Professional Documents
Culture Documents
2, April 1991
840
T. YAMAGIWA, B. YAMADA,
Member, IEEE
Kokubu Works
F. ENDO, Y. OHSHITA,
Hitachi Research Lab.
Hitachi, Ltd.
Hitachi-shi, Ibaraki-ken, Japan
SYSTEM
90 X: le0-2 ??:RE
IZUMI, I. YAMADA
Energy Research Lab.
S.
[Technologies]
Prevention of accidents
and faults
Abnormal
conditions
diagnosis/
prediction
SENSING
Planned suspension
__
Quick restoration
after accidents
Operation support
Figure 1.
Equipment
conditions
monitoring
Accident
locat ion
detection
Expert system
0885-8977/91/0400-0840$0
1.ooO1991 IEEE
Authorized licensed use limited to: UNIVERSITY TENAGA NASIONAL. Downloaded on March 11,2010 at 05:36:07 EST from IEEE Xplore. Restrictions apply.
84 1
Table 1.
G I S Operation
Function
Insulation
Table 2
Detection Method
Principle
Spacer coupling
method
Discharge pulse
voltage is detected by
u s i n g suacercapacitance
lOOpC
Tank potential
method
Pulse voltage on a
tank induced by discharge is detected
lOOpC
lOOpC
groundins conductor is
detected
Magnetic radiation Magnetic field radiamethod
tion is detected by
loop antenna
2OOpC
Vibration method
50 to
Tank vibration
generated due to
discharge is detected
Abnormality/Fault
Causes
.Insulator change
Sensor1
Fault Development
+Partial Discharge
.Partial discharge
.Acoustic
.Particles
Gas Decomposition
.Decomposition gas
.Gas density
etc.
.Excessive overload
Breakdown
-Local heating-Gas
decomposition
.Tank temperature
.Poor tightening
Contact resistance
.Infrared camera
increase
.Vibrations
.Contact consumption,
Partial discharge
.Accumulated
etc.
breaking current
Breakdown
Switching
lOOpC
.Insulator crack
Current conduction
Sensitivity
.Large mechanical
friction
.Fault of control
+Stroke change/strain
----i
Stroke
circuit
.Gas/oil leakage,
etc.
Lightning
Arrester
.1
Temperature rise -Thermal
Breakdown
.Leakage current
7
runaway
Authorized licensed use limited to: UNIVERSITY TENAGA NASIONAL. Downloaded on March 11,2010 at 05:36:07 EST from IEEE Xplore. Restrictions apply.
842
A successful method with higher sensitivity has
been achieved by the introduction of a new technique
wherein the electromagnetic wave generated
in
association with partial discharge is captured and its
frequency spectrum is analyzed.
Figure 2 shows an example electromagnetic wave
noise spectrum from a substation.
The field noise is
extremely large in the frequency band of 300MHz and
below, while there is almost no noise in the frequency
band above this level. The spectrum around 750MHz seems
to be a communication wave and differs in level and
frequency depending on the area. In the laboratory,
artificial partial discharge is generated from a voltage
application line to a simulated GIS and the generated
electromagnetic wave is measured by an antenna mounted
on the side o f the GIs. For example, the spectrum shown
in Figure 3 is obtained. The level rapidly attenuates
with an increase in frequency and there is almost no
electronagnetic wave in the G H z region.
This
electromagnetic wave is attenuated due to the impedance
of the application line and bushing in the process of
entering the GIS interior via the voltage application
line and bushing. Thus, the high frequency components of
several hundred MHz and more almost disappear. However,
the generation of partial discharge inside the simulated
GIs in such a manner as by using metal particles o r
forcibly cracking a spacer results in the discharge of
an electromagnetic wave with a spectrum intensity nearly
uniform over the area from MHz to GHz. Since the high
voltage conductor and the tank form a coaxial conduit
line inside the simulate GIs, the electromagnetic waves
with frequencies less than those expressed by Equation
(1) are cut off and electromagnetic waves with greater
frequencies propagate with almost no attenuation:
'
TLk?seA
cl
300
600
900
Frequency
Figure 2 .
1200
1500
(MHz)
rl
cl
300
600
900
1200
1500
Frequency (MHz)
Figure 3 .
$-?y/T
P a r t i a l discharge sensor
~
Grounded tank
GIS bus
kP a r t i c l e k W
Analyzer
Feature
In partial discharge
generated outside the
GIs, components
at frequencies of
5OMHz and more are
small even if the
level is high.
Partial discharge
generated inside
the GIS appears
in the band from
750 to 1500MHz.
Inside
partial
discharge
Q = 8pC
300
3I
Ultrasonic sensor
Amp. : a m p l i f i e r
Frequency spectrum
C e n t r a l conductor
Acceleration sensor
400pC
1 Outside
partial
discharge
and
2 Inside
partial
discharge
are added
together
It is possible to
distinguish and detect
the GIS inside discharge
even if partial
discharge occurs
inside and
outside the GIS
simultaneowly.
Authorized licensed use limited to: UNIVERSITY TENAGA NASIONAL. Downloaded on March 11,2010 at 05:36:07 EST from IEEE Xplore. Restrictions apply.
843
associated with partial discharge generated inside the
GIs,
electromagnetic waves with frequencies of some
lOMHz to G H z propagate without being cut off. Due to
this, detection of a electromagnetic wave frequency band
o f several hundred MHz o r more with no external noise
leads to the detection of partial discharge in the
inside of a G I S at a high S/N ratio.
Figure 4 shows this new sensing technology. An
antenna with good frequency characteristics, i.e. a
partial discharge sensor, is placed o n the inside of the
The detected electrogrounded tank of the G I S bus.
magnetic wave is analyzed by a frequency analyzer and
processed by a computer. If 400pC partial discharge is
purposely generated outside of the G I s ,
only an
electromagnetic waves with a frequency of 300MHz or less
propagate into the G I s , (condition 1). Electro-magnetic
waves with frequencies of several hundred MHz and more
are detected if partial discharge is generated inside
the G I S (condition 2 ) [ 5 , 6 ] .
This frequency band tends
to extend with an increase in the discharge level.
Simultaneous generation of the 400pC G I S outside partial
discharge and 8pC G I S inside partial discharge gives a
spectrum of the shape created by adding the shapes of
conditions 1 and 2 .
Therefore, it is possible to
distinguish the inside partial discharge from the
outside partial discharge based on the frequency.
According to this method, if the S/N ratio is extremely
large, the detection sensitivity can be improved by o n e
order compared with the conventional methods, and lOpC
is detectable.
One of the causes of a reduction in the G I S insulation function is metal particles.
With metal
particles mixed in, partial discharge occurs at a
voltage quite lower than the flashover voltage.
The
quantity of charge by the discharge differs depending o n
the length of the particles and has the value shown in
Figure 5. This value becomes almost one order smaller
if the suspended particles attaches itself to the
conductor o r spacer.
According to the new sensing
technology shown in Figure 4, lOpC can be detectable and
thus metal particles several millimeters long can be
detected with certainty.
U
a
v
20
10I
aru
$4
4 7
ala
v u
4
U 0
7
I
-40L
Pp
-50
10
20
30
Particle length (mm)
4iE
7
Figure 5.
.B
a 7
0
E
i2z
wa wa
o a oar
a u
a0 nrn
o
u 0
L
L
t j n
.rl
z
0
Noise Source
Figure 6.
Authorized licensed use limited to: UNIVERSITY TENAGA NASIONAL. Downloaded on March 11,2010 at 05:36:07 EST from IEEE Xplore. Restrictions apply.
844
Abnormal Conductinq Condition Sensinq Technoloqy
Bad contact in the electrical section results in a
reduction in conducting condition area and current
flowing in concentration to a local area. As a result,
the contact microscopically expands and contracts
repeatedly so that the vibration propagate to the tank.
The contact, as shown in Figure 7, can be regarded as an
assemblage of point contacts, and Joule heat q is
represented by Equation ( 2 ) 1 7 , 8 1 .
Ari
q
p (1
aTi)-
LI
I*
Si
where p is resistivity, a is temperature coefficient, Ti
is the temperature at element i, Si is the sectional
area, ari is the thickness of the point contact and I is
the current.
This heat generation causes a higher
harmonic strain in the contact potential difference of
the contact point, resulting in the generation of a very
small vibrations at a frequency proportional to the
product of the integral multiplication of the power
source frequency. The detection of abnormal conducting
condition can be attained if an acceleration sensor is
mounted in the tank as shown in Figure 7, and the signal
detected by the sensor is analyzed by a frequency
A
analyzer. A detection example is shown in Figure 8 .
normal vibration (Figure 8 (a)), has components of
relatively low frequencies.
If a bad contact occurs,
components of high frequencies of the integral
multiplication of commercial frequencies appear as shown
Monitoring of these vibration
in Figure 8 (b).
components allows the detection of an abnormal condition
at a very early stage.
Next, consideration is given to the relationships
between the detection sensitivity and softening, melting
and vaporizing
o f metals.
Vibration
energy
(proportional to the sum of the square of the vibration
speed) is calculated from the signal detected by the
acceleration sensor in order to find a relationship with
voltage at the contact.
The result is shown in Figure
9. The vibration energy changes stepwise if the voltage
. Frequency (KHz)
(a) Tank vibration when normal
Frequency (KHz)
(b) Tank vibration when abnormal
condition
Figure 8.
\Acceleration/
d
Point contact
condition
Figure 7.
i
Table 3
Analytical model
Simulation of Abnormal
Current Conduction
Authorized licensed use limited to: UNIVERSITY TENAGA NASIONAL. Downloaded on March 11,2010 at 05:36:07 EST from IEEE Xplore. Restrictions apply.
845
Partial discharge
sensor
Stroke sensor
Acceleration
sensor
I t __ t
Example of sensors for GIS
Local
monitoring
unit
for G I S
Local
monitoring
unit
for
transformer
Main monitoring
__
-1
LTC torque
sensor
Figure 10.
Rogowsky coil
Ultrasonic
microphone
Dissolved gas in o i l
SenSer
[2]
Authorized licensed use limited to: UNIVERSITY TENAGA NASIONAL. Downloaded on March 11,2010 at 05:36:07 EST from IEEE Xplore. Restrictions apply.
846
[3]
BIOGRAPHIES
Tokio YAMAGIWA (M'87) was born in
Nagano
Prefecture, Japan on
February 12, 1949. He received the
B.S.
degree
in
electrical
engineering
from
Science
University of Tokyo in 1971. Then
he
joined Hitachi
Research
Laboratory, Hitachi, Ltd. and
engaged in the research on SF6 gas
insulation,
gas
insulated
switchgears and bushings.
Since 1 9 8 7 he has been
engaged in the development of S F 6 gas insulated
apparatus and diagnostic techniques for them. Now, he is
a senior engineer in Kokubu Works, Hitachi, Ltd.
Mr. Yamagiwa is a member of the IEE of Japan.
Hiroshi
YAMADA was b o r n
in
Niigata, Japan on January 15,
1945. He received the B.S. degree
in electrical engineering from
Tokyo Institute of Technology,
Tokyo in 1968. Since 1968 he has
been with Kokubu Works, Hitachi,
Ltd., working in the Power System
Control h Protection Engineering
Department.
Mr. Yamada is a member of the
IEE of Japan.
Authorized licensed use limited to: UNIVERSITY TENAGA NASIONAL. Downloaded on March 11,2010 at 05:36:07 EST from IEEE Xplore. Restrictions apply.
847
Discussion
RUNDE (Norwegian Electric Power Research I n s t . ,
Trondheim. Norway): The a u t h o r s have d e s c r i b e d s e v e r a l
i n t e r e s t i n g concepts f o r d i a g n o s i s of CIS. I n p a r t i c u l a r t h e u s e of a c o u s t i c s e n s o r s t o monitor t h e
c o n d i t i o n s of t h e c o n t a c t s i n s i d e a g a s compartment
seems t o m e as a novel and very i n t e r e s t i n g approach.
M.
Q u e s t i o n 1:
Table 3 shows t h e s o f t e n i n g , m e l t i n g and evaporation
v o l t a g e s and t h e corresponding temperatures for a
number o f m e t a l s . I am n o t a b l e t o s e e how t h i s is of
r e l e v a n c e t o t h e v i b r a t i o n e n e r g i e s . The d i s t o r t i o n of
t h e v o l t a g e waveform is s o l e l y a r e s u l t of t h e nonuniform r e s i s t i v i t y caused by t h e temperature i n c r e a s e
i n t h e s m a l l c o n t a c t spots. T h i s temperature and t h u s
also t h e v o l t a g e waveform a r e , t o my
knowledge,
b a s i c a l l y independent of t h e c o n t a c t material or its
thermoelastic p r o p e r t i e s .
Have t h e a u t h o r s made o t h e r o b s e r v a t i o n s ? Is t h e
s e n s i t i v i t y of t h e method found t o correspond t o t h e
softening
voltage?
I f so, is t h i s confirmed by
experiments on o t h e r c o n t a c t m a t e r i a l s , as f o r example
n i c k e l ? I would a p p r e c i a t e v e r y much i f t h e a u t h o r s
could elaborate on t h e s e matters.
Q u e s t i o n 2:
The a u t h o r s c l a i m t h a t t h i s technique a l l o w s for
d e t e c t i o n o f abnormal c o n t a c t s i n a very e a r l y s t a g e of
t h e i r d e g r a d a t i o n , and t h a t t h e s e n s i t i v i t y is s u p e r i o r
to thermal monitoring of t h e metal e n c l o s u r e [l]. What
type of thermal monitoring does t h i s r e f e r t o ?
shown i n F i g . 9 t h e d e t e c t i o n l e v e l is t h e c o n t a c t
r e s i s t a n c e t h a t y i e l d s a v o l t a g e drop across t h e
i n t e r f a c e of about 100 mV. These r e s u l t s w e r e o b t a i n e d
by a p p l y i n g a c u r r e n t of 1050 A rms [ l ] . and consequently the heat generation i n the contact i n t e r f a c e
w a s i n e x c e s s of 100 W. I assume t h a t t h i s y i e l d s a
s i g n i f i c a n t temperature rise on t h e surrounding metal
e n c l o s u r e . Standard i n f r a - r e d cameras with a tempera t u r e r e s o l u t i o n of t h e o r d e r of 0 . 1 K a r e now
a v a i l a b l e , and I have a f e e l i n g t h a t t h i s h o t region
would be e a s i l y o b s e r v a b l e through such a camera. Have
t h e a u t h o r s t r i e d i n f r a - r e d imaging t o locate t h e
degraded c o n t a c t s ?
As
Q u e s t i o n 3:
Has t h i s technique been a p p l i e d on c o n t a c t s i n C I S i n
s e r v i c e ? If y e s , d i d you o b t a i n t h e same s e n s i t i v i t y ?
Our e x p e r i e n c e is t h a t v a r i o u s n o i s e s o u r c e s p r e s e n t i n
a s u b s t a t i o n have a n e g a t i v e impact on t h e s e n s i t i v i t y
of a c o u s t i c methods, e s p e c i a l l y t h o s e o p e r a t i n g i n t h e
l o w kHz range.
Reference
1)
The results
obtained show that a temperature change exceeding 100C
takes place at the contact spot portion following the
current charge of the commerical frequency under the
condition that the voltage distortion appears. When the
distortion of the voltage waveform starts to appear o n
the copper electrode, it almost corresponds to the
softening voltage and the detecting level for conductive
abnormalities is in the vicinity of the softening
temperature.
Near the softening temperature welding
traces etc. do not occur, s o there is no substantial
change into the electrode state. Since abnormalities do
not progress even with
the heat generation,
abnormalities can be detected in a very early stage o f
their progression.
In measurements regarding other electrode materials, though many measurements were made with silverplated electrode besides copper, the results turned out
to be almost the same as for copper.
In the aluminum
and coppertungsten alloy electrode the occurrence of
vibration was confirmed but no quantitative discussion
has been made.
The
first ones are those which do not have features as shown
in Fig. D ( b ) , in the frequency region of rain, walking,
nearby construction, etc. and can be removed by
averaging and simple feature extraction, etc.
The
Authorized licensed use limited to: UNIVERSITY TENAGA NASIONAL. Downloaded on March 11,2010 at 05:36:07 EST from IEEE Xplore. Restrictions apply.
848
second ones are caused by electromagnetic force and
magnetic distortional vibrations due to conductive
current, which show the same pattern as the crest value
in the integer mutiple frequency of the power frequency.
Treatment is difficult when the noise level is large.
Authorized licensed use limited to: UNIVERSITY TENAGA NASIONAL. Downloaded on March 11,2010 at 05:36:07 EST from IEEE Xplore. Restrictions apply.