You are on page 1of 5

AMES/VIL/Q-3085/2015

APRIL 14, 2015

TO,
VIDEOCON INDUSTRIES LTD.
5 MW Comet power Plant,
Osiyan,
Dist:Jodhpur(Rajasthan)
Mo:09649063376
E-mail: premesh.vijayvargiy@videoconmail.com

KIND ATTN: MR.PREMESH VIJAYVARGIY

REF. : Your E-mail Enquiry,Date:14-04-2015


SUB. : Your requirement of Offer for 1600 KVA 33 KV/0.324-0.324 KV
Dry Type Cast resin Transformers.
Dear Sir,
With reference to above, we are pleased to quote our best Offer for design,
manufacturing, testing and supply of 1600 kVA Dry type Cast Resin
Transformers as per following annexures.

1. Specification and fittings

: Schedule A

2. Price, Commercial terms & conditions.

: Schedule B

3. Technical Particulars

: Schedule C

5. List of Customers.
6. Technical Catalogue.

We hope you will find our offer technically acceptable and commercially
economical and assuring you of our best service all the times.

Thanking you.
Yours faithfully,
For, AMES IMPEX ELECTRICALS PVT.LTD.,

AUTHORISED SIGNATORY
Encl. a/a

SCHEDULE A
SPECIFICATION AND FITTINGS

AMES' make 1600 KVA Dry Type Cast Resin Transformer, Voltage ratio 33 KV /
324-324 Volt, 3 Ph, 50 c/s A.C. at NO LOAD suitable for OUTDOOR installation
core type, double COPPER WOUND, self (AN) cooled type. The winding will be
connected in DELTA/STAR-STAR as per vector group ref Dyn11/yn11. The
Transformer will be designed and manufactured generally conforming to
IS:2026/77, IS:11171/85. The tapping of +5% to -5% in steps of 2.5% will be
provided on Primary side by means of manually operated OFF CIRCUIT TAP
CHANGING LINKS. The temp. rise of winding will not exceed 90 Degree
centigrade by Resistance method over an ambient temp of 50 Degree
Centigrade. The class of insulation will be F. Enclosure will manufactured
from 14 SWG MS Sheet Steel. Degree of Protection class for Enclosure shall
be IP-33. Enclosure will painted with Siemens Grey colour.

TERMINAL ARRANGEMENT :[A] PRIMARY


[B] SECONDARY

: Cable End Box.


: Cable End Box

The following fittings will be provided with the Transformer.


[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]

Rating and diagram plate


Lifting Lugs
Jacking Pads
Earthing & terminals
Bi-Directional Plain Rollers.
off circuit tap Changing Links
Primary bushing 36 KV Class
Secondary bushing 1.1 KV Class
Extra Neutral Bushing
Winding Temp. Indicator
PECON MAKE, Model No. TR-7570

For, AMES IMPEX ELECTRICALS PVT.LTD.,

AUTHORISED SIGNATORY

:
:
:
:
:
:
:
:
:
:

1
4
4
2
4
1
3
7
1
1

No.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
Nos.
No.

SCHEDULE B
PRICE, COMMERCIAL TERMS & CONDITIONS
SR.NO
1
2

DESCRIPTION
QUANTITY
UNIT PRICE
(EX-WORKS)

PRICE
VARIATION
PACKING

AS REQUIRED
RS.17,10,000/= (SEVENTEEN LACS TEN THOUSAND ONLY) for
1600 KVA, 33 KV/324-324 V DRY TYPE CAST RESIN
TRANSFORMER.
FIRM PRICE

EXCISE DUTY
& EDU. CESS
SALES TAX

FREIGHT

NOT REQURIED.
ONLY POLYTHELENE WRAPPING WILL BE PROVIDED.
At present E.D. @ 12.5% will be charged extra. However
actual will be charged at the time of dispatch.
At present C.S.T @ 2% against Form C OR Full tax @ 5%
without Form `C will be charged extra. However actual
will be charged at the time of dispatch.
Extra at actual to your account.

INSURANCE

Extra to your account.

DELIVERY

Within 10 to 12 Weeks from the date of PO / receipt of


Approval of Drawing, whichever is later.

TERMS OF
PAYMENT

30% Advance along with P.O. and 70% with 100% taxes and
duties against proforma invoice prior to dispatch.

10

VALIDITY

Our offer is valid for 30 days from the date of offer.

11

INSPECTION

Will be carried out in presence of your engineer or his


authorized representative at our works.

12

GUARANTEE

The equipment offered by us is guaranteed for a period of


18 Months from the date of dispatch or 12 Months from the
date of Commissioning whatever is earlier.

14

UNLOADING

At your stores shall be arranged by you at your cost.

FOR, AMES IMPEX ELECTRICALS P.LTD.,

AUTHORISED SIGNATORY

SCHEDULE C
TECHNICAL PARTICULARS

1. MAKE

: AMES make

2. KVA RATING

: 1600 KVA

3. Type

: Dry Type Cast Resin Transformer

4. Type of cooling

: Air Natural.

5. Duty

: Continuous duty.

6. Application

: Distribution ( OUTDOOR )

7. Primary Voltage

(AC)

: 33 KV

8. Secondary Voltage

(AC)

: 324-324 Volt

9. No of phase

: Three

10.Frequency

: 50 Hz

11.Insulation (HV/LV)

: Class F'

12. Max Temp Rise

: 90 Deg.C over 50 Deg.C Ambient

13. Ambient temperature

: 50 Deg.C

14. Vector Group

: Dyn11/yn11

15. Connection

: Delta /Star-star

16. Tappings (HV Side)


: +5% to -5% in steps of 2.5%
(Off ckt tap changing links)
17. Impedance (+ IS TOLERANCE )

6 %

18. No load loss at Rated


voltage ( + IS Tolerance)

3600 Watts

19. Full load loss at Rated


Voltage ( + IS Tolerance)

: 14500 Watts

20. No load current at rated


Voltage and frequency

: 2 % of Rated current.

21. Efficiency at rated voltage


and frequency (U.P.F)
At 100 %
At 75 %
At 50 %

1600 KVA
: 98.88 %
: 99.03 %
: 99.10 %

22. Regulation at Full load


at 75 Deg.C
At U.P.F
At 0.8 P.F lagging

: 1.082 %
: 4.372 %

23. Installation

: Indoor

24. Weight of transformer (APPROXIMATE)


Core & Winding
: 4500 kg
Enclosure
: 900 kg
Total Weight
: 5400 kg
25. Overall Dimensions (APPROXIMATE)
Length
: 2400 mm
Breadth
: 2500 mm
Height
: 2800 mm

For, AMES IMPEX ELECTRICALS P.LTD.,

AUTHORISED SIGNATORY