-6P
Protective Modules
-3B
Cat. No.
Modification
-8L
-8M
-8B
RS-485
-20S
DeviceNet
-20D
Ethernet/IP
-20E
Control Net
-20C
ProfiBUS
-20P
-98
-99
-98X
-99X
-BP
-NB
-NI
-HC6
-SEL
Bulletin 509 NEMA Size 1starter and Bulletin 592 solid-state overload
-OPS
Add the designated letter to the end of the cat. no. Example: To add the EtherNet/IP option: Cat. No. 152H-SB1FBD-48-1 becomes Cat. No. 152H-SB1FBD48-1-20E.
Bypass contactor and overload are not included with this option. A -BP or -NB needs to be added to the catalog number to add these devices.
29
Bulletin 150
Maximum # of
Option Modules of this
Type Per Controller
7&8
150-SM2
7, 8, 9
150-SM3
7, 8, 9
150-SM4
7, 8, 9
150-SM6
Description
Cat. No.
Converter Modules
Description
Rated Current
Cat. No.
30180 A
825-MCM180
181520 A
825-MCM20
Description
Turns Ratio
100:1
825-MCA
Cat. No.
825-CBCT
Protective Modules
Current Rating
Description
Cat. No.
90...520
150-F84L
90520
150-F86L
The same protective module mounts on the line or load side of the SMC-50. Use of protective modules is highly recommended. For applications requiring
both line and load side protection, two protective modules must be ordered.
Protective modules must not be placed on the load (motor) side of an SMC-50 when using an inside-the-delta connection or with pump, braking, or linear
speed acceleration/deceleration control.
30
Publication 150-SG010E-EN-P
Bulletin 150
Current
Range [A]
150-SB
Line Side
Load Side
Pkg.
Qty.
Cat. No.
90180
199-LF1
150-SC
210320
199-LF1
150-SD
361520
199-LG1
Current
Range [A]
150-SB
Total No. of
Terminal Lugs
Possible Each Side
Wire Size Range
Line Side
Load Side
Pkg.
Qty.
Lug Cat.
No.
90180
1494R-N14
150-SC
210320
6 (6 additional
needed for bypass
kit)
199-LF1
150-SD
361520
6 (6 additional
needed for bypass
kit)
199-LG1
Current
Range [A]
Total No. of
Distribution Blocks
Needed per Side
Line Side
Load Side
Line Side
Load Side
Pkg.
Qty.
Cat. No.
1492-BG
150-SB
155311
150-SC
363554
Marathon Special
Products Cat. No.
1353703
150-SD
625900
Marathon Special
Products Cat. No.
1352702
Bypass Kits
Current
Range [A]
Bypass
Kit Cat.
No.
150-SC
210320
150-SCBK
150-SD
361520
150-SDBK
For additional information, see page 8, page 43, and page 47.
Pkg.
Quantity
Cat. No.
150-STCB
31
Bulletin 150
Cat. No.
Door-Mounted HIM
20-HIM-A6
1202-H03
1202-H10
1202-H30
1202-H90
Description (IP30/Type 1)
1203-S03
20-COMM-S
20-COMM-P
20-COMM-C
20-COMM-I
20-COMM-M
Bulletin 150-Sxx
20-COMM-D
20-COMM-E
20-COMM-ER
20-COMM-H
20-COMM-Q
Programming Software
Windows
7/2000/XP/Vista
DriveTools SP
AnaCANda RS-232 to DPI
DPI to USB
9303-4DTS01ENE
PC Interface
A cable is required if 20-HIM-A6 is connected to the SMC-50 DPI Port #2 and used as a handheld device.
A 3 m (9.8 ft.) 1202-C30 cable is provided.
Includes DriveExecutive and DriveObserver .
Includes Cat. No. 1203-SFC and 1202-C10 cables.
Includes Cat. No. 20-HIM-H10 and 22-HIM-H10 cables.
32
20-HIM-H10
Communication Modules
(installed into the physical
space assigned to control
module expansion port 9;
connected to DPI port 4 via
cable)
20-HIM-C6S
Publication 150-SG010E-EN-P
Serial
1203-SSS
USB
1203-USB
Bulletin 150
24V DC Control
Voltage
Cat. No.
Cat. No.
90 A, 200480V AC line
150-SPPB1B
150-SPPB1BR
150-SPPB2B
150-SPPB2BR
150-SPPB3B
150-SPPB3BR
150-SPPB4B
150-SPPB4BR
90 A, 200690V AC line
150-SPPB1U
150-SPPB1UR
150-SPPB2U
150-SPPB2UR
150-SPPB3U
150-SPPB3UR
150-SPPB4U
150-SPPB4UR
150-SPPC1B
150-SPPC2B
150-SPPC3B
150-SPPC1U
150-SPPC2U
150-SPPC3U
150-SPPD1B
150-SPPD2B
150-SPPD3B
150-SPPD1U
150-SPPD2U
150-SPPD3U
Cat. No.
150-SCMD
150-SCMR
Replacement Parts
Description
Replacement Fan
Replacement Cover
Replacement Removable
Terminal Block
100240V AC
100240V AC
100240V AC
24V DC
24V DC
24V DC
Cat. No.
150-SF1
150-SF1R
150-SF2D
150-SF2R
150-SF3D
150-SF3R
90180 A units
150-SBFC
210320 A units
150-SCFC
361520 A units
150-SDFC
90520 A units
150-SCMRC
210320 A units
150-SCRC
361520 A units
150-SDRC
Control module
150-SCMRTB
150-SM2
150-SM2RTB
150-SM3
150-SM3RTB
150-SM4
150-SM4RTB
33
Bulletin 150
Configuration/Setup
Description
Power Wiring
Control Wiring
Keypad
Software
parameter values are downloaded to the SMC-50 with the DriveTools and DriveExplorer
programming software
Parameter Configuration
Option Module (PCM)
Cat. No. 150-SM6 provides simple and limited configuration by DIP and rotary dial switches
Communications
four DPI ports for local serial communications. Network communication supported by optional 20COMM-X modules
modes include: Soft Start, Coast-to-Stop, Soft Stop, Current Limit Start, Dual Ramp, Full Voltage,
Linear Speed Acceleration (start), Linear Speed Deceleration (stop), Torque Start, and Preset Slow
Speed
Pump Control
Braking Control
helps reduce fluid surges in centrifugal pumping systems during the starting and stopping period
provides motor braking without additional equipment for applications that require the motor to stop
quickly
Accu-Stop
provides controlled position stopping; during stopping, brake torque is applied to the motor until
the motor reaches the preset slow speed and holds the motor at this speed until a stop command
is given - braking torque is then applied until the motor reaches zero speed - braking current is
programmable
used on applications that require slow speed (in the forward or reverse direction) for positioning or
alignment and requires braking control to stop
External Braking
displays: Power Loss, Line Fault, Voltage Unbalance, Excessive Starts/Hour, Phase Reversal,
Undervoltage, Overvoltage, Controller Temperature, Stall, Jam, Open Gate, Overload, Underload,
and Communication Fault
Metering Indication
provides: Phase Current, Current Average, Phase-to-Phase Voltage, Voltage P-P Average, Phaseto-Neutral Voltage, Calculated Torque, Real Phase Power, Real Power, Real Energy, Real Demand,
Max Real Demand, Reactive Power, Reactive Energy + & -, Reactive Energy, Reactive Demand,
Max Reactive Demand, Apparent Power, Apparent Energy, Apparent Demand, Number of Periods,
Power Factor, Energy Savings, Elapsed Time 1 & 2, Running Time, Motor Speed, Start Time 1-5,
Peak Current 1-5, Total Starts, THD V, THD I, THD V Average, THD I Average, Line Frequency,
Current Imbalance, and Voltage Unbalance
displays fault and alarm codes: Running - with alarm, Running - no alarm, Ready - with alarm,
Ready - no alarm, Ready - tuning enabled on next start, and Firmware Download Active - with
alarm
two fully programmable contacts as: normal, UTS, fault, alarm, external brake, auxilliary control,
network, or external bypass
The configuration method must be ordered separately from the controller which doers not include a setup tool.
Diagnostic indication depends on the type of configuration tool used, The standard LED status indication displays: Inhibit (stop enabled), Fault (nonresettable), Fault (resettable). For full local access, a HIM or PC software is required, For network access, full access to data can also be obtained.
Metering Indication depends on the type of configuration tool being used. Metering Indication requires the use of a HIM or a PC software configuration tool
for full local access. Full access to data can also be obtained via network.
Accu-Stop is not included as a parameter/function like that of the SMC-Flex. However, the Accu-Stop function can be accomplished with the SMB mode and
Slow Speed with Braking functions.
Not intended to be used as an emergency stop. Refer to the applicable standards for emergency stop requirements.
34
Publication 150-SG010E-EN-P
Bulletin 150
Device
Rating
480V
690V
480V
690V
480V
690V
480V
690V
480V
690V
All
UL/CSA/NEMA
200480V AC (15%, +10%)
200600V AC (15%, +10%)
N/A
N/A
N/A
N/A
2200V AC
2200V AC
1400V
1800V
47...63 Hz
UL/CSA/NEMA
90520 A
MG 1
90520 A
90180 A
480V
690V
480...600V
690V
IEC
200415V (-15%, +10%)
200690V/Y (15%, +10%)
500V
690V
6000V
6000V
2500V
2500V
1400V
1800V
47...63 Hz
IEC
AC-53a:3.5-10:99-2
AC-53a:3.5-30:99-1
IP00 (IP20 - Control Terminals only)
IP2X (with Cat. No. 150-STCB Terminal Cover)
N/A
RC Snubber Network
Metal Oxide Varistors: 220 Joules
None
UL/CSA/NEMA
IEC
100240V AC (-15%+10%) or 24V DC (-10%+10%)
NA
240V
NA
3000V
1500V AC
1500V
4763 Hz or DC
22 ms
300 mA
CR 2032
UL/CSA/NEMA
IEC
24V DC
1530V DC
2.8 mA
10V DC
3 mA
10.9V DC
7 mA
On-to-Off: 30 ms, Off-to-On: 20 ms
Yes
NA
60V
NA
500V
500V AC
1000V AC
UL/CSA/NEMA
IEC
Aux 1, Aux 2
Electromagnetic Relay
1
Programmable N.O./N.C. (electrically held closed)
AC
3 A @ 120V AC, 1.5 A @ 240V AC
5A
3600/360
B300
AC-15
0.024 mA @ 24V
0.12 mA @120V
0.24 mA @ 240V
Wiring Terminals (applies to Control Module Standard I/O & Expansion Module Terminals 150-SM2, 150-SM3, 150-SM4)
Terminal Style
M3 Screw Clamp
Terminal Type
Removable
Screw Terminal Torque
0.8 N m (7.0 lb-in)
Terminal Wire Size
Wire Strip Length
35
Bulletin 150
UL/CSA/NEMA
NA
NA
1600V AC
240V
3000V
2000V AC
UL/CSA/NEMA
IEC
100240V AC
85V264V AC @ 47 Hz63 Hz
5.1 mA @ 47 Hz, 5.0 mA @ 62.4 Hz
74.5V AC @ 47 Hz, 55.8V AC @ 62.4 Hz
4.7 mA @ 47 Hz, 4.8 mA @ 62.4 Hz
68.6V AC @ 47 Hz, 53.5V AC @ 62.4 Hz
3.64 A
On-to-Off: 30 ms, Off-to-On: 25 ms
NA
NA
1600V AC
UL/CSA/NEMA
240V
3000V
2000V AC
IEC
Aux 1, Aux 2, Aux 3
Electromagnetic Relay
1
Programmable N.O./N.C. (electrically held closed)
AC
3 A @ 120V AC, 1.5 A @ 240V AC
5A
3600/360
B300
AC-15
0.024 mA @ 24V
0.12 mA @120V
0.24 mA @ 240V
Meets IEC Type 2 specifications for inputs per IEC 60947-1 for 240V AC only.
36
IEC
100240V AC
85V264V AC @ 47 Hz63 Hz
9.7 mA @ 47 Hz, 9.7 mA @ 62.4 Hz
74.5V AC @ 47 Hz, 55.9V AC @ 62.4 Hz
9.0 mA @ 47 Hz, 9.3 mA @ 62.4 Hz
68.8V AC @ 47 Hz, 53.6V AC @ 62.4 Hz
3.64 A
On-to-Off: 30 ms, Off-to-On: 25 ms
Publication 150-SG010E-EN-P
Bulletin 150
Number of Inputs
Normal Operating Input Ranges
Full Scale Operating Input Ranges
Input Resolution
Data Refresh Rate
Rated Working Voltage
Common Mode Voltage Range
Input Impedance
Input Channel Diagnostics
Open Circuit Detection Time
Maximum Overload at Input Terminals
External Calibration
Module Isolation to Control Board
Removable Terminal Block
Cable Type
Number of Outputs
Normal Operating Ranges
Full Scale Operating Ranges
Output Resolution
10.5V, 0 10.5V, -0.55.25V,
021 mA, 3.5 21 mA
Resistive Load on Current Output
Load Range on Voltage Output
Max. Inductive Load (Current Outputs)
Max. Capacitive Load (Voltage Outputs)
Overall Accuracy
Accuracy Drift with Temperature
Output Impedance
Open and Short-Circuit Protection
Maximum Short-Circuit Current
Output Overvoltage Protection
3400 150
1600 100
25 10
< 7.5 V
30V
6
1500
800 ms
37
Bulletin 150
100240V AC
Base Power Draw: Control Module with Heat Sink Fan
90180
150 VA
210260
150 VA
361520
300 VA
Human Interface Module (HIM)
10 VA
30 VA
150-SM2
150-SM3
30 VA
Option Power Adder (for each option installed, add to base
power to obtain total power requirement)
150-SM4
50 VA
5 VA
150-SM6
25 VA
20-COMM-X
Continuous Duty Power Structure Heat Dissipation at Rated Current (Watts)
90
110
140
180
210
Controller Rating [A]
260
320
361
420
520
24V DC
75 W
75 W
300 W
2W
4W
4W
2W
1W
4W
270
330
420
540
630
780
960
1083
1260
1560
Power Calculation:
Max. Total Power
Dissipation =
Base Power
Options
Power Structure
Power Structure
Watts
Example: 361 A device with a 20-COMM-X, HIM, and Cat. No. 150-SM4
Max. Total Power
Dissipation =
300
Base Power
(25 + 10 + 50)
Options
38
Publication 150-SG010E-EN-P
1083
Watts
Bulletin 150
Type 1
Non-Time Delay Fuse
Line
Inside Delta
Cat. No.
150-SB1N
Current
Rating
[A]
90
150-SB2N
110
150-SB3N
140
150-SB4N
180
150-SC1N
210
150-SC2N
260
150-SC3N
320
150-SD1N
361
Max.
Standard
Available
Fault [kA]
10
18
Typical
Amps
Max.
Amps
Typical
Amps
Max.
Amps
Max.
Standard
Available
Fault [kA]
Typical
Amps
Max.
Amps
250
350
150
200
225
350
300
400
175
225
250
300
400
500
225
300
350
400
500
300
400
450
500
600
350
450
500
600
450
500
600
700
800
500
700
800
800
1000
600
800
800
1000
700
10
18
10
18
150-SD2N
420
700
800
1000
1200
150-SD3N
520
1200
800
1000
1200
1200
150-SB1N
155
450
250
300
350
450
150-SB2N
190
500
300
400
450
500
150-SB3N
242
400
500
600
700
150-SB4N
311
800
500
600
700
800
150-SC1N
363
1000
600
800
800
1000
150-SC2N
450
700
1000
1000
1200
150-SC3N
554
1600
800
1200
1200
1600
150-SD1N
625
1600
1000
1200
1200
1600
150-SD2N
727
1200
1600
1600
2000
150-SD3N
900
1200
2000
2000
2500
30/18
18
30
42
1200
700
1200
2000
30/18
18
30
42
2500
30/18
18
30
42
39
Bulletin 150
SCPD Performance
Line
Inside Delta
Cat. No.
150-SB1N
150-SB2N
150-SB3N
150-SB4N
150-SC1N
150-SC2N
150-SC3N
150-SD1N
150-SD2N
150-SD3N
150-SB1N
150-SB2N
150-SB3N
150-SB4N
150-SC1N
150-SC2N
150-SC3N
150-SD1N
150-SD2N
150-SD3N
Type 1
Inverse Time (Thermal Magnetic) Circuit Breaker
480V, 65kA Maximum
Bul. 140U
Frame
Size
M
Max. Amps
350
300
400
400
600
700
800
1000
1200
1200
450
500
700
700
1000
1200
1200
1600
2000
2000
Cat. No.
Rating Plug
140U-M6D3-D35
N/A
140U-M6D3-D30
N/A
140U-M6D3-D40
N/A
140U-M6D3-D40
N/A
140U-M6D3-D60
N/A
140U-M6D3-D70
N/A
140U-M6D3-D80
N/A
140U-N6L3-E12
140U-NRP3-E10
140U-N6L3-E12
140U-NRP3-E12
140U-N6L3-E12
140U-NRP3-E12
140U-M6D3-D45
N/A
140U-M6D3-D50
N/A
140U-M6D3-D70
N/A
140U-M6D3-D70
N/A
140U-N6L3-E12
140U-NRP3-E10
140U-N6L3-E12
140U-NRP3-E12
140U-N6L3-E12
140U-NRP3-E12
140U-R6L3-E20 140U-R20RP3-E16
140U-R6L3-E20 140U-R20RP3-E20
140U-R6L3-E20 140U-R20RP3-E20
Cat. No.
150-SB1N
150-SB2N
150-SB3N
150-SB4N
150-SC1N
150-SC2N
150-SC3N
150-SD1N
150-SD2N
150-SD3N
40
Publication 150-SG010E-EN-P
Bulletin 150
Operational
Non-Operational
90520 A
Operational
90...520 A
Non-Operational
30 G
Power Poles
Construction
Control Modules
Metal Parts
Terminals
90180 A
210320 A
361520 A
Control Terminals
Other
EN
Electrostatic Discharge
Radio Frequency Electromagnetic Field
Fast Transient
Surge Transient
8 kV Air Discharge
Per EN 60947-4-2
Per EN 60947-4-2
Per EN 60947-4-2
Overload Characteristics
Current Range
Line
Delta
90
30...90
52155
110
37110
65190
140
47140
82242
180
60180
104311
210
70210
122363
260
87260
151450
320
107320
186554
361
120361
210625
420
140420
243727
520
174520
Overload Type
Trip Classes
5 to 30
Number of Poles
Certifications
302900
2
3
Open-Type Controllers
41
Bulletin 150
150-SB1N*
150-SB2N*
150-SB3N*
150-SB4N*
150-SC1N*
150-SC2N*
150-SC3N*
150-SD1N*
150-SD2N*
90
110
140
180
210
260
320
361
420
150-SD3N*
520
Voltage
230600V
AC
230600V
AC
230600V
AC
230600V
AC
230600V
AC
230600V
AC
230600V
AC
230600V
AC
230600V
AC
230600V
AC
10
18
30
350 A
400 A
500 A
500 A
600 A
700 A
800 A
1000 A
1200 A
1200 A
200 A
225 A
300 A
400 A
450 A
500 A
700 A
800 A
800 A
1000 A
350 A
300 A
400 A
500 A
600 A
700 A
800 A
1000 A
1200 A
1200 A
500 A
700 A
800 A
800 A
1000 A
700 A
800 A
1000 A
1200 A
1200 A
100
200 A
225 A
300 A
400 A
450 A
65
350 A
300 A
400 A
400 A
600 A
M
Branch Protection Reference
Inverse Time Circuit Breaker Selections
35 kA at 600V Maximum
140GK6F3-D*
140GK6F3-D*
140GK6F3-D*
140GK6F3-D*
140GM6F3-D*
140GM6F3-D*
140GM6F3-D*
140GN6H3-E12
140GN6H3-E12
140GN6H3-E12
65 kA at 480V
Maximum
140UM6D3-D*
140UM6D3-D*
140UM6D3-D*
140UM6D3-D*
140UM6D3-D*
140UM6D3-D*
140UM6D3-D*
100-D630*
100-D630*
100-D630*
100-C97*
100-D115*
100-D140*
100-D180*
100-D250*
100-D250*
10
350 A
100-D300*
18
250 A
350 A
450 A
600 A
30
700 A
700 A
1000 A
1200 A
1200 A
100-D250*
100-D300*
100-D420*
100-D630*
100-D630*
100-C97*
100-D115*
100-D140*
100-D180*
100-D210*
100
120 A
150 A
100
200 A
225 A
300 A
350 A
100
450 A
500 A
42
600 A
700 A
For complete catalog numbers, refer to the online catalog: www.rockwellautomation.com or appropriate manufacturer's website
Always refer to local codes for proper selection of branch circuit components.
Circuit Breaker must be of the designated 140U Frame size for high fault short circuit ratings. Other circuit breakers pending.
Requires rating plug selection based on application, refer to the online catalog: www.rockwellautomation.com
For most up to date information including voltage ratings other than 600V please see the Global SCCR Tables at www.rockwellautomation.com
In IEC regulated regions when sizing the bypass contactor per AC-1 or AC-3 ratings, the short circuit rating of the bypass contactor must be similar to the
SMC-50.
42
Publication 150-SG010E-EN-P
Bulletin 150
L1
L3
SCR Fusing
L1/1
L3/5
L2/3
SMC-50
T1/2
T2/4
T3/6
T2
T3
T1
Motor
The 825-MCMxx provides current feedback to the SMC-50 when RUN in Bypass Operation. A Cat. No.150-SM2 is also required. For
30180 A, use Cat. No. 825-MCM180; For 181520A, use Cat. No. 825-MCM20 and user-supplied CTs with 5A secondary.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if
maintenance is required on the motor. See the isolation contactor application information for details.
Bypass must be controlled by an auxiliary contact of the SMC-50 configured to exernal bypass.
43
Bulletin 150
L1
L3
L1/1
L3/5
L2/3
SMC-50
T1/2
T2/4
T3/6
T2
T3
T1
Motor
44
Publication 150-SG010E-EN-P
Bulletin 150
L1
L3
L3/5
L2/3
SMC-50
T1/2
T2/4
T3/6
Thermal Magnetic
Overload Relay
T2
T3
T1
Motor
Overload is required.
NOTE: Bypass must be fully rated to motor Hp/kW and FLA.
Isolation Contactors A and B are required if bypass is used for emergency START, STOP, and RUN operation.
Due to current leakage through an SCR in the OFF state (controller stopped), some form of upstream line power isolation is recommended if
maintenance is required on the motor. See the isolation contactor application information for details.
Bypass must be controlled by an auxiliary contact of the SMC-50 configured to exernal bypass.
45
Bulletin 150
150-SB1N*
150-SB2N*
150-SB3N*
150-SB4N*
150-SC1N*
150-SC2N*
150-SC3N*
150-SD1N*
150-SD2N*
155
190
242
311
363
450
554
625
727
150-SD3N*
900
Voltage
230600V
AC
230600V
AC
230600V
AC
230600V
AC
230600V
AC
230600V
AC
230600V
AC
230600V
AC
230600V
AC
230600V
AC
18
450 A
500 A
30
700 A
800 A
1000 A
42
1200 A
1600 A
1600 A
2000 A
2500 A
300 A
400 A
500 A
600 A
800 A
1000 A
1200 A
1200 A
1600 A
2000 A
450 A
500 A
700 A
800 A
1000 A
1200 A
1600 A
1600 A
2000 A
2500 A
1000 A
1200 A
1200 A
1600 A
2000 A
1200 A
1200 A
1600 A
2000 A
2000 A
65
300 A
400 A
500 A
600 A
800 A
65
450 A
500 A
700 A
700 A
1000 A
N
Branch Protection Reference
Inverse Time Circuit Breaker Selections
35 kA at 600V Maximum
140GK6F3-D*
140GM6F3-D*
140GM6F3-D*
140GM6F3-D*
140GN6H3-E12
140GN6H3-E12
50 kA at 600V Maximum
140GR12I3-E20
140GR12I3-E20
140GR12I3-E20
140GR12I3-E25
65 kA at 480V
Maximum
140UM6D3-D*
140UM6D3-D*
140UM6D3-D*
140UM6D3-D*
140UN6L3-E12
140UN6L3-E12
140UN6L3-E12
140UR6L3-E20
140UR6L3-E20
140UR6L3-E20
100-D630*
100-D630*
100-D860*
100-D860*
100-D250*
100-D250*
100-D250*
100-D300*
100-D630*
18
450 A
500 A
30
700 A
700 A
1000 A
42
1200 A
1600 A
1600 A
100-D630*
100-D630*
100-D630*
2000 A
100-D180*
100-D180*
100-D250*
100-D300*
65
225 A
225 A
100-D420*
65
350 A
450 A
500 A
42
600 A
100-D860* 100-G1200*
42
700 A
800 A
65
1000 A
1300 A
For complete catalog numbers, refer to the online catalog: www.ab.com/catalogs or the appropriate manufacturer's web site.
Always refer to local codes for proper selection of branch circuit components.
Circuit Breaker must be of the designated Bul. 140U Frame size for high fault short circuit ratings. Other circuit breakers pending.
Requires rating plug selection based on application; refer to the online catalog: www.ab.com/catalogs
For most up to date information including voltage ratings other than 600V please see the Global SCCR Tables at www.rockwellautomation.com
In IEC regulated regions when sizing the bypass contactor per AC-1 or AC-3 ratings, the short circuit rating of the bypass contactor must be similar to the
SMC-50.
46
Publication 150-SG010E-EN-P
Bulletin 150
L1
L3
L1
L3
T6
T5
SCR Fusing
825-MCMxx
L1/1
L2/3
L3/5
SMC-50
T1/2
T2/4
T3/6
T2
T3
T1
Motor
T6
T4
T5
The 825-MCMxx provides current feedback to the SMC-50 when RUN in Bypass Operation. A Cat. No. 150-SM2 is also required. For
30180 A, use Cat. No. 825-MCM180; For 181520A, use Cat. No. 825-MCM20 and user-supplied CTs with 5A secondary.
Configuration not acceptable for emergency RUN off bypass.
Isolation contactor required.
Bypass must be controlled by an auxiliary contact of the SMC-50 configured to exernal bypass.
47
Bulletin 150
L1
L3
L1
L3
T6
T5
SCR Fusing
L1/1
L2/3
L3/5
SMC-50
T1/2
T2/4
T3/6
T2
T3
T1
Motor
T6
T4
T5
48
Publication 150-SG010E-EN-P
Bulletin 150
Type
Width
Height
Depth
Wye
609.6
(24.0)
762.0
(30.0)
304.8
(12.0)
Inside-theDelta
762.0
(30.0)
965.2
(38.0)
355.6
(14.0)
150-SC
All
762.0
(30.0)
965.2
(38.0)
355.6
(14.0)
150-SD
All
914.4
(36.0)
1295.4
(51.0)
355.6
(14.0)
150-SB
7.25
(184.2)
0.41 dia
(10.5)
See detail A
0.49
(12.5)
0.79
(20)
1.54
(39.1)
2.76
(70.0)
1.07
(27.1)
0.30
(7.5)
1.41
(35.8)
0.19
(4.8)
#8-32 UNC 2B
Detail A
6.25
(158.8)
13.95
(354.4)
13.39
(340.0)
14.63
(371.6)
15.62
(396.6)
2.51
(63.7)
6.69
(170.0)
7.65
(194.4)
2.51
(63.7)
Four Quantity
0.296
(7.51)
Cat. No.
6.79
(172.5)
Weight
150-SB1
150-SB2
15.7 kg
(34.6 lbs)
150-SB3
150-SB4
49
Bulletin 150
3.86
(97.9)
20.13
(511.3)
1.40
(35.6)
9.22
(234.1)
9.93
(252.3)
10.19
(258.9)
Cat. No.
1.54
(39.0)
Weight
150-SB1
150-SB2
15.9 kg
(35.1 lbs)
150-SB3
150-SB4
50
Publication 150-SG010E-EN-P
Bulletin 150
9.84 (250)
7.17 (182.1)
0.67
(17)
2.47
(62.8)
3.92 (99.6)
9.11
(231.3)
2.00
(50.8)
See detail A
0.25
(6.4)
9.30
(236.2)
23.25
(590.6)
24.08
(611.6)
24.24
(615.7)
25.14
(638.5)
0.281 dia.
2.00
(50.8)
2.09
(53.1)
2.09
(53.1)
1.16
(29.5)
0.413 dia
(10.49) 2 holes
0.53
(13.5)
5.34 (135.6)
7.19
(182.6)
7.66 (194.6)
0.98
(25)
9.84 (250)
10.75
(273.1)
Detail A
Cat. No.
Weight
150-SC1
47.6 kg
(105 lb)
150-SC2
150-SC3
51
Bulletin 150
0.35
(8.8)
3.08
(78.2)
1.44
(36.5)
1.02
(26)
0.53
(13.4)
23.25
(590.6)
26.17
(664.6)
1.70
(43.2)
26.84
(681.8)
27.23
(691.6)
2.14
(54.2)
1.44 (36.5)
8.23
(209.2)
3.15
(80)
Cat. No.
Weight
150-SC1
47.6 kg
(105 lb)
150-SC2
150-SC3
52
Publication 150-SG010E-EN-P
Bulletin 150
10.69
(271.5)
5.05
(128.3)
11.64 (295.8)
9.96 (253)
8.68 (220.5)
See detail A
2.04 (51.7)
0.25 (6.4)
1.31 (33.3)
3.00 (76.2)
1.53
(38.9)
0.69
(17.5)
9.21
(233.8)
2.13
(54)
Detail A
0.53 dia.
(13.5) 12 holes
26.43
(671.3)
25.25
(641.4)
25.88
(657.3)
3.156
3.156
(80.16)
(80.16)
7.844 (199.24)
10.908 (277.06)
15.00 (381)
17.38 (441.5)
18.00 (457.2)
27.25
(692.2)
0.400 dia.
Cat. No.
8.63 (219.2)
Weight
150-SD1
77.1 kg
(170 lb)
150-SD2
150-SD3
53
Bulletin 150
8.68
(220.5)
1.54
(39.2)
0.33
(8.5)
3.49
(88.5)
25.25
(641.4)
28.58
(726)
29.79
(756.8)
2.41
(61.2)
1.82
(46.2)
1.44 (36.5)
10.08 (256)
Cat. No.
Weight
150-SD1
77.1 kg
(170 lb)
150-SD2
150-SD3
54
Publication 150-SG010E-EN-P
Bulletin 150
C
D
F
Figure 1 Wall-Mount
A
Figure 2 Floor-Mount
55
Bulletin 150
Controller
Rating [A]
Bulletin
Input Line
Voltage
Code
With
Option
H,A,B,C
30 (762)
H,A,B,C
BP, NB
36 (914)
Dimension
Figure No.
A (Width)
C (Depth)
D (Mtg.
Dim.)
38 (965)
14 (356)
0.75 (19)
36.5 (927)
28.5 (724)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
B (Height)
E (Mtg.
Dim.)
F (Mtg.
Dim.)
152H, 153H
152B, 153B
B2
B3
B4
C1
153H
152B
153B
152H
C2
153H
152B
153B
D2
D3
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
H,A,B,C
BP, NB
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
H,A,B,C
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
H,A,B,C
BP, NB
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
H,A,B,C
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
H,A,B,C
BP, NB
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
H,A,B,C
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
H,A,B,C
NB
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
H,A,B,C
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
H,A,B,C
NB
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
H,A,B,C
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
H,A,B,C
NB
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
H,A,B,C
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
H,A,B,C
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
H,A,B,C
NB
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
H,A,B,C
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
H,A,B,C
NB
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
H,A,B,C
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
H,A,B,C
NB
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
H,A,B,C
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
34.5 (876)
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
H,A,B,C
NB
2
35 (889)
90 (2286)
20 (508)
H,A,B,C
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
H,A,B,C
NB
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
H,A,B,C
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
H,A,B,C
NB
2
35 (889)
90 (2286)
20 (508)
153B
H,A,B,C
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
H,A,B,C
2
35 (889)
90 (2286)
20 (508)
H,A, B
2
35 (889)
90 (2286)
20 (508)
2
35 (889)
90 (2286)
20 (508)
153H
152B
D1
H,A,B,C
152H
C3
H,A,B,C
H,A,B,C
NB
2
60 (1524)
90 (2286)
20 (508)
H,A
2
35 (889)
90 (2286)
20 (508)
B, C
2
35 (889)
90 (2286)
20 (508)
B, C
NB
2
60 (1524)
90 (2286)
20 (508)
The optional external mounting channels will add 1.5 inches to the height of an MCC section
56
Publication 150-SG010E-EN-P
Bulletin 150
Controller
Rating [A]
Bulletin
Input Line
Voltage
Code
With
Option
H, A, B, C
H, A, B, C
NB
H, A, B, C
Dimension
Figure No.
A (Width)
B (Height)
C (Depth)
D (Mtg.
Dim.)
E (Mtg.
Dim.)
F (Mtg.
Dim.)
28.5 (724)
150
150B
B2
150
150B
B3
150
150B
B4
150
150B
C1
C2
C3
D1
H, A, B, C
H, A, B, C
NB
H, A, B, C
H, A, B, C
H, A, B, C
NB
H, A, B, C
H, A, B, C
H, A, B, C
NB
H, A, B, C
150
H, A, B, C
150B
H, A, B, C
150
H, A, B, C
150B
H, A, B, C
150
H, A, B, C
150B
H, A, B, C
150
H, A, B, C
H, A, B, C
H, A, B, C
NB
H, A, B
NB
H, A, B, C
H, A, B, C
150B
150
D2
150B
150
D3
150B
1
1
1
1
30 (762)
38 (965)
14 (356)
0.75 (19)
36.5 (927)
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
30 (762)
38 (965)
14 (356)
0.75 (19)
36.5 (927)
28.5 (724)
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
30 (762)
38 (965)
14 (356)
0.75 (19)
36.5 (927)
28.5 (724)
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
30 (762)
38 (965)
14 (356)
0.75 (19)
36.5 (927)
28.5 (724)
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
36 (914)
51 (1295)
14 (356)
0.75 (19)
49.5 (1257)
34.5 (876)
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
34.5 (876)
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
35 (889)
90 (2286)
20 (508)
60 (1524)
90 (2286)
20 (508)
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
60 (1524)
90 (2286)
20 (508)
35 (889)
90 (2286)
20 (508)
NB
60 (1524)
90 (2286)
20 (508)
H, A
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
34.5 (876)
B, C
34.5 (876)
B, C
NB
H, A, B, C
H, A, B, C
NB
2
1
2
2
36 (914)
60 (1524)
14 (356)
0.75 (19)
58.5 (1486)
60 (1524)
90 (2286)
20 (508)
35 (889)
90 (2286)
20 (508)
60 (1524)
90 (2286)
20 (508)
The optional external mounting channels will add 1.5 inches to the height of an MCC section
57
Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.