Professional Documents
Culture Documents
nx frequency converters
2 vacon
General
GENERAL ......................................................................................................................................... 3
1.1
1.2
2.
CONTROL I/O.................................................................................................................................... 6
2.1
3.
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
5.10
5.11
6.
7.
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
4.13
4.14
4.15
4.16
5.
COMMISSIONING ............................................................................................................................... 8
3.1
3.2
3.3
3.4
3.5
3.6
4.
General
vacon 3
3-Speed Positioning
1.
General
Frequency converter works as a positioning controller with the help of incremental encoder and
target reference. Encoder board OPT-A4/A5 as an option is necessary. Encoder could be installed on
a motor shaft or on a conveyors axis behind the gear (NXS). Encoder information is used both
positioning control and Closed Loop motor control (NXP). If Closed Loop is in use, then the encoder
must be on the motor shaft.
Digital inputs and outputs are programmable.
Additional functions:
Positioning is based on 32 programmable targets, which are saved to parameter group 2.11.
Active target could be select with the combination of five digital inputs. (Optional I/O-expander
board, OPT-B1.)
2)
Analog target reference; current or voltage input. Using this method, notice the influences of
analog electronics disturbances (1%).
3)
Target reference from fieldbus. Expander board should be selected from the OPT-C-serie
depending on the fieldbus type.
Positioning accuracy depends on the units in use and the positioning length.
4 vacon
General
SLOT
A
OPT-A1*
OPT-A2*
OPT-A4/A5
OPT-B1
--
OPT-A1*
OPT-A2*
OPT-A4/A5
--
OPT-C2/
OPT-C3/
OPT-C7
OPT-A1*
OPT-A2*
OPT-A4/A5
--
--
Table 1-1. I/O-expander boards in different function modes, using default slots
SLOT
Board type
OPT-A1
OPT-A2
DI
DO
AI
mA/V
/+V
AO
mA/V
A B C D E
RO NO/NC
+10V
Ref.
+24V/
ext+2
4V
DI/Encoder (1024V)
Out+15/2
4V
DI/Encoder
(RS422)
Out+5/ 15V
OPT-A4
OPT-A5
OPT-B1
I/O- Signals
3+1
3+1
X
OPT-C2
OPT-C3
OPT-C7
We are developing new boards all the time. If you cant find the suitable board of this collection,
check the board development status from our salesmen.
General
vacon 5
Speed [Hz]
Speed- HI1
P2.10.10
Speed MED1
P2.10.11
Selection DIN
Pos. speed groups 1/2
STOP HYSTERES
P2.10.9
Speed CREEP1
P2.10.12
Speed- HI2
P2.10.14
Speed MED2
P2.10.15
Speed CREEP2
P2.10.16
Trip [ANY]
Med. speed
P2.10.7
Creep speed
P2.10.8
Positioning uses three different speed. When approaching the target, speed is decelerated with
three different phases. Speeds, hysteresis and ramps should be chosen by tests. In addition, the
application has so called automatic ramp scaling function (P2.10.21), which makes the positioning
quality better (See page 67). There are also two different speed groups, for example positioning
with or without the load. Maximum positioning speed is adjustable. This function is selected with
parameter P2.10.24.1. (See page 69)
6 vacon
2.
Control I/O
Control I/O
OPT-A1
1
2
READY
mA
Terminal
+10Vref
AI1+
Signal
Reference output
Analogue input, voltage range
010V DC
Description
Voltage for potentiometer, etc.
Voltage input frequency reference
3
4
5
AI1AI2+
AI2-
I/O Ground
Analogue input, current range
020mA
6
7
8
+24V
GND
DIN1
DIN2
10
DIN3
11
CMA
12
13
14
+24V
GND
DIN4
15
DIN5
16
17
18
19
20
DIN6
CMB
AO1+
AO1DO1
OPT-A2
RUN
21
22
23
RO1
RO1
RO1
Relay output 1
CALIBRATION OK
Programmable
24
25
26
RO2
RO2
RO2
Relay output 2
EXTERNAL BRAKE CTRL
Programmable
Jumper block X 3 :
CM A a nd CM B grounding
CMB connected to GN D
CMA connected to GN D
CMB isolated from GN D
CMA isolated from GN D
CMB and CMA
internally connected together,
isolated from GN D
= Factory default
Control I/O
vacon 7
Parameter
P2.2.1
Default
Fixed
Fixed
DIA3
DIA4
DIA5
DIA6
DO1
OPT-A2
RO1
RO2
OPT-B1
DIB1
DIB2
DIB3
DIB4
DIB5
P2.2.7.10
P2.2.7.11
P2.2.7.12
P2.2.7.13
P2.3.6
A.3
A.4
A.5
A.6
1
Function
Start forward, positioning
Start reverse, positioning
Preset speed
Positioning speed 1/2
Positioning mode
Calibration, teaching
Ready
P2.3.7
P2.3.8
17
24
Calibration OK
Ext. brake control
P2.2.7.14
P2.2.7.15
P2.2.7.16
P2.2.7.17
P2.2.7.18
D.1
D.2
D.3
D.4
D.5
8 vacon
3.
Commissioning
Commissioning
Download the application with NCLoad, use replace all function. Select the panel language on
page S6.1. Available languages are English and Finnish.
Option board parameters are in menu M7. (See the corresponding manual)
P2.10.1; Target reference selection. Target reference could be given in spite of control
place P3.1 settings. If you want to control frequency converter eg. via fieldbus
(Start, stop, speed ref, positioning CW and so on), it must be selected with
parameter P3.1 as an active control place.
0= Fixed positions 0-31, combination of 5 digital inputs.
1= Analog target reference; voltage or current input (P2.10.2)
2= Target reference from fieldbus
Fixed positions 0-31;
Storage location in parameter group G2.11 selected with the combination of 5 digital
inputs.
Analog target reference;
Target reference could be given eg. potentiometer, voltage or current signal.
Reference is adjustable during the positioning also. Notice analog electronics
disturbances, which could effect to positioning accuracy (1%).
P2.10.4; Total trip (Max. 60000). Unit type: ANY. Total length of the positioning area. Use the
same units in all trip parameters. (P2.10.4, P2.10.7, P2.10.8, P2.10.9 and all parameters in group
G2.11)
Commissioning
vacon 9
Total Rounds =
Total Trip
* Axis Diameter
Total Rounds =
Total Trip
Lenght of the 1 revolution
P2.10.7; Medium speed position. Advance position, when moving to medium speed.
(P2.10.11 or P2.10.15). Outside this area, speed reference is high positioning
speed (P2.10.10 or P2.10.14). Same units as P2.10.4.
P2.10.8; Creep speed positioning. Advance position, when moving to creeping speed.
(P2.10.12 tai P2.10.16). Same units as P2.10.4.
P2.10.9; Stop hysteresis. Advance position, when stopping. Finally positioning accuracy is
defined with this parameter. Frequency converter keeps the conveyor inside the hysteresis as
long as the START-command is on. In other words, it repairs the positioning all the time. If
hysteresis is too small, conveyor starts to oscillate. If this happens, you could decrease the
creeping speed, tune the ramps or increase the stop hysteresis. Same units as P2.10.4.
P2.11.1; Safety area Low. End limit area settings to positioning areas beginning.
Same units as P2.10.4.
P2.11.2;Safety area High. End limit area setting to positioning area end.
Same units as P2.10.4.
10 vacon
Commissioning
3.2 Calibration
Trip counter must be calibrate always, when frequency converter is switched on, driving outside the
positioning area (=Fault) or calibration is reset by parameter P2.10.19 (value=1). Safety area is
activated, when calibration is done. (See chapter 3.3) Calibration could execute either manually or
automatically. The meaning of calibration is to set the known position to trip counter. Calibration
position is defined with parameter P2.11.3 or if using fieldbus, the calibration position is given to
processdata input field 4.
Calibration function mode is selected by parameter P2.10.18 AutoCalibration: Off/On;
Off= Manual calibration, see chapters 3.2.1 and 3.2.2
On= Automatic calibration, see chapter 3.2.3 and 3.2.4
NOTE! When doing calibration, all digital inputs must be set to zero!
In sheet cutter mode, you dont have to make calibration. Also safety area function is disabled!
3.2.1
Manual calibration is executed in manual mode, DIA5=0. Conveyor is manually driven to position
corresponding to the parameter P2.11.3, then stop and confirm the calibration with DIA6. Now the
trip caunters value is same as parameter P2.11.3 and safety limits will be activated.
You could facilitate the manual calibration using preset speed defined with parameter P2.1.14,
activated with DIA3.
3.2.2
Manual calibration is executed in manual mode, processdata in 2, bit 1=0. Conveyor is driven to
position corresponding to the calibration position written to processdata in 4. Then stop and confirm
the calibration with processdata in 2, bit 0=1. Now the trip counters value is same as value in
processdata in 4 and safety limits will be activated. Note that the active target (V1.17) is not updated
until the next start-command.
3.2.3
3.2.4
1)
2)
3)
4)
Commissioning
vacon 11
Note: When the proximity switch is connected to PLC, then the status of the proximty switch must
be forwarded by the PLC to the frequency converter process data in 2, PDIN2, Bit0 (Calibration)
5) When the sequency is ready, (motor is running on zero frequency) give stop-command.
6) Now the trip counters value is same as value in P2.11.3 and safety limits will be activated.
Three steps of automatic calibration:
Step 1)
Step 2)
Proximty switch recognizes the car, DIA6=01 (PDIN2, Bit 0=1). Change of
direction, and speed is decreased to creeping speed reference defined by parameter
P2.10.16.
Step 3)
The car moves away from proximity switch target area, DIB6=10, (PDIN2, Bit
0=0) and the conveyor stops. Now the calibration is executed automatically, if using
I/O-control. On fieldbus control, the drive remains run-state, until the stop-command
is given. After that, the calibration must be confirmed using processdata in 2, bit 3
(Rising edge).
Now the trip counters value is same as parameter P2.11.3 and safety limits will
activate.
12 vacon
Commissioning
P2.11.1
P2.11.2
Reverse
1)
Safetyarea
Safetyarea
DIA6
Change of direction
P2.11.2
Safetyarea
2)
DIA6
P2.11.1
P2.11.2
STOP&Calibration
3)
Safetyarea
Safetyarea
DIA6
NOTE! Proximity switch must install so, that the car dont fit totally to the safety area, outside
the proximity switch target area!
Commissioning
vacon 13
Alarm:"End limits"
Alarm:"End limits"
Fault:"New Calib."
Fault:"New Calib."
POSITIONING AREA
End limit speed
P2.10.13
End limit
P2.11.2
14 vacon
Commissioning
3.4 Teaching
Teaching is possible after the calibration. Teaching mode could be activated with parameter
P2.10.17. Conveyor is driven to the wanted position and receiptioned by digital input DIA 6. Position
is stored to place in group G2.11, which is selected with the combination of digital inputs.
START-->
Reset tripcounter
START-->
Reset tripcounter
Time
vacon 15
Application processdata.
Masterslave
Field
Processdata 1
Signal
Target reference
Type
UINT
Processdata 2
INT
Processdata 3
INT
Description
0-60000. Internally limited.(Same as
parameters in group G2.11)
Updating always on START-command.
Digital input simulation from fieldbus:
B0=Calibration, teaching.
B1=Positioning mode OFF/ON
B2=Positioning speed groups 1/2
B3=Not used
B4=Not used
B5=Reset Calibration
B6=Calibration prohibited
Max. speed adjusting from fieldbus. Scaling
limits P2.10.24.2 P2.10.24.5.
NOTE! When using positioning CW, control place must be on fieldbus (P3.1).
Slavemaster
Field
Processdata 3
Signal
Positioning status word.
Type
INT
Description
ID
B0= Calibration OK,
B1= Position reached
B2= At positioning speed max.
B3= Programmable digital input.
B4= Programmable digital input.
B5= Programmable digital input.
B6= Programmable digital input.
B7= Programmable digital input.
B8= Positioning mode OFF/ON
B9= Calibration input
B10= Not used
B11= Warning Low End
B12= Warning High End
B13= Out of Area
B14= RunEnable Low End
B15= RunEnable High End
16 vacon
4.
On the next pages you will find the lists of parameters within the respective parameter groups. The
parameter descriptions are given on pages 32-77.
Column explanations:
Code
Parameter
Min
Max
Unit
Default
Cust
ID
= Location indication on the keypad; Shows the operator the present parameter
number
= Name of parameter
= Minimum value of parameter
= Maximum value of parameter
= Unit of parameter value; Given if available
= Value preset by factory
= Customers own setting
= ID number of the parameter (used with PC tools)
= In parameter row: Use TTF method to program these parameters.
= On parameter code: Parameter value can only be changed after the frequency
converter has been stopped.
Parameter
Unit
ID
Description
V1.1
V1.2
V1.3
V1.4
V1.5
V1.6
V1.7
V1.8
V1.9
V1.10
V1.11
V1.12
V1.13
V1.14
V1.15
V1.16
V1.17
V1.18
V1.19
Output frequency
Frequencyreference
Motor speed
Motor current
Motor torque
Motor power
Motor voltage
DC link voltage
Unit temperature
Voltage input
Current input
DIN1, DIN2, DIN3
DIN4, DIN5, DIN6
DO1, RO1, RO2
Analogue Iout
Actual position
Target position
Total rounds
Decimal rounds
FB Positioning
Control Word
FB Positioning
Status Word
Status Word
Current Unfilteres
Torque Unfiltered
FreqRampOut
DC Voltage
Unfiltered
Hz
Hz
rpm
A
%
%
V
V
C
V
mA
1
25
2
3
4
5
6
7
8
13
14
15
16
17
26
1551
1553
1580
1581
V1.20
V1.21
V1.22
V1.23
V1.24
V1.25
V1.26
mA
--r
Dec
Heatsink temperature
AI1
AI2
Digital input statuses
Digital input statuses
Digital and relay output statuses
AO1
Actual position in real units
Target position in real units
Enc. rounds
1 full round=65535
1700
1701
1702
1113
1081
1129
1082
vacon 17
15
Description
Value = 0
No meaning
Manual mode
Positioning speed group 1
Not used
Not used
No meaning
Calibration permitted
Not used
Not used
Not used
Value = 1
FB Calibration input
Positioning mode
Positioning speed group 2
Not used
Not used
FB Reset calibration
Calibration prohibited
Not used
Not used
Not used
V1.21
Description
Value = 0
Not calibrated
Not in position reference
Positioning low speed
Value = 1
Calibration OK
Position reached
Positioning Max Speed
Programmable digital input. P2.10.22.1
Programmable digital input. P2.10.22.2
Programmable digital input. P2.10.22.3
Programmable digital input. P2.10.22.4
Programmable digital input. P2.10.22.5
Manual mode
Positioning mode
Calibration input FALSE
Calibration input TRUE
Not Used
Not Used
No Warning
Warning Low End
No Warning
Warning High End
In side of area
Out of area fault
Run Disable Low End
Run Enable Low End
Run Disable High End
Run Enable High End
V1.22
Status Word
NOTE: Content of internal status word may vary with different versions
Bit
0
1
2
3
4
5
6
15
Description
Value = 0
Run Disabled
No Warning
FC Stopped
No Fault
No Run Request
Calibration permitted
Brake closed
Not used
Not used
Value = 1
Run Enabled
Warning
FC Running
Fault active
Run Request
Calibration prohibited
Brake opened
Not used
Not used
18 vacon
Parameter
Min frequency
Min
0,00
Max
Par. 2.1.2
Unit
Hz
Default
0,00
Cust
ID
101
P2.1.2
Max frequency
Par. 2.1.1
320,00
Hz
50,00
102
P2.1.3
P2.1.4
Acceleration time 1
Deceleration time 1
0,1
0,1
3000,0
3000,0
s
s
3,0
3,0
103
104
P2.1.5
Current limit
0,1 x IL
2,5 x IL
1,5 x IL
107
P2.1.6
Nominal voltage of
the motor
180
690
NX2: 230V
NX5: 400V
NX6: 690V
110
P2.1.7
Nominal frequency
of the motor
30,00
320,00
Hz
50,00
111
P2.1.8
Nominal speed of
the motor
300
20 000
rpm
1440
112
P2.1.9
Nominal current of
the motor
1 x IL
2,5 x IL
IL
113
2.1.10
Motor cos
0,30
1,00
0,85
120
2.1.11
I/O reference
117
2.1.12
Keypad control
reference
121
2.1.13
Fieldbus control
reference
122
2.1.14
Preset speed
0,00
Par. 2.1.2
10,00
105
Hz
Note
NOTE: If fmax > than the
motor synchronous speed,
check suitability for motor
and drive system
vacon 19
Parameter
Min
Max
Unit
Default
Cust
ID
P2.2.1
Start/Stop logic
300
P2.2.2
Current reference
offset
302
P2.2.3
Reference scaling
minimum value
0,00
par. 2.2.5
Hz
0,00
303
P2.2.4
Reference scaling
maximum value
0,00
320,00
Hz
0,00
304
P2.2.5
Reference inversion
305
P2.2.6
0,00
10,00
0,10
306
Note
DIN1
0
1
2
3
4
5
6
Start fwd
Start/Stop
Start/Stop
Start pulse
Fwd*
Start*/Stop
Start*/Stop
DIN2
Start rvs
Rvs/Fwd
Run enable
Stop pulse
Rvs*
Rvs/Fwd
Run enable
0=No offset
1=420 mA
Selects the frequency that
corresponds to the min.
reference signal
0,00 = No scaling
Selects the frequency that
corresponds to the max.
reference signal
0,00 = No scaling
0 = Not inverted
1 = Inverted
0 = No filtering
20 vacon
4.3.1
Parameter
Ext. fault
Closing cont.
Ext. fault
Opening cont.
Run enable
Acc./Dec
Time selection
Force control
place to I/O
Force control
place to keypad
Force control
place to fieldbus
Reverse (if par.
2.2.1=3)
Fault reset
Manual speed
(Preset speed)
Positioning speed
group sel.
Positioning mode
Calibration,
teaching
Select position,
Bit 0, LSB
Select position,
Bit 1
Select position,
Bit 2
Select position,
Bit 3
Select position,
Bit 4, MSB
Ext.Brake enable
Run Enable Low
End
Run Enable High
End
Reset Calibration
Calibration
Negative
Calibration
Prohibited
Reset Encoder
Min
Max
Unit
Init.
Cust.
ID
0.1
E.10
0.1
1554
0.1
E.10
0.1
1555
0.1
E.10
0.1
1556
0.1
E.10
0.1
1557
0.1
E.10
0.1
1558
0.1
E.10
0.1
1559
0.1
E.10
0.1
1560
0.1
E.10
0.1
1561
0.1
E.10
0.1
1565
0.1
E.10
A.3
1562
0.1
E.10
A.4
1563
0.1
E.10
A.5
1564
0.1
E.10
A.6
1566
0.1
E.10
D.1
1567
0.1
E.10
D.2
1568
0.1
E.10
D.3
1569
0.1
E.10
D.4
1570
0.1
E.10
D.5
1571
0.1
E.10
0.2
1605
0.1
E.10
0.2
1609
0.1
E.10
0.2
1608
0.1
E.10
0.1
1611
0.1
E.10
0.2
1612
0.1
E.10
0.1
1613
0.1
E.10
0.1
1614
vacon 21
Parameter
Min
Max
P2.3.1
Analogue output
function
0,00
10,00
P2.3.2
P2.3.3
P2.3.4
P2.3.5
P2.3.6
P2.3.7
P2.3.8
Analogue output
filter time
Analogue output
inversion
Analogue output
minimum
Analogue output
scale
Digital output 1
function
Relay output 1
function
Relay output 2
function
Unit
Default
Cust
ID
307
1,00
308
309
310
10
1000
100
311
Note
0=Not used
1=Output freq. (0fmax)
2=Freq. reference (0fmax)
3=Motor speed (0Motor
nominal speed)
4=Output current (0
InMotor)
5=Motor torque (0TnMotor)
6=Motor power (0PnMotor)
7=Motor voltage (0-UnMotor)
8=DC-link volt (01000V)
9=Target ref. Scaled to
current signal
0 = Not inverted
1 = Inverted
0 = 0 mA
1 = 4 mA
24
312
0=Not used
1=Ready
2=Run
3=Fault
4=Fault inverted
5=FC overheat warning
6=Ext. fault or warning
7=Ref. fault or warning
8=Warning
9=Reversed
10=Preset speed
11=At speed
12=Mot. regulator active
13=OP freq. limit superv.
14=Control place: IO
15=Therm. fault/warning
16=FB digin1
17=Calibration OK
18=Position reached
19=At high speed
20=At medium speed
21=At creep speed
22=Outside positioning
area
23=Over the end limit
24=Mech.brake open
24
17
313
As parameter 2.3.6
24
24
314
As parameter 2.3.6
P2.3.9
Output frequency
limit 1 supervision
P2.3.10
Output frequency
limit 1;
Supervised value
0,00
320,00
Hz
315
0,00
316
0=No limit
1=Low limit supervision
2=High limit supervision
22 vacon
P2.3.11
P2.3.12
P2.3.13
P2.3.14
P2.3.15
P2.3.16
Analogue output 2
signal selection
Analogue output 2
function
Analogue output 2
filter time
Analogue output 2
inversion
Analogue output 2
minimum
Analogue output 2
scaling
0.1
471
472
As parameter 2.3.1
1,00
473
0,00
10,00
474
475
10
1000
1000
476
0=Not inverted
1=Inverted
0=0 mA
1=4 mA
Parameter
Min
Max
Unit
Default
Cust
ID
P2.4.1
Ramp 1 shape
0,0
10,0
0,0
500
P2.4.2
Ramp 2 shape
0,0
10,0
0,0
501
P2.4.3
P2.4.4
Acceleration time 2
Deceleration time 2
0,1
0,1
3000,0
3000,0
s
s
10,0
10,0
502
503
P2.4.5
Brake chopper
504
P2.4.6
Start function
505
P2.4.7
Stop function
506
P2.4.8
Flux brake
520
0,0
Varies
0,0
519
P2.4.9
Note
0 = Linear
>0 = S-curve ramp time
0 = Linear
>0 = S-curve ramp time
0=Disabled
1=Used when running
2=External brake chopper
3=Used when
stopped/running
0=Ramp
1=Flying start
0=Coasting
1=Ramp
2=Ramp+Run enable coast
3=Coast+Run enable ramp
0 = Off
1 = On
Parameter
Prohibit frequency
range 1 low limit
Prohibit frequency
range 1 high limit
Prohibit acc./dec.
ramp
Min
Max
Unit
Default
Cust
ID
0,00
par. 2.5.2
Hz
0,00
509
0,00
320,00
Hz
0,0
510
0,1
10,0
1,0
518
Note
vacon 23
Parameter
Min
Max
P2.6.1
600
P2.6.2
U/f optimisation
109
P2.6.3
108
P2.6.4
Field weakening
point
30,00
320,00
Hz
50,00
602
P2.6.5
Voltage at field
weakening point
10,00
200,00
100,00
603
0,00
par.
P2.6.4
Hz
50,00
604
0,00
100,00
100,00
605
n% x Unmot
0,00
40,00
0,00
606
n% x Unmot
1,0
16,0
kHz
Varies
601
607
608
Depends on kW
0=Not used
1=Used
0=Not used
1=Used
P2.6.6
P2.6.7
P2.6.8
P2.6.9
P2.6.10
P2.6.11
Unit
Default
Cust
ID
Note
0=Frequency control
1=Speed control
2=Torque control
3=Closed Loop, speed ctrl
0=Not used
1=Automatic torque boost
0=Linear
1=Squared
2=Programmable
3=Linear with flux optim.
n% x Unmot
Parameter max. value =
par. 2.6.7
24 vacon
Parameter
Min
Max
P2.7.1
Response to
reference fault
P2.7.2
P2.7.3
P2.7.4
P2.7.5
P2.7.6
P2.7.7
P2.7.8
P2.7.9
P2.7.10
P2.7.11
P2.7.12
Reference fault
0,00
frequency
Response to external
0
fault
Input phase
0
supervision
Response to
1
undervoltage fault
Output phase
0
supervision
Earth fault
0
protection
Thermal protection
0
of the motor
Motor ambient
100,0
temperature factor
Motor cooling factor
0,0
at zero speed
Motor thermal time
1
constant
Motor duty cycle
0
728
701
730
727
702
703
704
0,0
705
150,0
40,0
706
200
min
10
707
100
100
708
P2.7.14
P2.7.15
P2.7.16
Stall current
Stall time limit
Stall frequency limit
0,1
1,00
1,0
6000,0
120,00
Par. 2.1.2
P2.7.19
P2.7.20
P2.7.21
P2.7.22
P2.7.23
Response to
thermistor fault
Response to
fieldbus fault
Response to slot
fault
Hz
100,0
Underload curve at
nominal frequency
Underload curve at
zero frequency
Underload
protection time
limit
ID
0,00
Par. 2.1.2
P2.7.18
Cust
700
Stall protection
Underload protection
Default
P2.7.13
P2.7.17
Unit
10
150
5,0
2
A
s
Hz
709
10,0
15,00
25,0
710
711
712
713
50
714
150,0
10,0
715
600
20
716
Note
0=No response
1=Warning
2=Warning+Old Freq.
3=Wrng+PresetFreq 2.7.2
4=Fault,stop acc. to 2.4.7
5=Fault,stop by coasting
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
732
0=No response
1=Warning
2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
733
See P2.7.21
734
See P2.7.21
vacon 25
Parameter
Wait time
Trial time
Min
0,10
0,00
Max
10,00
60,00
P2.8.3
Start function
719
10
720
10
721
722
10
723
10
726
10
725
P2.8.4
P2.8.5
P2.8.6
P2.8.7
P2.8.8
P2.8.9
Unit
s
s
Default
0,50
30,00
Cust
ID
717
718
Note
0=Ramp
1=Flying start
2=According to par. 2.4.6
26 vacon
Parameter
Min
Max
P2.10.1
Reference selection
1548
P2.10.2
Analog reference
1549
P2.10.3
1578
P2.10.4
Total trip
60000
15000
1500
P2.10.5
Total rounds
65535
954.9
1501
P2.10.6
Desimals
Med. Speed
starting point
Creep speed
starting point
Stop hysteresis
Positioning speed
max. 1
Positioning speed
med. 1
Positioning speed
creep 1
End limit speed
Positioning speed
max. 2
Positioning speed
med. 2
Positioning speed
creep 2
4
P2.10.4P2.11.1
1502
200
1506
P2.10.7
P2.10.8
P2.10.9
P2.10.10
P2.10.11
P2.10.12
P2.10.13
P2.10.14
P2.10.15
P2.10.16
P2.10.8
Unit
Init.
Cust
ID
P2.10.9
P2.10.7
100
1505
P2.10.8
10
1504
P2.10.11
P2.1.2
Hz
20.00
1509
P2.10.12
P2.10.10
Hz
10.00
1508
0.00
P2.10.11
Hz
5.00
1507
0,00
P2.1.2
Hz
5.00
1552
P2.10.15
P2.1.2
Hz
15.00
1512
P2.10.16
P2.10.14
Hz
7.50
1511
0.00
P2.10.15
Hz
3.75
1510
P2.10.17
Teaching
1513
P2.10.18
Automatic
calibration
1546
P2.10.19
Calibration Reset
1586
P2.10.20
Save position
1606
P2.10.21
Automatic ramp
scaling
1572
Note
0=Fixed positions
1=Analog reference
2=Fieldbus reference
0=AI1
1=AI2
0=Off
1=On
Users defined accurate
rounds per total trip
Affects to P2.10.5
0=Off
1=On
0=Off
1=On
0=Norm. calibration
1=Reset calibration
Save position on power
off/on situation
0=Off
1=On
vacon 27
4.10.1
4.10.1.1
Koodi
Parametri
Min
Max
Yks.
Oletus
Oma
ID
P2.10.22.1
Statusword,
3.BIT
0.1
E.10
0.1
1573
P2.10.22.2
Statusword,
4.BIT
0.1
E.10
0.1
1574
P2.10.22.3
Statusword,
5.BIT
0.1
E.10
0.1
1575
P2.10.22.4
Statusword,
6.BIT
0.1
E.10
0.1
1576
P2.10.22.5
Statusword,
7.BIT
0.1
E.10
0.1
1577
Huomautuksia
Programmable digital
input for the third bit of
the statusword.
Programmable digital
input for the fourth bit of
the statusword.
Programmable digital
input for the fifth bit of
the statusword.
Programmable digital
input for the sixth bit of
the statusword.
Programmable digital
input for the seventh bit
of the statusword.
Table 4-14. Programmable digital inputs for own status word, G2.10.22.
4.10.2
Description
Value = 0
Not calibrated
Not in position reference
Positioning low speed
Value = 1
Calibration OK
Position reached
Positioning Max Speed
Programmable digital input. P2.10.22.1
Programmable digital input. P2.10.22.2
Programmable digital input. P2.10.22.3
Programmable digital input. P2.10.22.4
Programmable digital input. P2.10.22.5
Manual mode
Positioning mode
Calibration input FALSE
Calibration input TRUE
Not Used
Not Used
No Warning
Warning Low End
No Warning
Warning High End
In side of area
Out of area fault
Run Disable Low End
Run Enable Low End
Run Disable High End
Run Enable High End
Into the multimonitor menu you could select three monitoring values at the same time. Values could
be selected from the menu M1, in addition frequency reference from panel, R3.2. See details on
page 67.
28 vacon
4.10.3
Koodi
Parametri
Min
Max
P2.10.24.1
P2.10.24.2
Max. speed 1
scaling MIN
0.00
P2.10.23.3
P2.10.24.3
Max.speed 1
scaling MAX
P2.10.24.2
P2.10.24.4
Max. speed 2
scaling MIN
P2.10.24.5
Max. speed 2
scaling MAX
Yks.
Oletus
ID
1579
100.00
1582
200.00
100.00
1584
0.00
P2.10.23.5
100.00
1583
P2.10.24.4
200.00
100.00
1585
Huomautuksia
0= Not used
1= AI1, analog input 1
2= AI2, analog input 2
3= Fieldbus reference
Positioning speed group
1 scaling minimum
value
Positioning speed group
1 scaling maximum
value
Positioning speed group
2 scaling minimum
value
Positioning speed group
2 scaling maximum
value
vacon 29
P2.11.3
Parameter
Safety area low
limit
Safety area high
limit
Calibration
position
Min
Max
Unit
Default
P2.10.4
200
1550
P2.10.4
200
1607
P2.11.1
(Total
trip) -(End limit)
=
P2.11.1
Cust.
ID
Position 1
Position 2
Position 3
Position 4
Position 5
Position 6
Position 7
Position 8
Position 9
Position 10
Position 11
Position12
Position 13
Position 14
Position 15
Position 16
Position 17
Position 18
Position 19
Position 20
Position 21
Position 22
Position 23
Position 24
Position 25
Position 26
Position 27
Position 28
Position 29
Position 30
Position 31
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
= previous
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
P2.11.1
Bi
t4
Bi
t3
Bi
t2
Bi
t1
Bi
t0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
1545
High end
limit
P2.11.4
P2.11.5
P2.11.6
P2.11.7
P2.11.8
P2.11.9
P2.11.10
P2.11.11
P2.11.12
P2.11.13
P2.11.14
P2.11.15
P2.11.16
P2.11.17
P2.11.18
P2.11.19
P2.11.20
P2.11.21
P2.11.22
P2.11.23
P2.11.24
P2.11.25
P2.11.26
P2.11.27
P2.11.28
P2.11.29
P2.11.30
P2.11.31
P2.11.32
P2.11.33
P2.11.34
Description
1514
1515
1516
1517
1518
1519
1520
1521
1522
1523
1524
1525
1526
1527
1528
1529
1530
1531
1532
1533
1534
1535
1536
1537
1538
1539
1540
1541
1542
1543
1544
30 vacon
Parameter
Current limit
Torque limit
Freq. Limit open
Brake open delay
Freq. Limit close
Brake close delay
Brake react.
Time
DC-brake current
Start DC-brake
time
Stop DC-brake
time
Stop DC-brake
frequency
Min
0,00
0,0
0
0,00
0,01
0,00
Max
In
100
Fn
10,00
Fn
10,00
Unit
A
%
Hz
s
Hz
s
Default
0,00
0,0
0,00
0,10
1,00
0,00
0,05
Cust.
ID
1587
1588
1589
1590
1591
1592
Description
0,00
10,00
0,15 x In
1,5 x In
Varies
507
0,000
60,000
0,000
516
0,000
60,000
0,000
508
0,10
10,00
Hz
1,50
515
1594
Parameter
Current limit
Torque limit
Freq. Limit open
Brake open delay
Freq limit close
Brake close delay
Start 0Hz time
Stop 0Hz time
Min
0
0
0
0,00
0,01
0,00
0
0
Max
In
100
Fn
10,00
Fn
10,00
2,000
2,000
Unit
A
%
Hz
s
Hz
s
s
s
Default
0,00
0
0,00
0,10
0,01
0,00
0,100
0,100
Cust.
ID
1596
1597
1598
1599
1600
1601
615
616
Description
Parameter
Min
Max
P3.1
Control place
R3.2
Keypad reference
Par.
2.1.1
Par. 2.1.2
P3.3
R3.4
Stop button
R3.5
Pulses calibrated
STOP
Unit
Default
Cust
ID
125
123
114
1610
Note
0 = I/O terminal
1 = Keypad
2 = Fieldbus
Hz
0 = Forward
1 = Reverse
0=Limited function of Stop
button
1=Stop button always
enabled
vacon 31
32 vacon
5.
Description of parameters
Description of parameters
2.1.5
Current limit
This parameter determines the maximum motor current from the frequency converter.
The current limit is 1.5 times the rated current (IL) by default.
2.1.6
2.1.7
2.1.8
2.1.9
2.1.10
2.1.11
33 vacon
2.1.12
Description of parameters
2.1.13
2.1.14
Preset speed
Parameter value is automatically limited between the minimum and maximum
frequencies (par. 2.1.1, 2.1.2). Reference is activated with digital input (Default A.3).
2.1.15
34 vacon
Description of parameters
FWD
Output
frequency
Stop function
(par 2.4.7)
= coasting
REV
DIN1
DIN2
NX12K09
c
d
e
Output
frequency
Stop function
(par 2.4.7
= coasting
REV
DIN1
DIN2
NX12K10
35 vacon
Description of parameters
FWD
Output
frequency
Stop function
(par 2.4.7)
= coasting
REV
DIN1
Start
DIN2
Stop
NX012K11
36 vacon
2.2.2
Description of parameters
No offset
Offset 4 mA (living zero), provides supervision of zero level signal. The response to
reference fault can be programmed with parameter 2.7.1.
2.2.3
2.2.4
Output
frequency
Max freq. par 2.1.2
par. 2.2.4
Analogue
input [V]
10
Analogue
input [V]
10
NX12K13
2.2.5
Reference inversion
Inverts reference signal:
Max. ref. signal = Min. set freq.
Min. ref. signal = Max. set freq.
Output
frequency
Max freq. par 2.1.2
0 No inversion
1 Reference inverted
par. 2.2.5
par. 2.2.4
Analogue
input
max.
NX12K14
37 vacon
2.2.6
Description of parameters
%
Unfiltered signal
100%
Filtered signal
63%
t [s]
Par. 2.2.7
NX12K15
2.2.7
Digital inputs
The programming principle of the input/output signals in the 3-Speed Positioning
Application is different compared to the conventional method used in most of the other
Vacon NX applications. With the help of this method, you could define any of the digital
inputs to function in parameter group G2.2.7.
In the conventional programming method, Function to Terminal Programming Method
(FTT), you have a fixed input or output that you define a certain function for. The
applications mentioned above, however, use the Terminal to Function Programming
method (TTF) in which the programming process is carried out the other way round:
Functions appear as parameters which the operator defines a certain input/output for.
38 vacon
Description of parameters
Example: You want to connect the digital input function Calibration (P2.2.7.13) to the digital input
DIA3 on the basic board OPT-A1.
First find the parameter 2.2.7.13 on the keypad. Press the Menu button right once to enter the edit
mode. On the value line, you will see the terminal type on the left (DigIN, DigOUT, An.IN, An.OUT)
and on the right, the present input/output the function is connected to (B.3, A.2 etc.), or if not
connected, a value (0.#).
When the value is blinking, hold down the Browser button up or down to find the desired board slot
and signal number. The program will scroll the board slots starting from 0 and proceeding from A
to E and the I/O numbers from 1 to 10.
Once you have set the desired value, press the Enter button once to confirm the change.
ENTER
Note: The inputs, unlike the outputs, can not be changed in RUN state
39 vacon
IN PUT SIGN AL
Description of parameters
APPLICATIO N
Parameter 2.2.7.1
0 .1
Parameter 2.2.7.2
0 .1
"ADDRESS 0 .x "
Address 0.1
FALSE
Address 0.2-0.10
TRUE
Parameter 2.2.7.3
0 .1
Parameter 2.2.7.4
N XO PTA1 , SLO T A
"Input 10" = A.1
0 .1
"Input 11" = A.2
Parameter 2.2.7.10
Preset speed
A.3
START-STOPLogic
P2.2.1
Parameter 2.2.7.11
Positioning speed
groups
A.4
Parameter 2.2.7.12
Positioning mode
A.5
Parameter 2.2.7.13
Ca libra tion/
Tea ching
A.6
N XO PTB1 , SLO T D
Parameter 2.2.7.14
"Input 40" = D.1
D.1
Parameter 2.2.7.15
Parameter 2.2.7.16
D.5
Parameter 2.2.7.19
D.4
Parameter 2.2.7.18
D.3
Parameter 2.2.7.17
D.2
0 .2
Address 0.1
TRUE
40 vacon
Description of parameters
=
=
=
=
2.2.7.8 Reverse
contact open
contact closed
=
=
Forward
Reverse
Reset
=
=
=
=
41 vacon
2.2.7.13
Description of parameters
Calibration
contact closed
2.2.7.14
2.2.7.15
2.2.7.16
2.2.7.17
2.2.7.18
Select the position with a combination of digital inputs. See truth table on page 29.
2.2.7.19
2.2.7.20
2.2.7.21
Posibility to connect proximity switch directly to frequency converter. When signal goes
low drive is stopped by coast.
2.2.7.22
Reset calibration
Posibility to reset calibration from IO. Action same as parameter 2.10.19
2.2.7.23
Calibration Negative
Posibility to use negative calibration signal, used only in manual calibration.
2.2.7.24
Calibration prohibited
Posibility to prohibit incoming calibration signal. Used when car needs to be in certain
position before calibration signal can be accept.
42 vacon
Description of parameters
2.3.2
%
Unfiltered signal
100%
Filtered signal
63%
t [s]
NX12K16
2.3.3
Analogue
output
current
20 mA
Param. 2.3.5
= 50%
10 mA
Param. 2.3.5
= 100%
4 mA
Param. 2.3.5
= 200%
2.3.4
0 mA
0.5
1.0
NX12K17
43 vacon
2.3.5
Description of parameters
Param. 2.3.5
= 200%
Param. 2.3.5
= 100%
20 mA
Signal
Output frequency
Freq. Reference
Motor speed
Output current
Motor torque
Motor power
Motor voltage
DC-link voltage
2.3.6
2.3.7
2.3.8
12 mA
Param. 2.3.5
= 50%
10 mA
Par. 2.3.4 = 1
4 mA
Par. 2.3.4 = 0
0 mA
0
0.5
1.0
UD012K18
Setting value
Signal content
0 = Not used
1 = Ready
Out of operation
Digital output DO1 sinks the current and
programmable relay (RO1, RO2) is activated when:
The frequency converter is ready to operate
2 = Run
3 = Fault
4 = Fault inverted
8 = Warning
9 = Reversed
10 = Preset speed
11 = At speed
44 vacon
Description of parameters
Table 5- 2. Digital output DO1 and relay outputs RO1 and RO2.
2.3.9
No supervision
Low limit supervision
High limit supervision
If the output frequency goes under/over the set limit (P 2.3.10) this function generates a
warning message via the digital output DO1 and via the relay output RO1
or RO2 depending on the settings of parameters 2.3.62.3.8.
2.3.10
f[Hz]
Par 2.3.9 = 2
Par 2.3.10
t
Example: 21 RO1
22 RO1
23 RO1
21 RO1
22 RO1
23 RO1
21 RO1
22 RO1
23 RO1
NX12K19
2.3.11
45 vacon
2.3.12
2.3.13
2.3.14
2.3.15
2.3.16
Description of parameters
46 vacon
5.4
2.4.1
2.4.2
Description of parameters
DRIVE CONTROL
Acceleration/Deceleration ramp 1 shape
Acceleration/Deceleration ramp 2 shape
The start and end of acceleration and deceleration ramps can be smoothed with these
parameters. Setting value 0 gives a linear ramp shape which causes acceleration and
deceleration to act immediately to the changes in the reference signal.
Setting value 0.110 seconds for this parameter produces an S-shaped
acceleration/deceleration. The acceleration time is determined with parameters
2.1.3/2.1.4 (2.4.3/2.4.4).
[Hz]
2.1.3, 2.1.4
(2.4.3, 2.4.4)
2.4.1 (2.4.2)
2.4.1 (2.4.2)
[t]
UD012K20
2.4.3
2.4.4
Acceleration time 2
Deceleration time 2
These values correspond to the time required for the output frequency to accelerate
from the zero frequency to the set maximum frequency (par. 2.1.2). These parameters
give the possibility to set two different acceleration/deceleration time sets for one
application. The active set can be selected with the programmable signal DIN3 (P.
2.2.7.4).
2.4.5
Brake chopper
0
1
2
3
=
=
=
=
When the frequency converter is decelerating the motor, the inertia of the motor and the
load are fed into an external brake resistor. This enables the frequency converter to
decelerate the load with a torque equal to that of acceleration (provided that the correct
brake resistor has been selected). See separate Brake resistor installation manual.
47 vacon
2.4.6
Description of parameters
Start function
Ramp:
0
The frequency converter starts from 0 Hz and accelerates to the set reference
frequency within the set acceleration time. (Load inertia or starting friction
may cause prolonged acceleration times).
Flying start:
1
The frequency converter is able to start into a running motor by applying a
small torque to motor and searching for the frequency corresponding to the
speed the motor is running at. Searching starts from the maximum frequency
towards the actual frequency until the correct value is detected. Thereafter,
the output frequency will be increased/decreased to the set reference value
according to the set acceleration/deceleration parameters.
Use this mode if the motor is coasting when the start command is given. With
the flying start it is possible to ride through short mains voltage interruptions.
2.4.7
Stop function
Coasting:
0
The motor coasts to a halt without any control from the frequency converter,
after the Stop command.
Ramp:
1
After the Stop command, the speed of the motor is decelerated according to
the set deceleration parameters.
If the regenerated energy is high it may be necessary to use an external
braking resistor for faster deceleration.
2.4.8
Flux brake
The flux braking can be set ON or OFF.
0 = Flux braking OFF
1 = Flux braking ON
2.4.9
48 vacon
Description of parameters
Output
frequency [Hz]
Reference [Hz]
2.5.1
2.5.3
2.5.2
NX12K24
Par. 2.5.2
Par. 2.5.1
49 vacon
Description of parameters
2.6.2
2.6.3
Frequency control:
Speed control:
Torque control
U/f optimisation
Automatic
torque boost
NOTE!
The voltage of the motor changes linearly with the frequency in the constant
flux area from 0 Hz to the field weakening point where the nominal voltage is
supplied to the motor. Linear U/f ratio should be used in constant torque
applications.
Squared: The voltage of the motor changes following a squared curve form
1
with the frequency in the area from 0 Hz to the field weakening point where
the nominal voltage is also supplied to the motor. The motor runs under
magnetised below the field weakening point and produces less torque and
electromechanical noise. Squared U/f ratio can be used in applications
where torque demand of the load is proportional to the square of the speed,
e.g in centrifugal fans and pumps.
24-hour support +358 (0)40 837 1150 Email: vacon@vacon.com
50 vacon
Description of parameters
U[V]
U[V]
Un
Nominal
par.2.6.5
UnDefault:
voltage of the motor
Field weakening
pointweakening
Field
point
Nominal
par.2.6.5 Default:
voltage of the motor
Linear
Linear
Squared
Squared
Default:Nominal
Nominal
Default:
frequencyofofthe
the
frequency
motor
motor
f[Hz]
f[Hz]
NX12K07
NX12K07
Default: Nominal
voltage of the motor
Par. 2.6.7
(Def. 10%)
Default: Nominal
frequency of the motor
f[Hz]
Par. 2.6.8
(Def. 1.3%)
Par. 2.6.6
(Def. 5 Hz)
Par. 2.6.4
NX12K08
2.6.4
51 vacon
2.6.5
Description of parameters
2.6.6
2.6.7
2.6.8
2.6.9
Switching frequency
Motor noise can be minimised using a high switching frequency. Increasing the
switching frequency reduces the capacity of the frequency converter unit.
The range of this parameter depends on the size of the frequency converter:
Up to NX5 0061: 116 kHz
>NX5 0072: 110 kHz
2.6.10
2.6.11
Overvoltage controller
Undervoltage controller
These parameters allow the under-/overvoltage controllers to be switched out of
operation. This may be useful, for example, if the mains supply voltage varies more than
15% to +10% and the application will not tolerate this over-/undervoltage. In this case,
the regulator controls the output frequency taking the supply fluctuations into account.
Note: Over-/undervoltage trips may occur when controllers are switched out of
operation.
0 Controller switched off
1 Controller switched on
52 vacon
Description of parameters
5.7 PROTECTIONS
2.7.1
2.7.2
2.7.3
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
A warning or a fault action and message is generated from the external fault signal
in the programmable digital inputs DIN3. The information can also be programmed into
digital output DO1 and into relay outputs RO1 and RO2.
2.7.4
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
The input phase supervision ensures that the input phases of the frequency converter
have an approximately equal current.
2.7.5
53 vacon
2.7.6
Description of parameters
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
Output phase supervision of the motor ensures that the motor phases have an
approximately equal current.
2.7.7
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
Earth fault protection ensures that the sum of the motor phase currents is zero. The
overcurrent protection is always working and protects the frequency converter from
earth faults with high currents.
Parameters 2.7.82.7.12, Motor thermal protection:
General
The motor thermal protection is to protect the motor from overheating. The Vacon drive is capable
of supplying higher than nominal current to the motor. If the load requires this high current there is
a risk that the motor will be thermally overloaded. This is the case especially at low frequencies. At
low frequencies the cooling effect of the motor is reduced as well as its capacity. If the motor is
equipped with an external fan the load reduction at low speeds is small.
The motor thermal protection is based on a calculated model and it uses the output current of the
drive to determine the load on the motor.
The motor thermal protection can be adjusted with parameters. The thermal current IT specifies the
load current above which the motor is overloaded. This current limit is a function of the output
frequency.
The thermal stage of the motor can be monitored on the control keypad display. See the products
User's Manual.
CAUTION!
The calculated model does not protect the motor if the airflow to the
motor is reduced by blocked air intake grill.
54 vacon
2.7.8
Description of parameters
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
If tripping is selected the drive will stop and activate the fault stage.
Deactivating the protection, i.e. setting parameter to 0, will reset the thermal stage of
the motor to 0%.
2.7.9
2.7.10
Overload area
IT
45%
INmotor
f
35 Hz
NX12k62
55 vacon
2.7.11
Description of parameters
2.7.12
Motor temperature
Trip area
105%
Motor
current
Fault/warning
par. 2.7.8
I/IT
Time constant T
Motor temperature
*)
= (I/IT)2 x (1-e-t/T)
Time
NX12k82
56 vacon
Description of parameters
2.7.13
Stall protection
0
1
2
3
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
Setting the parameter to 0 will deactivate the protection and reset the stall time counter.
2.7.14
Stall area
Par. 2.7.14
Par. 2.7.16
NX12k63
57 vacon
2.7.15
Description of parameters
Stall time
Stall time counter
Trip area
Par. 2.7.15
Trip/warning
par. 2.7.13
Time
Stall
No stall
NX12k64
2.7.16
2.7.17
Underload protection
0
1
2
3
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
If tripping is set active the drive will stop and activate the fault stage.
Deactivating the protection by setting the parameter to 0 will reset the underload time
counter to zero.
58 vacon
2.7.18
Description of parameters
Torque
Par. 2.7.18
Par. 2.7.19
Underload area
f
5 Hz
Fieldweakening
point par. 2.6.4
NX12k65
2.7.19
2.7.20
Underload time
This time can be set between 2.0 and 600.0 s.
This is the maximum time allowed for an underload state to exist. An internal up/down
counter counts the accumulated underload time. If the underload counter value goes
above this limit the protection will cause a trip according to parameter 2.7.17). If the
drive is stopped the underload counter is reset to zero.
59 vacon
2.7.21
Description of parameters
= No response
= Warning
= Fault, stop mode after fault according to parameter 2.4.7
= Fault, stop mode after fault always by coasting
Setting the parameter to 0 will deactivate the protection and reset the stall time counter.
2.7.22
2.7.23
60 vacon
Description of parameters
2.8.2
Wait time
Par. 2.8.1
Wait time
Par. 2.8.1
Fault trigger
Restart 2
Trial time
Par. 2.8.2
Fault active
RESET/
Fault reset
NX12k67
2.8.3
61 vacon
2.8.4
Description of parameters
2.8.5
2.8.6
2.8.7
2.8.8
2.8.9
62 vacon
Description of parameters
Reference selection
Target reference could be given in spite of control place P3.1 settings. If you want to
control frequency converter eg. via fieldbus (Start, stop, speed ref, positioning CW and so
on), it have to select with parameter P3.1 as an active control place.
0= Fixed positions 0-31, digital input combination.
1= Analog target reference; current or voltage input (P2.10.2)
2= Target reference from fieldbus
Fixed positions 0-31;
Storage location in parameter group G2.11 selected with the compination of 5 digital
inputs.
Analog target reference;
Target reference could be given eg. potentiometer, voltage or current signal. Reference
is adjustable during the positioning also. Notice analog electronics disturbances, which
could effect to positioning accuracy (1%).
Fieldbus target reference;
Target reference is written to processdata field 1, type UINT. Value is internally limited
like position parameters is group G2.11. See also chapter 3.6 Fieldbus control.
2.10.2
2.10.3
2.10.4
Total trip
Positioning area total lenght (Max. 60000). Unit type: ANY. Use the same units in all trip
parameters. (P2.10.4, P2.10.7, P2.10.8, P2.10.9 and all parameters in group G2.11)
Example: Total length is 2m.
2m = 200cm = 2000mm = 20000 (1/10)mm (<60000). P2.10.4=20000
63 vacon
Description of parameters
Total Rounds =
Total Trip
* Axis Diameter
Total Rounds =
2.10.6
Total Trip
Lenght of the 1 revolution
2.10.7
2.10.8
2.10.9
Stop hysteresis
Stop hysteresis. Advance position, when stopping. Finally positioning accuracy is defined
with this parameter. Frequency converter keeps the conveyor inside the hysteresis as
long as the START-command is on. In other words, it fixes the positioning all the time. If
hysteresis is too small, conveyor starts to oscillate. If this happens, you could decrease
the creeping speed, tune the ramps or increase the stop hysteresis. Same units as
P2.10.4.
2.10.10
2.10.11
2.10.12
Creeping speed 1
Positioning speed group 1. Positioning speed groups selected with programmable input
function P2.2.7.11.
64 vacon
Description of parameters
2.10.17 Teaching
Teaching the positions is possible, when calibration is done. See chapter 3.4
0=Off
1=On
2.10.18
2.10.19
Calibration Reset
0=No action
1=Reset calibration
2.10.20
Save position?
With this parameter it is possible to save the actual position during the power off/on
situation. When powering on again, the calibration has to be done, when the position is
reached. (No calibration in sheet cut mode)
2.10.21
65 vacon
Description of parameters
Fieldbus
2.10.22.1 Statusword, bit 3
2.10.22.2 Statusword, bit 4
2.10.22.3 Statusword, bit 5
2.10.22.4 Statusword, bit 6
2.10.22.5 Statusword, bit 7
See chapter 3.6.
66 vacon
2.10.23
Description of parameters
Multimonitor
Into the multimonitor menu you could select three monitoring values at the same time.
Values could be select from the menu M1, in addition frequency reference from panel
R3.2.
Example: You want to monitor actual position, target position and output frequency at
the same time.
Press the Menu button right once to enter Multimonitor menu. Press the Menu button
right once again. Now the value up and left starts blinking. Select the value, which you
want to monitor (Act. position=V1.16, Target pos.=V1.17 and Output freq.=V1.1) with
up/down- buttons and confirm the selection with Enter. Repeat the same to all values.
2.10.24.1
2.10.24.2
2.10.24.3
2.10.24.4
2.10.24.5
67 vacon
Description of parameters
68 vacon
Description of parameters
2.11.2
2.11.3
Calibration position
Placing to safety area prohibited. Same units as parameter P2.10.4.
2.11.3-2.11.33
Positions 1-31
31 storage locations. Each one could be selected with the combination of five digital
inputs. See the truth table on page 29.
Placing to safety area is prohibited. Same units as parameter P2.10.4.
69 vacon
5.11
Description of parameters
f/Hz
Max Freq
Brake closed
P2.12.1.7
I/T/F- limits
P2.12.1.1-3
P2.12.1.12
StopDC freq
*)
P2.12.1.5
FreqCloseLim
Run request
signal
DC- brake
P2.12.1.9-10
Br. open delay
P2.12.1.4
Mec. delay
P2.12.1.8
Br. close delay
P2.12.1.6
BRAKE OPEN
Eg. R02
Figure 5-27. Mechanical brake control logic in Open Loop. Start signal to brake open delay, when
current, frequency and torque go above limits defined by parameters. External input must be ON if
used.
70 vacon
Description of parameters
Mechanical brake control signal can be selected to any digital or relay output to control
the external mechanical brake
In the upper section is the mechanical brake opening logic. Mechanical brake needs five
signals to open and delay after that. If current or torque signal is not needed for opening
logic, those parameters can be set to zero. External brake input signal is programmable
and any digital input can be used for that purpose.
In the lower section is the mechanical brake closing logic. Brake close circuit has a
higher priority than open circuit. So if it is TRUE, then mechanical brake will close.
Brake will be closed immediately, if fault occurs.
71 vacon
Description of parameters
2.12.1.9
DC-brake current
Defines the current injected into the motor during DC-braking.
2.12.1.10
72 vacon
Description of parameters
73 vacon
Description of parameters
74 vacon
Description of parameters
75 vacon
Description of parameters
76 vacon
Control Place
The active control place can be changed with this parameter. For more information, see
the products User's Manual.
Pushing the Start button for 3 seconds selects the control keypad as the active control
place and copies the Run status information (Run/Stop, direction and reference).
3.2
Keypad Reference
The frequency reference can be adjusted from the keypad with this parameter.
The output frequency can be copied as the keypad reference by pushing the Stop button
for 3 seconds when you are on any of the pages of menu M3. For more information, see
the products User's Manual.
3.3
Keypad Direction
0
Forward: The rotation of the motor is forward, when the keypad is the active
control place.
Reverse: The rotation of the motor is reversed, when the keypad is the active
control place.
3.4
3.5
77 vacon
6.
Relay output
DIN5 x
DIN3 x
&
Calibration OK
Preset speed
3.2 Keypad reference
Fieldbus reference
Calibration OK
P2.10.18 Autom.calib.
in action
&
Internal frequency
reference
2.10.13 End
limit speed
Speed group1
Speed group2
P2.10.10-16 1
DIN4 x
Autom. calib.
frequencies
Keypad
Start/Stop- buttons
DIN1 x
DIN2 x
Forward
Reverse
Programmable
Start/Stop and
reverse logic
Start/Stop
Internal Start/Stop
Start/Stop from
fieldbus
Reset-button
Reverse
P2.10.18 Autom.Calib.
ON
Internal reverse
DIN6 x
Calibration, teaching
Automatic calibration
reverse logic
Positioning internal
reverse logic
DIN# x
Figure 6-1. Control signal logic with digital inputs default values
78 vacon
7.
When a fault is detected by the frequency converter control electronics, the drive is stopped and the
symbol F together with the ordinal number of the fault, the fault code and a short fault description
appear on the display. The fault can be reset with the Reset button on the control keypad or via the
I/O terminal. The faults are stored in the Fault History menu, which can be browsed. The different
fault codes you will find in the table below.
Shadowed rows are the A- faults (alarms) and black rows are F- faults (fault). Texts on the white
base could be both A- and F- faults.
The fault codes and their possible causes are presented in the table below.
Fault
code
1
Fault
Possible cause
Action
Overcurrent
Check loading.
Check motor.
Check cables.
Overvoltage
Earth fault
Charging
switch
6
7
Emergency
stop
Saturation trip
Unknown fault
Undervoltage
10
Input line
supervision
Output phase
supervision
11
79 vacon
12
Brake chopper
supervision
13
Frequency
converter
undertemperature
Frequency
converter overtemperature
15
16
Motor stalled
Motor overtemperature
17
Motor
underload
EEPROM
checksum fault
14
22
23
24
Changed data
warning
25
Microprocessor
watchdog fault
29
Thermistor
fault
Thermistor is broken.
32
Fan cooling
34
36
CAN bus
communication
Control unit
37
Device change
38
Device added
39
Device removed
40
Device
unknown
80 vacon
41
IGBT temperature
42
Brake resistor
overtemperature
43
Encoder fault
50
Analogue input
Iin < 4mA
(selected signal
range 4 to 20
mA)
51
52
External fault
Keypad
communication
fault
Fieldbus
communication
fault
54
55
56
New calibration
End limits
53
Check loading.
Check motor size.
Set the deceleration time longer.
Use external brake resistor.
81 vacon
Vaasa
Vacon Plc (Head office and production)
Runsorintie 7
65380 Vaasa
firstname.lastname@vacon.com
telephone: +358 (0)201 2121
fax: +358 (0)201 212 205
Helsinki
Vacon Plc
yritie 12
01510 Vantaa
telephone: +358 (0)201 212 600
fax: +358 (0)201 212 699
Vacon Traction Oy
Vehnmyllynkatu 18
33700 Tampere
telephone: +358 (0)201 2121
fax: +358 (0)201 212 710
Tampere
Vacon Plc
Vehnmyllynkatu 18
33700 Tampere
telephone: +358 (0)201 2121
fax: +358 (0)201 212 750
Italy
Vacon S.p.A.
Via F.lli Guerra, 35
42100 Reggio Emilia
telephone: +39 0522 276811
fax: +39 0522 276890
Belgium
Vacon Benelux NV/SA
Interleuvenlaan 62
3001 Heverlee (Leuven)
telephone: +32 (0)16 394 825
fax: +32 (0)16 394 827
The Netherlands
Vacon Benelux BV
Weide 40
4206 CJ Gorinchem
telephone: +31 (0)183 642 970
fax: +31 (0)183 642 971
France
Vacon France s.a.s.
1 Rue Jacquard BP72
91280 Saint Pierre du Perray CDIS
telephone: +33 (0)1 69 89 60 30
fax: +33 (0)1 69 89 60 40
Norway
Vacon AS
Langgata 2
3080 Holmestrand
telephone: +47 330 96120
fax: +47 330 96130
Germany
Vacon GmbH
Gladbecker Strasse 425
45329 Essen
telephone: +49 (0)201 806 700
fax: +49 (0)201 806 7099
PR China
Vacon Suzhou Drives Co. Ltd.
Blk 11A
428 Xinglong Street
Suchun Industrial Square
Suzhou 215126
telephone: +86 512 6283 6630
fax: +86 512 6283 6618
Great Britain
Vacon Drives (UK) Ltd.
18, Maizefield
Hinckley Fields Industrial Estate
Hinckley
LE10 1YF Leicestershire
telephone: +44 (0)1455 611 515
fax: +44 (0)1455 611 517
Russia
ZAO Vacon Drives
Bolshaja Jakimanka 31,
stroenie 18
109180 Moscow
telephone: +7 (095) 974 14 47
fax: +7 (095) 974 15 54
ZAO Vacon Drives
2ya Sovetskaya 7, office 210A
191036 St. Petersburg
telephone: +7 (812) 332 1114
fax: +7 (812) 279 9053
Singapore
Vacon Plc
Singapore Representative Office
102F Pasir Panjang Road
#02-06 Citilink Warehouse Complex
Singapore 118530
telephone: +65 6278 8533
fax: +65 6278 1066
Spain
Vacon Drives Ibrica S.A.
Miquel Servet, 2. P.I. Bufalvent
08243 Manresa
telephone: +34 93 877 45 06
fax: +34 93 877 00 09
Sweden
Vacon AB
Torget 1
172 67 Sundbyberg
telephone: +46 (0)8 293 055
fax: +46 (0)8 290 755
24-hour
+358 (0)40 837 1150 Email: vacon@vacon.com
Vacon support
distributor: