You are on page 1of 81

user's manual

nx frequency converters

3-speed positioning application


asfiff15

2 vacon

General

Vacon 3-Speed Positioning (Application ASFIFF15)


INDEX
1.

GENERAL ......................................................................................................................................... 3

1.1
1.2
2.

CONTROL I/O.................................................................................................................................... 6

2.1
3.

Monitoring values (Control keypad: menu M1)................................................................ 16


Basic parameters (Control keypad: Menu M2 G2.1) ................................................... 17
Input signals (Control keypad: Menu M2 G2.2.1-G2.2.6) ............................................ 19
Output signals (Control keypad: Menu M2 G2.3)......................................................... 21
Drive control parameters (Control keypad: Menu M2 G2.4)....................................... 22
Prohibit frequency parameters (Control keypad: Menu M2 G2.5).............................. 22
Motor control parameters (Control keypad: Menu M2 G2.6)...................................... 23
Protections (Control keypad: Menu M2 G2.7).............................................................. 24
Autorestart parameters (Control keypad: Menu M2 G2.8) ......................................... 25
Positioning (Control keypad: Menu M2 G2.10) ............................................................ 26
Positions (Control keypad: Menu M2 G2.11) ............................................................... 29
Mechanical brake control (Control keypad: Menu M2 G2.12.1).................................. 30
Mechanical brake control (Control keypad: Menu M2 G2.12.2).................................. 30
Keypad control (Control keypad: Menu M3)..................................................................... 30
System menu (Control keypad: M6) ................................................................................. 31
Expander boards (Control keypad: Menu M7) ................................................................. 31

DESCRIPTION OF PARAMETERS ......................................................................................................... 32

5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
5.11
6.
7.

Commissioning parameter settings .................................................................................. 8


Calibration......................................................................................................................... 10
Safety area ........................................................................................................................ 13
Teaching ............................................................................................................................ 14
Sheet cutter function ........................................................................................................ 14
Fieldbus control ................................................................................................................ 15

3-SPEED POSITIONING PARAMETER LISTS ..................................................................................... 16

4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
4.13
4.14
4.15
4.16
5.

Programmable I/Os with default settings ......................................................................... 7

COMMISSIONING ............................................................................................................................... 8

3.1
3.2
3.3
3.4
3.5
3.6
4.

I/O expander boards in positioning .................................................................................... 4


Positioning sequence.......................................................................................................... 5

BASIC PARAMETERS ........................................................................................................ 32


OUTPUT SIGNALS ............................................................................................................. 42
DRIVE CONTROL ............................................................................................................... 46
PROHIBIT FREQUENCIES................................................................................................. 48
MOTOR CONTROL ............................................................................................................. 49
PROTECTIONS................................................................................................................... 52
AUTO RESTART PARAMETERS ........................................................................................ 60
POSITIONING PARAMETERS............................................................................................ 62
POSITIONS PARAMETERS................................................................................................ 68
MECHANICAL BRAKE CONTROL ..................................................................................... 69
KEYPAD CONTROL PARAMETERS ................................................................................... 76

CONTROL SIGNAL LOGIC IN 3-SPEED POSITIONING APPLICATION ......................................................... 77


FAULTS AND FAULT CODES............................................................................................................... 78

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

General

vacon 3

3-Speed Positioning
1.

General

Frequency converter works as a positioning controller with the help of incremental encoder and
target reference. Encoder board OPT-A4/A5 as an option is necessary. Encoder could be installed on
a motor shaft or on a conveyors axis behind the gear (NXS). Encoder information is used both
positioning control and Closed Loop motor control (NXP). If Closed Loop is in use, then the encoder
must be on the motor shaft.
Digital inputs and outputs are programmable.
Additional functions:

Programmable Start/Stop and Reverse signal logic


Reference scaling
One frequency limit supervision
Second ramps and S-shape ramp programming
Programmable start and stop functions
DC-brake at start and stop
One prohibit frequency area
Programmable U/f curve and switching frequency
Autorestart
Motor thermal and stall protection: Programmable action; off, warning, fault

Target reference could be given with three different ways;


1)

Positioning is based on 32 programmable targets, which are saved to parameter group 2.11.
Active target could be select with the combination of five digital inputs. (Optional I/O-expander
board, OPT-B1.)

2)

Analog target reference; current or voltage input. Using this method, notice the influences of
analog electronics disturbances (1%).

3)

Target reference from fieldbus. Expander board should be selected from the OPT-C-serie
depending on the fieldbus type.

Positioning accuracy depends on the units in use and the positioning length.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

4 vacon

General

1.1 I/O expander boards in positioning


(eg. configurations)
Function mode,
For example.
32 target references,
selection with digital inputs.

SLOT
A

OPT-A1*

OPT-A2*

OPT-A4/A5

OPT-B1

--

Target reference from


fieldbus

OPT-A1*

OPT-A2*

OPT-A4/A5

--

OPT-C2/
OPT-C3/
OPT-C7

Sheet cutter, 1-2 ref.


Selection with standard
boards digital inputs, using
TTF- logic

OPT-A1*

OPT-A2*

OPT-A4/A5

--

--

Table 1-1. I/O-expander boards in different function modes, using default slots

*) OPT-A1 and OPT-A2 normally as standard.

SLOT
Board type

OPT-A1
OPT-A2

DI

DO

AI
mA/V
/+V

AO
mA/V

A B C D E

RO NO/NC

+10V
Ref.

+24V/
ext+2
4V

DI/Encoder (1024V)
Out+15/2
4V

DI/Encoder
(RS422)
Out+5/ 15V

OPT-A4

OPT-A5

OPT-B1

I/O- Signals

3+1
3+1
X

OPT-C2

Modbus, SPI- bus

OPT-C3

Profibus DP, SPI- bus

OPT-C7

DeviceNet, SPI- bus

Table 1-2. Optional slots and I/O- signals. (X=default)

We are developing new boards all the time. If you cant find the suitable board of this collection,
check the board development status from our salesmen.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

General

vacon 5

1.2 Positioning sequence


Figure 1- 1 Positioning sequence

Speed [Hz]
Speed- HI1
P2.10.10

Speed MED1
P2.10.11

Selection DIN
Pos. speed groups 1/2

STOP HYSTERES
P2.10.9

Speed CREEP1
P2.10.12

Speed- HI2
P2.10.14
Speed MED2
P2.10.15
Speed CREEP2
P2.10.16

Trip [ANY]

Med. speed
P2.10.7
Creep speed
P2.10.8

Positioning uses three different speed. When approaching the target, speed is decelerated with
three different phases. Speeds, hysteresis and ramps should be chosen by tests. In addition, the
application has so called automatic ramp scaling function (P2.10.21), which makes the positioning
quality better (See page 67). There are also two different speed groups, for example positioning
with or without the load. Maximum positioning speed is adjustable. This function is selected with
parameter P2.10.24.1. (See page 69)

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

6 vacon

2.

Control I/O

Control I/O
OPT-A1
1
2

READY

mA

Terminal
+10Vref
AI1+

Signal
Reference output
Analogue input, voltage range
010V DC

Description
Voltage for potentiometer, etc.
Voltage input frequency reference

3
4
5

AI1AI2+
AI2-

I/O Ground
Analogue input, current range
020mA

Ground for reference and controls


Current input frequency reference

6
7
8

+24V
GND
DIN1

Voltage for switches, etc. max 0.1 A


Ground for reference and controls
Contact closed = start forward

DIN2

10

DIN3

11

CMA

Control voltage output


I/O ground
Start forward, positioning
(programmable)
Start reverse, positioning
(programmable)
Preset speed (Manual speed)
(programmable)
Common for DIN 1DIN 3

12
13
14

+24V
GND
DIN4

15

DIN5

16
17
18
19
20

DIN6
CMB
AO1+
AO1DO1

Control voltage output


I/O ground
Positioning speed groups
(programmable)
Positioning mode
(programmable)
Calibration, teaching
Common for DIN4DIN6
Output frequency
Analogue output
Digital output
READY

Contact closed = start reverse


Contact closed = activated
Connect to GND or +24V
Voltage for switches (see #6)
Ground for reference and controls
Contact open = Speed group 1
Contact closed = Speed group 2
Contact closed = activated
Teaching, when calibration is done
Connect to GND or +24V
Programmable
Range 020 mA/RL, max. 500
Programmable
Open collector, I50mA, U48 VDC

OPT-A2
RUN

21
22
23

RO1
RO1
RO1

Relay output 1
CALIBRATION OK

Programmable

24
25
26

RO2
RO2
RO2

Relay output 2
EXTERNAL BRAKE CTRL

Programmable

Table 2-1. Positioning application, default I/O configuration.

Note: See jumper selections below.


More information in the products
User's Manual.

Jumper block X 3 :
CM A a nd CM B grounding
CMB connected to GN D
CMA connected to GN D
CMB isolated from GN D
CMA isolated from GN D
CMB and CMA
internally connected together,
isolated from GN D

= Factory default

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

Control I/O

vacon 7

2.1 Programmable I/Os with default settings


OPT-A1
DIA1
DIA2

Parameter
P2.2.1

Default
Fixed
Fixed

DIA3
DIA4
DIA5
DIA6
DO1
OPT-A2
RO1
RO2
OPT-B1
DIB1
DIB2
DIB3
DIB4
DIB5

P2.2.7.10
P2.2.7.11
P2.2.7.12
P2.2.7.13
P2.3.6

A.3
A.4
A.5
A.6
1

Function
Start forward, positioning
Start reverse, positioning
Preset speed
Positioning speed 1/2
Positioning mode
Calibration, teaching
Ready

P2.3.7
P2.3.8

17
24

Calibration OK
Ext. brake control

P2.2.7.14
P2.2.7.15
P2.2.7.16
P2.2.7.17
P2.2.7.18

D.1
D.2
D.3
D.4
D.5

Target selection, bit 0;LSB


Target selection, bit 1
Target selection, bit 2
Target selection, bit 3
Target selection, bit 4;MSB

Programmable I/O-function explained in details on page 37-39.

In chapter 3. Commissioning digital inputs are having default settings.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

8 vacon

3.

Commissioning

Commissioning

Download the application with NCLoad, use replace all function. Select the panel language on
page S6.1. Available languages are English and Finnish.
Option board parameters are in menu M7. (See the corresponding manual)

3.1 Commissioning parameter settings

Motor name-plate parameters in group G2.1 BASIC PARAMETERS.

P2.10.1; Target reference selection. Target reference could be given in spite of control
place P3.1 settings. If you want to control frequency converter eg. via fieldbus
(Start, stop, speed ref, positioning CW and so on), it must be selected with
parameter P3.1 as an active control place.
0= Fixed positions 0-31, combination of 5 digital inputs.
1= Analog target reference; voltage or current input (P2.10.2)
2= Target reference from fieldbus
Fixed positions 0-31;
Storage location in parameter group G2.11 selected with the combination of 5 digital
inputs.
Analog target reference;
Target reference could be given eg. potentiometer, voltage or current signal.
Reference is adjustable during the positioning also. Notice analog electronics
disturbances, which could effect to positioning accuracy (1%).

Target reference from fieldbus;


Target reference is written to processdata field 1, type UINT. Calibration reference is
written to processdata field 4, type UINT. Values is internally limited like position
parameters in group G2.11. See also chapter 3.6 Fieldbus control.

P2.10.4; Total trip (Max. 60000). Unit type: ANY. Total length of the positioning area. Use the
same units in all trip parameters. (P2.10.4, P2.10.7, P2.10.8, P2.10.9 and all parameters in group
G2.11)

P2.10.5; User defined encoder axis rounds per total trip.


Max. 65535. Decimals to this value is defined by parameter P2.10.6.

Note! This parameter affects essentially to positioning accuracy.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

Commissioning

vacon 9

Total rounds calculation based on a carefully measurement of the conveyors axis


diameter:

Total Rounds =

Total Trip
* Axis Diameter

Or total rounds calculation based on a trip measurement corresponding one


conveyors axis revolution:

Total Rounds =

Total Trip
Lenght of the 1 revolution

P2.10.6; Decimals. (Max. 4) Total rounds (P2.10.5) decimal numbers.


Example: If calculated total rounds are 5.24943, choose maximum value 4, because
52494<65535. Now you reach the optimal accuracy.

P2.10.7; Medium speed position. Advance position, when moving to medium speed.
(P2.10.11 or P2.10.15). Outside this area, speed reference is high positioning
speed (P2.10.10 or P2.10.14). Same units as P2.10.4.

P2.10.8; Creep speed positioning. Advance position, when moving to creeping speed.
(P2.10.12 tai P2.10.16). Same units as P2.10.4.

P2.10.9; Stop hysteresis. Advance position, when stopping. Finally positioning accuracy is
defined with this parameter. Frequency converter keeps the conveyor inside the hysteresis as
long as the START-command is on. In other words, it repairs the positioning all the time. If
hysteresis is too small, conveyor starts to oscillate. If this happens, you could decrease the
creeping speed, tune the ramps or increase the stop hysteresis. Same units as P2.10.4.

P2.11.1; Safety area Low. End limit area settings to positioning areas beginning.
Same units as P2.10.4.

P2.11.2;Safety area High. End limit area setting to positioning area end.
Same units as P2.10.4.

P2.11.3; Calibration position. Same units as P2.10.4. Locationing to safety area is


prohibited.
After these settings the calibration could be done!

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

10 vacon

Commissioning

3.2 Calibration
Trip counter must be calibrate always, when frequency converter is switched on, driving outside the
positioning area (=Fault) or calibration is reset by parameter P2.10.19 (value=1). Safety area is
activated, when calibration is done. (See chapter 3.3) Calibration could execute either manually or
automatically. The meaning of calibration is to set the known position to trip counter. Calibration
position is defined with parameter P2.11.3 or if using fieldbus, the calibration position is given to
processdata input field 4.
Calibration function mode is selected by parameter P2.10.18 AutoCalibration: Off/On;
Off= Manual calibration, see chapters 3.2.1 and 3.2.2
On= Automatic calibration, see chapter 3.2.3 and 3.2.4
NOTE! When doing calibration, all digital inputs must be set to zero!

In sheet cutter mode, you dont have to make calibration. Also safety area function is disabled!

3.2.1

Manual calibration using I/O-control

Manual calibration is executed in manual mode, DIA5=0. Conveyor is manually driven to position
corresponding to the parameter P2.11.3, then stop and confirm the calibration with DIA6. Now the
trip caunters value is same as parameter P2.11.3 and safety limits will be activated.
You could facilitate the manual calibration using preset speed defined with parameter P2.1.14,
activated with DIA3.
3.2.2

Manual calibration using fieldbus control

Manual calibration is executed in manual mode, processdata in 2, bit 1=0. Conveyor is driven to
position corresponding to the calibration position written to processdata in 4. Then stop and confirm
the calibration with processdata in 2, bit 0=1. Now the trip counters value is same as value in
processdata in 4 and safety limits will be activated. Note that the active target (V1.17) is not updated
until the next start-command.
3.2.3

Automatic calibration using I/O-control

Automatic calibration is executed in positioning mode, DIA5=1. Automatic calibration is activated,


when the function is selected with P2.10.18. and START-command is given. This way the conveyor
moves pursuant a sequence shown in Figure 3-1. This funtion uses positioning speed group 2 and
differential proximity switch connected to digital input.

3.2.4
1)
2)
3)
4)

Automatic calibration using fieldbus control

Set parameter P2.10.18 AutoCalibration = On


Set the positioning mode on; processdata in 2, bit 1=1
Give start-command
Now the conveyor moves pursuant a sequence shown in Figure 3-1.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

Commissioning

vacon 11

Note: When the proximity switch is connected to PLC, then the status of the proximty switch must
be forwarded by the PLC to the frequency converter process data in 2, PDIN2, Bit0 (Calibration)
5) When the sequency is ready, (motor is running on zero frequency) give stop-command.
6) Now the trip counters value is same as value in P2.11.3 and safety limits will be activated.
Three steps of automatic calibration:
Step 1)

When START-command is activated, the conveyor moves on speed, which is defined


with parameter P2.10.15. In this case, direction of rotation is always reverse. If the
conveyor is already in proximity switch target area, this step is by-passed. Proximity
switch is connected to digital input DIA6 or the status of the switch is forwarded by
the PLC to the drive to processdata in 2, bit 0.

Step 2)

Proximty switch recognizes the car, DIA6=01 (PDIN2, Bit 0=1). Change of
direction, and speed is decreased to creeping speed reference defined by parameter
P2.10.16.

Step 3)

The car moves away from proximity switch target area, DIB6=10, (PDIN2, Bit
0=0) and the conveyor stops. Now the calibration is executed automatically, if using
I/O-control. On fieldbus control, the drive remains run-state, until the stop-command
is given. After that, the calibration must be confirmed using processdata in 2, bit 3
(Rising edge).
Now the trip counters value is same as parameter P2.11.3 and safety limits will
activate.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

12 vacon

Commissioning

P2.11.1

P2.11.2
Reverse

1)

Safetyarea

Safetyarea

DIA6
Change of direction

P2.11.2

Safetyarea

2)

DIA6

P2.11.1

P2.11.2

STOP&Calibration

3)

Safetyarea

Safetyarea

DIA6

Figure 3- 1Steps of automatic caliration

NOTE! Proximity switch must install so, that the car dont fit totally to the safety area, outside
the proximity switch target area!

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

Commissioning

vacon 13

3.3 Safety area


Intention is to control manual drive near both mechanical ends. End limits are activated, when
calibration is done. Limits are set by parameters P2.11.1and P2.11.2. When driving manually over
the end limits, alarm End limits occurs and frequency is limited to value set by parameter
P2.10.13. If driving still goes on, until car goes outside the positioning area, fault New Calib.occurs
and calibration have to do again. If driving is stopped in safety area, starting to same direction is not
possible. In that case, new start have to do to opposite direction.

Calibration and position settings to safety area is prohibited!!!


This function is disabled in sheet cutter mode.

Alarm:"End limits"

Alarm:"End limits"

Fault:"New Calib."

Fault:"New Calib."

POSITIONING AREA
End limit speed
P2.10.13

End limit speed


P2.10.13
Positions 0-31
End limit
P2.11.1

End limit
P2.11.2

Figure 3- 2 Principal of safety area function

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

14 vacon

Commissioning

3.4 Teaching
Teaching is possible after the calibration. Teaching mode could be activated with parameter
P2.10.17. Conveyor is driven to the wanted position and receiptioned by digital input DIA 6. Position
is stored to place in group G2.11, which is selected with the combination of digital inputs.

3.5 Sheet cutter function


The purpose is to drive a proportinal sequence. Target reference is given by digital inputs, analog
reference or from fieldbus. Total trip and corresponding total rounds could be set using one
positioning sequence or multiply of them. (See Figure 3-3) Trip counter is reset on every STARTcommand. Function is activated in positioning mode (DIB5=1) with the parameter P2.10.3. Sheet
cutter positioning is possible to both directions. Calibration and safety area functions are disabled.

Example 1: Total trip-->Total rounds


Example 2: Total trip-->Total rounds
Speed/Hz
Example 2
Example 1

START-->
Reset tripcounter

START-->
Reset tripcounter

Time

Figure 3- 3 Function sequence

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

vacon 15

3.6 Fieldbus control


Fieldbus reference is selected by P2.10.1 (value=2). PPO- type selection eg. PP0 2 or PPO 5, because
processdata fields are in use. Control place is selected differentially by P3.1, whereby the function
mode must be ProfiDrive (CW and SW remains ProfiDrive- profile. See also profibus manual). Target
reference could be given from fieldbus in spite of control place P3.1 settings.
3.6.1

Application processdata.

Masterslave
Field
Processdata 1

Signal
Target reference

Type
UINT

Processdata 2

Positioning control word

INT

Processdata 3

Max. speed adjusting

INT

Description
0-60000. Internally limited.(Same as
parameters in group G2.11)
Updating always on START-command.
Digital input simulation from fieldbus:
B0=Calibration, teaching.
B1=Positioning mode OFF/ON
B2=Positioning speed groups 1/2
B3=Not used
B4=Not used
B5=Reset Calibration
B6=Calibration prohibited
Max. speed adjusting from fieldbus. Scaling
limits P2.10.24.2 P2.10.24.5.

Table 3-1. Processdata in.

NOTE! When using positioning CW, control place must be on fieldbus (P3.1).
Slavemaster
Field
Processdata 3

Signal
Positioning status word.

Type
INT

Description
ID
B0= Calibration OK,
B1= Position reached
B2= At positioning speed max.
B3= Programmable digital input.
B4= Programmable digital input.
B5= Programmable digital input.
B6= Programmable digital input.
B7= Programmable digital input.
B8= Positioning mode OFF/ON
B9= Calibration input
B10= Not used
B11= Warning Low End
B12= Warning High End
B13= Out of Area
B14= RunEnable Low End
B15= RunEnable High End

Table 3-2. Processdata out.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

16 vacon

4.

3-Speed Positioning Parameter lists

3-Speed Positioning Parameter lists

On the next pages you will find the lists of parameters within the respective parameter groups. The
parameter descriptions are given on pages 32-77.
Column explanations:
Code
Parameter
Min
Max
Unit
Default
Cust
ID

= Location indication on the keypad; Shows the operator the present parameter
number
= Name of parameter
= Minimum value of parameter
= Maximum value of parameter
= Unit of parameter value; Given if available
= Value preset by factory
= Customers own setting
= ID number of the parameter (used with PC tools)
= In parameter row: Use TTF method to program these parameters.
= On parameter code: Parameter value can only be changed after the frequency
converter has been stopped.

4.1 Monitoring values (Control keypad: menu M1)


The monitoring values are the actual values of parameters and signals as well as statuses and
measurements. Monitoring values cannot be edited.
See the products Users manual for more information.
Code

Parameter

Unit

ID

Description

V1.1
V1.2
V1.3
V1.4
V1.5
V1.6
V1.7
V1.8
V1.9
V1.10
V1.11
V1.12
V1.13
V1.14
V1.15
V1.16
V1.17
V1.18
V1.19

Output frequency
Frequencyreference
Motor speed
Motor current
Motor torque
Motor power
Motor voltage
DC link voltage
Unit temperature
Voltage input
Current input
DIN1, DIN2, DIN3
DIN4, DIN5, DIN6
DO1, RO1, RO2
Analogue Iout
Actual position
Target position
Total rounds
Decimal rounds
FB Positioning
Control Word
FB Positioning
Status Word
Status Word
Current Unfilteres
Torque Unfiltered
FreqRampOut
DC Voltage
Unfiltered

Hz
Hz
rpm
A
%
%
V
V
C
V
mA

1
25
2
3
4
5
6
7
8
13
14
15
16
17
26
1551
1553
1580
1581

Output frequency to motor


Frequency reference to motor control
Motor speed in rpm

V1.20
V1.21
V1.22
V1.23
V1.24
V1.25
V1.26

mA
--r
Dec

In % of the nominal motor torque


Motor shaft power

Heatsink temperature
AI1
AI2
Digital input statuses
Digital input statuses
Digital and relay output statuses
AO1
Actual position in real units
Target position in real units
Enc. rounds
1 full round=65535

1700
1701
1702
1113
1081
1129
1082

Table 4- 1. Monitoring values

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

3-Speed Positioning Parameter lists

vacon 17

V1.20 Fieldbus positioning control word


Bit
0
1
2
3
4
5
6
7

15

Description
Value = 0
No meaning
Manual mode
Positioning speed group 1
Not used
Not used
No meaning
Calibration permitted
Not used
Not used
Not used

Value = 1
FB Calibration input
Positioning mode
Positioning speed group 2
Not used
Not used
FB Reset calibration
Calibration prohibited
Not used
Not used
Not used

Table 4-1. Fieldbus positioning control word

V1.21

Fielbus positioning status word


Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

Description
Value = 0
Not calibrated
Not in position reference
Positioning low speed

Value = 1
Calibration OK
Position reached
Positioning Max Speed
Programmable digital input. P2.10.22.1
Programmable digital input. P2.10.22.2
Programmable digital input. P2.10.22.3
Programmable digital input. P2.10.22.4
Programmable digital input. P2.10.22.5
Manual mode
Positioning mode
Calibration input FALSE
Calibration input TRUE
Not Used
Not Used
No Warning
Warning Low End
No Warning
Warning High End
In side of area
Out of area fault
Run Disable Low End
Run Enable Low End
Run Disable High End
Run Enable High End

Table 4-2. Fieldbus positioning status word

V1.22

Status Word
NOTE: Content of internal status word may vary with different versions
Bit
0
1
2
3
4
5
6

15

Description
Value = 0
Run Disabled
No Warning
FC Stopped
No Fault
No Run Request
Calibration permitted
Brake closed
Not used
Not used

Value = 1
Run Enabled
Warning
FC Running
Fault active
Run Request
Calibration prohibited
Brake opened
Not used
Not used

Table 4-3. Status word

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

18 vacon

3-Speed Positioning Parameter lists

4.2 Basic parameters (Control keypad: Menu M2 G2.1)


Code
P2.1.1

Parameter
Min frequency

Min
0,00

Max
Par. 2.1.2

Unit
Hz

Default
0,00

Cust

ID
101

P2.1.2

Max frequency

Par. 2.1.1

320,00

Hz

50,00

102

P2.1.3
P2.1.4

Acceleration time 1
Deceleration time 1

0,1
0,1

3000,0
3000,0

s
s

3,0
3,0

103
104

P2.1.5

Current limit

0,1 x IL

2,5 x IL

1,5 x IL

107

P2.1.6

Nominal voltage of
the motor

180

690

NX2: 230V
NX5: 400V
NX6: 690V

110

P2.1.7

Nominal frequency
of the motor

30,00

320,00

Hz

50,00

111

P2.1.8

Nominal speed of
the motor

300

20 000

rpm

1440

112

P2.1.9

Nominal current of
the motor

1 x IL

2,5 x IL

IL

113

2.1.10

Motor cos

0,30

1,00

0,85

120

2.1.11

I/O reference

117

2.1.12

Keypad control
reference

121

2.1.13

Fieldbus control
reference

122

2.1.14

Preset speed

0,00

Par. 2.1.2

10,00

105

Hz

Note
NOTE: If fmax > than the
motor synchronous speed,
check suitability for motor
and drive system

NOTE: This applies for


frequency converters up to
FR7. For greater sizes,
consult the factory.

Check the rating plate of


the motor
The default applies for a 4pole motor and a nominal
size frequency converter.
Check the rating plate of
the motor
Check the rating plate of
the motor
0=AI1
1=AI2
2=Keypad
3=Fieldbus
0=AI1
1=AI2
2=Keypad
3=Fieldbus
0=AI1
1=AI2
2=Keypad
3=Fieldbus
Speed preset by operator

Table 4-4. Basic parameters G2.1

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

3-Speed Positioning Parameter lists

vacon 19

4.3 Input signals (Control keypad: Menu M2 G2.2.1-G2.2.6)


Code

Parameter

Min

Max

Unit

Default

Cust

ID

P2.2.1

Start/Stop logic

300

P2.2.2

Current reference
offset

302

P2.2.3

Reference scaling
minimum value

0,00

par. 2.2.5

Hz

0,00

303

P2.2.4

Reference scaling
maximum value

0,00

320,00

Hz

0,00

304

P2.2.5

Reference inversion

305

P2.2.6

Reference filter time

0,00

10,00

0,10

306

Note
DIN1
0
1
2
3
4
5
6

Start fwd
Start/Stop
Start/Stop
Start pulse
Fwd*
Start*/Stop
Start*/Stop

DIN2
Start rvs
Rvs/Fwd
Run enable
Stop pulse
Rvs*
Rvs/Fwd
Run enable

0=No offset
1=420 mA
Selects the frequency that
corresponds to the min.
reference signal
0,00 = No scaling
Selects the frequency that
corresponds to the max.
reference signal
0,00 = No scaling
0 = Not inverted
1 = Inverted
0 = No filtering

Table 4-5. Input signals, G2.2.1-G2.2.6

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

20 vacon

4.3.1

3-Speed Positioning Parameter lists

Digital inputs (Control keypad: Menu M2 G2.2.7)


Code
P2.2.7.1
P2.2.7.2
P2.2.7.3
P2.2.7.4
P2.2.7.5
P2.2.7.6
P2.2.7.7
P2.2.7.8
P2.2.7.9
P2.2.7.10
P2.2.7.11
P2.2.7.12
P2.2.7.13
P2.2.7.14
P2.2.7.15
P2.2.7.16
P2.2.7.17
P2.2.7.18
P2.2.7.19
P2.2.7.20
P2.2.7.21
P2.2.7.22
P2.2.7.23
P2.2.7.24
P2.2.7.25

Parameter
Ext. fault
Closing cont.
Ext. fault
Opening cont.
Run enable
Acc./Dec
Time selection
Force control
place to I/O
Force control
place to keypad
Force control
place to fieldbus
Reverse (if par.
2.2.1=3)

Fault reset
Manual speed
(Preset speed)
Positioning speed
group sel.
Positioning mode
Calibration,
teaching
Select position,
Bit 0, LSB
Select position,
Bit 1
Select position,
Bit 2
Select position,
Bit 3
Select position,
Bit 4, MSB
Ext.Brake enable
Run Enable Low
End
Run Enable High
End
Reset Calibration
Calibration
Negative
Calibration
Prohibited
Reset Encoder

Min

Max

Unit

Init.

Cust.

ID

0.1

E.10

0.1

1554

0.1

E.10

0.1

1555

0.1

E.10

0.1

1556

0.1

E.10

0.1

1557

0.1

E.10

0.1

1558

0.1

E.10

0.1

1559

0.1

E.10

0.1

1560

0.1

E.10

0.1

1561

0.1

E.10

0.1

1565

0.1

E.10

A.3

1562

0.1

E.10

A.4

1563

0.1

E.10

A.5

1564

0.1

E.10

A.6

1566

0.1

E.10

D.1

1567

0.1

E.10

D.2

1568

0.1

E.10

D.3

1569

0.1

E.10

D.4

1570

0.1

E.10

D.5

1571

0.1

E.10

0.2

1605

0.1

E.10

0.2

1609

0.1

E.10

0.2

1608

0.1

E.10

0.1

1611

0.1

E.10

0.2

1612

0.1

E.10

0.1

1613

0.1

E.10

0.1

1614

Table 4-6. Digital inputs, G2.2.7.1-G2.2.7.19

See details on page 37.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

3-Speed Positioning Parameter lists

vacon 21

4.4 Output signals (Control keypad: Menu M2 G2.3)


Code

Parameter

Min

Max

P2.3.1

Analogue output
function

0,00

10,00

P2.3.2
P2.3.3
P2.3.4
P2.3.5

P2.3.6

P2.3.7
P2.3.8

Analogue output
filter time
Analogue output
inversion
Analogue output
minimum
Analogue output
scale

Digital output 1
function

Relay output 1
function
Relay output 2
function

Unit

Default

Cust

ID

307

1,00

308

309

310

10

1000

100

311

Note
0=Not used
1=Output freq. (0fmax)
2=Freq. reference (0fmax)
3=Motor speed (0Motor
nominal speed)
4=Output current (0
InMotor)
5=Motor torque (0TnMotor)
6=Motor power (0PnMotor)
7=Motor voltage (0-UnMotor)
8=DC-link volt (01000V)
9=Target ref. Scaled to
current signal

0 = Not inverted
1 = Inverted
0 = 0 mA
1 = 4 mA

24

312

0=Not used
1=Ready
2=Run
3=Fault
4=Fault inverted
5=FC overheat warning
6=Ext. fault or warning
7=Ref. fault or warning
8=Warning
9=Reversed
10=Preset speed
11=At speed
12=Mot. regulator active
13=OP freq. limit superv.
14=Control place: IO
15=Therm. fault/warning
16=FB digin1
17=Calibration OK
18=Position reached
19=At high speed
20=At medium speed
21=At creep speed
22=Outside positioning
area
23=Over the end limit
24=Mech.brake open

24

17

313

As parameter 2.3.6

24

24

314

As parameter 2.3.6

P2.3.9

Output frequency
limit 1 supervision

P2.3.10

Output frequency
limit 1;
Supervised value

0,00

320,00

Hz

315

0,00

316

0=No limit
1=Low limit supervision
2=High limit supervision

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

22 vacon

P2.3.11
P2.3.12
P2.3.13
P2.3.14
P2.3.15
P2.3.16

3-Speed Positioning Parameter lists

Analogue output 2
signal selection
Analogue output 2
function
Analogue output 2
filter time
Analogue output 2
inversion
Analogue output 2
minimum
Analogue output 2
scaling

0.1

471

TTF programming method


used. See PFC application.

472

As parameter 2.3.1

1,00

473

0,00

10,00

474

475

10

1000

1000

476

0=Not inverted
1=Inverted
0=0 mA
1=4 mA

Table 4-7. Output signals, G2.3

4.5 Drive control parameters (Control keypad: Menu M2 G2.4)


Code

Parameter

Min

Max

Unit

Default

Cust

ID

P2.4.1

Ramp 1 shape

0,0

10,0

0,0

500

P2.4.2

Ramp 2 shape

0,0

10,0

0,0

501

P2.4.3
P2.4.4

Acceleration time 2
Deceleration time 2

0,1
0,1

3000,0
3000,0

s
s

10,0
10,0

502
503

P2.4.5

Brake chopper

504

P2.4.6

Start function

505

P2.4.7

Stop function

506

P2.4.8

Flux brake

520

Flux braking current

0,0

Varies

0,0

519

P2.4.9

Note
0 = Linear
>0 = S-curve ramp time
0 = Linear
>0 = S-curve ramp time

0=Disabled
1=Used when running
2=External brake chopper
3=Used when
stopped/running
0=Ramp
1=Flying start
0=Coasting
1=Ramp
2=Ramp+Run enable coast
3=Coast+Run enable ramp
0 = Off
1 = On

Table 4-8. Drive control parameters, G2.4

4.6 Prohibit frequency parameters (Control keypad: Menu M2 G2.5)


Code
P2.5.1
P2.5.2
P2.5.3

Parameter
Prohibit frequency
range 1 low limit
Prohibit frequency
range 1 high limit
Prohibit acc./dec.
ramp

Min

Max

Unit

Default

Cust

ID

0,00

par. 2.5.2

Hz

0,00

509

0,00

320,00

Hz

0,0

510

0,1

10,0

1,0

518

Note

Table 4-9. Prohibit frequency parameters, G2.5

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

3-Speed Positioning Parameter lists

vacon 23

4.7 Motor control parameters (Control keypad: Menu M2 G2.6)


Code

Parameter

Min

Max

P2.6.1

Motor control mode

600

P2.6.2

U/f optimisation

109

P2.6.3

U/f ratio selection

108

P2.6.4

Field weakening
point

30,00

320,00

Hz

50,00

602

P2.6.5

Voltage at field
weakening point

10,00

200,00

100,00

603

0,00

par.
P2.6.4

Hz

50,00

604

0,00

100,00

100,00

605

n% x Unmot

0,00

40,00

0,00

606

n% x Unmot

1,0

16,0

kHz

Varies

601

607

608

Depends on kW
0=Not used
1=Used
0=Not used
1=Used

P2.6.6
P2.6.7
P2.6.8
P2.6.9
P2.6.10
P2.6.11

U/f curve midpoint


frequency
U/f curve midpoint
voltage
Output voltage at
zero frequency
Switching frequency
Overvoltage
controller
Undervoltage
controller

Unit

Default

Cust

ID

Note
0=Frequency control
1=Speed control
2=Torque control
3=Closed Loop, speed ctrl
0=Not used
1=Automatic torque boost
0=Linear
1=Squared
2=Programmable
3=Linear with flux optim.

n% x Unmot
Parameter max. value =
par. 2.6.7

Table 4-10. Motor control parameters, G2.6

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

24 vacon

3-Speed Positioning Parameter lists

4.8 Protections (Control keypad: Menu M2 G2.7)


Code

Parameter

Min

Max

P2.7.1

Response to
reference fault

P2.7.2
P2.7.3
P2.7.4
P2.7.5
P2.7.6
P2.7.7
P2.7.8
P2.7.9
P2.7.10
P2.7.11
P2.7.12

Reference fault
0,00
frequency
Response to external
0
fault
Input phase
0
supervision
Response to
1
undervoltage fault
Output phase
0
supervision
Earth fault
0
protection
Thermal protection
0
of the motor
Motor ambient
100,0
temperature factor
Motor cooling factor
0,0
at zero speed
Motor thermal time
1
constant
Motor duty cycle
0

728

701

730

727

702

703

704

0,0

705

150,0

40,0

706

200

min

10

707

100

100

708

P2.7.14
P2.7.15
P2.7.16

Stall current
Stall time limit
Stall frequency limit

0,1
1,00
1,0

6000,0
120,00
Par. 2.1.2

P2.7.19
P2.7.20

P2.7.21

P2.7.22
P2.7.23

Response to
thermistor fault
Response to
fieldbus fault
Response to slot
fault

Hz

100,0

Underload curve at
nominal frequency
Underload curve at
zero frequency
Underload
protection time
limit

ID

0,00

Par. 2.1.2

P2.7.18

Cust

700

Stall protection

Underload protection

Default

P2.7.13

P2.7.17

Unit

10

150

5,0
2

A
s
Hz

709

10,0
15,00
25,0

710
711
712

713

50

714

150,0

10,0

715

600

20

716

Note
0=No response
1=Warning
2=Warning+Old Freq.
3=Wrng+PresetFreq 2.7.2
4=Fault,stop acc. to 2.4.7
5=Fault,stop by coasting

0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting

0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting

0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting

732

0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting

733

See P2.7.21

734

See P2.7.21

Table 4-11. Protections

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

3-Speed Positioning Parameter lists

vacon 25

4.9 Autorestart parameters (Control keypad: Menu M2 G2.8)


Code
P2.8.1
P2.8.2

Parameter
Wait time
Trial time

Min
0,10
0,00

Max
10,00
60,00

P2.8.3

Start function

719

10

720

10

721

722

10

723

10

726

10

725

P2.8.4
P2.8.5
P2.8.6
P2.8.7
P2.8.8
P2.8.9

Number of tries after


undervoltage trip
Number of tries after
overvoltage trip
Number of tries after
overcurrent trip
Number of tries after
reference trip
Number of tries after
motor temperature
fault trip
Number of tries after
external fault trip

Unit
s
s

Default
0,50
30,00

Cust

ID
717
718

Note

0=Ramp
1=Flying start
2=According to par. 2.4.6

Table 4-12. Autorestart parameters, G2.8

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

26 vacon

3-Speed Positioning Parameter lists

4.10 Positioning (Control keypad: Menu M2 G2.10)


Code

Parameter

Min

Max

P2.10.1

Reference selection

1548

P2.10.2

Analog reference

1549

P2.10.3

Sheet cutter mode

1578

P2.10.4

Total trip

60000

15000

1500

P2.10.5

Total rounds

65535

954.9

1501

P2.10.6

Desimals
Med. Speed
starting point
Creep speed
starting point
Stop hysteresis
Positioning speed
max. 1
Positioning speed
med. 1
Positioning speed
creep 1
End limit speed
Positioning speed
max. 2
Positioning speed
med. 2
Positioning speed
creep 2

4
P2.10.4P2.11.1

1502

200

1506

P2.10.7
P2.10.8
P2.10.9
P2.10.10
P2.10.11
P2.10.12
P2.10.13
P2.10.14
P2.10.15
P2.10.16

P2.10.8

Unit

Init.

Cust

ID

P2.10.9

P2.10.7

100

1505

P2.10.8

10

1504

P2.10.11

P2.1.2

Hz

20.00

1509

P2.10.12

P2.10.10

Hz

10.00

1508

0.00

P2.10.11

Hz

5.00

1507

0,00

P2.1.2

Hz

5.00

1552

P2.10.15

P2.1.2

Hz

15.00

1512

P2.10.16

P2.10.14

Hz

7.50

1511

0.00

P2.10.15

Hz

3.75

1510

P2.10.17

Teaching

1513

P2.10.18

Automatic
calibration

1546

P2.10.19

Calibration Reset

1586

P2.10.20

Save position

1606

P2.10.21

Automatic ramp
scaling

1572

Note
0=Fixed positions
1=Analog reference
2=Fieldbus reference
0=AI1
1=AI2
0=Off
1=On
Users defined accurate
rounds per total trip
Affects to P2.10.5

0=Off
1=On
0=Off
1=On
0=Norm. calibration
1=Reset calibration
Save position on power
off/on situation
0=Off
1=On

Table 4-13. Positioning parameters, G2.10

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

3-Speed Positioning Parameter lists

vacon 27

4.10.1

Fieldbus; Programmable status word (Control keypad: Menu M2 G2.10.22)

4.10.1.1

Processdata out, field 3.

Koodi

Parametri

Min

Max

Yks.

Oletus

Oma

ID

P2.10.22.1

Statusword,
3.BIT

0.1

E.10

0.1

1573

P2.10.22.2

Statusword,
4.BIT

0.1

E.10

0.1

1574

P2.10.22.3

Statusword,
5.BIT

0.1

E.10

0.1

1575

P2.10.22.4

Statusword,
6.BIT

0.1

E.10

0.1

1576

P2.10.22.5

Statusword,
7.BIT

0.1

E.10

0.1

1577

Huomautuksia
Programmable digital
input for the third bit of
the statusword.
Programmable digital
input for the fourth bit of
the statusword.
Programmable digital
input for the fifth bit of
the statusword.
Programmable digital
input for the sixth bit of
the statusword.
Programmable digital
input for the seventh bit
of the statusword.

Table 4-14. Programmable digital inputs for own status word, G2.10.22.

Bit structure of programmable statusword:


Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

4.10.2

Description
Value = 0
Not calibrated
Not in position reference
Positioning low speed

Value = 1
Calibration OK
Position reached
Positioning Max Speed
Programmable digital input. P2.10.22.1
Programmable digital input. P2.10.22.2
Programmable digital input. P2.10.22.3
Programmable digital input. P2.10.22.4
Programmable digital input. P2.10.22.5
Manual mode
Positioning mode
Calibration input FALSE
Calibration input TRUE
Not Used
Not Used
No Warning
Warning Low End
No Warning
Warning High End
In side of area
Out of area fault
Run Disable Low End
Run Enable Low End
Run Disable High End
Run Enable High End

Multimonitor (Control keypad: Menu M2 G2.10.23)

Into the multimonitor menu you could select three monitoring values at the same time. Values could
be selected from the menu M1, in addition frequency reference from panel, R3.2. See details on
page 67.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

28 vacon

4.10.3

3-Speed Positioning Parameter lists

Maximum positioning speed adjusting (Control keypad: Menu M2 G2.10.24)

Koodi

Parametri

Min

Max

P2.10.24.1

Max. speed adj.


Reference sel.

P2.10.24.2

Max. speed 1
scaling MIN

0.00

P2.10.23.3

P2.10.24.3

Max.speed 1
scaling MAX

P2.10.24.2

P2.10.24.4

Max. speed 2
scaling MIN

P2.10.24.5

Max. speed 2
scaling MAX

Yks.

Oletus

ID

1579

100.00

1582

200.00

100.00

1584

0.00

P2.10.23.5

100.00

1583

P2.10.24.4

200.00

100.00

1585

Huomautuksia
0= Not used
1= AI1, analog input 1
2= AI2, analog input 2
3= Fieldbus reference
Positioning speed group
1 scaling minimum
value
Positioning speed group
1 scaling maximum
value
Positioning speed group
2 scaling minimum
value
Positioning speed group
2 scaling maximum
value

Table 4-15. Maximum positioning speed adjusting

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

3-Speed Positioning Parameter lists

vacon 29

Positions (Control keypad: Menu M2 G2.11)


Code
P2.11.1
P2.11.2

P2.11.3

Parameter
Safety area low
limit
Safety area high
limit

Calibration
position

Min

Max

Unit

Default

P2.10.4

200

1550

P2.10.4

200

1607

P2.11.1

(Total
trip) -(End limit)
=

P2.11.1

Cust.

ID

Position 1
Position 2
Position 3
Position 4
Position 5
Position 6
Position 7
Position 8
Position 9
Position 10
Position 11
Position12
Position 13
Position 14
Position 15
Position 16
Position 17
Position 18
Position 19
Position 20
Position 21
Position 22
Position 23
Position 24
Position 25
Position 26
Position 27
Position 28
Position 29
Position 30
Position 31

P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1

= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous

X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X

P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1

Bi
t4

Bi
t3

Bi
t2

Bi
t1

Bi
t0

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1

0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1

0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1

1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1

1545

High end
limit
P2.11.4
P2.11.5
P2.11.6
P2.11.7
P2.11.8
P2.11.9
P2.11.10
P2.11.11
P2.11.12
P2.11.13
P2.11.14
P2.11.15
P2.11.16
P2.11.17
P2.11.18
P2.11.19
P2.11.20
P2.11.21
P2.11.22
P2.11.23
P2.11.24
P2.11.25
P2.11.26
P2.11.27
P2.11.28
P2.11.29
P2.11.30
P2.11.31
P2.11.32
P2.11.33
P2.11.34

Description

1514
1515
1516
1517
1518
1519
1520
1521
1522
1523
1524
1525
1526
1527
1528
1529
1530
1531
1532
1533
1534
1535
1536
1537
1538
1539
1540
1541
1542
1543
1544

Table 4-16. Positions, G2.11 and boolean truth table.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

30 vacon

3-Speed Positioning Parameter lists

4.11 Mechanical brake control (Control keypad: Menu M2 G2.12.1)


Open loop parameters
Code
P2.12.1.1
P2.12.1.2
P2.12.1.3
P2.12.1.4
P2.12.1.5
P2.12.1.6
P2.12.1.7
P2.12.1.8
P2.12.1.9
P2.12.1.11
P2.12.1.12

Parameter
Current limit
Torque limit
Freq. Limit open
Brake open delay
Freq. Limit close
Brake close delay
Brake react.
Time
DC-brake current
Start DC-brake
time
Stop DC-brake
time
Stop DC-brake
frequency

Min
0,00
0,0
0
0,00
0,01
0,00

Max
In
100
Fn
10,00
Fn
10,00

Unit
A
%
Hz
s
Hz
s

Default
0,00
0,0
0,00
0,10
1,00
0,00
0,05

Cust.

ID
1587
1588
1589
1590
1591
1592

Description

0,00

10,00

0,15 x In

1,5 x In

Varies

507

0,000

60,000

0,000

516

0 = DC-brake not in use

0,000

60,000

0,000

508

0 = DC-brake not in use

0,10

10,00

Hz

1,50

515

1594

Table 4-17. Open loop parameters

4.12 Mechanical brake control (Control keypad: Menu M2 G2.12.2)


Closed Loop parameters
Code
P2.12.2.1
P2.12.2.2
P2.12.2.3
P2.12.2.4
P2.12.2.5
P2.12.2.6
P2.12.2.7
P2.12.2.8

Parameter
Current limit
Torque limit
Freq. Limit open
Brake open delay
Freq limit close
Brake close delay
Start 0Hz time
Stop 0Hz time

Min
0
0
0
0,00
0,01
0,00
0
0

Max
In
100
Fn
10,00
Fn
10,00
2,000
2,000

Unit
A
%
Hz
s
Hz
s
s
s

Default
0,00
0
0,00
0,10
0,01
0,00
0,100
0,100

Cust.

ID
1596
1597
1598
1599
1600
1601
615
616

Description

Table 4-18. Mechanical brake control

4.13 Keypad control (Control keypad: Menu M3)


The parameters for the selection of control place and direction on the keypad are listed below. See
the Keypad control menu in the products User's Manual.
Code

Parameter

Min

Max

P3.1

Control place

R3.2

Keypad reference

Par.
2.1.1

Par. 2.1.2

P3.3

Direction (on keypad)

R3.4

Stop button

R3.5

Pulses calibrated
STOP

Unit

Default

Cust

ID

125

123

114

1610

Note
0 = I/O terminal
1 = Keypad
2 = Fieldbus

Hz
0 = Forward
1 = Reverse
0=Limited function of Stop
button
1=Stop button always
enabled

Table 4-19. Keypad control parametrs, M3

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

3-Speed Positioning Parameter lists

vacon 31

4.14 System menu (Control keypad: M6)


For parameters and functions related to the general use of the frequency converter, such as
application and language selection, customised parameter sets or information about the hardware
and software, see the products User's Manual.

4.15 Expander boards (Control keypad: Menu M7)


The M7 menu shows the expander and option boards attached to the control board and boardrelated information. For more information, see the products User's Manual.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

32 vacon

5.

Description of parameters

Description of parameters

5.1 BASIC PARAMETERS


2.1.1, 2.1.2 Minimum/maximum frequency
Defines the frequency limits of the frequency converter.
The maximum value for parameters 2.1.1 and 2.1.2 is 320 Hz.
The software will automatically check the values of parameters 2.1.14, 2.3.10 and 2.7.2

2.1.3, 2.1.4 Acceleration time 1, deceleration time 1


These limits correspond to the time required for the output frequency to
accelerate from the zero frequency to the set maximum frequency (par. 2.1.2).

2.1.5

Current limit
This parameter determines the maximum motor current from the frequency converter.
The current limit is 1.5 times the rated current (IL) by default.

2.1.6

Nominal voltage of the motor


Find this value Un on the rating plate of the motor. This parameter sets the voltage at the
field weakening point (parameter 2.6.5) to 100% x Unmotor.

2.1.7

Nominal frequency of the motor


Find this value fn on the rating plate of the motor. This parameter sets the field
weakening point (parameter 2.6.4) to the same value.

2.1.8

Nominal speed of the motor


Find this value nn on the rating plate of the motor.

2.1.9

Nominal current of the motor


Find this value In on the rating plate of the motor.

2.1.10

Motor cos phi


Find this value cos on the rating plate of the motor.

2.1.11

I/O frequency reference selection


Defines which frequency reference source is selected when controlled from the I/O
control place. Default value is 0.
0 = Analogue voltage reference from terminals 23, e.g. potentiometer
1 = Analogue current reference from terminals 45, e.g. transducer
2 = Keypad reference from the Reference Page (Group M3)
3 = Reference from the fieldbus

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

33 vacon

2.1.12

Description of parameters

Keypad frequency reference selection


Defines which frequency reference source is selected when controlled from the keypad.
Default value is 2.
0=
1=
2=
3=

2.1.13

Analogue voltage reference from terminals 23, e.g. potentiometer


Analogue current reference from terminals 45, e.g. transducer
Keypad reference from the Reference Page (Group M3)
Reference from the Fieldbus

Fieldbus frequency reference selection


Defines which frequency reference source is selected when controlled from the fieldbus.
Default value is 3.
0=
1=
2=
3=

2.1.14

Analogue voltage reference from terminals 23, e.g. potentiometer


Analogue current reference from terminals 45, e.g. transducer
Keypad reference from the Reference Page (Group M3)
Reference from the Fieldbus

Preset speed
Parameter value is automatically limited between the minimum and maximum
frequencies (par. 2.1.1, 2.1.2). Reference is activated with digital input (Default A.3).

2.1.15

Can Bus node number


Only for NXP-drive when using NCSysDrive.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

34 vacon

Description of parameters

5.2 INPUT SIGNALS


2.2.1

Start/Stop logic selection


0 DIN1: closed contact = start forward
DIN2: closed contact = start reverse

FWD

Output
frequency

Stop function
(par 2.4.7)
= coasting

REV

DIN1

DIN2

NX12K09

Figure 5- 1. Start forward/Start reverse

c
d
e

The first selected direction has the highest priority.


When the DIN1 contact opens the direction of rotation starts the change.
If Start forward (DIN1) and Start reverse (DIN2) signals are active simultaneously
the Start forward signal (DIN1) has priority.

1 DIN1: closed contact = start


DIN2: closed contact = reverse
See figure below.
FWD

Output
frequency

open contact = stop


open contact = forward

Stop function
(par 2.4.7
= coasting

REV

DIN1

DIN2

NX12K10

Figure 5- 2. Start, Stop, Reverse

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

35 vacon

Description of parameters

2 DIN1: closed contact = start


open contact = stop
DIN2: closed contact = start enabled open contact = start disabled and drive stopped
if running
3 3-wire connection (pulse control):
DIN1: closed contact = start pulse
DIN2: open contact = stop pulse
(DIN3 can be programmed for reverse command)
See figure below.

FWD

Output
frequency

Stop function
(par 2.4.7)
= coasting

If Start and Stop pulses are


simultaneous the Stop pulse
overrides the Start pulse

REV

DIN1
Start
DIN2
Stop

NX012K11

Figure 5- 3. Start pulse/ Stop pulse.

The selections 4 to 6 shall be used to exclude the possibility of an unintentional start


when, for example, power is connected, re-connected after a power failure, after a fault
reset, after the drive is stopped by Run Enable (Run Enable = False) or when the control
place is changed. The Start/Stop contact must be opened before the motor can be
started.
4 DIN1: closed contact = start forward (Rising edge required to start)
DIN2: closed contact = start reverse (Rising edge required to start)
5 DIN1: closed contact = start
open contact = stop
DIN2: closed contact = reverse
open contact = forward

(Rising edge required to start)

6 DIN1: closed contact = start


(Rising edge required to start)
open contact = stop
DIN2: closed contact = start enabled
open contact = start disabled and drive stopped if running

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

36 vacon

2.2.2

Description of parameters

Reference offset for current input


0
1

No offset
Offset 4 mA (living zero), provides supervision of zero level signal. The response to
reference fault can be programmed with parameter 2.7.1.

2.2.3
2.2.4

Reference scaling, minimum value/maximum value


Setting value limits: 0 par. 2.2.4 par. 2.2.5 par. 2.1.2. If parameter 2.2.5 = 0 scaling
is set off. The minimum and maximum frequencies are used for scaling.
Output
frequency

Output
frequency
Max freq. par 2.1.2

Max freq. par 2.1.2


par. 2.2.5

par. 2.2.4
Analogue
input [V]

Min freq. par 2.1.1


0

10

Analogue
input [V]

Min freq. par 2.1.1


0

10
NX12K13

Figure 5- 4. Left: Reference scaling;

2.2.5

Right: No scaling used (par. 2.2.5 = 0).

Reference inversion
Inverts reference signal:
Max. ref. signal = Min. set freq.
Min. ref. signal = Max. set freq.

Output
frequency
Max freq. par 2.1.2

0 No inversion
1 Reference inverted

par. 2.2.5

par. 2.2.4
Analogue
input

Min freq. par 2.1.1

Figure 5- 5. Reference invert.

max.
NX12K14

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

37 vacon

2.2.6

Reference filter time


Filters out disturbances from the
incoming analogue Uin signal.
Long filtering time makes regulation
response slower.

Description of parameters

%
Unfiltered signal
100%

Filtered signal
63%

Figure 5- 6. Reference filtering

t [s]
Par. 2.2.7
NX12K15

2.2.7

Digital inputs
The programming principle of the input/output signals in the 3-Speed Positioning
Application is different compared to the conventional method used in most of the other
Vacon NX applications. With the help of this method, you could define any of the digital
inputs to function in parameter group G2.2.7.
In the conventional programming method, Function to Terminal Programming Method
(FTT), you have a fixed input or output that you define a certain function for. The
applications mentioned above, however, use the Terminal to Function Programming
method (TTF) in which the programming process is carried out the other way round:
Functions appear as parameters which the operator defines a certain input/output for.

Defining an input for a certain function on keypad:


Connecting a certain input with a certain function (parameter) is done by giving the
parameter an appropriate value. The value is formed of the Board slot on the Vacon NX
control board (see the product User's Manual) and the respective signal
number, see below.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

38 vacon

Description of parameters

Example: You want to connect the digital input function Calibration (P2.2.7.13) to the digital input
DIA3 on the basic board OPT-A1.
First find the parameter 2.2.7.13 on the keypad. Press the Menu button right once to enter the edit
mode. On the value line, you will see the terminal type on the left (DigIN, DigOUT, An.IN, An.OUT)
and on the right, the present input/output the function is connected to (B.3, A.2 etc.), or if not
connected, a value (0.#).
When the value is blinking, hold down the Browser button up or down to find the desired board slot
and signal number. The program will scroll the board slots starting from 0 and proceeding from A
to E and the I/O numbers from 1 to 10.
Once you have set the desired value, press the Enter button once to confirm the change.

ENTER

Note: The inputs, unlike the outputs, can not be changed in RUN state

Defining unused inputs/outputs


All unused inputs and outputs must be given the board slot value 0 and the value 1 also for the
terminal number. The value 0.0 is also the default value for most of the functions. However, if you
want to use the values of a digital input signal for e.g. testing purposes only, you can set the board
slot value to 0 and the terminal number to any number between 210 to place the input to a TRUE
state. In other words, the value 1 corresponds to 'open contact' and values 2 to 10 to closed contact.
In case of analogue inputs, giving the value 1 for the terminal number corresponds to 0%, value 2
corresponds to 20% and any value between 3 and 10 corresponds to 100%.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

39 vacon

IN PUT SIGN AL

Description of parameters

APPLICATIO N
Parameter 2.2.7.1

Ex t. fa ult, cl. cont.

0 .1
Parameter 2.2.7.2

Ex t. fa ult, op. cont.

0 .1

"ADDRESS 0 .x "
Address 0.1

FALSE
Address 0.2-0.10

TRUE

Parameter 2.2.7.3

Run ena ble

0 .1
Parameter 2.2.7.4

Acc./ dec. time

N XO PTA1 , SLO T A
"Input 10" = A.1

0 .1
"Input 11" = A.2
Parameter 2.2.7.10

Preset speed

A.3

START-STOPLogic
P2.2.1

"Input 12" = A.3

Parameter 2.2.7.11

Positioning speed
groups

"Input 13" = A.4

A.4
Parameter 2.2.7.12

Positioning mode

A.5

"Input 14" = A.5

"Input 15" = A.6

Parameter 2.2.7.13

Ca libra tion/
Tea ching

A.6
N XO PTB1 , SLO T D
Parameter 2.2.7.14
"Input 40" = D.1

Position sel. Bit0

D.1
Parameter 2.2.7.15

Position sel. Bit1

Parameter 2.2.7.16

Position sel. Bit2

"Input 44" = D.5

D.5
Parameter 2.2.7.19

Ex t. bra k e ena ble

"Input 43" = D.4

D.4
Parameter 2.2.7.18

Position sel. Bit4

"Input 42" = D.3

D.3
Parameter 2.2.7.17

Position sel. Bit3

"Input 41" = D.2

D.2

0 .2

Address 0.1

TRUE

Figure 5- 7. Digital inputs, programming principle

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

40 vacon

Description of parameters

2.2.7.1 External fault, closing contact


Fault is shown and motor is stopped when the input is active.

2.2.7.2 External fault, opening contact


Fault is shown and motor is stopped when the input is not active.

2.2.7.3 Run enable


contact open
contact closed

=
=

Motor start disabled and the motor is stopped


Motor start enabled

2.2.7.4 Acc./Dec time selection


contact open
contact closed

=
=

Acceleration/deceleration time 1 selected


Acceleration/deceleration time 2 selected

2.2.7.5 Force control place to I/O terminal


contact closed: Force control place to I/O terminal

2.2.7.6 Force control place to keypad


contact closed: Force control place to keypad

2.2.7.7 Force control place to fieldbus


contact closed: Force control place to fieldbus
When the control place is forced to change the values of Start/Stop, Direction and
Reference valid in the respective control place are used (reference according to
parameters 2.1.11, 2.1.12 and 2.1.13).
Note: The value of parameter 3.1 Keypad Control Place does not change.
When DIN3 opens the control place is selected according to parameter 3.1.

2.2.7.8 Reverse
contact open
contact closed

=
=

Forward
Reverse

Reset

Can be used for reversing if


parameter 2.2.1 has value 3

2.2.7.9 Fault reset


contact closed

2.2.7.10 Manual speed (Preset speed)


contact open
contact closed

=
=

normal frequency reference


Force frequency reference to par. Value P2.1.14.

2.2.7.11 Positioning speed group selection


contact open
contact closed

=
=

Group 1. Par. P2.10.10 P2.10.12.


Group 2. Par. P2.10.14 - P2.10.16.

2.2.7.12 Positioning mode ON


contact closed

positioning mode active

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

41 vacon

2.2.7.13

Description of parameters

Calibration
contact closed

2.2.7.14

Position selection, bit 0

2.2.7.15

Position selection, bit 1

2.2.7.16

Position selection, bit 2

2.2.7.17

Position selection, bit 3

2.2.7.18

Position selection, bit 4

calibration pulse active

Select the position with a combination of digital inputs. See truth table on page 29.

2.2.7.19

Enable mechanical brake control


contact closed

2.2.7.20

Run Enable Low End

2.2.7.21

Run Enable High End

Enable external brake. Details on page 70.

Posibility to connect proximity switch directly to frequency converter. When signal goes
low drive is stopped by coast.

2.2.7.22

Reset calibration
Posibility to reset calibration from IO. Action same as parameter 2.10.19

2.2.7.23

Calibration Negative
Posibility to use negative calibration signal, used only in manual calibration.

2.2.7.24

Calibration prohibited
Posibility to prohibit incoming calibration signal. Used when car needs to be in certain
position before calibration signal can be accept.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

42 vacon

Description of parameters

5.3 OUTPUT SIGNALS


2.3.1

Analogue output function


This parameter selects the desired function for the analogue output signal.
See Table 4-7. Output signals, G2.3 on page 21.

2.3.2

Analogue output filter time


Defines the filtering time of the
analogue output signal.

%
Unfiltered signal
100%

Filtered signal
63%

t [s]

Figure 5- 8. Analogue output filtering


Par. 2.3.2

NX12K16

2.3.3

Analogue output invert


Inverts the analogue output signal:

Analogue
output
current
20 mA

Maximum output signal = Minimum set value


Minimum output signal = Maximum set value
12 mA

Param. 2.3.5
= 50%

10 mA

See parameter 2.3.5 below.

Param. 2.3.5
= 100%
4 mA
Param. 2.3.5
= 200%

Figure 5- 9. Analogue output invert

2.3.4

Selected (para. 2.3.1)


signal max. value

0 mA
0.5

1.0

NX12K17

Analogue output minimum


Defines the signal minimum to either 0 mA or 4 mA (living zero). Note the difference in
analogue output scaling in parameter 2.3.5 (Figure 5-10).
0 Set minimum value to 0 mA
1 Set minimum value to 4 mA

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

43 vacon

2.3.5

Description of parameters

Analogue output scale


Analogue
output
current

Scaling factor for analogue output.

Param. 2.3.5
= 200%

Param. 2.3.5
= 100%

20 mA

Signal
Output frequency
Freq. Reference
Motor speed
Output current
Motor torque
Motor power
Motor voltage
DC-link voltage

Max. value of the signal


Max frequency (par. 2.1.2)
Max frequency (par. 2.1.2)
Motor
nom.
speed
1xnmMotor
Motor nom. current 1xInMotor
Motor
nom.
torque
1xTnMotor
Motor nom. power 1xPnMotor
100% x Unmotor
1000 V

Table 5- 1. Analogue output scaling

2.3.6

Digital output function

2.3.7

Relay output 1 function

2.3.8

Relay output 2 function

12 mA

Param. 2.3.5
= 50%

10 mA

Par. 2.3.4 = 1
4 mA

Max. value of signal


selected by param. 2.3.1

Par. 2.3.4 = 0
0 mA
0

0.5

1.0
UD012K18

Figure 5- 10. Analogue output scaling

Setting value

Signal content

0 = Not used

1 = Ready

Out of operation
Digital output DO1 sinks the current and
programmable relay (RO1, RO2) is activated when:
The frequency converter is ready to operate

2 = Run

The frequency converter operates (motor is running)

3 = Fault

A fault trip has occurred

4 = Fault inverted

A fault trip not occurred

5 = Vacon overheat warning

The heat-sink temperature exceeds +70C

6 = External fault or warning

Fault or warning depending on par. 2.7.3


Fault or warning depending on par. 2.7.1

7 = Reference fault or warning

- if analogue reference is 420 mA and signal is <4mA

8 = Warning

Always if a warning exists

9 = Reversed

The reverse command has been selected

10 = Preset speed

The preset speed has been selected with digital input

11 = At speed

The output frequency has reached the set reference

12 = Motor regulator activated

14 = Control from I/O terminals

Overvoltage or overcurrent regulator was activated


The output frequency goes outside the set
supervision low limit/high limit (see parameters
2.3.9 and 2.3.10 below)
I/O control mode selected (in menu M3)

15= Thermistor fault/warning

Thermistor fault/warning active

13 = Output frequency supervision

16= Fieldbus DIN 1


17= Calibration OK

Calibration executed and active

18= Position reached

Actual position inside the stop hysteresis


The output frequency has reached the set maximum
positioning speed reference

19= At maximum speed

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

44 vacon

Description of parameters

20= At medium speed

The output frequency has reached the set medium


positioning speed reference

21= At creeping speed

The output frequency has reached the set creeping


positioning speed reference

22= New calibration!

Fault active. (Positioning area override)

23= End limit

Warning active. (End limit override)

24=Mechanical brake open

Mechanical brake control logic

Table 5- 2. Digital output DO1 and relay outputs RO1 and RO2.

2.3.9

Output frequency limit supervision function


0
1
2

No supervision
Low limit supervision
High limit supervision

If the output frequency goes under/over the set limit (P 2.3.10) this function generates a
warning message via the digital output DO1 and via the relay output RO1
or RO2 depending on the settings of parameters 2.3.62.3.8.

2.3.10

Output frequency limit supervision value


Selects the frequency value supervised by parameter 2.3.9.

f[Hz]

Par 2.3.9 = 2

Par 2.3.10

t
Example: 21 RO1
22 RO1
23 RO1

21 RO1
22 RO1
23 RO1

21 RO1
22 RO1
23 RO1
NX12K19

Kuva5- 11. Output frequency limit supervision

2.3.11

Analogue output 2 signal selection


Connect the AO2 signal to the analogue output of your choice with this parameter. For
more information, see Pump and fan control application manual, Chapter 2.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

45 vacon

2.3.12
2.3.13
2.3.14
2.3.15
2.3.16

Description of parameters

Analogue output 2 function


Analogue output 2 filter time
Analogue output 2 inversion
Analogue output 2 minimum
Analogue output 2 scaling
For more information of these five parameters, see the corresponding parameters for
the analogue output 2 on page 42 and 43.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

46 vacon

5.4
2.4.1
2.4.2

Description of parameters

DRIVE CONTROL
Acceleration/Deceleration ramp 1 shape
Acceleration/Deceleration ramp 2 shape
The start and end of acceleration and deceleration ramps can be smoothed with these
parameters. Setting value 0 gives a linear ramp shape which causes acceleration and
deceleration to act immediately to the changes in the reference signal.
Setting value 0.110 seconds for this parameter produces an S-shaped
acceleration/deceleration. The acceleration time is determined with parameters
2.1.3/2.1.4 (2.4.3/2.4.4).
[Hz]

2.1.3, 2.1.4
(2.4.3, 2.4.4)
2.4.1 (2.4.2)

2.4.1 (2.4.2)

[t]
UD012K20

Figure 5- 12. S-shaped acceleration/deceleration

2.4.3
2.4.4

Acceleration time 2
Deceleration time 2
These values correspond to the time required for the output frequency to accelerate
from the zero frequency to the set maximum frequency (par. 2.1.2). These parameters
give the possibility to set two different acceleration/deceleration time sets for one
application. The active set can be selected with the programmable signal DIN3 (P.
2.2.7.4).

2.4.5

Brake chopper
0
1
2
3

=
=
=
=

No brake chopper used


Brake chopper in use when running
External brake chopper
Used when stopped/running

When the frequency converter is decelerating the motor, the inertia of the motor and the
load are fed into an external brake resistor. This enables the frequency converter to
decelerate the load with a torque equal to that of acceleration (provided that the correct
brake resistor has been selected). See separate Brake resistor installation manual.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

47 vacon

2.4.6

Description of parameters

Start function
Ramp:
0

The frequency converter starts from 0 Hz and accelerates to the set reference
frequency within the set acceleration time. (Load inertia or starting friction
may cause prolonged acceleration times).

Flying start:
1
The frequency converter is able to start into a running motor by applying a
small torque to motor and searching for the frequency corresponding to the
speed the motor is running at. Searching starts from the maximum frequency
towards the actual frequency until the correct value is detected. Thereafter,
the output frequency will be increased/decreased to the set reference value
according to the set acceleration/deceleration parameters.
Use this mode if the motor is coasting when the start command is given. With
the flying start it is possible to ride through short mains voltage interruptions.

2.4.7

Stop function
Coasting:
0
The motor coasts to a halt without any control from the frequency converter,
after the Stop command.
Ramp:
1

After the Stop command, the speed of the motor is decelerated according to
the set deceleration parameters.
If the regenerated energy is high it may be necessary to use an external
braking resistor for faster deceleration.

Normal stop: Ramp/ Run Enable stop: coasting


2
After the Stop command, the speed of the motor is decelerated according to
the set deceleration parameters. However, when Run Enable is selected (e.g.
DIN3), the motor coasts to a halt without any control from the frequency
converter.
Normal stop: Coasting/ Run Enable stop: ramping
3
The motor coasts to a halt without any control from the frequency converter.
However, when Run Enable signal is selected (e.g. DIN3), the speed of the
motor is decelerated according to the set deceleration parameters. If the
regenerated energy is high it may be necessary to use an external braking
resistor for faster deceleration.

2.4.8

Flux brake
The flux braking can be set ON or OFF.
0 = Flux braking OFF
1 = Flux braking ON

2.4.9

Flux braking current


Defines the flux braking current value.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

48 vacon

Description of parameters

5.5 PROHIBIT FREQUENCIES


2.5.1, 2.5.2 Prohibit frequency area; Low limit/High limit
In some systems it may be
necessary to avoid certain
frequencies because of mechanical
resonance problems. With these
parameters it is possible to set
limits for the "skip frequency"
region.

Output
frequency [Hz]

Reference [Hz]

2.5.1

Figure 5-13. Prohibit frequency area


setting.

2.5.3

2.5.2

NX12K24

Acc/dec ramp speed scaling ratio between prohibit frequency limits


Defines the acceleration/deceleration time when the output frequency is between the
selected prohibit frequency range limits (parameters 2.5.1 and 2.5.2). The ramping
speed (selected acceleration/ deceleration time 1 or 2) is multiplied with this factor. E.g.
value 0.1 makes the acceleration time 10 times shorter than outside the prohibit
frequency range limits.
fout [Hz]

par. 2.5.3 = 0,2

Par. 2.5.2
Par. 2.5.1

par. 2.5.3 = 1,2

Figure 5- 14. Ramp speed scaling between prohibit frequencies

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

49 vacon

Description of parameters

5.6 MOTOR CONTROL


2.6.1

2.6.2

2.6.3

Motor control mode


0

Frequency control:

Speed control:

The I/O terminal and keypad references are frequency


references and the frequency converter controls the output
frequency (output frequency resolution = 0.01 Hz)

The I/O terminal and keypad references are speed references


and the frequency converter controls the motor speed
(accuracy 0,5%).
The following selections are available for Vacon NXP drives only, althou Torque control
is wisible it han not be used fro positioning.

Torque control

In torque control mode, the references are used to control


the motor torque.

Speed crtl (closed loop)

The I/O terminal and keypad references are speed


references and the frequency converter controls the motor
speed very accurately comparing the actual speed received
from the tachometer to the speed reference (accuracy
0.01%).

U/f optimisation
Automatic
torque boost

The voltage to the motor changes automatically which makes the


motor produce sufficient torque to start and run at low
frequencies. The voltage increase depends on the motor type and
power. Automatic torque boost can be used in applications where
starting torque due to starting friction is high, e.g. in conveyors.

NOTE!

In high torque - low speed applications - it is likely that the motor


will overheat. If the motor has to run a prolonged time under these
conditions, special attention must be paid to cooling the motor. Use
external cooling for the motor if the temperature tends to rise too
high.

U/f ratio selection


Linear:
0

The voltage of the motor changes linearly with the frequency in the constant
flux area from 0 Hz to the field weakening point where the nominal voltage is
supplied to the motor. Linear U/f ratio should be used in constant torque
applications.

Squared: The voltage of the motor changes following a squared curve form
1
with the frequency in the area from 0 Hz to the field weakening point where
the nominal voltage is also supplied to the motor. The motor runs under
magnetised below the field weakening point and produces less torque and
electromechanical noise. Squared U/f ratio can be used in applications
where torque demand of the load is proportional to the square of the speed,
e.g in centrifugal fans and pumps.
24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

50 vacon

Description of parameters

U[V]
U[V]

Un
Nominal
par.2.6.5
UnDefault:
voltage of the motor

Field weakening

pointweakening
Field
point

Nominal
par.2.6.5 Default:
voltage of the motor

Linear

Linear

Squared
Squared

Default:Nominal
Nominal
Default:
frequencyofofthe
the
frequency
motor
motor
f[Hz]
f[Hz]
NX12K07
NX12K07

Figure 5- 15. Linear and squared change of motor voltage

Programmable U/f curve:


2
The U/f curve can be programmed with three different points. Programmable
U/f curve can be used if the other settings do not satisfy the needs of the
application.
U[V]
Un
Par 2.6.5

Default: Nominal
voltage of the motor

Field weakening point

Par. 2.6.7
(Def. 10%)

Default: Nominal
frequency of the motor
f[Hz]

Par. 2.6.8
(Def. 1.3%)
Par. 2.6.6
(Def. 5 Hz)

Par. 2.6.4
NX12K08

Figure 5- 16. Programmable U/f curve

Linear with flux optimisation:


3
The frequency converter starts to search for the minimum motor current in
order to save energy, lower the disturbance level and the noise. This function
can be used in applications with constant motor load, such as fans, pumps etc.

2.6.4

Field weakening point


The field weakening point is the output frequency at which the output voltage reaches
the set (par. 2.6.5) maximum value.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

51 vacon

2.6.5

Description of parameters

Voltage at field weakening point


Above the frequency at the field weakening point, the output voltage remains at the set
maximum value. Below the frequency at the field weakening point, the output voltage
depends on the setting of the U/f curve parameters. See parameters 2.6.2, 2.6.3, 2.6.6
and 2.6.7.
When the parameters 2.1.6 and 2.1.7 (nominal voltage and nominal frequency of the
motor) are set, the parameters 2.6.4 and 2.6.5 are automatically given the corresponding
values. If you need different values for the field weakening point and the maximum
output voltage, change these parameters after setting the parameters 2.1.6 and 2.1.7.

2.6.6

U/f curve, middle point frequency


If the programmable U/f curve has been selected with the parameter 2.6.3 this
parameter defines the middle point frequency of the curve. See figure 5-16.

2.6.7

U/f curve, middle point voltage


If the programmable U/f curve has been selected with the parameter 2.6.3 this
parameter defines the middle point voltage of the curve. See figure 5-16.

2.6.8

Output voltage at zero frequency


If the programmable U/f curve has been selected with the parameter 2.6.3 this
parameter defines the zero frequency voltage of the curve. See figure 5-16.

2.6.9

Switching frequency
Motor noise can be minimised using a high switching frequency. Increasing the
switching frequency reduces the capacity of the frequency converter unit.
The range of this parameter depends on the size of the frequency converter:
Up to NX5 0061: 116 kHz
>NX5 0072: 110 kHz

2.6.10
2.6.11

Overvoltage controller
Undervoltage controller
These parameters allow the under-/overvoltage controllers to be switched out of
operation. This may be useful, for example, if the mains supply voltage varies more than
15% to +10% and the application will not tolerate this over-/undervoltage. In this case,
the regulator controls the output frequency taking the supply fluctuations into account.
Note: Over-/undervoltage trips may occur when controllers are switched out of
operation.
0 Controller switched off
1 Controller switched on

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

52 vacon

Description of parameters

5.7 PROTECTIONS
2.7.1

Response to the reference fault


0 = No response
1 = Warning
2 = Warning, the frequency from 10 seconds back is set as reference
3 = Warning, the Preset Frequency (Par. 2.7.2) is set as reference
4 = Fault, stop mode after fault according to parameter 2.4.7
5 = Fault, stop mode after fault always by coasting
A warning or a fault action and message is generated if the 420 mA reference signal
is used and the signal falls below 3.5 mA for 5 seconds or below 0.5 mA for 0.5 seconds.
The information can also be programmed into digital output DO1 or relay outputs RO1
and RO2.

2.7.2

4 mA Fault: preset frequency reference


If the value of parameter 2.7.1 is set to 3 and the 4 mA fault occurs then the frequency
reference to the motor is the value of this parameter.

2.7.3

Response to external fault


0
1
2
3

= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting

A warning or a fault action and message is generated from the external fault signal
in the programmable digital inputs DIN3. The information can also be programmed into
digital output DO1 and into relay outputs RO1 and RO2.

2.7.4

Input phase supervision


0
1
2
3

= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting

The input phase supervision ensures that the input phases of the frequency converter
have an approximately equal current.

2.7.5

Response to undervoltage fault


1 = Warning
2 = Fault, stop mode after fault according to parameter 2.4.7
3 = Fault, stop mode after fault always by coasting
For the undervoltage limits see the products User's Manual.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

53 vacon

2.7.6

Description of parameters

Output phase supervision


0
1
2
3

= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting

Output phase supervision of the motor ensures that the motor phases have an
approximately equal current.

2.7.7

Earth fault protection


0
1
2
3

= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting

Earth fault protection ensures that the sum of the motor phase currents is zero. The
overcurrent protection is always working and protects the frequency converter from
earth faults with high currents.
Parameters 2.7.82.7.12, Motor thermal protection:
General
The motor thermal protection is to protect the motor from overheating. The Vacon drive is capable
of supplying higher than nominal current to the motor. If the load requires this high current there is
a risk that the motor will be thermally overloaded. This is the case especially at low frequencies. At
low frequencies the cooling effect of the motor is reduced as well as its capacity. If the motor is
equipped with an external fan the load reduction at low speeds is small.
The motor thermal protection is based on a calculated model and it uses the output current of the
drive to determine the load on the motor.
The motor thermal protection can be adjusted with parameters. The thermal current IT specifies the
load current above which the motor is overloaded. This current limit is a function of the output
frequency.
The thermal stage of the motor can be monitored on the control keypad display. See the products
User's Manual.

CAUTION!

The calculated model does not protect the motor if the airflow to the
motor is reduced by blocked air intake grill.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

54 vacon

2.7.8

Description of parameters

Motor thermal protection


0
1
2
3

= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting

If tripping is selected the drive will stop and activate the fault stage.
Deactivating the protection, i.e. setting parameter to 0, will reset the thermal stage of
the motor to 0%.

2.7.9

Motor thermal protection: Motor ambient temperature factor


The factor can be set between -100.0%100.0%.

2.7.10

Motor thermal protection: Zero frequency current


The current can be set between 0150.0% x InMotor. This parameter sets the value for
thermal current at zero frequency. See figure 5-17.
The default value is set assuming that there is no external fan cooling the motor. If an
external fan is used this parameter can be set to 90% (or even higher).
Note: The value is set as a percentage of the motor name plate data, parameter 2.1.9
(Nominal current of motor), not the drive's nominal output current. The motor's nominal
current is the current that the motor can withstand in direct on-line use without being
overheated.
If you change the parameter Nominal current of motor, this parameter is automatically
restored to the default value.
Setting this parameter does not affect the maximum output current of the drive which is
determined by parameter 2.1.5 alone.
I
Current
limit,
par. 2.1.5
100%
INmotor

Overload area
IT

45%
INmotor

f
35 Hz

NX12k62

Figure 5- 17. Motor thermal current IT curve

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

55 vacon

2.7.11

Description of parameters

Motor thermal protection: Time constant


This time can be set between 1 and 200 minutes.
This is the thermal time constant of the motor. The bigger the motor, the bigger the time
constant. The time constant is the time within which the calculated thermal stage has
reached 63% of its final value.
The motor thermal time is specific to the motor design and it varies between different
motor manufacturers.
If the motor's t6time (t6 is the time in seconds the motor can safely operate at six times
the rated current) is known (given by the motor manufacturer) the time constant
parameter can be set basing on it. As a rule of thumb, the motor thermal time constant
in minutes equals to 2xt6. If the drive is in stop stage the time constant is internally
increased to three times the set parameter value. The cooling in the stop stage is based
on convection and the time constant is increased. See also figure 5-18.

2.7.12

Motor thermal protection: Motor duty cycle


Defines how much of the nominal motor load is applied.
The value can be set to 0%100%.

Motor temperature

Trip area
105%

Motor
current

Fault/warning

par. 2.7.8

I/IT

Time constant T
Motor temperature

*)

= (I/IT)2 x (1-e-t/T)

Time

*) Changes by motor size and


adjusted with parameter 2.7.11

NX12k82

Figure 5- 18. Motor temperature calculation

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

56 vacon

Description of parameters

Parameters 2.7.132.7.16, Stall protection:


General
The motor stall protection protects the motor from short time overload situations such as one
caused by a stalled shaft. The reaction time of the stall protection can be set shorter than that of
motor thermal protection. The stall state is defined with two parameters, 2.7.14 (Stall current) and
2.7.16 (Stall frequency). If the current is higher than the set limit and output frequency is lower than
the set limit, the stall state is true. There is actually no real indication of the shaft rotation. Stall
protection is a type of overcurrent protection.

2.7.13

Stall protection
0
1
2
3

= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting

Setting the parameter to 0 will deactivate the protection and reset the stall time counter.

2.7.14

Stall current limit


The current can be set to 0.06000.0
A. For a stall stage to occur, the
current must have exceeded this
limit. See figure 5-19. This value is set
in percentage of the motor's name
plate data (parameter 2.1.9). If the
para-meter 2.1.9 Nominal current of
motor is changed, this parameter is
automatically restored to the default
value.

Stall area

Par. 2.7.14

Par. 2.7.16

NX12k63

Figure 5-19. Stall characteristics settings

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

57 vacon

2.7.15

Description of parameters

Stall time
Stall time counter

This time can be set between 1.0 and


120.0s.
This is the maximum time allowed for
a stall stage. The stall time is counted
by an internal up/down counter.
If the stall time counter value goes
above this limit the protection will
cause a trip (see parameter 2.7.13).

Trip area

Par. 2.7.15
Trip/warning
par. 2.7.13

Time
Stall
No stall
NX12k64

Figure 5- 20. Stall time count

2.7.16

Maximum stall frequency


The frequency can be set between 1-fmax (par. 2.1.2).
For a stall state to occur, the output frequency must have remained below this limit.

Parameters 2.7.172.7.20, Underload protection:


General
The purpose of the motor underload protection is to ensure that there is load on the motor when the
drive is running. If the motor loses its load there might be a problem in the process, e.g. a broken
belt or a dry pump.
Motor underload protection can be adjusted by setting the underload curve with parameters 2.7.18
(Field weakening area load) and 2.7.19 (Zero frequency load), see below. The underload curve is a
squared curve set between the zero frequency and the field weakening point. The protection is not
active below 5Hz (the underload time counter is stopped).
The torque values for setting the underload curve are set in percentage which refers to the nominal
torque of the motor. The motor's name plate data, parameter motor nominal current and the drive's
nominal current ICT are used to find the scaling ratio for the internal torque value. If other than
nominal motor is used with the drive, the accuracy of the torque calculation decreases.

2.7.17

Underload protection
0
1
2
3

= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting

If tripping is set active the drive will stop and activate the fault stage.
Deactivating the protection by setting the parameter to 0 will reset the underload time
counter to zero.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

58 vacon

2.7.18

Description of parameters

Underload protection, field weakening area load


The torque limit can be set
between 10.0150.0 % x TnMotor.
This parameter gives the value for
the minimum torque allowed when
the output frequency is above the
field weakening point.
If you change the parameter 2.1.9
(Motor nominal current) this
parameter is automatically
restored to the default value.

Torque

Par. 2.7.18

Par. 2.7.19
Underload area

f
5 Hz

Fieldweakening
point par. 2.6.4

NX12k65

Figure 5-21. Setting of minimum load

2.7.19

Underload protection, zero frequency load


The torque limit can be set between 5.0150.0 % x TnMotor.
This parameter gives value for the minimum torque allowed with zero frequency.
If you change the value of parameter 2.1.9 (Motor nominal current) this parameter is
automatically restored to the default value.

2.7.20

Underload time
This time can be set between 2.0 and 600.0 s.
This is the maximum time allowed for an underload state to exist. An internal up/down
counter counts the accumulated underload time. If the underload counter value goes
above this limit the protection will cause a trip according to parameter 2.7.17). If the
drive is stopped the underload counter is reset to zero.

Figure 5- 22. Underload time counter function

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

59 vacon

2.7.21

Description of parameters

Response to thermistor fault


0
1
2
3

= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting

Setting the parameter to 0 will deactivate the protection and reset the stall time counter.

2.7.22

Response to fieldbus fault


Set here the response mode for the fieldbus fault if a fieldbus board is used. For more
information, see the respective Fieldbus Board Manual.
See parameter 2.7.21.

2.7.23

Response to slot fault


Set here the response mode for a board slot fault due to missing or broken board.
See parameter 2.7.21.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

60 vacon

Description of parameters

5.8 AUTO RESTART PARAMETERS


2.8.1

Automatic restart: Wait time


Defines the time before the frequency converter tries to automatically restart the motor
after the fault has disappeared.

2.8.2

Automatic restart: Trial time


The Automatic restart function restarts the frequency converter when the faults selected
with parameters 2.8.4 to 2.8.10 have disappeared and the waiting time has elapsed.
Wait time
Par. 2.8.1

Wait time
Par. 2.8.1

Wait time
Par. 2.8.1

Fault trigger

Motor stop signal


Restart 1

Restart 2

Motor start signal


Supervision

Trial time
Par. 2.8.2

Fault active
RESET/
Fault reset
NX12k67

Autoreset function: (Trials = 2)

Figure 5-23. Example of Automatic restart with two restarts.

Parameters 2.8.4 to 2.8.10 determine the maximum number of automatic restarts


during the trial time set by parameter 2.8.2. The time count starts from the first
autorestart. If the number of faults occurring during the trial time exceeds the values of
parameters 2.8.4 to 2.8.10, the fault state becomes active. Otherwise the fault is cleared
after the trial time has elapsed and the next fault starts the trial time count again.
If a single fault remains during the trial time, a fault state is true.

2.8.3

Automatic restart, start function


The Start function for Automatic restart is selected with this parameter. The parameter
defines the start mode:
0 = Start with ramp
1 = Flying start
2 = Start according to par. 2.4.6

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

61 vacon

2.8.4

Description of parameters

Automatic restart: Number of tries after undervoltage fault trip


This parameter determines how many automatic restarts can be made during the trial
time set by parameter 2.8.2 after an undervoltage trip.
0
>0

2.8.5

= No automatic restart after undervoltage fault trip


= Number of automatic restarts after undervoltage fault. The fault is
reset and the drive is started automatically after the DC-link voltage
has returned to the normal level.

Automatic restart: Number of tries after overvoltage trip


This parameter determines how many automatic restarts can be made during the trial
time set by parameter 2.8.2 after an overvoltage trip.
0
>0

2.8.6

= No automatic restart after overvoltage fault trip


= Number of automatic restarts after overvoltage fault. The fault is
reset and the drive is started automatically after the DC-link voltage
has returned to the normal level.

Automatic restart: Number of tries after overcurrent trip


(NOTE! IGBT temp Fault also included)
This parameter determines how many automatic restarts can be made during the trial
time set by parameter 2.8.2.
0
>0

2.8.7

= No automatic restart after overcurrent fault trip


= Number of automatic restarts after overcurrent trip, saturation trip
and IGBT temperature faults.

Automatic restart: Number of tries after reference trip


This parameter determines how many automatic restarts can be made during the trial
time set by parameter 2.8.2.
0
>0

2.8.8

= No automatic restart after reference fault trip


= Number of automatic restarts after the analogue current signal
(420 mA) has returned to the normal level (>4 mA)

Automatic restart: Number of tries after motor temperature fault trip


This parameter determines how many automatic restarts can be made during the trial
time set by parameter 2.8.2.
0
>0

2.8.9

= No automatic restart after Motor temperature fault trip


= Number of automatic restarts after the motor temperature has
returned to its normal level.

Automatic restart: Number of tries after external fault trip


This parameter determines how many automatic restarts can be made during the trial
time set by parameter 2.8.2.
0
>0

= No automatic restart after External fault trip


= Number of automatic restarts after External fault trip

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

62 vacon

Description of parameters

5.9 POSITIONING PARAMETERS


2.10.1

Reference selection
Target reference could be given in spite of control place P3.1 settings. If you want to
control frequency converter eg. via fieldbus (Start, stop, speed ref, positioning CW and so
on), it have to select with parameter P3.1 as an active control place.
0= Fixed positions 0-31, digital input combination.
1= Analog target reference; current or voltage input (P2.10.2)
2= Target reference from fieldbus
Fixed positions 0-31;
Storage location in parameter group G2.11 selected with the compination of 5 digital
inputs.
Analog target reference;
Target reference could be given eg. potentiometer, voltage or current signal. Reference
is adjustable during the positioning also. Notice analog electronics disturbances, which
could effect to positioning accuracy (1%).
Fieldbus target reference;
Target reference is written to processdata field 1, type UINT. Value is internally limited
like position parameters is group G2.11. See also chapter 3.6 Fieldbus control.

2.10.2

Analog reference selection


0=AI1 (Default: voltage signal)
1=AI2 (Default: current signal)

2.10.3

Sheet cutter function


Selection of sheet cutter function
0=Off
1=On
See details from chapter 3.5.

2.10.4

Total trip
Positioning area total lenght (Max. 60000). Unit type: ANY. Use the same units in all trip
parameters. (P2.10.4, P2.10.7, P2.10.8, P2.10.9 and all parameters in group G2.11)
Example: Total length is 2m.
2m = 200cm = 2000mm = 20000 (1/10)mm (<60000). P2.10.4=20000

Smaller units gives better resolution!


2.10.5

Total rounds corresponding to total trip


User defined encoder axis rounds per total trip.
Max. 65535. Decimals for this value is defined by parameter P2.10.6.

Note! This parameter affects essentially to positioning accuracy.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

63 vacon

Description of parameters

Total rounds calculation based on a carefully measurement of the conveyors axis


diameter:

Total Rounds =

Total Trip
* Axis Diameter

Or total rounds calculation based on a trip measurement corresponding one


conveyors axis revolution:

Total Rounds =
2.10.6

Total Trip
Lenght of the 1 revolution

Decimals for total rounds


Total rounds (P2.10.5) decimal numbers. (Max. 4)
Example: If calculated total rounds are 5.24943, choose maximum value 4, because
52494<65535. Now you reach the optimal accuracy.

2.10.7

Medium positioning speed starting point


Advance position, when moving to medium speed. (P2.10.11 or P2.10.15). Outside this
area, speed reference is high positioning speed (P2.10.10 or P2.10.14). Same units as
P2.10.4.

2.10.8

Creeping speed starting point


Advance position, when moving to creeping speed.
(P2.10.12 tai P2.10.16). Same units as P2.10.4.

2.10.9

Stop hysteresis
Stop hysteresis. Advance position, when stopping. Finally positioning accuracy is defined
with this parameter. Frequency converter keeps the conveyor inside the hysteresis as
long as the START-command is on. In other words, it fixes the positioning all the time. If
hysteresis is too small, conveyor starts to oscillate. If this happens, you could decrease
the creeping speed, tune the ramps or increase the stop hysteresis. Same units as
P2.10.4.

2.10.10

Positioning speed maximum 1

2.10.11

Positioning speed medium 1

2.10.12

Creeping speed 1
Positioning speed group 1. Positioning speed groups selected with programmable input
function P2.2.7.11.

2.10.13 End limit speed


This parameter value limits the frequency in safety area. Safety area speed limit
activates, when calibration is done.

2.10.14 Positioning speed maximum 2


2.10.15 Positioning speed medium 2
24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

64 vacon

Description of parameters

2.10.16 Creeping speed 2


Positioning speed group 2. This group is used also in automatic calibration logic.
(P2.10.15 ja P2.10.16).

2.10.17 Teaching
Teaching the positions is possible, when calibration is done. See chapter 3.4
0=Off
1=On

2.10.18

Automatic calibration function


Automatic calibration is executed in positioning mode, DIA5=1. Function activates, when
it is selected with this parameter and START-command is given. Now the car moves, as
shown in a figure 3-1.
Frequency reference comes from positioning speed group 2 (P2.10.15 ja P2.10.16).
External proximity switch is connected to digital input. See chapter 3.2.
0=Off
1=On

2.10.19

Calibration Reset
0=No action
1=Reset calibration

2.10.20

Save position?
With this parameter it is possible to save the actual position during the power off/on
situation. When powering on again, the calibration has to be done, when the position is
reached. (No calibration in sheet cut mode)

2.10.21

Automatic ramp scaling function


When switching from positioning group to other, function tries to scale frequency ramps
so, that deceleration is smoother. See figures 5-24 and 5-25.
This function works best, when the frequencies of speed groups is given in a same ratio.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

65 vacon

Description of parameters

Example: Default values of speed groups 1 and 2;

Figure 5- 24 Without scaling


2.10.22

Figure 5- 25 With scaling

Fieldbus
2.10.22.1 Statusword, bit 3
2.10.22.2 Statusword, bit 4
2.10.22.3 Statusword, bit 5
2.10.22.4 Statusword, bit 6
2.10.22.5 Statusword, bit 7
See chapter 3.6.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

66 vacon

2.10.23

Description of parameters

Multimonitor
Into the multimonitor menu you could select three monitoring values at the same time.
Values could be select from the menu M1, in addition frequency reference from panel
R3.2.
Example: You want to monitor actual position, target position and output frequency at
the same time.

Press the Menu button right once to enter Multimonitor menu. Press the Menu button
right once again. Now the value up and left starts blinking. Select the value, which you
want to monitor (Act. position=V1.16, Target pos.=V1.17 and Output freq.=V1.1) with
up/down- buttons and confirm the selection with Enter. Repeat the same to all values.

2.10.24 Maximun positioning speed adjusting


With this function you could adjust the maximum positioning speed manually.

2.10.24.1

Maximum positioning speed adjusting reference selection


0=Not used
1=AI1, adjusting from analog input 1. (Default: voltage)
2=AI2, adjusting from analog input 2. (Default: current)
3=Fieldbus. Adjusting value to processdata field 3.

2.10.24.2

Maximum positioning speed 1 adjust scaling, low limit


Percentage of parameter P2.10.10. Min=0, max=P2.10.24.3

2.10.24.3

Maximum positioning speed 1 adjust scaling, high limit


Percentage of parameter P2.10.10. Min= P2.10.24.2, max=200.00%

2.10.24.4

Maximum positioning speed 2 adjust scaling, low limit


Percentage of parameter P2.10.14. Min=0, max=P2.10.24.5

2.10.24.5

Maximum positioning speed 2 adjust scaling, high limit


Percentage of parameter P2.10.14. Min= P2.10.24.4, max=200.00%

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

67 vacon

Description of parameters

Figure 5-26. Maximum speed adjusting

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

68 vacon

Description of parameters

5.10 POSITIONS PARAMETERS


2.11.1

Safety Area Low Limit

2.11.2

Safety Area High Limit


End limit settings to both ends of the positioning area.
Limits activates after the calibration. Same units as parameter P2.10.4.
See end limits details in chapter 3.3.

2.11.3

Calibration position
Placing to safety area prohibited. Same units as parameter P2.10.4.

2.11.3-2.11.33

Positions 1-31

31 storage locations. Each one could be selected with the combination of five digital
inputs. See the truth table on page 29.
Placing to safety area is prohibited. Same units as parameter P2.10.4.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

69 vacon

5.11

Description of parameters

MECHANICAL BRAKE CONTROL


Mechanical brake control parameters are affected the mechanical brake control, the
smooth start and stop function and the safety functions.
Mechanical brake can be set to release on current, on torque, on frequency or on
external input. The closing can be performed by frequency, by external input or by run
request signal. In case of fault, the closing is done immediately without delay. In
positioning mode, brake closing is done with a certain delay, starting at the point when
actual position is inside the stop hysteresis.
Mechanical brake control is different in Open Loop and in Closed Loop motor control
mode. Parameters are divided in two different groups. Parameters in Closed Loop group
does not affect in Open Loop mode and vice versa. In figures 5-27(Open Loop) and 5-28
(Closed Loop) are a graphical presentations of the mechanical brake control logic.

f/Hz
Max Freq
Brake closed
P2.12.1.7
I/T/F- limits
P2.12.1.1-3

P2.12.1.12
StopDC freq
*)

P2.12.1.5
FreqCloseLim

Run request
signal
DC- brake
P2.12.1.9-10
Br. open delay
P2.12.1.4
Mec. delay
P2.12.1.8
Br. close delay
P2.12.1.6
BRAKE OPEN
Eg. R02

Figure 5-27. Mechanical brake control logic in Open Loop. Start signal to brake open delay, when
current, frequency and torque go above limits defined by parameters. External input must be ON if
used.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

70 vacon

Description of parameters

Figure 5-29. Mechanical brake control logic in Open Loop.

Mechanical brake control signal can be selected to any digital or relay output to control
the external mechanical brake
In the upper section is the mechanical brake opening logic. Mechanical brake needs five
signals to open and delay after that. If current or torque signal is not needed for opening
logic, those parameters can be set to zero. External brake input signal is programmable
and any digital input can be used for that purpose.
In the lower section is the mechanical brake closing logic. Brake close circuit has a
higher priority than open circuit. So if it is TRUE, then mechanical brake will close.
Brake will be closed immediately, if fault occurs.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

71 vacon

Description of parameters

2.12. BRAKE CONTROL


2.12.1 OPEN LOOP
2.12.1.1 Current limit
Parameter defines the actual current limit that has to be exceeded for a brake release. If
set to zero this condition is excluded. The value is updated always when the nominal
current of the motor P2.1.9 is set.

2.12.1.2 Torque limit


Parameter defines the actual torque limit that has to be exceeded for a brake release. If
set to zero this condition is excluded. 100 % corresponds to the calculated nominal
torque of the motor

2.12.1.3 Frequency limit opening


Parameter defines the actual frequency limit that has to be exceeded for brake release.
If set to zero this condition is excluded

2.12.1.4 Opening delay


Delay which starts when the opening conditions are TRUE.
(See parameters P2.12.1.1-3 ja P2.12.2.1-3) If set to zero this condition is excluded.

2.12.1.5 Frequency limit closing


The output frequency limit for the brake closing. The run request signal needs to be
disabled to allow the signal to affect.
In a positioning mode, actual position must be inside the stop hysteresis, before the
closing demand is fulfilled.

2.12.1.6 Closing delay


The brake closing is delayed with defined time. If set to zero there is no delay between
the brake closing condition and the actual brake closing.

2.12.1.7 Mechanical brake reaction time


Mechanical brake reaction time will hold the speed reference for a defined time. This
hold time should be set according to the mechanical brake reaction time. See figure 529.

2.12.1.9

DC-brake current
Defines the current injected into the motor during DC-braking.

2.12.1.10

DC-braking time at start


DC-brake is activated when the start command is given. This parameter defines the
time before the brake is released.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

72 vacon

Description of parameters

2.12.1.11 DC-braking time at stop


Determines if braking is ON or OFF and the braking time of the DC-brake when the
motor is stopping. The function of the DC-brake depends on the stop function,
parameter 2.4.7.
0
>0

DC-brake is not used


DC-brake is in use and its function depends on the Stop function,
P2.4.7. The DC-braking time is determined with this parameter.

Par. 2.4.7 = 0; Stop function = Coasting:


After the stop command, the motor coasts to a stop without control of the frequency
converter.
With DC-injection, the motor can be electrically stopped in the shortest possible time,
without using an optional external-braking resistor.
The braking time is scaled according to the frequency when the DC-braking starts. If the
frequency is the nominal frequency of the motor, the set value of parameter 2.12.1.11
determines the braking time. When the frequency is 10% of the nominal, the braking
time is 10% of the set value of parameter 2.12.1.11.

Figure 5- 30. DC-braking time, when stop mode 0=Coasting

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

73 vacon

Description of parameters

Par. 2.4.7 = 1; Stop function = Ramp


After the Stop command, the speed of the motor is reduced according to the set
deceleration parameters, as fast as possible, to the speed defined with parameter
2.12.1.12, where the DC-braking starts.
The braking time is defined with parameter 2.12.1.11. If high inertia exists, it is
recommended to use an external braking resistor for faster deceleration.

Figure 5-31. DC-braking time, when stop mode 1=Ramping

2.12.1.12 DC-braking frequency at stop


The output frequency which the DC-braking is applied.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

74 vacon

Description of parameters

2.12.2 CLOSED LOOP


Parameters are valid in Closed Loop motor control mode only.

2.12.2.1 Current limit


Parameter defines the actual current limit that has to be exceeded for a brake release. If
set to zero this condition is excluded. The value is updated always when the nominal
current of the motor P2.1.9 is set.

2.12.2.2 Torque limit


Parameter defines the actual torque limit that has to be exceeded for a brake release. If
set to zero this condition is excluded. 100 % corresponds to the calculated nominal
torque of the motor

2.12.2.3 Frequency limit opening


Parameter defines the actual frequency limit that has to be exceeded for brake release.
If set to zero this condition is excluded

2.12.2.4 Opening delay


Delay which starts when the opening conditions are TRUE.
(See parameters P2.12.1.1-3 ja P2.12.2.1-3) If set to zero this condition is excluded.

2.12.2.5 Frequency limit closing


The output frequency limit for the brake closing. The run request signal needs to be
disabled to allow the signal to affect.
In a positioning mode, actual position must be inside the stop hysteresis, before the
closing demand is fulfilled.

2.12.2.6 Closing delay


The brake closing is delayed with defined time. If set to zero there is no delay between
the brake closing condition and the actual brake closing.

2.12.2.7 0 Hz time at start


2.12.2.8 0 Hz time at stop
Zero hertz time during start and stop. Motor can be magnetised and torque generated
during that time. In closed loop mode, this time should be used. Smooth start time (par
2.12.2.10) will commence straight after zero hertz time. The mechanical brake should be
set to release when this change takes place.

2.12.2.9 Smooth start time


The smooth start time function is used in closed loop mode. It cannot be used in open
loop. After the start command has been given the drive is rotating the motor shaft with a
very low frequency (par 2.12.2.11) to overcome the static friction.
Smooth start time will commence straight after zero hertz time (par 2.12.2.8). The
mechanical brake should be set to release when this change takes place. This is
achieved through setting the same value for the frequency limit (par 2.3.2.3) and the
smooth start frequency (par 2.12.2.11).
Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

75 vacon

Description of parameters

2.12.2.10 Smooth start frequency


Smooth start frequency is a reference frequency that is used with the smooth start time
operation. Value should be set very low.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

76 vacon

5.12 KEYPAD CONTROL PARAMETERS


3.1

Control Place
The active control place can be changed with this parameter. For more information, see
the products User's Manual.
Pushing the Start button for 3 seconds selects the control keypad as the active control
place and copies the Run status information (Run/Stop, direction and reference).

3.2

Keypad Reference
The frequency reference can be adjusted from the keypad with this parameter.
The output frequency can be copied as the keypad reference by pushing the Stop button
for 3 seconds when you are on any of the pages of menu M3. For more information, see
the products User's Manual.

3.3

Keypad Direction
0

Forward: The rotation of the motor is forward, when the keypad is the active
control place.

Reverse: The rotation of the motor is reversed, when the keypad is the active
control place.

For more information, see the products User's Manual.

3.4

Stop button activated


If you wish to make the Stop button a "hotspot" which always stops the drive regardless
of the selected control place, give this parameter the value 1.
See also parameter 3.1.

3.5

Pulses calibrated STOP


When calibration is made drive is possible to stop in spite of run command.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

77 vacon

6.

Control signal logic in 3-Speed Positioning application

Control signal logic in 3-Speed Positioning application

Relay output
DIN5 x
DIN3 x

Positioning mode on/off

&
Calibration OK

Preset speed
3.2 Keypad reference
Fieldbus reference

2.1.11 End limit


override

2.1.11 I/O reference


2.1.12 Keypad ctrl ref.
2.1.13 FB ctrl. reference

Calibration OK
P2.10.18 Autom.calib.
in action

3.1 Control place


AI1

&

Internal frequency
reference

2.1.14 Manual speed

2.10.13 End
limit speed
Speed group1
Speed group2
P2.10.10-16 1

DIN4 x

Autom. calib.
frequencies

Keypad

Positioning speed group selection

Start/Stop- buttons
DIN1 x
DIN2 x

Forward
Reverse

Programmable
Start/Stop and
reverse logic

Start/Stop

Internal Start/Stop

Start/Stop from
fieldbus

3.3 Keypad direction


Direction from FB

Reset-button

Reverse

P2.10.18 Autom.Calib.
ON
Internal reverse

Pos.mode, Calib. NOT OK


Pos.mode, Calib. OK

DIN6 x

Calibration, teaching

Automatic calibration
reverse logic
Positioning internal
reverse logic

DIN# x

Fault reset input

Internal fault reset


>=

Figure 6-1. Control signal logic with digital inputs default values

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

78 vacon

7.

Faults and fault codes

Faults and fault codes

When a fault is detected by the frequency converter control electronics, the drive is stopped and the
symbol F together with the ordinal number of the fault, the fault code and a short fault description
appear on the display. The fault can be reset with the Reset button on the control keypad or via the
I/O terminal. The faults are stored in the Fault History menu, which can be browsed. The different
fault codes you will find in the table below.
Shadowed rows are the A- faults (alarms) and black rows are F- faults (fault). Texts on the white
base could be both A- and F- faults.
The fault codes and their possible causes are presented in the table below.
Fault
code
1

Fault

Possible cause

Action

Overcurrent

Check loading.
Check motor.
Check cables.

Overvoltage

Earth fault

Charging
switch

6
7

Emergency
stop
Saturation trip

Frequency converter has detected too


high a current (>4*In) in the motor cable:
sudden heavy load increase
short circuit in motor cables
-- unsuitable motor
The DC-link voltage has exceeded the
limits.
too short a deceleration time
high overvoltage spikes in utility
Current measurement has detected that
the sum of motor phase current is not
zero.
insulation failure in cables or motor
The charging switch is open, when the
START command has been given.
faulty operation
component failure
Stop signal has been given from the
option board.
Defective component

Unknown fault

The frequency converter troubleshooting


system is unable to locate the fault.

Undervoltage

DC-link voltage is under the voltage limits


defined in Table 4-2 of the Vacon NX
User's Manual.
Most probable causes:
too low a supply voltage
frequency converter internal fault

Reset the fault and restart.


Should the fault re-occur, contact the
distributor near to you.
In case of temporary supply voltage
break reset the fault and restart the
frequency converter. Check the supply
voltage. If it is adequate, an internal
failure has occurred.
Contact the distributor near to you.

10

Input line
supervision
Output phase
supervision

Input line phase is missing.

Check supply voltage and cable.

Current measurement has detected that


there is no current in one motor phase.

Check motor cable and motor.

11

Make the deceleration time longer. Use


brake chopper or brake resistor
(available as options)
Check motor cables and motor.

Reset the fault and restart.


Should the fault re-occur, contact the
distributor near to you.

Cannot be reset from the keypad.


Switch off power. If this does not help
contact the distributor near to you.

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

79 vacon

Faults and fault codes

12

Brake chopper
supervision

no brake resistor installed


brake resistor is broken
brake chopper failure

13

Frequency
converter
undertemperature
Frequency
converter overtemperature

Heatsink temperature is under 10C

15
16

Motor stalled
Motor overtemperature

17

Motor
underload
EEPROM
checksum fault

Motor stall protection has tripped.


Motor overheating has been detected by
frequency converter motor temperature
model. Motor is overloaded.
Motor underload protection has tripped.

14

22
23

Heatsink temperature is over 90C.


Overtemperature warning is issued when
the heatsink temperature exceeds 85C.

parameter save fault


faulty operation
component failure
Changes may have occurred in the
different counter data due to mains
interruption
faulty operation
component failure

Check brake resistor.


If the resistor is ok, the chopper is
faulty. Contact the distributor near to
you.

Check the correct amount and flow of


cooling air.
Check the heatsink for dust.
Check the ambient temperature.
Make sure that the switching frequency
is not too high in relation to ambient
temperature and motor load.
Check motor.
Decrease the motor load.
If no motor overload exists, check the
temperature model parameters.

24

Changed data
warning

25

Microprocessor
watchdog fault

29

Thermistor
fault

Thermistor is broken.

Reset the fault and restart.


Should the fault re-occur, contact the
distributor near to you.

32

Fan cooling

Contact the distributor near to you.

34
36

CAN bus
communication
Control unit

Cooling fan of the frequency converter


does not start, when ON command is
given
Sent message not acknowledged.

37

Device change

38

Device added

39

Device removed

40

Device
unknown

NXS Control Unit can not control NXP


Power Unit and vice versa
Option board changed.
Different power rating of drive.
Option board added.
Drive of different power rating added.
Option board removed.
Drive removed.
Unknown option board or drive.

Reset the fault and restart.


Should the fault re-occur, contact the
distributor near to you.

Ensure that there is another device on


the bus with the same configuration.
Change the control unit.
Reset
Note: No fault time data record!
Reset
Note: No fault time data record!
Reset
Note: No fault time data record!

Contact the distributor near to you.

24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com

80 vacon

Faults and fault codes

41

IGBT temperature

42

Brake resistor
overtemperature

43

Encoder fault

50

Analogue input
Iin < 4mA
(selected signal
range 4 to 20
mA)

51
52

External fault
Keypad
communication
fault
Fieldbus
communication
fault

Digital input fault.


The connection between the control
keypad and the frequency converter is
broken.
The connection from the fieldbus to the
frequency converter is broken.

54

SPI communication fault

The connection between the component


board and the control board is broken.

Check board and slot.


Contact the nearest Vacon distributor.

55
56

New calibration
End limits

Positioning area override


End limit override

Make new calibration


Stop the motor and restart to opposite
direction (Starting to same direction
prohibited.)

53

IGBT Inverter Bridge overtemperature


protection has detected too high a short
term overload current
Too powerful braking.

Note the exceptional Fault data record.


Additional codes:
1 = Encoder 1 channel A is missing
2 = Encoder 1 channel B is missing
3 = Both encoder 1 channels are missing
4 = Encoder reversed
Current at the analogue input is < 4mA.
control cable is broken or loose
signal source has failed

Check loading.
Check motor size.
Set the deceleration time longer.
Use external brake resistor.

Check encoder channel connections.


Check the encoder board.

Check the current loop circuitry.

Check keypad connection and possible


keypad cable.
Check installation.
If installation is correct contact the
nearest Vacon distributor.

Table 7- 1. Fault codes

Tel. +358 (0)201 2121 Fax +358 (0)201 212 205

81 vacon

Vaasa
Vacon Plc (Head office and production)
Runsorintie 7
65380 Vaasa
firstname.lastname@vacon.com
telephone: +358 (0)201 2121
fax: +358 (0)201 212 205

Faults and fault codes

Helsinki
Vacon Plc
yritie 12
01510 Vantaa
telephone: +358 (0)201 212 600
fax: +358 (0)201 212 699

Vacon Traction Oy
Vehnmyllynkatu 18
33700 Tampere
telephone: +358 (0)201 2121
fax: +358 (0)201 212 710

Tampere
Vacon Plc
Vehnmyllynkatu 18
33700 Tampere
telephone: +358 (0)201 2121
fax: +358 (0)201 212 750

sales companies and representative offices:


Austria
Vacon AT Antriebssysteme GmbH
Aumhlweg 21
2544 Leobersdorf
telephone: +43 2256 651 66
fax: +43 2256 651 66 66

Italy
Vacon S.p.A.
Via F.lli Guerra, 35
42100 Reggio Emilia
telephone: +39 0522 276811
fax: +39 0522 276890

Belgium
Vacon Benelux NV/SA
Interleuvenlaan 62
3001 Heverlee (Leuven)
telephone: +32 (0)16 394 825
fax: +32 (0)16 394 827

The Netherlands
Vacon Benelux BV
Weide 40
4206 CJ Gorinchem
telephone: +31 (0)183 642 970
fax: +31 (0)183 642 971

France
Vacon France s.a.s.
1 Rue Jacquard BP72
91280 Saint Pierre du Perray CDIS
telephone: +33 (0)1 69 89 60 30
fax: +33 (0)1 69 89 60 40

Norway
Vacon AS
Langgata 2
3080 Holmestrand
telephone: +47 330 96120
fax: +47 330 96130

Germany
Vacon GmbH
Gladbecker Strasse 425
45329 Essen
telephone: +49 (0)201 806 700
fax: +49 (0)201 806 7099

PR China
Vacon Suzhou Drives Co. Ltd.
Blk 11A
428 Xinglong Street
Suchun Industrial Square
Suzhou 215126
telephone: +86 512 6283 6630
fax: +86 512 6283 6618

Great Britain
Vacon Drives (UK) Ltd.
18, Maizefield
Hinckley Fields Industrial Estate
Hinckley
LE10 1YF Leicestershire
telephone: +44 (0)1455 611 515
fax: +44 (0)1455 611 517

Vacon Suzhou Drives Co. Ltd.


Beijing Office
A205, Grand Pacific Garden Mansion
8A Guanhua Road
Beijing 100026
telephone: +86 10 6581 3734
fax: +86 10 6581 3754

Russia
ZAO Vacon Drives
Bolshaja Jakimanka 31,
stroenie 18
109180 Moscow
telephone: +7 (095) 974 14 47
fax: +7 (095) 974 15 54
ZAO Vacon Drives
2ya Sovetskaya 7, office 210A
191036 St. Petersburg
telephone: +7 (812) 332 1114
fax: +7 (812) 279 9053
Singapore
Vacon Plc
Singapore Representative Office
102F Pasir Panjang Road
#02-06 Citilink Warehouse Complex
Singapore 118530
telephone: +65 6278 8533
fax: +65 6278 1066
Spain
Vacon Drives Ibrica S.A.
Miquel Servet, 2. P.I. Bufalvent
08243 Manresa
telephone: +34 93 877 45 06
fax: +34 93 877 00 09
Sweden
Vacon AB
Torget 1
172 67 Sundbyberg
telephone: +46 (0)8 293 055
fax: +46 (0)8 290 755

24-hour
+358 (0)40 837 1150 Email: vacon@vacon.com
Vacon support
distributor:

You might also like