Operating Principle
Unlike ordinary level switches that use a float for level detection, the
61F Floatless Level Controller uses electrodes to electrically detect
the liquid level. The following figures illustrate this simple operating
principle.
8 VAC X
Relay
X
Relay contacts
b a
E1
Magnetic contactor (To)
E3
Relay
X
Relay contacts
b a
E1
Magnetic contactor (To)
E3
9--1
a2
c2
b2
8 VAC X
A pump is usually connected to a contactor, which in turn is connected to the Controller contact outputs. The Level Controller would
automatically operate the pump, to control the liquid level in the
tank.
However, in practice, with only two electrodes, ripples on the surface of the liquid cause the Controller to jump and start, shortening
pump (and other equipment) life. This problem can be solved by adding another electrode to form a self-holding circuit. The additional
electrode, E2, is connected in parallel with E1, as shown below.
Relay contacts
b1 a1
c1
Magnetic contactor (To)
PUMP OFF
E3 E2
E1
PUMP ON
As shown in the above figure, when the holding circuit relay is energized, contact a2, its NO contact, is closed. The electrical circuit
made through the liquid and the electrodes is then retained by E2
and E3, even when the liquid level falls below E1, as long as contact
a2 is closed.
When the liquid level falls below E2, the circuit made through the
electrode circuit opens, which de-energizes relay X, thus closing
the NC contact of X.
Operating as simply as it does, possible applications of the Floatless Level Controller are virtually endless. Not only liquid level control is possible, but such applications as leakage detection, object
size discrimination, and many other problems may be solved by one
of the reliable 61F Floatless Level Controllers.
61F
61F
Model Selection
Basic Configuration of 61F Conductive Level Controller
To use a 61F Conductive Level Controller, the 61F itself, Electrode Holders, and Electrodes are required.
Select from the capability, function, and size to suit the application.
61F
Refer to the following Controller selection guidelines.
Basic configuration
61F Controller
Cermet wire is used in the transformer to
prevent accidents by short-circuiting.
Relay Unit
Incorporates a transistor-based control circuit and output relay.
One to five Relay Units are used, depending on the application.
Electrode Holder/Electrodes
Many materials, sensitivities and mounting variations are available.
M: Electrical Motor
P: Fluid Pump
M
Water supply
source
Ordering Information
61F Controller Selection Guide by Installation Method
Standard Model
Plug-in Model
Compact Plug-in Model
9--2
61F
61F
61F Controller Selection Guide by Application
Item
Function
G
A t
Automatic
ti water
t supply
l and
d drainage
d i
control
t l
Automatic pump
operation
(constant water
level)
Water level
indication
abnormal alarm
Water drainage
Water supply
P
Pump
ON
Automatic water
supply (idling
prevention)
Automatic water
supply (abnormal
shortage alarm)
Pump
ON
Pump
OFF
Pump
OFF
G1
Pump
OFF
Pump
OFF
Pump
ON
Pump
ON
Water supply
source
---
Water tank
Pump OFF
(idling preShortvention)
age
B
Appearance
Shortage
Standard Model
Plug-in Model
61F-GP-N
(Pages 9--16 to
9--18, 9--25)
61F-G1--AP*
(Pages 9--6 to 9--7, 9--9 to
9--10, 9--24)
AP -- Asia Pacific Type
61F-G--AP*
(Pages 9--6 to 9--15,
9--24)
AP -- Asia Pacific Type
61F-G1P
61F-GP-N8
Item
Function
G2
Automatic water supply and drainage control
(abnormal water increase alarm)
Automatic pump
operation
(constant water
level)
Water supply
Water drainage
G3
Automatic water supply and
drainage control (abnormal
filling/shortage alarm)
Water supply
Water drainage
Pump
OFF
Pump
ON
Pump
OFF
Pump
ON
Pump
ON
Pump
OFF
Pump
ON
Pump
OFF
P
Water level
indication
abnormal alarm
Full
Appearance
LH
Upper
limit
Standard Model
Plug-in Model
LL
Shortage
Standard Model
61F-G2P
61F-G2
(Pages 9--6 to 9--7,
9--11, 9--24)
9--3
61F-G3
(Pages 9--6 to 9--7,
9--12, 9--25)
61F
61F
Item
Function
Automatic pump
operation
(constant water
level)
G4
Water source level indication, prevention
of pump idling due to water shortage,
automatic water supply control, and
indication of water level in tank
Elevated water tank
I
Liquid level indication and alarm
---
Water
supply
Pump
OFF
Pump
ON
Pump
ON
Pump
OFF
Water level
indication
abnormal alarm
LH
LH
Full
Middle
LM
LH
Upper
limit
B
B
LL
LL
Lower
limit
Shortage
Appearance
Upper
limit
LL
Lower
limit
Standard Model
Plug-in Model
Standard Model
61F-G4
(Pages 9--6 to
9--7, 9--24)
61F-IP
61F-I
Related Products
Relay Unit for standard
models (Page 9--7)
61F-WLA Water
Leakage Alarm
61F-GPN-V50 Water
Leakage Detector
Accessories
Electrode Holders
Applications
General
applications
such as water
supply lines
Applications
where only a
small space is
available
Applications
where high
mounting
strength is
required
Applications
where high
temperature/
high pressure
conditions are
severe
Applications
where high
corrosion
resistance is
required
Applications
where
distance to the
water surface
is long
Models
PS-3S/-4S/-5S
(Two-wire
models are
also
available.)
PS-31
BF-1
BF-3/-4/-5
BS-1
BS-1T
PH-1/-2
SUS
PH-2
Appearance
Hastelloy
titanium
PH-1
9--4
61F
61F
Electrodes
Sets of Electrodes, connecting nuts, lock nuts, and spring washers are available. When ordering individual parts, refer to page 9--19.
Applications
Sodium hydroxide,
acetic acid, dilute
sulfuric acid, dilute
hydrochloric acid
Models
F03-60-SUS201
F03-60-SUS316
F03-60 HAS B
F03-60 HAS C
F03-60 Titanium
Others
Item
Model
Protective Cover
(for PS or BF electrode holders)
F03-11
Spring Clamp
(for PS electrode holders)
F03-12
Note:
9--5
For more complete range of products, please contact nearest OMRON office.
61F
61F
Specifications
Standard Models
Specifications
Items
General-purpose
Controller
High-temperature Controller
Long-distance Controllers
High-sensitivity
Controllers
Low-sensitivity
Controller
61F-j (TDL)
(see note
1 and 2)
61F-jT
(see note 1)
61F-jH
(see note 1)
61F-jD
(see note 1)
24 VAC
8 VAC
Controlling materials
and operating
conditions
Supply voltage
Operating voltage
range
Interelectrode
voltage
8 VAC
Interelectrode
current
Approx. 1 mA AC max.
Power consumption
Interelectrode
operate resistance
0 to approx. 4 k
0 to approx. 5 k
Approx. 15 k to
70 k
(see note 5)
0 to approx.
1.8 k
Interelectrode
release resistance
Approx. 15 k to
1
Approx. 15 k to
1
4 k to 1 (for 2 km)
2.5 k to 1 (for 4 km)
Approx. 300 k to
1
Approx. 5 k to
1
Cable length
(see note 3)
1 km max.
600 m max.
2 km max.
4 km max.
50 m max.
1 km max.
Control output
Ambient temperature
Ambient humidity
Insulation resistance
(see note 4)
Dielectric strength
(see note 4)
Life expectancy
Note:
1. The j in the model name represents G, G1, G2, G3, G4, and I.
2. The suffix TDL attached to the model name represents models designed for tropical regions (storage humidity of 45 to 90% RH).
3. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become
shorter as the cable diameter or number of conductors becomes larger.
4. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power
terminals and contact terminals, and between Electrode terminals and contact terminals.
5. Possible to use with 15 k or less, however, this may cause reset failure
9--6
61F
61F
Internal Circuit Diagrams
The schematic diagrams shown below typify the internal connections of the various 61F models. The designations Ta, Tb, and Tc (sometimes
referred to collectively as U) may occur more than once in a product, however, the a terminal is always an NO contact, a b terminal is an NC
contact, and the c terminal is the common terminal.
61F-GT
61F-G--AP
0V
100, 110
or 120 V
200, 220
or 240 V
24 V
61F-11
Relay Unit
61F-GL
0V
100, 110
or 120 V
200, 220
or 240 V
8V
61F-11T
Relay Unit
24 V
8V
Tb
S0
S1
E2
E1
S2
Ta
E3
61F-GD
24 V
61F-11H
Relay Unit
24 V
Tb
E2
S1
S2
0V
100, 110
or 120 V
200, 220
or 240 V
24 V
S0
E3
61F-11D
Relay Unit
Tc
Tb
E2
S1
E1
S2
E3
8V
U
U
U
Tc
Tb
S1
S0
Ta
E1
Ta
U
U
Tc
S0
8V
Tc
61F-11L
Relay Unit
24 V
U
Ta
0V
100, 110
or 120 V
200, 220
or 240 V
E2
Ta
E1
S2
Tc
S0
E3
Tb
E2
S1
S2
E1
E3
Item
61F-11T
61F-11L
61F-11H
61F-11D
Interchangeable with
general-purpose model (61F-11)
---
Provided
Provided
Not provided
Provided
---
Red
Yellow
Blue
Black
61F-11T
61F-11
E
7
8V
6
24 V
61F-11L
E
24 V
10
11
Tb2
Ta2
Tc2
Tc1
Ta1
Tb1
61F-11H
(see note)
Tr2
S
Tr2
11
Tb2
Ta2
Tc2
Tc1
Ta1
24 V
S
5
Tr2
3
Tb1
24 V
Tr1
10
11
Tb2
Ta2
Tc2
Tc1
Ta1
3
Tb1
61F-11D
24 V
Tr1
Tr2
24 V
10
11
10
11
Ta2
Tb2
Tc2
Tc1
Tb1
Ta1
Tb2
Ta2
Tc2
Tc1
Ta1
9--7
8V
10
8V
24 V
Tr2
24 V
Tr1
Tr1
6
24 V
24 V 24 V
7
8V
Tr2
Tr1
3
Tb1
Note:
61F
61F
Connections
61F-G--AP
Automatic Water Supply and Drainage Control
1. Water Supply
2. Drainage
Water drainage
Water supply
P
Pump OFF
Pump ON
(U indicator ON)
E1
(U indicator OFF)
E2
(U indicator ON)
E1
Pump ON
(U indicator OFF)
E2
E3
E3
and starts (indicator OFF) when the water level drops below E2.
200-VAC power supply
R S T
Pump OFF
and stops (indicator OFF) when the water level drops below E2.
61F-G--AP
0V
100 V
200 V
MCCB
Transformer
61F-11
24 V
Relay Unit
8V
U
Ta
Tc
S0
Tb
S1
E2
S2
E1
E3
(See note 1)
Rated voltage:
S0--S1: 100 or 110 or 120 VAC
S0--S2: 200 or 220 or 240 VAC
Electromagnetic switch
Water tank
PS-3S
THR
E1
E2
Stop
Start
E3
Note:
1. The diagram shows the connections for the water supply. When draining, change the connection from terminal Tb to terminal Ta.
2. Be sure to ground terminal E3.
9--8
61F
61F
61F-G1--AP
The pump stops (U2 indicator ON) when the water level reaches
Water tank
E1 and the pump starts (U2 indicator OFF) when the water level
in the tank drops below E2.
E1
E2
Shortage
E3
B
Water
supply
pump stops (U1 indicator OFF). Pump idling is prevented and the
alarm sounds.
Water supply
source
Pump OFF
When the level of the water supply source drops below E2, the
Pump ON
E2
E3
61F-G1--AP
200-VAC power supply
R S T
0V
100 V
Transformer
61F-11
24 V
Relay Unit
U1
61F-11
Relay Unit
U2
24 V
200 V
8V
MCCB
U1
U2
U1
U2
Tb1
S0
S1
S2
Tc2
Ta1
E3
E2
E1
Tb2
E2
E1
(E4)
Alarm
Pushbutton
switch
Rated voltage:
S0--S1: 100 or 110 or 120 VAC
S0--S2: 200 or 220 or 240 VAC
Electromagnetic
switch
*
PS-3S
THR
E1
Water tank
E2
E3
E1
Note:
9--9
E3
E2
Water supply
source
61F
61F
61F-G1--AP
Application 2: Automatic Water Supply Control with Abnormal Water Shortage Alarm
Water tank
The pump stops (U2 indicator ON) when the water level reaches
Water supply
E1 and starts (U2 indicator OFF) when the water level drops
P
below E2.
(U2 indicator ON)
Pump OFF
E1
If the water level drops below E4 for any reason, the pump stops
Pump ON
E2
B
Shortage
E4
E3
61F-G1
0V
100 V
Transformer
61F-11
24 V
Relay Unit
U1
61F-11
Relay Unit
U2
24 V
200 V
8V
U1
MCCB
U2
U1
U2
Tb1
S0
S1
S2
Ta1
E3
Tc2
E2
E1
Tb2
E2
E1
(E4)
B
Alarm
Pushbutton
switch
Electromagnetic
switch
Rated voltage:
S0--S1: 100 or 110 or 120 VAC
S0--S2: 200 or 220 or 240 VAC
PS-4S
E1
E2
Water tank
THR
E3
Note:
E4
9--10
61F
61F
61F-G2
Automatic Drainage Control and Water Supply with Abnormal Water Increase Alarm
2. Water Supply
1. Drainage
Water supply
Water drainage
B
Upper
E4
limit
E4
E1
Upper
limit
Pump OFF
Pump ON
E2
E1
Pump ON
Pump OFF
E2
E3
E1 and stops (U2 indicator OFF) when the water level drops
below E2.
reaches E2 and stops (U2 indicator ON) when the water level
rises to E1.
If the water level reaches E4 for any reason, the alarm sounds
If the water level reaches E4 for any reason, the alarm sounds
0V
24 V
61F-11
Relay Unit
U1
24 V
61F-11
Relay Unit
U2
100 V
200 V
8V
U2
MCCB
U2
U1
S0
Ta1
S1
Tc1
S2
Ta2
Tb1
E3
E2
Tc2
E1
(See note 1)
E4
Rated voltage:
S0--S1: 100 or 110 or 120 VAC
S0--S2: 200 or 220 or 240 VAC
Water supply
source
Electromagnetic
switch
THR
PS-4S
E1 E4
Note:
E3
E2
Water supply
source
1. The diagram shows the connections for the water supply. When draining, change the connection from terminal Tb1 to terminal Ta1.
2. Be sure to ground terminal E3.
9--11
Reservoir
61F
61F
61F-G3
Automatic Water Supply and Drainage Control with Abnormal Water Shortage Alarm and Water Tank Repletion
2. Drainage
1. Water Supply
Water supply
Upper
limit
E1
Pump OFF
LH
LH
Water drainage
Upper
limit
E1
E2
E2
Pump ON
Pump ON
E3
E4
E5
LL
E4
LL
Lower limit
Lower limit
E5
E2 and starts (U2 indicator OFF) when the water level drops
below E3.
E2 and stops (U2 indicator OFF) when the water level drops
below E3.
If the water level drops below E4 for any reason, the lower-limit
If the water level drops below E4 for any reason, the lower-limit
0V
Transformer
61F-11
24 V
Relay Unit
U1
24 V
61F-11
Relay Unit
U2
24 V
61F-11
Relay Unit
U3
100 V
200 V
MCCB
8V
U2
U1
U3
U2
Ta
Tc
S0
Tb
S1
B1
Lc
B2
S2
(See note 1)
U3
U1
LH
Alarm
Upper
B limit
E1
LL
E5
E3
E2
E4
*
PL
Power
source
Lower
PL limit
Power
source
Electromagnetic
switch
Rated voltage:
S0--S1: 100 or 110 or 120 VAC
S0--S2: 200 or 220 or 240 VAC
PS-5S
Water repletion
THR
Water tank
E1
E2
E3
E4
Note:
E5
Water shortage
1. The diagram shows the connections for the water supply. When draining, change the connection from terminal Tb to terminal Ta.
2. Be sure to ground terminal E5.
9--12
61F
61F
61F-G4
Water Source Level Indication, Prevention of Pump Idling Due to Water Shortage, Automatic Water Supply Control, and Indication of Water Level in Tank
Insert four Electrodes in the water supply source and five
The pump stops (U5 indicator ON) when the water level reaches
Electrodes in the elevated water tank.
E5 and starts (U5 indicator OFF) when the water level drops
below E6.
The lower-limit indicator for the water supply source remains ON
If the water level reaches E4 for any reason, the tank repletion
while the water source level is below E3 (U2 indicator OFF).
indicator for the elevated tank turns ON (U4 indicator ON).
When the water level rises to E2, the lower-limit indicator turns
Insert a pushbutton switch (NO contact) between E2 and E8 as
OFF (U2 indicator ON) and the pump is ready for operation.
shown by the dotted line. When starting the pump and after
When the water level reaches E1, the upper-limit indicator turns
recovering from a power failure, if the water source level has not
ON (U3 indicator ON).
yet reached E2 (U2 indicator OFF), press the pushbutton switch
to start the pump by momentarily short-circuiting E2 and E8.
The water-shortage indicator for the elevated tank remains ON
When the pump stops during normal operation subsequent to an
while the water level in the elevated tank is below E7. The
alarm issued for low water level (i.e., the water level has not
indicator turns OFF (U1 indicator ON) when the water level rises
reached E3), do not press the pushbutton switch.
to E7.
61F-G4
0V
100 V
24 V
24 V
24 V
24 V
24 V
200 V
0V
U2
MK3P
Relay
X
100 V
8V
LL2
Electromagnetic
switch
Elevated tank
repletion
LL1
LH1
LH2
S1
S2
LH1
U5
BL1
Tc
LH2
BL2
TC2
BL1
BL2
U3
BH1
B
BH2
TA
BH1
U2
E4
E8
U5
E3
E7
E2
Pushbutton
switch
PS-5S
Water tank
E4
E6
E8
E2
Note:
9--13
E5
BH2
PS-4S
E1
E6
Rated voltage:
S0--S1: 100 or 110 or 120 VAC
S0--S2: 200 or 220 or 240 VAC
THR
U4
LL2
S0
U1
Elevated tank
repletion
LL1
U3
MCCB
U4
Elevated tank
water shortage
200 V
U1
E8
E3
E1
Upper limit
ON
OFF
Lower limit
E5
Water repletion
OFF
ON
E7
Water shortage
61F
61F
Connection with Three-phase Four-line Circuit
When supplying power from N-phase to the Controller in three-phase four-line circuit, refer to the following diagrams.
Line voltage (R-S, S-T, or R-T):
380 or 415 VAC
Phase voltage (N-R, N-S, or N-T): 220 or 240 VAC
Transformer
61F-11
24 V
Relay Unit
8V
Ta
Tc
S0
Tb
S1
E1
E2
S2
S3
Rated voltage:
S0--S2: 220 or 240 VAC
Electromagnetic switch
Water tank
E1
E2
Stop
Start
E3
Note:
9--14
61F
61F
61F-I
LH
Upper
limit
E1
LM
LL
When the water level drops below E2, the lower-limit indicator
When the water level reaches E2, the alarm turns OFF and the
intermediate indicator turns ON (U2 indicator ON).
Middle
Lower
limit
When the water level rises to E1, the upper-limit indicator turns
61F-I
Transformer
0V
R S T
24 V
61F-11
Relay Unit
24 V
61F-11
Relay Unit
100 V
U1
U2
200 V
MCCB
8V
U1
U2
U2
U1
L1
Tc
L3
B
S0
S1
L2
S2
E3
E2
E1
Intermediate
Alarm
PL
PL
PL
Upper limit
Lower
limit
Rated voltage:
S0--S1: 100 or 110 or 120 VAC
S0--S2: 200 or 220 or 240 VAC
PS-3S
E1
Water tank
E3
Note:
9--15
E2
Upper alarm
Intermediate
Lower alarm
61F
61F
Compact Plug-in Models (11-pin Type)
Specifications
Item
Generalpurpose
Controller
High-temperature Controller
61F-GP-NT
61F-GP-N
Long-distance Controllers
High-sensitivity
Controller
Low-sensitivity
Controller
61F-GP-NH
(see note 1)
61F-GP-ND
Approx. 0.12 mA
AC max.
Approx. 1 mA AC
max.
Approx. 10 k to
approx. 40 k
(see note 4)
0 to approx.
1.3 k
4 k to
(for 2 km)
0.5 k to
(for 4 km)
Approx. 100 k to
Approx. 4 k to
2 km max.
4 km max.
50 m max.
1 km max.
Controlling materials
and operating
conditions
For control of
ordinary purified water or
sewage water
Supply voltage
24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz
Operating voltage
range
Interelectrode
voltage
8 VAC
Interelectrode
current
Approx. 1 mA AC max.
Power consumption
Interelectrode
operate resistance
0 to approx.
4 k
Interelectrode
release resistance
Approx. 15 k to Approx. 15 k to
Response time
Operate:
Release:
Cable length
(see note 2)
1 km max.
Control output
Ambient temperature
Ambient humidity
Insulation resistance
(see note 3)
Dielectric strength
(see note 3)
Life expectancy
Note:
0 to approx. 4 k
80 ms max.
160 ms max.
600 m max.
1. The relay in the 61F-GP-NH de-energizes when there is water present across the Electrodes, whereas the relay in the 61F-GPN8HY energizes when there is water present across the Electrodes.
2. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become
shorter as the cable diameter or number of conductors becomes larger.
3. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power
terminals and contact terminals, and between Electrode terminals and contact terminals.
4. Possible to use with 10 k or less, however, this may cause reset failure.
9--16
61F
61F
Internal Circuit Diagrams
61F-GP-N/-NT/-NL/-ND
61F-GP-NH
24 V Control circuit
24 V Control circuit
8V
8V
U
11
S0
S1
E3
E1
Ta1 Tc1
Note:
10
1
Tb1
Ta2 Tc2
11
Tb2
S0
S1
E3
E1
Ta1 Tc1
10
Tb1
Ta2 Tc2
8
Tb2
When applying a self-holding circuit, short between terminals 5 and 6 and use terminal 7 as E2.
Connections
61F-GP-N
2. Drainage
Water drainage
Water supply
P
Pump OFF
Pump ON
Indicator ON
E1
Indicator OFF
E2
Indicator ON
E1
Pump ON
Indicator OFF
E2
E3
E3
and starts when the water level drops below E2 (indicator OFF).
Pump OFF
61F-GP-N
5
4
MCCB
0V
Control circuit
24 V
8V
200 V
10
11
2
(See note 1
below.)
Contactor
(See note 2
below.)
THR
PS-3S
Water tank
E1
E3
Note:
Stop
Start
1. The diagram shows the connections for the water supply. When draining, change the connection from terminal 1 to terminal 11.
2. Be sure to ground terminal 4.
9--17
E2
61F
61F
Connection with Three-phase Four-line Circuit
When supplying power from N-phase to the Controller in three-phase four-line circuit, refer to the following diagrams.
Line voltage (R-S, S-T, or R-T):
380 or 415 VAC
Phase voltage (N-R, N-S, or N-T): 220 or 240 VAC
61F-GP-Nj 220 or 240 VAC
61F-GP-N
U
Power source
380 or 415 VAC
R S T N *
0V
Control circuit
24 V
8V
Source voltage:
between 3 and 9
220 or
240 V
10
11
(See note 1)
Electromagnetic switch
Water
tank
Stop
Start
E1
E2
*(See note 2 )
E3
Note:
1. The diagram shows the connections for the water supply. When draining, change the connection from terminal 1 to terminal 11.
2. Be sure to ground terminal 4.
9--18
61F
61F
Accessories (Order Separately)
Electrode Holders
Applications
Mounting style
Flange
Screw
Flange
Insulator material
Phenol resin
Ceramics
Max. temperature
70C max.
150C max.
Appearance
PS-3S(R)
PS-4S(R)
PS-5S(R)
BF-1
BF-3(R)
BF-4(R)
BF-5(R)
PS-31
Heat resisting
temp.
Heat resisting
temp.
(see note 2)
No.
o of
o
El t d
Electrodes
Note:
---
---
BF-1
---
PS-31
---
---
---
---
---
1. Those with the suffix R in their model name are for 2-wire circuits.
2. The Electrode material for PS-31 is SUS304. (Length: 300 mm)
Applications
Mounting style
Screw
Insulator material
Teflon
Max. temperature
Appearance
Maximum tightening
torque at the terminal:
14 kgDcm (137.2 N)
Material at tightening section: iron (standard),
SUS304, SUS316
No.
o of
o
El t d
Electrodes
Note:
9--19
1.
2.
3.
4.
When corrosion
resistance is required.
Since Teflon is used as
the main part, the
Electrode is free from rust
and corrosion. Ideal for
liquid level control in food
processing, level control
of strong alkaline liquids,
etc.
Withstand pressure:
981 kPa {10 kg/cm2}
-----
Heat resisting
temp.:
150 _C
150C max.
SUS
Hastelloy
titanium
Heat resisting
temp.:
250 _C
BS-1
BS-1T
PH-1
---
---
---
---
PH-2
The BS-1 and BS-1T are pressure-proof models. The rest of models are not pressure-proof.
The BS-1 that uses SUS304 for clamping sections and screws of PT1/2 specifications is called BS-1S1.
The BS-1 that uses SUS304 for clamping sections is called BS-1S and one that uses SUS316 is called BS-1S2.
When using the BS-1T in liquids with low specific resistance, provide a large clearance between Electrodes. This clearance must be
varied depending on the specific resistance, for example, approximately 1 m for acid or alkali liquids.
61F
61F
Electrodes, Connecting Nuts, and Lock Nuts
Applicable
pp cab e
li id
liquids
Material
ae a
Electrode
ec ode
assembly
bl
Electrode (1 m long)
Model
Model
Indication
mark
Connecting nut
Model
Inscription
Lock nut
Model
Spring
washer
Inscription
Model
Purified city
water,
industrial
water,
sewage
Equivalent
to SUS
304
(AISI-304)
F03-60
SUS201
F03-01
SUS201
1 line
F03-02
SUS201
---
F03-03
SUS201
---
F03-04
SUS201
Purified city
water,
industrial
water,
sewage,
dilute alkaline
solution
SUS316
(AISI-316)
F03-60
SUS316
F03-01
SUS316
2 lines
F03-02
SUS316
F03-03
SUS316
316
F03-04
SUS316
Sodium
hydroxide,
acetic acid,
dilute sulfuric
acid, dilute
hydrochloric
acid
Hastelloy
B
F03-60
HASB
F03-01
HASB
3 lines
F03-02
HASB
F03-03
HASB
---
Sea water,
ammonia
water, nitric
acid
Hastelloy
C
F03-60
HASC
F03-01
HASC
4 lines
F03-02
HASC
F03-03
HASC
---
Acetic acid,
dilute sulfuric
acid, sea
water
Titanium
F03-60
CHITAN
F03-01
CHITAN
5 lines
F03-02
CHITAN
F03-03
CHITAN
---
Note:
Material
indication
mark
5. When long Electrodes are required, connect them with connecting nuts and lock nuts (2 pieces) every 1 m.
Electrode Separators
No. of Electrodes
Model
F03-14 1P
F03-14 3P
F03-14 5P
When the required length of Electrode is more than 1 m, use a Separator at each joint of two Electrodes so as to prevent the Electrodes
from contacting one another.
Use a one-pole type for BF Electrodes. The five-pole type can be
used for PS-5S and PS-4S Electrodes.
Material: Ceramic
Electrode Holder
Separator
Separator
Connecting nut
Spring washer
Lock nut
Electrode
9--20
61F
61F
Electrode Band
Sheath:
Core:
Length:
Vinyl chloride
0.3 dia. x 21, straight wire, SUS304
50 m max. (When ordering, specify the length by meters.)
The Electrodes come in three types: 3P, 4P, and 5P. Each of them
require the following accessories that are separately sold.
ccesso es
Accessories
Electrode
Weight
eg
(
(per
1)
3P
4P
Application Example
5P
Connecting
nut
Approx.
20 g
Weight
Approx.
50 g
3 to 4
4 to 6
5 to 8
End cap
Approx.
1g
Insulation
Cap
Approx.
10 g
Adhesive
Approx.
5g
Electrode
Band weight
(1m)
---
Approx.
110 g
Approx.
140 g
Approx.
180 g
Weight
Electrode Band
End cap
Other Accessories
F03-11 Protective Cover
Use this Cover for PS-series Electrode
Holders with Mounting Frames (upper one
in the following illustration), This Cover can
also be used when installing the BF-series
Electrode Holders outdoors. Since this
Cover is not water-proof, water or dust may
enter through the wire hole (lower one
below).
Applicable Electrode Holders:
BF-3, BF-4, BF-5, PS-3S(R), PS-4S(R),
PS-5S(R)
Weight:
approx. 65g
Operating
temp.: --10C
to 70C
60
80
100
60
10
Four, M5 x 25
mounting
screws
70
96
112 dia.
72 dia.
82 dia.
120 dia.
Mounting Frame embedded into concrete
Electrode
Commonly used with
Mounting Frame
Two, M5 x 25
mounting screws
Electrode
Electrode
9--21
61F
61F
Mounting
PS-3S Electrode Holders
1. Mounting Electrode Holder
Screw the Electrode Holder into the Insert each Electrode into the connecting Fit the Electrode section into the
coupling secured at the installation
location.
Connect the leads, inserted through the Check the Electrode section for proper
hole of the rubber bushing, into the
respective terminals.
Twin
clockwise
Electrode section
housing
Electrode
Holder
Electrode
section
housing
Rubber
bushing
Electrode
Electrode
Holder
Lock nut
Coupling
Note:
Clamp screw
Electrode
3.
Connecting nut
1.
2.
Electrode
Note:
Lock nut
2.
Spring washer
Connecting nut
4.
Lock nut
1.
3.
4.
PH-1/PH-2 Electrodes
PH-1
(See Notes 1 and 2)
PH-2
E2
(white)
E3
(black)
E1
(white)
Note:
Control range
200 mm max.
Control range
5 mm
9--22
61F
61F
Electrode Bands
Connecting Electrode Holder and Electrode Band
Mounting Weight(1)
Connect the connecting nut to the Electrode section as shown in the illustration below
and secure the connecting nut with the clamp screw. Insert the Electrode Band into the
lower hold of the connecting nut, and tighten the two clamp screws so that the
conductor in the Electrode Band will come into contact with the connecting nut. Then
mount the Electrode Holder to the Electrode section and secure them with two
mounting screws, which are provided with the model.
Drip-proof
cover
Connecting nut
(SUS304)
Electrode
section
housing
Securing
screws
Connecting
nut
Electrode Band
Electrode
Band
Electrode
Holder
Electrode
band
Guides
F03-10
Adhesive
In purified city water, if the distance between the long Electrode (E3) and short Electrode (E1) is more than 50 cm, install another
Electrode Band Weight as E3 in the vicinity of E1 at intervals of 15 to 20 cm, referring to Mounting Weight (2) above. An Insulation Cap
is not needed for the long Electrode.
E1 (short)
Insulation Cap
Control range
E3 (long)
Insulation Cap
End cap
9--23
E3 (long)
61F
61F
Mounting the Protective Cover on the
PS-series Electrode Holder
Remove the two mounting screws (M5 x 25) of the BF-series Electrode Holder and attach the two cap screws (M5 x 25) supplied with
the F03-11 Protective Cover.
Next, put the Protective Cover over the top of the BF-series Electrode Holder, and then tighten the supplied two screws (M3 x 20 with
washers). Refer to the following illustration.
Protective Cover
Tighten here
Secure with the
claw of the cover
PS-series Electrode
Holder
M3 x 20
Washer
Protective Cover
Cap screw M5 x 25
Dimensions
Note:
Standard Models
61F-G--AP*
M3 screw
Mounting Holes
Four, 6-dia mounting holes
61F-G1--AP*
61F-G2
61F-I
Mounting Holes
M3 screw
Note:
9--24
61F
61F
61F-G3
M3 screw
Mounting Holes
61F-G4
M3 screw
Mounting Holes
Four, 6-dia mounting holes
Plug-in Models
61F-GP-N
61FGP-N
PF113A-E
Electrode Holders
PS-3S/-4S/-5S
PS-3SR/-4SR/-5SR
(see note)
9-dia. rubber
bushing (inner)
Mounting Holes
Used with
coupling
34 dia.
65 dia.
hole
With
Mounting
Bracket
9--25
The PS-3SR, PS-4SR, and PS-5SR have built-in resistor of 6.8 k and used for the two-wire 61F models.
61F
61F
PS-31
Mounting Holes
11 dia.
Weight: approx. 325 g
Electrode
SUS304
Rubber
packing
M3
29.5 dia.
Note:
Weight: approx. 20 g
BF-1
Mounting Holes
Two M5 x 25
Terminal bolt Cast iron mounting screws
SUS201 (M6)
Nut (M6)
26-dia. hole
20 dia.
BF-3/-3R
BF-4/-4R
BF-5/-5R
BF-3
Weight: approx. 420 g
BF-3R
Weight: approx. 425 g
Two, 6-dia. holes
Mounting Holes
64-dia. hole
Three, 26-dia.
holes
BF-4
Weight: approx. 520 g
BF-4R
Weight: approx. 525 g
Cast iron
Terminal bolt
Nut
SUS201
Mounting Holes
Two, M5 x 25
mounting holes
M6
Four, 26-dia.
holes
Two, 6-dia. holes
BF-5
Weight: approx. 710 g
BF-5R
Weight: approx. 715 g
Mounting Holes
Two, 6-dia. holes
Five, 26-dia.
holes
110 dia.
9--26
61F
61F
BS-1
Weight: approx. 70 g
Terminal bolt
SUS304 (M4) P=0.7
Mounting Holes
Two, M4
24 dia.
Nut (iron)
M18 P=1.5
(fine screw thread)
Terminal bolt
SUS304
SUS316
Titanium
Hastelloy B
Hastelloy C
BS-1T
Mounting Holes
M4 nut Width between
SUS304 flats: 20.5
Two, M4
24 dia.
Hastelloy
titanium
M18 P=1.5
(fine screw thread)
Material
SUS304
SUS316
Titanium
HAS B
HAS C
Weight
Approx. 55 g
Approx. 55 g
Approx. 45 g
Approx. 65 g
Approx. 60 g
PH-1
PH-2
19 dia.
Single-core
cable
21.7
dia.
5 dia.
Two-core
cable
Electrode Separators
F03-14 1P for one pole
6.5 dia.
Three, 7 dia.
Five, 7 dia.
20
20
28 dia.
Weight: Approx. 15 g
41
Weight: Approx. 30 g
9--27
46
Weight: Approx. 30 g
61F
61F
Electrode Bands
F03-05 3P, 4P, 5P
Black printing
(1 mm wide)
5.5 dia.
5 dia.
8 dia.
Application Examples
Level control in tanks, reservoirs, sewage plants, underground
wells, mixing plants etc.
! Caution
In case of the 61F-HSL ultra high-sensitivity variable model,
malfunction due to electric corrosion may occur in the DC electrode circuit. Be careful not to use the product in such a way
where current constantly flows between electrodes.
Table 1 Water Resistivity Values
(Japanese Reference Values)
Water type
Resistivity
City water
5 to 10 k S cm
Well water
2 to 5 k S cm
River water
5 to 15 k S cm
Rain water
15 to 25 k S cm
Sea water
0.03 k S cm
Sewage
0.5 to 2 k S cm
Distilled water
9--28
61F
61F
Table 2 Detectable Resistivity Ranges
Resistivity (recommended
values)
City water
5 k S cm max.
Well water
10 k S cm max.
River water
10 k S cm max.
67 to 200 S/cm
Low-sensitivity models
Rain water
10 k S cm max.
40 to 67 S/cm
2-wire models
Sea water
10 to 30 k S cm
33,300 S/cm
General-purpose models
Sewage
10 to 30 k S cm
High-temperature models
Distilled water
30 to 200 k S cm
High-sensitivity models
(compact plug-in models)
High-sensitivity models
(standard models)
30 to 300 k S cm
100 to 10 k S cm
Model
Note:
Conductance
Water type
Precautions
! WARNING
Never touch any of the terminals. Doing so may result in electric shock.
Never attempt to disassemble the 61F or touch the inside of
the 61F while the power is being supplied. Doing so may result
in electric shock.
Correct Use
9--29
Ground Correctly
Ground the common Electrode terminal to reduce the effects of
noise.
61F
61F
Consider the Operating Level
Due to the liquid type and fluctuations in the power supply voltage,
the operating level may fluctuate to a small degree from the level at
which the liquid surface makes contact with the Electrode tip.
Use Separators
If the Electrode length reaches 1 m min., insert Separators at the
joint positions to prevent the Electrodes touching each other in the
liquid.
8 VAC
8 VAC
Electrode Holder
Separator
R
61F
So
S2
61F
So
Tape
100 mm
S2
Cautions on Electrodes
Be sure to disconnect the 61F before conducting a insulation test on
the Electrode circuit for inspection purposes.
When cutting an Electrode, be sure to chamfer cut surfaces of the
electrode.
1m
1m
E1
E2
E3
50 mm min.
Bottom of tank
Thickness of contaminants
collected between cleanings
9--30
61F
61F
Drill an approximately 10-dia. vent hole at the top of the pipe.
Using an Anti-ripple Pipe:
Use an anti-ripple pipe as shown below in cases where large ripples
are produced by a rapid fluid flow rate.
E1 E2 E3
Tester
PS-jS
Ground
Tester
E3
mA
9--31
Ground
E1
E3