Outline of Presentation
I Sprinkler Systems
A. General Requirements
B. Provisions on Specific
Types of Occupancies
FIRE SAFETY
IS OUR MAIN
CONCERN
Outline of Presentation
Outline of Presentation
FIRE
FIRESAFETY
SAFETY
ISISOUR
OURMAIN
MAIN
CONCERN
CONCERN
Definition
FIRE SAFETY
IS OUR MAIN
CONCERN
Definition
Sprinkler System. An integrated network
of hydraulically designed piping system
installed in a building, structure or area
with outlets arranged in a systematic
pattern which automatically discharges
water when activated by heat or
combustion products from a fire.
FIRE SAFETY
IS OUR MAIN
CONCERN
Sprinkler
Systems
FIRE SAFETY
IS OUR MAIN
CONCERN
FIRE SAFETY
IS OUR MAIN
CONCERN
Notification
FIRE SAFETY
IS OUR MAIN
CONCERN
Where required?
1. On Places of Assembly
Section 10.2.8.8.para E
o bars with live entertainment
o dance halls
FIRE SAFETY
IS OUR MAIN
CONCERN
Where required?
1. On Places of Assembly
o buildings containing assembly occupancies with
an occupant load of more than 300 persons
FIRE SAFETY
IS OUR MAIN
CONCERN
Except !!!
Assembly occupancies consisting
of single multipurpose room of
less than 1115 square meters
that are not used for exhibition
or display and are not part of
mixed occupancy
FIRE SAFETY
IS OUR MAIN
CONCERN
Except !!!
All assembly occupancies with all
sides open
Places of worship at the level of
exit discharge with sufficient
means of egress.
FIRE SAFETY
IS OUR MAIN
CONCERN
Where required?
At the ceiling
Under the gridiron
Usable spaces under the stage or platform
In auxiliary spaces
Dressing rooms
Storerooms
Workshops
Where required?
2. On Educational Occupancies
Section 10.2.9.5 para E
o every portion of educational
buildings below the floor of exit
discharge.
FIRE SAFETY
IS OUR MAIN
CONCERN
Where required?
2. On Educational Occupancies
Section 10.2.9.5 para F
o hazardous areas shall be
separated from other parts of
the building by 1-hr fire
resistance rating construction
or shall be provided with AFSS
Where required?
2. On Educational Occupancies
Section 10.2.9.9
o Underground or Windowless
educational buildings shall be
provided completely with AFSS
Where required?
2. On Educational Occupancies
Section 10.2.9.11
Existing educational buildings
o The provision of additional means of
egress, automatic fire suppression
system, area separations, emergency
lighting and other alternate means of
protection may be used to provide
reasonable life safety from fire and
panic.
Where required?
FIRE SAFETY
IS OUR MAIN
CONCERN
Where required?
4. On Residential Occupancies
For Hotels and Dormitories
Section 10.2.12.3 para C number 5
o All buildings shall be protected
throughout by sprinkler system except
where all guest rooms or guest suites
have a door opening directly outside at
the street or grade level or exterior exit
access in buildings up to and including
three (3) storeys in height.
FIRE SAFETY
IS OUR MAIN
CONCERN
Where required?
4. On Residential Occupancies
For Apartment Buildings
Section 10.2.12. para C number 5
o Throughout all buildings except where
all guest rooms or guest suites have a
door opening directly outside at the
street or grade level or exterior exit
access in buildings up to and including
three (3) storeys in height.
FIRE SAFETY
IS OUR MAIN
CONCERN
Where required?
5. On Mercantile Occupancies
Where required?
5. On Mercantile Occupancies
Section 10.2.13.3. para D
o Throughout the floor below the
street floor with an area exceeding
232 square meters when used for
the sale, storage or handling of
combustible goods and
merchandise.
FIRE SAFETY
IS OUR MAIN
CONCERN
Where required?
6. On Business Occupancies
Section 10.2.14.3 para D
number 3 (b)
o High hazard content areas
within the building.
FIRE SAFETY
IS OUR MAIN
CONCERN
Where required?
7. On Industrial Occupancies
Section 10.2.15.3 para D
number 1
o Every high hazard occupancy
FIRE SAFETY
IS OUR MAIN
CONCERN
Where required?
8. On Storage Occupancies
Section 10.2.16.2 para C
o Every high hazard occupancy
FIRE SAFETY
IS OUR MAIN
CONCERN
Where required?
9. On High Rise Buildings
Section 10.2.19.4
o throughout all floor spaces
including every closet and
concealed spaces
FIRE SAFETY
IS OUR MAIN
CONCERN
General Requirements
Section 10.2.6.6.
Design shall be in accordance with
NFPA 14, Standard for the
Installation of Standpipe, Private
Hydrant and Hose Systems.
FIRE SAFETY
IS OUR MAIN
CONCERN
Dry Standpipe
Where required?
Dry Standpipe
Specific Requirements
No point in a building shall be more
than 40 meters travel distance from a
dry standpoint outlet connection.
Dry standpipes shall not be concealed
in building walls or built into pilasters.
FIRE SAFETY
IS OUR MAIN
CONCERN
FIRE SAFETY
IS OUR MAIN
CONCERN
Where required?
Assembly occupancies with an
occupant load exceeding 1000
persons.
Educational, healthcare, business,
mercantile, industrial and hotels and
apartments occupancies, of 4 or more
storeys in height.
FIRE SAFETY
IS OUR MAIN
CONCERN
Specific Requirements
In theaters, auditoriums and other
occupancies, where the occupant load
is more than 1000, outlets shall be
located on each side of the stage, on
each side of the rear of the
auditorium and on each side of the
balcony.
Alternative Measures
Section 14.0.0.4 IRR of RA 9514
In cases of existing buildings which
when forced to comply will
compromise its structural
integrity/stability
The Chief, BFP may accept adequate
alternative and/or remedial fire safety
measures
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Section 14.0.0.4 IRR of RA 9514
Technical
Alternative Measures
MC 2010 - 17
Guidelines in the
Approval of Alternative
and/or Remedial Fire
Safety Measures
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Authority to Grant Approval/
Exemption
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Requirements
Letter
request;
As-built plans;
Occupancy Permit/s;
FSCS/Checklist/Clearance/FSIC;
FSIR/NTC/NTCV
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Requirements
Certification from Structural
Engr that the bldg cannot
support additional load for AFSS;
Proposed Alternative and/or
Remedial Fire Safety Measures;
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Requirements
Fire Safety and Prevention
Program;
Fire Drill Certificate; and
Affidavit of Undertaking
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Procedures
Processing an approval of
application.
2. Issuance of Certificate of
Exemption
1.
FIRE SAFETY
IS OUR MAIN
CONCERN
ACTIVITIES
OWNER
2. Conduct pre-evaluation
and endorse findings to
the Regional Director thru
channel
3. Evaluate the application
and recommend to the
C, BFP thru Chairman,
FSTC
4. Conduct physical
inspection and evaluate
proposed alternative
measures
5. Deliberate the inspection
and evaluation reports
and recommend action to
the C, BFP
6. Approve/disapprove
application.
Persons Responsible
C/MFM
REGIONAL CHAIRMAN,
DIRECTOR
FSTC/FSTC
CHIEF, BFP
2
3
4
5
6
Alternative Measures
Bureau
Order
Name of the building
Location/Address
Name of owner/administrator
Alternative Measures to be
installed/constructed
Conditions of approval
FIRE SAFETY
IS OUR MAIN
CONCERN
ACTIVITIES
1. Request the C/MFM for
an inspection of the
completed fire safety
measures
2. Conduct inspection and
endorse findings to the
Regional Director thru
channel
3. Evaluate the findings and
recommend action to
the C, BFP thru Chairman,
FSTC
4. Conduct physical
inspection and evaluate
compliance with the
approved alternative
measures
5. Deliberate the inspection
and evaluation reports
and recommend action to
the C, BFP
6. Approve/disapprove
application.
OWNER
Persons Responsible
C/MFM
REGIONAL CHAIRMAN,
DIRECTOR
FSTC/FSTC
CHIEF, BFP
2
3
5
6
Alternative Measures
Bureau
Order
Name of the building
Location/Address
Name of owner/administrator
Alternative Measures
installed/constructed
Conditions of approval
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Compliance of Alternative Measures
+
Certificate of approval by the C, BFP
=
ISSUANCE OF FSIC
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Areas of Emphasis
Fire Safety Construction
Occupancy Load
Fire Protection
Means of Egress
Fire Safety and Prevention
Programs
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Fire Safety Construction
1.
2.
3.
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Fire Safety Construction
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Occupant Load
Actual
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Fire Protection
1.
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Fire Protection
2. Provision for 20% increase in fire
extinguishers.
3. Installation of wet and dry standpipe
system.
4. Provision for detection and alarm
system.
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Means of Egress
1.
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Fire Safety and Prevention Programs
Fire Brigade with COC
Compulsory attendance of all members of
fire brigade in seminars conducted in the
building.
Quarterly fire and evacuation drill.
Compulsory attendance of all occupants to
at least 2 seminars conducted in the building.
Compulsory orientation on new tenants of
the building
FIRE SAFETY
IS OUR MAIN
CONCERN
Alternative Measures
Grace Period
Within
FIRE SAFETY
IS OUR MAIN
CONCERN
Thank You!