You are on page 1of 5

1.0.

JOB TITLE:
132kV Protection Relay Calibration in Compliance to ABE 1990

TENDER NO : T/ JUN / 14/ 1508/ EI

& Peraturan-peraturan Elektrik 1994.


2.0. JOB SECTION:
132kV Incomer- MCC 900.
3.0. JOB DESCRIPTION:
To supply skilled manpower, all tools and equipment to test, calibrate &
generate test reports for items in Appendix 1.
4.0. JOB SCOPE OF CONTRACTOR:
4.1 Mobilization & demobilization.
4.2 Bring necessary tools such as but not limited to test wires, plugs, sockets,
interfacing devices, computer program etc for the successful completion of the
job.
4.3 To have proper discussion prior to commencement of work.
4.4 The whole job as specified in Appendix 1 to be completed within allocated
time frame which will be specified later.
4.5 The contractors main contact persons are: (Pls indicate name, HP)
a)
b)
4.6 The contractor is not permitted to sub-contract the work
in whole without the principal (Main contact person) at site during work.
4.7 The contractor shall start mobilization of work within two (2) days
notice. However the approximate date will be given much earlier.
4.8 The contractor shall submit detail activity list & total manpower for PCSBs
review prior to mobilization.
4.9 All relay calibration must be done with at least three (3) different points for
IDMT curve.
4.10 All relays parameter & configuration settings to be documented before and
after testing. This is to be submitted in official calibration report.

4.11 All relays parameter settings / configuration settings must be delivered in soft
copy DIGSI file format (if applicable) and PDF file format along with calibration

TENDER NO : T/ JUN / 14/ 1508/ EI

certificates.
4.12 Calibration sticker with due date two (2) years from the execution date to be
applied immediately on the device upon calibration. (Old stickers to be removed &
adhesives cleaned properly)
4.13 Official calibration report to be delivered to PCSB representative within two
(2) weeks from the date of calibration works.

5.0. JOB SCOPE OF PCSB:


5.1 To arrange for supply outage & switching of 132kV system.
5.2

To provide any information necessary for the job.

6.0. TERMS & CONDITIONS:


6.1

Contractor must follow all PCSB rules, regulations and take all safety
precautions during working at site.

6.2. Contractor to attend safety briefing arranged by PCSB before carry out the
works.
6.3 Only trained / competent personnel shall attend and execute the works.
6.4. Contractor must be in proper attire and bring along own safety helmet and
safety shoes that are in good condition.
6.5. PCSB does not bind itself to accept the cheapest or any offer submitted.
6.6. Contractor must clean and tidy up the area after job completion or PCSB will
charge accordingly for the clean up work.
6.7. Job completion is subject to satisfaction of PCSB representative.
6.8. Any additional parts or accessories repair or replacement to be agreed &
certified by PCSB representative prior to rectification or replacement.
6.9. The Contractor will be responsible to make good, replace any damages
done to PCSB equipment or properties during the job at contractors own
cost.
6.10. Successful tendered party must provide Socso or workman compensation

for their staff who is engaged to work in PCSB.


6.11 The contractor shall comply with ABE 1990 & Peraturan-peraturan Elektrik
1994 when doing the job.

TENDER NO : T/ JUN / 14/ 1508/ EI

7.0. TENDER VALIDITY: Not applicable


8.0. WARRANTY:
No loose connections in any part of relays or accessories,
etc for a period of 2 years from calibration date.
9.0. PCSB REPRESENTATIVE:

Ir. Sashindran Seth (013-7419224)

10.0. TENDER CLOSING DATE & TIME:

26 June 2014, 1700hrs

Appendix 1 :

TENDER NO : T/ JUN / 14/ 1508/ EI

NOS

PANEL

CIRCUIT

=E01+R

TGLN 132kV
OHL No. 1
TNB CB TAG:
805

RELAY
Numerical Distance Protection
Siemens 7SA5111-4CA722AG3/GG
O/C Protection
Siemens
7SJ60014EA000DA0/BB

B/F Protection
Siemens 7SV6001-4EA001DA0/BB

Differential Protection
Siemens 7UT5121-4CB010AA0/JH

O/C Protection
Siemens
132/6.6kV
TRANSFORMER 7SJ60014EA000DA0/BB
=E02+R
1 TNB CB TAG:
B/F Protection
110
Siemens 7SV5001-4CA00
Restricted E/F Protection.
Siemens 7VH8000-4CA04/B

7
132kV
BUSCOUPLER
PROTECTION
TNB CB TAG:
120

10

=E03+R
132kV BUSBAR
PROTECTION
TNB CB TAG:
120

11

12
=E05+R
13
14

KTNN 132kV
OHL No. 2
TNB CB TAG:
905

O/C Protection
Siemens
7SJ60014EA000DA0/BB
B/F Protection
Siemens 7SV5001-4CA00
Differential Protection CHECK ZONE
Siemens 7VH8300-4CA04/A
Differential Protection - ZONE
A
Siemens 7VH8300-4CA04/A
Differential Protection - ZONE
B
Siemens 7VH8300-4CA04/A
Numerical Distance Protection
Siemens 7SA5111-4CA722AG3/GG
O/C Protection
Siemens
7SJ60014EA000DA0/BB

RLY
DueDate

TENDER NO : T/ JUN / 14/ 1508/ EI

15

B/F Protection
Siemens 7SV5001-4CA00

16

Differential Protection
Siemens 7UT5121-4CB010AA0/JH

17

18

19

O/C Protection
Siemens
132/6.6kV
TRANSFORMER 7SJ60014EA000DA0/BB
=E04+R
2 TNB CB TAG: B/F Protection
210
Siemens 7SV6001-4EA001DA0/BB
Restricted E/F Protection.
Siemens 7VH8000-4CA04/B

You might also like