TX-I/O
Universal modules
CM2N8173en_08
2014-01-10
TXM1.8U
TXM1.8U-ML
Separate terminal base and plug-in I/O module for convenient handling
Self-establishing bus connection for maximum ease of installation
Terminal isolation function for fast commissioning
I/O module replaceable in seconds, without rewiring and without affecting
the full functioning of the remaining I/O modules
All terminals are directly on the I/O modules, allowing direct connection of
field devices without additional terminal strips.
Building Technologies
Functions
The modules support the following I/O functions:
Function
Signal type
Signaltyp
Description
Status signal
BI NO
BI NC
BI Pulse NO
BI Pulse NC
D20
D20R
D20S
CI El (100Hz)
CI Mech (10/25Hz)
AI 0-10V
C
U10
AI 2500 Ohm
R2K5
Resistance
2500
AI Ni1000 extended
Ni1K
Temperature sensor
AI Ni1000
R1K
Temperature sensor
AI PT1K375
Pt1K 375
Temperature sensor
Pt 1000 (USA)
AI PT1K385
Pt1K 385
Temperature sensor
Pt 1000 (Europe)
AI Pt1000
P1K
Resistance
AI T1 (PTC)
T1
Temperature sensor
PTC
AI NTC10K
NTC10 K
Temperature sensor
NTC 10 K
AI NTC100K
NTC100 K
Temperature sensor
NTC 100 K
AO 0-10V
Y10S
Status pulses
Counter pulses
Voltage,
resistance and
temperature
Proportional
output signal
Compatibility
Support of signal types and functions in different building automation and control
systems: see TX-I/O Engineering and installation manual, CM110562
Type summary
ASN
Delivery
The terminal base and the electronic plug-in unit are interconnected and delivered in
the same box.
Accessories
The available accessories include address keys, label sheets, and spare transparent
label holders. Refer to data sheet CM2N8170.
2/10
Siemens
Building Technologies
CM2N8173en_08
2014-01-10
The I/O status LEDs (green) indicate the status of the inputs and outputs (peripheral
devices)
They are also used for diagnostics
Address key
3/10
Siemens
Building Technologies
CM2N8173en_08
2014-01-10
Warning
Pressing an override button in the middle enables or disables the local override
Pressing "+" or "" respectively increases or reduces the output value.
Only outputs can be overwritten. Any attempt to overwrite an input results in an error
indication.
The yellow "Override" LED indicates that local override is active
The following information is displayed for each I/O point:
Configured signal type
Symbolic display of process value
Information for diagnostics.
All safety-relevant functions must be implemented with external solutions
The local override must not be used for safety shutdown operations
In compliance with the standard (ISO 16 484-2, Section 3.110), the module
executes all local overrides directly, without safety precautions or interlocks.
Full responsibility lies with the operator.
Module labeling
The plug-in I/O module has a removable transparent cover (the label holder) for
insertion of a label.
8172z11
Disposal
The device is classified as waste electronic equipment in terms of the European Directive 2002/96/EC (WEEE) and should not be disposed of as unsorted municipal waste.
The relevant national legal rules are to be adhered to.
Regarding disposal, use the systems setup for collecting electronic waste.
Observe all local and applicable laws.
4/10
Siemens
Building Technologies
CM2N8173en_08
2014-01-10
Number
CM110561
CM110562
CM110563
Mounting
Permitted orientation
Technical data
Supply
(bus connector on side)
Operating voltage
Extra low voltage SELV or PELV
in accordance with HD384
Max. power consumption
TXM1.8U
TXM1.8U-ML
DC 21.5 ... 26 V
Protection
Field devices
Insulation resistance
Measuring cables
The of the connected field devices against mains voltage must comply with the
requirements for safety extra-low voltage (SELV) or protection by extra-low voltage
(PELV) as per HD 384.
Cable material
Solid or stranded copper wire
Cable cross section
See manual CM110562
Permitted cable length
max. 300 m
AC/DC output
(field supply)
Voltage
Admissible current per module
Fuse
1.5 W
1.8 W
AC / DC 12 ... 24 V
Max. 4 A
(total for all 4 terminals)
T 10A, in power supply
module/bus connection module
5/10
Siemens
Building Technologies
CM2N8173en_08
2014-01-10
Digital inputs /
counter inputs
Digital inputs are not electrically separated from the system electronics.
Mechanical contacts must be volt-free.
Electronic switches must comply with SELV / PELV standards.
Counter inputs faster than 1 Hz that are routed for more than 10 m in the same
trunking as analog inputs must be shielded.
Contact sensing voltage
Contact sensing current
Contact resistance with contacts closed
Contact resistance with contacts open
Min. closing /
opening time [ms]
including bouncing
60
30
20
..5
Maintained contact
Pulse contact
Mechanical counter
electronic counter
Analog inputs
DC 21.5 ...25 V
1.0 mA (initial current 6 mA)
Max. 200
Min. 50k
Max.
bounce time
[ms]
20
10
10
..0
Max. Counting
frequency
(symmetric)
25 Hz
100 Hz
9
counter memory
1 (calibrated In module)
Range
0...2500 Ohm
0...2500 Ohm
Resolution
100 mOhm
100 mOhm
AI PT1K 375
AI PT1K 385 1)
AI NI1000 extended 1)
AI Ni1000
AI T1 (PTC)
1)
AI NTC10K
1)
AI NTC100K
1)
-50180
-50...400 (600) C
-50150 (180) C
-50...150C
-50...130 (150) C
(-40...115 C)
(-40 ...125 C)
-52.5...185.0 C
-52.5...610C
-52.5...185.0 C
-52.5...155.0 C
-52.5...155.0 C
-52.5...155C
-52.5...155C
10 mK
20 mK
10 mK
10 mK
10 mK
10 mK (25C)
10 mK (25C)
-1.5...11.5 V
1 mV
1)
1)
1)
1)
1)
Voltage measurement
AI 0-10V 2)
0 ... 10 V
2)
2) In case of open connection: negative voltage 3.1 V, 0.05 mA (open circuit detection)
Analog outputs
Output voltage
Output current
Signal type
AO 0-10V
Connection terminals
Mechanical design
Solid conductors
Range
0 10 V
max. 1 mA
Resolution
1 mV
6/10
Siemens
Building Technologies
CM2N8173en_08
2014-01-10
Classification to EN 60730
Housing
protection standard
Ambient conditions
Product standard
Automatic electronic controls for
household and similar use
Electromagnetic compatibility
Immunity (domestic & industrial)
Emissions (domestic & industrial)
CE conformity
EMC Directive
C-tick conformity (EMC)
UL approbation
Type 1
2
Protection class III
IP30
IP20
To IEC 60721-3-3
Class 3K5
5 ... 50 C
5 95 % rh
Class 3M2
To IEC 60721-3-2
Class 2K3
2570 C
5 95 % rh
Class 2M2
EN 60730-1
EN 60730-1
EN 60730-1
2004/108/EC
AS / NZS 61000-6-3
UL 916, UL 864
Environmental compatibility
Color
Dimensions
Weight
179 / 200 g
202 / 223 g
7/10
Siemens
Building Technologies
CM2N8173en_08
2014-01-10
U
(1)
2
(2)
4
(3)
8
10
K2
K1
(4)
14
12
K3
(5)
16
19
21
K4
S5
Terminal layout
I/O point
1)
()
(+)
System neutral
Input
STOP
Counter inputs
Analog inputs
(1)
2
4
8174z13
Digital inputs
U
K1
K2
K3
K4
S5
Universal module
Status contact (N/O)
Status contact (N/C)
Pulse contact (N/O)
Pulse contact (N/C)
Electronic switch
TXM1.8U, TXM1.8U-ML
(2) (3) (4) (5) (6) (7)
6
10 14 19 23 27
8
12 16 21 25 29
(8)
31
33
Counter inputs faster than 1 Hz that are routed for more than 10 m in the same trunking
as analog inputs must be shielded.
U
(1)
(2)
U
B1
B2
R3
B4
(3)
8
10
12
B5
B1
B2
Universal module
LG-Ni 1000 temperature sensor
Pt 1000 temperature sensor
Resistance-type sensor
Active sensor with external supply
External supply must NOT be earthed
(earth loop)
Active sensor with AC / DC supply
R3
U
(1)
(2)
4
V
7
B4
B5
8173z14
Terminal layout
I/O point
1)
Measuring neutral ()
Input
(+)
AC / DC sensor supply voltage
TXM1.8U, TXM1.8U-ML
(1) (2) (3) (4) (5) (6) (7) (8)
2
6
10 14 19 23 27 31
4
8
12 16 21 25 29 33
2)
Selected from: 7, 15, 24, 32
8/10
Siemens
Building Technologies
CM2N8173en_08
2014-01-10
.
.
.
Analog outputs
U
(1)
(2)
4
V
7
12
10
Y3
Y1
Y2
Y3
8173z15
U
Y1
Y2
(3)
Terminal layout
I/O point
1)
System neutral ()
Output
(+)
AC / DC operating voltage
1)
2)
Caution!
2)
(1)
2
4
Universal module
Actuator with input DC 0 ..10 V
General device with input
DC 0 ..10 V, supplied by module
General device with input
DC 0 ..10 V, supplied externally
External supply must NOT be
earthed (earth loop)
TXM1.8U, TXM1.8U-ML
(2) (3) (4) (5) (6) (7) (8)
6
10 14 19 23 27 31
8
12 16 21 25 29 33
2)
Selected from: 7, 15, 24, 32
All measuring / system neutral terminals are interconnected, not in the terminal base
but in the plug-in I/O module. When this unit is pulled outward (into the "parking"
position) there is no connection.
The system neutral of a digital input can be connected to any system neutral
terminal
With analog inputs and outputs, the measuring / system neutral must always be
connected to the terminal associated with that I/O point.
All AC/DC 24V supply terminals are interconnected
(in the I/O module, not in the terminal base).
They are protected in the power supply module / bus connection module (T10A).
Wiring of the AC/DC 24 V supply (terminals 7, 15, 24, 32):
Use cable cross section suited for 10 A according to local regulations.
For wiring details refer to the TX-I/O Engineering and installation manual, CM110562.
9/10
Siemens
Building Technologies
CM2N8173en_08
2014-01-10
Dimensions
Dimensions in mm
90
67
77.5
22
44
70
45
98
108
64
8172M01
7.1
10/10
Subject to change