4M Protective and Measuring Transformers

Medium-Voltage Equipment
Selection and Ordering Data
Catalog HG 24 2009

Answers for energy.

R-HG24-050.tif

4M Protective and Measuring Transformers

Siemens HG 24 2009

4M Protective and Measuring Transformers

4M Protective and
Measuring Transformers
Medium-Voltage Equipment
Catalog HG 24 2009

Contents

Contents

Page

Description

General

Construction and mode of operation

Current transformers

Voltage transformers

12

Ambient conditions and dielectric strength

14

Partial discharge measurement and standards

15

Invalid: Catalog HG 24 1994

Equipment Selection

17

Ordering data and configuration example

18

Product overview of current transformers

19

Selection of current transformers

20

Product overview of voltage transformers

62

Selection of voltage transformers

63

Technical Data

69

Current transformers

70

Voltage transformers

78

Annex

83

Inquiry form

84

Configuration instructions

85

Configuration aid

Foldout page

Siemens HG 24 2009

R-HG11-214.tif

4M Protective and Measuring Transformers

Siemens HG 24 2009

4M Protective and Measuring Transformers

Description
Contents

Contents

Page

Description

General

Construction and mode of operation:


Types of construction

Approvals/Certifications

R-HG11-174.tif

Current transformers:

Industrial application: Refinery

Glossary of terms

Measuring current transformers

Protective current transformers

Multi-ratio current transformers

Performance in the event of overcurrent

10

Operation and earthing

10

Voltage detecting system

11

Voltage transformers:
Glossary of terms

12

Multi-ratio

13

Operation and earthing

13

Relaxation oscillations

13

Ambient conditions

14

Dielectric strength

14

Partial discharge measurement

15

Standards

15

Siemens HG 24 2009

4M Protective and Measuring Transformers

Description
General

Protective and Measuring Transformers The Adaptable

Current transformer

Voltage transformer

R-HG24-052.tif

with evaluable signals, which enable the protection device


to e.g. trip a switching device depending on the situation.
Furthermore, they isolate the connected measuring or
protection equipment electrically from live parts of the
switchgear.

R-HG24-051.tif

The task of instrument transformers is to transform high


currents and voltages proportionally and in-phase into
small current or voltage values for measuring or protection purposes. So they are used either to measure and
record the transmitted power or to feed protection devices

Current transformers can be regarded as transformers working in short-circuit, with the full normal current flowing
through their primary side. Devices connected on the secondary side are series-connected. Current transformers can
have several secondary windings with magnetically separated cores of the same or different characteristics. They can,
for example, be equipped with two measuring cores of different accuracy class, or with measuring and protection
cores with different accuracy limit factors.
Due to the risk of overvoltages, current transformers must
not be operated with open secondary terminals, but only in
short circuit or with the burden of the measuring equipment.

Siemens HG 24 2009

Voltage transformers contain only one magnet core and


are normally designed with one single secondary winding.
If necessary, earthed (single-phase) voltage transformers
are provided with an additional residual voltage winding
(earth-fault winding) beside the secondary winding
(measuring winding).
In contrast to current transformers, voltage transformers
must never be short-circuited on the secondary side. The
earth-side terminal of the primary winding is effectively
earthed in the terminal box, and must not be removed in
operation.

4M Protective and Measuring Transformers

Description
Construction and mode of operation

Types of construction

The following transformer types are available for selection in


this catalog:

R-HG24-053.eps

Protective and measuring transformers are designed in different types of construction for the multiple installation requirements and operating conditions they are subjected to.
They are electrical devices which convert primary electrical
values currents or voltages into proportional and in-phase
values that are adequate for the connected devices such as
measuring instruments, meters, protection relays and similar. A distinction is made here between current and voltage
transformers.

Example for transformer in block-type design

Current transformers
Indoor support-type current transformer in block-type
design
Indoor support-type current transformer in single-turn
design (e.g. bar-primary transformer)
Indoor bushing-type current transformer in single-turn
design
R-HG24-054.eps

Indoor bar-primary bushing-type current transformer


Outdoor support-type current transformer

Voltage transformers
Earthed (single-phase) or unearthed (double-phase)
indoor transformers in different sizes

Example for bushing-type transformer

Earthed (single-phase) or unearthed (double-phase)


outdoor transformers in different sizes

Approvals/Certifications
In Germany, instrument transformers may only be used
for commercial purposes, such as billing metering of electricity, if they have been approved once (type approval) by
the Physikalisch-Technische Bundesanstalt (PTB) (Federal
Physical-Technical Institute), and if every transformer is calibrated by an officially recognised inspecting authority.

R-HG24-055.tif

The transformers offered in the selection are only a part of


the possible variations. If the transformer required is not
shown, please clarify the feasibility with the responsible
sales partner or the order processing department in the
Switchgear Factory Berlin. The same applies to transformers
according to the ANSI standard.

Example for outdoor transformer

Calibration is done by a calibration office, or by the transformer manufacturer on behalf of a calibration office. The
test is documented by means of a test mark as well as a calibration certificate.
The calibration costs are charged in accordance with the official scale of fees.

Siemens HG 24 2009

4M Protective and Measuring Transformers

Description
Current transformers

Current transformers

Rated dynamic current Idyn

Current transformers can be regarded as transformers operating in short circuit, which carry the full rated current on
the primary side. The devices on the secondary side are
series-connected. They can have several secondary windings
with mechanically separated cores of the same or different
characteristics. Thus, current transformers can be designed
e.g. with two measuring cores of different accuracy class, or
with measuring or protection cores with different accuracy
limit factors.

The peak value of the primary current which a transformer


will withstand, without being damaged electrically or mechanically by the resulting electromagnetic forces, the
secondary winding being short-circuited.

Due to the risk of overvoltages, current transformers must


not be operated with open secondary terminals, but only in
short circuit or with the burden of the measuring equipment.

Rated output SN

Glossary of terms
Rated current IN (r.m.s. value in A)
The rated primary (IPN) and secondary (ISN) current is the
current that characterises the transformer, or the current it
is designed for. Both values are given on the transformer
rating plate. The rated primary current (IPN) depends on the
power system and is defined by the system operator.
Usual values for primary currents (in A):
10; 12.5; 15; 20; 25; 30; 40; 50; 60; 75
and their decimal multiples (preferred values are underlined).
Usual values for secondary currents: 1 and 5 A.
For technical reasons, but above all for economical reasons,
1 A is recommended as secondary current, especially if there
are long measuring leads.
Rated continuous thermal current ID (thermal strength)
The value of the current which can be permitted to flow continuously in the primary winding, the secondary winding
being connected to the rated burden, without the temperature rise exceeding the values specified.
ID is often equal to IN, but it can also be defined as a multiple
thereof.
Rated short-time thermal current Ith
The r.m.s. value of the primary current, flowing in case of
short circuit, which a current transformer will withstand for
1 or 3 seconds without suffering harmful effects, the secondary winding being short-circuited.

Siemens HG 24 2009

Rated transformation ratio KN


The ratio of the rated primary current to the rated secondary current. It is expressed as an unreduced fraction, e.g.
500 A/1 A.

The value of the apparent power (in VA at a specified power


factor), for which the current transformer has to keep the
accuracy class at the rated secondary current and with rated
burden. Thus, the rated output describes the capacity of a
current transformer to drive the secondary current within
the error limits by means of a burden.
Current transformers can feature the following preferred
rated outputs: 2.5 VA; 5 VA; 10 VA; 15 VA; 30 VA.
Rated burden ZN
The burden is the apparent resistance of the devices connected on the secondary side (including all connection
leads), for which the current transformer has to keep the
stipulated class limits. The burden is normally expressed as
apparent power in VA.
Current error Fi
The current error of a current transformer is (in %):
Fi = 100

K N I sec I prim
I prim

KN Rated transformation ratio


Iprim Actual primary current
Isec Actual secondary current

Phase displacement di
The difference in phase between the primary and secondary
current vectors, the direction of the vectors being so chosen
that the angle is zero for a perfect transformer.
The phase displacement is said to be positive when the secondary current vector leads the primary current vector. It is
usually expressed in minutes.

4M Protective and Measuring Transformers

Description
Current transformers

Limits of current error and phase displacement according to IEC 60044-1


Accuracy class

current error in percent

phase displacement in minutes

at rated current In
120 %
Measuring current transformers
0.2
0.2
0.5
0.5
1
1
Protective current transformers
5P

10P

at rated current In

100 %

20 %

5%

120 %

100 %

20 %

5%

0.2
0.5
1

0.35
0.75
1.5

0.75
1.5
3

10
30
60

10
30
60

15
45
90

30
80
100

1
3

60

Measuring current transformers

Protective current transformers

Current transformers provided for the connection of


measuring instruments, meters and similar devices
(e.g. 10 VA Cl. 0.5 FS5).

Current transformers intended to supply protection relays


(e.g. 15 VA CI. 10 P 10).

Rated instrument limit primary current

The limit of the percentage current error for the rated accuracy limit primary current.

The value of the primary current at rated burden and a composite error of 10 %.
Instrument security factor n
The ratio of rated instrument limit primary current to the
rated primary current
Note:
In the event of short-circuit currents flowing through the
primary winding of a current transformer, the thermal stress
to the measuring instruments supplied by the current transformer is smallest when the value of the rated instrument
security factor is small.
Accuracy class
The limit of the percentage current error at rated current IN
(see table).
Generally, current transformers are used for a measuring
range of 5 % to 120 % of the rated primary current.
Special designs
Extended current ratings
Current transformers with ext. 200 % can be continuously
operated at 2 x IN, and keep the error limits of their class in
the range up to 200 % of the rated primary current.

Accuracy class (identification P)

Rated accuracy limit primary current


The value of primary current up to which the transformer
will comply with the requirements for composite error.
Accuracy limit factor
The ratio of the rated accuracy limit primary current to the
rated primary current.
Multi-ratio current transformers
If the ratio of current transformers has to be variable, e.g.
for planned switchgear extensions, it is possible to use multiratio current transformers.
Primary multi-ratio
Only possible for wound-primary transformers (transformers with several primary turns) with a ratio of 1:2 (e.g. 2 x
600 A/1 A). Reconnection is made by re-arrangement of copper lugs in the primary connection area. Ratings, instrument
security factors as well as the secondary internal resistance
remain constant during reconnection.
Secondary multi-ratio
In single-turn and wound-primary transformers, this can
be implemented by taps of the secondary windings (e.g.
20001000 A/1 A).
Ratings or instrument security factors change almost linearly
with the ratio. If not stated otherwise, the specified rated
data is always referred to the lower current value.

Siemens HG 24 2009

4M Protective and Measuring Transformers

Description
Current transformers

Performance in the event of overcurrent


In the event of an overcurrent, the rated secondary current
increases proportionally with the rated primary current up to
the rated instrument limit primary current.

Protection core 5P10


IS
I SN

F i > -10%

The ratio of the rated instrument limit primary current to the


rated primary current provides the instrument security factor
assigned to the core. In accordance with this factor, the rated instrument limit primary current is subjected to specific
error limits.

Fg < 5%

Measuring core
Cl. 1M5

10

HG24-2200a_en eps

10

IP
I PN

The measuring and protection cores place different demands


on these error limits.
For measuring cores, the current error Fi is > 10 % in order
to protect the supplied measuring devices, meters, etc. safely in case of overcurrent.
In protection cores, the composite error Fg is max. 5 % (5P)
or 10 % (10P) in order to ensure the desired protection tripping.

Overcurrent performance of current transformers


when loaded with rated burden
Fi Current error

The specified limits are only fulfilled at the rated burden of the
transformer. If the operating burden differs from the rated
burden of the transformer, the instrument security factor
changes as follows:

Fg Composite error

n = n
n
n
ZN
SE
S

Z N + SE
S + SE

Actual instrument security factor


Rated instrument security factor
Rated burden in VA
Internal power consumption of the transformer in VA (approx. 5 % to 20 % of ZN)
Actually connected burden in VA

Operation and earthing

HG24-2201 eps

The secondary circuits of current transformers must never be


open during operation, as dangerously high voltages can
occur, especially at high currents and cores with high ratings.

Earthing of the secondary winding, for example,


in a 4MA7 current transformer

10

Siemens HG 24 2009

All metal parts of a transformer that are not live, but accessible, must be earthed. Therefore, the transformers have earth
connection points identified with the earthing symbol. Also,
one terminal of the secondary winding (for current transformers, normally k or 1s, etc.) must be earthed.
For earthing the secondary windings, a thread is provided
under each secondary terminal. The earth connection required is made by fitting a special screw.

4M Protective and Measuring Transformers

Description
Current transformers

Capacitively coupled voltage detecting system


The guidelines for every medium-voltage switchgear of the
new generation state that doors and covers can only be
opened when there is no risk of electric shock. The
movable single-pole voltage testers used up to now are not
suitable for this. Therefore, every medium-voltage switchgear is offered with a system including a fixed-mounted
capacitive voltage divider.

Indication range:
At 0.01 x UN, no indication,
as of 0.40 x UN, secure indication.
On request, support-type current transformers type 4MA7
can be delivered with capacitive layers for the voltage detecting system then they contain a coupling electrode.
This electrode is cast in a firm and protected way, and lead
out at the secondary terminals with the designation CK.
These current transformers are routine-tested additionally
for compliance with the requested capacitance values
(C1 and C2W). These values are documented on an additional
label.

U1

U
HG24-2202a_en eps

The capacitive voltage detecting system consists of a capacitive divider which divides the voltage U between the phase L
and earth into the partial voltages U1 and U2, and of an indicator applied to U2. The indicator contains a glow lamp that
flashes when voltage is applied.

U2

C1

C 2W

A
C 2L

Coupling section

Voltage detecting system


A

Indicator

C1

High-voltage capacitance (transformer)

C2W Low-voltage capacitance (transformer)


C2L Low-voltage capacitance (lead)
L

High-voltage phase

Voltage between phase and earth

U1 Partial voltage at C1
U2 Partial voltage at C2 and A
V

Surge arrester

To ensure protection against electric shock even in the most


improbable case that the current transformer punctures with
the high-voltage capacitor (while an operator is touching the
test sockets), a surge arrester is connected in parallel to this
arrangement inside the transformer. If the high voltage is exceeded, it responds within nanoseconds, limiting the voltage
at the test socket to harmless values.
Important for the ordering selection
When ordering transformers with capacitive layers
it is necessary to state the actual operating voltage UN
(rated voltage), e.g. Um = 24 kV, UN = 15 kV.

Siemens HG 24 2009

11

4M Protective and Measuring Transformers

Description
Voltage transformers

Voltage transformers

Phase displacement

Voltage transformers have only one magnet core, and are


normally designed with one single secondary winding. If
necessary, earthed (single-phase) voltage transformers
are equipped with an additional residual voltage winding
(earth-fault winding) beside the secondary winding
(measuring winding).

The difference in phase between the primary voltage and


the secondary voltage vectors, the direction of the vectors
being so chosen that the angle is zero for a perfect transformer. The phase displacement is said to be positive when
the secondary voltage vector leads the primary voltage vector. It is usually expressed in minutes.

In contrast to current transformers, voltage transformers


must never be short-circuited on the secondary side. The
earth-side terminal of the primary winding is effectively
earthed in the terminal box, and must not be removed
during operation.

Limits for voltage error and phase displacement


according to IEC 60044-1

Glossary of terms
Highest voltage for equipment Um

The voltage error and phase displacement at rated frequency


shall not exceed the values given in the table at any voltage
between 80 % and 120 % of rated voltage and with burdens
of between 25 % and 100 % of rated burden at a power factor of 0.8 lagging.

The highest r.m.s. phase-to-phase voltage (in kV) for which


a transformer is designed in respect of its insulation.

Accuracy class

Rated voltage UN

0.2
0.5
1

The voltage values (primary UPN or secondary USN) stated on


the rating plate of a transformer. If the voltage transformers
are connected between phase and earth in three-phase systems, this phase-to-neutral voltage is considered the rated
voltage. Except for the residual voltage winding, it is expressed as U/3, with U being the phase-to-phase voltage.
Um

Rated
primary voltage

Rated
secondary voltage

kV

kV

up to 52

3.3 3.6 4.8 5 6 6.6


7.2 10 11 13.8 15
17.5 20 22 30 33 35
40 45
or the values divided
by 3

voltage error

phase displacement

Minutes

0.2
0.5
1

10
20
40

Rated output SN
The value of the apparent power (in VA at a specified power
factor) which the transformer is intended to supply to the
secondary circuit at the rated secondary voltage and with
rated burden connected to it.
Preferred values:

100 110 120


Accuracy
class
or the values divided
by 3

Rated output
VA

0.2
0.5
1

10
10

15
15

30
30
30

50
50
50

75
75

100
100

200

Rated transformation ratio KN


The ratio of the rated primary voltage to the rated secondary
voltage. It is expressed as unreduced fraction, e.g.
10000/3 V / 100/3 V (single-phase)
10000 V/100 V (double-phase).
Voltage error FU
The voltage error expressed in percent is defined by the
formula:
FU = 100

K N U sec U prim
U prim

Uprim Actual primary voltage


Usec Actual secondary voltage under measuring conditions when Uprim is applied

Thermal limiting output Sth


The value of the apparent power referred to rated voltage
which can be taken from a secondary winding, at rated primary voltage applied, without exceeding the limits of temperature rise.
Thermal limiting output of the residual voltage winding
As the residual voltage winding is connected in broken delta,
it is only stressed in case of fault. Therefore, the thermal
limiting output of the residual voltage winding is referred
to a stress duration of e.g. 8 h, and is expressed in VA.
Rated voltage factor
The multiplying factor to be applied to the rated primary voltage to determine the maximum voltage at which a transformer must comply with the relevant thermal requirements
for a specified time and with the relevant accuracy requirements.

12

Siemens HG 24 2009

4M Protective and Measuring Transformers

Description
Voltage transformers

Voltage transformers for different rated primary voltages


can only be reconnected on the secondary side for reasons
of insulation.
Operation and earthing
In contrast to current transformers, voltage transformers
must never be short-circuited on the secondary side. The
earth-side primary terminal of earthed voltage transformers
is insulated for a test voltage of 2 kV. It is connected to the
earthed base plate in the terminal box.

HG24-2203 eps

Multi-ratio

Connection and earthing of the en or dadn winding

Attention
This connection must not be opened during operation.
Residual voltage windings connected in broken delta may
only be earthed together at one point.
For earthing the secondary windings, a thread is provided
under each secondary terminal. The earth connection required is established by fitting a special screw.
Relaxation oscillations

HG24-2204 eps

When single-phase voltage transformers are used in isolated


systems, damping of the en windings connected in broken
delta is recommended in order to avoid the possible destruction of the voltage transformers by relaxation oscillations.

Earthing of the secondary winding, for example,


in a 4MR voltage transformer

Siemens HG 24 2009

13

4M Protective and Measuring Transformers

Description
Ambient conditions and dielectric strength

Ambient conditions
The transformers are designed for the normal operating conditions defined in the standards.

40C

-5C

The conditions shown opposite apply to indoor transformers.


All indoor transformers are suitable for use with high air humidity and occasional condensation (e.g. in tropical areas).

max. 95% per day


max. 90% per month

As for outdoor transformers, the following conditions apply:


HG11-2515a_en eps

Minimum temperature
Outdoor transformers class 25

25 C

Outdoor transformers class 40

40 C

Relative air humidity


Outdoor transformers

up to 100 %

Dielectric strength
The dielectric strength of air insulation decreases with
increasing altitude due to low air density. According to
IEC 62271-1, the values of the rated lightning impulse withstand voltage and the rated short-duration power-frequency
withstand voltage specified, among others, in the chapter
Technical Data apply to a site altitude of 1000 m above
sea level. For an altitude above 1000 m, the insulation level
must be corrected according to the opposite diagram.

1.40

1.30

1.20

1.10

1.00
1000

The characteristic shown applies to both rated withstand


voltages.

HG11-2517c_en eps

Altitude correction factor

1.50

1500

2000

2500

To select the devices, the following applies:


U W U0 x Ka

3000 3500 m 4000


Site altitude

U Rated withstand voltage under reference atmosphere


U0 Rated withstand voltage requested for the place of installation
Ka Altitude correction factor according to the opposite diagram

Example
For a requested rated lightning impulse withstand voltage of
75 kV at an altitude of 2500 m, an insulation level of 90 kV
under reference atmosphere is required as a minimum:
90 kV W 75 kV x 1.2
Test voltages and insulation level for instrument transformers

Highest voltage
for equipment
Um

14

Rated short-duration
power-frequency
withstand voltage

Rated lightning
impulse withstand
voltage

kV

kV

7.2
12
17.5
24
36
52

20
28
38
50
70
95

60
75
95
125
170
250

Siemens HG 24 2009

Proper operation of the transformers is proved by the following tests:


Impulse test (type test)
Separate source withstand voltage test (routine test)
Induced voltage withstand test (routine test)
Partial discharge measurement (routine test)

All transformers correspond to insulation class E, i.e. the


maximum temperature rise is 120 C.

4M Protective and Measuring Transformers

Description
Partial discharge measurement and standards

Partial discharge measurement


Apart from the tests mentioned on page 14, partial discharge measurements are required for current and voltage transformers to test the insulation. A partial discharge is to be understood as any small, brief electrical discharge appearing on
or in a test object when voltage is applied. The discharges
appear as soon as the partial discharge inception voltage of
the insulating medium is exceeded at any point.

Type of earthing

Type of transformer

Systems with
isolated or impedance
earthed neutral

Current transformers
and earthed voltage
transformers

Systems with solidly


earthed neutral

Unearthed voltage
transformers
Current transformers
and earthed voltage
transformers
Unearthed voltage
transformers

Relatively high field strengths appear at sharp edges and


peaks of metal parts, or also on bubbles and gas inclusions
in solid or liquid insulating materials.
Partial discharges act like HF emitters, producing a mixture of
the most different frequencies. The partial discharge measurement enables an assessment about the homogeneity of the
insulating material. Partial discharge measurements are performed as a routine test on inductive transformers with solid
insulation as of Um = 3.6 kV.

Pre-stressing voltage

Measuring voltage

Permissible partial
discharge level

10 s
1.3 Um

1 min
1.1 Um

Apparent load
250 pC

U
1. 1 m
3

50 pC

1.3 Um

1.1 Um

50 pC

0.8 x 1.3 Um

U
1. 1 m
3

50 pC

1.3 Um

1.1 Um

50 pC

Standards
Protective and measuring transformers conform to the
following standards:
VDE 0414 Stipulations for instrument transformers
VDE 0111 Insulation co-ordination for equipment in
three-phase systems above 1 kV
IEC 60044-1
IEC 60044-2
ANSI 1675 (IEEE)
DIN 42600

Siemens HG 24 2009

15

R-HG24-057.tif

4M Protective and Measuring Transformers

16

Siemens HG 24 2009

4M Protective and Measuring Transformers

Equipment Selection
Contents

Contents

Page

R-HG24-053.eps

Equipment Selection
Ordering data and configuration example

18

Product overview of current transformers

19

4MA7 indoor support-type current transformer,


block-type design

20

4MB1 indoor support-type current transformer,


single-turn design

41

4MC2 indoor bushing-type current transformer,


single-turn design

44

4MC3 indoor bar-primary bushing-type


current transformer

47

4ME2 outdoor support-type current transformer

53

4ME3 outdoor support-type current transformer

58

Product overview of voltage transformers

62

4MR1 indoor voltage transformer,


block-type design, single-phase, small

63

4MR2 indoor voltage transformer,


block-type design, double-phase, small

63

4MR5 indoor voltage transformer,


block-type design, single-phase, large

63

4MR6 indoor voltage transformer,


block-type design, double-phase, large

63

4MS3 outdoor voltage transformer,


single-phase, small

63

4MS4 outdoor voltage transformer,


double-phase, small

63

4MS5 outdoor voltage transformer,


single-phase, large

63

4MS6 outdoor voltage transformer,


double-phase, large

63

R-HG24-058.eps

4MA74 current transformer

17

4MS6 outdoor voltage transformer

Siemens HG 24 2009

17

4M Protective and Measuring Transformers

Equipment Selection
Ordering data and configuration example

Order number structure

Order codes

Protective and measuring transformers are described by a


12 or 16-digit order number. The first five characters describe the type, design and application of the transformer
(primary part), and the positions 6 to 12 or 6 to 16 identify
the core data of the transformer.

Individual equipment versions, marked with 9 or Z in the


9th to 16th position, are explained more in detail by a 3-digit
order code. Several order codes can be added to the order
number in succession and in any sequence.

The transformers offered in the selection are only a part of


the possible variations. If the transformer required is not
shown, please clarify the feasibility with the responsible
sales partner or the order processing department at the
Switchgear Factory Berlin. The same applies to transformers
according to the ANSI standard.

For built-on components and special versions, -Z is added


to the order number and a descriptive order code follows.
If several built-on components and special versions are required, the suffix -Z is listed only once. If a requested special version is not in the catalog and can therefore not be
ordered via order code, it has to be identified with Y 9 9
after consultation. The agreement hereto is made directly
between your responsible sales partner and the order processing department in the Switchgear Factory Berlin.

Built-on components and special versions ()

a: alphabetical
Position:

Order No.:
1st position

n: numerical

10 11 12

13 14 15 16

4 M a

Order codes

Primary part
Superior group
Transformers

2nd position

Main group
Current and voltage transformers
for medium voltage

3rd position

Subgroup
Transformer type

4th and 5th position

Basic equipment
Design and operating voltage
of the transformer

6th to 16th position


6th to 12th position

Core data
Design and data of the current transformer
Design and data of the voltage transformer
Special versions ()
Initiated with -Z
Group of 3 after the Order No.
Format: a n n

Configuration example
At the end of each of the following pages with selection
data you will find a configuration example to make the
order number structure more clear.
Starting from the last selection of the basic type, this
example is continued, so that at the end of the equipment
selection a completely configured and orderable transformer
results for every product group.

Example for Order No.:


Order codes:

18

Siemens HG 24 2009

On the foldout page we offer a configuring aid.


Here you can fill in the order number you have
determined for your transformer.

4 M A

n n n n n n n n n

n n n

4M Protective and Measuring Transformers

Equipment Selection
Product overview of current transformers

Current transformer,
type of construction according to IEC 1)

10 11 12

13 14 15 16

4 M n n n n n n n n n n n n n n

Order codes

n n n

Type of design

R-HG24-071.eps

R-HG24-062.eps

R-HG24-054.eps

R-HG24-061.eps

R-HG24-060.eps

R-HG24-056.eps

Illustration

Position:

Order No.:

Indoor support-type current transformer,


block-type design,
small type according to DIN 42600,
cast-resin insulated,
operating voltage up to 12 kV, 24 kV or 36 kV

4 M A

7 Selection from page 20ff

Indoor support-type current transformer,


single-turn design,
cast-resin insulated,
operating voltage up to 12 kV or 24 kV

4 M B

1 Selection from page 41ff

Indoor bushing-type current transformer,


single-turn design,
cast-resin insulated,
operating voltage up to 12 kV, 24 kV or 36 kV

4 M C

2 Selection from page 44ff

Indoor bar-primary bushing-type current transformer,


cast-resin insulated,
operating voltage up to 12 kV, 24 kV or 36 kV

4 M C

3 Selection from page 47ff

Outdoor support-type current transformer,


cast-resin insulated,
operating voltage up to 12 kV, 24 kV or 36 kV

4 M E

2 Selection from page 53ff

Outdoor support-type current transformer,


top-assembly type,
operating voltage up to 12 kV, 24 kV, 36 kV and 52 kV 4 M E

3 Selection from page 58ff

1) Transformers according to ANSI standard on request

Example for Order No.:

4 M A

7 n n n n n n n n n n n n

Order codes:
Siemens HG 24 2009

19

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

4MA7 indoor support-type current


transformer, block-type design

kV

kV

75
95
125
170

28
38
50
70

12
17.5
24
36

10 11 12

13 14 15 16

4
4
4
4

7
7
7
7

M
M
M
M

A
A
A
A

2
2
4
6

2
6th/7th position
Rated short-time thermal current
Rated short-time
thermal current

Remark

Ith
kA
8
12.5
16
20
25
31.5
40
50
63

Not for Um = 36 kV
Not for Um = 24 kV and Um = 36 kV

Configuration example
Indoor support-type current transformer, block-type design
Maximum operating voltage Um = 12 kV
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-duration power-frequency withstand voltage Ud = 28 kV
Rated short-time thermal current Ith = 16 kA
Example for Order No.:
Order codes:

20

Siemens HG 24 2009

Order codes

4 M A

3
4
4
4
5
5
6
6
7

3
0
4
8
4
7
3
7
1

4 M A

n n n n n n n n n

n n n

See page 40

kV

See page 40

Ud

See page 40

Up

7 n n n n n n n n n n n n

page 39

Um

to

Rated short-duration
power-frequency
withstand voltage

See page 22

Rated lightning impulse


withstand voltage

4 M A

See page 21

Operating voltage

Position:

Order No.:

See page 21

5th position
Operating voltage (maximum value)

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n

n
n
n
n
n
n

n
n
n
n
n
n

n
n
n
n
n
n

n
n
n
n
n
n

n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n

Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Up = 75 kV, Ud = 28 kV, Ith = 16 kA)
Rated primary current IPN = 100 A

10 11 12

Order codes

n n n

See page 40

See page 40

See page 22
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

4 M A

13 14 15 16

7 n n n n n n n n n n n n

See page 40

page 39

63 kA

50 kA

n
n
n
n
n
n
n
n
n
n
n
n
n
n

Page 38

40 kA

31.5 kA

25 kA

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

Page 36

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

20 kA

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

Page 34

n Feasible (other combinations on


request)

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

Page 32

20
25
30
40
50
60
75
100
125
150
200
250
300
400
500
600

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

Page 30

2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x

16 kA

20
25
30
40
50
60
75
100
125
150
200
250
300
400
500
600
750
800
1000
1200
1250
1500
2000
2500

Page 28

Page 26

8 kA

IPN

12.5 kA

IPN

4 M A

Rated short-time
thermal current Ith

Page 24

Rated
primary current,
with primary
multi-ratio

Page 22

Rated
primary
current

Position:

Order No.:

to

8th/9th position
Rated primary current

E
F
G
H
J
K
L
M
N
P
Q
R
S
T
U
V
W
X
A
B
C
D
F
G
E
F
G
H
J
K
L
M
N
P
Q
R
S
T
U
V

7
2

0 M

Example for Order No.:

4 M A

0 M n n n n n n n

Order codes:
Siemens HG 24 2009

21

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

8 kA

0.5

FS5

FS5

FS5

5P

10

10P

10

5P

10

10P

10

100 x IPN

FS5

150 x IPN

0.5

200 x IPN

10

300 x IPN

10P

n n n n n n n n n

10 11 12

13 14 15 16

0
1
2
3
4

400 x IPN

10

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN

500 x IPN

5P

600 x IPN

FS5

800 x IPN

1000 x IPN

FS5

7 n 3

Thermal strength
VA rating

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Factor

FS10

Class

Factor

0.2

2nd core
VA rating

Class

Thermal
strength

100 A 125 A 150 A 200 A 250 A


300 A 400 A 500 A 600 A 750 A
1000 A 1200 A 1250 A 1500 A 2000 A 2500 A
60 A 75 A
40 A 50 A
30 A
20 A 25 A

1st core

s. p. 40

At rated primary current IPN

4 M A

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n
n n
n n
n
n n
n n

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

n n n
n n n

n n n
n n n
n n
n

n n n
n n n
n n
n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

0 A

0 A n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 8 kA, IPN = 100 A)
Thermal strength 100 x IPN
1st core class 5P; instrument security factor 10; rating 30 VA
2nd core without

4 M A

Order codes:
Siemens HG 24 2009

0 M
0

Example for Order No.:

22

4 M A

0 M L

Order codes

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n n n

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

8 kA with primary multi-ratio

FS5

FS5

FS5

10

10P

10

5P

10

10P

10

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
o

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n
n n
n n
n
n n

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

n Feasible (other combinations on request)

100 x IPN

0.5

5P

150 x IPN

FS5

200 x IPN

0.5

300 x IPN

10

n n n n n n n n n

10 11 12

13 14 15 16

Order codes

n n n

0
1
2
3
4

400 x IPN

10P

500 x IPN

10

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN

600 x IPN

5P

800 x IPN

FS5

1000 x IPN

7 n 3

Thermal strength
VA rating

FS5

Factor

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Class

Factor
FS10

2nd core
VA rating

Class
0.2

Thermal
strength

2x 100 A 2x 125 A 2x 150 A 2x 200 A 2x 250 A


2x 300 A 2x 400 A 2x 500 A 2x 600 A
2x 60 A 2x 75 A
2x 40 A 2x 50 A
2x 30 A
2x 20 A 2x 25 A

1st core

s. p. 40

At rated primary current IPN

4 M A

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n n n
n

n n n
n n n
n n
n
o
n n n
n n n
n n
n
o

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

4 Q

4 Q n n

o Not for 2x 40 A

Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 8 kA, IPN = 2x 100 A)
Thermal strength 100 x IPN
1st core class 1; instrument security factor FS5; rating 15 VA
2nd core class 10P; accuracy limit factor 10; rating 30 VA

4 M A

7
2

3 M
0
H 3

Example for Order No.:

4 M A

3 M H 3

Order codes:
Siemens HG 24 2009

23

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

12.5 kA

0.5

FS5

FS5

FS5

5P

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

100 x IPN

FS5

150 x IPN

0.5

n
n

200 x IPN

10

300 x IPN

10P

n
n

400 x IPN

10

n n n n n n n n n

10 11 12

13 14 15 16

0
1
2
3
4
5
7

500 x IPN

5P

n
n

600 x IPN

FS5

800 x IPN

1000 x IPN

FS5

Thermal strength
VA rating

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Factor

FS10

Class

Factor

0.2

7 n 4

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
500 x IPN
800 x IPN

2nd core
VA rating

Class

Thermal
strength

125 A 150 A 200 A 250 A 300 A


400 A 500 A 600 A 750 A 1000 A
1200 A 1250 A 1500 A 2000 A 2500 A
100 A
75 A
50 A 60 A
40 A
25 A 30 A
20 A

1st core

s. p. 40

At rated primary current IPN

4 M A

n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n n
n n n
n n n
n
n n n
n n n

n n n n
n n n n
n n

n n n
n n n
n n
n n

n
n
n
n
n

n n n
n n n
n n
n n
n

n
n
n
n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

0 A

0 A n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 12.5 kA, IPN = 100 A)
Thermal strength 150 x IPN
1st core class 10P; instrument security factor 10; rating 5 VA
2nd core without

4 M A

0 M

Q 1

Order codes:
Siemens HG 24 2009

Example for Order No.:

24

4 M A

0 M Q 1

Order codes

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n n n

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

12.5 kA with primary multi-ratio

FS5

FS5

FS5

n
n
n
n
n

5P

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

100 x IPN

0.5

n
n

150 x IPN

FS5

n
n

200 x IPN

0.5

300 x IPN

10

n n n n n n n n n

10 11 12

13 14 15 16

Order codes

n n n

0
1
2
3
4
5
7

400 x IPN

10P

500 x IPN

10

600 x IPN

5P

800 x IPN

FS5

1000 x IPN

Thermal strength
VA rating

FS5

Factor

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Class

Factor
FS10

7 n 4

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
500 x IPN
800 x IPN

2nd core
VA rating

Class
0.2

Thermal
strength

2x 125 A 2x 150 A 2x 200 A 2x 250 A


2x 300 A 2x 400 A 2x 500 A 2x 600 A
2x 100 A
2x 75 A
2x 50 A 2x 60 A
2x 40 A
2x 25 A 2x 30 A
2x 20 A

1st core

s. p. 40

At rated primary current IPN

4 M A

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n

n n n
n n n
n n n

n n n
n

n n n n
n n
n

n n n
n n n
n n
n

n
n
n
n
n

n n n
n n n
n n
n n

n
n
n
n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

3 Q

3 Q n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 12.5 kA, IPN = 2x 100 A)
Thermal strength 150 x IPN
1st core class 0.5; instrument security factor FS5; rating 15 VA
2nd core class 10P; accuracy limit factor 10; rating 15 VA

4 M A

7
2

3 M
1

Example for Order No.:

4 M A

3 M E

Order codes:
Siemens HG 24 2009

25

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

16 kA

0.5

FS5

FS5

FS5

5P

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

n n
n

n n

n n n

n n n

100 x IPN

FS5

n n n
n n n
n

150 x IPN

0.5

n n n
n n n
n
n n n
n

200 x IPN

10

n n n n n n n n n

10 11 12

13 14 15 16

0
1
2
3
4
6
7
8

300 x IPN

10P

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
600 x IPN
800 x IPN
1000 x IPN

400 x IPN

10

n n n
n n

500 x IPN

5P

600 x IPN

FS5

800 x IPN

1000 x IPN

FS5

7 n 4

Thermal strength
VA rating

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Factor

FS10

Class

Factor

0.2

2nd core
VA rating

Class

Thermal
strength

200 A 250 A 300 A 400 A 500 A 600 A 750 A 800 A


1000 A 1200 A 1250 A 1500 A 2000 A 2500 A
125 A 150 A
100 A
60 A 75 A
40 A 50 A
30 A
25 A
20 A
1st core

s. p. 40

At rated primary current IPN

4 M A

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n
n n
n n
n
n n
n n

n n n
n n n
n n
n
n n n
n n n
n n
n n
n
n
n n n
n n n
n n
n n
n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

L n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 16 kA, IPN = 100 A)
Thermal strength 200 x IPN
1st core class 0.5; instrument security factor FS5; rating 10 VA
2nd core class 5P; accuracy limit factor 10; rating 10 VA

4 M A

Order codes:
Siemens HG 24 2009

0 M
2

Example for Order No.:

26

4 M A

0 M E

Order codes

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n n n

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

16 kA with primary multi-ratio

FS5

FS5

FS5

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

100 x IPN

0.5

5P

150 x IPN

FS5

n n n
n

200 x IPN

0.5

n n n
n n n

300 x IPN

10

n n n n n n n n n

10 11 12

13 14 15 16

Order codes

n n n

0
1
2
3
4
6
7
8

400 x IPN

10P

n n n
n

500 x IPN

10

600 x IPN

5P

800 x IPN

FS5

1000 x IPN

Thermal strength
VA rating

FS5

Factor

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Class

Factor
FS10

7 n 4

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
600 x IPN
800 x IPN
1000 x IPN

2nd core
VA rating

Class
0.2

Thermal
strength

2x 200 A 2x 250 A 2x 300 A 2x 400 A


2x 500 A 2x 600 A
2x 125 A 2x 150 A
2x 100 A
2x 60 A 2x 75 A
2x 40 A 2x 50 A
2x 30 A
2x 25 A
2x 20 A
1st core

s. p. 40

At rated primary current IPN

4 M A

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n n
n n n
n

n n
n n
n n

n n
n

n n n
n n
n

n n n

n n n
n n n
n n
n n
n

n n n

n n n
n n n
n n
n n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

0 A

0 A n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 16 kA, IPN = 2x 100 A)
Thermal strength 200 x IPN
1st core class 0.5; instrument security factor FS5; rating 10 VA
2nd core without

4 M A

7
2

3 M
2

Example for Order No.:

4 M A

3 M E

Order codes:
Siemens HG 24 2009

27

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

20 kA

0.5

FS5

FS5

FS5

n n
n n

5P

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

100 x IPN

FS5

n n

150 x IPN

0.5

n n
n n

n n
n
n n
n n
n n
n n
n n
n n
n n
n n
n

200 x IPN

10

n n n n n n n n n

10 11 12

13 14 15 16

0
1
2
3
4
5
7
8

300 x IPN

10P

n n
n

400 x IPN

10

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
500 x IPN
800 x IPN
1000 x IPN

500 x IPN

5P

600 x IPN

FS5

800 x IPN

1000 x IPN

FS5

7 n 4

Thermal strength
VA rating

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Factor

FS10

Class

Factor

0.2

2nd core
VA rating

Class

Thermal
strength

200 A 250 A 300 A 400 A 500 A 600 A 750 A


1000 A 1200 A 1250 A 1500 A 2000 A 2500 A
150 A
100 A 125 A
75 A
50 A 60 A
40 A
30 A
25 A
1st core

s. p. 40

At rated primary current IPN

4 M A

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n n
n n n
n n n
n
n n n
n n

n n n n n
n n n n
n n

n n

n n n n
n n n
n n
n n

n
n
n
n
n

n n

n n n
n n n
n
n

n
n
n
n
n
n

n
n
n
n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

L n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 20 kA, IPN = 100 A)
Thermal strength 200 x IPN
1st core class 1; instrument security factor FS5; rating 10 VA
2nd core class 5P; accuracy limit factor 10; rating 15 VA

4 M A

0 M

H 2

Order codes:
Siemens HG 24 2009

Example for Order No.:

28

4 M A

0 M H 2

Order codes

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n n n

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

20 kA with primary multi-ratio

FS5

FS5

FS5

n
n
n
n
n

n n

n n
n

5P

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

100 x IPN

0.5

n n
n n

150 x IPN

FS5

n
n

200 x IPN

0.5

n n

300 x IPN

10

n n n n n n n n n

10 11 12

13 14 15 16

Order codes

n n n

0
1
2
3
4
5
7
8

400 x IPN

10P

500 x IPN

10

600 x IPN

5P

800 x IPN

FS5

1000 x IPN

Thermal strength
VA rating

FS5

Factor

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Class

Factor
FS10

7 n 4

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
500 x IPN
800 x IPN
1000 x IPN

2nd core
VA rating

Class
0.2

Thermal
strength

2x 200 A 2x 250 A 2x 300 A 2x 400 A


2x 500 A 2x 600 A
2x 150 A
2x 100 A 2x 125 A
2x 75 A
2x 50 A 2x 60 A
2x 40 A
2x 30 A
2x 25 A
1st core

s. p. 40

At rated primary current IPN

4 M A

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n n
n n n
n n n
n n n
n

n n n n
n
n n
n
n n

n n n n
n n n
n n
n n

n n

n n n n
n n n
n n
n n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

1 Q

1 Q n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 20 kA, IPN = 2x 100 A)
Thermal strength 200 x IPN
1st core class 1; instrument security factor FS5; rating 5 VA
2nd core class 10P; accuracy limit factor 10; rating 5 VA

4 M A

7
2

3 M
2
H 1

Example for Order No.:

4 M A

3 M H 1

Order codes:
Siemens HG 24 2009

29

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

25 kA

0.5

FS5

FS5

FS5

5P

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

100 x IPN

FS5

n
n

150 x IPN

0.5

n n
n
n n
n n
n n
n n
n n
n n
n n
n n
n

200 x IPN

10

n n n n n n n n n

10 11 12

13 14 15 16

0
1
2
3
4
5
7

300 x IPN

10P

n
n

400 x IPN

10

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
500 x IPN
800 x IPN

500 x IPN

5P

600 x IPN

FS5

800 x IPN

1000 x IPN

FS5

7 n 5

Thermal strength
VA rating

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Factor

FS10

Class

Factor

0.2

2nd core
VA rating

Class

Thermal
strength

250 A 300 A 400 A 500 A 600 A 750 A


1000 A 1200 A 1250 A 1500 A 2000 A 2500 A
200 A
125 A 150 A
100 A
75 A
50 A 60 A
40 A

1st core

s. p. 40

At rated primary current IPN

4 M A

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n n
n n n
n n n
n
n n n
n n

n n n n n
n n n n
n n

n n n n
n n n
n n
n n

n
n
n
n
n

n n n
n n n
n
n

n
n
n
n
n
n

n
n
n
n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

0 A

0 A n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 25 kA, IPN = 100 A)
Thermal strength 300 x IPN
1st core class 10P; instrument security factor 10; rating 15 VA
2nd core without

4 M A

0 M

Q 3

Order codes:
Siemens HG 24 2009

Example for Order No.:

30

4 M A

0 M Q 3

Order codes

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n n n

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

25 kA with primary multi-ratio


Thermal
strength

2x 250 A 2x 300 A 2x 400 A 2x 500 A 2x 600 A


2x 200 A
2x 125 A 2x 150 A
2x 100 A
2x 75 A
2x 50 A 2x 60 A
2x 40 A

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
500 x IPN
800 x IPN

0.5

FS5

FS5

FS5

5P

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

100 x IPN

FS5

150 x IPN

0.5

n n
n
n n
n n
n n
n n
n n
n n
n n
n n
n

200 x IPN

10

7 n 5

n n n n n n n n n

10 11 12

13 14 15 16

Order codes

n n n

0
1
2
3
4
5
7

300 x IPN

10P

400 x IPN

10

n
n

500 x IPN

5P

600 x IPN

FS5

800 x IPN

1000 x IPN

FS5

Thermal strength
VA rating

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Factor

FS10

Class

Factor

0.2

2nd core
VA rating

Class

1st core

s. p. 40

At rated primary current IPN

4 M A

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n n
n n n
n n n
n n n
n

n n n n
n n n
n

n n n n
n n n
n n
n n

n n n
n n n
n
n

n
n
n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

0 A

0 A n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 25 kA, IPN = 2x 100 A)
Thermal strength 300 x IPN
1st core class 10P; instrument security factor 10; rating 15 VA
2nd core without

4 M A

7
2

3 M
3
Q 3

Example for Order No.:

4 M A

3 M Q 3

Order codes:
Siemens HG 24 2009

31

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

31.5 kA

0.5

FS5

FS5

FS5

5P

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

100 x IPN

FS5

150 x IPN

0.5

200 x IPN

10

n n n

n n
n
n n
n n
n n
n n
n n
n n
n n
n n
n

300 x IPN

10P

n n n
n n

400 x IPN

10

n n n
n n

500 x IPN

5P

n n n n n n n n n

10 11 12

13 14 15 16

0
1
2
3
4
5
6
7
8

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
500 x IPN
600 x IPN
800 x IPN
1000 x IPN

600 x IPN

FS5

800 x IPN

1000 x IPN

FS5

7 n 5

Thermal strength
VA rating

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Factor

FS10

Class

Factor

0.2

2nd core
VA rating

Class

Thermal
strength

400 A 500 A 600 A 750 A 1000 A 1200 A


1250 A 1500 A 2000 A 2500 A
250 A 300 A
200 A
125 A 150 A
100 A
75 A
60 A
50 A
40 A
1st core

s. p. 40

At rated primary current IPN

4 M A

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n n n n n
n n n n n n
n n n
n
n n n n n
n n

n n n n n n n
n n n n n
n n
n n n n n n n
n n n
n n
n n

n
n
n
n
n

n n n n n n
n n n
n
n

n
n
n
n
n
n

n
n
n
n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

0 A

0 A n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 31.5 kA, IPN = 100 A)
Thermal strength 400 x IPN
1st core class 0.2; instrument security factor FS10; rating 15 VA
2nd core without

4 M A

Order codes:
Siemens HG 24 2009

0 M
4

Example for Order No.:

32

4 M A

0 M C

Order codes

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n n n

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

31.5 kA with primary multi-ratio

FS5

FS5

FS5

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

n n n

n n n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n n n
n n n
n

n n n n n n
n n n
n
n

n
n
n
n

n n n n n n
n n n
n
n

n
n
n
n
n

100 x IPN

0.5

5P

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

150 x IPN

FS5

n
n
n
n
n
n
n
n
n
n
n

200 x IPN

0.5

n n n n
n n n
n n

300 x IPN

10

n n

n n
n
n n
n n
n n
n n
n n
n n
n n
n n
n

400 x IPN

10P

n n
n n

500 x IPN

10

n n
n

600 x IPN

5P

800 x IPN

FS5

1000 x IPN

n n n n n n n n n

10 11 12

13 14 15 16

Order codes

n n n

0
1
2
3
4
5
6
7
8

Thermal strength
VA rating

FS5

Factor

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Class

Factor
FS10

7 n 5

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
500 x IPN
600 x IPN
800 x IPN
1000 x IPN

2nd core
VA rating

Class
0.2

Thermal
strength

2x 300 A 2x 400 A 2x 500 A 2x 600 A


250 A 300 A
200 A
125 A 150 A
100 A
75 A
60 A
50 A
40 A
1st core

s. p. 40

At rated primary current IPN

4 M A

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

1 Q

1 Q n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 31.5 kA, IPN = 2x 100 A)
Thermal strength 400 x IPN
1st core class 0.5; instrument security factor FS5; rating 5 VA
2nd core class 10P; accuracy limit factor 10; rating 5 VA

4 M A

7
2

3 M
4

Example for Order No.:

4 M A

3 M E

Order codes:
Siemens HG 24 2009

33

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

40 kA

0.5

FS5

FS5

FS5

n n n
n n
n
5P

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

n n n

100 x IPN

FS5

n n n

150 x IPN

0.5

n n n
n n n

200 x IPN

10

n n n
n n n

300 x IPN

10P

400 x IPN

10

500 x IPN

5P

600 x IPN

FS5

800 x IPN

1000 x IPN

FS5

n n n n n n n n n

10 11 12

13 14 15 16

0
1
2
3
4
6
7
8

Thermal strength
VA rating

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Factor

FS10

Class

Factor

0.2

7 n 6

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
600 x IPN
800 x IPN
1000 x IPN

2nd core
VA rating

Class

Thermal
strength

400 A 500 A 600 A 750 A 1000 A


1200 A 1250 A 1500 A 2000 A 2500 A
300 A
200 A 250 A
150 A
100 A 125 A
75 A
60 A
50 A

1st core

s. p. 40

At rated primary current IPN

4 M A

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n
n n
n n
n
n n
n n

n n n

n n n n
n n n n
n n

n n n

n n n
n n n
n n
n n

n
n
n
n
n

n n n

n n n
n n n
n n
n n
n

n
n
n
n
n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

L n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 40 kA, IPN = 100 A)
Thermal strength 400 x IPN
1st core class 1; instrument security factor FS5; rating 5 VA
2nd core class 5P; accuracy limit factor 10; rating 5 VA

4 M A

Order codes:
Siemens HG 24 2009

0 M
4

Example for Order No.:

34

4 M A

0 M E

Order codes

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n n n

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

40 kA with primary multi-ratio


Thermal
strength

2x 400 A 2x 500 2x 600 A


2x 300 A
2x 200 A 2x 250 A
2x 150 A
2x 100 A 2x 125 A
2x 75 A
2x 60 A
2x 50 A

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
600 x IPN
800 x IPN
1000 x IPN

FS5

FS5

FS5

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

n n

100 x IPN

0.5

5P

150 x IPN

FS5

200 x IPN

0.5

n n n
n n
n

300 x IPN

10

n n n
n n
n
n n n
n n n
n
n n n
n

400 x IPN

10P

500 x IPN

10

600 x IPN

5P

800 x IPN

FS5

1000 x IPN

7 n 6

n n n n n n n n n

10 11 12

13 14 15 16

Order codes

n n n

0
1
2
3
4
6
7
8

Thermal strength
VA rating

FS5

Factor

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Class

Factor
FS10

VA rating

Class
0.2

2nd core

s. p. 40

At rated primary current IPN

1st core

4 M A

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n
n n
n n
n
n n
n

n n

n n n
n n n
n

n n n

n n n
n n n
n n
n n

n n n

n n n
n n n
n n
n n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

0 A

0 A n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 40 kA, IPN = 2x 100 A)
Thermal strength 400 x IPN
1st core class 0.2; instrument security factor FS10; rating 10 VA
2nd core without

4 M A

7
2

3 M
4

Example for Order No.:

4 M A

3 M C

Order codes:
Siemens HG 24 2009

35

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

50 kA

0.5

FS5

FS5

FS5

5P

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

100 x IPN

FS5

150 x IPN

0.5

n n
n

200 x IPN

10

n n

n n
n
n n
n n
n n
n n
n n
n n
n n
n n
n

300 x IPN

10P

n n n n n n n n n

10 11 12

13 14 15 16

0
1
2
3
4
5
7
8

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
500 x IPN
800 x IPN
1000 x IPN

400 x IPN

10

n n
n n

500 x IPN

5P

n n
n

600 x IPN

FS5

800 x IPN

1000 x IPN

FS5

7 n 6

Thermal strength
VA rating

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

Factor

FS10

Class

Factor

0.2

2nd core
VA rating

Class

Thermal
strength

500 A 600 A 750 A 1000 A 1200 A 1250 A 1500 A


2000 A 2500 A
400 A
250 A 300 A
200 A
125 A 150 A
100 A
75 A
60 A

1st core

s. p. 40

At rated primary current IPN

4 M A

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n n
n n n
n n n
n
n n n
n n

n n n n n
n n n n
n n n

n n n n
n n n
n n
n n

n
n
n
n
n

n n n
n n n
n
n

n
n
n
n
n
n

n
n
n
n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

L n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 50 kA, IPN = 100 A)
Thermal strength 500 x IPN
1st core class 0.5; instrument security factor FS5; rating 5 VA
2nd core class 5P; accuracy limit factor 10; rating 5 VA

4 M A

Order codes:
Siemens HG 24 2009

0 M
5

Example for Order No.:

36

4 M A

0 M E

Order codes

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n n n

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

50 kA with primary multi-ratio

FS5

FS5

10

5P

10

10P

10

100 x IPN

10P

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

150 x IPN

FS5

10

200 x IPN

0.5

5P

n n
n
n n
n n
n n
n n
n n
n n
n n
n n
n

300 x IPN

FS5

n n

400 x IPN

0.5

n n
n n

500 x IPN

10

n n
n

600 x IPN

10P

800 x IPN

10

1000 x IPN

5P

n n n n n n n n n

10 11 12

13 14 15 16

Order codes

n n n

0
1
2
3
4
5
7
8

Thermal strength
VA rating

FS5

Factor

Class

Factor
FS5

VA rating

Class
0.5

2nd core

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

7 n 6

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
500 x IPN
800 x IPN
1000 x IPN

1st core

FS10

Thermal
strength

2x 500 A 2x 600 A
2x 400 A
2x 250 A 2x 300 A
2x 200 A
2x 125 A 2x 150 A
2x 100 A
2x 75 A
2x 50 A 2x 60 A

0.2

s. p. 40

At rated primary current IPN

4 M A

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n

n n n
n n n
n n

n n n
n n

n n n n
n n n
n

n n n n
n n n
n
n

n n n
n n n
n
n

n
n
n
n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

L n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 50 kA, IPN = 2x 100 A)
Thermal strength 500 x IPN
1st core class 0.5; instrument security factor FS5; rating 5 VA
2nd core class 5P; accuracy limit factor 10; rating 5 VA

4 M A

7
2

3 M
5

Example for Order No.:

4 M A

3 M E

Order codes:
Siemens HG 24 2009

37

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

63 kA

300 A
150 A

FS5

0.5

FS5

FS5

FS5

5P

10

10P

10

5P

10

10P

10

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

100 x IPN

0.5

n n
n

150 x IPN

10

n n

n n
n
n n
n n
n n
n n
n n
n n
n n
n n
n

200 x IPN

10P

n n n n n n n n n

10 11 12

13 14 15 16

0
1
2
3
4
5
7
8

100 x IPN
150 x IPN
200 x IPN
300 x IPN
400 x IPN
500 x IPN
800 x IPN
1000 x IPN

300 x IPN

10

400 x IPN

5P

n n
n n

500 x IPN

FS5

n n
n

600 x IPN

800 x IPN

FS5

1000 x IPN

0.5

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

7 n 7

Thermal strength
VA rating

FS10

Class

0.2

2nd core
VA rating

Factor

Class

1st core

Thermal
strength

1000 A 1200 A 1250 A 1500 A 2000 A 2500 A


600 A

Factor

750 A
500 A
400 A
250 A
200 A
125 A
100 A
75 A

s. p. 40

At rated primary current IPN

4 M A

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n n
n n n
n n n
n
n n n
n n

n n n n n
n n n n
n n

n n n n n
n n n n
n n n n
n n n
n

n n n
n n n
n n
n

n
n
n
n
n

n
n
n
n
n
n

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

0 A

0 A n n

n Feasible (other combinations on request)


Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 63 kA, IPN = 100 A)
Thermal strength 800 x IPN
1st core class 0.5; instrument security factor FS5; rating 15 VA
2nd core without

4 M A

Order codes:
Siemens HG 24 2009

0 M
7

Example for Order No.:

38

4 M A

0 M E

Order codes

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

n n n

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

63 kA with primary multi-ratio

FS5

FS5

n n n n n n n n n

10 11 12

10P

10

5P

10

10P

10

13 14 15 16

Order codes

n n n

1
2
3
4
5
7
8

5
10
15
30
5
10
15
30
5
10
15
15
30
30
5
10
15
15
30
30

n Feasible (other combinations on request)

n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n n
n n n
n n n
n
n n n
n n

n n n n
n n n
n

n n n n
n n n
n n n
n n

n n n
n n n
n n
n

n
n
n
n
n

100 x IPN

10

150 x IPN

FS5

5P

200 x IPN

0.5

n n
n

n n
n
n n
n n
n n
n n
n n
n
n n
n n
o n

300 x IPN

FS5

n n

400 x IPN

0.5

n n
n n

500 x IPN

10

n n
n

600 x IPN

10P

800 x IPN

10

1000 x IPN

5P

Thermal strength
VA rating

FS5

Factor

Class

Factor
FS5

VA rating

Class
0.5

2nd core

10
15
10
15
30
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
15
30
5
10
10
15
15
30
5
10
10
15
15
30

7 n 7

150 x IPN
200 x IPN
300 x IPN
400 x IPN
500 x IPN
800 x IPN
1000 x IPN

1st core

FS10

Thermal
strength

2x 500 A 2x 600 A
2x 400 A
2x 250 A 2x 300 A
2x 200 A
2x 125 A 2x 150 A
2x 100 A
2x 75 A

0.2

s. p. 40

At rated primary current IPN

4 M A

s. p. 40

Position:

Order No.:

s. p. 40

10th to 14th position


Core versions

C
C
E
E
E
H
H
H
L
L
L
L
Q
Q
Q
Q
E
E
E
E
E
E
E
E
H
H
H
H
H
H
H
H
H
H
H
H

2
3
2
3
4
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
2
3
3
4
1
2
2
3
3
4

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
2
3
4
1
2
3
4
1
2
3
3
4
4
1
2
3
3
4
4

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
Q
Q
Q
Q
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

1 Q

1 Q n n

o Not for 2x 125 A

Configuration example
Indoor support-type current transformer, block-type design
(Um = 12 kV, Ith = 63 kA, IPN = 2x 100 A)
Thermal strength 800 x IPN
1st core class 0.5; instrument security factor FS5; rating 5 VA
2nd core class 10P; accuracy limit factor 10; rating 5 VA

4 M A

7
2

3 M
7

Example for Order No.:

4 M A

3 M E

Order codes:
Siemens HG 24 2009

39

4M Protective and Measuring Transformers

Equipment Selection
4MA7 indoor support-type current transformer, block-type design

15th position
Rated secondary current

Position:

Order No.:

Rated current for 1st core

Rated current for 2nd core

1A
5A
1A
5A
1A
5A

Without 2nd core


Without 2nd core
1A
5A
5A
1A

4 M A

10 11 12

13 14 15 16

Order codes

7 n n n n n n n n n n n n

n n n

0 A A
0 A B
C
D
E
F

16th position
Additional features

Options

50 Hz, VDE marking


50 Hz, IEC marking
50 Hz, VDE marking with approval 1)
60 Hz, IEC marking
Further not listed special versions (only after consultation with the
order processing department in the Switchgear Factory Berlin).
Information additionally in clear text.

0
1
2
6
9

1) Only for class 0.2 and 0.5

Special versions
Options

With routine test certificate in German/English


With capacitive layer for voltage detecting system

6 kV
10 kV
15 kV

Differential earth-fault balance in protection core


Other special versions on request

Configuration example
Indoor support-type current transformer, block-type design
Maximum operating voltage Um = 12 kV
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-duration power-frequency withstand voltage Ud = 28 kV
Rated short-time thermal current Ith = 63 kA
Rated primary current IPN = 2x 100 A
Thermal strength 800 x IPN
1st core class 0.5; instrument security factor FS5; rating 5 VA
2nd core class 10P; accuracy limit factor 10; rating 5 VA
Rated secondary current 1st core 1A; 2nd core 5A
Power frequency 50 Hz; marking according to IEC
With routine test certificate in German/English
With capacitive layer for voltage detecting system 10 kV
Example for Order No.:
Order codes:

40

Siemens HG 24 2009

4 M A

Z
Z
Z
Z
Z

A
C
C
C
D

1
0
1
1
1

0
6
0
5
0

Z
Z

A
C

1
1

0
0

2
7

3 M
7
E

1 Q
E
1

4 M A

3 M E

1 Q E

4M Protective and Measuring Transformers

Equipment Selection
4MB1 indoor support-type current transformer, single-turn design

4MB1 indoor support-type current


transformer, single-turn design
3

Order codes

4 M B
4 M B
4 M B

1
1
1

n n n

See page 43

28
38
50

See page 43

75
95
128

See page 43

Ud
kV

See page 42

Up
kV

13 14 15 16

See page 42

Um

10 11 12

1 n n n n n n n n n n n n

Rated short-duration
power-frequency
withstand voltage

kV
12
17.5
24

See page 42

Rated lightning
impulse withstand
voltage

4 M B

See page 42

Operating voltage

Position:

Order No.:

See page 42

5th position
Operating voltage (maximum value)

2
3
4

6th/7th position
Rated short-time thermal current

Rated short-time thermal current


Ith
kA
150
200
250
300
500

7
8
8
8
8

8
2
4
5
8

8th/9th position
Rated primary current

1500
2000
2500
3000
4000
5000
6000

500 kA

300 kA

150 kA

IN

Rated
short-time
thermal current
250 kA

Remark

200 kA

Rated primary
current

1 D
1 F
1 G
1 H
1 J
1 K
1 L

n
n
n
n
n
n

Only 4MB13
Only 4MB13

n Feasible (other combinations on request)

Configuration example
Indoor support-type current transformer, single-turn design
Maximum operating voltage Um = 24 kV
Rated lightning impulse withstand voltage Up = 125 kV
Rated short-duration power-frequency withstand voltage Ud = 50 kV
Rated short-time thermal current Ith = 300 kA
Rated primary current IPN = 3000 A
Example for Order No.:

4 M B

4
8

1 H

4 M B

1 H n n n n n n n

Order codes:
Siemens HG 24 2009

41

4M Protective and Measuring Transformers

Equipment Selection
4MB1 indoor support-type current transformer, single-turn design

0.5

FS10

FS10

0.5

FS10

FS10

5P

10

5P

10

10P

10

10P

10

15
30
60
15
30
60
15
30
60
15
30
60

6000 A

10

5000 A

10P

4000 A

10

3000 A

5P

2500 A

FS10

10 11 12

13 14 15 16

2000 A

100 x IPN

1500 A

FS10

n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n n n n n
n n n n n
n n n n n
n n n n n
n n n n n
n n n n n

C
C
F
F
F
J
J
J
L
L
Q
Q
F
F
F
J
J
J
F
F
F
J
J
J

3
4
3
4
6
3
4
6
4
6
4
6
3
4
6
3
4
6
3
4
6
3
4
6

0
0
0
0
0
0
0
0
0
0
0
0
3
4
6
3
4
6
3
4
6
3
4
6

A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
L
L
Q
Q
Q
Q
Q
Q

L n n

n Feasible (other combinations on request)

Configuration example
Indoor support-type current transformer, single-turn design
(Um = 24 kV, Ith = 300 kA, IPN = 3000 A)
Thermal strength 100 x IPN
1st core class 0.5; instrument security factor FS10; rating 30 VA
2nd core class 5P; accuracy limit factor 10; rating 30 VA

4 M B

Siemens HG 24 2009

1 H
0

Order codes:

42

1
4

Example for Order No.:

4 M B

Order codes

1 n n n n n n n n n n n n

Rated primary current IPN


VA rating

0.5

15
30
15
30
60
15
30
60
30
60
30
60
15
30
30
15
30
60
15
30
60
15
30
60

Factor

FS10

Class

Factor

0.2

2nd core
VA rating

Class

Thermal
strength

1500 A 2000 A 2500 A 3000 A 4000 A


5000 A 6000 A

1st core

See page 43

At rated primary current IPN

4 M B

1 H F

See page 43

Position:

Order No.:

See page 43

10th to 14th position


Core versions

n n n

4M Protective and Measuring Transformers

Equipment Selection
4MB1 indoor support-type current transformer, single-turn design

15th position
Rated secondary current

Position:

Order No.:

Rated current for 1st core

Rated current for 2nd core

1A
5A
1A
5A
1A
5A

Without 2nd core


Without 2nd core
1A
5A
5A
1A

4 M B

10 11 12

13 14 15 16

Order codes

1 n n n n n n n n n n n n

n n n

0 A A
0 A B
C
D
E
F

16th position
Additional features

Options

50 Hz, VDE marking


50 Hz, IEC marking
50 Hz, VDE marking with approval 1)
60 Hz, IEC marking
Further not listed special versions (only after consultation with the
order processing department in the Switchgear Factory Berlin).
Information additionally in clear text.

0
1
2
6
9

1) Only for class 0.2 and 0.5

Special versions
Options

With routine test certificate in German/English


Other special versions on request

Configuration example
Indoor support-type current transformer, single-turn design
Maximum operating voltage Um = 24 kV
Rated lightning impulse withstand voltage Up = 125 kV
Rated short-duration power-frequency withstand voltage Ud = 50 kV
Rated short-time thermal current Ith = 300 kA
Rated primary current IPN = 3000 A
Thermal strength 100 x IPN
1st core class 0.5; instrument security factor FS10; rating 30 VA
2nd core class 5P; accuracy limit factor 10; rating 30 VA
Rated secondary current 1st core 5 A; 2nd core 5 A
Power frequency 60 Hz; marking according to IEC
Example for Order No.:

4 M B

4
8

1 H
0
F

L
D
6

4 M B

1 H F

D 6

Order codes:
Siemens HG 24 2009

43

4M Protective and Measuring Transformers

Equipment Selection
4MC2 indoor bushing-type current transformer, single-turn design

4MC2 indoor bushing-type current


transformer, single-turn design

28
50
70

2
2
2

2
4
6

6th to 9th position


Rated short-time thermal current/
Rated primary current
Rated
short-time
thermal current

Rated
primary current

Ith

IPN

kA

15
20
30
40
50
60
80
100
120
150
200
250
300

150
200
300
400
500
600
800
1000
1200
1500
2000
2500
3000

Configuration example
Indoor bushing-type current transformer, single-turn design
Maximum operating voltage Um = 36 kV
Rated lightning impulse withstand voltage Up = 170 kV
Rated short-duration power-frequency withstand voltage Ud = 70 kV
Rated short-time thermal current Ith = 50 kA
Rated primary current IPN = 500 A
Example for Order No.:
Order codes:

44

Siemens HG 24 2009

Order codes

4 M C

4
4
5
6
6
7
7
7
7
7
8
8
8

3
8
6
3
7
0
3
5
6
8
2
4
5

0
0
0
0
0
0
0
1
1
1
1
1
1

P
Q
S
T
U
V
X
A
B
D
F
G
H

0 U

0 U n n n n n n n

4 M C

See page 46

75
125
170

See page 46

12
24
36

See page 46

kV

See page 45

Ud

kV

See page 45

Up

kV

13 14 15 16

4 M C
4 M C
4 M C

Rated short-duration
power-frequency
withstand voltage

Um

10 11 12

2 n n n n n n n n n n n n
See page 45

Rated lightning
impulse withstand
voltage

4 M C

See page 45

Operating voltage

Position:

Order No.:

See page 45

5th position
Operating voltage (maximum value)

n n n

4M Protective and Measuring Transformers

Equipment Selection
4MC2 indoor bushing-type current transformer, single-turn design

0.5

FS5

0.5

FS10

FS5

FS10

8001500 A

FS10

10 11 12

13 14 15 16

n
n
n
n

n
n
n
n

n n
n n
n
n n
n
n
n n
n
n n
n n
n n
n n
n n
n
n
n n
n n
n
n
n
n
n n
n n
n
n

n n n
n n n

10P

10

10P

10

10P

10

10P

10

10P

10

Order codes

n n n

30
30
15
30
30
60
15
30
15
30
30
60
15
30

n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n

n n n
n n n
n n n
n n

20003000 A

0.2

n
n
n
n

200 A

FS10
10

300600 A

1
10P

150 A

FS10
FS5

Rated
primary
current IPN

VA rating

0.5
1

Factor

FS5

Class

Factor

0.5

10
15
15
30
15
15
30
15
15
30
60
10
15
15
15
30
30
15
15
15
15
30
30
15
15

2 n n n n n n n n n n n n

100 x IPN

2nd core

VA rating

Class

1st core

FS10

Thermal
strength

150 A 200 A 300 A 400 A 500 A 600 A 800 A


1000 A 1200 A 1500 A 2000 A 2500 A 3000 A

0.2

See page 46

At rated primary current IPN

4 M C

See page 46

Position:

Order No.:

See page 46

10th to 14th position


Core versions

C
C
E
E
F
H
H
J
Q
Q
Q
C
C
E
E
E
E
F
F
H
H
H
H
J
J

2
3
3
4
3
3
4
3
3
4
6
2
3
3
3
4
4
3
3
3
3
4
4
3
3

0
0
0
0
0
0
0
0
0
0
0
4
4
3
4
4
6
3
4
3
4
4
6
3
4

A
A
A
A
A
A
A
A
A
A
A
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q

4 Q

4 Q n n

n Feasible (other combinations on request)

Configuration example
Indoor bushing-type current transformer, single-turn design
(Um = 36 kV, Ith = 50 kA, IPN = 500 A)
Thermal strength 100 x IPN
1st core class 1; instrument security factor FS5; rating 30 VA
2nd core class 10P; accuracy limit factor 10; rating 30 VA

4 M C

2
6

0 U
0
H 4

Example for Order No.:

4 M C

0 U H 4

Order codes:
Siemens HG 24 2009

45

4M Protective and Measuring Transformers

Equipment Selection
4MC2 indoor bushing-type current transformer, single-turn design

15th position
Rated secondary current

Position:

Order No.:

Rated current for 1st core

Rated current for 2nd core

1A
5A
1A
5A
1A
5A

Without 2nd core


Without 2nd core
1A
5A
5A
1A

4 M C

10 11 12

13 14 15 16

Order codes

2 n n n n n n n n n n n n

n n n

0 A A
0 A B
C
D
E
F

16th position
Additional features

Options

50 Hz, VDE marking


50 Hz, IEC marking
50 Hz, VDE marking with approval 1)
60 Hz, IEC marking
Further not listed special versions (only after consultation with the
order processing department in the Switchgear Factory Berlin).
Information additionally in clear text.

0
1
2
6
9

1) Only for class 0.2 and 0.5

Special versions
Options

With routine test certificate in German/English


Other special versions on request

Configuration example
Indoor bushing-type current transformer, single-turn design
Maximum operating voltage Um = 36 kV
Rated lightning impulse withstand voltage Up = 170 kV
Rated short-duration power-frequency withstand voltage Ud = 70 kV
Rated short-time thermal current Ith = 50 kA
Rated primary current IPN = 500 A
Thermal strength 100 x IPN
1st core class 1; instrument security factor FS5; rating 30 VA
2nd core class 10P; accuracy limit factor 10; rating 30 VA
Rated secondary current 1st core 5 A; 2nd core 1 A
Power frequency 50 Hz; marking according to VDE
Example for Order No.:
Order codes:

46

Siemens HG 24 2009

4 M C

6
6

0 U
0
H 4

4 Q
F
0

4 M C

0 U H 4

4 Q F

4M Protective and Measuring Transformers

Equipment Selection
4MC3 indoor bar-primary bushing-type current transformer

4MC3 indoor bar-primary


bushing-type current transformer
2

28
50
70

Order codes

3
3
3

n n n

See page 49

75
125
170

See page 49

12
24
36

See page 49

kV

See page 48

Ud

kV

See page 48

Up

kV

13 14 15 16

4 M C
4 M C
4 M C

Rated short-duration
power-frequency
withstand voltage

Um

10 11 12

3 n n n n n n n n n n n n
See page 48

Rated lightning
impulse withstand
voltage

4 M C

See page 48

Operating voltage

Position:

Order No.:

See page 48

5th position
Operating voltage (maximum value)

2
4
6

6th to 9th position


Rated short-time thermal current/
Rated primary current
Rated
short-time
thermal current

Rated
primary current

Ith

IPN

kA

200
250
300
400
500
600
800
1000

2000
2500
3000
4000
5000
6000
8000
10000

Configuration example
Indoor bar-primary bushing-type current transformer
Maximum operating voltage Um = 12 kV
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-duration power-frequency withstand voltage Ud = 28 kV
Rated short-time thermal current Ith = 400 kA
Rated primary current IPN = 4000 A
Example for Order No.:

4 M C

8
8
8
8
8
7
7
7

2
4
5
7
8
0
2
3

1 F
1 G
1 H
1 J
1 K
1 L
1 N
1 P

4 M C

n n n n n n n

Order codes:
Siemens HG 24 2009

47

4M Protective and Measuring Transformers

Equipment Selection
4MC3 indoor bar-primary bushing-type current transformer

2000 A 2500 A 3000 A 4000 A 5000 A


6000 A 8000 A 10000 A

10 11 12

13 14 15 16

10P 10 30 10P 10 60
10P 20 60 10P 20 100
0.2 FS10 30 10P 10 30
30
30
1 FS10 60 10P 10 60 10P 20 100
60
60
100
60
60
100
1 FS10 60 10P 10 60 10P 20 100
60
60
100
60
60
100

40006000 A

30
60
10P 20 60
60
10P 20 100

800010000 A

10P 10

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

C
C
F
F
J
J
Q
Q
S
S
F
F
F
F
J
Q
S
S
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y

3
4
3
4
4
6
4
6
6
8
3
3
3
4
6
6
6
8
0
0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0
0
4
6
6
6
8
8
8
8
0
0
0
0
1
1
1
1
1
1

A
A
A
A
A
A
A
A
A
A
Q
Q
S
S
S
S
S
S
A
B
C
D
A
B
C
D
E
F

0 D

0 D n n

n Feasible (other combinations on request)

Configuration example
Indoor bar-primary bushing-type current transformer
(Um = 12 kV, Ith = 400 kA, IPN = 4000 A)
Thermal strength 100 x IPN
1st core class 0.5; instrument security factor FS10; rating 15 VA
2nd core class 0.2; instrument security factor FS10; rating 30 VA
3rd core class 10P; accuracy limit factor 10; rating 30 VA
Example for Order No.:
Order codes:

48

Siemens HG 24 2009

4 M C

3
2

J
0

4 M C

Order codes

See page 49

3 n n n n n n n n n n n n

Rated
primary
current
IPN

VA rating

Factor

Class

4th core

VA rating

Factor

Class

3rd core

VA rating

Factor

100 x IPN

20003000 A

0.2 FS10 15
30
0.5 FS10 15
30
1 FS10 30
60
10P 10 30
60
10P 20 60
100
0.5 FS10 15
15
15
30
1 FS10 60
10P 10 60
10P 20 60
100
0.5 FS10 15
1 FS10 30
0.2 FS10 15
0.5 FS10 15
0.2 FS10 30
0.5 FS10 30
1 FS10 30
0.2 FS10 30
0.5 FS10 30
1 FS10 30

Class

2nd core

VA rating

Factor

Class

Thermal
strength

At rated primary current IPN

1st core

4 M C

See page 49

Position:

Order No.:

See page 49

10th to 14th position


Core versions

n n n

4M Protective and Measuring Transformers

Equipment Selection
4MC3 indoor bar-primary bushing-type current transformer

15th position
Rated secondary current
Rated current
for 1st core

Position:

Order No.:

Rated current
for 2nd core

Rated current
for 3rd core

Rated current
for 4th core

Without
Without
1A
5A
5A
1A
1A
5A
1A
5A

Without
Without
Without
Without
Without
Without
1A
5A
1A
5A

Without
Without
Without
Without
Without
Without
Without
Without
1A
5A

1A
5A
1A
5A
1A
5A
1A
5A
1A
5A

4 M C

10 11 12

13 14 15 16

Order codes

3 n n n n n n n n n n n n

n n n

0 A A
0 A B
C
D
E
F
G
H
J
K

16th position
Additional features

Options
50 Hz, VDE marking
50 Hz, IEC marking
50 Hz, VDE marking with approval 1)
60 Hz, IEC marking
Further not listed special versions (only after consultation with the
order processing department in the Switchgear Factory Berlin).
Information additionally in clear text.

0
1
2
6
9

1) Only for class 0.2 and 0.5

Special versions
Options
With routine test certificate in German/English
Size (for specification see the following pages)

11
12
21
22
31
32
41
42
51
52
61
62
72
73

Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z
Z

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A

1
1
1
2
2
3
3
4
4
5
5
6
6
7
7

0
1
2
1
2
1
2
1
2
1
2
1
2
2
3

Other special versions on request


Configuration example
Indoor bar-primary bushing-type current transformer
Maximum operating voltage Um = 12 kV
Rated lightning impulse withstand voltage Up = 75 kV
Rated short-duration power-frequency withstand voltage Ud = 28 kV
Rated short-time thermal current Ith = 400 kA
Rated primary current IPN = 4000 A
Thermal strength 100 x IPN
1st core class 0.5; instrument security factor FS10; rating 15 VA
2nd core class 0.2; instrument security factor FS10; rating 30 VA
3rd core class 10P; accuracy limit factor 10; rating 30 VA
Rated secondary current 1st core 1 A; 2nd core 1 A; 3rd core 1 A
Power frequency 50 Hz; marking according to IEC
Size 42
Example for Order No.:
Order codes:

4 M C

2
8

J
0

0 D
G
1

4 M C
A

0 D G 1

2
Siemens HG 24 2009

49

4M Protective and Measuring Transformers

Equipment Selection
4MC3 indoor bar-primary bushing-type current transformer

Size specification for 4MC32 transformers 1)


10th to 14th
position of
Order No.

82-1F

84-1G

85-1H

87-1J

88-1K

90-1L

92-1N

93-1P

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32,
41, 42

11, 12,
21, 22,
31, 32,
41, 42,
51, 52

11, 12,
21, 22,
31, 32,
41, 42,
51, 52

21, 22,
31, 32,
41, 42,
51, 52,
61, 62

31, 32,
41, 42,
51, 52,
61, 62,
72, 73

41, 42,
51, 52,
61, 62,
72, 73

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32,
41, 42

11, 12,
21, 22,
31, 32,
41, 42,
51, 52

12, 21,
22, 31,
32, 41,
42, 51,
52

31, 32,
41, 42,
51, 52,
62, 72,
73

41, 42,
51, 52,
62, 72,
73

F30-4Q

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32,
41, 42

51, 52,
62, 72,
73

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32,
41, 42

32, 42,
51, 52,
62, 72,
73

42, 51,
52, 62,
72, 73

F30-6S
F40-6S

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32,
41, 42

42, 51,
52, 62,
72, 73

42, 51,
52, 62,
72, 73

J60-8S

12, 21,
22, 31,
32

12, 21,
22, 31,
32

12, 21,
22, 31,
32, 41,
42

11, 12,
21, 22,
31, 32,
41, 42,
51, 52
12, 21,
22, 31,
32, 41,
42, 51,
52
12, 21,
22, 31,
32, 41,
42, 51,
52
21, 22,
31, 32,
41, 42,
51, 52

32, 42,
51, 52,
62, 72,
73

F30-6Q

12, 21,
22, 31,
32

12, 21,
22, 31,
32

12, 21,
22, 31,
32, 41,
42

31, 32,
41, 42,
51, 52,
61, 62,
72, 73
32, 41,
42, 51,
52, 62,
72, 73

S60-8S

12, 21,
22, 31,
32

12, 21,
22, 31,
32

21, 22,
31, 32,
41, 42

21, 22,
31, 32,
41, 42,
51, 52,
61, 62
21, 22,
32, 41,
42, 51,
52, 61,
62
21, 22,
32, 41,
42, 52,
61, 62

42, 52,
62, 72,
73

Q60-8S

32, 41,
42, 51,
52, 62,
72, 73

42, 52,
62, 72,
73

S80-8S

21, 22,
32

12, 21,
22, 32

21, 22,
31, 32,
41, 42

11, 12,
21, 22,
31, 32

11,12,
21, 22,
31, 32

12, 21,
22, 31,
32, 41,
42

21, 22,
32, 41,
42, 51,
52
22, 31,
32, 41,
42, 51,
52

22, 32,
41, 42,
51, 52,
62
32, 42,
51, 52,
61, 62

41, 42,
51, 52,
62, 72,
73
52, 62,
72, 73

42, 52,
62, 72,
73

Y00-0A

Y00-0B

21, 22,
32

21, 22,
32

22, 32,
41, 42

22, 32,
42, 52

22, 42,
52, 62

Y00-0C
Y00-0D

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

12, 21,
22, 31,
32, 41,
42

12, 22,
32, 41,
42, 51,
52

22, 32,
42, 51,
52

42, 52,
62, 72,
73
52, 62,
72, 73

52, 62,
72, 73

Y00-1A
Y00-1B
Y00-1C
Y00-1D
Y00-1E
Y00-1F

12, 22,
32

22, 32

22, 32,
42

11, 12,
21, 22,
31, 32,
41, 42,
51, 52
11, 12,
21, 22,
31, 32,
41, 42,
51, 52
11, 12,
21, 22,
31, 32,
41, 42,
51, 52
12, 21,
22, 31,
32, 41,
42, 51,
52
12, 21,
22, 31,
32, 41,
42, 51,
52
12, 21,
22, 31,
32, 41,
42, 51,
52
21, 22,
32, 41,
42, 51,
52
12, 21,
22, 31,
32, 41,
42, 51,
52
22, 32,
42, 51,
52
12, 21,
22, 31,
32, 41,
42, 51,
52
22, 32,
42, 52

22, 31,
32, 41,
42, 51,
52, 61,
62, 72,
73
22, 31,
32, 41,
42, 51,
52, 62,
72, 73
22, 31,
32, 41,
42, 51,
52, 62,
72, 73
22, 32,
41, 42,
51, 52,
61, 62

42, 52

52, 62

73

73

22, 32

22, 32

22, 32,
42

41, 52

52

52, 62

73

73

C30-0A
C40-0A
F30-0A
F40-0A
J40-0A
J60-0A
Q40-0A
Q60-0A
S60-0A
S80-0A

6th to 9th position of Order No.

1) Selection for transformers with rated secondary current 1 A. Sizes for 5 A on request

50

Siemens HG 24 2009

21, 22,
31, 32,
41, 42,
51, 52
21, 22,
31, 32,
41, 42,
51, 52

42, 52,
62, 72,
73

52, 62,
72, 73

52, 62,
72, 73

4M Protective and Measuring Transformers

Equipment Selection
4MC3 indoor bar-primary bushing-type current transformer

Size specification for 4MC34 transformers 1)


10th to 14th
position of
Order No.

6th to 9th position of Order No.


82-1F

84-1G

85-1H

87-1J

88-1K

90-1L

92-1N

93-1P

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

12, 21,
22, 31,
32, 41,
42

11, 12,
21, 22,
31, 32,
41, 42,
51, 52

21, 22,
31, 32,
41, 42,
51, 52

21, 22,
31, 32,
41, 42,
51, 52,
61, 62

31, 32,
41, 42,
51, 52,
61, 62,
72, 73

41, 42,
51, 52,
61, 62,
72, 73

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

12, 21,
22, 31,
32, 41,
42

11, 12,
21, 22,
31, 32,
41, 42,
51, 52

21, 22,
31, 32,
41, 42,
51, 52

31, 32,
41, 42,
51, 52,
62, 72,
73

41, 42,
51, 52,
62, 72,
73

F30-4Q

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32,
41, 42

21, 22,
31, 32,
41, 42,
51, 52

32, 42,
51, 52,
62, 72,
73

51, 52,
62, 72,
73

F30-6Q

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32,
41, 42

32, 42,
51, 52,
62, 72,
73

42, 51,
52, 62,
72, 73

F30-6S
F40-6S

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32,
41, 42

42, 51,
52, 62,
72, 73

42, 51,
52, 62,
72, 73

J60-8S

12, 21,
22, 31,
32

12, 21,
22, 31,
32

12, 21,
22, 31,
32, 41,
42

12, 21,
22, 31,
32

12, 21,
22, 31,
32

12, 21,
22, 31,
32, 41,
42

21, 22,
31, 32,
41, 42,
51, 52

21, 22,
31, 32,
41, 42,
51, 52,
61, 62
22, 32,
41, 42,
51, 52,
61, 62

31, 32,
41, 42,
51, 52,
61, 62,
72, 73
32, 41,
42, 51,
52, 62,
72, 73

42, 52,
62, 72,
73

Q60-8S

S60-8S

21, 22,
31, 32

21, 22,
31, 32

21, 22,
31, 32,
41, 42

21, 22,
32

21, 22,
31, 32,
41, 42

11, 12,
21, 22,
31, 32

11,12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32,
41, 42

Y00-0B

22, 32

21, 22,
32

22, 32,
41, 42

22, 32,
42, 52

22, 42,
52, 62

Y00-0C
Y00-0D

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32,
41, 42

22, 32,
41, 42,
51, 52

22, 32,
42, 51,
52

41, 42,
51, 52,
62, 72,
73
22, 32,
42, 51,
52, 61,
62, 72,
73
42, 52,
62, 72,
73
52, 62,
72, 73

42, 52,
62, 72,
73

Y00-0A

22, 32,
41, 42,
52, 61,
62
22, 32,
41, 42,
51, 52,
62
22, 32,
42, 51,
52, 61,
62

42, 52,
62, 72,
73

21, 22,
32

21, 22,
31, 32,
41, 42,
51, 52
21, 22,
32, 41,
42, 51,
52
21, 22,
31, 32,
41, 42,
51, 52

42, 51,
52, 62,
72, 73

S80-8S

Y00-1A
Y00-1B
Y00-1C
Y00-1D
Y00-1E
Y00-1F

12, 22,
32

22, 32

22, 32,
42

11, 12,
21, 22,
31, 32,
41, 42,
51, 52
11, 12,
21, 22,
31, 32,
41, 42,
51, 52
12, 21,
22, 31,
32, 41,
42, 51,
52
12, 21,
22, 31,
32, 41,
42, 51,
52
12, 21,
22, 31,
32, 41,
42, 51,
52
21, 22,
31, 32,
41, 42,
51, 52
21, 22,
32, 41,
42, 51,
52
11, 12,
21, 22,
31, 32,
41, 42,
51, 52
22, 32,
42, 51,
52
12, 21,
22, 31,
32, 41,
42, 51,
52
22, 32,
42, 52

22, 31,
32, 41,
42, 51,
52, 61,
62, 72,
73
22, 31,
32, 41,
42, 51,
52, 62,
72, 73
22, 31,
32, 41,
42, 51,
52, 62,
72, 73
22, 32,
41, 42,
51, 52,
61, 62

42, 52

52, 62

73

73

22, 32

22, 32

22, 32,
42

52

52, 62

73

73

C30-0A
C40-0A
F30-0A
F40-0A
J40-0A
J60-0A
Q40-0A
Q60-0A
S60-0A
S80-0A

41, 52

21, 22,
31, 32,
41, 42,
51, 52
21, 22,
31, 32,
41, 42,
51, 52
21, 22,
31, 32,
41, 42,
51, 52

42, 52,
62, 72,
73

42, 52,
62, 72,
73
52, 62,
72, 73
52, 62,
72, 73

1) Selection for transformers with rated secondary current 1 A. Sizes for 5 A on request

Siemens HG 24 2009

51

4M Protective and Measuring Transformers

Equipment Selection
4MC3 indoor bar-primary bushing-type current transformer

Size specification for 4MC36 transformers 1)


10th to 14th
position of
Order No.

6th to 9th position of Order No.


82-1F

84-1G

85-1H

87-1J

88-1K

90-1L

92-1N

93-1P

C30-0A
C40-0A
F30-0A
F40-0A
J40-0A
J60-0A
Q40-0A
Q60-0A
S60-0A

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32,
41, 42

11, 12,
21, 22,
31, 32,
41, 42,
51, 52

11, 12,
21, 22,
31, 41,
42, 51,
52

21, 22,
31, 32,
41, 42,
51, 52,
61, 62

31, 32,
41, 42,
51, 52,
61, 62,
72, 73

41, 42,
51, 52,
61, 62,
72, 73

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32,
41, 42

21, 22,
31, 32,
41, 42,
51, 52

21, 22,
31, 32,
41, 42,
51, 52

12, 21,
22, 31,
32

11, 12,
21, 22,
31, 32,
41, 42

21, 22,
31, 32,
41, 42,
51, 52

21, 22,
31, 32,
41, 42,
51, 52

31, 32,
41, 42,
51, 52,
61, 62,
72, 73
41, 42,
51, 52,
62, 72,
73

F30-4Q

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32
12, 21,
22, 31,
32

42, 52,
62, 72,
73

52, 62,
72, 73

F30-6S

12, 21,
22, 31,
32

12, 21,
22, 31,
32

42, 52,
62, 72,
73

52, 62,
72, 73

F40-6S

12, 21,
22, 31,
32

12, 21,
22, 31,
32

21, 22,
31, 32,
41, 42,
51, 52
21, 22,
31, 32,
41, 42,
51, 52
21, 22,
31, 32,
41, 42,
51, 52
21, 22,
31, 32,
41, 42,
51, 52

52, 62,
72, 73

12, 21,
22, 31,
32

21, 22,
31, 32,
41, 42,
51, 52
21, 22,
31, 32,
41, 42,
51, 52
21, 22,
31, 32,
41, 42,
51, 52
21, 22,
31, 32,
41, 42,
51, 52

42, 52,
62, 72,
73

F30-6Q

12, 21,
22, 31,
32, 41,
42
12, 21,
22, 31,
32, 41,
42
12, 21,
22, 31,
32, 41,
42
21, 22,
31, 32,
41, 42

41, 42,
51, 52,
62, 72,
73

42, 52,
62, 72,
73

J60-8S

12, 21,
22, 31,
32

12, 21,
22, 31,
32

21, 22,
31, 32,
41, 42

21, 22,
31, 32,
41, 42,
51, 52

21, 22,
31, 32,
41, 42,
51, 52

41, 42,
51, 52,
61, 62,
72, 73

42, 52,
62, 72,
73

Q60-8S

21, 22,
31, 32

12, 21,
22, 31,
32

21, 22,
32, 41,
42

22, 32,
41, 42,
51, 52

42, 51,
52

42, 52,
62, 72,
73

S60-8S

21, 22,
32

21, 22,
32

21, 22,
32, 41,
42

42, 52,
62, 72,
73

52, 62,
72, 73

S80-8S

21, 22,
32

31, 32,
42

21, 22,
32, 41,
42

42, 52,
62, 72,
73

52, 62,
72, 73

Y00-0A

11, 12,
21, 22,
31, 32

11,12,
21, 22,
31, 32

21, 22,
31, 32,
41, 42

52

52, 62,
72, 73

Y00-0B

22, 32

22, 32

22, 32

52

73

Y00-0C
Y00-0D

11, 12,
21, 22,
31, 32

11, 12,
21, 22,
31, 32

21, 22,
31, 32,
41, 42

73

73

Y00-1A
Y00-1B
Y00-1C
Y00-1D
Y00-1E
Y00-1F

22, 32

22, 32

22, 32

21, 22,
32, 41,
42, 51,
52
21, 22,
32, 41,
42, 51,
52
21, 22,
32, 41,
42, 51,
52
21, 22,
32, 41,
42, 51,
52
22, 42,
52
21, 22,
32, 41,
42, 51,
52
42, 52

21, 22,
31, 32,
41, 42,
51, 52,
61, 62
22, 31,
32, 41,
42, 51,
52, 61,
62
22, 31,
32, 41,
42, 51,
52, 62
22, 31,
32, 41,
42, 51,
52, 62
22, 32,
42, 51,
52, 61,
62
21, 22,
32, 41,
42, 51,
52, 61,
62
21, 22,
31, 32,
41, 42,
51, 52,
61, 62
22, 32,
41, 42,
51, 52,
61, 62
22, 41,
42, 51,
52, 61,
62
22, 32,
41, 42,
51, 52,
62
22, 42,
52, 61,
62

41, 42,
51, 52,
61, 62,
72, 73

S80-0A

11, 12,
21, 22,
31, 32,
41, 42,
51, 52
11, 12,
21, 22,
31, 32

22

22

22, 42

52

1) Selection for transformers with rated secondary current 1 A. Sizes for 5 A on request

52

Siemens HG 24 2009

22, 32,
41, 42,
51, 52
22, 32,
41, 42,
51, 52
22, 32,
41, 42,
51, 52
42, 52
22, 32,
41, 42,
51, 52

42, 52,
62
22, 52,
62

41, 42,
51, 52,
62, 72,
73

52

73

73

73

73

4M Protective and Measuring Transformers

Equipment Selection
4ME2 outdoor support-type current transformer

4ME2 outdoor support-type current transformer


2

28
50
70

Order codes

2
2
2

n n n

See page 56

75
125
170

See page 56

12
24
36

See page 56

kV

See page 55

Ud

kV

See page 55

Up

kV

13 14 15 16

4 M E
4 M E
4 M E

Rated short-duration
power-frequency
withstand voltage

Um

10 11 12

2 n n n n n n n n n n n n
See page 55

Rated lightning
impulse withstand
voltage

4 M E

See page 55

Operating
voltage

Position:

Order No.:

See page 55

5th position
Operating voltage (maximum value)

2
4
6

6th to 9th position


Rated short-time thermal current/
Rated primary current

Ith

IPN

IPN

kA

0.5
0.6
1
1.5
2.5
3
5
5
7.5
10
10
15
15
20
20
25
30
30
40
40
50
50
60
60

A
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x

5
10
5
15
25
15
25
50
75
50
100
75
150
100
200
250
150
300
200
400
250
500
300
600

Thermal
strength

n
n

100 x IPN

Rated
primary current,
with primary
multi-ratio

200 x IPN

Rated
primary current

300 x IPN

Rated
short-time
thermal current

n
n
n

n
n

n
n
n
n

n
n n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n

0
0
0
0
1
1
2
2
3
3
3
4
4
4
4
5
5
5
6
6
6
6
7
7

0
1
3
7
6
7
5
5
2
6
6
3
3
8
8
4
6
6
3
3
7
7
0
0

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

A
B
A
D
F
D
F
J
L
J
M
L
P
M
Q
R
P
S
Q
T
R
U
S
V

L n n n n n n n

6th to 9th position continued on page 54

Configuration example
Outdoor support-type current transformer
Maximum operating voltage Um = 24 kV
Rated lightning impulse withstand voltage Up = 125 kV
Rated short-duration power-frequency withstand voltage Ud = 50 kV
Rated short-time thermal current Ith = 15 kA
Rated primary current IPN = 2x 75 A
Example for Order No.:

4 M E

4 M E

Order codes:
Siemens HG 24 2009

53

4M Protective and Measuring Transformers

Equipment Selection
4ME2 outdoor support-type current transformer

0.5
0.6
1
1.5
2
2
3
3
4
4
5
6
6
7.5
8
10
10
12
15
15
20
20
25
30
30
40
40
50
50
60
60
80
80
100
100
120
120

5
10
5
15
10
20
15
30
20
40
50
30
60
75
40
50
100
60
75
150
100
200
250
150
300
200
400
250
500
300
600
400
800
500
1000
600
1200

n
n

n
n
n

n
n

n
n

n
n

n
n

n
n
n

n
n

n
n
n
n

n
n
n

n
n

n
n

n
n
n

n
n

n
n

n
n

n
n

n
n

n
n

4 M E

10 11 12

13 14 15 16

Order codes:

4 M E

Order codes

0
1
3
7
3
3
7
7
2
2
5
6
6
2
3
6
6
8
3
3
8
8
3
6
6
3
3
7
7
0
0
3
3
5
5
6
6

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
1

A
B
A
D
B
E
D
G
E
H
J
G
K
L
H
J
M
K
L
P
M
Q
R
P
S
Q
T
R
U
S
V
T
X
U
A
V
B

1 A

1 A n n n n n n n

See page 56

See page 56

See page 56

0
0
0
0
1
1
1
1
2
2
2
2
2
3
3
3
3
3
4
4
4
4
5
5
5
6
6
6
6
7
7
7
7
7
7
7
7

Example for Order No.:

Siemens HG 24 2009

Thermal
strength

Configuration example
Outdoor support-type current transformer
(Um = 24 kV, Up = 125 kV, Ud = 50 kV)
Rated short-time thermal current Ith = 100 kA
Rated primary current IPN = 1000 A

54

See page 55

2 n n n n n n n n n n n n

See page 55

IPN

See page 55

IPN

kA

See page 55

Ith

4 M E

100 x IPN

Rated
primary current,
with primary
multi-ratio

200 x IPN

Rated
primary current

300 x IPN

Rated
short-time
thermal current

Position:

Order No.:

See page 55

6th to 9th position (continued)


Rated short-time thermal current/
Rated primary current

n n n

4M Protective and Measuring Transformers

Equipment Selection
4ME2 outdoor support-type current transformer

0.5 0.6 1.5 2 2.5 3 4 5 6 7.5 10 15 20 25 30 40


50 60 80 100 120
1 2 3 4 5 6 8 10 12 15 20 30 40 50 60 80 100
120
0.5 0.6 1.5 2 2.5 3 4 5 6 7.5 10 15 20 25 30 40
50 60 80 100 120

0.2

FS10

0.5

FS5

FS5

FS5

0.2

FS10

0.5

FS5

10 11 12

5P

10

5P

10

5P

10

10P

10

0.5

FS5

5P

10

30
30
60
30
30
30
60
30
30
60
30
30
60
15
30
15
30

5P

10

5P

10

300 x IPN

13 14 15 16

Order codes

See page 56

n n n

Rated
primary
current
IPN
100 x IPN

10

200 x IPN

200 x IPN

10P

2 n n n n n n n n n n n n

300 x IPN

10

100 x IPN

VA rating

5P

Factor

FS5

Class

3rd core

VA rating

FS5

Factor

0.5

5
10
15
30
10
15
30
15
30
15
30
60
15
30
60
10
15
30
10
15
30
30
15
30
30
15
30
30
15
15
15
15

Class

Factor
FS10

2nd core

VA rating

Class
0.2

Thermal
strength

At rated primary current IPN

1st core

4 M E

See page 56

Position:

Order No.:

See page 56

10th to 14th position


Core versions

15
30
15
30

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

C
C
C
C
E
E
E
H
H
L
L
L
Q
Q
Q
C
C
C
E
E
E
E
H
H
H
H
H
H
Y
Y
Y
Y

1
2
3
4
2
3
4
3
4
3
4
6
3
4
6
2
3
4
2
3
4
4
3
4
4
3
4
4
0
0
0
0

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
4
4
6
4
4
4
6
4
4
6
4
4
6
0
0
0
0

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
L
L
L
L
L
L
Q
Q
Q
E
F
G
H

0 A

0 A n n

n Feasible (other combinations on request)

Configuration example
Outdoor support-type current transformer
(Um = 24 kV, Ith = 100 kA, IPN = 1000 A)
Thermal strength 300 x IPN
1st core class 10P; instrument security factor 10; rating 60 VA
2nd core without
3rd core without

4 M E

2
4

1 A
3

Q 6

Example for Order No.:

4 M E

1 A Q 6

Order codes:
Siemens HG 24 2009

55

4M Protective and Measuring Transformers

Equipment Selection
4ME2 outdoor support-type current transformer

15th position
Rated secondary current
Rated current
for 1st core

1A
5A
1A
5A
1A
5A
1A
5A

Position:

Order No.:

Rated current
for 2nd core

Rated current
for 3rd core

Without
Without
1A
5A
5A
1A
1A
5A

Without
Without
Without
Without
Without
Without
1A
5A

4 M E

10 11 12

13 14 15 16

Order codes

2 n n n n n n n n n n n n

n n n

0 A A
0 A B
C
D
E
F
G
H

16th position
Additional features
Options

50 Hz, VDE marking


50 Hz, IEC marking
50 Hz, VDE marking with approval 1)
60 Hz, IEC marking
Further not listed special versions (only after consultation with the
order processing department in the Switchgear Factory Berlin).
Information additionally in clear text.

0
1
2
6
9

1) Only for class 0.2 and 0.5

Special versions
Options

With routine test certificate in German/English


Size (for specification see the following page)

0
1
2
3

Z
Z
Z
Z
Z

A
A
A
A
A

1
0
0
0
0

0
0
1
2
3

Other special versions on request

Configuration example
Outdoor support-type current transformer
Maximum operating voltage Um = 24 kV
Rated lightning impulse withstand voltage Up = 125 kV
Rated short-duration power-frequency withstand voltage Ud = 50 kV
Rated short-time thermal current Ith = 100 kA
Rated primary current IPN = 1000 A
Thermal strength 300 x IPN
1st core class 10P; instrument security factor 10; rating 60 VA
2nd core without
3rd core without
Rated secondary current 1st core 5 A; 2nd core without; 3rd core without
Power frequency 50 Hz; marking according to IEC
Size 1
Example for Order No.:
Order codes:

56

Siemens HG 24 2009

4 M E

4
7

1 A
3

Q 6

0 A
B
1

4 M E
A

1 A Q 6

0 A B

4M Protective and Measuring Transformers

Equipment Selection
4ME2 outdoor support-type current transformer

Size specification for 4ME2 transformers


Up to 12 kV
Order No.

At 24 kV

At 36 kV

with rated short-time thermal current


100 x IPN

200 x IPN

300 x IPN

100 x IPN

200 x IPN

100 x IPN

. . . C1.-0A . . .

. . . C2.-0A . . .

. . . C3.-0A . . .

. . . C4.-0A . . .

. . . E2.-0A . . .

. . . E3.-0A . . .

. . . E4.-0A . . .

. . . H3.-0A . . .

. . . H4.-0A . . .

. . . L3.-0A . . .

. . . L4.-0A . . .

. . . L6.-0A . . .

. . . Q3.-0A . . .

. . . Q4.-0A . . .

. . . Q6.-0A . . .

. . . C2.-4L . . .

. . . C3.-4L . . .

. . . C4.-6L . . .

. . . E2.-4L . . .

. . . E3.-4L . . .

. . . E4.-4L . . .

. . . E4.-6L . . .

. . . H3.-4L . . .

. . . H4.-4L . . .

. . . H4.-6L . . .

. . . H3.-4Q . . .

. . . H4.-4Q . . .

. . . H4.-6Q . . .

. . . Y0.-0E . . .

. . . Y0.-0F . . .

. . . Y0.-0G . . .

. . . Y0.-0H . . .

Siemens HG 24 2009

57

4M Protective and Measuring Transformers

Equipment Selection
4ME3 outdoor support-type current transformer

4ME3 outdoor support-type current transformer


2

28
50
70
95

4
4
4
4

3
3
3
3

M
M
M
M

E
E
E
E

2
4
6
8

6th to 9th position


Rated short-time thermal current/
Rated primary current
Rated
primary current,
with primary
multiratio

Ith

IPN

IPN

kA

0.5
0.6
1
1.5
2.5
3
5
5
7.5
10
10
15
15
20
20
25
30
30
40
40
50
50
60
60

A
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x
2x

Thermal
strength

5
10
5
15
25
15
25
50
75
50
100
75
150
100
200
250
150
300
200
400
250
500
300
600

n
n

100 x IPN

Rated
primary current

200 x IPN

Rated
short-time
thermal current

n
n
n

n
n

n
n
n
n

n
n n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n

0
0
0
0
1
1
2
2
3
3
3
4
4
4
4
5
5
5
6
6
6
6
7
7

0
1
3
7
6
7
5
5
2
6
6
3
3
8
8
4
6
6
3
3
7
7
0
0

3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3

A
B
A
D
F
D
F
J
L
J
M
L
P
M
Q
R
P
S
Q
T
R
U
S
V

R n n n n n n n

6th to 9th position continued on page 59

Configuration example
Outdoor support-type current transformer
Maximum operating voltage Um = 52 kV
Rated lightning impulse withstand voltage Up = 250 kV
Rated short-duration power-frequency withstand voltage Ud = 95 kV
Rated short-time thermal current Ith = 25 kA
Rated primary current IPN = 2x 250 A
Example for Order No.:
Order codes:

58

Siemens HG 24 2009

Order codes

4 M E

4 M E

See page 61

75
125
170
250

See page 61

12
24
36
52

See page 61

kV

See page 60

Ud

kV

13 14 15 16

See page 60

Up

kV

See page 60

Um

10 11 12

3 n n n n n n n n n n n n

Rated short-duration
power-frequency
withstand voltage

300 x IPN

Rated lightning
impulse withstand
voltage

4 M E

See page 60

Operating
voltage

Position:

Order No.:

See page 60

5th position
Operating voltage (maximum value)

n n n

4M Protective and Measuring Transformers

Equipment Selection
4ME3 outdoor support-type current transformer

5
10
5
15
10
20
15
30
20
40
50
30
60
75
40
50
100
60
75
150
100
200
250
150
300
200
400
250
500
300
600
400
800
500
1000
600
1200
1500
2000
2500
3000

n
n
n

n
n

n
n

n
n

n
n

n
n
n

n
n

n
n
n
n

n
n
n

n
n

n
n

n
n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n
n
n
n

Configuration example
Outdoor support-type current transformer
(Um = 52 kV, Up = 250 kV, Ud = 95 kV)
Rated short-time thermal current Ith = 100 kA
Rated primary current IPN = 1000 A

4 M E

13 14 15 16

Order codes

0
0
0
0
1
1
1
1
2
2
2
2
2
3
3
3
3
3
4
4
4
4
5
5
5
6
6
6
6
7
7
7
7
7
7
7
7
7
8
8
8

0
1
3
7
3
3
7
7
2
2
5
6
6
2
3
6
6
8
3
3
8
8
3
6
6
3
3
7
7
0
0
3
3
5
5
6
6
8
2
4
5

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
1
1
1
1
1

1 A

1 A n n n n n n n

n n n

See page 61

See page 61

See page 61

Thermal
strength

n
n

10 11 12

See page 60

3 n n n n n n n n n n n n

See page 60

IPN

See page 60

IPN

kA

See page 60

Ith

0.5
0.6
1
1.5
2
2
3
3
4
4
5
6
6
7.5
8
10
10
12
15
15
20
20
25
30
30
40
40
50
50
60
60
80
80
100
100
120
120
150
200
250
300

4 M E

100 x IPN

Rated
primary current,
with primary
multiratio

200 x IPN

Rated
primary current

300 x IPN

Rated
short-time
thermal current

Position:

Order No.:

See page 60

6th to 9th position (continued)


Rated short-time thermal current/
Rated primary current

A
B
A
D
B
E
D
G
E
H
J
G
K
L
H
J
M
K
L
P
M
Q
R
P
S
Q
T
R
U
S
V
T
X
U
A
V
B
D
F
G
H

3
8

Example for Order No.:

4 M E

Order codes:
Siemens HG 24 2009

59

4M Protective and Measuring Transformers

Equipment Selection
4ME3 outdoor support-type current transformer

0.5 0.6 1.5 2 2.5 3 4 5 6 7.5 10 15 20 25 30 40


50 60 80 100 120 150 200 250 300
1 2 3 4 5 6 8 10 12 15 20 30 40 50 60 80 100
120
0.5 0.6 1.5 2 2.5 3 4 5 6 7.5 10 15 20 25 30 40
50 60 80 100 120

10

0.2

FS10

0.5

FS5

FS5

FS5

0.2

FS10

0.5

FS5

10 11 12

5P

10

5P

10

5P

10

10P

10

0.5

FS5

5P

10

30
30
60
30
30
30
60
30
30
60
30
30
60
15
30
15
30

5P

10

5P

10

300 x IPN

13 14 15 16

Rated
primary
current
IPN
100 x IPN

10P

200 x IPN

200 x IPN

10

15
30
15
30

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n

C
C
C
C
E
E
E
H
H
L
L
L
Q
Q
Q
C
C
C
E
E
E
E
H
H
H
H
H
H
Y
Y
Y
Y

1
2
3
4
2
3
4
3
4
3
4
6
3
4
6
2
3
4
2
3
4
4
3
4
4
3
4
4
0
0
0
0

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
4
4
6
4
4
4
6
4
4
6
4
4
6
0
0
0
0

A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
L
L
L
L
L
L
L
L
L
L
Q
Q
Q
E
F
G
H

0 A

0 A n n

n Feasible (other combinations on request)

Configuration example
Outdoor support-type current transformer
(Um = 52 kV, Ith = 100 kA, IPN = 1000 A)
Thermal strength 300 x IPN
1st core class 10P; instrument security factor 10; rating 60 VA
2nd core without
3rd core without

4 M E

Siemens HG 24 2009

1 A
3

Q 6

Order codes:

60

3
8

Example for Order No.:

4 M E

Order codes

1 A Q 6

See page 61

3 n n n n n n n n n n n n

300 x IPN

5P

100 x IPN

VA rating

FS5

Factor

Class

FS5

3rd core

VA rating

0.5

5
10
15
30
10
15
30
15
30
15
30
60
15
30
60
10
15
30
10
15
30
30
15
30
30
15
30
30
15
15
15
15

Factor

FS10

Class

Factor

0.2

2nd core

VA rating

Class

1st core

Thermal
strength

At rated primary current IPN

4 M E

See page 61

Position:

Order No.:

See page 61

10th to 14th position


Core versions

n n n

4M Protective and Measuring Transformers

Equipment Selection
4ME3 outdoor support-type current transformer

15th position
Rated secondary current
Rated current
for 1st core

1A
5A
1A
5A
1A
5A
1A
5A

Position:

Order No.:

Rated current
for 2nd core

Rated current
for 3rd core

Without
Without
1A
5A
5A
1A
1A
5A

Without
Without
Without
Without
Without
Without
1A
5A

4 M E

10 11 12

13 14 15 16

Order codes

3 n n n n n n n n n n n n

n n n

0 A A
0 A B
C
D
E
F
G
H

16th position
Additional features

Options

50 Hz, VDE marking


50 Hz, IEC marking
50 Hz, VDE marking with approval 1)
60 Hz, IEC marking
Further not listed special versions (only after consultation with the
order processing department in the Switchgear Factory Berlin).
Information additionally in clear text.

0
1
2
6
9

1) Only for class 0.2 and 0.5

Special versions
Optionen

With routine test certificate in German/English


Other special versions on request

Configuration example
Outdoor support-type current transformer
Maximum operating voltage Um = 52 kV
Rated lightning impulse withstand voltage Up = 250 kV
Rated short-duration power-frequency withstand voltage Ud = 95 kV
Rated short-time thermal current Ith = 100 kA
Rated primary current IPN = 1000 A
Thermal strength 300 x IPN
1st core class 10P; instrument security factor 10; rating 60 VA
2nd core without
3rd core without
Rated secondary current 1st core 5 A; 2nd core without; 3rd core without
Power frequency 50 Hz; marking according to IEC
Example for Order No.:

4 M E

8
7

1 A
3

Q 6

0 A
B
1

4 M E

1 A Q 6

0 A B

Order codes:
Siemens HG 24 2009

61

4M Protective and Measuring Transformers

Equipment Selection
Product overview of voltage transformers

Voltage transformers,
type of construction according to IEC 1)

10 11 12

13 14 15 16

4 M R

1 Selection from page 63ff

Indoor voltage transformer,


block-type design,
small type of construction according to DIN 42600,
double-phase cast-resin insulated,
operating voltage up to 12 kV or 24 kV

4 M R

2 Selection from page 63ff

R-HG24-063.eps

Indoor voltage transformer,


block-type design,
large type of construction according to DIN 42600,
single-phase cast-resin insulated,
operating voltage up to 12 kV, 24 kV or 36 kV

4 M R

5 Selection from page 63ff

R-HG24-064.eps

Indoor voltage transformer,


block-type design,
large type of construction according to DIN 42600,
double-phase cast-resin insulated,
operating voltage up to 12 kV, 24 kV or 36 kV

4 M R

6 Selection from page 63ff

Outdoor voltage transformer,


small type of construction,
single-phase cast-resin insulated,
operating voltage up to 12 kV, 24 kV,
36 kV or 52 kV

4 M S

3 Selection from page 63ff

Outdoor voltage transformer,


small type of construction,
double-phase cast-resin insulated,
operating voltage up to 12 kV, 24 kV,
36 kV or 52 kV

4 M S

4 Selection from page 63ff

Outdoor voltage transformer,


large type of construction,
single-phase cast-resin insulated,
operating voltage up to 12 kV, 24 kV or 36 kV

4 M S

5 Selection from page 63ff

Outdoor voltage transformer,


large type of construction,
double-phase cast-resin insulated,
operating voltage up to 12 kV, 24 kV or 36 kV

4 M S

6 Selection from page 63ff

4 M S

3 n n n n n n n n n n n n

R-HG24-059.eps

R-HG24-058.eps

Indoor voltage transformer,


block-type design,
small type of construction according to DIN 42600,
single-phase cast-resin insulated,
operating voltage up to 12 kV or 24 kV

R-HG24-065.eps

Type of design

R-HG24-066.eps

R-HG24-055.eps

4 M n n n n n n n n n n n n n n

R-HG24-067.eps

Illustration

Position:

Order No.:

1) Transformers according to ANSI standard on request

Example for Order No.:


Order codes:

62

Siemens HG 24 2009

Order codes

n n n

4M Protective and Measuring Transformers

Equipment Selection
Voltage transformers

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n
n n n n

Configuration example
Voltage transformer
Outdoor design, single-phase
Rated primary voltage Uprim = 6.6/ 3 kV

10 11 12

2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2

0
0
7
7
7
7
1
1
1
1
1
1
2
2
2
2
3
3
6
6
9

8
8
0
0
1
1
3
3
5
5
7
7
2
2
7
7
0
0
1
1
9

See page 67

See page 66

See page 66

See page 65

n
n

Order codes

n n n

See page 67

4 M n n n n n n n n n n

Type 4MS6 double-phase

kV
3.3/ 3
3.3
3.6/ 3
3.6
4.8/ 3
4.8
5 / 3
5
6 / 3
6
6.6/ 3
6.6
7.2/ 3
7.2
10 / 3
10
11 / 3
11
610 / 3
610
Others

Type 4MS5 single-phase

28

Type 4MS4 double-phase

75

Type 4MS3 single-phase

12

Type 4MR6 double-phase

Uprim

kV

Type 4MR5 single-phase

Rated primary voltage

Ud

kV

Type 4MR2 double-phase

Rated short-duration
power-frequency
withstand voltage

Up

kV

Maximum
operating voltage
Umax

Type 4MR1 single-phase

Order No.:
Rated lightning impulse
withstand voltage

50/60 Hz

See page 65

Maximum operating voltage Umax = 52 kV


Position:
12 kV

4 M
S

Example for Order No.:

4 M S

n n n n n

Order codes:
Siemens HG 24 2009

63

4M Protective and Measuring Transformers

Equipment Selection
Voltage transformers

13.8/
13.8
15 /
15
17.5/
17.5
20 /
20
22 /
22
1020 /
1020
1520 /
1520
Others

3 n

Uprim

n
n

3 n

n
n

n
n

3 n
n
3 n

n
3 n
n
3 n

n
n

n
n

n
n

10 11 12

n
n
n n n n

4
4
4
4
4
4
4
4
4
4
4
4
4
4
4

3
3
3
3
7
7
4
4
4
4
6
6
6
6
9

5
5
8
8
2
2
2
2
3
3
5
5
2
2
9

6
6
6
6
6
6
6
6
6
6
6
6
6
6
6

4
4
4
4
4
4
4
4
4
4
4
4
6
6
9

2
2
3
3
5
5
6
6
7
7
8
8
4
4
9

See page 67

See page 66

See page 66

36 kV

70

20
20
22
22
25
25
30
30
33
33
35
35
2030
2030
Others

/ 3

4MS6

170

4MS5

kV

36

4MS4

kV

4MS3

Ud

kV

4MR6

Up

kV

4MR5

Umax

4MR2

50/60 Hz

n
n

/ 3

/ 3

n
n
n
/ 3

/ 3

/ 3

/ 3

n
n

n
n

n
n

n
n

n
n

n
n

n
n

n
n n

Configuration example
Voltage transformer
Outdoor design, single-phase
Rated primary voltage Uprim = 20/ 3 kV

4 M
S

Example for Order No.:


Order codes:

64

Siemens HG 24 2009

4 M S

n n n n n

Order codes

See page 67

Type 4MS6 double-phase


n

n
3 n

n
n

n
n

4 M n n n n n n n n n n

n
n

n
n

Type 4MS5 single-phase

50

Type 4MS4 double-phase

125

Type 4MS3 single-phase

24

Type 4MR6 double-phase

kV

Type 4MR5 single-phase

Uprim

kV

Type 4MR2 double-phase

Ud

kV

Type 4MR1 single-phase

Up

kV

4MR1

Rated primary voltage

Umax

Maximum
operating voltage

Rated short-duration
power-frequency
withstand voltage

Rated lightning impulse


withstand voltage

Order No.:

See page 65

Position:

50/60 Hz

See page 65

24 kV

n n n

4M Protective and Measuring Transformers

Equipment Selection
Voltage transformers

33/
35/
40/
45/

n
n
n
n

3
3
3
3

10 11 12

8
8
8
8

4
4
5
5

See page 67

Order codes

n n n

See page 67

4 M n n n n n n n n n n

Type 4MS6 double-phase

95

Type 4MS5 single-phase

250

Type 4MS4 double-phase

52

Type 4MS3 single-phase

kV

Type 4MR6 double-phase

Uprim

kV

Type 4MR5 single-phase

Ud

kV

Type 4MR2 double-phase

Up

kV

Type 4MR1 single-phase

Rated primary voltage

Umax

Maximum
operating voltage

Rated short-duration
power-frequency
withstand voltage

Rated lightning impulse


withstand voltage

Order No.:

See page 66

Position:

50/60 Hz

See page 66

52 kV

7
8
0
1

2
4MS6

4MS5

n n n n n n n n
n
n
n
n
n
n
n
n
n
n
n
n

4MS4

Without auxiliary winding


100/3
110/3
120/3

4MS3

4MR6

4MR5

4MR1

Voltage

4MR2

8th position
Auxiliary residual voltage winding

0
1
2
3

n
n

4MS6

A
A
B
B
C
C

n
n

n
n

4MS5
n

n
n

4MS4

n
n

n
n

4MS3

4MR6

4MR5

V
100/3
100
110/3
110
120/3
120

4MR2

Voltage

4MR1

9th position
Rated secondary voltage

n
n

Configuration example
Voltage transformer
Outdoor design, single-phase
Rated primary voltage with multi-ratio Uprim = 35/ 3 kV
Without auxiliary residual voltage winding
Rated secondary voltage Usec = 110 V

4 M
S

3
8

0
B

Example for Order No.:

4 M S

B n n n

Order codes:
Siemens HG 24 2009

65

4M Protective and Measuring Transformers

Equipment Selection
Voltage transformers

24

36

52

n
n

n n
n
n n n

n
n

n n
n
n

n
n

n n
n n
n
n n n

n
n

n n
n
n n n
n
n n

n
n
n

n
n

n
n

n n
n
n

n
n

n n
n
n
n
n

n
n
n
n

E
G
K
N
P
P
S
T
E
F
G
J
K
M
P
P
R
T
F
K
L
M
P
R
R
T
V
L
S
V

1
1
2
2
2
3
3
3
1
1
1
1
2
2
2
3
3
3
1
1
1
2
2
2
3
3
3
1
2
3

2 n

4 M
S

Order codes:

Order codes

n n
n n n

10 11 12

See page 67

See page 67

n n n n n n

Example for Order No.:

Siemens HG 24 2009

n n

Configuration example
Voltage transformer
Outdoor design, single-phase
Rated output of measuring winding 180 VA
Accuracy class 0.5

66

4 M n n n n n n n n n n

Type 4MS6 double-phase

Type 4MS5 single-phase

20
30
50
90
100
100
180
200
20
25
30
45
50
75
100
100
150
200
25
50
60
75
100
150
150
200
400
60
180
400

Type 4MS4 double-phase

0.2
0.2
0.5
0.5
0.5
1
1
1
0.2
0.2
0.2
0.2
0.5
0.5
0.5
1
1
1
0.2
0.2
0.2
0.5
0.5
0.5
1
1
1
0.2
0.5
1

Type 4MS3 single-phase

12

Type 4MR6 double-phase

VA

Type 4MR5 single-phase

Type 4MR2 double-phase

kV

Type 4MR1 single-phase

SN

Umax

Rated output

Class

Voltage level

10th/11th position
Position:
Rated output of measuring winding and accuracy class Order No.:

4 M S

n n n

4M Protective and Measuring Transformers

Equipment Selection
Voltage transformers

12th position
Additional features

Position:

Options

4MR1

4MR2

4MR5

4MR6

4MS3

4MS4

4MS5

4MS6

50 Hz, VDE marking


50 Hz, IEC marking
50 Hz, VDE marking with approval 1)
60 Hz, IEC marking
Other features on request

n
n
n
n
n

n
n
n
n
n

n
n
n
n
n

n
n
n
n
n

n
n
n
n
n

n
n
n
n
n

n
n
n
n
n

n
n
n
n
n

Options

Type 4MR1 single-phase

Type 4MR2 double-phase

Type 4MR5 single-phase

Type 4MR6 double-phase

Type 4MS3 single-phase

Type 4MS4 double-phase

Type 4MS5 single-phase

Type 4MS6 double-phase

Order No.:

With routine test certificate


in German/English

n n n n n n n n

10 11 12

4 M n n n n n n n n n n

Order codes

n n n

0
1
2
6
9

1) Only for class 0.2 and 0.5

Additional equipment

Configuration example
Voltage transformer
Outdoor design, single-phase, cast-resin insulated
Rated primary voltage with multi-ratio Uprim = 35/ 3 kV
Without auxiliary residual voltage winding
Rated secondary voltage Usec = 110 V
Rated output of measuring winding 180 VA
Accuracy class 0.5
Additional features 50 Hz, IEC marking
With routine test certificate in German/English

4 M
S

3
8

0
B
S

2
1

Example for Order No.:


Order codes:

4 M S
A

0
Siemens HG 24 2009

67

R-HG24-068.tif

4M Protective and Measuring Transformers

68

Siemens HG 24 2009

4M Protective and Measuring Transformers

Technical Data
Contents

Contents

Page

Technical Data

69

Current transformers:
Electrical data, dimensions and weights

70

Dimension drawings

72

Terminal designations

77

Voltage transformers:
78

Dimension drawings

79

Terminal designations

82

R-HG11-069.tif

Electrical data, dimensions and weights

Primary connection terminal of 4MR12 voltage transformer

Siemens HG 24 2009

69

4M Protective and Measuring Transformers

Technical Data

kV

kV

12

28

17.5

4MA74

kg

1/5

1.2

80

120

5000

20

2 x 20 to 2 x 600

1/5

1.2

80

120

5000

20

20 to 2500

2 x 20 to 2 x 600

1/5

1.2

80

120

5000

25

50/60

20 to 2000

2 x 20 to 2 x 600

1/5

1.2

80

120

5000

35

75

50/60

1500 to
4000

only possible on
secondary side

1/5

1.2

100 x IPN

practically
unlimited

3000

19 or 26

28

75

50/60

1500 to
6000

only possible on
secondary side

1/5

1.2

100 x IPN

practically
unlimited

3000

34

241)

501)

1251)

50/60

1500 to
4000

only possible on
secondary side

1/5

1.2

100 x IPN

practically
unlimited

3000

26

4MC22

12

28

75

50/60

150 to 3000

only possible on
secondary side

1/5

1.2

100 x IPN

practically
unlimited

5000

12 to 48

4MC24

24

50

125

50/60

150 to 3000

only possible on
secondary side

1/5

1.2

100 x IPN

practically
unlimited

5000

28 to 48

4MC26

36

70

170

50/60

150 to 3000

only possible on
secondary side

1/5

1.2

100 x IPN

practically
unlimited

5000

35 to 48

4MC32

12

28

75

50/60

2000 to
10000

only possible on
secondary side

1/5

1.2

100 x IPN

practically
unlimited

5000

32 to 150

4MC34

24

50

125

50/60

2000 to
10000

only possible on
secondary side

1/5

1.2

100 x IPN

practically
unlimited

5000

32 to 150

4MC36

36

70

170

50/60

2000 to
10000

only possible on
secondary side

1/5

1.2

100 x IPN

practically
unlimited

5000

32 to 150

4ME22

12

28

75

50/60

5 to 1200

2 x 5 to 2 x 600

1/5

1.2

80

2.5 x Ith

2400

22

9/10

4ME24

24

50

125

50/60

5 to 1200

2 x 5 to 2 x 600

1/5

1.2

80

2.5 x Ith

2400

22

9/10

4ME26

36

70

170

50/60

5 to 1200

2 x 5 to 2 x 600

1/5

1.2

80

2.5 x Ith

2000

22

11/12

4ME32

12

28

75

50/60

5 to 3000

2 x 5 to 2 x 600

1/5

1.2

80

2.5 x Ith

5000

65

13

4ME34

24

50

125

50/60

5 to 3000

2 x 5 to 2 x 600

1/5

1.2

80

2.5 x Ith

5000

65

13

4ME36

36

70

170

50/60

5 to 3000

2 x 5 to 2 x 600

1/5

1.2

80

2.5 x Ith

5000

65

14

4ME38

52

95

250

50/60

5 to 3000

2 x 5 to 2 x 600

1/5

1.2

80

2.5 x Ith

5000

65

15

ISN

Hz

kA

75

50/60

20 to 2500

2 x 20 to 2 x 600

38

95

50/60

20 to 2500

24

50

125

50/60

4MA76

36

70

170

4MB12

12

28

4MB13

12

4MB14

4MA72
4MA72Z F18

1) Also possible on request: Um = 17.5, Ud = 38 kV and Up = 75 kV

70

Siemens HG 24 2009

Catalog dimension
drawing

maximum

IPN

Maximum rated
continuous thermal
current

kA

Secondary current

kA

Multi-ratio

x IPN

Rated primary current

Idyn

Rated frequency

Ith

Order No.

Weight

kV

Short-time load
(mechanical)

Up

Number of cores

Rated lightning impulse


withstand voltage

Ud

Rated dynamic current


(Idyn 2.5 x Ith)

Rated short-duration
power-frequency
withstand voltage

Um

Rated short-time
thermal current
(minimum 100 x IPN)

Operating voltage
(maximum value)

Electrical data, dimensions and weights of current transformers

4M Protective and Measuring Transformers

Technical Data
Electrical data, dimensions and weights of current transformers

Size specification for 4MC2 transformers


10th to 14th
position of
Order No.

6th to 9th position of Order No.


43-0P

48-0Q

56-0S

63-0T

67-0U

C20-0A
C30-0A
E30-0A
E40-0A
H30-0A
H40-0A
Q30-0A
Q40-0A
Q60-0A
C20-4Q
C30-4Q
E30-3Q
E30-4Q
E40-4Q
E40-6Q
H30-3Q
H30-4Q
H40-4Q
H40-6Q

1
2
1
2
0
1
2
2
21
3
3
3
3
3

1
2
2

0
0
0
0
0
2
1
1
3
2
2
2
2
2
21
1
2
2
21

0
0
0
0
0
2
0
1
2
1
1
1
1
1
3
0
1
1
2

0
0
0
0
0
2
0
1
1
0
1
0
0
0
2
0
0
0
2

0
0
0
0
0
2
0
0
1
0
0
0
0
0
2
0
0
0
1

C20-0A
C30-0A
E30-0A
E40-0A
H30-0A
H40-0A
Q30-0A
Q40-0A
Q60-0A
C20-4Q
C30-4Q
E30-3Q
E30-4Q
E40-4Q
E40-6Q
H30-3Q
H30-4Q
H40-4Q
H40-6Q

1
1
1
1
1
1
1
1
11
2
2
2
2
2

1
1
2

1
1
1
1
1
1
1
1
2
1
1
2
2
2
11
1
1
1
11

1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
2

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

C20-0A
C30-0A
E30-0A
E40-0A
H30-0A
H40-0A
Q30-0A
Q40-0A
Q60-0A
C20-4Q
C30-4Q
E30-3Q
E30-4Q
E40-4Q
E40-6Q
H30-3Q
H30-4Q
H40-4Q
H40-6Q

1
1
1
1
1
1
1
1

01
01
01
01
01

1
1
01

1
1
1
1
1
1
1
1
01
1
1
1
1
1

1
1
1

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

70-0V

73-0X

75-1A

Sizes of 4MC22 transformers


0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
2
2
2
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
0
0
0
0
0
0
0
0
0
1
1
1
Sizes of 4MC24 transformers
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Sizes of 4MC26 transformers
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

76-1B

78-1D

82-1F

84-1G

86-1H

0
0
0
0
0
2
0
0
1
0
0
0
0
0
1
0
0
0
1

0
0
0
0
0
2
0
0
1
0
0
0
0
0
2
0
0
0
2

0
0
0
0
0
2
0
0
1
0
0
0
0
0
2
0
0
0
2

0
0
0
0
0
2
0
0
1
0
0
0
0
0
2
0
0
0
2

21
21
21
21
21
21
21
21
21
21
21
21
21
21
21
21
21
21
21

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11

11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11
11

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01

01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01

01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01
01

Siemens HG 24 2009

71

4M Protective and Measuring Transformers

Technical Data
Electrical data, dimensions and weights of current transformers

Dimension drawings for current transformers

12

184
120

M12, 23 deep

347

270

184
120

M12, 23 deep

40
70

HG24-2205a_en eps

125
148

220

24

74.5

Primary connection W 1500 A

Dimension drawing 1

14

184
120

M12, 23 deep

356

280

M12, 23 deep

184
120

40
65

HG24-2206a_en eps

150
178

280

32

80

Dimension drawing 2

284
220

M12, 23 deep
284
220

Dimension drawing 3

72

Siemens HG 24 2009

300

HG24-2207_en eps

385

M12, 23 deep

40

225
249

390

14

4M Protective and Measuring Transformers

Technical Data
Electrical data, dimensions and weights of current transformers

e2
e1

Type

10

4MB12, size 1
4MB12, size 2
4MB13
4MB14

e2

h1

h2

214
260
273
260

210
230

230

350
350

350

235
295
288
295

342
425
425
425

176
196
300
196

h2

e1

102

HG24-2208 eps

h1

180

277

HG24-2209 eps

40
80
14

50
100

40

155

14

40

155

Current ratings

Bars

Up to 1500 A
1500 A to 2500 A
2500 A to 3000 A
3000 A to 4000 A

2 x 50 x 10
2 x 80 x 10
2 x 80 x 10 or 3 x 80 x 10
3 x 80 x 10 or 3 x 100 x 10

Dimension drawing 4
200
175

236
200
HG24-2210 eps

d1

14

45

40

40

14

100

90 x 20

30

40

14

68 x 16

e1

e1

14

40

68 x 16

80

40
14

e1

e1

20

60 x 12

80

35 x 10
30 x 8

e1

105

e2

d2

250

357
286

225

340

135

e1

14

14

Dimension drawing 5
Type

4MC22

4MC24

4MC26

Size

0
1
2
3
21
1
2
11
1
01

d1

d2

e1

max.
mm

mm

mm

up to 1500 A
mm

2000 A
mm

50
60
115
195
150
60
140
100
60
50

180
180
180
180
230
180
180
230
180
230

185
185
185
185
235
185
185
235
185
253

190
190
255
315
280
255
315
280
315
280

195
195
260
320
285
260
320
285
320
285

e2
up to 3000 A1) up to 1500 A
mm
mm
215
215
280
340
315
280
340
315
340
315

150
210
270
330
290
270
330
290
330
290

Weight

2000 A
mm

up to 3000 A1)
mm

approx.
kg

155
215
275
335
295
275
335
295
335
295

175
235
295
355
325
295
355
325
355
325

12 to 18
16 to 22
28 to 32
35 to 40
40 to 48
28 to 32
35 to 40
40 to 48
35 to 40
40 to 48

1) Design for rated primary current 3000 A only available in size 21, 11 or 01

Siemens HG 24 2009

73

4M Protective and Measuring Transformers

Technical Data
Electrical data, dimensions and weights of current transformers

h1

80

h2

e1

40

86
40

14

10

M5

100
50

182
230

a
e2

Bars re-adjustable by 90

86
40

HG24-2211 eps

14
14

168

Dimension drawing 6

Size

amax

e1

e2

h1

h2

11
12
21
22
31
32
41
42
51
52
61
62
72
73

10
60
10
60
10
60
10
60
10
60
10
60
10
60

295
295
370
370
370
370
440
440
530
530
530
530
650
650

278
278
356
356
356
356
440
440
530
530
530
530
650
650

115
115
115
115
155
155
205
205
297
297
310
310
380
380

255
255
325
325
325
325
490
490
490
490
490
490
600
600

175
250
175
250

313
288
313
288

285
360
285
360
285
360
285
360
285
360

h1

e1

10

M5

239
285

HG24-2212 eps

14

a
e2

Bars re-adjustable by 90

Dimension drawing 7

74

Size

amax

e1

e2

h1

h2

11
12
21
22
31
32
41
42
51
52
61
62
72
73

10
60
10
60
10
60
10
60
10
60
10
60
10
60

295
295
370
370
370
370
440
440
530
530
530
530
650
650

278
278
356
356
356
356
440
440
530
530
530
530
650
650

115
115
115
115
155
155
205
205
297
297
310
310
380
380

255
255
325
325
325
325
490
490
490
490
490
490
600
600

230
305
230
305

427
502
427
50

399
474
399
474
399
474
399
474
399
474
399
474

Siemens HG 24 2009

Conductor bars
Normal designs
2000 A:

2 bars, 80 x 10 mm

2500 A:

2 bars, 100 x 10 mm

3000 A:

3 bars, 80 x 10 mm

4000 A:

3 bars, 100 x 10 mm

4M Protective and Measuring Transformers

Technical Data
Electrical data, dimensions and weights of current transformers

h1

h2

e1

10

M5

319
365

HG24-2213 eps

14

a
e2

Bars re-adjustable by 90

305

Dimension drawing 8
Size

amax

e1

e2

h1

h2

11
12
21
22
31
32
41
42
51
52
61
62
72
73

10
60
10
60
10
60
10
60
10
60
10
60
10
60

295
295
370
370
370
370
440
440
530
530
530
530
650
650

278
278
356
356
356
356
440
440
530
530
530
530
650
650

115
115
115
115
155
155
205
205
297
297
310
310
380
380

255
255
325
325
325
325
490
490
490
490
490
490
600
600

175
250
175
250

313
288
313
288

285
360
285
360
285
360
285
360
285
360

235

100

60

240

20

35

200

355

14

HG24-2239 eps

Type
40

115

M10

4ME22

155

4ME24

Dimension drawing 9
4ME26

404

335

150

Arcing distance

Creepage
distance

229
310
229
440
405
440

486
400
486
1010
945
1010

335

300

60

20

HG24-2240 eps

355

10

14

195

M10
32

300

32

Dimension drawing 10
Siemens HG 24 2009

75

4M Protective and Measuring Transformers

Technical Data
Electrical data, dimensions and weights of current transformers

235

100

HG24-2241 eps

60

240

20

35

200

419

14

40

115
155

M10

Type

95

Arcing distance

Creepage
distance

229
310
229
440
405
440

486
400
486
1010
945
1010

4ME22

90

Dimension drawing 11

4ME24

335

4ME26

10

404
150

335

20

HG24-2242 eps

60

300

439

14

M10
32

195

32

300

Dimension drawing 12
l
380

IPN

Arcing
distance

Creepage
distance

Up to 600 A
600 to 1250 A
1250 to 2000 A
2000 to 3000 A

20
30
42
48

500
560
600
620

268
268
268
268

665
665
665
665

Dimension drawing 13

76

Siemens HG 24 2009

300
230

350

175
178

HG24-2251 eps

437

268

592

18

4M Protective and Measuring Transformers

Technical Data
Electrical data, dimensions and weights of current transformers

IPN

Arcing
distance

Creepage
distance

Up to 600 A
600 to 1250 A
1250 to 2000 A
2000 to 3000 A

20
30
42
48

572
632
672
692

557.5
557.5
557.5
557.5

1290
1290
1290
1290

IPN

Arcing
distance

Creepage
distance

500 A
Up to 1250 A
1250 to 2000 A
2000 to 3000 A
2x 600 A

30
30
42
45
30

700
700
740
760
700

1125
1188
1188
1188
1217

745
745
745
745
745

1823
1823
1823
1823
1823

1002

18

300

175
10

HG24-2250 eps

350

725

557.5

956

l
452

178

230

Dimension drawing 14
l
520

175

10

148

500

80
30

300

HG24-2249 eps

900

745

18

247

Dimension drawing 15
Terminal designations of current transformers
Designation of connection terminals

1 secondary winding

2 equivalent
primary windings

Ka

1 secondary winding

l
Kb La

P1
HG24-2216 eps

Lb

P2

S1
P1

HG24-2218 eps

1 primary winding

Example for
rated current data

acc. to IEC

S2
C1 C2

S1

HG24-2217 eps

acc. to VDE

100/1 A

P2

S2

HG24-2219 eps

Transformer design

2 x 100/1 A

with primary multi-ratio

2 or more secondary
windings on
separate cores

l3 l2 l1

1k

S1

S2 S3 S4

P1

P2

with secondary multi-ratio,


highest rated current at I1 or S4

1l 2k

2l

P2

1S1

1S2 2S1

2S2

HG24-2221 eps

P1

HG24-2223 eps

1 primary winding

L
HG24-2220 eps

1 secondary winding
with tappings

HG24-2222 eps

1 primary winding

1000800 200/1A

100/1/1 A

Siemens HG 24 2009

77

4M Protective and Measuring Transformers

Technical Data

75

50/60

11.5/3

100/3; 110/3;
120/3

350

50

125

50/60

22/3

100/3; 110/3;
120/3

12

28

75

50/60

11.5

24

50

125

50/60

4MR12

12

28

4MR14

24

4MR22
4MR24

VA/A

kg

1.9

230/4

18

16

500

1.9

230/4

28

16

100; 110; 120

400

18

17

22

100; 110; 120

400

30

17

100/3; 110/3;
120/3

600

1.9

350/6

25

18

Catalog dimension
drawing

kV

Rated voltage factor


(8h)

kV

Weight

VA

kV

Short-time load
(mechanical)

Thermal limiting output

kV

UP

Rated thermal limiting


output of the residual
voltage winding

Multi-ratio

kV

Ud

Rated frequency
Hz

Rated lightning impulse


withstand voltage

Sth

Rated short-duration
power-frequency
withstand voltage

USN

Operating voltage
(maximum value)

UPN

Um

Order No.

Maximum rated
primary voltage

Electrical data, dimensions and weights of voltage transformers

4MR52

12

28

75

50/60

11.5/3

4MR54

24

50

125

50/60

22/3

100/3; 110/3;
120/3

600

1.9

350/6

35

18

4MR56

36

70

170

50/60

35/3

100/3; 110/3;
120/3

800

1.9

350/6

60

18

4MR62

12

28

75

50/60

11.5

100; 110; 120

600

25

19

4MR64

24

50

125

50/60

22

100; 110; 120

600

35

19

4MR66

36

70

170

50/60

35

100; 110; 120

800

70

19

400

1.9

230/4

1000

72

20

4MS32

12

28

75

50/60

12/3

100/3; 110/3;
120/3

4MS34

24

50

125

50/60

22/3

100/3; 110/3;
120/3

400

1.9

230/4

1000

75

20

4MS36

12

28

75

50/60

35/3

100/3; 110/3;
120/3

400

1.9

230/4

1000

79

20

4MS38

52

70

250

50/60

50/3

100/3; 110/3;
120/3

800

1.9

500/9

1000

79

20

4MS42

12

28

75

50/60

12

100; 110; 120

500

1000

73

21

4MS44

24

50

125

50/60

22

100; 110; 120

500

1000

76

21

4MS46

12

28

75

50/60

35

100; 110; 120

900

1000

82

21

400

1.9

230/4

1000

35.5

22

4MS52

12

28

75

50/60

12/3

100/3; 110/3;
120/3

4MS54

24

50

125

50/60

22/3

100/3; 110/3;
120/3

400

1.9

230/4

1000

35.5

22

4MS56

36

28

75

50/60

35/3

100/3; 110/3;
120/3

400

1.9

230/4

1000

51

23

4MS62

12

28

75

50/60

12

100; 110; 120

500

1000

37

24

4MS64

24

50

125

50/60

22

100; 110; 120

500

1000

37

24

4MS66

36

28

75

50/60

35

100; 110; 120

500

1000

57

25

78

Siemens HG 24 2009

4M Protective and Measuring Transformers

Technical Data
Electrical data, dimensions and weights of current transformers

Dimension drawings for voltage transformers

e1

HG24-2224 eps

Type
4MR12
4MR14

e1

e2

148
178

220
280

335
357

125
150

270
280

11
14

e2

Dimension drawing 16

e1

e3

HG24-2225 eps

Type
4MR12
4MR14

e1

e2

e3

148
178

220
280

335
357

125
150

270
280

110
130

11
14

e2

Dimension drawing 17

3
d

HG24-2226 eps

e1

Type

e2

4MR52
4MR54
4MR54 1)
4MR56

e1

e2

200
225
200
249

240
300
300
390

342
370
324
395

175
200
175
225

225
250
225
300

11
14
14
14

1) Design on request

Dimension drawing 18

e2

e1

HG24-2227 eps

e3

Type
4MR62
4MR64
4MR64 1)
4MR66

e1

e2

e3

200
225
200
249

240
300
260
390

342
370
324
395

175
200
175
225

225
250
225
300

150
210
155
320

11
14
14
14

1) Design on request

Dimension drawing 19

Siemens HG 24 2009

79

4M Protective and Measuring Transformers

Technical Data
Electrical data, dimensions and weights of voltage transformers

55

150
20

Type

Arcing
distance

Creepage
distance

Number
of sheds

520
655
880
880

420
550
760
760

790
1055
1615
1615

2
5
10
10

220

32

25

280

162

20

HG24-2243 eps

4MS32
4MS34
4MS36
4MS38

50

14

380

205

215

160

245

Dimension drawing 20

b
e

Type

150
20

55

4MS42
4MS44
4MS46

Arcing
distance

Creepage
distance

Number
of sheds

515
645
865

375
445
560

270
340
455

420
550
760

760
1035
1595

2x2
2x5
2 x 10

280

220

50

Dimension drawing 21

80

Siemens HG 24 2009

25

245

HG24-2244 eps

205

160

380

215

M12

14

4M Protective and Measuring Transformers

Technical Data

M10

HG24-2246_en eps

20

HG24-2245_en eps

520

644.5

Electrical data, dimensions and weights of current transformers

110

M10

310

320
270

17.5

14

40

200

215

260

196

12

240

270
12

Dimension drawing 23

Dimension drawing 22

50

512
400

M10

HG24-2248 eps

20

HG24-2247 eps

490

622

405
320

110

M10
320

310

270

270

200

260

215

196

Dimension drawing 24

Dimension drawing 25

240

14

12

50

Siemens HG 24 2009

81

4M Protective and Measuring Transformers

Technical Data
Electrical data, dimensions and weights of voltage transformers

Terminal designations of the voltage transformers


Designation of the connection terminals

1 secondary winding

Unearthed

1 secondary winding
with tappings

u1

u2

A
HG24-2231 eps

HG24-2233 eps

Unearthed

acc. to IEC
B

a1

a2

HG24-2232 eps

acc. to VDE

Example for
low-voltage data

HG24-2234 eps

Transformer design

10000/100 V

500010000/100 V

highest rated voltage at u1 or a1

82

Siemens HG 24 2009

x e

n da

dn

HG24-2236 eps

1 measuring winding
1 auxiliary residual
voltage winding

HG24-2235 eps

Earthed

10000/3 / 100/3 / 100/3 V

4M Protective and Measuring Transformers

Annex
Contents

Contents

Page

Annex

83

Inquiry form

84

Configuration instructions

85
Foldout page

R-HG11-181.tif

Configuration aid

Brandenburg Gate, Berlin, Germany

R-HG11-180.tif

Switchgear Factory Berlin, Germany

Siemens HG 24 2009

83

4M Protective and Measuring Transformers

Annex
Inquiry form

Please copy, fill in and return


to your Siemens partner.

Inquiry concerning

o
o
o
o
o
o
o
o

4MA7 current transformer


4MB1 current transformer
4MC2 current transformer
4MC3 current transformer
4ME2 current transformer
4ME3 current transformer
4MR voltage transformer
4MS voltage transformer

Technical data of current transformer


o 12 kV
o 36 kV

o 17.5 kV
o 52 kV

o 24 kV

Rated lightning impulse


withstand voltage

o 75 kV
o 170 kV

o 95 kV
o 250 kV

o 125 kV

Rated short-duration powerfrequency withstand voltage

o 28 kV
o 70 kV

o 38 kV
o 95 kV

o 50 kV

Rated primary current

o ___A

o 2x _ _ _ A

Secondary current

o 1A

o 5A

Thermal strength

o 100 x IPN
o 300 x IPN
o 600 x IPN

o 150 x IPN
o 400 x IPN
o 800 x IPN

Operating voltage

Please

o Submit an offer
o Call us
o Visit us

o _ _ _ kV

o _ _ _ kV

o 200 x IPN
o 500 x IPN
o 1000 x IPN

o _ _ _ x IPN

o Protection core o _ _ _ Class


o Measuring core o _ _ _ Class

o _ _ _ Factor
o _ _ _ Factor

o _ _ _ VA
o _ _ _ VA

2nd core

o Protection core o _ _ _ Class


o Measuring core o _ _ _ Class

o _ _ _ Factor
o _ _ _ Factor

o _ _ _ VA
o _ _ _ VA

3rd core

o Protection core o _ _ _ Class


o Measuring core o _ _ _ Class

o _ _ _ Factor
o _ _ _ Factor

o _ _ _ VA
o _ _ _ VA

Technical data of voltage transformer


Maximum operating voltage

Dept.

o 12 kV
o 36 kV

o 24 kV
o 52 kV

Other values
o _ _ _ kV

Rated lightning impulse


withstand voltage

o 75 kV
o 170 kV

o 95 kV
o 250 kV

o 125 kV

Name

Rated short-duration powerfrequency withstand voltage

o 28 kV
o 70 kV

o 38 kV
o 95 kV

o 50 kV

Street

Rated primary voltage

o _ _ _ kV

o _ _ _ /3

Rated secondary voltage

o 100 V
o 100/3 V

o 110 V
o 110/3 V

o 120 V
o 120/3 V

o ___V
o _ _ _ /3 V

Auxiliary residual
voltage winding

o Without

o 100/3 V

o 110/3 V

o 120/3 V

Fax
E-mail

Rated output of the


measuring winding

o Class 0.2
o 20 VA

o Class 0.5
o 50 VA

o Class 1
o 100 VA

o _ _ _ VA

Siemens AG

Application and other requirements

Postal code/city
Phone

o _ _ _ kV

1st core

Your address
Company

Other values

o _ _ _ kV

o _ _ _ kV

Dept.
Name
Street
Postal code/city
Fax

o Please check off

84

Siemens HG 24 2009

_ _ _ Please fill in

For configuration of your


4M protective and measuring transformers

You prefer to configure your instrument transformer on your own?


Please follow the steps for configuration and enter the order number in the configuration aid.

9 10 11 12

13 14 15 16

4 M n n n n n n n n n n n n n n Z

Instruction for configuration of the 4M protective and measuring transformers


1st step: Definition of the current transformer
Please specify the following ratings:

Possible options:

Transformer design
Operating voltage (Um)
Rated lightning impulse withstand voltage (Up)
Rated short-duration power-frequency withstand voltage (Ud)
Rated primary current (IPN)
Secondary current (ISN)
Thermal strength
Core data

Block-type transformer, bushing-type transformer, outdoor transformer, etc.


Um: 12 kV to 52 kV
Up: 75 kV to 250 kV
Ud: 28 kV to 95 kV
IPN: 20 A to 10000 A
ISN: 1 A or 5 A
100 x IPN to 1000 IPN
Quantity, type, class, factor and rating of cores

4 M

4 M

These ratings define the positions 3 to 15 of the order number of the current transformer.

Please specify the following ratings:

Possible options:

Transformer design
Number of phases
Operating voltage (Um)
Rated lightning impulse withstand voltage (Up)
Rated short-duration power-frequency withstand voltage (Ud)
Rated primary voltage (UPN)
Rated secondary voltage (USN)
Rated output of the measuring winding

Block-type transformer, outdoor transformer


Single-phase or double-phase
Um: 12 kV to 52 kV
Up: 75 kV to 250 kV
Ud: 28 kV to 95 kV
UPN: 3.3 kV to 45 kV or values divided by 3
USN: 100 V, 110 V, 120 V or values divided by 3
25 VA, class 0.2 up to 400 VA, class 1

4 M

4 M

These ratings define the positions 3 to 11 of the order number of the voltage transformer.

4 M

2nd step: Definition of the voltage transformer

4 M

3rd step: Do you have any further requirements concerning the equipment?

Should you still need more options than the possible equipment like terminal designations according
to VDE or IEC, selection of sizes, routine test certificate, etc., please contact your responsible sales partner.

4 M

4 M

85

4 M

Siemens HG 24 2009

Published by and copyright 2009:


Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany
Siemens AG
Energy Sector
Power Distribution Division
Medium Voltage
Nonnendammallee 104
13623 Berlin, Germany
For more information, please contact our
Customer Support Center.
Phone: +49 180 524 70 00
Fax:
+49 180 524 24 71
(Charges depending on provider)
E-mail: support.energy@siemens.com
Order No. E50001-K1524-A101-A3-7600
Printed in Germany
Dispo 31601, c4bs 7460
KG 05.09 2.0 88 En
6101/15477 480488
Printed on elementary chlorine-free bleached paper.
All rights reserved.
If not stated otherwise on the individual pages of this
catalog, we reserve the right to include modifications,
especially regarding the stated values, dimensions and weights.
Drawings are not binding.
All product designations used are trademarks or product
names of Siemens AG or other suppliers.
If not stated otherwise, all dimensions in this
catalog are given in mm.
Subject to change without prior notice.
The information in this document contains general
descriptions of the technical options available, which
may not apply in all cases. The required technical
options should therefore be specified in the contract.

Responsible for
Technical contents:
Siemens AG, E D MV C I LM
Berlin

General editing:
Siemens AG, E CC MCC G
Erlangen

www.siemens.com/energy