You are on page 1of 59

ion &

Agenda
Day 2

Day 1

Introduction
Information Required
Using Log-Log Paper & TCCs
Types of Fault Current
Protective Devices & Characteristic
Curves
Coordination Time Intervals (CTIs)
Effect of Fault Current Variations
Multiple Source Buses

Transformer Overcurrent Protection


Motor Overcurrent Protection
Conductor Overcurrent Protection
Generator Overcurrent Protection
Coordinating a System

Introduction

Protection Objectives
Personnel Safety

Protection Objectives
Equipment Protection

Protection Objectives
Service Continuity & Selective Fault Isolation
13.8 kV
Faults should be quickly
detected and cleared with a
minimum disruption of service.
13.8 kV/480 V
2.5 MVA
5.75%

480 V

Protective devices perform this


function and must be adequately
specified and coordinated.
Errors in either specification or
setting can cause nuisance
outages.

Types of Protection

Distance
High Impedance Differential
Current Differential
Under/Over Frequency
Under/Over Voltage
Over Temperature
Overcurrent
Overload

Coordinating Overcurrent Devices


Tools of the trade in the good ole days

Coordinating Overcurrent Devices


Tools of the trade in the good ole days

Coordinating Overcurrent Devices


Tools of the trade in the good ole days

Coordinating Overcurrent Devices


Tools of the trade in the good ole days

Coordinating Overcurrent Devices


Tools of the trade in the good ole days

Coordinating Overcurrent Devices


Tools of the trade today

Using Log-Log Paper & TCCs

Log-Log Plots
Time-Current Characteristic Curve (TCC)
1000
effectively
steady state
100

I2t withstand
curves plot as
straight lines

1 minute

Time In Seconds

Why log-log paper?


Log-Log scale compresses
values to a more manageable
range.

10
typical motor
acceleration

I2t withstand curves plot as


straight lines.

0.1

typical fault
clearing
5 cycles
(interrupting)

1 cycle
(momentary)
0.01
0.5

FLC = 1 pu

Fs = 13.9 pu

10

100`

Fp = 577 pu

1000

10000

Current in Amperes

Plotting A Curve
5000 hp Motor TCC
1000

FLC = 598.9 A
13.8 kV

Time In Seconds

100
13.8/4.16 kV
10 MVA
6.5%

10

Accel. Time = 2 s
4.16 kV
1

M 4.16 kV 5000 hp
90% PF, 96% , 598.9 A
3593.5 LRA, 2 s start

0.1

LRA = 3593.5 A
0.01
0.5

10

100`

1000

10000

Current in Amperes

Plotting Fault Current & Scale Adjustment


5000 hp Motor TCC with Fault on Motor Terminal
1000
13.8 kV

FLC = 598.9 A
100

Time In Seconds

13.8/4.16 kV
10 MVA
6.5%
10

Accel. Time = 2 s
4.16 kV
15 kA

M 4.16 kV 5000 hp
90% PF, 96% , 598.9 A
3593.5 LRA, 2 s start

0.1

15 kA

LRA = 3593.5 A
0.01
0.5

10

100`

1000

10000

Current in Amperes x 10 A

Voltage Scales
5000 hp Motor TCC with Fault on Transformer Primary

45 kA @ 13.8 kV
= ? @ 4.16 kV

1000
13.8 kV

= (45 x 13.8/4.16)
= 149.3 kA @ 4.16 kV

45 kA

100

Time In Seconds

13.8/4.16 kV
10 MVA
6.5%
10
4.16 kV
15 kA

M 4.16 kV 5000 hp
90% PF, 96% , 598.9 A
3593.5 LRA, 2 s start

0.1

15 kA
0.01
0.5

10

100`

1000

149.3 kA

10000

Current in Amperes x 100AA @ 4.16 kV

Types of Fault Currents

Fault Current Options


Crest/Peak
Current

Interrupting/Breaking

Momentary
Initial Symmetrical

ANSI

IEC

Momentary Symmetrical
Momentary Asymmetrical
Momentary Crest
Interrupting Symmetrical
Adjusted Interrupting Symmetrical

Initial Symmetrical (Ik)


Peak (Ip)
Breaking (Ib)
Asymmetrical Breaking (Ib,asym)

Fault Current Options


Crest/Peak
Current

Momentary

Interrupting/Breaking

Initial Symmetrical

Symmetrical currents are most appropriate.


Momentary asymmetrical should be considered when setting
instantaneous functions.
Use of duties not strictly appropriate, but okay.
Use of momentary/initial symmetrical currents lead to conservative CTIs.
Use of interrupting currents will lead to lower, but still conservative CTIs.

10

Protective Devices & Characteristic


Curves

Electromechanical Relays (EM)


100

IFC 53
RELAY Very
Inverse Time
Time-Current
Curves

10

3
2

0.1

Time Dial
Settings

TIME IN SECONDS

10

0.01
1

10

100

MULTIPLES OF PICK-UP SETTING

11

Electromechanical Relays Pickup Calculation


The relay should pick-up for current
values above the motor FLC ( ~ 600 A).

4.16 kV

IFC
53

For the IFC53 pictured, the available


ampere-tap (AT) settings are 0.5, 0.6,
0.7, 0.8, 1, 1.2, 1.5, 2, 2.5, 3, & 4.

800/5

For this type of relay, the primary pickup


current was calculated as:
PU = CT Ratio x AT

4.16 kV
5000 hp FLC =
598.9 A SF =
1.0

Set AT = 4

PU = (800/5) x 3 = 480 A (too low)


= (800/5) x 4 = 640 A (107%, okay)

Electromechanical Relays Operating Time Calculation


4.16 kV

IFC 53
RELAY Very
Inverse Time TimeCurrent Curves
10

IFC
53 Setting = 4 AT, ?? TD

800/5
10 kA
15 kA
M

1.21
1
1.05

10

0.34
0.30

3
2

0.1

0.08
7

0.01

15.6
1

Time Dial Settings

TIME IN SECONDS

100

23.4

4.16 kV
5000 hp
598.9 A, SF = 1

IFC 53 Relay Operating Times


Fault Current

15 kA

10 kA

15000/640
= 23.4

10000/640
= 15.6

Time Dial

0.07 s

0.08 s

Time Dial 3

0.30 s

0.34 s

Time Dial 10

1.05 s

1.21 s

Multiple of Pick-up

10
100
MULTIPLES OF PICK-UP SETTING

12

Solid-State Relays (SS)

Microprocessor-Based Relays
52B

2000/5
01-52B

41-SWGR-01B
13.8 kV
OCR F15B
400/5
01-F15B

Seconds

52B
OC1
ANSI-Normal Inverse
Pickup = 2.13 (0.05 20 xCT Sec)
Time Dial = 0.96
Inst = 20 (0.05 20 xCT Sec)
Time Delay = 0.01 s

F15B
OC1
ANSI-Extremely Inverse
Pickup = 8 (0.05 20 xCT Sec)
Time Dial = 0.43
Inst = 20 (0.05 20 xCT Sec)
Time Delay = 0.02 s

52B 3P
F15B 3P
30 kA @ 1 3.8 kV

Amps X 100 (Plot Ref. kV=13.8)

13

Power CBs
PWR MCB
3200 A

LT Pickup

16-SWGR-02A
0.48 kV
PWR FCB
1600 A

LT Band
Power MCB

Seconds

Cutler-Hammer RMS 520 Series


Sensor = 3200
LT Pickup = 1 (3200 Amps)
LT Band = 4
ST Pickup = 2.5 (8000 Amps)
ST Band = 0.3 (I^x)t = OUT

Power FCB
Cutler-Hammer RMS 520 Series
Sensor = 1200
LT Pickup = 1 (1200 Amps)
LT Band = 2
ST Pickup = 4 (4500 Amps)
ST Band = 0.1 (I^x)t = OUT

ST Pickup
ST Band

Power MCB 3P
47.4 kA @ 0.48 kV

Power FCB 3P
90.2 kA @ 0.48 kV

Amps X 100 (Plot Ref. kV=0.48)

Insulated & Molded Case CB


Insulated Case MCB
1200 A
16-SWGR-02A
0.48 kV
Molded Case CB
250 A

Insulated Case MCB

Seconds

Frame = 1250 Plug = 1200 A


LT Pickup = Fixed (1200 A)
LT Band = Fixed
ST Pickup = 4 x (4000 A)
ST Band = Fixed (I^2)t = IN
Override = 14000 A

Molded Case CB
HKD
Size = 250 A
Terminal Trip = Fixed
Magnetic Trip = 10

Fault current
< Inst. Override

Insulated Case MCB


11 kA @ 0.48 kV

Amps X 100 (Plot Ref. kV=0.48)

14

Insulated & Molded Case CB


Insulated Case MCB
1200 A
16-SWGR-02A
0.48 kV
Molded Case CB
250 A
Insulated Case MCB

Seconds

Frame = 1250 Plug = 1200 A


LT Pickup = Fixed (1200 A)
LT Band = Fixed
ST Pickup = 4 x (4000 A)
ST Band = Fixed (I^2)t = IN
Override = 14000 A

Molded Case CB
HKD
Size = 250 A
Terminal Trip = Fixed
Magnetic Trip = 10

Fault current
> Inst. Override

Insulated Case MCB


42 kA @ 0.48 kV

Amps X 100 (Plot Ref. kV=0.48)

Power Fuses
MCC 1
4.16 kV
Mtr Fuse

Seconds

Mtr Fuse JCL


(2/03) Standard
5.08 kV
5R

Minimum
Melting

Total
Clearing

Mtr Fuse
15 kA @
4.16 kV

Amps X 10 (Plot Ref. kV=4.16 kV)

15

Coordination Time Intervals (CTIs)

Coordination Time Intervals (CTIs)


The CTI is the amount of time allowed between a
primary device and its upstream backup.

Backup devices wait for sufficient


time to allow operation of primary
devices.

Primary devices sense, operate


& clear the fault first.

Main

Feeder

When two such


devices are
coordinated such
that the primary
device should
operate first at all
fault levels, they are
selectively
coordinated.

16

Coordination Time Intervals EM


In the good old days,
Main

What typical CTI would we


want between the feeder and
the main breaker relays?
Seconds

Feeder

It depends.

30 kA

Main

Feeder
?s

30 kA
Amps X 100 (Plot Ref. kV=13.8)

Coordination Time Intervals EM


On what did it depend?
Remember the TD setting?
It is continuously adjustable
and not exact.
So how do you really
know where TD = 5?
FIELD TESTING !
(not just hand set)

17

Coordination Time Intervals EM


Plotting the field test points.

3x means 3 times pickup


3 * 8 = 24 A (9.6 kA primary)
5 * 8 = 40 A (16 kA primary)
8 * 8 = 64 A (25.6 kA primary)

Seconds

Feeder

3x (9.6 kA), 3.3 s


5x (16 kA), 1.24 s
8x (25.6 kA), 0.63 s

30 kA
Amps X 100 (Plot Ref. kV=13.8)

Coordination Time Intervals EM


So now, if test points are not
provided what should the CTI
be?

Main

0.4 s

Feeder

Seconds

30 kA

But, if test points are provided


what should the CTI be?

0.3 s

Main w/ testing
Main w/o testing
Feeder

0.3 s 0.4 s

30 kA
Amps X 100 (Plot Ref. kV=13.8)

18

Coordination Time Intervals EM


Where does the 0.3 s or 0.4 s come from?
1.
2.
3.

breaker operating time


(Feeder breaker)
CT, relay errors
(both)
disk overtravel (Main relay only)
Tested

Hand Set

breaker 5 cycle

0.08 s

0.08 s

Disk over travel

0.10 s

0.10 s

CT, relay errors

0.12 s

0.22 s

TOTAL

0.30 s

0.40 s

Main

Feeder

30 kA

Coordination Time Intervals EM


Red Book (per Section 5.7.2.1)
Components

Obviously, CTIs can be a


subjective issue.
Buff Book (taken from Tables 15-1 & 15-2)
Field Tested

Components
0.08 s
0.10 s
0.17 s
0.35 s

0.08 s
0.10 s
0.12 s
0.30 s

19

Coordination Time Intervals EM & SS


So, lets move forward a few years.
For a modern (static) relay what part of the
margin can be dropped?

Disk overtravel

So if one of the two relays is static, we can


use 0.2 s, right?

It depends

Main (EM)

CTI = 0.2 s

CTI = 0.3 s

Main (SS)

(because disk OT is
still in play)
Feeder (SS)

Feeder (EM)

Coordination Time Intervals EM & SS


Main (EM)

Main (SS)

Feeder (SS)

Feeder (SS)

Main (SS)

Seconds

Main (EM)

Feeder (EM)

Feeder EM
0.3 s

0.2 s

disk OT still applicable


Main (EM)

Main (SS)

Feeder (SS)
30 kA @ 13.8 kV

Feeder (EM)
30 kA @ 13.8 kV

Amps X 100 (Plot Ref. kV=13.8)

Amps X 100 (Plot Ref. kV=13.8)

20

Coordination Time Intervals EM/SS with Banded Devices


OC Relay combinations with banded devices

disk over travel

EM Relay

Power
Fuse

Power
Fuse

operating time x
CTI

0.22 s

disk over travel x


CT, relay errors
operating time x
CTI

0.12 s
0.12 s

Static Trip or
Molded Case
Breaker

Static Relay

Static Trip or
Molded Case
Breaker

0.1 s

Coordination Time Intervals EM/SS with Banded Devices


EM-Banded

SS-Banded

EM Relay

SS Relay

PWR MCB

PWR MCB

PWR MCB

EM Relay

SS Relay

Seconds

PWR MCB

0.22 s

25 kA
Amps X 100 (Plot Ref. kV=0.48)

0.12 s

25 kA
Amps X 100 (Plot Ref. kV=0.48)

21

Coordination Time Intervals Banded Devices


Banded characteristics include
tolerances & operating times.

Seconds

There is no
intentional/additional time delay
needed between two banded
devices.
All that is required is clear
space (CS).

Amps X 100 (Plot Ref. kV=0.48)

Coordination Time Intervals Summary


Buff Book (Table 15-3 Minimum CTIsa)

22

Effect of Fault Current Variations

CTI & Fault Current Magnitude


Inverse relay characteristics
imply
Operating
Time

For a fault current of 10 kA the


CTI is 0.2 s.
For a fault current of 20 kA the
CTI is 0.06 s.

Feeder

F1 = 10 kA
Seconds

Relay
Current

Main

Main

F2 = 20 kA

Feeder

0.2 s
0.06 s

If CTI is set based on 10 kA, it


reduces to less than the
desired value at 20 kA.

F1 = 10 kA

F2 = 20 kA

Amps X 100 (Plot Ref. kV=13.8)

23

Total Bus Fault versus Branch Currents


10 kA
15 kA

1.2 kA

0.8 kA

1 kA

2 kA

For a typical distribution bus all feeder relays will see a slightly different
maximum fault current.

Years back, the simple approach was to use the total bus fault current as
the basis of the CTI, including main incomer.

Using the same current for the main led to a margin of conservatism.

Total Bus Fault versus Branch Currents

10 kA

Using Total Bus


Fault Current of
15 kA

Using Actual
Maximum Relay
Current of 10 kA

15 kA

Feeder

Feeder

0.2 s

15 kA
Amps X 100 (Plot Ref. kV=13.8)

Seconds

Main
Main

0.8 s

10 kA

15 kA

Amps X 100 (Plot Ref. kV=13.8)

24

Curve Shaping

Using a definite time


characteristic (or delayed
instantaneous) can
eliminate the affect of
varying fault current levels.

Seconds

Most modern relays


include multiple OC
Elements.

0.2 s
20 kA
15 kA
10 kA
Amps X 100 (Plot Ref. kV=13.8)

Multiple Source Buses

25

Multiple Source Buses

When a bus includes multiple sources, care must be


taken to not coordinate all source relays at the total
fault current.

Source relays should be plotted only to their respective


fault currents or their normalized plots.

Plotting the source curves to the total bus fault current


will lead to much larger than actual CTIs.

Multiple Source Buses

Plot to Full Fault


Level

Plot to Actual
Relay Current

18 kA

12 kA

30 kA

Seconds

1.1 s

0.2 s

12 kA

30 kA

Amps X 100 (Plot Ref. kV=13.8)

12 kA

30 kA

Amps X 100 (Plot Ref. kV=13.8)

26

Adjusted Pickup Method

Many software packages include the facility to


adjust/shift the characteristics of the source relays to
line up at the bus maximum fault currents.

The shift factor (SF) is calculated using:


SF = Bus Fault / Relay Current

Adjusted Pickup Method

Without shift factor


both pickups = 3000 A.

18 kA

12 kA

30 kA

Seconds

With shift factor relay 2


pickup shifts to 7500 A.
SF = (30/12) * 3000 A

12 kA

0.2 s

0.2 s

30 kA

30 kA

Amps X 100 (Plot Ref. kV=13.8)

Amps X 100 (Plot Ref. kV=13.8)

27

Multiple Source Buses

10 kA
Bus A

10 kA

5 kA
Bus B

15 kA (Fa)
10 kA (Fb)
Fb = 25 kA

Fa = 25 kA

Different fault locations cause different flows in tie.


SF(Fa) = 25 / (10 + 5) = 1.67
SF(Fb) = 25 / 10
=2
Preparing a TCC for each unique location can confirm defining case.
Cases can be done for varying sources out of service & breaker logic
used to enable different setting groups.

Partial Differential Relaying

Source 1
Ip1

Is1

51A

51B

Is1+Is2

Is2

Source 2
Is2

Ip2

Is2

Bus A

Bus B

Typically used on double-ended


systems with normally closed
ties.
Automatically discriminates
between Bus A and Bus B faults.

Ip2
Ip1+Ip2

Feeder A

Feeder B

Eliminates need for relay on tie


breaker.
Saves coordination step.

28

Partial Differential Relaying


Embellish notes
Source 1
Ip1

Is1

51A

51B

Is1

Is1

Source 2
0

Scheme works even with one


source out of service.

0
Open

Is1

Bus A

Bus B
Ip1

However, the relay in the open


source must remain in operation
since the relay in the remaining
source sees no operating current.

Ip1

Feeder A

Feeder B

Partial Differential Relaying


Show same 3 source 1 tie example

29

Directional Current Relaying

67

Bus A

67

Bus B

Directional overcurrent (67) relays should be used on double-ended


line-ups with normally closed ties and buses with multiple sources.
Protection is intended to provide more sensitive and faster detection
of faults in the upstream supply system.

Transformer Overcurrent Protection

30

Transformer Overcurrent Protection


NEC Table 450.3(A) defines overcurrent setting requirements for primary &
secondary protection pickup settings.

Transformer Overcurrent Protection


C37.91 defines the ANSI
withstand protection limits.
Withstand curve defines
thermal & mechanical limits of
a transformer experiencing a
through-fault.

mechanical
withstand

thermal
withstand
based on
transformer Z

25 x FLC
@ 2s

31

Transformer Overcurrent Protection


Requirement to protect for
mechanical damage is based
on frequency of through faults
& transformer size.
Right-hand side (thermal) used
for setting primary protection.
Left-hand side (mechanical)
used for setting secondary
protection.

mechanical
withstand

thermal
withstand
25 x FLC
@2s

based on
transformer Z

Transformer Overcurrent Protection


FLC = 2.4 MVA/(3 x 13.8) = 100.4 A
Relay PU must be 600% FLC = 602.4 A

PWR-MCB

400 / 100.4 = 398% so okay

Seconds

Using a relay setting of 2.0 x CT, the relay


PU = 2 x 200 = 400 A

2.4 MVA, 5.75% Z


-Y Resistor Ground

13.8 kV

Time Dial depends on level of protection


desired.
13.8/0.48 kV
2.4 MVA
5.75%
PWR-MCB
480 V

Amps X 10 (Plot Ref. kV=13.8)

32

Transformer Overcurrent Protection


-Y Connections Phase-To-Phase Faults
A
0

1.0

0.866

b
c

0.5
C

0.866

Assume
1:1 turns ratio
X1 = X2 = X0
3-Phase fault current = base current.
Phase-phase fault current is typically
0.866 per unit.
This current transforms to 0.5
(0.866/3) per unit on the delta phase
winding and adds up to 1.0 per unit on
the line-side.

primary relay clipped


at 100% secondary
fault current
coordinated with a
secondary relay
clipped at 86% of the
secondary fault
current.

Trim down notes on


left and summarize
that we normally dont
mess with this issue

The CTIs need to be set assuming


1.15 (1/0.866) per unit fault current.

Transformer Overcurrent Protection


-Y Connections Phase-To-Ground Faults
1.0

0.577

0.577

0
b

0.577

Add TCC with a


shifted and non-shifted
transformer damage
curve.

Assume
1:1 turns ratio
X1 = X2 = X0
3-Phase fault current = base current.
The 1 per unit phase-ground fault
current transforms to 0.577 (1/3) per
unit on the delta phase.
The transformer damage curve is
shifted to the left to ensure protection.

33

Will be deleted once the previous page is fixed.


For a solidly-grounded
secondary

For resistancegrounded secondary


PWR-MCB

PWR-MCB

2.4 MVA, 5.75% Z


-Y Solid Ground

Seconds

2.4 MVA, 5.75% Z


-Y Resistor Ground

13.8 kV

13.8/0.48 kV
2.4 MVA
5.75%

Withstand
curve shifted
left due to
-Y xfmr.
More difficult
to provide
protection.

PWR-MCB
480 V

Amps X 10 (Plot Ref. kV=13.8)

Amps X 10 (Plot Ref. kV=13.8)

Transformer Overcurrent Protection


Inrush Current
PWR-MCB

Use of 8-12 times FLC @ 0.1 s is an


empirical approach based on EM
relays.
The instantaneous peak value of the
inrush current can actually be much
higher than 12 times FLC.

Seconds

2.4 MVA, 5.75% Z


-Y Resistor Ground

The inrush is not over at 0.1 s, the dot


just represents a typical rms
equivalent of the inrush from
energization to this point in time.

13.8 kV

13.8/0.48 kV
2.4 MVA
5.75%

8-12 x FLC
(typical)

PWR-MCB
480 V

Amps X 10 (Plot Ref. kV=13.8)

34

Transformer Overcurrent Protection


Setting the primary inst. protection
PWR-MCB

The primary relay instantaneous


(50) setting should clear both the
inrush & the secondary fault current.
It was common to use the
asymmetrical rms value of
secondary fault current (1.6 x sym)
to establish the instantaneous
pickup, but most modern relays filter
out the DC component.

Seconds

2.4 MVA, 5.75% Z


-Y Resistor Ground

13.8 kV

13.8/0.48 kV
2.4 MVA
5.75%

8-12 x FLC
(typical)

PWR-MCB
480 V

Amps X 10 (Plot Ref. kV=13.8)

Transformer Overcurrent Protection


-Y Connection & Ground Faults

A secondary L-G fault is not sensed by the ground devices on the


primary () side.
Low-resistance and solidly grounded systems are coordinated as
separately derived systems.

35

Transformer Overcurrent Protection


-Y Connection & Ground Faults
The ground resistor size is selected to
limit the fault current while still providing
sufficient current for coordination.
The resistor ratings include a maximum
continuous current that must be
considered.

Motor Overcurrent Protection

36

Motor Overcurrent Protection


Fuse provides short-circuit
protection.

GE Multilin 469
Standard O/L Curve
Pickup = 1.01 X FLC
Curve Multiplier = 3

49 or 51 device provide motor


overload protection.

Bussmann
JCL Size 9R
Hot

Seconds

Overload pickup depends on


motor FLC and service factor.

1000 hp
4.16 kV
650% LRC

The time delay for the 49/51


protection is based on motor
stall time.

M
Amps X 10 (Plot Ref. kV=4.16)

Motor Overcurrent Protection


GE Multilin 469
Standard O/L Curve
Pickup = 1.01 X FLC
Curve Multiplier = 3

In the past, instantaneous OC


protection was avoided on contactorfed motors since the contactors could
not clear high short-circuits.
Hot
1000 hp
4.16 kV
650% LRC
Seconds

With modern relays, a delayed


instantaneous can be used if its
setting is coordinated with the
contactor interrupting rating.

Bussmann
JCL Size 9R

Contactor
6 kA Int.
M
Amps X 10 (Plot Ref. kV=4.16)

37

Motor Overcurrent Protection


The instantaneous setting for a
breaker-fed motor must be set to pass
the motor asymmetrical inrush.
Can be done with a pickup over the
asymmetrical current.

GE Multilin 469
Standard O/L Curve
Pickup = 1.01 X FLC
Curve Multiplier = 3

1000 hp
4.16 kV
650% LRC

Hot

Seconds

Can be done using a lower pickup with


time delay to allow DC component to
decay out.

3 kA @ 4.16 kV

Amps X 10 (Plot Ref. kV=4.16)

Conductor Overcurrent Protection

38

Conductor Overcurrent Protection


LV Cables
NEC 240.4 Protection of Conductors conductors shall be protected against
overcurrent in accordance with their ampacities
(B) Devices Rated 800 A or Less the next higher standard device rating
shall be permitted
(C) Devices Rated over 800 A the ampacity of the conductors shall be the
device rating

NEC 240.6 Standard Ampere Ratings


(A) Fuses & Fixed-Trip Circuit Breakers cites all standard ratings
(B) Adjustable Trip Circuit Breakers Rating shall be equal to maximum
setting
(C) Restricted Access Adjustable-Trip Circuit Breakers Rating can be
equal to setting if access is restricted

Conductor Overcurrent Protection


MV Cables
NEC 240.101 (A) Rating or Setting of Overcurrent Protective Devices
Fuse rating 3 times conductor ampacity
Relay setting 6 times conductor ampacity

40

Conductor Overcurrent Protection


The insulation temperature rating
is typically used as the operating
temperature (To).

Seconds

The final temperature (Tf) depends


on the insulation type (typically
150 deg. C or 250 deg. C).

1 3/C 350 kcmil


Copper Rubber
Tc = 90 deg. C

When calculated by hand, you


only need one point and then draw
in at a -2 slope.

Amps X 100 (Plot Ref. V=600)

Generator Overcurrent Protection

41

Generator Overcurrent Protection

A generators fault current


contribution decays over time.

Overcurrent protection must


allow both for moderate
overloads & be sensitive enough
to detect the steady state
contribution to a system fault.

Generator Overcurrent Protection


FLC/Xd

Voltage controlled/ restrained


relays (51V) are commonly
used.

The pickup at full restraint is


typically 150% of Full Load
Current (FLC).

The pickup at no restraint must


be < FLC/Xd.

42

Generator 51V Pickup Setting Example

Fg

19500 kVA
903 A
Xd = 280%

1200/5

51V

12.47 kV

Fg = FLC/Xd = 903 / 2.8 = 322.5 A


51V pickup (full restraint)

> 150% FLC = 1354 A

51V pickup (no restraint)

< 322.5 A

Generator 51V Pickup Setting Example


51V Setting > 1354/1200
Using 1.15, 51V pickup
With old EM relays,
51V pickup (no restraint)

= 1.13
= 1.15 x 1200 A = 1380 A

= 25% of 1380 A
= 345 A (> 322.5 A, not good)

With new relays a lower MF can be set, such that 51V


pickup (no restraint)
= 15% of 1380 A
= 207 A (< 322.5, so okay)

43

Generator 51V Settings on TCC

Seconds

15% x Pickup

Pickup = 1.15 x
CT-Sec

GTG-101A
No Load
Constant Excitation
Total Fault Current

Limited guidance on
overcurrent protection
(C37.102 Section 4.1.1)
with respect to time delay.
Want to avoid nuisance
tripping, especially on
islanded systems, so
higher TDs are better.

30 kA

Amps X 10 (Plot Ref. kV=12.47)

Coordinating a System

44

Coordinating a System
TCCs show both
protection & coordination.
Most OC settings should
be shown/confirmed on
TCCs.
Showing too much on a
single TCC can make it
impossible to read.

Coordinating a System
Showing a
vertical slice of
the system can
reduce
crowding, but
still be hard to
read.
Upstream
equipment is
shown on
multiple and
redundant
TCCs.

45

TCC Zone Map

TCC-6
TCC-3
TCC-2

TCC-5

TCC-1

TCC-Comp

TCC-4

TCC-307J
TCC-101J

TCC-212J

Coordinating a System: TCC-1


Zone Map

Motor starting & protection is adequate.


Cable withstand protection is adequate.
The MCC main breaker may trip for faults
above 11 kA, but this cannot be helped.
The switchgear feeder breaker is selective
with the MCC main breaker, although not
necessarily required

46

Coordinating a System: TCC-2


Zone Map

The switchgear feeder breaker settings


established on TCC-1 set the basis for this
curve.
The main breaker is set to be selective with
the feeder at all fault levels.
A CTI marker is not required since the
characteristic curves include all margins and
breaker operating times.
The main breaker curve is clipped at its
through-fault current instead of the total bus
fault current to allow tighter coordination of
the upstream relay.

Coordinating a System: TCC-3


Zone Map

The LV switchgear main breaker settings


established on TCC-2 set the basis for this curve.
The transformer damage curve is based on
frequent faults and is not shifted since the
transformer is resistance grounded.
The primary side OC relay is selective with the
secondary main and provides adequate
transformer and feeder cable protection.
The OC relay instantaneous high enough to pass
the secondary fault current and transformer
inrush current.

47

Coordinating a System: TCC-307J


Zone Map

This curve sets the basis for the upstream


devices since its motor is the largest on the
MCC.
Motor starting and overload protection is
acceptable.
Motor feeder cable protection is acceptable
The motor relay includes a second definite
time unit to provide enhanced protection.
The definite time function is delay to allow
the asymmetrical inrush current to pass.

Coordinating a System: TCC-4


Zone Map

The 307J motor relay settings established


on TCC-307J set the basis for this curve.
The tie breaker relay curve is plotted to the
total bus fault current to be conservative.
The main breaker relay curve is plotted to its
let-through current.
A coordination step is provided between the
tie and main relay although this decision is
discretionary.
All devices are selectively coordinated at all
fault current levels.
The definite time functions insulation the
CTIs from minor fault current variations..

48

Coordinating a System: TCC-5


Zone Map

The MV MCC main breaker settings


established on TCC-4 set the basis for this
curve.
The transformer damage curve is based on
frequent faults and is not shifted since the
transformer is resistance grounded.
The primary side OC relay is selective with the
secondary main and provides adequate
transformer and feeder cable protection.
The OC relay instantaneous high enough to
pass the secondary fault current and
transformer inrush current.

Coordinating a System: TCC-Comp


Zone Map

Due to the compressor size, this curve may


set the basis for the MV switchgear main
breaker.
Motor starting and overload protection is
acceptable.
Short-circuit protection is provided by the
relay/breaker instead of a fuse as with the
1000 hp motor.
The short-circuit protection is delay 50 ms to
avoid nuisance tripping.

49

Coordinating a System: TCC-6


Zone Map

The feeder breaker settings established on


TCC-3, TCC-4, and TCC-Comp are shown
as the basis for this curve.
The settings for feeder 52A1 (to the 2.4
MVA) could be omitted since it does not
define any requirements.
A coordination step is provided between the
tie and main relay although this decision is
discretionary.
All devices are selectively coordinated at all
fault current levels.
The definite time functions insulation the
CTIs from minor fault current variations.

TCC Zone Map

TCC-G1

TCC-G2

50

Coordination Pop Quiz #1


2000/5

OCR

Does this TCC look good??

Main
SWGR-1
400/5

OCR
600/5
TR-FDR1

OCR

There is no need to maintain a


coordination interval between
feeder breakers.

The CTI between the main and


feeder 2 is appropriate unless all
relays are electromechanical and
hand set.

TR-FDR2

0.301 s
0.3 s

Coordination Pop Quiz #2


2000/5

Does this TCC look good??

OCR

Main-1
SWGR-3
400/5

OCR

600/5
FDR-1

The CTIs shown between main


and both feeders are sufficient.

Assuming testing EM relays, the


0.615s CTI cannot be reduced
since the 0.304s CTI is at the
limit.

The main relay time delay is


actually too fast since the CTI at
30 kA is less than 0.2s.

OCR

FDR-2

0.615 s
0.304 s

51

Coordination Pop Quiz #3


Does this TCC look good??

The marked CTIs are okay,


but.

A main should never include an


instantaneous setting.

0.472 s
0.325 s

Coordination Pop Quiz #4


Does this TCC look good??

Primary relay pickup is 525% of


transformer FLC, thus okay.

Transformer frequent fault


protection is not provided by the
primary relay, but this is okay
adequate protection is provided
by the secondary main.

Cable withstand protection is


inadequate. Adding a 50 to the
primary relay would be
appropriate and fix this.

52

Coordination Pop Quiz #5


Does this TCC look good??

Crossing of feeder
characteristics is no problem.

There is no need to maintain an


intentional time margin between
two LV static trip units clear
space is sufficient.

0.021 s

Coordination Pop Quiz #6


Does this TCC look good??

0.03 s

The source relays should not be


plotted to the full bus fault level
unless their plots are shifted
based on:
SF = Total fault current / relay
current.

Assuming each relay actually


sees only half of the total fault
current, the CTI is actually much
higher than 0.3s.

53

Coordination Pop Quiz #7


Does this TCC look good??

There are two curves to be


concerned with for a 51V full
restraint and zero restraint.

Assuming the full restraint curve


is shown, it is coordinated too
tightly with the feeder.

The 51V curve will shift left and


lose selectivity with the feeder if
a close-in fault occurs and the
voltage drops.

0.302 s

Coordination Software
Computer-aided coordination software programs
originated in the late 1980s.
The accuracy of the device characteristic curves was
often highly questionable.
There are numerous, much more powerful programs
available today, many of which are very mature.
Even still, the accuracy of the protective devices
functions and characteristics is still extremely critical.

54

Coordination Software
For many years clients maintained separate impedance
models for power studies and protective device models
for coordination studies.
Integrated models are now the norm and are required to
support arc-flash studies.

Information Required

55

Accurate One-Line Diagram

Equipment Ratings

drive short-circuit
calculations
affect asymmetrical
currents

56

Equipment Ratings

drives short-circuit
calculations
affects transformer
through-fault protection
inrush affects settings

Equipment Ratings

size and construction


ampacity
insulation type/rating
affects I2t damage curve

57

Equipment Ratings

bus continuous rating affects


relay pickup (different for LV
and MV)
short-circuit rating must be
adequate but does not affect
overcurrent coordination
differing fault current affect
coordination

Equipment Ratings

adds to short-circuit
LRC, acceleration time, & hot/
cold stall times affect time
curve selection

58

Protective Devices
Make & model
CT Ratio
Tap & time dial
settings (old days)
setting files (today)
Trip device type
LT, ST, Inst settings

References

59

Selected References

Applied Protective Relaying Westinghouse


Protective Relaying Blackburn
IEEE Std 242
Buff Book
IEEE Std 141
Red Book
IEEE Std 399
Brown Book
IEEE C37.90
Relays
IEEE C37.91
Transformer Protection
IEEE C37.102
Guide for AC Generator Protection
NFPA 70
National Electrical Code

120

60

You might also like