How knows the maximum allowance THD for off-grid

network in distributed generation which is supply by gas


turbine?

Like (1)
Comment (6)
Follow
Reply Privately
3 days ago
Comments
Bruno Ricardo Marques likes this
6 comments

Jim
Jim Phipps
Trekeng.com
You can use guidelines taken from various power quality standards.
For low voltage, power distribution, where voltage sensitive loads are mixed with
harmonic producing loads like rectifiers in motor drives, 5% THDv is a typical
guideline to follow.
For low voltage, dedicated systems, where sensitive loads are not part of the mix,
higher distortion might be acceptable. A guideline of 8% THDv might be
considered.

o
o
o
o

Check with the manufacturer of the gas turbine alternator to verify their design for
harmonic losses. Typically, alternators are designed based on a maximum
temperature rise. When voltage and current distortion levels are high, the harmonic
losses in the alternator will be greater. This will cause the machine to reach its
temperature rise limit at a lower loading level than rated. If you intend to operate
the alternator at its rated values and get maximum service life from the insulation
system, then the system distortion levels will need to be controlled to be less than
manufacture's design limits.
Like
Reply privately
Flag as inappropriate
2 days ago

Saeed
Saeed Radmanesh
Offshore Platform Engineering

o
o
o
o

thank a lot Dear Jim for your great comment,


Actually in this DG micro-grid we have a controlled heater which made around 4%
harmonic distortion and it caused to rapture the gas turbine coupling, so refer to
IEEE 519 for below 69Kv , THD is 5% , that's I interested about, but I didn't check
the GTG recommended THD.
for microgroove should consider other THD rate or standard?
Like
Reply privately
Flag as inappropriate
2 days ago

Hossein
Hossein Vahedi
Head Of Electrical Substation & Power Plant Interface Department at
Moshanir Power Engineering Consultants
o
o
o
o

According to IEEE standard it can be less than 5% in normal area.


Like
Reply privately
Flag as inappropriate
2 days ago

Didik Erfan
Didik Erfan Fahrudi
GG Field Development Project at Pertamina Hulu Energi ONWJ Ltd
o
o
o
o

You should check individual harmonic distortion, sometime more than 5%.
Like
Reply privately
Flag as inappropriate
2 days ago

Narendra Babu

Narendra Babu Nityanandam


Freelance Consultant
o
o
o
o

pl refer IEEE 519 - 2014


Like
Reply privately
Flag as inappropriate
1 day ago

Ahmad
Ahmad Ali Khan
Construction Professional
about that i have no sufficient information ,i think Mr Jim have a good knowledge