MAC9812043C2
Service Manual
Room Air Conditioners
CS-G93KE / CU-G93KE
CS-G123KE / CU-G123KE
Contents
Features .......................................................... 1
Functions ................................................... 2 6
Product Specifications ............................. 7 10
Dimensions ............................................ 11 12
Refrigeration Cycle Diagram ......................... 13
Block Diagram ............................................... 14
Wiring Diagram ...................................... 15 16
Operation Details ................................... 17 47
Installation Information .......................... 48 49
Servicing Information ............................. 50 62
Technical Data ....................................... 63 64
Exploded View ......................................... 65, 68
Replacement Parts List ..................... 66, 67, 69
Electronic Parts List ............................... 70 71
Untitled-7
6/21/00, 9:47 AM
CS-G93KE
! WARNING
This service information is designed for experienced repair technicians only and is not designed for use by the general public. It does not contain
warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product. Products powered by electricity
should be serviced or repaired only by experienced professional technicians. Any attempt to service or repair the product or products dealt with
in this service information by anyone else could result in serious injury or death.
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigeration circuit.
Features
Product
Serviceability
Self diagnosis
Test Run at both Cooling and Heating rated frequency
Quality Improvement
High power supply voltage protection
Low power supply voltage protection
Gas leakage detection
Untitled-1
6/20/00, 4:18 PM
CS-G93KE
Functions
Remote Control
OFF / ON
L
TEMP
Operation OFF / ON
MODE
POWERFUL
FAN SPEED
TIMER
ON OFF
HEAT
COOL
DRY
FAN
SET
CANCEL
Low
CLOCK
Medium
Medium
Clock Setting
Current time setting.
Medium+
SLEEP
High
Automatic Fan Speed
WIDE/
SPOT
AIR SWING
WIDE / SPOT
POWERFUL
P O W E R LOW
MONITOR
Automatic Control
AUTO
POWERFUL
P O W E R LOW
MONITOR
Manual Control
Automatic Control
Manual Control
2
Untitled-1
6/20/00, 4:18 PM
MAC9609040C2
CS-G93KE
Functions
Indoor Unit
AUTO
OFF / ON
Timer Operation *
Powerful Mode *
Lights up in operation,
blinks in Automatic
Operation judging
and Hot Start operation.
TIMER (Orange)
Lights up in Timer
Setting.
Blinks in Self Diagnosis Control.
SLEEP (Orange)
Lights up in Sleep
Mode Operation.
POWERFUL (Orange) Lights up when
Powerful mode is
selected
POWER
(Red)
Untitled-1
6/20/00, 4:18 PM
CS-G93KE
Functions
CS-G93KE
CS-G93KE
Functions
Functions
Outdoor Unit
HEATING OPERATION
AUTOMATIC OPERATION
CS-G123KE
Cooling
15 64 Hz
15 92 Hz
Soft Dry
15 22 Hz
15 22 Hz
Heating
15 99 Hz
15 115 Hz
Hot Start *
FAN OPERATION
Minimum Frequency Operation
Protection *
Temperature Shift *
Self Diagnosis *
Anti-Freezing Control *
Standby Control *
Quiet Operation *
Deice Operation *
DC Peak *
Standby Control *
Deice Operation *
Compressor Overheating
Protection *
Untitled-1
6/20/00, 4:29 PM
MAC9609040C2
CS-G93KE
CS-G93KE
Product Specifications
Product Specifications
Unit
kW
Btu/h
kW
Btu/h
s/h
Pint/h
Phase
V
Cycle
OUTLET
Cooling Capacity
Heating Capacity
Moisture Removal
Power Source
Airflow Method
CU-G93KE
2.6 (0.70 - 3.00)
8,800 (2,300 - 10,200)
3.6 (0.63 - 5.00)
12,200 (2,100 - 17,000)
1.6
3.4
Single
230
50
TOP VIEW
SIDE VIEW
INTAKE
Air Volume
m3/min (cfm)
m3/min (cfm)
m3/min (cfm)
Outdoor Air
m3/min (cfm)
Noise Level
Electrical
Data
dB (A)
kW
Input
Running Current
W/W
COP
Starting Current
Piping Connection Port
(Flare piping)
Pipe Size
(Flare piping)
Drain
Inner diameter
Hose
Length
Power Cord Length
Number of core-wire
Height
Dimensions
Width
Depth
Net Weight
Compressor
Type
Motor
Rated
Air Circulation
Motor
Fan
Speed
Type
Output
Type
Material
Type
Input
Rated Output
Lo (Cool/Heat)
Me (Cool/Heat)
Hi (Cool/Heat)
A
inch
inch
inch
inch
mm
m
inch (mm)
inch (mm)
inch (mm)
lb (kg)
W
W
rpm
rpm
rpm
Untitled-1
Cooling
Heating
Cooling
Heating
Cooling
Heating
;
;
;
;
;
;
7.0 (250)
7.6 (270)
8.8 (310)
9.4 (330)
10.0 (350)
10.8 (380)
34.1 (1200)
Product Specifications
CS-G93KE
CU-G93KE
Evaporator
Condenser
Copper
Copper
Aluminium
Aluminium
Corrugated Fin
Slit Fin
(Plate fin configuration, forced draft)
1/20
2/14
19
21
614 294 25.4
782.9 508 22
Capillary Tube
SUNISO 4GDID or
780 (27.5)
Electronic Control
Electronic Control
Electronic Control
Honeycomb
Unit
CS-G93KE
Heat
Exchanger
Description
Tube material
Fin material
Fin Type
Row / Stage
FPI
Size (W H L)
Refrigerant Control Device
mm
Refrigeration Oil
(c.c)
Refrigerant (R-22)
Thermostat
Protection Device
Length
Capillary Tube Flow Rate
Inner Diameter
Material
Air Filter
Style
Fan Motor Capacitor
CS-G93KE
g (oz)
mm
s/min
mm
F, VAC
Cooling Capacity
Heating Capacity
Moisture Removal
Power Source
CU-G123KE
3.45 (0.74 - 4.00)
11,700 (2,500 - 13,600)
4.80 (0.70 - 6.50)
16,300 (2,300 - 22,100)
2.0
4.2
Single
230
50
SIDE VIEW
TOP VIEW
OUTLET
Airflow Method
INTAKE
Air Volume
Cooling ; 46
Cooling ; High 38, Low 30
Heating ; 47
Heating ; High 39, Low 30
Cooling ; 0.73 (0.21 - 0.99)
Heating ; 0.99 (0.20 - 1.40)
Cooling ; 3.75 (max. 6.76)
Heating ; 4.80 (max. 6.76)
Cooling ; 3.56
Heating ; 3.64
4.80
G ; 3-way valve 3/8"
G ; Half Union 3/8"
L ; 2-way valve 1/4"
L ; Half Union 1/4"
G (gas side) ; 3/8"
G (gas side) ; 3/8"
L (liquid side) ; 1/4"
L (liquid side) ; 1/4"
12
0.7
2.1 m
3 core wires 1.0 mm2
10-31/32 (279)
21-9/32 (540)
27-17/32 (699)
31-15/32 (799)
11-7/32 (285)
7-15/32 (190)
86 (39)
20 (9.0)
Rotary (2 cylinders)
500
Propeller Fan
Cross-flow Fan
P.P + (Mica + Glass Fiber) 30%
AS + Glass Fiber 30%
Induction (6-poles)
Transistor (4-poles)
64
20
20
980/1,010
1,160/1,220
760
1,280/1,380
CS-G123KE
Unit
kW
Btu/h
kW
Btu/h
s/h
Pint/h
Phase
V
Cycle
m3/min (cfm)
m3/min (cfm)
m3/min (cfm)
Outdoor Air
m3/min (cfm)
Noise Level
Electrical
Data
dB (A)
kW
Input
Running Current
W/W
COP
Starting Current
Piping Connection Port
(Flare piping)
Pipe Size
(Flare piping)
Drain
Inner diameter
Hose
Length
Power Cord Length
Number of core-wire
Height
Dimensions
Width
Depth
Net Weight
Compressor
Type
Motor
Rated
Air Circulation
Motor
Fan
Speed
Type
Output
Type
Material
Type
Input
Rated Output
Lo (Cool/Heat)
Me (Cool/Heat)
Hi (Cool/Heat)
A
inch
inch
inch
inch
mm
m
inch (mm)
inch (mm)
inch (mm)
lb (kg)
W
W
rpm
rpm
rpm
6/20/00, 4:29 PM
MAC9609040C2
31.5 (1110)
12
0.7
2.1 m
Rotary (2 cylinders)
rolling piston type
Induction (4-poles)
500
Cross-flow Fan
Propeller Fan
AS + Glass Fiber 30%
P.P + (Mica + Glass Fiber) 30%
Transistor (4-poles)
Induction (6-poles)
67
20
25
1,170/1,200
1,320/1,360
1,410/1,480
790
CS-G93KE
Product Specifications
Unit
Heat
Exchanger
FPI
Size (W H L)
Refrigerant Control Device
mm
Refrigeration Oil
(c.c)
Refrigeration (R-22)
Thermostat
Protection Device
Length
Capillary Tube Flow Rate
Inner Diameter
Material
Air Filter
Style
Fan Motor Capacitor
CU-G123KE
Condenser
Copper
Aluminium
Corrugated Fin
(Plate fin configuration, forced draft)
2/14
2/20
21
16
693.5 508 44
614 294 25.4
Capillary Tube
SUNISO 4GDID or
1,070 (37.8)
Electronic Control
Electronic Control
Electronic Control
C1,C2 ; 720, C3 ; 420
P.P.
Honeycomb
Description
Tube material
Fin material
Fin Type
Row / Stage
g (oz)
mm
s/min
mm
F, VAC
10
Untitled-2
10
6/20/00, 4:33 PM
MAC9509078C2
CS-G93KE
Dimensions
CS-G93KE / CS-G123KE
Unit : mm
<Front View>
190
60
799
Left piping
hole
36
279
Air intake
direction
Air outlet
direction
60
58
60
83
<Back View>
LIQUID SIDE
65
DRAIN PORT
122
TEMP
C
POWERFUL
425
48
Relative position between the indoor unit and the installation plate <Front View>
Slot (2 places)
Slot (2 places)
Centre notch
(40)
17.8
100
350
100
Arrow
Arrow
Centre
Indoor unit
external
dimensions
line
(60)
(99)
11
Untitled-2
16.5
550
257.2
Installation
plate
(49)
710
11
6/20/00, 4:33 PM
CS-G93KE
Dimensions
CU-G93KE / CU-G123KE
699
100
69
500
99
(52)
32
162
(120)
10 cm
10 cm
100 cm
285
540
7.5
67
High Pressure
2-Ways Valve
67
Low Pressure
3-Ways Valve
11
(323)
347
12
Untitled-2
12
6/20/00, 4:33 PM
MAC9509078C2
CS-G93KE
OUTDOOR
C1
CHECK VALVE
2-WAY
VALVE
C2
C3
INTAKE AIR
TEMP.
SENSOR
OUTDOOR AIR
TEMP.
SENSOR
HEAT
EXCHANGER
TEMP.
SENSOR
HEAT EXCHANGER
(EVAPORATOR)
HEAT EXCHANGER
(CONDENSER)
4-WAY VALVE
3-WAY
VALVE
COMPRESSOR
TEMP.
SENSOR
COOLING
COMPRESSOR
HEATING
13
Untitled-2
13
6/20/00, 4:33 PM
HEAT
EXCHANGER
TEMP.
SENSOR
Untitled-2
SINGLE
PHASE
230V
50Hz
14
"C"
6/20/00, 4:33 PM
ELECTRONIC
CONTROLLER
ZNR
FUSE
(3.15A)
RY-PWR
INDOOR UNIT
DC/DC
CONVERTOR
THERMAL
FUSE
102C
POWER
SUPPLY
SWITCH
CS-G93KE / CU-G93KE
CS-G123KE / CU-G123KE
9C
3C
5C
5C
5C
4C
3C
POWER MONITOR
& INDICATOR
RECEIVER
ASM
UP/DOWN
ASM
RIGHT
ASM
LEFT
SENSOR
FAN
MOTOR
2
3
WIRELESS
REMOTE CONTROL
TRANSMITTER
1
FUSE
(20A)
FUSE
3.15A
4-WAY
VALVE
CT
SSR
C-FM
FAN
MOTOR
FM
CR1
CR2
RY-FM
RY-PWR
OUTDOOR UNIT
DIODE
ELECTRIC
RESISTOR
CU-G123K
ONLY
ELECTRONIC
CONTROLLER
POWER
SWITCHING
SOURCE
FUSE
3.15A
IPM
COMPRESSOR
CS-G93KE
Block Diagram
14
MAC9509078C2
NOISE FILLTER
CS-G93KE
Wiring Diagram
CS-G93KE / CU-G93KE
POWER SUPPLY CORD
AUTO SW.
1 35
MOTOR
WIRELESS
REMOTE
CONTROL
ZNR
ELECTRONIC
CONTROLLER
(RECEIVER)
CN-RCV (W)
RY-PWR
SENSOR
SENSOR
(AIR TEMP.) (PIPE TEMP.)
MOTOR
(LEFT)
MOTOR
(RIGHT)
CN-DISP2 (W)
TERMINAL
COMPLETE
123456789
P Y O R BR
Y/G
MOTOR
(FLAP)
P Y O R BR
W
W
W
P Y O R BR
CN-RCV2 (W)
54321
1234
CN-STM1 (B)
54321
CN-TH1 (W)
CN-STM2 (Y)
54321
CN-PWR1 (B)
16
16
123
3
2
1
CN-STM3 (W)
MAIN SW.
ELECTRONIC CONTROLLER
FUSE
T 3.15A L 250V
3 21
R B Y
CN-MTR1 (G)
BR
W W W W W WW WW
987654321
TERMINAL
CN-DISP1 (W)
Y/G
DISPLAY, SELF-DIAGNOSIS
POWER MONITOR DISPLAY
1 2 3
THERMAL FUSE
102C (3A)
REMARKS
B: BLUE BR: BROWN W: WHITE G: GREEN
P: PINK Y: YELLOW O: ORANGE
BL: BLACK R: RED Y/G: YELLOW/GREEN
TO OUTDOOR UNIT
CWA95384 ()
BLUE - YELLOW
264.1
YELLOW - RED
304.8
2RD132X5BB03()
U-V
0.8
U-W
0.8
V-W
0.8
15
Untitled-2
15
6/20/00, 4:33 PM
CS-G93KE
Wiring Diagram
CS-G123KE / CU-G123KE
POWER SUPPLY CORD
AUTO SW.
1 35
MOTOR
WIRELESS
REMOTE
CONTROL
ZNR
ELECTRONIC
CONTROLLER
(RECEIVER)
CN-RCV (W)
RY-PWR
SENSOR
SENSOR
(AIR TEMP.) (PIPE TEMP.)
MOTOR
(LEFT)
MOTOR
(RIGHT)
CN-DISP2 (W)
TERMINAL
COMPLETE
123456789
P Y O R BR
Y/G
MOTOR
(FLAP)
P Y O R BR
W
W
W
P Y O R BR
CN-RCV2 (W)
54321
1234
CN-STM1 (B)
54321
CN-TH1 (W)
CN-STM2 (Y)
54321
CN-PWR1 (B)
16
16
123
3
2
1
CN-STM3 (W)
MAIN SW.
ELECTRONIC CONTROLLER
FUSE
T 3.15A L 250V
3 21
R B Y
CN-MTR1 (G)
BR
W W W W W WW WW
987654321
TERMINAL
CN-DISP1 (W)
Y/G
DISPLAY, SELF-DIAGNOSIS
POWER MONITOR DISPLAY
1 2 3
THERMAL FUSE
102C (3A)
REMARKS
B: BLUE BR: BROWN W: WHITE G: GREEN
P: PINK Y: YELLOW O: ORANGE
BL: BLACK R: RED Y/G: YELLOW/GREEN
TO OUTDOOR UNIT
CWA95380 ()
BLUE - YELLOW
234.1
YELLOW - RED
263.5
2RD132X5BA03 ()
U-V
0.8
U-W
0.8
V-W
0.8
16
Untitled-2
16
6/20/00, 4:33 PM
MAC9509078C2
CS-G93KE
Operation Details
A. FUNCTIONS
1. TEMPERATURE SHIFT
Once the operation starts, the remote control setting temperature will be shifted internally based on the setting fan
speed and outdoor air temperature. In addition, if Sleep Mode or Powerful Mode are set, the temperature shift will
be carried out.
Setting of Internal Setting Temperature
The internal setting temperature can be decided as follows:
Remote control setting temperature
+
Outdoor temperature shift (refer Table a)
+
Fan speed shift (+ 1.0 C)
+
Any Sleep Mode shift operation?
+
Any Powerful Operation shift? (refer Table b)
+
[Check upper/lower (33C/16C) limit for setting temperature]
Shift amount
CSG93KE
1.0C
CSG123KE
1.0C
0.5C
1.5C
1.0C
1.0C
1.0C
0.0C
0.0C
0.0C
+1.0C
+1.0C
+0.5C
+1.0C
+1.0C
+1.5C
Table b
Powerful Mode Shift.
Powerful
Cooling
Dry
Heating
4.0C
3.0C
+6.0C
17
Untitled-3
17
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
2. COOLING OPERATION
A. Room Temperature Control
(i) When the remote control setting temperature is less than 24C.
Cooling
+1.5
+1.0
+0.5
0
0.5
64 (Fc max) or 50
64 (Fc max) or 50
92 (Fc max) or 70
92 (Fc max) or 70
36
40
44
49
31
31
31
31
15
22
16
22
15
15
15
16
15
15
15
15
Comp OFF
Comp OFF
Comp OFF
Comp OFF
Model No.
CS-G93KE
CS-G123KE
(ii) When the remote control setting temperature is 24C and above.
Cooling
+1.5
+1.0
+0.5
0
0.5
64 (Fc max) or 50
64 (Fc max) or 50
92 (Fc max) or 70
92 (Fc max) or 70
36
36
44
44
31
31
31
31
15
15
16
16
15
15
15
15
15
15
15
15
Comp OFF
Comp OFF
Comp OFF
Comp OFF
CS-G93KE
CS-G123KE
30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
The compressor stops when the intake air temperature reaches 1C below internal setting temperature and
continues for 3 minutes.
When the compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation.
When the compressor stops, the outdoor fan motor stops 30 seconds later.
18
Untitled-3
18
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
B. Deodorizing Control
This control is available during automatic fan speed for Cooling and Soft Dry Operation. It is not available
during anti-freezing control.
Deodorizing Status
Compressor
ON
Time (second)
Indoor Fan Speed
40
50
OFF
SLo
6, 7, 6, 7,
OFF
Auto
1
ON
30
60
30
60
40
SLo
OFF
SLo
OFF
OFF
ON
ON
OFF
Compressor
OFF
Indoor
Fan Speed
When the compressor stops operation, the deodorizing status starts from 4 5 6 7.
If the compressor still stops operation after 3 minutes, the deodorizing status will start from 6.
19
Untitled-3
19
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
3. SOFT DRY OPERATION
A. Room Temperature Control
At the start of operation, cooling operation is running until the intake air temperature is 0.5C higher than internal
setting temperature, then the operation will shift to Soft Dry with indoor fan speed SLo.
Soft Dry
Cooling Operation
+1.0
+0.5
Cooling Operation
+1.5
22
22
22
22
15
15
16
16
15
15
15
15
15
15
15
15
Comp OFF
Comp OFF
Comp OFF
Comp OFF
0.5
When the
temperature falls
Condition
Model No.
When the
temperature rises
When the
temperature falls
CS-G93KE
When the
temperature rises
CS-G123KE
30 minutes from the start of the operation, the compressor is operating at Fc max Hz.
The Compressor stops when the intake air temperature reaches 3.5C below internal setting temperature and continues
for 3 minutes.
When the compressor stops operation, indoor fan stops for 330 seconds.
When the Compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control)
When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation
immediately.
When the Compressor stops, the outdoor fan motor stops 30 seconds later.
20
Untitled-3
20
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
B. Deodorizing Control
This control is available during automatic fan speed for Cooling and Soft Dry Operation. It is not available
during anti-freezing control.
Deodorizing Status
Compressor
ON
Time (second)
Fan Speed
4, 5, 4, 5,
OFF
40
OFF
SLo
1
ON
330
30
60
40
OFF
SLo
OFF
OFF
ON
ON
OFF
Compressor
ON
ON
OFF
OFF
Fan Speed
When the compressor stops operation, the deodorizing status starts from 3 4 5.
When the compressor stops operation, indoor fan stops for 330 seconds.
This control is to improve the feeling in high fan speed and low operation frequency. When the operation
frequency is less than 33Hz (CU-G93KE) or 36Hz (CU-G123KE), the fan speed will reduce. When the
operation frequency is increased to 40Hz (CU-G93KE) or 49Hz (CU-G123KE) continuously for 5 minutes,
the fan speed will resume to normal condition. (During Cooling operation).
21
Untitled-3
21
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
4. HEATING OPERATION
A. Room Temperature Control
During heating operation, the room temperature control depends on intake air temperature and internal
setting temperature. Basically it can be divided into 2 periods as shown below:
0C
Stabilized
period
Transition
period
1.5C
CS-G93KE
Heating Operation
16C ~ 30C
Stabilized Period
16C ~ 20C
21C ~ 30C
Comp Off
Comp Off
Comp Off
Comp Off
Comp Off
15
15
15
15
15
15
15
15
26
15
22
22
22
33
22
46
26
26
36
26
53
33
33
46
33
64
36
36
53
36
+1.5
+1.0
+0.5
0
0.5
1.0
1.5
71 (Fh) or
99 (Fhmax)
71 (Fh) or
99 (Fhmax)
71 (Fh) or
99 (Fhmax)
71 (Fh) or
99 (Fhmax)
71 (Fh) or
99 (Fhmax)
Less than
1C
1C and
above
Less than
1C
1C and
above
22
Untitled-3
22
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
CS-G123KE
Heating Operation
Transition Period
Remote Control Setting Temp.
16C ~ 30C
21C ~ 30C
16C ~ 20C
Comp Off
Comp Off
Comp Off
Comp Off
Comp Off
16
16
16
16
16
16
16
16
27
16
22
22
22
36
22
64
27
27
44
27
74
36
36
64
36
86
44
44
74
44
+1.5
+1.0
+0.5
0
0.5
1.0
1.5
90 (Fh) or
115 (Fhmax)
90 (Fh) or
90 (Fh) or
90 (Fh) or
90 (Fh) or
115 (Fhmax) 115 (Fhmax) 115 (Fhmax) 115 (Fhmax)
Less than
1C
1C and
above
Less than
1C
1C and
above
CS-G93KE
Heating Operation
16C ~ 30C
21C ~ 30C
16C ~ 20C
Comp Off
Comp Off
Comp Off
Comp Off
Comp Off
15
15
15
15
15
15
22
22
26
22
22
26
26
33
26
46
33
33
36
33
53
36
36
46
36
64
46
46
53
46
+1.5
+1.0
+0.5
Stabilized Period
0
0.5
1.0
1.5
71 (Fh) or
99 (Fhmax)
71 (Fh) or
99 (Fhmax)
71 (Fh) or
99 (Fhmax)
71 (Fh) or
99 (Fhmax)
71 (Fh) or
99 (Fhmax)
Less than
1C
1C and
above
Less than
1C
1C and
above
23
Untitled-3
23
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
CS-G123KE
Heating Operation
16C ~ 30C
Stabilized Period
21C ~ 30C
16C ~ 20C
Comp Off
Comp Off
Comp Off
Comp Off
Comp Off
16
16
16
16
16
16
22
22
27
22
22
27
27
36
27
64
36
36
44
36
74
44
44
64
44
86
64
64
74
64
+1.5
+1.0
+0.5
0
0.5
1.0
1.5
90 (Fh) or
115 (Fhmax)
90 (Fh) or
90 (Fh) or
90 (Fh) or
90 (Fh) or
115 (Fhmax) 115 (Fhmax) 115 (Fhmax) 115 (Fhmax)
Less than
1C
1C and
above
Less than
1C
1C and
above
When the difference of the intake air temperature and Internal setting temperature is 1.5C or more, compressor will operate at Fh
continuously for 3 minutes and then change over to Fhmax.
The compressor stops when the intake air temperature reaches 1.5C above internal setting temperature and continues for 3 minutes.
When the compressor stops, it will not start operation for 3 minutes. (Time Delay Safety Control)
When the intake air temperature decreases to the compressor ON temperature, the compressor starts immediately.
When the compressor stops, the outdoor fan motor stops 30 seconds later.
24
Untitled-3
24
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
B. Anti Cold Draft Control
(i) Indoor Fan Control
Indoor fan speed and airflow direction varies in accordance to the indoor heat exchanger temperature as
shown below:
a. Manual Fan speed control
(Manual Airflow Direction Control)
Min Me
58C
(58C)
Remote Control
Setting Fan Speed
25C
(30C)
18C
(28C)
13C
(13C)
55C
(55C)
Remote Control
Setting Fan Speed
37C
(37C)
Lo-
24C
(29C)
SLo
15C
(21C)
9C
(9C)
Stop
Min Me
58C
(58C)
Indoor heat
exchanger temp.
28C
(28C)
13C
(13C)
55C
(55C)
Lo-
29C
(29C)
SLo
21C
(21C)
9C
(9C)
Stop
Indoor heat
exchanger temp.
52C
(52C)
37C
(37C)
Max
UP
Max or
Up
DOWN
32C
(32C)
Me
25C
(30C)
32C
(32C)
DOWN
18C
(28C)
13C
(13C)
DOWN
Lo-
24C
(29C)
SLo
15C
(21C)
Stop
9C
(9C)
Indoor heat
exchanger temp.
Note:
37C
(37C)
28C
(28C)
13C
(13C)
Lo-
29C
(29C)
SLo
21C
(21C)
Stop
9C
(9C)
Indoor heat
exchanger temp.
Untitled-3
25
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
(ii) Hot Start
At the start of heating operation, the indoor fan stops and compressor operates at Fhmax frequency 99Hz
(CS-G93KE) or 115 Hz (CS-G123KE). This is to heat up the indoor heat exchanger in order to avoid cold
air discharged.
After Hot Start operation, compressor operates at Fhmax 99Hz(CS-G93KE) or 115Hz (CS-G123KE) for
2 minutes.
Vertical and horizontal airflow direction control is in accordance to indoor heat exchanger temperature.
This control is valid for automatic airflow direction only.
C. Deice Operation
Deice operation occurs when the deice operation starting signal is generated. This happens when one of the
following conditions occurs. However, the first deice operation will begin 1 hour after start of heating operation.
Outdoor Heat Exchanger
Temp. Th < 3C
Case 1
120 minutes
continuously
To > 1C
Case 2
80 minutes
continuously
To > 1C
Case 3
40 minutes
continuously
To 3C
Case 4
40 minutes
continuously
To < 3C
26
Untitled-3
26
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
Deice Operation Time Chart
Outdoor Heat
Exchanger
Temperature (C)
Deice Operation
Ending
Signal
16
30 sec
30
sec
Heating
Operation
30 sec
Heating
Operation
Deice
Operation
Starting
Signal
7
9
11
40Hz (CU-G93KE)
49Hz (CU-G123KE)
58Hz (CU-G93KE)
83Hz (CU-G123KE)
99Hz
(CU-G93KE)
Compressor operating
frequency
Free
Indoor Fan
ON
ON
OFF
OFF
OFF
Hot Start
Outdoor Fan
ON
ON
OFF
OFF
OFF
ON
4-way valve
ON
ON
OFF
OFF
OFF
ON
OFF
115Hz
(CU-G123KE)
Compressor frequency is set at 40Hz (CU-G93KE) or 49Hz (CU-G123KE) when the deice operation starting signal is
generated.
30 seconds later deice operation starting signal is generated, indoor fan, outdoor fan, 4-way valve are turned off and
compressor operates at 40Hz (CU-G93KE) or 49Hz (CU-G123KE) for 30 seconds. (Deice operation starts)
During deice operation, the compressor operating frequency is set at 58Hz (CU-G93KE) or 83Hz (CU-G123KE).
Deice will end when the outdoor heat exchanger temperature rises to 16C or after 11 minutes.
27
Untitled-3
27
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
D. Standby Control
(a) The purpose of Standby Control is to warm up the compressor when outdoor temperature is low.
The standby control will be activated when all of the followings occur.
(i) Main power switch is ON.
(ii) Unit is not operating.
(iii)Outdoor ambient temperature is below 3C.
(iv)Compressor stops more than 3 hours.
(v) Standby switch at indoor electronic controller is ON.
(The standby switch is at ON position during product delivery from factory).
(b) When the standby control is activated, low electricity will be supplied to compressor for 1 minute and stops
for 4 minutes. This condition is repeated until standby control is cancelled. It will consume about 35 W of
electric power.
Electricity supplied
to compressor
Time
ON
OFF
ON
OFF
1 min
4 min
1 min
4 min
(c) Standby control will be cancelled when one of the following conditions occurs.
(i) Unit starts operation.
(ii) Outdoor ambient temperature 5C.
(iii)Compressor starts operation.
(iv)Standby switch at indoor electronic controller is switched to OFF.
(v) Protection control is activated.
(d) When the unit is switched on by the remote control, the compressor operates at frequency as shown in
below:Frequency
CS-G93KE
Max. 36Hz
Min. 33Hz
Max. 36Hz
Max. 71Hz
Free
CS-G123KE
Max. 44Hz
Min. 36Hz
Max. 44Hz
Max. 90Hz
Free
Time (sec)
60
120
180
(e) The standby control can be cancelled by switching off the standby switch (SW2) at indoor electronic
controller.
28
Untitled-3
28
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
5. FAN OPERATION
This operation is to enable the fan operation without compressor running. Timer operation is valid for fan operation.
6. AUTOMATIC OPERATION
When the Automatic mode is selected, the operation mode is decided in accordance to remote control setting
temperature, intake air temperature and outdoor air temperature.
During judging the operation mode, indoor fan is running at Lo speed and outdoor fan at ON in order to sense
the indoor intake air temperature and outdoor air temperature for 20 seconds. At this time, Power LED is blinking.
After the operation mode is selected, Power LED lights up.
Refer to the examples below, there are 4 determination charts when automatic mode is selected.
(a) When setting temperature of remote control is 18C and below.
29
Untitled-3
29
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
(c) When setting temperature of remote control is 23C ~ 26C.
30
Untitled-3
30
6/20/00, 5:03 PM
MAC9509078C2
CS-G93KE
Operation Details
When the operation mode is changed over, the value for t1, t2 and t3 are shifted as follows:
Cooling/Soft dry Heating:
2C
Heating Cooling/Soft dry:
+2C
When the indoor intake air temperature is lower than 16C, heating operation is immediately started.
When the outdoor air temperature is more than 25C, and the intake air temperature is over 16C, cooling
operation is immediately started.
When the operation mode (Heating, Cooling or Soft Dry) is decided, the internal setting temperature will shift
as shown below:
+0.75C
Soft Dry
0C
Heating
0.75C
31
Untitled-3
31
6/20/00, 5:03 PM
MAC9509078C2
Untitled-4
32
24.0
24.4
27.1
27.8
30.7
30.8
33.0
33.4
18.4
18.7
19.3
20.1
21.4
22.0
22.7
23.0
23.1
23.5
24.3
25.0
25.3
26.0
26.4
26.4
26.5
27.3
27.6
28.0
28.3
29.0
29.3
29.8
29.8
32.7
8
9
10
11
12
13
14
15
16
32
6/20/00, 5:08 PM
17
18
19
20
21
22
23
24
25
26
27
28
33
29
30
31
36.9
32.6
32.6
32.3
31.9
31.5
31.1
30.5
30.1
29.8
29.8
29.1
28.8
28.4
28.3
28.3
26.4
23.4
21.7
17.9
20.3
17.6
17.6
16.3
16.3
15.6
Hi
Me
Me
Me
Lo
OFF
Auto
Fan
Auto
Fan
Auto
Fan
Lo
OFF
Cooling
Voltage
Voltage
Fan
Supply to
Speed Supply to
Fan Motor Fan Motor
No.
Manual Auto
DC (V)
DC (V)
CS-G93KE CS-G123KE
Operation Details
SLo
OFF
Soft
Dry
Test Run
Temporary Operation
Auto
Fan
(Max.)
SHi
Me+
Me
Temporary operation
Remarks
Me
Lo
OFF
OFF
Auto
Fan
(Min.)
Auto
Manual
Heating
Deodorizing control
Sleep Mode(Soft Dry)
Remarks
CS-G93KE
CS-G93KE
CS-G93KE
Operation Details
CS-G93KE
Operation Details
During Cooling operation, Indoor Fan speed is set at SHi when the following conditions occur:
Fan No. 15
Fan No. 13
Fan No. 11
a
10
sec.
80 sec.
(ii) When Automatic Fan Speed and Powerful Mode are selected
Fan No. 17
Indoor intake air temperature is 17C or above and less than 23C
Fan No. 15
Fan No. 13
a
10
sec.
80 sec.
Note: The Fan Speed will change every 10 seconds and it will be repeated from a to h every 80
seconds.
Outdoor fan motor is controlled with 1 speed only. Fan is in operation when the compressor starts operation
and stops 30 seconds after compressor stops operation.
When Automatic Fan Speed is selected, the Fan Speed will change every 10 seconds from Fan
Speed No. 7 to No. 15 depending on indoor heat exchanger temperature. Each time the Fan Speed
will move 1 rank up or down.
When Automatic Fan Speed and Powerful Mode are selected, the Fan Speed will change for every
10 seconds from Fan Speed No. 11 to No. 27 depend on heat exchanger temperature. Each time
the Fan Speed will move 1 rank up or down.
ON
Compressor
33
OFF
ON
Outdoor Fan
ON
OFF
30
sec
35
34
Untitled-4
ON
6/20/00, 5:08 PM
CS-G93KE
Operation Details
9. AIRFLOW DIRECTION
A. Vertical Airflow Direction
Operation
1
Heating
Cooling
33
70
15
13
46
33
15
25
33
41
11
15
18
22
25
3 ~ 33
11 ~ 25
18
25
33
11
15
18
22
25
33
41
Fan
7 ~ 36
15
25
143
Stop
70
57
11 ~ 25
7 ~ 36
Setting angle
Cooling, Soft Dry & Fan Auto Airflow Direction
Horizontal
Horizontal
3
36
15
33
70
143
143
Heating
Cooling
Fan
Soft Dry
Close
positon
Close
positon
Horizontal
Horizontal
3
41
13
Heating
Cooling
Fan
Soft Dry
33
143
70
143
Close
positon
Close
positon
36
Untitled-5
36
6/20/00, 5:11 PM
MAC9509078C2
CS-G93KE
Operation Details
(a) Vertical Airflow Direction Manual
By pressing the remote control vertical airflow direction setting switch, the vane will move to the indicated
angle (1, 2, 3, 4, 5) as shown in the table. When the remote control OFF/ON switch is pressed to stop the
unit, the vane will move to the Close position.
(b) Vertical Airflow Direction Auto
By setting the vertical airflow direction to AUTO, the vane swings up and down from 7 ~ 36 (during Cooling
and Fan) and 3 ~ 33 (during Soft Dry). During Heating operation, the vane angle will shift according to the
indoor heat exchanger temperature as shown below.
Zone C
(33)
58C
55C
Zone B
(70)
33C
Zone A
(15)
30C
125
125
90
90
55
55
55 ~ 125
55 ~ 125
64 ~ 110
64 ~ 110
55 ~ 125
55 ~ 125
64 ~ 110
64 ~ 110
55 ~ 125
55 ~ 125
Operation
Indoor heat exchanger
temperature
Heating
Cooling
Anti-dew formation control
Soft Dry
Anti-dew formation control
Fan
Heating
Zone C
(125)
Left Vane
Right Vane
40C
Zone B
(90)
50
55
125 55 50
90
33C
30C
Zone A
(55)
Stopper position
90
125
Stopper position
Indoor heat
exchanger temperature
37
Untitled-5
37
6/20/00, 5:11 PM
MAC9509078C2
CS-G93KE
Operation Details
(b) Manual Horizontal vane angle setting
By pressing the remote control horizontal airflow direction setting switch, the vane will move to the indicated
position (1, 2, 3, 4, 5, 6, 7) as shown in the table.
Operation
Heating
Cooling Anti-dew Formation Control
Soft
Dry
90
125
55
55
55
90
125
90
125
55
125
90
55
55
90
125
55
55
55
90
125
90
125
55
125
90
55
55
90
110
64
64
64
90
110
90
110
64
110
90
64
64
90
125
55
55
55
90
125
90
125
55
125
90
55
55
90
110
64
64
64
90
110
90
110
64
110
90
64
64
90
125
55
55
55
90
125
90
125
55
125
90
55
55
For All
Operations
WIDE
SPOT
17C
Lo-
Lo
13C
Indoor Heat
Exchanger Temperature
Untitled-5
38
6/20/00, 5:11 PM
MAC9509078C2
CS-G93KE
Operation Details
11. POWERFUL MODE OPERATION
When the powerful mode is selected, the internal setting temperature will shift to achieve the setting temperature
quickly.
(a) Cooling Operation
Internal setting
temperature
4C
When powerful
button is pressed
When powerful
button is pressed
When powerful
button is pressed
When the sleep button is pressed, the remote control setting temperature will increase 0.5C after 1 hour
or when the remote control setting temperature is reached. After another hour, 0.5C will be increased again.
+0.5C
Remote control
setting
temperature
+0.5C
1 hour
When Sleep
button is pressed
max 1 hour
8 hours
All stop
Sleep mode
shift operation
starts
During sleep shift operation, indoor fan speed operates at Lo (for Cooling operation) or SLo (for Soft Dry operation).
39
Untitled-5
39
6/20/00, 5:11 PM
MAC9509078C2
CS-G93KE
Operation Details
(b) Heating Operation
When the sleep button is pressed, the remote control setting temperature will decrease 2C after 1 hour or
when the remote control setting temperature is reached. After another hour, 3C will be decreased again.
Remote control
setting temperature
2C
When Sleep
button is pressed
3C
1 hour
8 hours
max 1 hour
All stop
When the Delay On Timer is set by using remote control, the unit will start to operate slightly earlier before the
set time, so that the room will nearly reach the set temperature by the On Timer set time.
60 minutes before the set time, the indoor fan operates at Lo and outdoor fan operates for 20 seconds to sense
the indoor intake air temperature and outdoor air temperature in order to determine the starting time for
preparatory operation. (The Power LED blinks during sampling.)
The time of the preparatory operation will start before the On Timer set time.
a. Cooling/Soft Dry
Indoor
intake
air temp
(C)
30
b. Heating
15 min
Indoor
intake
air temp
(C)
15
10 min
25 min
35 min
25
5
5 min
45 min
30
35 (C)
(C)
If there is a power failure, operation will automatically be restarted when the power is resumed from 2 minutes
58 seconds to 3 minutes 52 seconds randomly. It will start with the previous operation mode and airflow direction.
Auto Restart Control is not available when Timer or Sleep Mode is set.
J1 at indoor electronic controller should be open circuit when cancellation of Auto Restart Control.
40
Untitled-5
40
6/20/00, 5:11 PM
MAC9509078C2
CS-G93KE
Operation Details
15. POWER MONITOR DISPLAY
POWERFUL
POWER SLEEP TIMER
HIGH
POWER
MONITOR
LOW
Power Monitor LED lights on when the compressor is in operation. The number of the LED lights on is in accordance
to the compressor operating frequency.
Model
CS-G93KE
Display
A, B
A, B, C
A, B, C, D
A, B, C, D, E
15 ~ 26
31 ~ 33
36 ~ 40
43 ~ 46
51 ~ 64
Heating Indication
Frequency (Hz)
15 ~ 26
31 ~ 40
43 ~ 58
63 ~ 64
71 ~ 99
15 ~ 27
31 ~ 36
44 ~ 49
58 ~ 64
71 ~ 92
15 ~ 27
31 ~ 44
58 ~ 79
83 ~ 86
91 ~ 115
Press the AUTO button for 10 seconds or longer to switch off the signal receiving sound.
Press the AUTO button for 10 seconds or longer again to switch on the signal receiving sound.
The power relay turns on when one of the indoor LED lights on.
The power relay turns off when all of the indoor LEDs lights off.
When the air conditioner is stopped during operation, the power relay stays ON for 3 minutes.
The power relay will turn off if a sudden power failure occurs > 0.05 second. The power relay will turn on again
after 3 - 4 minutes (Refer AUTO RESTART CONTROL). It will start with the previous operation condition before
the power failure.
41
Untitled-5
41
6/20/00, 5:11 PM
MAC9509078C2
CS-G93KE
Operation Details
B. PROTECTION
1. PROTECTION CONTROL FOR ALL OPERATIONS
a.
b.
c.
Once the compressor is ON, it will not turn OFF for 30 seconds. However, it is turned off by remote control
or Automatic switch.
When the outdoor unit total running current (AC) exceeds I1, the frequency is lowered by 1 rank. If I1 is not
exceeded for 30 seconds, the frequency is highered by 1 rank at one time. If the outdoor unit total running
current exceeds I2, the compressor is immediately stopped for 3 minutes.
Zone B
Model No.
CU-G93KE
I1(A)
5.3
6.7
4.3
5.2
I2(A)
7.3
10.8
7.3
10.8
CU-G123KE CU-G93KE
38.5C
CU-G123KE
Zone B
Outdoor air
temperature
37.5C
Zone A
CU-G93KE
CU-G123KE
I1(A)
6.1
9.2
I2(A)
7.3
10.8
If the outdoor unit total running current exceeds I2 3 times within 30 minutes, all indoor and outdoor relays will
be turned off ; TIMER LED will blink and F98 is displayed.
d.
When the IPM (power transistor) temperature rises to 100 10C, the compressor stops immediately. The
compressor is restarted when the IPM (power transistor) temperature decreases to 90 10C after 3 minutes
(Time Delay Safety Control). If this condition occurs 4 times within 40 minutes, all indoor and outdoor relays
will be turned off; TIMER LED will blink and F96 is displayed
42
Untitled-6
42
6/20/00, 5:13 PM
MAC9509078C2
CS-G93KE
Operation Details
2. DC Peak Current Control
When the electric current to the IPM (power transistor) exceeds the set value, DC 27 4A, the compressor
stops. The compressor restarts after 3 minutes.
If within 30 seconds the set value is exceeded again, the compressor will stop for 1 minute. If this condition
repeats for 7 times, all indoor and outdoor relays will be turned off; TIMER LED will blink and F99 is displayed.
DC electric current
(A)
274
Comp.
Off
Comp. Off
min
33 min
Comp.
Off
<30
30sec
sec 11 min
min <3030
sec
sec
<30
30sec
sec 1 min
min <3030sec
sec
7 times
e.
When the temperature of compressor rises to 105C, the frequency is reduced as shown in diagram below.
When the temperature rises to 115C or above, the compressor stops. The compressor will start operating
at low frequency when the temperature falls to 115C and resume to normal condition when the temperature
falls to 94C.
Compressor
temp. (C)
Comp OFF
Comp OFF
115
max 33 Hz (CU-G93KE)
max 36 Hz (CU-G123KE)
110
106
105
94
Condition
f.
Free
Free
max 33 Hz (CU-G93KE)
max 36 Hz (CU-G123KE)
The compressor stops when the temperature rises to 115C. If this condition occurs 4 times within 20
minutes, all indoor and outdoors relays will be turned off; TIMER LED will blink and F97 is displayed.
When the following conditions as shown in the below table occur, the compressor stops and restarts after
3 minutes. If this phenomenon is continuously occuring twice within 30 minutes, all indoor and outdoor relays
will be turned off; TIMER LED will blink and F91 is displayed.
Comp. Frequency *
51 Hz and above
71 Hz and above
70 Hz and above
90 Hz and above
Total Running
Current
1.88 A and
< 1.9 A
1.88 A and
< 2.1 A
1.88 A and
< 2.4 A
1.88 A and
< 2.7 A
Indoor Heat
Exchanger Temp.
Operation
Model No.
15C
or above
30C
or below
15C
or above
30C
or below
Cooling/Soft Dry
Heating
Cooling/Soft Dry
Heating
CU-G93KE
CU-G123KE
Note: The above conditions are not valid during Deice operation.
*
Untitled-6
43
6/20/00, 5:13 PM
MAC9509078C2
CS-G93KE
Operation Details
g.
When the compressor operates at less than 31 Hz for 40 minutes, the operating frequency will increase to
31 Hz for 2 minutes.
Comp. Operating
Frequency
31Hz
40 min
h.
i.
2 min
24C or < 4C
< 30C
> 0C
Operation
Cooling/Soft Dry
Heating
When the above conditions occur, the compressor will operate at minimum frequency as below:CU-G93KE
CU-G123KE
Min 31Hz
Min 31Hz
Heating
Min 33Hz
Min 36Hz
When the DC voltage supplied to IPM (Power transistor) is reduced to 169 5V (CS-G93KE) or 160 5V
(CS-G123KE) the compressor stops and restarts after 3 minutes.
If within 30 seconds after restarting of compressor, the DC voltage is reduced to 169 5V (CS-G93KE) or
160 5V (CS-G123KE) again, the compressor will stop for 1 minute.
If this condition repeats for 7 times, all indoor and outdoor relays will be turned off; TIMER LED will blink and
F99 is displayed.
DC Voltage
Supplied to IPM
(V)
169 or 160
Comp OFF
3 min
TIMER LED
Blinks
F99 is
displayed
Comp
OFF
< 30 sec
sec
11min
sec
min <3030sec
<30
30 sec
sec
7 times
j.
When the voltage supply (AC) exceeds 295 15 V (T0), the air conditioner stops and restarts automatically
when the voltage supply (AC) is below (T0 - 5)V. However, waiting for 3 minutes is necessary for re-operation.
44
Untitled-6
44
6/20/00, 5:13 PM
MAC9509078C2
CS-G93KE
Operation Details
2. PROTECTION CONTROL FOR COOLING & SOFT DRY
a.
Anti-Freezing Control
When the temperature of the indoor heat exchanger becomes low, the compressor operating frequency is
reduced and stopped when the temperature falls to lower than 2C continuously for 6 minutes. This is to
prevent freezing of indoor heat exchanger. When the temperature rises to 10C or above, the compressor
restarts with 3 minutes. The compressor operating frequency will resume to normal when the temperature
reaches 14C.
Indoor fan speed will increase when the temperature falls and it will resume to original speed when the
temperature increases to 14C for 5 minutes continuously.
Indoor Heat
Exchanger 14
Temp. (C) 12
Free
Free
Original
10
6
4
2
Original
Max 36 Hz (CS-G93KE)
Max 44 Hz (CS-G123KE)
Max 26 Hz (CS-G93KE)
Max 27 Hz (CS-G123KE)
Shift *
Shift *
OFF
OFF
Comp.
Indoor Fan
Comp.
Indoor Fan
Fan Speed
Shift *
Me+
2 rank up
Me
1 rank up
Me-
1 rank up
Lo
2 rank up
AUTO FAN
1 rank up
Note: The above phenomenon occurs when the fan is running at Me+ or below.
b.
When the following conditions occur for 20 minutes continuously, anti-dew formation is controlled:
1. Indoor intake air temperature is 24C or above.
2. Outdoor air temperature is less than 30C.
3. Remote control setting temperature is less than 25C.
Shift
Hi
2 rank down
Me+
3 rank up
Me
unchange
Me-
unchange
Lo
2 rank up
This control is cancelled immediately when either condition 13 as written above is changed, or remote
control setting temperature or fan speed is changed.
45
Untitled-6
45
6/20/00, 5:13 PM
MAC9509078C2
CS-G93KE
Operation Details
c.
The compressor operating frequency is regulated by operation time to prevent fog discharged from indoor
unit as shown in the table below.
Model No.
0 T < 30
50Hz
70Hz
30 T < 90
46Hz
64Hz
T 90
43Hz
58Hz
CU-G93KE
CU-G123KE
d.
When the outdoor air temperature increases to 38.6C, compressor operating frequency reduces to
minimum of 31 Hz. Compressor operating frequency will resume to normal when outdoor air temperature
decreases to 37.8C.
46
Untitled-6
46
6/20/00, 5:13 PM
MAC9509078C2
CS-G93KE
Operation Details
3. PROTECTION CONTROL FOR HEATING OPERATION
a.
b.
When the intake air temperature is 10C or above and remote control setting fan speed is less than Me-, the
compressor operates maximum at 71 Hz (CU-G93KE) or 90 Hz (CU-G123KE).
When the intake air temperature is 30C and above, the compressor operates maximum at 71 Hz (CUG93KE) or 90 Hz (CU-G123KE).
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown
in the diagram below. This control will begin 50 seconds after the compressor starts.
Outdoor air
Temperature (C)
43 Hz
43 Hz
21
19
64 Hz
64 Hz
Free
Model No.
c.
Free
When temp.
rises
Condition
58 Hz
86 Hz
12
10
58 Hz
When temp.
falls
86 Hz
Free
Free
When temp.
rises
CU-G93KE
When temp.
falls
CU-G123KE
The compressor operating frequency is regulated in accordance to the indoor heat exchanger temperature.
Indoor heat
exchanger temp. (C)
OFF
59
OFF
33 Hz
33 Hz
53
51
47
Min 33 Hz
43
Max 43 Hz
OFF
OFF
36 Hz
Min 36 Hz
36 Hz
Max 58 Hz
Max 53 Hz
Max 74 Hz
Min 33 Hz
Min 36 Hz
37
Condition
Model No.
Free
Free
Free
Free
When temp.
rises
When temp.
falls
When temp.
rises
When temp.
falls
CU-G93KE
CU-G123KE
47
Untitled-6
47
6/20/00, 5:13 PM
MAC9509078C2
CS-G93KE
Installation Information
Attached accessories
No.
Accessories part
Qty.
No.
1 6
Installation plate fixing screw
2
3
6
Remote control
1 8
Battery
1
Band
1
Vinyl tape
3
Vinyl tape
4
5
Qty.
Drain elbow
Installation plate
Accessories part
There should not be any heat source or steam near the unit.
There should not be any obstacles blocking the air circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
Indoor unit of this room air conditioner shall be installed on the wall in a height of at least 2.3 m.
OUTDOOR UNIT
There should not be any animal or plant which could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
Rated
Length
Max.
Elevation
(m)
Max.
Piping
Length
(m)
Piping size
MODEL
Gas
Liquid
G93KE
3/8"
1/4"
G123KE
1/2"
1/4"
48
Untitled-7
48
6/20/00, 5:15 PM
MAC9509078C2
CS-G93KE
Installation Information
Piping direction
about 1.8 m
<
Right
Right
rear
Left
Right bottom rear
<
Left
Left bottom
Installation plate 1
Sleeve (*)
Bushing-Sleeve (*)
SLEEP
POWER
TIMER
UL
POWERF
ECONOM
5 cm
or more
Vinyl tape
9
Vinyl tape 8
Saddle (*)
cm
10 ore
m
or
Connecting cable
(4-CORE WIRE/1.5 mm2)
Locally approved cable.
Additional drain hose (*)
10 cm
or mor
e
49
Untitled-7
49
6/20/00, 5:15 PM
CS-G93KE
Servicing Information
A.
TROUBLESHOOTING
POWER SWITCH
POWERFUL
POWER
MONITOR
LOW
(ii) Short the service terminal (CN-S) of the outdoor printed circuit board. The air conditioner starts operation
at Cooling rated frequency.
CN-S
(b) Heating
Keep pressing the Test Run button, switch off and on the Power Switch, then release the Test Run button. The
air conditioner starts operation at Heating rated frequency.
50
Untitled-8
50
6/20/00, 5:17 PM
MAC9509078C2
CS-G93KE
Servicing Information
2. TROUBLESHOOTING AIR CONDITIONER
Refrigeration cycle system
Normal Pressure and Outlet Air Temperature (Standard)
Gas pressure
MPa (kg/cm2G)
Outlet air
temperature (C)
Cooling mode
0.4 ~ 0.6 (4 ~ 6)
12 ~ 16
Heating Mode
36 ~ 45
Normal
Above 8C
(15 minutes after an
operation is started.)
at cooling mode
Above 14C
(15 minutes after an
operation is started.)
at heating mode
Value of electric
current during operation
Dusty condenser
preventing heat radiation
Excessive amount
of refrigerant
Cooling Mode
High
Gas side
pressure
Inefficient compressor
Low
Insufficient refrigerant
Low
Clogged strainer or
capillary tube
Low
Inefficient compressor
Heating Mode
Low
Insufficient refrigerant
Low
Clogged strainer or
capillary tube
51
Untitled-8
51
6/20/00, 5:17 PM
CS-G93KE
Servicing Information
1. Relationship between the condition of the air conditioner and pressure and
electric current
Cooling Mode
Heating Mode
Low Pressure
High Pressure
Electric
current during
operation
Low Pressure
High Pressure
Electric
current during
operation
Insufficient refrigerant
(gas leakage)
Inefficient
compression
Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is
started.
52
Untitled-8
52
6/20/00, 5:17 PM
MAC9509078C2
CS-G93KE
Servicing Information
B.
The diagnostic display can be seen on the receiver of the Front Grille.
When an abnormality occurs, the unit automatically stops, and the TIMER LED blinks to indicate a malfunction. At the
same time, the type of abnormality will be indicated on the receiver as shown in the diagram below. Providing this
information reduces the time spent in diagnosing procedures.
Display
(Red)
POWERFUL
P O W E R LOW
MONITOR
HIGH
TIMER
OPEN
By starting cooling operation using TEST RUN button and short the Diagnostic Terminals at the remote control, the
previous abnormalities are deleted.
Depending on the type of abnormality, you may be able to override the abnormality and use temporary operation (for
abnormalities indicated by t mark in the table).
Use the remote control to select cooling or heating operation mode and press OFF/ON button. At this moment, four short
beeps bip.bip.bip.bip will sound and TIMER LED will blink.
53
Untitled-8
53
6/20/00, 5:17 PM
CS-G93KE
Servicing Information
Diagnosis
display
Abnormality
Judgement
Temporary
operation
1 min after
starting operation
H11
H14
H15
H16
Outdoor PCB
IPM (Power transistor) module
H19
Indoor PCB
Fan motor
H23
H27
H28
H98
H99
Insufficient refrigerant
Air filter dirty
F11
4 times
occurance within
40 minutes
4-way valve
V-coil
F91
2 times
occurance within
30 minutes
No refrigerant
(3-way valve is closed)
F93
4 times
occurance within
30 minutes
Compressor
Outdoor PCB
F96
4 times
occurance within
40 minutes
Excess refrigerant
Improper heat radiation
IPM (Power transistor)
F97
4 times
occurance within
20 minutes
Insufficient refrigerant
Compressor
F98
3 times
occurance within
30 minutes
Excess refrigerant
Improper heat radiation
F99
7 times
occurance
continuously
Outdoor PCB
IPM (Power transistor)
Compressor
t
(Cooling only)
54
Untitled-8
54
6/20/00, 5:17 PM
MAC9509078C2
CS-G93KE
Servicing Information
(a) Current Transformer Defective
When the Current Transformer (CT) is an open circuit, total running current is less than 1.88 A and the indicated
frequency is 53 Hz (CU-G93KE) or 74 Hz (CU-G123KE) or above. If this condition continues for 20 seconds,
the abnormality signal is sent from outdoor to indoor after 3 minutes of operation and [H16] is displayed.
55
Untitled-8
55
6/20/00, 5:17 PM
CS-G93KE
Servicing Information
C.
Reset Button
REMOTE CONTROL
a.
b.
SW1
AB
Main electronic
controller
BA
By adding a jumper wire to the remote control side and shorting the J2 at the indoor printed circuit board,
it is possible to select 4 transmission codes including one at time of delivery condition (1).
Remote control
Note
Switch SW B A
JB
Switch SW1
J2
At product delivery
Jumper wire
Shorted
Jumper wire
Shorted
56
Untitled-8
56
6/20/00, 5:17 PM
MAC9509078C2
CS-G93KE
Servicing Information
D.
a.
DISASSEMBLY OF PARTS
Indoor Control Board Removal Procedure
1. Remove the Front Grille
Fig. 1
Fig. 2
3 Press the
2 tabs
2 Remove the
Front Grille
Fig. 3
Fig. 4
5 Remove the
whole control
board.
4 Remove
earth wire screw
4 Remove screws
57
Untitled-1
57
6/21/00, 9:24 AM
CS-G93KE
Servicing Information
b.
Fig. 5
1 Remove screw
2 Remove the
particular plate
Fig. 8
Fig. 7
3 Remove screw
Fig. 10
Fig. 9
5 Remove screw
58
Untitled-1
58
6/21/00, 9:24 AM
MAC9509078C2
CS-G93KE
Servicing Information
c.
Fig. 11
2 Press down
1 Remove screw
Tabs
1 Remove screw
2 Press up
Fig. 14
Fig. 13
3 Remove the
front cover
4 Remove the
side cover
Fig. 15
5 Remove the Cross Flow Fan Screw
6 Remove the
Indoor Fan
Motor
59
Untitled-1
59
6/21/00, 9:24 AM
CS-G93KE
Servicing Information
d.
Fig. 16
1.
Fig. 17
2 Remove
the screw
Fig. 19
3 Pull slightly
60
Untitled-1
60
6/21/00, 9:24 AM
MAC9509078C2
CS-G93KE
Servicing Information
c.
! WARNING
Be save to return the wiring to its original
position
There are many high voltage components within the heat sink cover so never
touch the interior during operation. Wait
at least two minutes after power has
been turned off.
Fig. 21
1 Remove screw
2 Remove 2 screws
5 Remove Front
Panel
4 Remove 2 screws
Fig. 23
6 Remove 5 screws
8 Remove the
electronic
controller
61
Untitled-1
61
6/21/00, 9:24 AM
CS-G93KE
Servicing Information
f.
Fig. 24
g.
Fig. 26
Fig. 28
62
Untitled-1
62
6/21/00, 9:24 AM
MAC9509078C2
CS-G93KE
Technical Data
L Operation characteristics
CS-G93KE / CU-G93KE
Cooling Characteristic
0.58
0.56
30
35
0.62
GP
0.61
0.60
0.59
0.58
4.5
4.0
3.5
3.0
40
Heating Characteristic
2.0
1.8
1.6
1.4
6.0
5.0
4.0
3.0
10
3.8
3.7
3.6
3.5
3.4
3.3
1.9
1.8
7
6
5
4
1.7
1.6
GP
I: Current (A)
I: Current (A)
GP
40
39
38
37
36
40
38
36
34
32
O: Outlet Air
Temperature (C)
230V
4.0
3.5
3.0
63
63
Untitled-2
6/21/00, 9:30 AM
O: Outlet Air
Temperature (C)
I: Current (A)
6
5
4
3
2.7
2.6
2.5
GP
0.62
0.60
2.8
2.7
2.6
2.5
2.4
2.3
17
16
15
14
13
12
I: Current (A)
O: Outlet Air
Temperature (C)
16
15
14
13
12
O: Outlet Air
Temperature (C)
230V
230V
CS-G93KE
Technical Data
L Operation characteristics
CS-G123KE / CU-G123KE
Cooling Characteristic
0.57
0.56
GP
I
30
35
0.55
0.54
0.53
7
6
5
4
40
0.57
0.56
GP
Heating Characteristic
2.0
1.8
1.6
1.4
I: Current (A)
GP
7
6
5
Q
GP: Gas Side
Piping Pressure (MPa)
6.0
5.0
4.0
3.0
4.9
4.8
4.7
4.6
4.5
4.4
8
7
6
5
2.0
1.9
1.8
1.7
10
44
43
42
41
40
39
GP
I: Current (A)
46
44
42
40
38
36
O: Outlet Air
Temperature (C)
230V
O: Outlet Air
Temperature (C)
I: Current (A)
7
6
5
4
0.58
I: Current (A)
0.55
0.54
3.6
3.5
3.4
3.3
3.2
3.1
3.7
3.6
3.5
3.4
3.3
3.2
15
14
13
12
11
O: Outlet Air
Temperature (C)
16
15
14
13
12
O: Outlet Air
Temperature (C)
230V
230V
64
Untitled-2
64
6/21/00, 9:30 AM
MAC9509078C2
CS-G93KE
Exploded View
CS-G93KE / CS-G123KE
1
#
4
<
6
&
"
2
#
\
[
!
5
*
}
@
^
>
+
|
,
$
%
:
:
.
6
)
9
!
7
(
&
;
2
8
!
9
4
)
(Note) : The above exploded view is for the purpose of parts
(
disassembly and replacement.
The non-numbered parts are not kept as standard
service parts.
65
Untitled-3
65
6/21/00, 9:35 AM
CS-G93KE
CS-G93KE
NO.
1
QTY
1
CS-G93KE
CWD50C338
CS-G123KE
@
REMARKS
O
CWF61696
CS-G123KE
@
INSTALLATION PLATE
CWH36157
54
FAN MOTOR
CWA98244
CWH02C060
55
CWH82C194
4
5
6
BEARING
EVAPORATOR
FLARE NUT (1/2) OR (3/8")
1
1
1
CWH64K007
CWB30C271
CWT25005 (3/8")
@
@
CWT25007 (1/2")
56
CWD00C111
7
8
1
1
CWH6002140
CWH54C031
@
@
9
10
11
1
1
1
CWH50211
CWD931039
CWA67C2310
@
@
@
12
13
TUBE ASSY
DISCHARGE GRILLE COMPLETE
1
1
CWT01C622
CWE20C629
CWT01C623
@
14
15
1
1
CWE24C113
CWE24C114
@
@
16
CWA98260
17
CWA67C1814
18
CWA98276
19
CWA67C2187
CWA98277
CWA67C2188
22
CAP COMPLETE
CWH52C003
23
VANE
CWE24462A
24
LEVER COMPLETE
CWH65C026
25
RETAINING RING
XUC3
26
PARTICULAR PIECE
CWD931019
27
ELECRTONIC CONTROLLER
CWA741406
CWA741405
28
CWA28C579
29
CWA20C763
CWA20C764
CWH13463
CWH13465
32
CWH13466
33
34
35
1
1
1
CWH13464
CWD931040
CWD931018
@
@
@
36
CWA74919
37
CWA67C2913
38
INDICATOR COMPLETE
CWE39C299
39
CWA67C2912
40
SENSOR COMPLETE
CWA50C613
41
HOLDER SENSOR
CWH32142
42
CWA75C711
43
CWE11C964
44
CWE22C333
45
DECORATION BASE
CWE35C024
46
TAB
CWD931020
47
CWE14C103
48
AIR FILTER
CWD00240
49
CWH52267
50
XTN4+16C
51
DRAIN HOSE
CWH5880580
52
OPERATING INSTRUCTIONS
CWF561630
CWD00220
58
CWH36161
All parts are supplied from MACC, Malaysia (Vendor Code: 086).
t marked parts are recommended to be kept in stock.
30
31
57
(Note)
21
20
O
O
O
67
66
Untitled-4
CS-G93KE
QTY
1
NO.
53
66
6/21/00, 9:40 AM
REMARKS
CS-G93KE
CS-G93KE
Exploded View
CU-G93KE / CU-G123KE
{
]
\
[
]
}
@
1
;
"
,
3
?
<
>
+
~
:
6
&
5
9
|
NO.
1
1
%
6
67
CU-G123KE
@
CWD54255
REMARKS
CWD54254
10
FAN MOTOR
CWA95384
CWA95380
CWH55406
COMPRESSOR
2RD132X5BB03
2RD132X5BA03
CWG30901
CWH50183
NUT
CWH56000
10
CONDENSER
CWB32C350
CWB32C349
11
WIRE NET
CWD04197A
CWD04198A
12
REACTOR (RIGHT)
CWA42134
13
REACTOR (LEFT)
CWA42135
14
HOLDER COUPLING
CWH35177
15
3 WAY VALVE
CWB01481
CWB01480
16
2 WAY VALVE
CWB02308
17
STRAINER
CWB11025
18
4 WAY VALVE
CWB00002
CWB00003
19
CWT01C668
CWT01C667
20
CWH15290
CWH15291
21
CWD31C035
22
PROPELLER FAN
CWH00K087
23
NUT
CWH56053
24
V COIL COMPLETE
CWA43C686
25
HOLDER SENSOR
CWH32074
26
HOLDER SENSOR
CWH32082
27
SENSOR COMPLETE
CWA50C614
28
TERMINAL COVER
CWH17006
29
NUT
CWH7080300
30
CONTROL BOARD
CWH10978
31
DIODE BRIDGE 1
A54S25VB60
32
DIODE BRIDGE 2
A54D15VBA80
A54D25VB80
33
CAPACITOR
1/2
CWA30201(1)
CWA30200 (2)
34
HOLDER CAPACITOR
CWH30183
CWH30184
35
SH CAPACITOR
CWA31137
36
CWA67C2209
CWA67C2146
37
38
39
40
CONTROL BOARD
NOISE FILTER
RESISTOR
ELECTRONIC CONTROLLER
1
1
1
1
CWH10979
CWA49C209
CWA47038
CWA73C312
@
@
@
CWA73C311
O
O
O
41
FUSE
XBACW12
42
CWH13C324
43
CWE04218A
44
CWE04217A
CWE04219A
45
HANDLE
CWE16037C
46
CWE06K103A
47
CWE03K036A
CWE03K037A
48
CWH13C325
49
DRAIN ELBOW
CWH5850080
All parts are supplied from MACC, Malaysia (Vendor Code: 086).
t marked parts are recommended to be kept in stock.
69
68
Untitled-4
CU-G93KE
CWD50K660A
(Note)
(Note) : The above exploded view is for the purpose of parts
disassembly and replacement.
The non-numbered parts are not kept as standard
service parts.
QTY
1
6/21/00, 9:40 AM
O
O
CS-G93KE
BZ1
PART NO.
BUZZER
A48040
DIODE
A541SS355T
D3, D6, D9
DIODE
A54D1F60
DIODE BRIDGE
A54D3SBA60F1
FUSE
XBA2C31TR0
IC1
INTERGRATED CIRCUIT
A5278366F100
IC2
INTERGRATED CIRCUIT
A52BR9020F
IC3
INTERGRATED CIRCUIT
A52MPC393G22
IC4
INTERGRATED CIRCUIT
A52PST600DR
DB1
FUSE
IC5, IC6
INTERGRATED CIRCUIT
A52A2003GR2
IC7, IC8
INTERGRATED CIRCUIT
A52C108
ICX
INTERGRATED CIRCUIT
A53715C (CWA741406)
A53714C (CWA741405)
PC1
PHOTO COUPLER
A52S2501L1KC
PC2
PHOTO COUPLER
A52TLP371LF
PC3
PHOTO COUPLER
A52LP521L1BL
TRANSISTOR
A55DA143XKTX
SW1, SW2
SWITCH
A04085
SW3, SW4
SWITCH
A01059
T1
TRANSFORMER
A40C295
X1
RESONATOR
A45CTS4MG02T
ZNR1
ZNR
ERZVEAV511
ZNR2
ZNR
ERZVA9V271
70
Untitled-6
70
6/21/00, 9:45 AM
MAC9509078C2
CS-G93KE
C-FM
PART NO.
CAPACITOR -FM
A31735
CURRENT TRANSFORMER
A40260
D1
DIODE
A54AU02ZV0
DIODE
A54RA15-06V3
D19
DIODE
A54RA15-10V3
DIODE
A54RA22-04V3
D6
DIODE
A541SS136T
D9 ~ D16
DIODE
A54MA165TA5
CT1
FUSE1, FUSE2
FUSE
XBA2C31TR0
IC1
INTERGRATED CIRCUIT
A5278214WP43
IC2
INTERGRATED CIRCUIT
A52MPA2003C
IC3
INTERGRATED CIRCUIT
A52C050
IC4
INTERGRATED CIRCUIT
A52M51951AST
IC5
INTERGRATED CIRCUIT
A52BX8454
IC6
INTERGRATED CIRCUIT
A52AN78L10TA
IC7
INTERGRATED CIRCUIT
A52AN79L10TA
IC8
INTERGRATED CIRCUIT
A52MPC339C
ICX
SERIAL PROM
A53716B (CWA741404)
A53717A (CWA741408)
LED
A54SLR342DB7
PHOTO COUPLER
A52S2501-1PC
PC2
PHOTO COUPLER
A52LP521-3GB
PC4
PHOTO COUPLER
A52PS2633E
LED1
PC5
PHOTO COUPLER
A52S2501-1LC
PC6 ~ PC11
PHOTO COUPLER
A52LP521-1GH
Q1
TRANSISTOR
A55C070
Q4, Q6, Q7
TRANSISTOR
A55DTA143XST
Q5
TRANSISTOR
A55C1740STPQ
Q8
TRANSISTOR
A5520CVL33A
RY-FM
RELAY
A00161
RY-PWR
RELAY
A00106
SSR1
T1
VR1
VR2
SSR
A56S26MD01M
TRANSFORMER
A40367
VARISTOR
A44EVMEASB22
VARISTOR
A44VMEASB13
X1
RESONATOR
A45ST12MTWOT
ZD1
ZENAR DIODE
A54D6.2EB1TB
ZNR
ERZVA9V271
ZNR1
71
Untitled-6
71
6/21/00, 9:45 AM
CS-G93K/G123K
CS-G93K/G123K
CS-G93K/G123K
CS-G93K/G123K
CS-G93KE
CS-G123KE
C6
0.01
C37
10
LC1
A49AF32102TL
R29
100k
5
R34
10k
R37
10k
R39
10k
R43
10k
RECEIVER
3 DL
(MX-3)
CN-RCV1
PH302C
1
2
3
VCC1 1
7 IN-
OUT 2
6 CO
VCC2 3
0.01
FO 4
R21
1k
3
2
1
+
C7
1.5 (T)
2 CS
R24
5.1k
C21
0.01
RESET SIGNAL
GENERATION
CLOCK PULSE
GENERATION
Q3
A55DC143XKTX
b
c
c
R62
5.1k
R66
330
RST 8
C18
0.022
R63
1k
CLOCK PULSE
GENERATION
10k
C23
100
6.3V
S0 6
6 D0
CS 3
S1 7
5 D1
BUSY 1
7
102C
THEROMAL
FUSE
R67
1k
CN-PWR
CN-PWR
PC2 TLP371
C17
0.1
R68
680
ICX
RECEPTION
4
3
1~3
CLOCK PULSE
1.1GENERATION
ZNR2
ERZVA9V271
R72
2.4k
D1
A541SS355T
R73
1k
R74
47k
2W
R79
47k
2W
R82
510k
R81
510k
C30
0.22
L6
A43101T
ZNR1
ERZVEAV511
D9
A54D1F60
LF1
A49217
T1
23
22
21
20
19
18
17
2.5
16
2.5
15
14
13
12
11
10
7
b
9
8
7
6
5
4
3
2
1
R110
R111
180 x 4
1
2
3
4
5
6
7
8
9
79
SPEED
CONTROL
78
28
77
29
76
31
12
C35
470
(FC)
C3
0.01
SEGMENT
DRIVE
5.1k
C25
0.01
Q10
A55DA143XKTX
Q8
A55DA143XKTX
Q7
A55DA143XKTX
SEGMENT DRIVE
SEGMENT DRIVE
SEGMENT DRIVE
e
10k
R71
5.1k
R77
5.1k
GND F
8
2 - 3.5
R23
10k
D5
STANDBY
4.7k
4.7k
10k
b
71
35
70
TIMER SHORTEN
38
R30
10k
40
R38
24k
R33
10k
R40
10k
2.5
AUTO
R3
1k
C36
390
(FA)
c
D
1 FAN SPEED CONTROL SIGNAL
R2
10k
R57
10k
4.7k
R1
1k
BZ1
10k
R48
(PH4)
CN-TH
1
2
3
4
(ZH5)
1
2
3
4
5
R73 +
10k
C26
33
25V
10
9
g
f
12
13
1
2
3
4
5
14
15
16
(MX-5)
CN-STM2
TEST RUN
CLOCK
PULSE INPUT
41
42
43
L3
44
45
46
FAN MOTOR
R4
10k
67
10
47
48
49
50
51
52
12
11
14
13
22
53
54
55
56
57
58
59
60
UP/DOWN
61
62
63
LOGIC
64
R55
10k
C13
0.01
5
L1
A438LM31A02T
LOGIC
(MX-5)
CN-STM3
9
e
13
14
1
2
3
4
5
15
16
RESISTANCE
AT 20C
( )
VOLTAGE
AC ( V )
1 & 2
6.1
21 ( 23 )
1 & 3
6.1
21 ( 23 )
2 & 3
6.1
21 ( 23 )
LOGIC
DRIVE
CIRCUIT
C24
1000P
C25
1000P
Fig.2
16
15
(XH3)
CN-MTR
RA
RA
RA
SENSOR
CIRCUIT
4
1
23
Fig. 1
3
2
1
Sensor (Thermistor)
Characteristics
17
R68
1M
70
DRIVE
CIRCUIT
IC5
A52A2003GR2
60
R59
5.49k
21
19
28
C12
1
50V
2
1
R28
10k
IC3
A52MPC393G22
6
5
D2
CHECK PIN
IC6
A52A2003GR2
R32
10k
SW3
TEST RUN
R69
26.7k
1
R25
220
C43
1000P
C44 +
1
50V
R80
13.7k
1/4 W
8
4
3
2
C42
1000P
IC3
A52MPC393G22
R47
10k
R26
49.9k
+
C28
10
C13
0.01
R46
10k
SW4
AUTO
R27
5.49k
R56
10k
C15
0.01
50
IC7
A52TPD4007K
R58
49.9k
D4
A541SS355
(GND)
12
BETWEEN
COILS
66
1
2
3
4
5
L2
1k
R18
1k
68
R45
374
7
65
LEFT
(ZH5)
1
2
3
4
5
R35 +
15k
C9
10
16V
11
(MX-5)
CN-STM1
1
2
3
4
5
R41 +
5.9k
C8
10
16V
R22
0.33
BZ
STANDBY
C11
0.01
R20
18.2k
C41
5600P
POWER
39
Q1
A55DC143XKTX
SW2
Fig.2
R51
2k
G93KE-ECD1
Intake
IntakeAir/
Air/Indoor
IndoorHeat
Heat
Exchanger
ExchangerTemp.
Temp.
44
Intake
IntakeAir
Air
Temp.
Temp.Data
Data
30
3
20
33
22
11
10
Indoor
IndoorHeat
HeatExchanger
Exchanger
Temp.
Temp.Data
Data
-10
10
20
30
40
50
00
10
10 20
20 30
30 40
40 50
50 6060 7070
Temperature
Temperature(C)
(C)
Temperature (C)
CS/CU-G93KE/G123KE
(45%)
CI-G123KE.DWG
Fig.
Fig.
22
Fig.2
40
(ZH5)
C10
22
(FC)
C29
1000P
630V
D8
69
GND
37
SW1
4.7k
D7
18
Fig.1
C40
1000P
630V
15 - 34
72
34
36
R31
1k
R36
10k
C39
2200P
A541SS355 x 3
73
J2
J1
C26
1000P
e
10k
CHECK PIN
(TEST)
COM1 d
COM2 COM3 D.P
1
2
3
4
5
6
UP/DOWN
DC INPUT C
7 DC OUTPUT
C38
0.01
R19
25.5k
74
33
LEFT
75
IC1
A5278366F100
32
D101
A54LNM23301A
RIGHT
C34
100
450V
(ECEC)
A
30
C104
C103
1000P x 4
Voltage (V)
(V)
Voltage
L5
CN-DISP2
CLK 8
10
IC101
A52M66311FP
9
FAN MOTOR
R50
A 4
820 x 7
10
CN-DISP1
CKS 6
OE 5
GND 9
5V
C2
0.01
DISPLAY
R108
R109
R112
100k
C106
0.01
BUZZER
27
1.5
R 7
RELAY
DRIVE
4MHz
OSC
26
+ C105
C102
R101
R102
R103
R104
R105
R106
R107
VCC 3
80
DATA TRANSMISSION
R117
R118
R119
R120
R121
C101
QA
QB
QC
QD
QE
QF
QG
QH
QI
QJ
QK
QL
QM
QN
QO
QP
5 GND
RESET
430 x 9
1
2
24
23
22
21
20
19
18
17
16
15
14
13
11
12
C1
100
C16
0.01
C33
0.1
DB1
A54D3SBA60F1
~
+
A
B
C
D
E
5
5
24
25
D103
A54LNK5372
5
5
5
5
11
L4
5
R113
R114
R115
R116
C32
0.01
250VAC
(KH)
C31
0.01
250VAC
(KH)
TH1
A47N11D5R0TT
REGULATOR
D102
A54LNK4171B POWERFUL
SLEEP
TIMER
POWER
FUSE1
3.15A
D6
A54D1F60
IC8
A52C108
DISPLAY
PC1
A52S2581L1KC
C5
2200P
R70
200k
1 0
R42
150k
R76
15k
2W
4
6 0
PC3
TLP521L1BL
11
5 0
2
1~2
10
D3
A54D1F68
TRANSMISSION
1
IC6
A52A2003GR2
IC2
A52BR9020F
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
4.7k
C4
1000p
R64
7.5k
X1
4MHz (27pF X 2)
TO OUTDOOR
1
2
3
R65
10k
2
4 SCK
C19
3300p
137k
5 GND
0.01
IC4
A52PST600D
4.7k
C24 +
33
25V
CN-RCV2
(MX-3)
6.3V
47
10k
I
G
Q4
A55DA143XKTX
Resistance (k )
8 IN+
330
1 8
SCK 5
C22
1.5
16V
(T)
MAIN
RY-PWR
MAIN SWITCH
AC 230V
50Hz
10
11
6/20/00, 4:03 PM
12
13
14
15
16
17
18
19
CS-G93K/G123K
CS-G93K/G123K
Time
Test mode
When test point
short-circuited
4 min.
2.4 sec.
30 min.
0 sec.
20 min.
0 sec.
Deice detection
Test mode
When test point
short-circuited
30 sec.
3 sec.
120 min.
24 sec.
80 min.
16 sec.
Anti-freezing control
6 min.
0 sec.
40 min.
8 sec.
3 min.
0 sec.
40 min.
8 sec.
3 min.
0 sec.
11 min.
66 sec.
2 min. 58 sec.
0 sec.
Hz lock time
30 sec.
0 sec.
30 sec.
3 sec.
3 min.
18 sec.
30 sec.
0 sec.
LED1
SID1003BQ
R5
2.2
1/8W
Q2
2SD602
X1
3.52Hz
(33P x 2)
R4
22k
C4
8P
(NPO)
X2
32.768kHz
16
15
14
13
12
11
10
17 XOSC2
SEG 7 64
SEG8 63
18 XOSC1
120 min.
12 sec.
30 min.
3 sec.
4 min.
0 sec.
R1
100k
R6
300
C6
0.1
SEG9 62
19 VSS
DOOR OPEN/CLOSE
SW1
(CLOSE:ON)
SW2
20 RESET
SEG10 61
21 PC3
SEG11 60
22 PC2
SEG12 59
SEG13 58
23 PC1
9 sec.
R14
51k
3 sec.
SEG19 52
30 PA5
SEG20 51
31 PA6
SEG21 50
SEG29
SEG28
SEG27
SEG26
SEG25
SEG24
12 sec.
SEG30
2 min.
SEG18 53
29 PA4
32 PA7
1 hour 6 sec.
SEG17 54
28 PA3
SEG31
42 sec.
SEG16 55
27 PA2
SEG32
420 min.
SEG15 56
26 PA1
RMO
18 sec.
R13
51k
SEG14 57
25 PA0
BZ
180 min.
30 min.
PC7
IC1
24 PC0
PC6
90 min.
R12
51k
PC5
J-B
3 sec.
PC4
30 min.
C5
8P
(NPO)
1 hour 1 min.
R7
200k
SEG6
0 sec.
R8
200k
R2
1.5k
SEG5
20 sec.
R9
200k
R3
51
SEG4
CN1
SEG3
0 sec.
C9
0.01
SEG2
10 sec.
SEG1
+ C2
47
SEG0
0 sec.
C8
0.01
COM2
2 min.
C1
47
R11
510k
R03
Q1
2SB710
COM1
60 sec.
C7
0.01
COM0
VLCD3
REMOTE CONTROL
VLCD2
DC PEAK
Time
VDD
Name
VLCD1
Name
OSC1
CS-G93K/G123K
OSC2
CS-G93K/G123K
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
SEG22 49
SEG 23
48
C
(POWERFUL)
FAN SPEED
(TEMP 9)
SELF
DIAGNOSIS
SLEEP
TIMER
ON
TIMER
CANCEL
AIR SWING
8
9
TIMER
OFF
TIMER
SET
SW2
0
WIDE / SPOT
AIR SWING
/(OFF / ON)
q
MODE
(TEMP 8)
CLOCK
J-B
OFF
ON
OFF
SHORT
ON
SHORT
G93KE-ECD1
10
11
6/20/00, 4:03 PM
12
13
14
15
16
17
18
19
CS-G93K/G123K
CS-G93K/G123K
CS-G93K/G123K
CU-G93KE
CU-G123KE
OUTDOOR TERMINAL
AC 230V
AC18-23V
Fig. 3
Fig. 3
FUSE
250V, 20A
1
2
3
DIODE
1
2
~
AC230V
REACTOR
CAPACITOR
Outdoor Air/Outdoor
Heat Exchanger Temp.
+
~
REACTOR
DIODE
+
C1
Outdoor Air
Temp. Data
C2
PTC
(WHT)
AC1
(WHT)
AC2
L
AC3
DC+
Voltage (V)
DC-
RY-PWR
Q8
D11
D14
FAN MOTOR
R79
10k
C27
220
10V
5
6
4
3
1
HOT
(YEL)
(XH-4)
CN-TH
COMPRESSOR
TEMP. SENSOR
(50k, 3975) Fig. 5
R81
1k
Fig. 3
R55 +
4.99k
5V
C31 +
10
16V
C29 +
10
16V
1
IPM
(POWER
TRANSISTOR)
BASE
SIGNAL
OUTPUT
C30
10
16V
L2
A43036
Fig. 4
4
5
C37
22
10V
C28 +
220
16V
R52
10k
VOLTAGE
DETECTION
PHOTO COUPLER
DRIVE
56
HEAT EXCHANGER
TEMP.
RELAY DRIVE
CS
S1 7
DL
R56
10k
S0 6
3.4
R66
38k
10
COMP. TEMP.
11
CURRENT
C39 +
22
400V
R65
51k
D18
ERA15-06
1
R59
680
C37
2200p
50V
2.6
c
2.6
b
Q6
UN421F
10k
2.2k
e
D17
ERA15-06
(RED)
AC4
ZNR1
R61
1k
R64
11k
3W
15
16
17
47
18
Vcc
Vsen
DATA
TRANSMISSION
FAN MOTOR
DRIVE
R2
27
3/4W
23
24
4-WAY VALVE
25
TLP521-IGH
LED1 (YLW)
A5448YPXTA3E
R34
620
R37
560
10k
4.7k
0
5
PC8
O
C46
3.3
50V
5V
I
+
C18
470
10V
C47
0.1
(ECQV)
IC4
78M05
REGULATOR
X1
12MHz
30pF X 2
R42
150k
0 (5)
38
TIMER SHORTEN
TLP521-IGH
A52MPC339C 18
13
11
RY-PWR
12
16
15
13
11
14
DC. PEAK
DC RESET
36
35
30
34
31
R28
4.7k
GND
R43
1k
32
R45
STN-BY 10k
R19
750k
C19
120
25V
R10
118
1W
+ C20
120
50V
R40
560
TLP521-IGH
8
9
C26
2200p
PC5
TLP521-1BL
(BL)
R7
330
C38
1000p
Vin
CT Vout
Vcc
Vsen
GND
11
Vfo
12
13
R3
1
C40
1
630v
(ECQE)
Total Running
Current Data
GND
Vin
CT Vout
Vcc
Vsen
GND
GND
Vin
CT Vout
Vcc
Vsen
GND
GND
3
2
1
C25
1000P
10V
0.1 (ECQB)
33k
C22 +
10
25V
3k
1
2
9
+
6
23.2k
989k
REGULATOR
0.1 (ECQB)
C23
1000P
C12
0.33
50V
(ECQV)
1M
33k
3k
11
1000P 47.5k
+
12
10
C11
0.33
50V
(ECQV)
33k
3k
11
1000P 47.5k
10
R84
383k
R15
619k
Fig.5 5
Fig.
Fig.
Fig. 65
23.2k
50
R14
75k
IC5
A52BX454
COMPRESSOR ROTOR
POSITION DETECTION
40
30
3
2
1
20
10
0
40
60
80
100
120
Temperature (C)
140
Temperature (C)
G93KE-ECD2
6/20/00, 4:06 PM
15
70
R24
3.6k
1.5k x 3
R27
R28
R29
10
Current (A)
60
1M
R26
3.6k
PC2
A52LP521-3
R83
499k
R13
499k
23.2k
0.1 (ECQB)
4
GND
R74
240k
1
GND
Vfo Temp.
R16
75k
+
R25
3.6k
989k
Vsen
R18
75k
C13
0.33
50V
(ECQV)
1000P 47.5k
-
D10
EBR12-01
TLP521-I
DC PEAK
Q5
C1740S
CT Vout
Vcc
1M
5
C48
0.01
R31
10k
R82
383k
R17
619k
989k
C21 +
10
25V
Vin
15
R63
7.5k
VR2
1k
C17
22
25V
(SXE)
D20
ERA15-06
100 ACV
Vfo
TLP521-I
1000p x 3
C34
C35
C36
Fig. 44
Fig.
ZD1
A54D6.2
EB1
IC7
A52AN79L10
R47
1k
C6
100
50V
(SXE)
IC8
R23
R33
18k
R30
15k
DC RESET
14
R76
4.7k
R46
2.2k
C5
0.033
(ECQM)
R21
1.82k
D8
A54RA22-04
R32
1k
C16
0.01
R11
5.23k
R9
4.53k
10V
PC3
R44
51k
GND
14
TLP521-IGH
TLP521-I
R41
470
1W
TEST (NH-2)
15
IC6
A52AN78L10
PC11
6
7
IC8
R77
56k
3W
D9
EBR12-01
RY-FM
RA1
10k X 5
L1
A43036
C24
0.01
GND
Vfo
R72
560
R73
5.23k
30
Temperature (C)
100 ACV
REGULATOR
PC1
29
R6
100
3/4W
D6
A541SS136
10
Vsen
20
10
16
PC10
R39
560
IC8
27
28
Vcc
10
COMPRESSOR
C3
100
10V
R78
56k
3W
Q1
A55C4420
C10
270
25V
(SXE)
C14
0.01
R1
5.23k
R22
2.55k
37
R70
560
CT Vout
R71
560
R12
510k
IC2
PA2003C
Vin
0
-10
3
2
1
IC8
3 4
2
5
12
TLP521-I
R75
10k
R38
560
R80
4.7k
2.5
5
2.5
1
PC9
12
D5
A54RA22-04
VOLTAGE
DETECTION
PC12
+
G
R8
560k
3/4W
R4
620k
3/4W
C4
470p
1kV AC
3
C1
470
25V
R5
680
3W
26
COMPRESSOR
ROTOR POSITION
DETECTION
13
C9
+ 270
25V
(SXE)
Q4
UN411F
Vfo
FUSE2
T3 15A L250V
R69
560
TLP521-IGH
8
39
C8
+ 270
25V
(SXE)
6
PC13
41
R68
560
GND
Vfo
D4
EBR43-02
21
42
C2
10
25V
5V
(XH3)
CN-MTR
100 ACV
11
3.4
20
22
GND
REGULATOR
D1
A54AU02ZV8
C7
270
25V
(SXE)
3.4
19
33
R62
300
2
C15
1000PF
AC250V
12MHz
OSC
14
48
40
2.6
R60
200k
POWER
RESET
43
PC4
A52PS2633E
R36
560
13
REF. VOLTAGE
3.4
12
44
D19
ERA15-10
1
2
3
4
5
45
R57
1k
54
46
2.3
SCK 5
55
49
Vcc 8
1 Vcc
4 GND
57
50
R52
10k
C33 +
470
16V
CN-AC
POWER ON
58
1
PC7
3.4
6
PHOTO COUPLER
DRIVE
51
C32 +
220
16V
1
2
60
53
R51
20.5k
ICX
A52D27C18C
61
52
(NH-2)
CN-S
TLP521-IGH
3.4
Fig. 6
CN-TANK
(NV-2)
TEST RUN
R54
15.8k
Fig. 3
1
2
R67
560
59
2.8
R53
15k
64
63
R50
10k
A56S26MD81M
4
3
2
1
D3
EBR43-02
62
PIPE TEMP.
SENSOR
(4.96k, 3800)
AIR TEMP. Fig. 1
SENSOR
(15k, 3950)
3
1
IC3
A5278M05
C98
0.01
3.4
1
2
3
IC1
A5278214WC26
SSR1
(BLUE)
(VH-3)
CN-HOT
1
PC6
R35
560
RY-FM
T1
A48367
D2
A54RA22-04
CR1
120
0.033
OPEN : 145C
CLOSE : 88C
Outdoor Heat
Exchanger Temp. Data
Voltage (V)
CR2
120
0.033
CT Vout
Voltage (V)
YEL
R49
598
VR1
200
1
2
3
4
5
Vin
Resistance (k )
CN-FM
D13
D15
C-FM
400V
2F
D12
FUSE1
T3 15A L250V
BLU
RED
4.7k
2
1
Q7
UN4116
D16
R48
1.65k
CT1
A40260
10
11
12
13
14
40
CS-G93K/G123K
CS-G93K/G123K
CS-G93K/G123K
PRINT PATTERN
INDOOR UNIT PRINTED CIRCUIT BOARD
MAIN
INDICATOR
MAIN
G93KE-ECD2
6/20/00, 4:07 PM
10
11
12
13
14
MACC
Untitled-7
6/21/00, 9:47 AM
Printed in Malaysia
P981203500YH