You are on page 1of 69

ORDER NO.

MAC9812043C2

Service Manual
Room Air Conditioners

CS-G93KE / CU-G93KE
CS-G123KE / CU-G123KE

Contents

Features .......................................................... 1
Functions ................................................... 2 6
Product Specifications ............................. 7 10
Dimensions ............................................ 11 12
Refrigeration Cycle Diagram ......................... 13
Block Diagram ............................................... 14
Wiring Diagram ...................................... 15 16
Operation Details ................................... 17 47
Installation Information .......................... 48 49
Servicing Information ............................. 50 62
Technical Data ....................................... 63 64
Exploded View ......................................... 65, 68
Replacement Parts List ..................... 66, 67, 69
Electronic Parts List ............................... 70 71

1998 Matsushita Air-Conditioning Corp. Sdn. Bhd.


(183914D)
All rights reserved. Unauthorized copying and distribution is a violation of law.

Untitled-7

6/21/00, 9:47 AM

CS-G93KE

! WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public. It does not contain
warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product. Products powered by electricity
should be serviced or repaired only by experienced professional technicians. Any attempt to service or repair the product or products dealt with
in this service information by anyone else could result in serious injury or death.

PRECAUTION OF LOW TEMPERATURE

In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigeration circuit.

Features
Product

Serviceability

Powerful Mode for quick cool/heat


Compressor operating frequency control to maintain
desired room temperature
Automatic Restart after power failure
Washable front panel
Power Monitor Display
Standby Control
High COP (new compressor and indoor heat
exchanger)
Vertical and Horizontal Airflow Auto Swing
Auto change over of Automatic Operation mode

Self diagnosis
Test Run at both Cooling and Heating rated frequency

Quality Improvement
High power supply voltage protection
Low power supply voltage protection
Gas leakage detection

Untitled-1

6/20/00, 4:18 PM

CS-G93KE

Functions
Remote Control

OFF / ON
L

TEMP

Operation OFF / ON

Room Temperature Setting


Temperature Setting (16C to 30C).

MODE

Operation Mode Selection

POWERFUL

FAN SPEED

TIMER
ON OFF

Automatic Operation Mode


Heating Operation Mode
Cooling Operation Mode
Soft Dry Operation Mode
Fan Operation Mode

HEAT
COOL
DRY
FAN

Timer Operation Selection


24-hour, OFF / ON Real Timer Setting.

Time / Timer Setting


Hours and minutes setting.

Powerful Mode Operation

SET
CANCEL

Indoor Fan Speed Selection


h j k
l
h j k
ll
h j k
lll
h j k
llll
h j k
lllll
AUTO FAN

Timer Operation Set / Cancel


ON Timer and OFF Timer setting and
cancellation.

Low
CLOCK

Medium
Medium

Clock Setting
Current time setting.

Medium+
SLEEP

Sleep Mode Operation OFF / ON

High
Automatic Fan Speed

WIDE/
SPOT

AIR SWING

WIDE / SPOT

Airflow Direction Control

POWERFUL

POWER SLEEP TIMER


HIGH

P O W E R LOW
MONITOR

Vertical Airflow Direction Control

WIDE Horizontal Airflow


Direction

Automatic Control

AUTO

POWERFUL

POWER SLEEP TIMER


HIGH

P O W E R LOW
MONITOR

Manual Control

SPOT Horizontal Airflow


Direction

Horizontal Airflow Direction Control


AUTO

Automatic Control
Manual Control
2

Untitled-1

6/20/00, 4:18 PM

MAC9609040C2

CS-G93KE

Functions
Indoor Unit

FOR ALL OPERATIONS


POWER L

Power Switch OFF / ON L

Power Monitor Display *


Lights up during compressor operation.

AUTO
OFF / ON

Automatic Operation Switch


Operation Mode

Used when the remote control cannot be


used.

Automatic, Heating, Cooling, Soft Dry and


Fan Operation.

Remote Control Signal Receiving


Sound Control OFF/ON *

Automatic Restart Control *

It can be controlled by pressing Automatic


Operation Switch for 10 seconds.
TEST RUN
OFF / ON

Operation is restarted after power failure at


previous setting mode.

Sleep Operation Mode *

Test Run Operation


Used when test running or servicing.
Compressor operation: rated frequency
Cooling: 50Hz (CS-G93KE), 70Hz (CS-G123KE)
Heating: 71Hz (CS-G93KE), 90Hz (CS-G123KE)

Timer Operation *

Powerful Mode *

Operation Indication Lamps

For quick cooling or heating

Lights up in operation,
blinks in Automatic
Operation judging
and Hot Start operation.
TIMER (Orange)
Lights up in Timer
Setting.
Blinks in Self Diagnosis Control.
SLEEP (Orange)
Lights up in Sleep
Mode Operation.
POWERFUL (Orange) Lights up when
Powerful mode is
selected
POWER

(Red)

Indoor Fan Speed Control *

Airflow Direction Control *

Untitled-1

6/20/00, 4:18 PM

CS-G93KE

Functions

CS-G93KE

CS-G93KE

Functions

Functions
Outdoor Unit

COOLING/SOFT DRY OPERATION


Deodorizing Control *

Room Temperature Control *

HEATING OPERATION

AUTOMATIC OPERATION

Anti-Cold Draft Control *

Outdoor Fan Motor


6 poles induction motor, 1 speed.

Compressor Operation Frequency


Operation Mode CS-G93KE

Sensible Heat Control *

CS-G123KE

Cooling

15 64 Hz

15 92 Hz

Soft Dry

15 22 Hz

15 22 Hz

Heating

15 99 Hz

15 115 Hz

Low Frequency Operation


Protection *

Hot Start *

FAN OPERATION
Minimum Frequency Operation
Protection *

Time Delay Safety Control *


Anti-Fog Discharge Control *

Intake Air Temperature Control *


Forced Operation 30 seconds *

Anti-Dew Formation Control *

Temperature Shift *

Outdoor Air Temperature


Control *

High Pressure Control *


High Pressure Control *
(For Cooling/Soft Dry)

Self Diagnosis *

Anti-Freezing Control *

Standby Control *

Low Pressure Control *


(Gas Leakage Detection)

Quiet Operation *

Deice Operation *

Low/High Power Supply Voltage


Protection *

Detect outdoor ambient temperature


and limits compressor operating
frequency

DC Peak *

Standby Control *

Total Running Current Control *

Deice Operation *

Compressor Overheating
Protection *

Indoor Power Relay Control *


IPM (Power Transistor)
Overheating Protection *
* Details can be refered to OPERATION
DETAIL in this manual.

Untitled-1

6/20/00, 4:29 PM

MAC9609040C2

CS-G93KE

CS-G93KE

Product Specifications

Product Specifications
Unit
kW
Btu/h
kW
Btu/h
s/h
Pint/h
Phase
V
Cycle
OUTLET

Cooling Capacity
Heating Capacity
Moisture Removal
Power Source

Airflow Method

CU-G93KE
2.6 (0.70 - 3.00)
8,800 (2,300 - 10,200)
3.6 (0.63 - 5.00)
12,200 (2,100 - 17,000)
1.6
3.4
Single
230
50
TOP VIEW
SIDE VIEW

INTAKE

Air Volume

Indoor Air (Lo)

m3/min (cfm)

Indoor Air (Me)

m3/min (cfm)

Indoor Air (Hi)

m3/min (cfm)

Outdoor Air

m3/min (cfm)

Noise Level
Electrical
Data

dB (A)
kW

Input
Running Current

W/W

COP
Starting Current
Piping Connection Port
(Flare piping)
Pipe Size
(Flare piping)
Drain
Inner diameter
Hose
Length
Power Cord Length
Number of core-wire
Height
Dimensions
Width
Depth
Net Weight
Compressor
Type
Motor
Rated
Air Circulation
Motor

Fan
Speed

Type
Output
Type
Material
Type
Input
Rated Output
Lo (Cool/Heat)
Me (Cool/Heat)
Hi (Cool/Heat)

A
inch
inch
inch
inch
mm
m

inch (mm)
inch (mm)
inch (mm)
lb (kg)

W
W
rpm
rpm
rpm

Untitled-1

Cooling
Heating
Cooling
Heating
Cooling
Heating

;
;
;
;
;
;

7.0 (250)
7.6 (270)
8.8 (310)
9.4 (330)
10.0 (350)
10.8 (380)

34.1 (1200)

Product Specifications
CS-G93KE
CU-G93KE
Evaporator
Condenser
Copper
Copper
Aluminium
Aluminium
Corrugated Fin
Slit Fin
(Plate fin configuration, forced draft)
1/20
2/14
19
21
614 294 25.4
782.9 508 22

Capillary Tube
SUNISO 4GDID or

ATMOS M60 (350)

780 (27.5)
Electronic Control

Electronic Control
Electronic Control

C1,C2 ; 1033, C3 ; 400

C1,C2 ; 4.8, C3 ; 23.6

C1,C2 ; 1.2, C3 ; 1.8


P.P.

Honeycomb

2.0 F, 400 VAC

Unit

CS-G93KE

Heat
Exchanger

Description
Tube material
Fin material
Fin Type
Row / Stage

FPI
Size (W H L)
Refrigerant Control Device

mm

Refrigeration Oil

(c.c)

Refrigerant (R-22)
Thermostat
Protection Device
Length
Capillary Tube Flow Rate
Inner Diameter
Material
Air Filter
Style
Fan Motor Capacitor

CS-G93KE

g (oz)

mm
s/min
mm

F, VAC

Cooling Capacity
Heating Capacity
Moisture Removal
Power Source

CU-G123KE
3.45 (0.74 - 4.00)
11,700 (2,500 - 13,600)
4.80 (0.70 - 6.50)
16,300 (2,300 - 22,100)
2.0
4.2
Single
230
50
SIDE VIEW
TOP VIEW

OUTLET

Airflow Method

INTAKE

Air Volume

Specifications are subject to change without notice for further improvement.

Cooling ; 46
Cooling ; High 38, Low 30
Heating ; 47
Heating ; High 39, Low 30
Cooling ; 0.73 (0.21 - 0.99)
Heating ; 0.99 (0.20 - 1.40)
Cooling ; 3.75 (max. 6.76)
Heating ; 4.80 (max. 6.76)
Cooling ; 3.56
Heating ; 3.64
4.80
G ; 3-way valve 3/8"
G ; Half Union 3/8"
L ; 2-way valve 1/4"
L ; Half Union 1/4"
G (gas side) ; 3/8"
G (gas side) ; 3/8"
L (liquid side) ; 1/4"
L (liquid side) ; 1/4"

12

0.7

2.1 m
3 core wires 1.0 mm2

10-31/32 (279)
21-9/32 (540)
27-17/32 (699)
31-15/32 (799)
11-7/32 (285)
7-15/32 (190)
86 (39)
20 (9.0)
Rotary (2 cylinders)

rolling piston type


Induction (4-poles)

500
Propeller Fan
Cross-flow Fan
P.P + (Mica + Glass Fiber) 30%
AS + Glass Fiber 30%
Induction (6-poles)
Transistor (4-poles)
64

20
20

980/1,010

1,160/1,220
760
1,280/1,380

CS-G123KE

Unit
kW
Btu/h
kW
Btu/h
s/h
Pint/h
Phase
V
Cycle

Indoor Air (Lo)

m3/min (cfm)

Indoor Air (Me)

m3/min (cfm)

Indoor Air (Hi)

m3/min (cfm)

Outdoor Air

m3/min (cfm)

Noise Level
Electrical
Data

dB (A)
kW

Input
Running Current

W/W

COP
Starting Current
Piping Connection Port
(Flare piping)
Pipe Size
(Flare piping)
Drain
Inner diameter
Hose
Length
Power Cord Length
Number of core-wire
Height
Dimensions
Width
Depth
Net Weight
Compressor
Type
Motor
Rated
Air Circulation

Motor

Fan
Speed

Type
Output
Type
Material
Type
Input
Rated Output
Lo (Cool/Heat)
Me (Cool/Heat)
Hi (Cool/Heat)

A
inch
inch
inch
inch
mm
m

inch (mm)
inch (mm)
inch (mm)
lb (kg)

W
W
rpm
rpm
rpm

6/20/00, 4:29 PM

MAC9609040C2

Cooling ; 9.0 (320)


Heating ; 9.0 (320)
Cooling ; 10.4 (370)
Heating ; 10.4 (370)
Cooling ; 11.2 (400)
Heating ; 11.6 (410)

31.5 (1110)

Cooling ; High 41, Low 35


Cooling ; 48
Heating ; High 41, Low 35
Heating ; 50
Cooling ; 1.05 (0.22 - 1.33)
Heating ; 1.41 ( 0.22 - 2.00)
Cooling ; 5.00 (max. 8.96)
Heating ; 6.30 (max. 8.96)
Cooling ; 3.29
Heating ; 3.40
6.3
G ; Half Union 1/2"
G ; 3-way valve 1/2"
L ; Half Union 1/4"
L ; 2-way valve 1/4"
G (gas side) ; 1/2"
G (gas side) ; 1/2"
L (liquid side) ; 1/4"
L (liquid side) ; 1/4"

12

0.7

2.1 m

3 core wires 1.5 mm2


10 - 31/32 (279)
21 - 9/32 (540)
31-15/32 (799)
27 17/32 (699)
7 - 15/32 (190)
11 - 7/32 (285)
20 (9.0)
95 (43.0)

Rotary (2 cylinders)
rolling piston type

Induction (4-poles)

500
Cross-flow Fan
Propeller Fan
AS + Glass Fiber 30%
P.P + (Mica + Glass Fiber) 30%
Transistor (4-poles)
Induction (6-poles)

67
20
25
1,170/1,200

1,320/1,360

1,410/1,480
790

CS-G93KE

Product Specifications
Unit
Heat
Exchanger

FPI
Size (W H L)
Refrigerant Control Device

mm

Refrigeration Oil

(c.c)

Refrigeration (R-22)
Thermostat
Protection Device
Length
Capillary Tube Flow Rate
Inner Diameter
Material
Air Filter
Style
Fan Motor Capacitor

CU-G123KE
Condenser
Copper
Aluminium
Corrugated Fin
(Plate fin configuration, forced draft)
2/14
2/20
21
16
693.5 508 44
614 294 25.4
Capillary Tube

SUNISO 4GDID or

ATMOS M60 (350)

1,070 (37.8)

Electronic Control
Electronic Control
Electronic Control
C1,C2 ; 720, C3 ; 420

C1, C2 ; 7.2, C3 ; 14.4

C1, C2 ; 1.3, C3 ; 1.5

P.P.

Honeycomb

2.0 F, 400 VAC


CS-G123KE
Evaporator
Copper
Aluminium
Slit Fin

Description
Tube material
Fin material
Fin Type
Row / Stage

g (oz)

mm
s/min
mm

F, VAC

Specifications are subject to change without notice for further improvement.

10

Untitled-2

10

6/20/00, 4:33 PM

MAC9509078C2

CS-G93KE

Dimensions
CS-G93KE / CS-G123KE
Unit : mm

<Front View>

190

60

799

Left piping
hole

36

279

Air intake
direction

Right piping hole

Air outlet
direction

60

58

60

83

Remote control transmitter


65
18
GAS SIDE

<Back View>

LIQUID SIDE

65

DRAIN PORT

122

TEMP
C

POWERFUL

425

48

Relative position between the indoor unit and the installation plate <Front View>
Slot (2 places)
Slot (2 places)

Centre notch
(40)

17.8

100

350

100

Arrow
Arrow

Centre

Right piping hole

Indoor unit
external
dimensions
line

(60)

(99)

Left piping hole

11

Untitled-2

16.5

550

257.2

Installation
plate

(49)

710

11

6/20/00, 4:33 PM

CS-G93KE

Dimensions
CU-G93KE / CU-G123KE

699
100

69

500

99

(52)

32

Space necessary for installation

162

(120)

10 cm

10 cm

100 cm

Anchor Bolt Pitch


323 x 500

285

540

7.5

67

High Pressure
2-Ways Valve

67

Low Pressure
3-Ways Valve

11

(323)
347

12

Untitled-2

12

6/20/00, 4:33 PM

MAC9509078C2

CS-G93KE

Refrigeration Cycle Diagram


CS-G93KE / CU-G93KE
CS-G123KE / CU-G123KE
INDOOR

OUTDOOR

C1
CHECK VALVE

2-WAY
VALVE

C2

C3

INTAKE AIR
TEMP.
SENSOR

OUTDOOR AIR
TEMP.
SENSOR

HEAT
EXCHANGER
TEMP.
SENSOR

HEAT EXCHANGER
(EVAPORATOR)

HEAT EXCHANGER
(CONDENSER)
4-WAY VALVE
3-WAY
VALVE

COMPRESSOR
TEMP.
SENSOR
COOLING

COMPRESSOR

C1, C2, C3; CAPILARRY TUBE

HEATING

13

Untitled-2

13

6/20/00, 4:33 PM

HEAT
EXCHANGER
TEMP.
SENSOR

Untitled-2

SINGLE
PHASE
230V
50Hz

14

"C"

6/20/00, 4:33 PM

ELECTRONIC
CONTROLLER

Indicates the electronic controller.

ZNR

FUSE
(3.15A)

RY-PWR

INDOOR UNIT

DC/DC
CONVERTOR

Indicates the number of core wires.(Example: 5C=5 core wires)

THERMAL
FUSE
102C

POWER
SUPPLY
SWITCH

CS-G93KE / CU-G93KE
CS-G123KE / CU-G123KE

9C

3C

5C

5C

5C

4C

3C

POWER MONITOR
& INDICATOR

RECEIVER

ASM
UP/DOWN

ASM
RIGHT

ASM
LEFT

SENSOR

FAN
MOTOR

2
3

WIRELESS
REMOTE CONTROL
TRANSMITTER

1
FUSE
(20A)

FUSE
3.15A

4-WAY
VALVE

CT

SSR
C-FM

FAN
MOTOR
FM

CR1

CR2

RY-FM

RY-PWR

OUTDOOR UNIT

DIODE

ELECTRIC
RESISTOR

CU-G123K
ONLY

ELECTRONIC
CONTROLLER

POWER
SWITCHING
SOURCE

FUSE
3.15A

IPM

COMPRESSOR

CS-G93KE

Block Diagram

14

MAC9509078C2

NOISE FILLTER

CS-G93KE

Wiring Diagram
CS-G93KE / CU-G93KE
POWER SUPPLY CORD

STANBY CONTROLLER REMOTE CONTROLLER PUMP DOWN SW.


ON-OFF SW.
NO. SW.
(TEST RUN)

AUTO SW.

1 35

MOTOR

WIRELESS
REMOTE
CONTROL

ZNR

ELECTRONIC
CONTROLLER
(RECEIVER)
CN-RCV (W)

RY-PWR

SENSOR
SENSOR
(AIR TEMP.) (PIPE TEMP.)

MOTOR
(LEFT)

MOTOR
(RIGHT)
CN-DISP2 (W)

TERMINAL
COMPLETE

123456789

P Y O R BR

Y/G

MOTOR
(FLAP)

P Y O R BR

W
W
W

P Y O R BR

CN-RCV2 (W)

54321

1234

CN-STM1 (B)

54321

CN-TH1 (W)

CN-STM2 (Y)

54321

CN-PWR1 (B)

16

16

123
3
2
1

CN-STM3 (W)

MAIN SW.

ELECTRONIC CONTROLLER
FUSE
T 3.15A L 250V

3 21

R B Y

CN-MTR1 (G)

BR

W W W W W WW WW

987654321

TERMINAL

CN-DISP1 (W)
Y/G

DISPLAY, SELF-DIAGNOSIS
POWER MONITOR DISPLAY

1 2 3
THERMAL FUSE
102C (3A)

REMARKS
B: BLUE BR: BROWN W: WHITE G: GREEN
P: PINK Y: YELLOW O: ORANGE
BL: BLACK R: RED Y/G: YELLOW/GREEN

TO OUTDOOR UNIT

Resistance of Outdoor Fan Motor Windings


CONNECTION

CWA95384 ()

BLUE - YELLOW

264.1

YELLOW - RED

304.8

Resistance of Compressor Windings


CONNECTION

2RD132X5BB03()

U-V

0.8

U-W

0.8

V-W

0.8

15

Untitled-2

15

6/20/00, 4:33 PM

CS-G93KE

Wiring Diagram
CS-G123KE / CU-G123KE
POWER SUPPLY CORD

STANBY CONTROLLER REMOTE CONTROLLER PUMP DOWN SW.


ON-OFF SW.
NO. SW.
(TEST RUN)

AUTO SW.

1 35

MOTOR

WIRELESS
REMOTE
CONTROL

ZNR

ELECTRONIC
CONTROLLER
(RECEIVER)
CN-RCV (W)

RY-PWR

SENSOR
SENSOR
(AIR TEMP.) (PIPE TEMP.)

MOTOR
(LEFT)

MOTOR
(RIGHT)
CN-DISP2 (W)

TERMINAL
COMPLETE

123456789

P Y O R BR

Y/G

MOTOR
(FLAP)

P Y O R BR

W
W
W

P Y O R BR

CN-RCV2 (W)

54321

1234

CN-STM1 (B)

54321

CN-TH1 (W)

CN-STM2 (Y)

54321

CN-PWR1 (B)

16

16

123
3
2
1

CN-STM3 (W)

MAIN SW.

ELECTRONIC CONTROLLER
FUSE
T 3.15A L 250V

3 21

R B Y

CN-MTR1 (G)

BR

W W W W W WW WW

987654321

TERMINAL

CN-DISP1 (W)
Y/G

DISPLAY, SELF-DIAGNOSIS
POWER MONITOR DISPLAY

1 2 3
THERMAL FUSE
102C (3A)

REMARKS
B: BLUE BR: BROWN W: WHITE G: GREEN
P: PINK Y: YELLOW O: ORANGE
BL: BLACK R: RED Y/G: YELLOW/GREEN

TO OUTDOOR UNIT

Resistance of Outdoor Fan Motor Windings


CONNECTION

CWA95380 ()

BLUE - YELLOW

234.1

YELLOW - RED

263.5

Resistance of Compressor Windings


CONNECTION

2RD132X5BA03 ()

U-V

0.8

U-W

0.8

V-W

0.8

16

Untitled-2

16

6/20/00, 4:33 PM

MAC9509078C2

CS-G93KE

Operation Details
A. FUNCTIONS
1. TEMPERATURE SHIFT
Once the operation starts, the remote control setting temperature will be shifted internally based on the setting fan
speed and outdoor air temperature. In addition, if Sleep Mode or Powerful Mode are set, the temperature shift will
be carried out.
Setting of Internal Setting Temperature
The internal setting temperature can be decided as follows:
Remote control setting temperature
+
Outdoor temperature shift (refer Table a)
+
Fan speed shift (+ 1.0 C)
+
Any Sleep Mode shift operation?
+
Any Powerful Operation shift? (refer Table b)
+
[Check upper/lower (33C/16C) limit for setting temperature]

INTERNAL SETTING TEMPERATURE


Table a
Setting Temperature Shift based on outdoor air temperature.
(i) Cooling, Soft Dry
(ii) Heating
Shift amount

Shift amount

38C Outdoor air temperature

CSG93KE
1.0C

CSG123KE
1.0C

30C Outdoor air temperature < 38C

0.5C

23C Outdoor air temperature < 30C


Outdoor air temperature < 23C

21C Outdoor air temperature

1.5C

17C Outdoor air temperature < 21C

1.0C

1.0C

13C Outdoor air temperature < 17C

1.0C

0.0C

0.0C

9C Outdoor air temperature < 13C

0.0C

+1.0C

+1.0C

5C Outdoor air temperature < 9C

+0.5C

1C Outdoor air temperature < 5C

+1.0C

3C Outdoor air temperature < 1C

+1.0C

Outdoor air temperature < 3C

+1.5C

Table b
Powerful Mode Shift.

Powerful

Cooling

Dry

Heating

4.0C

3.0C

+6.0C

17

Untitled-3

17

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details
2. COOLING OPERATION
A. Room Temperature Control
(i) When the remote control setting temperature is less than 24C.
Cooling

Compressor Operation Frequency (Hz)

Intake air temp.


Internal setting
temp. (C)

+1.5
+1.0
+0.5

Internal setting temp.

0
0.5

Compressor OFF temp. 1.0

Outdoor Air Temperature

64 (Fc max) or 50

64 (Fc max) or 50

92 (Fc max) or 70

92 (Fc max) or 70

36

40

44

49

31

31

31

31

15

22

16

22

15

15

15

16

15

15

15

15

Comp OFF

Comp OFF

Comp OFF

Comp OFF

Less than 38C

38C and above

Less than 38C

38C and above

Model No.

CS-G93KE

CS-G123KE

(ii) When the remote control setting temperature is 24C and above.
Cooling

Compressor Operation Frequency (Hz)

Intake air temp.


Internal setting
temp. (C)

+1.5
+1.0
+0.5

Internal setting temp.

0
0.5

Compressor OFF temp. 1.0

Outdoor Air Temperature


Model No.

64 (Fc max) or 50

64 (Fc max) or 50

92 (Fc max) or 70

92 (Fc max) or 70

36

36

44

44

31

31

31

31

15

15

16

16

15

15

15

15

15

15

15

15

Comp OFF

Comp OFF

Comp OFF

Comp OFF

Less than 38C

38C and above

Less than 38C

38C and above

CS-G93KE

CS-G123KE

Compressor OFF temperature = Compressor ON temperature.

The operation frequency can be changed every 30 seconds.

30 minutes from the start of the operation, the compressor is operating at Fc max Hz.

The compressor stops when the intake air temperature reaches 1C below internal setting temperature and
continues for 3 minutes.

When the compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)

When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation.

When the compressor stops, the outdoor fan motor stops 30 seconds later.

18

Untitled-3

18

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details
B. Deodorizing Control

This control is available during automatic fan speed for Cooling and Soft Dry Operation. It is not available
during anti-freezing control.
Deodorizing Status

Compressor

ON

Time (second)
Indoor Fan Speed

40

50

OFF

SLo

6, 7, 6, 7,

OFF

Auto

1
ON

30

60

30

60

40

SLo

OFF

SLo

OFF

OFF

ON

ON
OFF

Compressor

OFF

Indoor
Fan Speed

When the compressor is in operation, the deodorizing status starts from 1 2 3.

When the compressor stops operation, the deodorizing status starts from 4 5 6 7.

If the compressor still stops operation after 3 minutes, the deodorizing status will start from 6.

C. Sensible Heat Control


This control is to improve the feeling in high fan speed during low operation frequency. When the operation
frequency is less than 33Hz (CU-G93KE) or 36Hz (CU-G123KE), the fan speed will reduce. When the
operation frequency is increased to 40Hz (CU-G93KE) or 49Hz (CU-G123KE) continuously for 5 minutes,
the fan speed will resume to normal condition.

19

Untitled-3

19

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details
3. SOFT DRY OPERATION
A. Room Temperature Control
At the start of operation, cooling operation is running until the intake air temperature is 0.5C higher than internal
setting temperature, then the operation will shift to Soft Dry with indoor fan speed SLo.

Soft Dry

Compressor Operation Frequency (Hz)

Intake air temp.


Internal setting
temp. (C)

Cooling Operation
+1.0
+0.5

Internal setting temp.

Cooling Operation

+1.5

22

22

22

22

15

15

16

16

15

15

15

15

15

15

15

15

Comp OFF

Comp OFF

Comp OFF

Comp OFF

0.5

Compressor OFF temp. 3.5

When the
temperature falls

Condition
Model No.

When the
temperature rises

When the
temperature falls

CS-G93KE

When the
temperature rises

CS-G123KE

Compressor OFF temperature = Compressor ON temperature.

The operation frequency changes every 30 seconds.

30 minutes from the start of the operation, the compressor is operating at Fc max Hz.

The Compressor stops when the intake air temperature reaches 3.5C below internal setting temperature and continues
for 3 minutes.

When the compressor stops operation, indoor fan stops for 330 seconds.

When the Compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)

When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation
immediately.

When the Compressor stops, the outdoor fan motor stops 30 seconds later.

20

Untitled-3

20

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details
B. Deodorizing Control

This control is available during automatic fan speed for Cooling and Soft Dry Operation. It is not available
during anti-freezing control.

Deodorizing Status

Compressor

ON

Time (second)
Fan Speed

4, 5, 4, 5,

OFF

40
OFF

SLo

1
ON

330

30

60

40

OFF

SLo

OFF

OFF

ON

ON

OFF
Compressor

ON

ON
OFF

OFF
Fan Speed

When the compressor is in operation, the deodorizing status starts from 1 2.

When the compressor stops operation, the deodorizing status starts from 3 4 5.

When the compressor stops operation, indoor fan stops for 330 seconds.

C. Sensible Heat Control

This control is to improve the feeling in high fan speed and low operation frequency. When the operation
frequency is less than 33Hz (CU-G93KE) or 36Hz (CU-G123KE), the fan speed will reduce. When the
operation frequency is increased to 40Hz (CU-G93KE) or 49Hz (CU-G123KE) continuously for 5 minutes,
the fan speed will resume to normal condition. (During Cooling operation).

21

Untitled-3

21

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details
4. HEATING OPERATION
A. Room Temperature Control

During heating operation, the room temperature control depends on intake air temperature and internal
setting temperature. Basically it can be divided into 2 periods as shown below:

Intake air temp. internal setting temp.

0C

Stabilized
period

Transition
period

1.5C

(i) When indoor fan speed is Medium or above.

CS-G93KE
Heating Operation

Compressor Operation Frequency (Hz)


Transition Period

Remote Control Setting Temp.

16C ~ 30C

Intake air temperature


Internal setting temperature
Compressor OFF

Stabilized Period
16C ~ 20C

21C ~ 30C

Comp Off

Comp Off

Comp Off

Comp Off

Comp Off

15

15

15

15

15

15

15

15

26

15

22

22

22

33

22

46

26

26

36

26

53

33

33

46

33

64

36

36

53

36

+1.5
+1.0
+0.5

Internal setting temp.

0
0.5
1.0
1.5

Outdoor air temperature

71 (Fh) or
99 (Fhmax)

71 (Fh) or
99 (Fhmax)

71 (Fh) or
99 (Fhmax)

71 (Fh) or
99 (Fhmax)

71 (Fh) or
99 (Fhmax)

Less than
1C

1C and
above

Less than
1C

1C and
above

22

Untitled-3

22

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details
CS-G123KE
Heating Operation

Compressor Operation Frequency (Hz)


Stabilized Period

Transition Period
Remote Control Setting Temp.

16C ~ 30C

Intake air temperature


Internal setting temperature
Compressor OFF

21C ~ 30C

16C ~ 20C

Comp Off

Comp Off

Comp Off

Comp Off

Comp Off

16

16

16

16

16

16

16

16

27

16

22

22

22

36

22

64

27

27

44

27

74

36

36

64

36

86

44

44

74

44

+1.5
+1.0
+0.5

Internal setting temp.

0
0.5
1.0
1.5
90 (Fh) or
115 (Fhmax)

90 (Fh) or
90 (Fh) or
90 (Fh) or
90 (Fh) or
115 (Fhmax) 115 (Fhmax) 115 (Fhmax) 115 (Fhmax)
Less than
1C

Outdoor air temperature

1C and
above

Less than
1C

1C and
above

(ii) When indoor fan speed is lower than Medium

CS-G93KE
Heating Operation

Compressor Operation Frequency (Hz)


Transition Period

Remote Control Setting Temp.

16C ~ 30C

Intake air temperature


Internal setting temperature
Compressor OFF

21C ~ 30C

16C ~ 20C

Comp Off

Comp Off

Comp Off

Comp Off

Comp Off

15

15

15

15

15

15

22

22

26

22

22

26

26

33

26

46

33

33

36

33

53

36

36

46

36

64

46

46

53

46

+1.5
+1.0
+0.5

Internal setting temp.

Stabilized Period

0
0.5
1.0
1.5

71 (Fh) or
99 (Fhmax)

Outdoor air temperature

71 (Fh) or
99 (Fhmax)

71 (Fh) or
99 (Fhmax)

71 (Fh) or
99 (Fhmax)

71 (Fh) or
99 (Fhmax)

Less than
1C

1C and
above

Less than
1C

1C and
above

23

Untitled-3

23

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details
CS-G123KE
Heating Operation

Compressor Operation Frequency (Hz)


Transition Period

Remote Control Setting Temp.

16C ~ 30C

Intake air temperature


Internal setting temperature
Compressor OFF

Stabilized Period
21C ~ 30C

16C ~ 20C

Comp Off

Comp Off

Comp Off

Comp Off

Comp Off

16

16

16

16

16

16

22

22

27

22

22

27

27

36

27

64

36

36

44

36

74

44

44

64

44

86

64

64

74

64

+1.5
+1.0
+0.5

Internal setting temp.

0
0.5
1.0
1.5

90 (Fh) or
115 (Fhmax)

90 (Fh) or
90 (Fh) or
90 (Fh) or
90 (Fh) or
115 (Fhmax) 115 (Fhmax) 115 (Fhmax) 115 (Fhmax)
Less than
1C

Outdoor air temperature

1C and
above

Less than
1C

1C and
above

Compressor OFF temperature = compressor ON temperature.

The operation frequency changes every 30 seconds.

When the difference of the intake air temperature and Internal setting temperature is 1.5C or more, compressor will operate at Fh
continuously for 3 minutes and then change over to Fhmax.

The compressor stops when the intake air temperature reaches 1.5C above internal setting temperature and continues for 3 minutes.

When the compressor stops, it will not start operation for 3 minutes. (Time Delay Safety Control)

When the intake air temperature decreases to the compressor ON temperature, the compressor starts immediately.

When the compressor stops, the outdoor fan motor stops 30 seconds later.

24

Untitled-3

24

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details
B. Anti Cold Draft Control
(i) Indoor Fan Control
Indoor fan speed and airflow direction varies in accordance to the indoor heat exchanger temperature as
shown below:
a. Manual Fan speed control
(Manual Airflow Direction Control)

(Auto Airflow Direction Control)

Min Me

58C
(58C)

Remote Control
Setting Fan Speed

25C
(30C)
18C
(28C)
13C
(13C)

55C
(55C)

Remote Control
Setting Fan Speed

37C
(37C)

Lo-

24C
(29C)

SLo

15C
(21C)
9C
(9C)

Stop

Min Me

58C
(58C)

Indoor heat
exchanger temp.

28C
(28C)
13C
(13C)

55C
(55C)

Lo-

29C
(29C)

SLo

21C
(21C)
9C
(9C)

Stop

Indoor heat
exchanger temp.

b. Auto Fan Speed Control


(Auto Airflow Direction Control)

52C
(52C)
37C
(37C)

Max
UP

(Manual Airflow Direction Control)

Max or
Up

DOWN
32C
(32C)

Me

25C
(30C)

32C
(32C)

DOWN

18C
(28C)
13C
(13C)

DOWN

Lo-

24C
(29C)

SLo

15C
(21C)

Stop

9C
(9C)

Indoor heat
exchanger temp.

Note:

37C
(37C)

28C
(28C)
13C
(13C)

Lo-

29C
(29C)

SLo

21C
(21C)

Stop

9C
(9C)

Indoor heat
exchanger temp.

UP means fan speed is increased by 1 rank.


DOWN means fan speed is decreased by 1 rank.
Max means fan speed is running at maximum auto fan speed.
Temperature in ( ) is indicating when powerful mode is selected.
25

Untitled-3

25

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details
(ii) Hot Start

At the start of heating operation, the indoor fan stops and compressor operates at Fhmax frequency 99Hz
(CS-G93KE) or 115 Hz (CS-G123KE). This is to heat up the indoor heat exchanger in order to avoid cold
air discharged.

Hot Start ends when


a. Indoor heat exchanger temperature reaches over 15C
or
b. 4 minutes after heating operation starts.

After Hot Start operation, compressor operates at Fhmax 99Hz(CS-G93KE) or 115Hz (CS-G123KE) for
2 minutes.

(iii)Vertical and Horizontal Airflow Direction Control

Vertical and horizontal airflow direction control is in accordance to indoor heat exchanger temperature.
This control is valid for automatic airflow direction only.

C. Deice Operation
Deice operation occurs when the deice operation starting signal is generated. This happens when one of the
following conditions occurs. However, the first deice operation will begin 1 hour after start of heating operation.
Outdoor Heat Exchanger
Temp. Th < 3C

Outdoor Heat Exchanger


Temp. (Th)

Outdoor Temp. (To)

Case 1

120 minutes
continuously

Th < -6C for 3 min


continuously

To > 1C

Case 2

80 minutes
continuously

Th < -7C for 3 min


continuously

To > 1C

Case 3

40 minutes
continuously

Th < -9C for 3 min


continuously

To 3C

Case 4

40 minutes
continuously

Th < -11C for 3 min


continuously

To < 3C

Note: The above 4 cases are under compressor operating condition.

26

Untitled-3

26

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details
Deice Operation Time Chart
Outdoor Heat
Exchanger
Temperature (C)
Deice Operation
Ending
Signal

16
30 sec

30
sec

Deice max 11 min

Heating
Operation

30 sec

Heating
Operation

Deice
Operation
Starting
Signal

7
9
11

40Hz (CU-G93KE)
49Hz (CU-G123KE)

58Hz (CU-G93KE)
83Hz (CU-G123KE)

99Hz
(CU-G93KE)

Compressor operating
frequency

Free

Indoor Fan

ON

ON

OFF

OFF

OFF

Hot Start

Outdoor Fan

ON

ON

OFF

OFF

OFF

ON

4-way valve

ON

ON

OFF

OFF

OFF

ON

OFF

115Hz
(CU-G123KE)

Compressor frequency is set at 40Hz (CU-G93KE) or 49Hz (CU-G123KE) when the deice operation starting signal is
generated.
30 seconds later deice operation starting signal is generated, indoor fan, outdoor fan, 4-way valve are turned off and
compressor operates at 40Hz (CU-G93KE) or 49Hz (CU-G123KE) for 30 seconds. (Deice operation starts)
During deice operation, the compressor operating frequency is set at 58Hz (CU-G93KE) or 83Hz (CU-G123KE).
Deice will end when the outdoor heat exchanger temperature rises to 16C or after 11 minutes.

27

Untitled-3

27

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details
D. Standby Control
(a) The purpose of Standby Control is to warm up the compressor when outdoor temperature is low.
The standby control will be activated when all of the followings occur.
(i) Main power switch is ON.
(ii) Unit is not operating.
(iii)Outdoor ambient temperature is below 3C.
(iv)Compressor stops more than 3 hours.
(v) Standby switch at indoor electronic controller is ON.
(The standby switch is at ON position during product delivery from factory).
(b) When the standby control is activated, low electricity will be supplied to compressor for 1 minute and stops
for 4 minutes. This condition is repeated until standby control is cancelled. It will consume about 35 W of
electric power.
Electricity supplied
to compressor
Time

ON

OFF

ON

OFF

1 min

4 min

1 min

4 min

(c) Standby control will be cancelled when one of the following conditions occurs.
(i) Unit starts operation.
(ii) Outdoor ambient temperature 5C.
(iii)Compressor starts operation.
(iv)Standby switch at indoor electronic controller is switched to OFF.
(v) Protection control is activated.
(d) When the unit is switched on by the remote control, the compressor operates at frequency as shown in
below:Frequency
CS-G93KE

Max. 36Hz
Min. 33Hz

Max. 36Hz

Max. 71Hz

Free

CS-G123KE

Max. 44Hz
Min. 36Hz

Max. 44Hz

Max. 90Hz

Free

Time (sec)

60

120

180

(e) The standby control can be cancelled by switching off the standby switch (SW2) at indoor electronic
controller.

28

Untitled-3

28

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details
5. FAN OPERATION
This operation is to enable the fan operation without compressor running. Timer operation is valid for fan operation.

6. AUTOMATIC OPERATION
When the Automatic mode is selected, the operation mode is decided in accordance to remote control setting
temperature, intake air temperature and outdoor air temperature.

During judging the operation mode, indoor fan is running at Lo speed and outdoor fan at ON in order to sense
the indoor intake air temperature and outdoor air temperature for 20 seconds. At this time, Power LED is blinking.
After the operation mode is selected, Power LED lights up.
Refer to the examples below, there are 4 determination charts when automatic mode is selected.
(a) When setting temperature of remote control is 18C and below.

(b) When setting temperature of remote control is 19C ~ 22C.

29

Untitled-3

29

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details
(c) When setting temperature of remote control is 23C ~ 26C.

(d) When setting temperature of remote control is 27C and above.

30

Untitled-3

30

6/20/00, 5:03 PM

MAC9509078C2

CS-G93KE

Operation Details

When the operation mode is changed over, the value for t1, t2 and t3 are shifted as follows:
Cooling/Soft dry Heating:
2C
Heating Cooling/Soft dry:
+2C

When the indoor intake air temperature is lower than 16C, heating operation is immediately started.

When the outdoor air temperature is more than 25C, and the intake air temperature is over 16C, cooling
operation is immediately started.

The operation mode is judged every 30 minutes.

When the operation mode (Heating, Cooling or Soft Dry) is decided, the internal setting temperature will shift
as shown below:

Remote Control Setting temperature


+
Outdoor temperature shift
+
Fan speed shift
+
Automatic mode shift
+
Cooling

+0.75C

Soft Dry

0C

Heating

0.75C

INTERNAL SETTING TEMPERATURE

31

Untitled-3

31

6/20/00, 5:03 PM

MAC9509078C2

Untitled-4
32

24.0

24.4

27.1
27.8

30.7
30.8

33.0
33.4

18.4

18.7

19.3
20.1
21.4
22.0
22.7
23.0

23.1
23.5

24.3
25.0
25.3
26.0
26.4
26.4
26.5
27.3
27.6
28.0
28.3
29.0
29.3
29.8
29.8

32.7

8
9
10
11
12
13

14
15

16

32

6/20/00, 5:08 PM

17
18
19
20
21
22
23
24
25
26
27
28

33

29
30

31

36.9

32.6

32.6

32.3

31.9

31.5

31.1

30.5

30.1

29.8

29.8

29.1

28.8

28.4

28.3

28.3

26.4

23.4

21.7

17.9

20.3

17.6

17.6

16.3

16.3

15.6

Hi

Me

Me

Me

Lo

OFF

Auto
Fan

Auto
Fan

Auto
Fan

Lo

OFF

Cooling
Voltage
Voltage
Fan
Supply to
Speed Supply to
Fan Motor Fan Motor
No.
Manual Auto
DC (V)
DC (V)
CS-G93KE CS-G123KE

7. INDOOR FAN SPEED CONTROL

Operation Details

SLo

OFF

Soft
Dry

SHi: Maximum Capacity


Operation

Manual Hi Fan + Powerful

Test Run

Manual Me Fan + Powerful


+

Auto Fan + Powerful

Manual Me Fan + Powerful


Sensible Heat Control (Hi)

Auto Fan + Powerful

Temporary Operation

Sensible Heat Control (Me+)


Auto Fan + Powerful
Sensible Heat Control +
Auto Fan

Manual Me Fan + Powerful

Auto
Fan
(Max.)

SHi

Me+

Me

SSHi: Maximum Capacity


Operation

Manual Hi Fan + Powerful


On Timer preparatory operation
+ Manual Fan + Powerful
Test Run

Auto Fan (max) + Powerful

Manual Me+ Fan + Powerful

Manual Me Fan + Powerful

Temporary operation

Manual Me Fan + Powerful

Auto Fan (min) + Powerful

Sensible Heat Control +


Auto Fan

On Timer preparatory operation


+ Auto Fan

Lo: Hot Start Control


Sleep Mode
Anti Cold Draft Control
Thermo OFF

SLo: Hot Start Control

Hot Start Control

Remarks

Manual Lo Fan + Powerful

Me

Lo

OFF

OFF

Auto
Fan
(Min.)

Auto

Manual

Heating

Sensible Heat Control (Me)

Sensible Heat Control +


Auto Fan

Manual Lo Fan + Powerful

Sensible Heat Control (Me)

Sensible Heat Control (Lo)


On Timer preparatory
operation + Auto Fan
Sleep mode (Cooling)

Auto operation mode


judgement
Quiet operation

Deodorizing control
Sleep Mode(Soft Dry)

Remarks

CS-G93KE
CS-G93KE

CS-G93KE

Operation Details

CS-G93KE

Operation Details

(a) Cooling Automatic Fan Speed

(c) Cooling Operation at SHi Speed

The Automatic Fan Speed for cooling operation is shown as below:

During Cooling operation, Indoor Fan speed is set at SHi when the following conditions occur:

(i) When Automatic Fan Speed is selected

Outside air temperature is 30C or above

Compressor operates at 50Hz (CU-G93KE) or 70Hz (CU-G123KE) and above

Remote control setting fan speed is High

Indoor intake air temperature is 24C or above

Remote control setting temperature is 16C

Within 30 minutes after start of operation.

Fan No. 15

Fan No. 13

Fan No. 11

a
10
sec.

80 sec.

(d) Heating Operation at SSHi Speed


During Heating operation, Indoor Fan speed is set at SSHi when the following conditions occur:

(ii) When Automatic Fan Speed and Powerful Mode are selected

Fan No. 17

Heating operation for 2 hours or more

When remote control setting fan speed is High

Indoor intake air temperature is 17C or above and less than 23C

Outdoor air temperature is below 4C

Remote control setting temperature is 30C

Compressor operates at 71Hz (CU-G93KE) or 90Hz (CU-G123KE) and above

Airflow Direction is set at Manual.

Fan No. 15

Fan No. 13

a
10
sec.

80 sec.

Note: The Fan Speed will change every 10 seconds and it will be repeated from a to h every 80
seconds.

8. OUTDOOR FAN CONTROL

(b) Heating Automatic Fan Speed

Outdoor fan motor is controlled with 1 speed only. Fan is in operation when the compressor starts operation
and stops 30 seconds after compressor stops operation.

The Automatic Fan Speed for heating operation is shown below:

When Automatic Fan Speed is selected, the Fan Speed will change every 10 seconds from Fan
Speed No. 7 to No. 15 depending on indoor heat exchanger temperature. Each time the Fan Speed
will move 1 rank up or down.
When Automatic Fan Speed and Powerful Mode are selected, the Fan Speed will change for every
10 seconds from Fan Speed No. 11 to No. 27 depend on heat exchanger temperature. Each time
the Fan Speed will move 1 rank up or down.

ON
Compressor

33

OFF
ON

Outdoor Fan

ON
OFF

30
sec

35

34

Untitled-4

ON

6/20/00, 5:08 PM

CS-G93KE

Operation Details
9. AIRFLOW DIRECTION
A. Vertical Airflow Direction

Vane angle setting


Vane angle

Operation
1
Heating

Cooling

Airflow direction auto

Indoor heat exchanger temperature

Airflow direction manual

Airflow direction auto

33

70

15
13

46

33

15

25

33

41

11

15

18

22

25

3 ~ 33
11 ~ 25

Anti-dew formation control

Airflow direction manual

Anti-dew formation control

18

25

33

11

15

18

22

25

33

41

Airflow direction auto

Fan

7 ~ 36

Airflow direction manual

15

25
143

Stop

70

Airflow direction auto

57

11 ~ 25

Anti-dew formation control


Soft Dry

7 ~ 36

Anti-dew formation control


Airflow direction manual

Setting angle
Cooling, Soft Dry & Fan Auto Airflow Direction

Heating Auto Airflow Direction

Horizontal
Horizontal

3
36

15

33

70

143

143

Heating

Cooling
Fan

Soft Dry

Close
positon

Close
positon

Cooling, Soft Dry & Fan Manual Airflow Direction

Heating Manual Airflow Direction

Horizontal
Horizontal

3
41

13

Heating

Cooling
Fan

Soft Dry

33
143

70
143

Close
positon

Close
positon

36

Untitled-5

36

6/20/00, 5:11 PM

MAC9509078C2

CS-G93KE

Operation Details
(a) Vertical Airflow Direction Manual
By pressing the remote control vertical airflow direction setting switch, the vane will move to the indicated
angle (1, 2, 3, 4, 5) as shown in the table. When the remote control OFF/ON switch is pressed to stop the
unit, the vane will move to the Close position.
(b) Vertical Airflow Direction Auto
By setting the vertical airflow direction to AUTO, the vane swings up and down from 7 ~ 36 (during Cooling
and Fan) and 3 ~ 33 (during Soft Dry). During Heating operation, the vane angle will shift according to the
indoor heat exchanger temperature as shown below.
Zone C
(33)

58C

55C
Zone B
(70)
33C
Zone A
(15)

30C

Indoor heat exchanger


temperature

B. Horizontal Airflow Direction


(a) Automatic Horizontal Vane angle setting
By setting the horizontal airflow direction to AUTO, the vanes swing left and right from 55 ~ 125 during
Cooling, Soft Dry and Fan operation. During Heating operation, the vane angle will shift according to the
indoor heat exchanger temperature as shown below:
Left Vane Position

Right Vane Position

125

125

90

90

55

55

55 ~ 125

55 ~ 125

64 ~ 110

64 ~ 110

55 ~ 125

55 ~ 125

64 ~ 110

64 ~ 110

55 ~ 125

55 ~ 125

Operation
Indoor heat exchanger
temperature

Heating

Cooling
Anti-dew formation control
Soft Dry
Anti-dew formation control
Fan
Heating

Vane angle position


43C

Zone C
(125)

Left Vane

Right Vane

40C
Zone B
(90)

50

55

125 55 50

90

33C
30C
Zone A
(55)

Stopper position

90
125

Stopper position

Indoor heat
exchanger temperature

37

Untitled-5

37

6/20/00, 5:11 PM

MAC9509078C2

CS-G93KE

Operation Details
(b) Manual Horizontal vane angle setting

By pressing the remote control horizontal airflow direction setting switch, the vane will move to the indicated
position (1, 2, 3, 4, 5, 6, 7) as shown in the table.

Horizontal vane angle position


1

Operation

(Left vane position)

Heating
Cooling Anti-dew Formation Control
Soft
Dry

Anti-dew Formation Control


Fan

(Right vane position)

90

125

55

55

55

90

125

90

125

55

125

90

55

55

90

125

55

55

55

90

125

90

125

55

125

90

55

55

90

110

64

64

64

90

110

90

110

64

110

90

64

64

90

125

55

55

55

90

125

90

125

55

125

90

55

55

90

110

64

64

64

90

110

90

110

64

110

90

64

64

90

125

55

55

55

90

125

90

125

55

125

90

55

55

(c) Wide / Spot Airflow Setting


By pressing the remote control WIDE/SPOT switch, the vane will move to position 3 while WIDE and position
2 while SPOT.

For All
Operations

WIDE

SPOT

10. QUIET OPERATION


The purpose of this control is to reduce indoor operating noise. Indoor fan speed is set to Lo- when the following
conditions occur.

Indoor fan speed is set at Low

Indoor heat exchanger temperature rises to 17C or above

Compressor operates for 5 minutes or more

Operation frequency is less than 33Hz (CU-G93KE) or 36Hz (CU-G123KE)

17C

Lo-

Lo

13C

Indoor Heat
Exchanger Temperature

This control is cancelled when one of the following conditions occurs.

Indoor fan speed is not set at Low

Indoor heat exchanger temperature is decreased to 13 C or below

Compressor operation frequency is more than 33Hz (CU-G93KE) or 36Hz (CU-G123KE)


38

Untitled-5

38

6/20/00, 5:11 PM

MAC9509078C2

CS-G93KE

Operation Details
11. POWERFUL MODE OPERATION
When the powerful mode is selected, the internal setting temperature will shift to achieve the setting temperature
quickly.
(a) Cooling Operation
Internal setting
temperature
4C

When powerful
button is pressed

(b) Soft Dry Operation


Internal setting
temperature
3C

When powerful
button is pressed

(c) Heating Operation


+6C
Internal setting
temperature

When powerful
button is pressed

12. SLEEP MODE OPERATION


(a) Cooling Operation / Soft Dry Operation

When the sleep button is pressed, the remote control setting temperature will increase 0.5C after 1 hour
or when the remote control setting temperature is reached. After another hour, 0.5C will be increased again.

+0.5C
Remote control
setting
temperature

+0.5C

1 hour

When Sleep
button is pressed

max 1 hour

8 hours
All stop

Sleep mode
shift operation
starts

During sleep shift operation, indoor fan speed operates at Lo (for Cooling operation) or SLo (for Soft Dry operation).
39

Untitled-5

39

6/20/00, 5:11 PM

MAC9509078C2

CS-G93KE

Operation Details
(b) Heating Operation

When the sleep button is pressed, the remote control setting temperature will decrease 2C after 1 hour or
when the remote control setting temperature is reached. After another hour, 3C will be decreased again.

Remote control
setting temperature

2C

When Sleep
button is pressed

3C

1 hour

8 hours
max 1 hour

All stop

Sleep mode shift


operation starts

During sleep shift operation, indoor fan speed operates at Lo.

13. DELAY ON TIMER CONTROL

When the Delay On Timer is set by using remote control, the unit will start to operate slightly earlier before the
set time, so that the room will nearly reach the set temperature by the On Timer set time.

60 minutes before the set time, the indoor fan operates at Lo and outdoor fan operates for 20 seconds to sense
the indoor intake air temperature and outdoor air temperature in order to determine the starting time for
preparatory operation. (The Power LED blinks during sampling.)

The time of the preparatory operation will start before the On Timer set time.
a. Cooling/Soft Dry
Indoor
intake
air temp
(C)
30

b. Heating

15 min

Indoor
intake
air temp
(C)
15

10 min

25 min

35 min

25

5
5 min

45 min
30

35 (C)

Outdoor air temp.

(C)

Outdoor air temp.

14. AUTO RESTART CONTROL

If there is a power failure, operation will automatically be restarted when the power is resumed from 2 minutes
58 seconds to 3 minutes 52 seconds randomly. It will start with the previous operation mode and airflow direction.
Auto Restart Control is not available when Timer or Sleep Mode is set.
J1 at indoor electronic controller should be open circuit when cancellation of Auto Restart Control.
40

Untitled-5

40

6/20/00, 5:11 PM

MAC9509078C2

CS-G93KE

Operation Details
15. POWER MONITOR DISPLAY
POWERFUL
POWER SLEEP TIMER
HIGH

POWER
MONITOR

LOW

Power Monitor LED lights on when the compressor is in operation. The number of the LED lights on is in accordance
to the compressor operating frequency.
Model

CS-G93KE

Display

A, B

A, B, C

A, B, C, D

A, B, C, D, E

Cooling & Soft Dry


Indication Frequency
(Hz)

15 ~ 26

31 ~ 33

36 ~ 40

43 ~ 46

51 ~ 64

Heating Indication
Frequency (Hz)

15 ~ 26

31 ~ 40

43 ~ 58

63 ~ 64

71 ~ 99

15 ~ 27

31 ~ 36

44 ~ 49

58 ~ 64

71 ~ 92

15 ~ 27

31 ~ 44

58 ~ 79

83 ~ 86

91 ~ 115

Cooling & Soft Dry


Indication Frequency
(Hz)
CS-G123KE
Heating Indication
Frequency (Hz)

16. REMOTE CONTROL SIGNAL RECEIVING SOUND ON/OFF

Press the AUTO button for 10 seconds or longer to switch off the signal receiving sound.
Press the AUTO button for 10 seconds or longer again to switch on the signal receiving sound.

17. INDOOR POWER RELAY CONTROL

The power relay turns on when one of the indoor LED lights on.
The power relay turns off when all of the indoor LEDs lights off.
When the air conditioner is stopped during operation, the power relay stays ON for 3 minutes.
The power relay will turn off if a sudden power failure occurs > 0.05 second. The power relay will turn on again
after 3 - 4 minutes (Refer AUTO RESTART CONTROL). It will start with the previous operation condition before
the power failure.

41

Untitled-5

41

6/20/00, 5:11 PM

MAC9509078C2

CS-G93KE

Operation Details
B. PROTECTION
1. PROTECTION CONTROL FOR ALL OPERATIONS
a.

Time Delay Safety Control

b.

30 Second Forced Operation

c.

The compressor is not restarted for 3 minutes after stop of compressor.

Once the compressor is ON, it will not turn OFF for 30 seconds. However, it is turned off by remote control
or Automatic switch.

Total Running Current Control

When the outdoor unit total running current (AC) exceeds I1, the frequency is lowered by 1 rank. If I1 is not
exceeded for 30 seconds, the frequency is highered by 1 rank at one time. If the outdoor unit total running
current exceeds I2, the compressor is immediately stopped for 3 minutes.

<Cooling, Soft Dry set value>


Zone A

Zone B

Model No.

CU-G93KE

I1(A)

5.3

6.7

4.3

5.2

I2(A)

7.3

10.8

7.3

10.8

CU-G123KE CU-G93KE

38.5C

CU-G123KE

Zone B
Outdoor air
temperature
37.5C
Zone A

Note: Zone A will be used 30 minutes after operation starts.


<Heating set value>
Model No.

CU-G93KE

CU-G123KE

I1(A)

6.1

9.2

I2(A)

7.3

10.8

If the outdoor unit total running current exceeds I2 3 times within 30 minutes, all indoor and outdoor relays will
be turned off ; TIMER LED will blink and F98 is displayed.

d.

IPM (Power transistor) Prevention Control


1. Overheating Prevention Control

When the IPM (power transistor) temperature rises to 100 10C, the compressor stops immediately. The
compressor is restarted when the IPM (power transistor) temperature decreases to 90 10C after 3 minutes
(Time Delay Safety Control). If this condition occurs 4 times within 40 minutes, all indoor and outdoor relays
will be turned off; TIMER LED will blink and F96 is displayed

42

Untitled-6

42

6/20/00, 5:13 PM

MAC9509078C2

CS-G93KE

Operation Details
2. DC Peak Current Control

When the electric current to the IPM (power transistor) exceeds the set value, DC 27 4A, the compressor
stops. The compressor restarts after 3 minutes.

If within 30 seconds the set value is exceeded again, the compressor will stop for 1 minute. If this condition
repeats for 7 times, all indoor and outdoor relays will be turned off; TIMER LED will blink and F99 is displayed.
DC electric current
(A)
274
Comp.
Off

Comp. Off
min
33 min

TIMER LED blinks


F99 is displayed

Comp.
Off

<30
30sec
sec 11 min
min <3030
sec
sec

<30
30sec
sec 1 min
min <3030sec
sec

7 times

e.

Compressor Overheating Prevention Control

When the temperature of compressor rises to 105C, the frequency is reduced as shown in diagram below.
When the temperature rises to 115C or above, the compressor stops. The compressor will start operating
at low frequency when the temperature falls to 115C and resume to normal condition when the temperature
falls to 94C.
Compressor
temp. (C)

Comp OFF

Comp OFF

115
max 33 Hz (CU-G93KE)
max 36 Hz (CU-G123KE)
110
106

max 40Hz (CU-G93KE)


max 49Hz (CU-G123KE)

105
94

Condition

f.

max 40Hz (CU-G93KE)


max 49Hz (CU-G123KE)

Free

Free

When temperature rises

max 33 Hz (CU-G93KE)
max 36 Hz (CU-G123KE)

When temperature falls

The compressor stops when the temperature rises to 115C. If this condition occurs 4 times within 20
minutes, all indoor and outdoors relays will be turned off; TIMER LED will blink and F97 is displayed.

Low Pressure Control (Gas Leakage Detection)

When the following conditions as shown in the below table occur, the compressor stops and restarts after
3 minutes. If this phenomenon is continuously occuring twice within 30 minutes, all indoor and outdoor relays
will be turned off; TIMER LED will blink and F91 is displayed.
Comp. Frequency *

51 Hz and above

71 Hz and above

70 Hz and above

90 Hz and above

Total Running
Current

1.88 A and
< 1.9 A

1.88 A and
< 2.1 A

1.88 A and
< 2.4 A

1.88 A and
< 2.7 A

Indoor Heat
Exchanger Temp.
Operation
Model No.

15C
or above

30C
or below

15C
or above

30C
or below

Cooling/Soft Dry

Heating

Cooling/Soft Dry

Heating

CU-G93KE

CU-G123KE

Note: The above conditions are not valid during Deice operation.
*

This conditions are continuous for 5 minutes.


43

Untitled-6

43

6/20/00, 5:13 PM

MAC9509078C2

CS-G93KE

Operation Details
g.

Minimum Frequency Operation Protection

When the compressor operates at less than 31 Hz for 40 minutes, the operating frequency will increase to
31 Hz for 2 minutes.
Comp. Operating
Frequency
31Hz

40 min

h.

Low Frequency Operation Protection

i.

2 min

Indoor intake air temp. (C)

30C or < 15C

28C or < 14C

Outdoor air temp. (C)

38C or < 16C

24C or < 4C

Indoor heat exchanger temp. (C)

< 30C

> 0C

Operation

Cooling/Soft Dry

Heating

When the above conditions occur, the compressor will operate at minimum frequency as below:CU-G93KE

CU-G123KE

Cooling / Soft Dry

Min 31Hz

Min 31Hz

Heating

Min 33Hz

Min 36Hz

Low Power Supply Voltage Protection

When the DC voltage supplied to IPM (Power transistor) is reduced to 169 5V (CS-G93KE) or 160 5V
(CS-G123KE) the compressor stops and restarts after 3 minutes.

If within 30 seconds after restarting of compressor, the DC voltage is reduced to 169 5V (CS-G93KE) or
160 5V (CS-G123KE) again, the compressor will stop for 1 minute.
If this condition repeats for 7 times, all indoor and outdoor relays will be turned off; TIMER LED will blink and
F99 is displayed.

DC Voltage
Supplied to IPM
(V)

169 or 160
Comp OFF
3 min

TIMER LED
Blinks
F99 is
displayed

Comp
OFF
< 30 sec
sec

11min
sec
min <3030sec

<30
30 sec
sec

7 times

j.

High Power Supply Voltage Protection

When the voltage supply (AC) exceeds 295 15 V (T0), the air conditioner stops and restarts automatically
when the voltage supply (AC) is below (T0 - 5)V. However, waiting for 3 minutes is necessary for re-operation.

44

Untitled-6

44

6/20/00, 5:13 PM

MAC9509078C2

CS-G93KE

Operation Details
2. PROTECTION CONTROL FOR COOLING & SOFT DRY
a.

Anti-Freezing Control

When the temperature of the indoor heat exchanger becomes low, the compressor operating frequency is
reduced and stopped when the temperature falls to lower than 2C continuously for 6 minutes. This is to
prevent freezing of indoor heat exchanger. When the temperature rises to 10C or above, the compressor
restarts with 3 minutes. The compressor operating frequency will resume to normal when the temperature
reaches 14C.

Indoor fan speed will increase when the temperature falls and it will resume to original speed when the
temperature increases to 14C for 5 minutes continuously.
Indoor Heat
Exchanger 14
Temp. (C) 12

Free
Free

Original

10
6
4
2

Original

Max 36 Hz (CS-G93KE)
Max 44 Hz (CS-G123KE)
Max 26 Hz (CS-G93KE)
Max 27 Hz (CS-G123KE)

* Indoor Fan Speed Shift


Max 36 Hz (CS-G93KE)
Max 44 Hz (CS-G123KE)
Max 26 Hz (CS-G93KE)
Max 27 Hz (CS-G123KE)

Shift *

Shift *
OFF

OFF
Comp.

Indoor Fan

When the temp. falls

Comp.

Indoor Fan

When the temp. rises

Fan Speed

Shift *

Me+

2 rank up

Me

1 rank up

Me-

1 rank up

Lo

2 rank up

AUTO FAN

1 rank up

Note: The above phenomenon occurs when the fan is running at Me+ or below.

b.

Anti-Dew Formation Control

When the following conditions occur for 20 minutes continuously, anti-dew formation is controlled:
1. Indoor intake air temperature is 24C or above.
2. Outdoor air temperature is less than 30C.
3. Remote control setting temperature is less than 25C.

During anti-dew formation control, compressor operates at 36 Hz (CS-G93KE) or 44 Hz (CS-G123KE) and


airflow direction vane move slightly (as shown in Airflow Direction Control). Indoor fan speed will shift as
below:
Fan Speed

Shift

Hi

2 rank down

Me+

3 rank up

Me

unchange

Me-

unchange

Lo

2 rank up

This control is cancelled immediately when either condition 13 as written above is changed, or remote
control setting temperature or fan speed is changed.

45

Untitled-6

45

6/20/00, 5:13 PM

MAC9509078C2

CS-G93KE

Operation Details
c.

Anti-Fog Discharge Control

The compressor operating frequency is regulated by operation time to prevent fog discharged from indoor
unit as shown in the table below.

Compressor operating frequency


Operation
Time, T (min)

Model No.

0 T < 30

50Hz

70Hz

30 T < 90

46Hz

64Hz

T 90

43Hz

58Hz

CU-G93KE

CU-G123KE

Note: Indoor fan is running at Me- or below.


After 420 minutes from the start of operation, the operation timer counting is restarted from 0.

d.

High Pressure Control at Minimum Frequency Control

When the outdoor air temperature increases to 38.6C, compressor operating frequency reduces to
minimum of 31 Hz. Compressor operating frequency will resume to normal when outdoor air temperature
decreases to 37.8C.

46

Untitled-6

46

6/20/00, 5:13 PM

MAC9509078C2

CS-G93KE

Operation Details
3. PROTECTION CONTROL FOR HEATING OPERATION
a.

b.

Intake Air Temperature Control

When the intake air temperature is 10C or above and remote control setting fan speed is less than Me-, the
compressor operates maximum at 71 Hz (CU-G93KE) or 90 Hz (CU-G123KE).

When the intake air temperature is 30C and above, the compressor operates maximum at 71 Hz (CUG93KE) or 90 Hz (CU-G123KE).

Outdoor Air Temperature Control

The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown
in the diagram below. This control will begin 50 seconds after the compressor starts.
Outdoor air
Temperature (C)

43 Hz

43 Hz

21
19

64 Hz
64 Hz
Free

Model No.

c.

Free

When temp.
rises

Condition

58 Hz

86 Hz

12
10

58 Hz

When temp.
falls

86 Hz
Free

Free

When temp.
rises

CU-G93KE

When temp.
falls

CU-G123KE

High Pressure Control

The compressor operating frequency is regulated in accordance to the indoor heat exchanger temperature.

Indoor heat
exchanger temp. (C)

OFF
59

OFF

33 Hz

33 Hz

53
51
47

Min 33 Hz

43

Max 43 Hz

OFF

OFF
36 Hz

Min 36 Hz

36 Hz
Max 58 Hz

Max 53 Hz

Max 74 Hz

Min 33 Hz

Min 36 Hz

37

Condition
Model No.

Free

Free

Free

Free

When temp.
rises

When temp.
falls

When temp.
rises

When temp.
falls

CU-G93KE

CU-G123KE

47

Untitled-6

47

6/20/00, 5:13 PM

MAC9509078C2

CS-G93KE

Installation Information
Attached accessories
No.

Accessories part

Qty.

No.

1 6
Installation plate fixing screw

2
3

6
Remote control

1 8

Battery

Air purifying filter

1
Band

1
Vinyl tape

3
Vinyl tape

4
5

Qty.

Drain elbow

Installation plate

Accessories part

Accessories: Flaring piping kit


CZ-3F5, 7AEN (CS-G93KE)
CZ-4F5, 7AEN (CS-G123KE)
SELECT THE BEST LOCATION
INDOOR UNIT

There should not be any heat source or steam near the unit.
There should not be any obstacles blocking the air circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
Indoor unit of this room air conditioner shall be installed on the wall in a height of at least 2.3 m.
OUTDOOR UNIT

There should not be any animal or plant which could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.

Rated
Length

Max.
Elevation
(m)

Max.
Piping
Length
(m)

Piping size
MODEL
Gas

Liquid

G93KE

3/8"

1/4"

G123KE

1/2"

1/4"

48

Untitled-7

48

6/20/00, 5:15 PM

MAC9509078C2

CS-G93KE

Installation Information

Indoor / Outdoor unit installation diagram


Length of power supply cord
about 1.1 m
< <

Piping direction

about 1.8 m
<

Attention not to bend up drain hose


(Front side)

Right
Right
rear
Left
Right bottom rear

<

Left
Left bottom

Installation parts you must


purchase (*)
5 cm
or more

Installation plate 1
Sleeve (*)
Bushing-Sleeve (*)
SLEEP

POWER

Putty, (Gum Type Sealer) (*)

TIMER

UL

POWERF

ECONOM

5 cm
or more

Air purifying filter 5

Bend the pipe as closely on the


wall as possible, but be careful
that it doesnt break.

(Left and right are identical)


Insulation of piping connections

Carry out installation


after checking for gas
leaks.
After securing with
three of the vinyl
tape 8, wrap with
vinyl tape 9.

Vinyl tape
9
Vinyl tape 8

Vinyl tape (Wide) (*)


Apply after carrying out a
drainage test.
To carry out the drainage
test, remove into the heat
exchanger. To carry out the
drainage test, remove into
the heat exchanger.

Saddle (*)

cm
10 ore
m
or

Connecting cable
(4-CORE WIRE/1.5 mm2)
Locally approved cable.
Additional drain hose (*)

10 cm
or mor
e

1/4" Liquid side piping (*)


cm
100 ore
or m

Gas side piping (*)


3/8" (G93KE)
1/2" (G123KE)

This illustration is for explanation purposes only.


The indoor unit will actually face a different way.

49

Untitled-7

49

6/20/00, 5:15 PM

CS-G93KE

Servicing Information
A.

TROUBLESHOOTING

1. RATED FREQUENCY OPERATION


During troubleshooting and servicing, rated compressor operating frequency must be obtained in order to check the
specification and technical data. Below are the methods used to obtain rated compressor operating specification.
(a) Cooling
(i) Press the Test Run button on the indoor unit. The air conditioner starts operation at Cooling rated frequency.

TEST RUN BUTTON

POWER SWITCH
POWERFUL

POWER SLEEP TIMER


HIGH

POWER
MONITOR

LOW

(ii) Short the service terminal (CN-S) of the outdoor printed circuit board. The air conditioner starts operation
at Cooling rated frequency.

CN-S

(b) Heating
Keep pressing the Test Run button, switch off and on the Power Switch, then release the Test Run button. The
air conditioner starts operation at Heating rated frequency.

50

Untitled-8

50

6/20/00, 5:17 PM

MAC9509078C2

CS-G93KE

Servicing Information
2. TROUBLESHOOTING AIR CONDITIONER
Refrigeration cycle system
Normal Pressure and Outlet Air Temperature (Standard)

In order to diagnose malfunctions, make sure that


there are no electrical problems before inspecting the refrigeration cycle. Such problems include
insufficient insulation, problem with the power source,
malfunction of a compressor or a fan.
The normal outlet air temperature and pressure
of the refrigeration cycle depends on various conditions; the standard values for them are shown in the
table on the right.

Difference in the intake


and outlet
air temperatures

Gas pressure
MPa (kg/cm2G)

Outlet air
temperature (C)

Cooling mode

0.4 ~ 0.6 (4 ~ 6)

12 ~ 16

Heating Mode

1.5 ~ 2.1 (15 ~ 21)

36 ~ 45

Condition: Indoor fan speed; High.


Outdoor temperature is 35C at cooling
mode and 7C at heating mode.
Compressor operates at rated frequency.

Normal

Above 8C
(15 minutes after an
operation is started.)
at cooling mode
Above 14C
(15 minutes after an
operation is started.)
at heating mode

Measure the air temperature


difference

Less than 8C at cooling mode


Less than 14C at heating mode

Higher than specified

Value of electric
current during operation

Dusty condenser
preventing heat radiation

Measure the electric current


during operation

Excessive amount
of refrigerant

Lower than specified

Cooling Mode

High

Gas side
pressure

Inefficient compressor

Measure the gas side pressure

Low

Insufficient refrigerant
Low

Clogged strainer or
capillary tube

Low

Inefficient compressor
Heating Mode

Low

Insufficient refrigerant
Low

Clogged strainer or
capillary tube

51

Untitled-8

51

6/20/00, 5:17 PM

CS-G93KE

Servicing Information
1. Relationship between the condition of the air conditioner and pressure and
electric current
Cooling Mode

Heating Mode

Condition of the air


conditioner

Low Pressure

High Pressure

Electric
current during
operation

Low Pressure

High Pressure

Electric
current during
operation

Insufficient refrigerant
(gas leakage)

Clogged capillary tube


or Strainer

Short circuit in the


indoor unit

Heat radiation deficiency of the outdoor


unit

Inefficient
compression

Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is
started.

52

Untitled-8

52

6/20/00, 5:17 PM

MAC9509078C2

CS-G93KE

Servicing Information
B.

SELF DIAGNOSIS DISPLAY

The diagnostic display can be seen on the receiver of the Front Grille.
When an abnormality occurs, the unit automatically stops, and the TIMER LED blinks to indicate a malfunction. At the
same time, the type of abnormality will be indicated on the receiver as shown in the diagram below. Providing this
information reduces the time spent in diagnosing procedures.

Display

(Red)

POWERFUL

POWER SLEEP TIMER

P O W E R LOW
MONITOR

HIGH

TIMER

The diagnostic display disappears when the power is turned off.


When power is re-supplied and the Diagnostic Terminals the Remote Control is shorted, the type of the previous
abnormality and the protection control works will be displayed on the receiver for approximately 10 seconds.
Diagnostic Terminals
To be used by the service
technician only.

OPEN

By starting cooling operation using TEST RUN button and short the Diagnostic Terminals at the remote control, the
previous abnormalities are deleted.
Depending on the type of abnormality, you may be able to override the abnormality and use temporary operation (for
abnormalities indicated by t mark in the table).
Use the remote control to select cooling or heating operation mode and press OFF/ON button. At this moment, four short
beeps bip.bip.bip.bip will sound and TIMER LED will blink.

53

Untitled-8

53

6/20/00, 5:17 PM

CS-G93KE

Servicing Information
Diagnosis
display

Abnormality / Protection control

Abnormality
Judgement

Temporary
operation

1 min after
starting operation

Internal / external cable connections


Indoor / Outdoor PCB

Primary location to verify

H11

Indoor / outdoor abnormal


communication

H14

Indoor intake air temperature


sensor abnormality

Intake air temperature sensor


(defective or disconnected)

H15

Outdoor compressor temperature


sensor abnormality

Compressor temperature sensor


(defective or disconnected)

H16

Outdoor Current Transformer open


circuit

Outdoor PCB
IPM (Power transistor) module

H19

Indoor fan motor mechanism lock

Indoor PCB
Fan motor

H23

Indoor heat exchanger temperature


sensor abnormality

H27

Outdoor air temperature sensor


abnormality

Outdoor temperature sensor


(defective or disconnected)

H28

Outdoor heat exchanger temperature sensor abnormality

Outdoor heat exchanger temperature


sensor
(defective or disconnected)

H98

Indoor high pressure protection

Air filter dirty


Air circulation short circuit

H99

Indoor heat exchanger anti-freezing


protection

Insufficient refrigerant
Air filter dirty

F11

Cooling / Heating cycle changeover


abnormality

4 times
occurance within
40 minutes

4-way valve
V-coil

F91

Refrigeration cycle abnormality

2 times
occurance within
30 minutes

No refrigerant
(3-way valve is closed)

F93

Outdoor compressor abnormal


revolution

4 times
occurance within
30 minutes

Compressor
Outdoor PCB

F96

IPM (power transistor)


overheating protection

4 times
occurance within
40 minutes

Excess refrigerant
Improper heat radiation
IPM (Power transistor)

F97

Outdoor compressor overheating


protection

4 times
occurance within
20 minutes

Insufficient refrigerant
Compressor

F98

Total running current protection

3 times
occurance within
30 minutes

Excess refrigerant
Improper heat radiation

F99

Outdoor Direct Current (DC) peak


detection

7 times
occurance
continuously

Outdoor PCB
IPM (Power transistor)
Compressor

t
(Cooling only)

Heat exchanger temperature sensor


(defective or disconnected)

54

Untitled-8

54

6/20/00, 5:17 PM

MAC9509078C2

CS-G93KE

Servicing Information
(a) Current Transformer Defective
When the Current Transformer (CT) is an open circuit, total running current is less than 1.88 A and the indicated
frequency is 53 Hz (CU-G93KE) or 74 Hz (CU-G123KE) or above. If this condition continues for 20 seconds,
the abnormality signal is sent from outdoor to indoor after 3 minutes of operation and [H16] is displayed.

(b) 4 Way Valve Defective


i. Heating Operation (except Deice)
When the indoor heat exchanger temperature is lower than 5C after 4 minutes of operation, the operation
stops and restarts after 3 minutes. If this phenomenon occurs for 4 times within 40 minutes, [F11] is displayed.
ii. Cooling Operation
When the indoor heat exchanger temperature is higher than 45C after 4 minutes of operation, the operation
stops and restarts after 3 minutes. If this phenomenon occurs for 4 times within 40 minutes, [F11] is displayed.
The abnormality is not judged in the following conditions:
deice operation
2 minutes after deice operation
hot start
2 minutes after hot start
3 minutes after heating and cooling/soft dry mode changeover

55

Untitled-8

55

6/20/00, 5:17 PM

CS-G93KE

Servicing Information
C.

Reset Button

REMOTE CONTROL
a.

Remote Control Reset


When the batteries are inserted for the first time,
or the batteries are replaced, all the indications
will blink and the remote control might not work.
If this happens, remove the back cover of the
remote control and you will find a resetting terminal, and by shorting it with a minus screwdriver,
it will return to normal.

b.

Changing the wireless remote control transmission code


When two indoor units are installed in the same
room, in order to prevent operating errors caused
by using two remote controls, set up the remote
control [B A] switch (SW1).
The unit is set to A when it is shipped.

SW1
AB

Main electronic
controller

BA

By adding a jumper wire to the remote control side and shorting the J2 at the indoor printed circuit board,
it is possible to select 4 transmission codes including one at time of delivery condition (1).

Indoor printed circuit board

Remote control

Note
Switch SW B A

JB

Switch SW1

J2
At product delivery

Jumper wire

Shorted

Jumper wire

Shorted

56

Untitled-8

56

6/20/00, 5:17 PM

MAC9509078C2

CS-G93KE

Servicing Information
D.
a.

DISASSEMBLY OF PARTS
Indoor Control Board Removal Procedure
1. Remove the Front Grille
Fig. 1

Fig. 2

3 Press the
2 tabs

2 Remove the
Front Grille

1 Remove caps and screws

2. Remove the Indoor Control Board

Fig. 3

Fig. 4

4 Disconnect all connectors

5 Remove the
whole control
board.

4 Remove
earth wire screw

4 Remove screws

Note : Remove the indoor and outdoor


connecting wires from terminal 1,
2, 3 and i.

57

Untitled-1

57

6/21/00, 9:24 AM

CS-G93KE

Servicing Information
b.

Removal of Electronic Controller Procedure


Fig. 6

Fig. 5

2 Remove the particular plate

1 Remove screw

2 Remove the
particular plate

Fig. 8

Fig. 7

4 Slide to remove PCB cover

3 Remove screw

Fig. 10

Fig. 9

6 Remove the Electronic Controller

5 Remove screw

58

Untitled-1

58

6/21/00, 9:24 AM

MAC9509078C2

CS-G93KE

Servicing Information
c.

Indoor Fan Motor Removal Procedure


Fig. 12

Fig. 11

2 Press down
1 Remove screw

Tabs

1 Remove screw
2 Press up

Fig. 14

Fig. 13

3 Remove the
front cover

4 Remove the
side cover

Fig. 15
5 Remove the Cross Flow Fan Screw

6 Remove the
Indoor Fan
Motor

59

Untitled-1

59

6/21/00, 9:24 AM

CS-G93KE

Servicing Information
d.

Cross Flow Fan Removal Procedure


1. Remove Discharge Grille

Fig. 16

1 Remove the Discharge Grille

1.

Remove Cross Flow Fan


Fig. 18

Fig. 17

2 Remove the bushing

2 Remove
the screw

3 Release the slot of indoor heat


exchanger from the chassis

Fig. 19

3 Pull slightly

4 Remove the Cross Flow Fan

60

Untitled-1

60

6/21/00, 9:24 AM

MAC9509078C2

CS-G93KE

Servicing Information
c.

Outdoor Electronic Controller Removal Procedure

! WARNING
Be save to return the wiring to its original
position
There are many high voltage components within the heat sink cover so never
touch the interior during operation. Wait
at least two minutes after power has
been turned off.

1. Remove the top panel and front panel


Fig. 20

Fig. 21
1 Remove screw

! Warning ! Do not touch High Voltage Area

3 Remove Top Panel

2 Remove 2 screws

5 Remove Front
Panel

4 Remove 2 screws

2. Remove the Outdoor Electronic Controller


Fig. 22

Fig. 23

6 Remove 5 screws

7 Disconnect all connectors

8 Remove the
electronic
controller

! Caution! When handling electronic


controller, be careful of electrostatic
discharge.

Note : Use magnetic type of screw driver to


avoid dropping of the screws

61

Untitled-1

61

6/21/00, 9:24 AM

CS-G93KE

Servicing Information
f.

Propeller Fan Removal Procedure


Fig. 25

Fig. 24

2 Remove the propeller fan


1 Remove the nut (clockwise direction)

g.

Outdoor Fan Motor Removal Procedure


Fig. 27

Fig. 26

3 Remove the connector


4 Remove 4 screws

Fig. 28

5 Remove the Outdoor Fan Motor

62

Untitled-1

62

6/21/00, 9:24 AM

MAC9509078C2

CS-G93KE

Technical Data
L Operation characteristics
CS-G93KE / CU-G93KE
Cooling Characteristic

Piping Length Characteristic (Cooling)

0.58
0.56

30

35

0.62

GP

0.61
0.60
0.59
0.58
4.5
4.0
3.5
3.0

40

Heating Characteristic

Piping Length Characteristic (Heating)


230V

2.0
1.8
1.6
1.4

6.0
5.0
4.0
3.0

10

3.8
3.7
3.6
3.5
3.4
3.3

1.9
1.8

7
6
5
4

OUTDOOR AIR TEMPERATURE (C)


[Condition] Room temperature: 20C
Heating Operation: at High Fan
Piping length: 5m
Rated Frequency Operation

1.7
1.6

GP

I: Current (A)

I: Current (A)

GP

GP: Gas Side


Piping Pressure (MPa)

Q: Heating Capacity (kW)

40
39
38
37
36

Q: Heating Capacity (kW)

40
38
36
34
32

O: Outlet Air
Temperature (C)

230V

4.0
3.5
3.0

63

PIPING LENGTH (m)


[Condition] Room temperature: 20C
Heating Operation: 7/6C
Piping length: at High Fan
Rated Frequency Operation

63

Untitled-2

PIPING LENGTH (m)


[Condition] Room temperature: 27/19C
Cooling Operation: at High Fan
Piping length: 5m
Rated Frequency Operation

OUTDOOR AIR TEMPERATURE (C)


[Condition] Room temperature: 27/19C
Cooling Operation: at High Fan
Piping length: 5m
Rated Frequency Operation

6/21/00, 9:30 AM

O: Outlet Air
Temperature (C)

I: Current (A)

6
5
4
3

2.7
2.6
2.5

GP: Gas Side


Piping Pressure (MPa)

GP

Q: Cooling Capacity (kW)

0.62
0.60

GP: Gas Side


Piping Pressure (MPa)

2.8
2.7
2.6
2.5
2.4
2.3

17
16
15
14
13
12

I: Current (A)

Q: Cooling Capacity (kW)

O: Outlet Air
Temperature (C)

16
15
14
13
12

O: Outlet Air
Temperature (C)

230V

230V

GP: Gas Side


Piping Pressure (MPa)

CS-G93KE

Technical Data
L Operation characteristics
CS-G123KE / CU-G123KE
Cooling Characteristic

Piping Length Characteristic (Cooling)

0.57
0.56

GP
I

30

35

0.55
0.54
0.53
7
6
5
4

40

OUTDOOR AIR TEMPERATURE (C)


[Condition] Room temperature: 27/19C
Cooling Operation: at High Fan
Piping length: 5m
Rated Frequency Operation

0.57
0.56

GP

PIPING LENGTH (m)


[Condition] Room temperature: 27/19C
Cooling Operation: 35/24C
Piping length: at High Fan
Rated Frequency Operation

Heating Characteristic

Piping Length Characteristic (Heating)


230V

2.0
1.8
1.6
1.4

I: Current (A)

GP

7
6
5

Q: Heating Capacity (kW)

Q
GP: Gas Side
Piping Pressure (MPa)

Q: Heating Capacity (kW)

6.0
5.0
4.0
3.0

4.9
4.8
4.7
4.6
4.5
4.4

8
7
6
5

OUTDOOR AIR TEMPERATURE (C)


[Condition] Room temperature: 20C
Heating Operation: at High Fan
Piping length: 5m
Rated Frequency Operation

2.0
1.9
1.8
1.7

10

44
43
42
41
40
39

GP

I: Current (A)

46
44
42
40
38
36

O: Outlet Air
Temperature (C)

230V

O: Outlet Air
Temperature (C)

I: Current (A)

7
6
5
4

0.58

I: Current (A)

0.55
0.54

3.6
3.5
3.4
3.3
3.2
3.1

GP: Gas Side


Piping Pressure (MPa)

3.7
3.6
3.5
3.4
3.3
3.2

GP: Gas Side


Piping Pressure (MPa)

15
14
13
12
11

Q: Cooling Capacity (kW)

Q: Cooling Capacity (kW)

O: Outlet Air
Temperature (C)

16
15
14
13
12

O: Outlet Air
Temperature (C)

230V

230V

GP: Gas Side


Piping Pressure (MPa)

PIPING LENGTH (m)


[Condition] Room temperature: 20C
Heating Operation: 7/6C
Piping length: at High Fan
Rated Frequency Operation

64

Untitled-2

64

6/21/00, 9:30 AM

MAC9509078C2

CS-G93KE

Exploded View
CS-G93KE / CS-G123KE
1

#
4

<

6
&
"

2
#

\
[
!

5
*

}
@
^

>

+
|

,
$

%
:
:

.
6

)
9

!
7

(
&

;
2

8
!
9

4
)
(Note) : The above exploded view is for the purpose of parts
(
disassembly and replacement.
The non-numbered parts are not kept as standard
service parts.

65

Untitled-3

65

6/21/00, 9:35 AM

CS-G93KE

CS-G93KE

Replacement Parts List

Replacement Parts List

<Model: CS-G93KE / CS-G123KE>

<Model: CS-G93KE / CS-G123KE>

NO.
1

DESCRIPTION & NAME


CHASSY COMPLETE

QTY
1

CS-G93KE
CWD50C338

CS-G123KE
@

REMARKS
O

CWF61696

CS-G123KE
@

INSTALLATION PLATE

CWH36157

DESCRIPTION & NAME


INSTALLATION INSTRUCTIONS

54

FAN MOTOR

CWA98244

CROSS FLOW FAN

CWH02C060

55

BAG COMPLETE ( INSTALLATION SCREW)

CWH82C194

4
5
6

BEARING
EVAPORATOR
FLARE NUT (1/2) OR (3/8")

1
1
1

CWH64K007
CWB30C271
CWT25005 (3/8")

@
@
CWT25007 (1/2")

56

AIR PURIFYING FILTER COMPLETE

CWD00C111

7
8

FLARE NUT (1/4)


SPACER COMPLETE

1
1

CWH6002140
CWH54C031

@
@

9
10
11

ANTI VIBRATION BUSHING


FAN MOTOR COVER
LEAD WIRE - FAN MOTOR

1
1
1

CWH50211
CWD931039
CWA67C2310

@
@
@

12
13

TUBE ASSY
DISCHARGE GRILLE COMPLETE

1
1

CWT01C622
CWE20C629

CWT01C623
@

14
15

VANE COMPLETE (LEFT)


VANE COMPLETE (RIGHT)

1
1

CWE24C113
CWE24C114

@
@

16

MOTOR - AIR SWING (UP/DOWN)

CWA98260

17

LEAD WIRE - AIR SWING MOTOR (UP/DOWN)

CWA67C1814

18

MOTOR - AIR SWING (RIGHT)

CWA98276

19

LEAD WIRE -AIR SWING MOTOR (RIGHT)

CWA67C2187

CWA98277

CWA67C2188

22

CAP COMPLETE

CWH52C003

23

VANE

CWE24462A

24

LEVER COMPLETE

CWH65C026

25

RETAINING RING

XUC3

26

PARTICULAR PIECE

CWD931019

27

ELECRTONIC CONTROLLER

CWA741406

CWA741405

28

TERMINAL BOARD COMPLETE

CWA28C579

29

POWER SUPPLY CORD

CWA20C763

CWA20C764

CONTROL BOARD COVER

CWH13463

CONTROL BOARD COVER

CWH13465

32

CONTROL BOARD COVER

CWH13466

33
34
35

CONTROL BOARD COVER


PARTICULAR PIECE
INDICATOR HOLDER

1
1
1

CWH13464
CWD931040
CWD931018

@
@
@

36

ELECTRONIC CONTROLLER (RECEIVER )

CWA74919

37

LEAD WIRE - RECEIVER

CWA67C2913

38

INDICATOR COMPLETE

CWE39C299

39

LEAD WIRE - INDICATOR

CWA67C2912

40

SENSOR COMPLETE

CWA50C613

41

HOLDER SENSOR

CWH32142

42

REMOTE CONTROL SWITCH

CWA75C711

43

FRONT GRILLE COMPLETE

CWE11C964

44

INTAKE GRILLE COMPLETE

CWE22C333

45

DECORATION BASE

CWE35C024

46

TAB

CWD931020

47

GRILLE DOOR COMPLETE

CWE14C103

48

AIR FILTER

CWD00240

49

CAP - FRONT GRILLE

CWH52267

50

SCREW - FRONT GRILLE

XTN4+16C

51

DRAIN HOSE

CWH5880580

52

OPERATING INSTRUCTIONS

CWF561630

CWD00220

58

REMOTE CONTROL HOLDER

CWH36161

All parts are supplied from MACC, Malaysia (Vendor Code: 086).
t marked parts are recommended to be kept in stock.

30

31

AIR PURIFYING FILTER

LEAD WIRE - AIR SWING MOTOR (LEFT)

MOTOR - AIR SWING (LEFT)

57

(Note)

21

20

O
O
O

67

66

Untitled-4

CS-G93KE

QTY
1

NO.
53

66

6/21/00, 9:40 AM

REMARKS

CS-G93KE

CS-G93KE

Exploded View

Replacement Parts List

CU-G93KE / CU-G123KE

<Model: CU-G93KE / CU-G123KE>


2

{
]

\
[
]

}
@

1
;

"

,
3
?

<
>

+
~

:
6

&

5
9
|

DESCRIPTION & NAME


CHASSY COMPLETE

NO.
1

1
%
6

67

CU-G123KE
@
CWD54255

REMARKS

FAN MOTOR BRACKET

CWD54254

SCREW - FAN MOTOR BRACKET

10

FAN MOTOR

CWA95384

CWA95380

SCREW - FAN MOTOR

CWH55406

COMPRESSOR

2RD132X5BB03

2RD132X5BA03

SOUND PROOF MATERIAL

CWG30901

ANTI VIBRATION BUSHING

CWH50183

NUT

CWH56000

10

CONDENSER

CWB32C350

CWB32C349

11

WIRE NET

CWD04197A

CWD04198A

12

REACTOR (RIGHT)

CWA42134

13

REACTOR (LEFT)

CWA42135

14

HOLDER COUPLING

CWH35177

15

3 WAY VALVE

CWB01481

CWB01480

16

2 WAY VALVE

CWB02308

17

STRAINER

CWB11025

18

4 WAY VALVE

CWB00002

CWB00003

19

TUBE ASSY (CAPILLARY TUBE)

CWT01C668

CWT01C667

20

SOUND PROOF BOARD

CWH15290

CWH15291

21

AIR GUIDER PROPELLER FAN

CWD31C035

22

PROPELLER FAN

CWH00K087

23

NUT

CWH56053

24

V COIL COMPLETE

CWA43C686

25

HOLDER SENSOR

CWH32074

26

HOLDER SENSOR

CWH32082

27

SENSOR COMPLETE

CWA50C614

28

TERMINAL COVER

CWH17006

29

NUT

CWH7080300

30

CONTROL BOARD

CWH10978

31

DIODE BRIDGE 1

A54S25VB60

32

DIODE BRIDGE 2

A54D15VBA80

A54D25VB80

33

CAPACITOR

1/2

CWA30201(1)

CWA30200 (2)

34

HOLDER CAPACITOR

CWH30183

CWH30184

35

SH CAPACITOR

CWA31137

36

LEAD WIRE COMPLETE (ZNR)

CWA67C2209

CWA67C2146

37
38
39
40

CONTROL BOARD
NOISE FILTER
RESISTOR
ELECTRONIC CONTROLLER

1
1
1
1

CWH10979
CWA49C209
CWA47038
CWA73C312

@
@
@
CWA73C311

O
O
O

41

FUSE

XBACW12

42

CONTROL BOARD COVER

CWH13C324

43

CABINET SIDE PLATE

CWE04218A

44

CABINET SIDE PLATE

CWE04217A

CWE04219A

45

HANDLE

CWE16037C

46

CABINET FRONT PLATE

CWE06K103A

47

CABINET TOP PLATE

CWE03K036A

CWE03K037A

48

CONTROL BOARD COVER

CWH13C325

49

DRAIN ELBOW

CWH5850080

All parts are supplied from MACC, Malaysia (Vendor Code: 086).
t marked parts are recommended to be kept in stock.

69

68

Untitled-4

CU-G93KE
CWD50K660A

(Note)
(Note) : The above exploded view is for the purpose of parts
disassembly and replacement.
The non-numbered parts are not kept as standard
service parts.

QTY
1

6/21/00, 9:40 AM

O
O

CS-G93KE

Electronic Parts List


<Model : CWA741405 / CWA741406> Indoor PCB
SYMBOL

DESCRIPTION & NAME

BZ1

PART NO.

BUZZER

A48040

D1, D2, D4, D5, D7, D8

DIODE

A541SS355T

D3, D6, D9

DIODE

A54D1F60

DIODE BRIDGE

A54D3SBA60F1

FUSE

XBA2C31TR0

IC1

INTERGRATED CIRCUIT

A5278366F100

IC2

INTERGRATED CIRCUIT

A52BR9020F

IC3

INTERGRATED CIRCUIT

A52MPC393G22

IC4

INTERGRATED CIRCUIT

A52PST600DR

DB1
FUSE

IC5, IC6

INTERGRATED CIRCUIT

A52A2003GR2

IC7, IC8

INTERGRATED CIRCUIT

A52C108

ICX

INTERGRATED CIRCUIT

A53715C (CWA741406)
A53714C (CWA741405)

PC1

PHOTO COUPLER

A52S2501L1KC

PC2

PHOTO COUPLER

A52TLP371LF

PC3

PHOTO COUPLER

A52LP521L1BL

TRANSISTOR

A55DA143XKTX

SW1, SW2

SWITCH

A04085

SW3, SW4

SWITCH

A01059

Q1, Q3, Q4, Q7, Q8, Q10

T1

TRANSFORMER

A40C295

X1

RESONATOR

A45CTS4MG02T

ZNR1

ZNR

ERZVEAV511

ZNR2

ZNR

ERZVA9V271

70

Untitled-6

70

6/21/00, 9:45 AM

MAC9509078C2

CS-G93KE

Electronic Parts List


<Model : CWA73C312 / CWA73C311> Outdoor PCB
SYMBOL

DESCRIPTION & NAME

C-FM

PART NO.

CAPACITOR -FM

A31735

CURRENT TRANSFORMER

A40260

D1

DIODE

A54AU02ZV0

D17, D18, D20

DIODE

A54RA15-06V3

D19

DIODE

A54RA15-10V3

D2, D3, D4, D5, D8

DIODE

A54RA22-04V3

D6

DIODE

A541SS136T

D9 ~ D16

DIODE

A54MA165TA5

CT1

FUSE1, FUSE2

FUSE

XBA2C31TR0

IC1

INTERGRATED CIRCUIT

A5278214WP43

IC2

INTERGRATED CIRCUIT

A52MPA2003C

IC3

INTERGRATED CIRCUIT

A52C050

IC4

INTERGRATED CIRCUIT

A52M51951AST

IC5

INTERGRATED CIRCUIT

A52BX8454

IC6

INTERGRATED CIRCUIT

A52AN78L10TA

IC7

INTERGRATED CIRCUIT

A52AN79L10TA

IC8

INTERGRATED CIRCUIT

A52MPC339C

ICX

SERIAL PROM

A53716B (CWA741404)
A53717A (CWA741408)

LED

A54SLR342DB7

PC1, PC3, PC12, PC13

PHOTO COUPLER

A52S2501-1PC

PC2

PHOTO COUPLER

A52LP521-3GB

PC4

PHOTO COUPLER

A52PS2633E

LED1

PC5

PHOTO COUPLER

A52S2501-1LC

PC6 ~ PC11

PHOTO COUPLER

A52LP521-1GH

Q1

TRANSISTOR

A55C070

Q4, Q6, Q7

TRANSISTOR

A55DTA143XST

Q5

TRANSISTOR

A55C1740STPQ

Q8

TRANSISTOR

A5520CVL33A

RY-FM

RELAY

A00161

RY-PWR

RELAY

A00106

SSR1
T1
VR1
VR2

SSR

A56S26MD01M

TRANSFORMER

A40367

VARISTOR

A44EVMEASB22

VARISTOR

A44VMEASB13

X1

RESONATOR

A45ST12MTWOT

ZD1

ZENAR DIODE

A54D6.2EB1TB

ZNR

ERZVA9V271

ZNR1

71

Untitled-6

71

6/21/00, 9:45 AM

CS-G93K/G123K

CS-G93K/G123K

CS-G93K/G123K

CS-G93K/G123K

ELECTRONIC CIRCUIT DIAGRAM <INDOOR UNIT>

CS-G93KE
CS-G123KE

C6
0.01

C37
10

LC1
A49AF32102TL

R29
100k
5

R34
10k

R37
10k

R39
10k

R43
10k

RECEIVER
3 DL

(MX-3)
CN-RCV1

PH302C

1
2
3

VCC1 1

7 IN-

OUT 2

6 CO

VCC2 3

0.01

FO 4

R21
1k

3
2
1
+
C7
1.5 (T)

2 CS

R24
5.1k

C21
0.01

RESET SIGNAL
GENERATION

CLOCK PULSE
GENERATION

Q3
A55DC143XKTX

b
c

c
R62
5.1k

R66
330

RST 8

C18
0.022

R63
1k

CLOCK PULSE
GENERATION

10k

C23
100
6.3V

S0 6

6 D0

CS 3

S1 7

5 D1

BUSY 1
7

102C
THEROMAL
FUSE

R67
1k

CN-PWR
CN-PWR

PC2 TLP371

C17
0.1

R68
680

ICX

RECEPTION
4

3
1~3

CLOCK PULSE
1.1GENERATION

ZNR2
ERZVA9V271

R72
2.4k

D1
A541SS355T

R73
1k

R74
47k
2W

R79
47k
2W

R82
510k

R81
510k

C30
0.22

L6
A43101T

ZNR1
ERZVEAV511

D9
A54D1F60

LF1
A49217

T1

23

22

21

20

19

18

17

2.5
16

2.5

15

14

13

12

11

10

7
b

9
8
7
6
5
4
3
2
1

R110
R111

180 x 4

1
2
3
4
5
6
7
8
9

79

SPEED
CONTROL

78

28

77

29

76

31

12
C35
470
(FC)

C3
0.01

SEGMENT
DRIVE

5.1k

C25
0.01

Q10
A55DA143XKTX

Q8
A55DA143XKTX

Q7
A55DA143XKTX

SEGMENT DRIVE

SEGMENT DRIVE

SEGMENT DRIVE

e
10k

R71

5.1k

R77

5.1k

GND F
8
2 - 3.5

R23
10k

D5

STANDBY

4.7k

4.7k

10k
b

71

35

70
TIMER SHORTEN

38

R30
10k

40
R38
24k

R33
10k

R40
10k

2.5

AUTO

REMOTE CONTROL COMMAND INPUT

R3
1k

C36
390
(FA)
c

D
1 FAN SPEED CONTROL SIGNAL

R2
10k

R57
10k

4.7k

R1

1k
BZ1

10k

R48

(PH4)
CN-TH
1
2
3
4

(ZH5)

1
2
3
4
5

R73 +
10k

C26
33
25V

10

9
g
f

12

13

1
2
3
4
5

14

15

16
(MX-5)
CN-STM2

TEST RUN

CLOCK
PULSE INPUT
41

42

43

STEPPING MOTOR DRIVE


RIGHT

HEAT EXCHANGER TEMP.

L3

44

45

46

FAN MOTOR
R4
10k

67

10

47

48

49

50

51

52

12

11

14

13

22

53

54

55

56

57

58

59

60

UP/DOWN
61

62

63

LOGIC
64

R55
10k

C13
0.01

5
L1
A438LM31A02T

LOGIC

(MX-5)
CN-STM3

9
e

13

14

1
2
3
4
5

15

16

RESISTANCE
AT 20C
( )

VOLTAGE
AC ( V )

1 & 2

6.1

21 ( 23 )

1 & 3

6.1

21 ( 23 )

2 & 3

6.1

21 ( 23 )

LOGIC
DRIVE
CIRCUIT

C24
1000P
C25
1000P

Fig.2

16
15

(XH3)
CN-MTR

RA
RA
RA

SENSOR
CIRCUIT

4
1
23

Fig. 1

3
2
1

Sensor (Thermistor)
Characteristics

17
R68
1M

70

INDOOR FAN MOTOR

DRIVE
CIRCUIT

IC5
A52A2003GR2

60

STEPPING MOTOR DRIVE


6
5
4

FAN MOTOR CONTROL


+

R59
5.49k

21

19

28

C12
1
50V

2
1

R28
10k

IC3
A52MPC393G22
6
5

D2

CHECK PIN

IC6
A52A2003GR2

R32
10k

SW3
TEST RUN

R69
26.7k
1
R25
220

C43
1000P
C44 +
1
50V

R80
13.7k
1/4 W

8
4

3
2

C42
1000P

IC3
A52MPC393G22

R47
10k

R26
49.9k
+

C28
10

C13
0.01

R46
10k
SW4
AUTO

R27
5.49k

R56
10k

C15
0.01

50

IC7
A52TPD4007K

R58
49.9k

D4
A541SS355

(GND)

12

BETWEEN
COILS

66

1
2
3
4
5

2 OVERCURRENT SIGNAL OUTPUT

L2

1k

R18
1k

68

R45
374
7

65

LEFT

(ZH5)

1
2
3
4
5

R35 +
15k

INTAKE AIR TEMP.

C9
10
16V

11
(MX-5)
CN-STM1

1
2
3
4
5

R41 +
5.9k

C8
10
16V

4 FAN SPEED CONTROL VOLTAGE

R22
0.33

BZ

STANDBY

C11
0.01

PIPE TEMP. SENSOR


(20k 3950)

R20
18.2k

C41
5600P

POWER

REMOTE CONTROL NO.

39

Q1
A55DC143XKTX

SW2

Fig.2

R51
2k

G93KE-ECD1

Intake
IntakeAir/
Air/Indoor
IndoorHeat
Heat
Exchanger
ExchangerTemp.
Temp.
44

Intake
IntakeAir
Air
Temp.
Temp.Data
Data

30
3

20

33
22
11

10

Indoor
IndoorHeat
HeatExchanger
Exchanger
Temp.
Temp.Data
Data

STEPPING MOTOR DRIVE


4

-10

10

20

30

40

50

00

10
10 20
20 30
30 40
40 50
50 6060 7070

Temperature
Temperature(C)
(C)

Temperature (C)

CS/CU-G93KE/G123KE
(45%)
CI-G123KE.DWG

Fig.
Fig.
22
Fig.2

Indoor Heat Exchanger


Sensor
Indoor Intake / Outdoor
Air Sensor
Outdoor Heat Exchanger
Sensor
1

40

(ZH5)

C10
22
(FC)

C29
1000P
630V

D8

69
GND

37

SW1
4.7k

D7

18

Fig.1

C40
1000P
630V

15 - 34

72

34

36
R31
1k

R36
10k

AIR TEMP. SENSOR


(15k 3950)

C39
2200P

A541SS355 x 3

73

J2

J1

C26
1000P

e
10k

REMOTE CONTROL NO.


SW1
J2
1
OFF
2
ON
3
OFF
SHORT
4
ON
SHORT

CHECK PIN
(TEST)

COM1 d
COM2 COM3 D.P
1
2
3
4
5
6

UP/DOWN

DC INPUT C

7 DC OUTPUT

C38
0.01

R19
25.5k

74

33

LEFT

A40C295 DC/DC CONVERTER

75

IC1
A5278366F100

32

D101
A54LNM23301A

RIGHT

C34
100
450V
(ECEC)

A
30

C104

C103

1000P x 4

Voltage (V)
(V)
Voltage

L5

CN-DISP2

CLK 8
10

IC101
A52M66311FP
9

FAN MOTOR

R50

A 4

820 x 7

10

CN-DISP1

CKS 6

OE 5
GND 9

5V

C2
0.01

DISPLAY

R108

R109

R112
100k
C106
0.01

BUZZER

27

1.5

R 7

RELAY
DRIVE

4MHz
OSC

26

+ C105

C102

R101
R102
R103
R104
R105
R106
R107

VCC 3

80
DATA TRANSMISSION

R117
R118
R119
R120
R121

C101

QA
QB
QC
QD
QE
QF
QG
QH
QI
QJ
QK
QL
QM
QN
QO
QP

5 GND
RESET

430 x 9
1
2
24
23
22
21
20
19
18
17
16
15
14
13
11
12

C1
100

C16
0.01

C33
0.1

DB1
A54D3SBA60F1
~
+

A
B
C
D
E
5

5
24

25

D103
A54LNK5372
5
5
5
5

11

L4

5
R113
R114
R115
R116

C32
0.01
250VAC
(KH)
C31
0.01
250VAC
(KH)

TH1
A47N11D5R0TT

REGULATOR

D102
A54LNK4171B POWERFUL
SLEEP
TIMER
POWER

FUSE1
3.15A

D6
A54D1F60

IC8
A52C108

DISPLAY

PC1
A52S2581L1KC

C5
2200P

R70
200k
1 0

R42
150k

R76
15k
2W

4
6 0

PC3
TLP521L1BL

11

5 0

2
1~2

10

D3
A54D1F68

TRANSMISSION
1

IC6
A52A2003GR2

IC2
A52BR9020F

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

4.7k

C4
1000p

R64
7.5k

X1
4MHz (27pF X 2)

TO OUTDOOR

1
2
3

R65
10k

2
4 SCK

C19
3300p

137k
5 GND

0.01

IC4
A52PST600D

4.7k

C24 +
33
25V

CN-RCV2
(MX-3)

6.3V
47

10k

I
G

Q4
A55DA143XKTX

Resistance (k )

8 IN+
330

1 8
SCK 5

C22
1.5
16V
(T)

MAIN

RY-PWR

MAIN SWITCH
AC 230V
50Hz

10

11

6/20/00, 4:03 PM

12

13

14

15

16

17

18

19

CS-G93K/G123K

CS-G93K/G123K

Time

Test mode
When test point
short-circuited

4 way valve abnormality

4 min.

2.4 sec.

Outdoor air temp. for Hz No. decision

30 min.

0 sec.

Anti-dew formation control

20 min.

0 sec.
Deice detection

Test mode
When test point
short-circuited

30 sec.

3 sec.

120 min.

24 sec.

80 min.

16 sec.

Anti-freezing control

6 min.

0 sec.

40 min.

8 sec.

Thermo OFF delay

3 min.

0 sec.

40 min.

8 sec.

Low pressure control (gas leakage) compressor OFF time

3 min.

0 sec.

Deice forced completion

11 min.

66 sec.

2 min. 58 sec.

0 sec.

Hz lock time

30 sec.

0 sec.

Outdoor fan delay operation control

30 sec.

3 sec.

4 way valve delay operation control

3 min.

18 sec.

30 sec.
0 sec.

LED1
SID1003BQ

R5
2.2
1/8W

Q2
2SD602

X1
3.52Hz
(33P x 2)

R4
22k

C4
8P
(NPO)

X2
32.768kHz

16

15

14

13

12

11

10

17 XOSC2

SEG 7 64
SEG8 63

18 XOSC1

* Diode without indication .............. MA165


* Circuit Diagram is subject to change without
notice for further development.

Heating SSHi fan speed shift

120 min.

12 sec.

Cooling SHi fan speed shift

30 min.

3 sec.

Hot start forced completion

4 min.

0 sec.

R1
100k
R6
300

C6
0.1

SEG9 62

19 VSS
DOOR OPEN/CLOSE
SW1
(CLOSE:ON)

SW2

20 RESET

SEG10 61

21 PC3

SEG11 60

22 PC2

SEG12 59
SEG13 58

23 PC1

9 sec.
R14
51k

3 sec.

SEG19 52

30 PA5

SEG20 51

31 PA6

SEG21 50
SEG29

SEG28

SEG27

SEG26

SEG25

SEG24

12 sec.

SEG30

2 min.

After Hot start / Deice

SEG18 53

29 PA4

32 PA7

1 hour 6 sec.

Sleep mode time shift

SEG17 54

28 PA3

SEG31

42 sec.

SEG16 55

27 PA2

SEG32

420 min.

SEG15 56

26 PA1

RMO

18 sec.

R13
51k

SEG14 57

25 PA0

BZ

180 min.

30 min.

Auto mode judgement interval

Remote Controller No.

PC7

Anti-fog discharge control

IC1

24 PC0

PC6

90 min.

R12
51k

PC5

J-B

3 sec.

PC4

30 min.

LIQUID CRYSTAL DISPLAY

C5
8P
(NPO)

1 hour 1 min.

24 hours ON / OFF timer

R7
200k

SEG6

0 sec.

R8
200k

R2
1.5k

SEG5

20 sec.

R9
200k
R3
51

SEG4

Auto mode judgement sampling time

CN1

SEG3

0 sec.

C9
0.01

SEG2

10 sec.

SEG1

Self diagnosis display time

+ C2
47

SEG0

0 sec.

C8
0.01

COM2

2 min.

C1
47

R11
510k

R03

Intake air temp. sampling time

Q1
2SB710

COM1

60 sec.

C7
0.01

COM0

Odour timer status shift time

WIRELESS REMOTE CONTROL

VLCD3

Time delay safety control

REMOTE CONTROL

VLCD2

DC PEAK

Time

VDD

* Indications for resistance


a. K .... k
M ... M
W ... watt
Not indicated .... 1/4W
b. Type
Not indicated .......... carbon resister
Tolerance5%
.......... metal oxide resister
Tolerance1%

* Indications for capacitor


a. Unit
.... F
P .... pF
b. Type Not indicated ... ceramic capacitor
(S) .......... S series aluminium
electrolytic capacitor
(Z) .......... Z series aluminium
electrolytic capacitor
(SU) ....... SU series aluminium
electrolytic capacitor
(P) .......... P series polyester system
(SXE) ..... SXE series aluminium
electrolytic capacitor
(SRA)...... SRA series aluminium
electrolytic capacitor
(KME)......KME series aluminium
electrolytic capacitor

Name

VLCD1

Name

ELECTRONIC CIRCUIT DIAGRAM

OSC1

Before using the circuit diagram, read the following carefully.


* Voltage measurement
Voltage has been measured with a digital
tester at rated frequency.
Use them for servicing.
Voltage indication is in Red at cooling and all
operations.
Voltage indication is in (Red) at heating.

TIMER TABLE <OUTDOOR>

TIMER TABLE <INDOOR>

How to use electronic circuit diagram

CS-G93K/G123K

OSC2

CS-G93K/G123K

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

SEG22 49
SEG 23
48

C
(POWERFUL)

FAN SPEED
(TEMP 9)

SELF
DIAGNOSIS

SLEEP

TIMER
ON

TIMER
CANCEL

AIR SWING
8
9

TIMER
OFF

TIMER
SET

SW2
0
WIDE / SPOT

AIR SWING
/(OFF / ON)
q

MODE
(TEMP 8)

CLOCK

J-B

OFF

ON

OFF

SHORT

ON

SHORT

G93KE-ECD1

10

11

6/20/00, 4:03 PM

12

13

14

15

16

17

18

19

CS-G93K/G123K

CS-G93K/G123K

CS-G93K/G123K

ELECTRONIC CIRCUIT DIAGRAM <OUTDOOR UNIT>

CU-G93KE
CU-G123KE
OUTDOOR TERMINAL
AC 230V
AC18-23V

Fig. 3
Fig. 3

FUSE
250V, 20A

1
2
3

DIODE
1

2
~

AC230V

REACTOR

CAPACITOR

Outdoor Air/Outdoor
Heat Exchanger Temp.

+
~

FOR CU-G123KE ONLY

REACTOR

DIODE

+
C1

Outdoor Air
Temp. Data

C2

PTC
(WHT)
AC1

(WHT)
AC2
L

APPROX 280 DCV

AC3

DC+

Voltage (V)

DC-

RY-PWR

Q8
D11

D14

FAN MOTOR
R79
10k

C27
220
10V

5
6

4
3
1

HOT

(YEL)
(XH-4)
CN-TH

COMPRESSOR
TEMP. SENSOR
(50k, 3975) Fig. 5

R81
1k
Fig. 3

R55 +
4.99k
5V

C31 +
10
16V

C29 +
10
16V

1
IPM
(POWER
TRANSISTOR)
BASE
SIGNAL
OUTPUT

C30
10
16V

L2
A43036

Fig. 4

4
5

C37
22
10V
C28 +
220
16V

R52
10k

VOLTAGE
DETECTION

PHOTO COUPLER
DRIVE

56

HEAT EXCHANGER
TEMP.

RELAY DRIVE

CS

S1 7

DL

R56
10k

S0 6

3.4

R66
38k

10

COMP. TEMP.

11

CURRENT

C39 +
22
400V

R65
51k

D18
ERA15-06

1
R59
680

C37
2200p
50V

2.6
c

2.6
b

Q6
UN421F

10k

2.2k
e

D17
ERA15-06

(RED)
AC4

ZNR1

R61
1k

R64
11k
3W

15
16
17

47

18

Vcc

Vsen

DATA
TRANSMISSION

FAN MOTOR
DRIVE

R2
27
3/4W

23
24
4-WAY VALVE

25

TLP521-IGH

LED1 (YLW)
A5448YPXTA3E

R34
620

R37
560

10k

4.7k

0
5

PC8

O
C46
3.3
50V

5V

I
+

C18
470
10V

C47
0.1
(ECQV)

IC4
78M05
REGULATOR

X1
12MHz
30pF X 2

R42
150k

0 (5)

38

TIMER SHORTEN

TLP521-IGH

A52MPC339C 18
13
11

RY-PWR

12

16

15

13

11

14

DC. PEAK
DC RESET

36
35

30

34

31

R28
4.7k

GND

R43
1k

32

R45
STN-BY 10k

R19
750k

C19
120
25V
R10
118
1W
+ C20
120
50V

R40
560

TLP521-IGH

8
9

C26
2200p

PC5
TLP521-1BL
(BL)

R7
330

C38
1000p

Vin

CT Vout

Vcc

Vsen

GND

11

Vfo

12

13

R3
1

C40
1
630v
(ECQE)

Total Running
Current Data

GND

Vin

CT Vout

Vcc

Vsen

GND

GND

Vin

CT Vout

Vcc

Vsen

GND

GND

3
2
1

C25
1000P

10V

0.1 (ECQB)

33k

C22 +
10
25V

3k

1
2
9

+
6

23.2k

989k

REGULATOR

0.1 (ECQB)

C23
1000P

C12
0.33
50V
(ECQV)

1M
33k
3k

11

1000P 47.5k

+
12

10

C11
0.33
50V
(ECQV)

33k
3k

11

1000P 47.5k

10

R84
383k
R15
619k

Fig.5 5
Fig.

Fig.
Fig. 65

Compressor Temp. Sensor


(Thermistor) Characteristics

Compressor Temp. Data

23.2k

50

R14
75k

IC5
A52BX454
COMPRESSOR ROTOR
POSITION DETECTION

40
30

3
2
1

20
10
0

50 60 70 80 90 100 110 120 130 140


20

40

60

80

100

120

Temperature (C)

140

Temperature (C)

G93KE-ECD2

6/20/00, 4:06 PM

15

70

R24
3.6k

1.5k x 3
R27
R28
R29

10

Current (A)

60

1M

R26
3.6k

PC2
A52LP521-3

R83
499k
R13
499k

23.2k

0.1 (ECQB)
4

GND

R74
240k
1

GND

Vfo Temp.

R16
75k

+
R25
3.6k

989k

Vsen

R18
75k

C13
0.33
50V
(ECQV)

1000P 47.5k
-

D10
EBR12-01

TLP521-I
DC PEAK

Q5
C1740S

CT Vout

Vcc

1M

5
C48
0.01

R31
10k

R82
383k
R17
619k

989k

C21 +
10
25V

Vin

15

R63
7.5k

VR2
1k

C17
22
25V
(SXE)

D20
ERA15-06

100 ACV

Vfo

TLP521-I

1000p x 3
C34
C35
C36

Fig. 44
Fig.

ZD1
A54D6.2
EB1

IC7
A52AN79L10

R47
1k

C6
100
50V
(SXE)

IC8

R23

R33
18k

R30
15k

DC RESET
14

R76
4.7k

R46
2.2k

C5
0.033
(ECQM)

R21
1.82k

D8
A54RA22-04

R32
1k

C16
0.01

R11
5.23k

R9
4.53k

10V

PC3

R44
51k

GND

14

TLP521-IGH

TLP521-I

R41
470
1W

TEST (NH-2)

15

IC6
A52AN78L10

PC11

6
7

IC8

R77
56k
3W

D9
EBR12-01

RY-FM

RA1
10k X 5

L1
A43036

C24
0.01

GND

Vfo

R72
560

R73
5.23k

30

Temperature (C)

100 ACV

REGULATOR

PC1

29

R6
100
3/4W
D6
A541SS136

10

Vsen

20

10

16

PC10
R39
560

IC8

27
28

Vcc

10

COMPRESSOR

C3
100
10V

R78
56k
3W

Q1
A55C4420

C10
270
25V
(SXE)

C14
0.01
R1
5.23k

R22
2.55k

37

R70
560

CT Vout

R71
560

R12
510k

IC2
PA2003C

Vin

0
-10

3
2
1

IC8

3 4
2
5
12

TLP521-I

R75
10k

R38
560

R80
4.7k

2.5

5
2.5

1
PC9

12

D5
A54RA22-04

VOLTAGE
DETECTION
PC12

+
G

R8
560k
3/4W

R4
620k
3/4W

C4
470p
1kV AC
3

C1
470
25V

R5
680
3W

26
COMPRESSOR
ROTOR POSITION
DETECTION

13

C9
+ 270
25V
(SXE)

Q4
UN411F

Vfo

FUSE2
T3 15A L250V

R69
560

TLP521-IGH

8
39

C8
+ 270
25V
(SXE)
6

PC13

41

R68
560

GND

Vfo

D4
EBR43-02

21

42

C2
10
25V

5V

(XH3)
CN-MTR
100 ACV

11

3.4

20

22

GND

REGULATOR

D1
A54AU02ZV8

C7
270
25V
(SXE)

3.4

19

33

R62
300
2

C15
1000PF
AC250V

12MHz
OSC

14

48

40
2.6

R60
200k

POWER

RESET

43

PC4
A52PS2633E

R36
560

13
REF. VOLTAGE

3.4

12

44

D19
ERA15-10

1
2
3
4
5

INTAKE AIR TEMP.

45

R57
1k

54

46

2.3

SCK 5

55

49

Vcc 8

1 Vcc

4 GND

57

50

R52
10k
C33 +
470
16V

CN-AC

POWER ON

58

1
PC7

3.4

6
PHOTO COUPLER
DRIVE

51

C32 +
220
16V

1
2

60

53

R51
20.5k

ICX
A52D27C18C

61

52

(NH-2)
CN-S

TLP521-IGH

3.4

Fig. 6

CN-TANK
(NV-2)

TEST RUN

R54
15.8k

Fig. 3

1
2

R67
560

59
2.8

R53
15k

64
63

R50
10k

A56S26MD81M

4
3
2
1

D3
EBR43-02

62

PIPE TEMP.
SENSOR
(4.96k, 3800)
AIR TEMP. Fig. 1
SENSOR
(15k, 3950)

3
1

IC3
A5278M05

C98
0.01
3.4

1
2
3

IC1
A5278214WC26

SSR1

(BLUE)
(VH-3)
CN-HOT

1
PC6
R35
560

RY-FM

T1
A48367

D2
A54RA22-04

CR1
120
0.033

OPEN : 145C
CLOSE : 88C

Outdoor Heat
Exchanger Temp. Data

Voltage (V)

CR2
120
0.033

CT Vout

Voltage (V)

YEL

R49
598

VR1
200

1
2
3
4
5

Vin

Resistance (k )

CN-FM

D13
D15

C-FM
400V
2F

D12

FUSE1
T3 15A L250V

BLU

RED

4.7k

2
1

Q7
UN4116

D16
R48
1.65k

CT1
A40260

10

11

12

13

14

40

CS-G93K/G123K

CS-G93K/G123K

CS-G93K/G123K

PRINT PATTERN
INDOOR UNIT PRINTED CIRCUIT BOARD

OUTDOOR UNIT PRINTED CIRCUIT BOARD

MAIN

INDICATOR

MAIN

G93KE-ECD2

6/20/00, 4:07 PM

10

11

12

13

14

MACC

Untitled-7

6/21/00, 9:47 AM

Printed in Malaysia
P981203500YH