Professional Documents
Culture Documents
Turbomachinery Engineering
Mastering the Science of Energy
ENGINEERING EVALUATION
Document:
Machine:
Model:
Serial Number:
Job:
Customer:
Date:
Subject:
Engineer:
EE-2010-0007-R00
Ellioitt/Ideal Electric Steam Turbine Generator
Various
Various
2010-0027
Sonino
2010.10.01
Steam Turbine Generator Skid Inspection
Michael Macek, P.E.
BACKGROUND
On September 17, 2010, Macek Power inspected a skid mounted steam turbine generator (STG)
package on behalf of its client, Sonino. The unit was originally constructed and installed in the
late 1980s as part of a combined-cycle generation facility at the Kellogg Company plant in Battle
Creek, Michigan. The equipment, therefore, is approximately 20 years in age. As constructed,
the skid consists of the major equipment listed below. More detail will be given about each
major equipment piece later in the evaluation. The supply scope as presented by the seller can be
seen in the appendix at the end of this evaluation.
Major Equipment
Skid Base:
Steam turbine:
Gear:
Generator:
Lube Oil System:
The inspecting engineer from Macek Power was Michael Macek. Witnessing the inspection on
behalf of Sonino was Project Manager, Ing. Astolfo Pincay. A summary of the persons involved
with the inspection and their home office locations is given by Table 1.
The equipment is currently housed by the Wabash warehouse in Saginaw, Michigan, USA as
shown in Figure 1. Sonino has expressed an interest in acquiring the equipment for the Miguel
Affiliation
Home Office
Function
Astolfo Pincay
Sonino
Guayaquil, Ecuador
Purchaser
Michael Macek
Macek Power
Purchaser representative
Rick Caitung
Wabash
Seller/Equipment owner
Venkatesha Naik
Belyea
Seller/Equipment owner
Rafael Sanchez
Prodek
Equipment broker
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
Elliott
NV-7
Multi-stage, single automatic extraction
265 psig, 580 F
160 psig
40 psig
4005 RPM
4300 kWe (zero extraction)
Upon arrival, the turbine was observed ready for inspection with the upper case half, rotor,
bearings, and seals removed (see Figures 2, 3, and 4). The steam path was observed to consist of
a total of seven (7) stages: Two (2) high-pressure (HP) section stages, and 5 low-pressure (LP)
section stages. The original design made use of extraction steam taken from the turbine casing
between the HP and LP sections, presumably for process at the original installation site. The
major stationary turbine components listed in Table 2 were visually inspected. Observations
made are also listed in the table. In general, these components were found in good visual
condition. Exposed surfaces were either painted or coated with preservative as appropriate.
Regardless of the observed visual condition, cleaning, non-destructive testing (NDT), and
clearance checks should be made prior to returning the hardware to service.
A partial view of the turbine rotor is presented by Figure 5. It was observed that the rotor had
been refurbished and was being carefully stored in a crate. Exposed surfaces at risk to corrosion
were coated with preservative and wrapped. Steam path surfaces had been coated as part of the
refurbishment work. General rotor visual condition is described more specifically by Table 3.
As with most rotors that have been out of service for a significant length of time, proper
inspection prior to return to service is strongly recommended. Such inspection would include
NDT, runout and balance checks, and diameter and axial location measurement.
In addition to the main steam turbine stationary and rotating components, a variety of ancillary
steam turbine hardware was briefly visually inspected. The inspection of this equipment was
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
General
Condition
Remarks
Casing Lower
Good
Casing Upper
Good
Unknown
Good
Unknown
HP nozzle
Good
None
HP Diaphragms
Good
None
Good
Good
LP nozzle
Good
None
LP Diaphragms
Good
None
Good
Check clearances
Steam seals
Good
Good
Check clearance
Good
None
Good
None
Good
Check clearance
Good
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
General Condition
Remarks
Good
None
Thrust collar
Good
None
Good
None
Fair/Good
HP blades
Good
LP blades
Fair/Good
Light erosion
Protective coating applied during refurbishment
Table 3. Rotor inspection
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
Lufkin
N2100C
4005 RPM
1800 RPM
2.225:1
6122 kW
1.35
44 GPM
Both high and low speed couplings are Kop-Flex brand gear tooth type, grease lubricated
flexible couplings. Overall, the gearbox seemed in good condition. The gear teeth are illustrated
by Figure 7. The teeth were observed in visually good condition. It is recommended that the
gearbox be disassembled, cleaned, and inspected prior to return to service. Inspection should
include shaft balance checks, bearing condition and clearance checks, gear tooth contact checks,
and lubrication system checks.
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
Ideal Electric
SAB
7339 kVA/5871 kW
0.8
1800 RPM
13,800 VAC
60 Hz, 3-Phase
At the time of inspection, the generator was observed with internal heaters on to protect the
unit from humidity while out of service. It is not known how long the heaters had been in
operation or if the heaters have been used consistently since the unit was removed from service.
To gain a better understanding of generator condition, a subcontractor, Hamilton Electric
(Saginaw, Michigan) was employed to conduct stator winding insulation resistance tests.
Insulation resistance tests were completed between each phase to ground and between each
phase to the other two phases. Phase to ground tests were done with 5000 VDC and phase to
phase tests were done with 2500 VDC. Each test had duration of 10 minutes so that a
polarization index value could be calculated. Specific results are shown below in Table 4.
The minimum acceptable insulation resistance for this generator is approximately 15 M. Table
4 demonstrates that all insulation resistance readings were consistently much higher than this
value. Polarization index values greater than 4.0 are considered excellent. Table 4 shows that all
six (6) polarization index values calculated from the stator tests were greater than 4.0. Although
more in depth inspection and testing should be done, these basic test results indicate a high
probability that the generator is in good working condition.
Test
Resistance (1 min.)
Polarization Index
3.60
11.6
439
37.8
4.35
15.8
570
36.1
4.70 G
18.7
614
32.8
A to B (2500 VDC)
192 G
479
2.52
5.3
A to C (2500 VDC)
151 G
431
1.77
4.1
141 G
366 G
1.80 T
Table 4. Generator stator insulation resistance and polarization index test results
B to C (2500 VDC)
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
4.9
The system is complete and appeared to be in good condition, but no statement can be made
about internal cleanliness or fitness for service. The system must be thoroughly cleaned prior to
return to service. Furthermore, it is strongly recommended that system testing, including alarm
and trip switch functionality, be tested prior to return to service.
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
Turbine
Accessories
Speed reducing gear and generator
Instrumentation
As shown in Figure 14, there was also one notebook without a volume designation. This volume
contained mostly drawings along with some information found in Volumes 1-4.
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
Original Design
Proposed Application
265
284
580
545
160
Not Required
40
20
4005
4005
137,500
106,000
4000
4300
Output [kWe]
Note that the steam flow and output shown in Table 5 for the original design correspond to zero
extraction (maximum flow to exhaust). With extraction, the turbogenerator was originally
capable of producing 5300 kWe. For the proposed application, the output given by the table
corresponds to the requirement specified by Sonino, and the steam flow is a calculated estimate
of that required to produce the desired power.
As Table 5 indicates, there are a number of significant differences between the original and
proposed operating conditions. Besides the obvious extraction requirement difference, there are
differences between the inlet and exhaust conditions. These differences affect the way the steam
path should be designed.
The original throttle flow capacity was 250,000 lbm/h. With an increase in steam density of
11.9% corresponding to the proposed conditions, it can be shown that the new throttle flow
capacity would be 280,000 lbm/h if the HP nozzle is left unmodified. This equates to
approximately 2.6 times the steam flow requirement for the proposed conditions. Similarly,
because the turbine was originally designed to provide a large extraction flow, the 2nd stage
diaphragm, if dimensionally inspected, would be found to contain substantially more flow area
than required for the proposed application. This means that both the 1st and 2nd stage flow areas
must be reduced by the appropriately calculated amounts to achieve desired performance.
The LP section of the turbine was originally designed to flow approximately 1.3 times as much
steam to exhaust (at 40 psig) as would be needed for the proposed conditions. This would
suggest that the stationary flow areas of stages 3-7 should also be reduced by various amounts.
Complicating the issue, however, is the decrease in the proposed exhaust pressure compared to
original. Exact statements cannot be made, therefore, about the modifications that would be
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
Item Description
30,000
25,000
40,000
10,000
18,000
70,000
Total
140,000
333,000
Table 6. Anticipated equipment inspection and readiness costs
The difference between 640,000 and the total (333,000) given in Table 6 is 307,000. It is
recommended, therefore, that a reasonable equipment purchase price should fall within the range
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952
1
1
1
1
1
1
1
8
9
10
11
12
13
14
15
16
17
2
1 box
1
1
1
1
1 box
1
4
1 lot
18
19
4
1 lot
296 L x8 6 x 9
124 x 4 x 53
12 x 77 x 78
8 x 8 x 68
6 x 4 x 4
4 x 4 x 7
5 x 4 x 7
44,000
3,600
38,000
19,000
2,500
800
1000
10 6 x 43 x 2 2
106 x 43 x 2 2
11 x 32 x 42
4 x 4 x 5
108 x 15 x15
128 x 24 x 15
33 x33 x22
4 x 4 x 3
3 x 3 x 2
2000
1000
1500
500
200
200
255
150
300
20
P.O Box 2480, Friendswood, TX, 77549 USA Tel: (+1) 281-724-8788
Apartado Postal 1076-3000, Herdia, Costa Rica Tel: (+506) 2262-1952