Professional Documents
Culture Documents
Philosophy
for
Electrical Design
Onshore
Document Number
TO-HQ-02-011-00
00
Final Issue
RAW
27/5/05
A2
RAW
15/4/05
A1
RAW
25/1/05
Origin
By
Date
Issue
Rev
JEA
31/5/05
PZ
31/5/05
MF
3/6/05
Chkd
By
Date
Appd
By
Date
Appd
By
Date
Revision
Description of revision
A1
For Comment/Approval
A2
00
Final Issue
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
2 of 27
Contents
1.0 PREFACE .......................................................................................................................5
2.0 DEFINITIONS .................................................................................................................5
3.0 ABBREVIATIONS...........................................................................................................5
4.0 INTRODUCTION.............................................................................................................5
5.0 APPLICABLE CODES, STANDARDS AND REGULATIONS........................................6
5.1
5.2
General ....................................................................................................................................... 9
Flammable Gas/Vapour Hazards............................................................................................ 10
Standardisation of Equipment and Materials........................................................................ 11
Certificates, Declarations and Test Reports ......................................................................... 11
Quality Assurance and Control .............................................................................................. 11
General ..................................................................................................................................... 11
Classification of Loads ........................................................................................................... 13
Load Assessment and Electricity Consumption .................................................................. 13
System Voltages and Frequency............................................................................................ 13
Supply Capacity....................................................................................................................... 13
Power Generation .................................................................................................................... 13
Transmission and Distribution Systems ............................................................................... 14
Switchgear................................................................................................................................ 14
Electric Motors......................................................................................................................... 16
General Lighting ...................................................................................................................... 16
Emergency and Escape Lighting ........................................................................................... 16
Short Circuit Ratings............................................................................................................... 17
Electrical Protection ................................................................................................................ 18
Earthing .................................................................................................................................... 19
Uninterruptible, Maintained Power Supplies ........................................................................ 21
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
3 of 27
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
4 of 27
1.0
PREFACE
This Philosophy defines the OMV Exploration & Production GmbH corporate
policy on the design of Electrical Systems for onshore hydrocarbon
production and processing facilities.
The document specifies basic
requirements and criteria, defines the appropriate codes and standards, and
assists in the standardisation of facilities design across all onshore
operations.
The design process needs to consider project specific factors such as the
location, production composition, production rates and pressures, the
process selected and the size of the plant. This philosophy aims to address
a wide range of the above variables, however it is recognised that not all
circumstances can be covered. In situations where project specific
considerations may justify deviation from this philosophy, a document
supporting the request for deviation shall be submitted to OMV E&P for
approval.
Reference should be made to the parent of this philosophy, document
number TO-HQ-02-001 for information on deviation procedures and
Technical Authorities, general requirements and definitions and
abbreviations not specific to this document
2.0
DEFINITIONS
The following definition is relevant to this document.
Variable Speed
Drive System
(VSDS)
3.0
ABBREVIATIONS
There are no abbreviations with particular relevance to this document.
4.0
INTRODUCTION
This document describes the philosophy to be used for the design, engineering
and installation of electrical facilities, which comprise all fixed Electrical
Installations for power and lighting up to and including main supply facilities for
instrument and control equipment and safeguarding systems, cathodic protection
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
5 of 27
Local Regulations,
National standards.
Design of the safety system shall comply with the standards listed within this
philosophy, however, for instances where local standards are more onerous local
standards shall apply.
5.1
API RP 540
NEMA MG2
IEC 60038
Standard voltages.
IEC 60050
IEC 60056
IEC 60071
Insulation co-ordination.
IEC 60076
Power Transformers.
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
6 of 27
IEC 60083
IEC 60099
Lightening arresters.
IEC 60113
IEC 60120
IEC 60227
IEC 60255
Electrical relays.
IEC 60298
IEC 60309
IEC 60332
IEC 60364
IEC 60383
IEC 60433
IEC 60439
IEC 60529
IEC 60536
IEC 60549
IEC 60593
IEC 60617
IEC 60623
IEC 60688
IEC 60742
IEC 60801
IEC 60815
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
7 of 27
IEC 60831
Shunt power capacitors of the self heating type for a.c. systems
having a rated voltage up to and including 1kV.
IEC 60871
IEC 60896
IEC 60909
IEC 60947
IEC 61000
Electromagnetic compatibility.
IEC 61089
Round wire
conductors.
IEC 61241
IEC 61800
concentric
lay
overhead
electrical
stranded
API-505
General requirements.
EN 50015
Oil Immersion.o
EN 50016
Pressurised apparatus p
EN 50017
Powder filled q
EN 50018
Flameproof enclosure d
EN 50019
Increased safety e
EN 50020
Intrinsic safety i
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
8 of 27
5.2
EN 50021
Type of protection n
EN 50028
Encapsulation m
EN 50039
EN50160
Voltage Characteristics
Distribution systems
of
Electricity
Supplied
by
Public
References
TO-HQ-02-012
SYSTEM GOAL
The Electrical Installation shall provide a safe and reliable supply of electricity
at all times, under all operating conditions, including those associated with
start-up and shutdown of plant and equipment, and throughout the intervening
shutdown periods.
7.0
SYSTEM BOUNDARIES
The boundary of the electrical system is the interface with the public utility supply.
8.0
DESIGN PHILOSOPHY
8.1
General
The design of the Electrical Installation shall be based on the provision of a
safe and reliable supply of electricity at all times. Safe conditions shall be
ensured under all operating conditions, including those associated with start-
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
9 of 27
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
10 of 27
8.3
8.4
8.5
9.0
DESIGN REQUIREMENTS
9.1
General
The design of the Electrical Installation shall be commensurate with any specific
design criteria philosophy and/or objective that may be stated in the project
definition phase, e.g. in a Basis of Design document and/or project specification,
relating to a particular plant or facility. For instance, it may be defined by plant
lifetime, skill of operating and maintenance personnel, operational flexibility,
extension possibilities or noise limitations, etc.
The philosophies to be employed will depend on the size and complexity of the
installation; those approved for a specific project shall be set down clearly during
the project definition phase. Any fundamental deviation thereafter shall be subject
to the OMVs approval.
The conceptual designs and philosophies relating to the electrical system shall
be adequately illustrated by the production of a system design specification, a
key line diagram, basic layout drawings and functional /outline specifications.
The electrical system and associated controls shall be designed on the basis of
forming an integral part of the process plant facilities, as far as is practicable. For
example, on-site electrical generation by the recovery of process heat energy
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
11 of 27
and integration of the electrical system controls with process control systems
shall be considered. Furthermore, due regard should be given to the selection
and utilisation of efficient electrical equipment in order to reduce energy
consumption. The use of high efficiency / power factor electric drives, the use of
VSDS for speed, flow or power control, the selection of low-loss transformers,
etc, should be evaluated during the detail design and equipment procurement
stages of a project.
When designing electrical power systems, the following alternatives for the
electricity supply shall be considered; own generation, public utility supply, or a
combination of these within the limits and possibilities given by OMV. The design
and selection of power sources shall ensure a degree of availability
commensurate with the service required.
Generating sets should normally be in an electrically centralised location and the
distribution system arranged radially. Ring distribution systems shall be
considered for residential/ industrial facilities located at relatively large distances
from the power source or from each other.
Power factor control and/or power transfer to alternative energy sources, mainly
in connection with tariff characteristic of outside supplies, shall also be
considered.
A key line diagram of the Electrical Power System shall be prepared and kept up
to date throughout the lifetime of the plant.
System studies and protection reports, etc, shall be provided in support of the
design. Depending on the type, size and complexity of the installation, such
studies may comprise the following:
The scope of the system studies shall be defined by OMV and agreed with the
Contractor before the commencement. Where there is a public utility
interconnection, the public utilitys study requirements should be considered
within the scope of these studies.
Philosophy for Electrical Design
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
12 of 27
9.2
Classification of Loads
Electrical loads shall be classified as performing a service that is vital,
essential, or non-essential as defined in Section 2.0.
9.3
9.4
9.5
Supply Capacity
The firm capacity of the electrical points of supply (generation, and associated
power plant switchgear, and/or grid intake transformers and switchgear) shall be
capable of supplying continuously 125% of the peak load, assessed in
accordance with the applicable load data without exceeding specified voltage and
frequency limits and equipment ratings.
The spare capacity at plant substations shall be a minimum defined by OMV at
the start of the construction phase, this spare capacity being retained for future
plant debottlenecking and changes.
The provision of stand-by capacity shall be considered in relation to safety,
reliability and the requirement of continuity of plant operations.
The reliability of distribution systems shall be at least comparable to their supply
systems, each incorporating sufficient stand-by capacity to enable maintenance
work, tests and inspection checks to be carried out. Electrical system
maintenance requirements shall be considered in relation to plant shutdown for
overhaul of process units.
9.6
Power Generation
The number of generating sets to be installed and their individual ratings depend
on many factors, e.g. maintenance requirements, economic size, future load
development pattern, unit reliability etc. Sufficient stand-by capacity shall be
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
13 of 27
incorporated to fulfil the requirement of the peak load with the largest generating
set out of service.
The availability of further stand-by supply capacity to cater for generating set
failures during such maintenance/repair periods shall be provided where the
aggregate maintenance time warrants this.
For plants with own generation capable of operating in island mode, an automatic
load shedding system shall be provided.
9.7
9.8
Switchgear
Currently available switchgear is considered to be sufficiently reliable to require
no duplication in itself. Consequently, distribution and plant switchboards,
including group motor control centres, shall have a single busbar system and a
single switching device per circuit.
HV switchboards at intake substations and power plant substations incorporating
double busbar systems may be selected as an alternative to the above
arrangement, but only if justifiable on the basis of facilitating system extension
and operating flexibility which would otherwise involve significant disruption of
electricity supply, or if facilitating a supply of differing priority/security from each
busbar. An example of the latter would be where own generation and higher
priority loads would be connected to one busbar, and a public utility supply (of
poorer reliability) together with lower priority loads to the other busbar. The bus
coupler circuit breaker would be utilised to effect disconnection in the case of grid
supply interruptions.
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
14 of 27
Switchboards with double busbar systems shall incorporate one circuit breaker
per circuit.
HV and LV switchboards shall generally have a maximum of three sections and,
consequently, a maximum of two bus section switches. LV switchboards with four
sections in H configuration are acceptable. Special arrangements, e.g.
automatic changeover, may be required for switchboards supplying Vital
Services, where an alternative supply is required.
In the absence of quantitative analysis of circuit reliability data relating to a
specific design that would support an alternative operating mode, and unless
specific system design requirements dictate otherwise, the normal operating
position of switchboard bus section switches shall be as follows:
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
15 of 27
9.9
Electric Motors
Currently available electric motors are considered sufficiently reliable for single
essential drives. For Vital Services, stand-by units shall be installed, and supplied
from a separate source of supply.
9.10
General Lighting
Industrial lighting in white colour shall in general be used for illumination. Where
special requirements regarding colour distinction exist, these shall be met.
Long life lamps in combination with electronic ballasts shall be used in new
installations and for upgrading old installations, so as to take advantage of their
increased efficiency and economic life.
High pressure discharge lamps should be used in the case of lighting high
buildings or large areas. In view of the restart time of this type of fitting after a
Voltage Dip, sufficient fluorescent luminaries shall be installed for the basic
lighting requirements of the area.
The plant lighting system shall be based on the operational requirements and
include as low as possible environmental influence.
As far as practical, fluorescent lighting shall be used throughout the plant
installations.
Refer to Document Number TO-HQ-02-018 Philosophy for Lighting and Trace
Heating Onshore for further details.
9.11
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
16 of 27
9.12
The maximum short circuit level at the point of supply from which the
new switchgear will be energised.
An electrical loading of the new installation such that the firm capacity of
the supply is fully utilised.
Future planned increases in short circuit level due to the direct or indirect
connection of machines, public utility supply or other sources of short
circuit current.
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
17 of 27
9.13
Any restrictions imposed by the public utility with respect to short circuit
current infeeds to their supply network shall not be exceeded.
Electrical Protection
The application and selection of protective systems and devices shall be based
on the following premises:
Electrical Installations connected to the public grid shall be protected in
compliance with the requirements of the public utility.
A standardised protection method:
The consideration to prescribe standardised protection methods shall be based
on the requirement to control the total area of electrical protection. In the design
phase attention should be paid at least to:
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
18 of 27
Earthing
AC system neutrals shall normally be earthed as detailed below. They shall not
be designed for unearthed operation, except where forming an extension to an
existing unearthed system
HV electrical systems shall be earthed by means of dedicated earth electrodes
connected to the plant main earth grid.
HV system neutrals shall be earthed at each source of supply (transformer,
direct-connected generator etc)
For grid infeed system the neutral point of transformers should be solidly earthed,
unless otherwise stated by the public utility.
Transformer feeders to HV switchboards shall be resistance earthed. The rating
of the resistors shall be such as to limit the earth fault current supplied by the
equipment to which the resistor is connected to a magnitude approximately equal
to the rated full load current of the supply equipment. (generator or transformer)
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
19 of 27
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
20 of 27
parallel with the normal high impedance device so that, if a fault on an outgoing
circuit is not cleared within the allowed time, the resistor can be switched in to
provide a higher fault current to allow clearance by back-up protection.
LV electrical system neutrals at each source of supply shall be solidly earthed by
means of dedicated earth electrodes which have a direct, low impedance
connection to the plant main earth grid.
For LV equipment, earth loop impedances shall be low enough to ensure that
circuit disconnection is achieved under fault conditions within agreed parameters.
AC UPS systems shall have their neutrals solidly earthed. This applies equally to
single phase and three phase systems. The Inverter (output) neutral shall be
connected to the neutral of the bypass mains neutral, which shall be solidly
earthed.
DC systems supplying instrumentation loads and switchgear control and
protection loads shall be earthed down through a high resistance earth fault
monitoring unit with a sensitivity to be defined during detailed design.
If buried cables are used for earthing purposes, only one side of the cable screen
may be connected to the earthing rod.
9.15
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
21 of 27
10.0
DESIGN CONSIDERATIONS
10.1
General
The design of the electrical system should take account of the following:
Life cycle costs as well as the capital cost, for example testing costs,
false trip costs, commissioning and modification costs.
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
22 of 27
Human factors.
Selection and positioning of the correct field equipment suitable for the
process and environmental conditions.
The electrical system shall provide protection for normal operation and for the
conditions that may arise from an abnormal condition.
11.0
DESIGN CRITERIA
The electrical system shall be designed to take account of the environmental
conditions of the site that it is to be located to ensure reliability is preserved.
Design of the electrical system should take account of the requirements covering
the full lifecycle of the plant.
The controls of the electrical system shall not be affected by radio-frequency
signals, from hand-held portable radio units.
All parts of the electrical system should be designed as a fail-safe system forcing
all outputs to a de-energised/ open circuit state on a failure. An exception to this
is for outputs where the failure of the output would create a hazard. Under these
circumstances the output circuit should be line monitored and configured
energised to trip.
Logic parts of the electrical system that cannot be designed as fail-safe, such as
timers, shall be used in redundant arrangements. Any single failure within a
redundant arrangement shall not prevent a demanded trip.
Digital and analogue signals shall be segregated from one another.
It should be noted that the CE Mark, or CE marking as it is officially named, is
an obligatory product mark for the European market, which indicates
compliance 'certification' according to the requirements formulated in the
approximately 22 European 'CE Marking Directives' and subsequent
European standards.
12.0
MAINTENANCE IN DESIGN
The electrical system shall be designed taking maintainability into consideration
by simplifying maintenance and reducing maintenance costs where practical.
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
23 of 27
DOCUMENTATION REQUIREMENTS
All necessary drawings documents and reports relating to the design of the
Electrical Installation and for its operation, and all necessary drawings required
for the installation interconnection of equipment and cabling shall form part of the
design package. The documents, reports and drawings shall be prepared and
submitted for approval as required by the client. This shall generally be in two
stages for document preparation and approval, namely Project Specification and
Design and Engineering which are typically required during the definition and
implementation phases of a project.
Fully detailed construction drawings shall be provided so that the site
construction contractor can install all electrical equipment with no design effort.
Vendor information and details shall be incorporated in the design package as
soon as it becomes available.
Such information shall be updated when alterations to the design are made and
shall include additional information that is required during construction or may be
required for future maintenance, troubleshooting and operation.
As built drawings shall be prepared for the project covering all parts of the
Electrical Installation and for its operation and all necessary related civil
engineering, mechanical and instrumentation work.
Documents shall include:
Key single line diagram. This shall show the complete a.c. electrical generation
and distribution system of the plant including all HV feeds, main LV feeds and
sub-distribution boards, together with:
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
24 of 27
Block diagrams.
Block Diagram: This shall show the basic control and protection systems
defining the protection, control, trip and alarm functions to be fulfilled at the
different locations. It shall also indicate the reference signals and controls needed
and all the auxiliary supplies required such as air, lube-oil, cooling water,
electrical auxiliary supplies etc.
Single Line Diagram: This shall detail the main circuitry and its earthing
systems. It shall also indicate the instrument transformers, relays, meters, etc, for
the control, protection and operation of the equipment together with electrical
data such as voltage, current and impedances.
A single line diagram of a.c. and d.c. interruptible and Uninterruptible, Maintained
Electricity Supply systems shall be provided. The single line diagram shall detail
for each system the system configuration, earthing arrangements, UPS and
emergency generator ratings, the equipment number, function, location, nominal
voltages, maximum load, number and type of battery cells and battery Autonomy
Time.
Switchgear drawings: The following drawings shall be provided for each HV
and LV switchboard:
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
25 of 27
Power, lighting, earthing, substation, and trench layout drawings shall identify:
All electrical equipment and cables by their equipment and cable numbers.
The power layouts shall show all power cabling, identified by cable numbers,
lighting supply cables up to the main junction boxes, and the power and
convenience outlet distribution board feeder cables.
Lighting and Small Power layouts shall show all luminaries, (normal and
emergency), all level gauges, all power and convenience outlets distribution
boards, and all boxes and cable routing, downstream of the main distribution
boxes.
N.B. Luminaires etc, shall be identified by a support detail reference, circuit
reference, and fitting/outlet reference. If required for clarity, separate or additional
layouts should be prepared for different levels within a building or installation.
Earthing layouts shall show the main earthing grid, branch connections, earth
electrodes, earth bars and conductor sizes for both the electrical earthing system
and instrument clean earth system.
Cathodic protection layouts shall include all items to be protected, (such as:
cables, rectifiers, anodes, reference cells, connection boxes, measuring posts,
insulation joints.)
HVAC layouts shall include all items involved, such as ducts, heat exchangers,
panels, heaters, fans, and cabling. As far as possible drawings shall be
combined with the other electrical drawings.
The cable trench layouts shall show the physical location of all underground
cable trenches, underground pipes and ducts.
Cross-sectional arrangement drawings shall be provided for all cable trenches,
ducts and above ground cable routes showing the location and number of each
cable along the routes.
Construction drawings (typical): Shall show typical construction and mounting
details of the power, lighting and earthing installations which cannot otherwise be
shown on the layouts. Each detail shall have a unique reference.
Philosophy for Electrical Design
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
26 of 27
Area classification drawings: These shall show the classification of the areas
with respect to the gas or vapour or dust explosion hazard, and shall include
sectional elevations where needed for clarity.
Vendor drawings: Shall be provided to show as a minimum all the information
specified in the relevant specification and requisition.
Equipment and Cable numbering: A logic system of numbering shall utilised.
For plants having an existing numbering system, this system shall be followed.
14.0
Layout drawings
Document Number
Onshore
TQ-HQ-02-011
Rev
00
Page
27 of 27