GENERATOR BUILDING - Precast Plank

Roof LL =
Roof DL =
Roofing Material DL =
Equipment Load =

20
97
15
10

psf
+
10 psf (Bottom Roof LL)
psf (16" thick plank without topping)
psf (Insulation+covering)
psf (See below sketch for location) (Equipment load replaces RLL where
equipment exists)
Wind Load = See the below sketch

Roof DL + Roof material =

112 psf

Roof LL =
30 psf
at Bottom Plank
+109.81 psf
-166.49 psf

Average wind pressure = 72.34psf +109.81 psf


-166.49 psf

+60.22 psf
-109.81 psf

Wind Load from C&C wind load


27.2'

4.4'

4.4'

36'-0"

ADDITIONAL LOAD FROM RADIATORS ON THE ROOF:


Weight of each radiator =
Number of Radiators=
Load at each support=

18.1 kip
2
4.53 kip

The load of each radiator will be shared by four supporting legs

Additional load due to wind on the radiators=

1.84kip

4.53kip

1.84 kip

-1.84kip

1.84kip

4.53kip

10'-10"

4.53kip

2'-4"

-1.84kip

4.53kip

UDL=0.17klf

10'-10"

36'-0"

Calculations
Page 1 of 10

PF - 6.6.#

Client:

Sheet:

Project:

Date:

Description:

Calculations
Page 2 of 10

of

Job No:
Chkd By:

PF - 6.6.#

CALCULATIONS
Client:

Sheet:

Project:

Date:

Description:

Job No:

of

Chkd
By:

GENERATOR BUILDING - Precast Plank

Roof LL =
Roof DL =
Roofing Material DL =
Equipment Load =

20
76
15
10

psf
+
10 psf (Bottom Roof LL)
psf (10" thick plank without topping)
psf (Insulation+covering)
psf (See below sketch for location) (Equipment load replaces RLL where
equipment exists)
Wind Load = See the below sketch

Roof DL + Roof material =

91 psf

Roof LL =
30 psf
at Bottom Plank
+109.81 psf
-166.49 psf

Average wind pressure = 78.4psf


+60.2 psf
-109.81 psf

+109.81 psf
-166.49 psf
Wind Load from C&C wind load

15.2'

4.4'

4.4'

24' - 0"

From load combination


calculations:

Uniform load =
Uniform load =

148.78 psf
-23.76 psf

downward
uplift

Span. L

24.3 ft

* Assume that the plank width is 4ft.


Check for Moment Capacity:
Max Mu = 10.982 k.ft
Use

10

<

Mn =

25.76 k.ft

inch Thick Precast Plank

Check for Superimposed Load Capacity:

Actual Superimposed Load= 72.78 psf


Calculations
Page 3 of 10

<

Allowable Superimposed Load=

169 psf

PF - 6.6.#

Client:

Sheet:

Project:

Date:

Description:

Job No:

of

Chkd
By:

Check for Deflection:


fc'=

4500 psi

Ec=

3823676.24

I=

3484 in^4

psi

Uniform Load at Service level (D + Lr)=


Theorotical Deflection,
Allowable Deflection=

Calculations
Page 4 of 10

=
0.61

146.00 psf
0.09

12.17 psi

inch

Allowable deflection
factor, L/x

480

PF - 6.6.#

CALCULATIONS
Client:

Sheet:

Project:

Date:

Description:

Job No:

of

Chkd
By:

CONTROL BUILDING - Precast Plank


Control Building
Roof LL =
Roof DL =
Roofing Material DL =
Equipment Load =

20
111
15
0

psf
+
10 psf (Bottom Roof LL)
psf (10" thick plank w/ topping)
psf (Insulation+covering)
psf (See below sketch for location) (Equipment load replaces RLL where
equipment exists)
Wind Load = See the below sketch

Roof DL + Roof material =

126 psf

Roof LL =
30 psf
at Bottom Plank
+21.82psf
-73.44psf

+21.82psf
-73.44psf

+21.82psf
-61.93psf

Wind Load from C&C wind load


in Section 1.2
37.67'

3'

3'

43'-8"

Uniform load =
Uniform load =

183.02 psf
176.40 psf

downward
uplift

Span. L

43.66 ft

* Assume that the plank width is 4ft.


Check for Moment Capacity:
Max Mu = 43.609 k.ft
Try

12

<

Mn =

78.48 k.ft

inch Thick Precast Plank

Check for Superimposed Load Capacity:

Actual Superimposed Load= 72.02 psf

Calculations
Page 5 of 10

<

Allowable Superimposed Load=

93 psf

PF - 6.6.#

Client:

Sheet:

Project:

Date:

Description:

Job No:

of

Chkd
By:

Check for Deflection:


fc'=

4500 psi

Ec=

3823676.24

I=

8904 in^4

psi

Uniform Load at Service level (D + Lr)=


Theorotical Deflection,
Allowable Deflection=

Calculations
Page 6 of 10

=
1.09

146.00 psf
0.35

12.17 psi

inch

Allowable deflection
factor, L/x

480

PF - 6.6.#

CALCULATIONS
Client:

Sheet:

Project:

Date:

of

Job No:

Description:

Chkd By:

CONTROL BUILDING - LOAD COMBINATION (ASCE7-10)

Loads:
1 Dead load (12" thick plank w/ topping), D

111 psf

2 Dead load (Insulation + covering), D

15 psf

3 Live Load Roof, Lr

20 psf

4 Live load Roof Bottom Lr

0 psf

5 Wind load, W

Zone 1 Zone 2
21.82
21.82 psf
-61.92 -73.48 psf
0 psf

6 Rain load, R

Average wind load on Control Building precast plank =

21.82 psf
-67.7 psf

LOAD COMBINATION for +ve Wind Pressure

ASD LEVEL (psf)


1

126.00 psf

2
3
4
5
6

D + (Lr or R)
D + 0.75(Lr or R)
D + 0.6W
D + 0.75(0.6W) + 0.75(Lr or R)
0.6D + 0.6W

146.00
141.00
139.09
150.82
88.69
150.82

MAX=

psf
psf
psf
psf
psf
psf

LOAD FACTOR (psf)


1

1.4D

176.40 psf

2
3
4
5

1.2D + 0.5(Lr or R)
1.2D + 0.5(Lr or R) + 0.5W
1.2D + 1.0W + 0.5(Lr or R)
0.9D + 1.0W

161.20
172.11
183.02
135.22
183.02

MAX=
Calculations
Page 7 of 10

psf
psf
psf
psf
psf

PF - 6.6.#

Client:

Sheet:

Project:

Date:

of

Job No:

Description:

Chkd By:

LOAD COMBINATION for -ve Wind Pressure

ASD LEVEL (psf)


1
2
3
4
5
6

D
D + (Lr or R)
D + 0.75(Lr or R)
D + 0.6W
D + 0.75(0.6W) + 0.75(Lr or R)
0.6D + 0.6W
MAX=

126.00
146.00
141.00
85.38
110.54
34.98
146.00

psf
psf
psf
psf
psf
psf
psf

MAX=

176.40
161.20
127.35
93.50
45.70
176.40

psf
psf
psf
psf
psf
psf

LOAD FACTOR (psf)


1
2
3
4
5

1.4D
1.2D + 0.5(Lr or R)
1.2D + 0.5(Lr or R) + 0.5W
1.2D + 1.0W + 0.5(Lr or R)
0.9D + 1.0W

Calculations
Page 8 of 10

PF - 6.6.#

CALCULATIONS
Client:

Sheet:

Project:

Date:

of

Job No:

Description:

By:

Chkd By:

GENERATOR BUILDING - LOAD COMBINATION (ASCE7-10)

Loads:
1 Dead load (16" thick plank w/ topping), D

76 psf

2 Dead load (Insulation + covering), D

15 psf

3 Live Load Roof, Lr

20 psf

4 Live load Roof Bottom Lr

10 psf

5 Wind load, W

Zone 1 Zone 2
60.22 109.81 psf
-109.81 -166.49 psf
28.6 psf

6 Rain load, R

Average wind load on Compressor room precast plank =

78.4 psf
-130.6 psf

LOAD COMBINATION for +ve Wind Pressure

ASD LEVEL (psf)


1

2
3
4
5
6

D + (Lr or R)
D + 0.75(Lr or R)
D + 0.6W
D + 0.75(0.6W) + 0.75(Lr or R)
0.6D + 0.6W

91.00 psf

MAX=

121.00
113.50
138.04
148.78
101.64
148.78

psf
psf
psf
psf
psf
psf

LOAD FACTOR (psf)


1

1.4D

127.40 psf

2
3
4
5

1.2D + 0.5(Lr or R)
1.2D + 0.5(Lr or R) + 0.5W
1.2D + 1.0W + 0.5(Lr or R)
0.9D + 1.0W

124.20
163.40
202.60
160.30
202.60

MAX=
Calculations
Page 9 of 10

psf
psf
psf
psf
psf

PF - 6.6.#

Client:

Sheet:

Project:

Date:

of

Job No:

Description:

By:

Chkd By:

LOAD COMBINATION for -ve Wind Pressure

ASD LEVEL (psf)


1
2
3
4
5
6

D
D + (Lr or R)
D + 0.75(Lr or R)
D + 0.6W
D + 0.75(0.6W) + 0.75(Lr or R)
0.6D + 0.6W
MAX=

91.00
121.00
113.50
12.64
54.73
-23.76
121.00

psf
psf
psf
psf
psf
psf
psf

MAX=

127.40
124.20
58.90
-6.40
-48.70
127.40

psf
psf
psf
psf
psf
psf

LOAD FACTOR (psf)


1
2
3
4
5

1.4D
1.2D + 0.5(Lr or R)
1.2D + 0.5(Lr or R) + 0.5W
1.2D + 1.0W + 0.5(Lr or R)
0.9D + 1.0W

Calculations
Page 10 of 10