Professional Documents
Culture Documents
Guide For
Inspectors
Firestopping
Inspection
Manual
ough
For Thr
Through
P
enetr
ations.
enetrations.
Penetr
Fir
e Resistiv
e Joints,
Fire
Resistive
Perimeter
Fir
e Barrier
Fire
Sy
stems and Fir
e
Systems
Fire
Rated Duct
Enclosur
esSy
stems.
EnclosuresSy
esSystems.
Third Edition
www.firestop.org
Contents
Scope .......... 3
Fire Test Standards ...... 4
Testing Laboratories ........ 5
Building Code Requirements ... 6
Products Overview .... 7
Inspection Process ..... 8
Firestopping and the Codes 14
Inspection Guidelines for Through
Penetration Firestop Systems ........ 15
Inspection Guidelines for Fire
Resistive Joints Systems ......... 17
Inspection Guidelines for Perimeter
Fire Barrier Systems (Curtain Walls) .... 20
Inspection Guidelines for
Fire Rated Duct Enclosures ... 25
Engineering Judgments ...... 28
Glossary ........... 29
UL System Approach .. 32
Seismic Considerations ... 35
Systems Listing Table . 36
Scope
Scope
The term Firestopping, in this manual, will refer to: (1) the
sealing of holes and gaps within a rated assembly, commonly
referred to as Through-Penetration Firestops, (2) the sealing
of linear gaps between rated assemblies, referred to as FireResistive Joint Systems and (3) the sealing of the linear gap
between or along rated floors and rated or non-rated curtain
walls, referred to as Perimeter Fire Barrier Systems. The term
Fire Rated Duct Enclosure will refer to protective systems used
to enclose duct systems penetrating a rated assembly.
The Firestopping Systems are tested to specific test standards.
Through-Penetration Firestops are tested to ASTM E814 or UL
1479, Fire-Resistive Joint Systems to ASTM E1966 or UL 2079
and Perimeter Fire Barrier Systems to ASTM E2307.
Firestopping Systems must be tested to the above criteria by
certified independent third party testing agencies. The Testing
Agencies usually publish the results in proprietary directories,
which are readily available. Some of the more common and well
known testing and approval agencies are Underwriters
Laboratories, Intertek Testing Services, Factory Mutual and
Southwest Research Institute.
Fire Resistive Duct Enclosure Systems, are tested alternatives
to fire resistive shaft enclosures which function to contain fires
that occur inside the duct, prevent fire spread into the ductwork
from an external fire and allow for zero, or reduced clearance to
combustible construction. A tested through penetration firestop
system is required when the duct enclosure system penetrates
3
a rated floor or wall assembly.
INSPECTION
GUIDELINES
INSPECTION GUIDELINES
For
Firestopping
Systems
Applicable Standards
The Test Standards relevant to Firestop Systems are:
1.
2.
3.
4.
5.
6.
7.
8.
9.
Testing Laboratories
There are several independent testing laboratories, also
referred to as third party testing agencies, which conduct the
fire testing of firestop and duct enclosure systems. The fire test
results are usually included as design listings in the fire
resistance directories published by the testing laboratory. These
Directories are an important source of information during the
plan review process and inspection process. The details, system
numbers, manufacturer installation recommendations, and other
design listing information are often referred to on the plan
submittals. A thorough knowledge of the design listing
information is critical to the inspections of firestops and duct
enclosures.
The following are some of the recognized independent
laboratories conducting tests of firestop systems:
1. Underwriters Laboratories Inc., Northbrook, IL
(847) 272-8800 www.ul.com
2. Southwest Research Institute, San Antonio, TX
(210) 522-2311 www.swri.com
3.
4.
Check Points:
NFPA 101, Life Safety Code, NFPA 70, National Electric Code,
and IAPMOs Uniform Plumbing Code (UPC), also include
provisions related to protection of penetrations. The IBC and
NFPA 5000 have explicit requirements for inspection of firestop
systems before they are concealed. The IBC requires that
evidence be submitted to the local official showing that the
materials and methods of construction used to protect
penetrations, joints and ventilation ducts in fire resistance rated
building elements shall not reduce the required fire resistance
rating. The International Fire Code has requirements for periodic
inspection of firestop systems throughout the life of the building.
Check Point:
Have you checked your local code requirements? The IBC,
NFPA 5000 and the Life Safety Code, NFPA 101, include different
requirements for firestop systems to meet certain performance
and testing criteria specific to various construction assemblies.
Check out the IFC website www.firestop.org for latest updates
on firestop systems regulations.
Products Overview
There are four categories of Firestop materials:
Forming/Backing Materials:
o
Mineral Wool Batts;
o
Ceramic Fiber Blankets/Boards;
o
Non-Ceramic Insulation Blankets;
o
Foam Packing/Backer Rod.
Duct and Pipe Covering Materials
Inspection Process
The following is a recommended inspection process based on
interviews across the country with building departments
inspectors who have successfully implemented such a program.
These jurisdictions require that the protection of penetrations,
joints and ventilation ducts not be concealed from view until
inspected and approved. Similar requirements are found in the
IBC (Section 109.3.6, 2006 Edition). Some building departments
collaborate with the fire department to conduct the firestop
systems inspections.
ASTM published ASTM E 2174 Standard Practice for On-Site
Inspection of Installed Fire Stops and ASTM E 2393 Standard
Practice for On-Site Inspection Fire Resistive Joint System and
Perimeter Fire Barriers. These standards shall be referenced
when third party inspections are conducted for penetration
firestop, fire resistive joint and perimeter barrier systems.
Check Points:
Check Points:
10
11
Check Points:
12
The
Inspection
Process
The time allocated for inspections can be drastically
reduced if the proper paperwork is present in advance of
the field inspection. Planning and communication
between the building designer and the installer prior to
construction will save time, costs and resources in
a s s u r i n g t h e a p p l i c a t i o n o f t h e p r o p e r s y s t e m s.
Verification of system testing and listings with a nationally
recognized laboratory, prior to installation in the field, is
key to a smooth inspection process. The costs and time
associated with removing improperly applied materials
can be drastically reduced if the respective through
penetration firestop systems, fire resistive joint systems
and flexible rated duct enclosure documentation is
confirmed prior to installation. Use of applicable ASTM
practices will provide guidelines for inspection of installed
systems.
13
INSPECTION
GUIDELINES
INSPECTION GUIDELINES
14
Firestopping
And The
Codes
Penetrations and Joints Firestopping is a form of passive fire
protection that is required in all penetrated rated assemblies
and the joints between them. The International Code Council
specifies firestopping within Chapter 7 of their International
Building Code. The National Fire Protection Association also
specifies firestopping requirements in its Life Safety Code, NFPA
101, National Electric Code publications and in its NFPA 5000
Building Code.
Fire Resistive Duct Enclosures for grease and HVAC ducts are
tested protection systems which provide 1 and/or 2 hour fire
ratings. The systems are utilized as an alternative to fire resistive
rated shaft construction and also permit zero, or reduced,
clearance to combustible materials. The International Code
Council specifies fire resistive duct enclosures in Chapter 5 of
their International Mechanical Code (IMC). Requirements are
also contained in NFPA 96, and IAPMO (UMC). A duct enclosure
system penetrating a rated assembly should also be properly
firestopped.
Step One:
Verify the documents and submitted drawings reference
applicable through penetration assemblies containing
sealants, devices and/or other materials tested to ASTM E814
or UL 1479 by accredited testing agencies. These systems
should be published and readily available via the internet or
other means. Such listings are found in section XHEZ within
Volume 2 of Underwriters Laboratories Inc. Fire Resistance
Directory or Warnock-Hersey and OPL Mark Product
Directory.
Reason: There are many different types and
combinations of through penetrations, coatings,
sealants and devices that have not been proven to
maintain or restore the rating of the assembly through testing to
ASTM E814 or UL 1479.
Step Two:
Verify that the Through-Penetration System being used has been
tested to the hourly rating necessary ie. 1 hr., 2 hr., etc., and
with the type of assembly being penetrated.
Reason: The building codes require that the rating
of a firestop system shall not be less than the fire
resistive rating of the penetrated assembly. Concrete,
gypsum and wood assemblies all behave differently in a fire.
INSPECTION
INSPECTION
GUIDELINES
GUIDELINES
For Through
Penetration
Firestop Systems
INSPECTION GUIDELINES
15
Step Three:
As an overview of these steps, verify the parameters indicated
in the system are the same as those installed in the field:
(Download checklist form from the IFC web site
www.firestop.org).
A. Is the through penetration system rated for the type and nature
of assembly (thickness of concrete, stud width, etc.)?
B. Is the rating of the through penetration system equal or
greater than the assembly penetrated?
C. Do the supplied products have labels from a recognized
quality assurance agency?
D. Does the field installation follow the listing?
a. For the size of opening prior to firestopping?
b. Nature and quantity of penetrant(s), (material, size,
diameter, insulation type & thickness, etc.)?
c. Annular space requirements, (minimum, maximum,
nominal, etc.)?
d. Specified forming, packing or backing material, (when
required)?
e. Specified sealant, coating, device or firestopping
product indicated, (type, amount, depth, location, etc.)?
f. Specified accessory items, (anchors, fasteners,
securing devices, plates, etc.)?
Reason: Deviations from a listed and labeled design
will likely result in a failure of the installed system.
Consult manufacturer for validation.
16
Step One:
Verify the documents and submitted drawings reference
legitimate, fire resistive joint systems tested to ASTM E1966 or
UL 2079 by accredited testing laboratories or certified third party
testing agencies. These systems should be published or readily
available via the internet or other means. Such listings can be
found in section XHBN within Volume 2 of Underwriters Laboratories
Inc. Fire Resistance Directory or Omega Point Laboratories
Directory of Listed Building Products, Materials & Assemblies.
Reason: Many coatings, sealants and configuration
of materials have never been tested in joint systems
and should not be applied to such applications.
Step Two:
Verify the documents and submitted drawings reference whether
the joint is static (not subject to movement) or dynamic, (subject
to movement). Virtually all joints are intended to be dynamic.
Reason: A static joint design, (e.g. FF-S, HW-S, FWS) should not be applied to a dynamic joint condition.
A dynamic joint design, (e.g. FF-D, HW-D, FW-D),
however, may be applied to a static condition.
INSPECTION
GUIDELINES
INSPECTION GUIDELINES
17
Step Three:
If the joint is dynamic, as in most cases, verify the documents
and submitted drawings reference systems that have been tested
for the required amount of movement. A system listing a nominal
1 inch joint width with 25% compression or extension, actually
allows for a movement of of compression and of extension.
Reason: Building code language requires that joint
systems be capable of handling expected building
movement. Joint systems not tested for the required
movement will likely fail after installation.
Step Four:
If the joint is dynamic, verify the documents and submitted
drawings reference joint systems that have been tested for the
class/type of movement.
Class I - Thermal (500 cycles at 1 CPM)
Class II - Wind Sway (500 cycles at 10 CPM)
Class III - Seismic (100 cycles at 30 CPM)
Combined (100 at 30 CPM & 400 at 10 CPM)
Reason: The installed joint shall be cycle tested for
the appropriate application.
Step Five:
Verify the rating of the joint system is greater than or equal to
the rating of the assemblies it is connecting.
18
Step Six:
As an overview of these steps, verify the parameters indicated
in the system are the same as those installed in the field:
(Download checklist form from the IFC web site www.firestop.org)
A. Is the joint system tested and listed?
B. Is the joint static or dynamic?
C. If dynamic, is the joint system tested for the amount
of movement required?
D. Is the joint system tested for the class & type of
movement required?
E. Is the rating of the joint equal to or greater than the
assemblies it is adjacent to?
F. If a mechanical system, are the specified tracks
installed in the installation?
G. Do the supplied products have labels from a
recognized quality assurance agency?
H. Does the field installation follow the listing?
a. Specified forming, packing or backing material?
b. Specified type of sealant, coating or device?
c. Specified amount, depth, location of sealant,
coating or device?
d. Specified accessory items cover plates, bond
breaker tape, and specified deflection track?
Reason: Deviations from a listed and labeled design
will likely result in a failure of the installed system.
Consult with manufacturer for validation.
19
INSPECTION
For Perimeter Fire Barrier Systems ( Curtain Walls)
GUIDELINES
INSPECTION GUIDELINES
20
For
Perimeter Fire
Barrier Systems
(Curtain Walls)
Step One:
Verify documents and submitted drawings reference legitimate
Perimeter Fire Barrier Systems such as Underwriter
Laboratories, Inc. CW-S or CW-D or Intertek Testing Services
CEJ designations.
Step Two:
Verify the rating of the system is greater than or equal to the
rating of the floor.
Reason: The continuity requirements within the
building codes state that the rating of a floor
assembly must extend to and be tight against an
exter ior wall.
Step Three:
Verify firestop material to be used is classified and listed for use
in Perimeter Fire Barrier Systems. Such listings can be found
in Section XHDG within Volume 2 of Underwriters Laboratories
Inc. Fire Resistance Directory or Omega Point Laboratories
Directory.
Reason: Many materials, coatings and sealants have
never been tested in perimeter fire containment
systems and should not be substituted in listed and
labeled systems.
Step Four:
Verify documents reference systems that have been tested with
windows or vision glass if the building has glazing close to the
safing area.
Reason: Some systems were tested with
glazing within 6" of the safing area while other
systems were for structures with limited glazing such
as storage and warehouse facilities.
Step Five:
Verify a stiff steel reinforcement member, if required, has been
placed behind exposed curtain wall panel insulation. Typical
stiffening members can be steel hat channels, L or T angles.
Reason: A stiffener is needed to maintain the
compression fit of the safing insulation. Without it,
the safing insulation may fail to perform as tested.
21
Step Six:
Verify insulation type and brand used is listed within the tested
system. Mineral wool is the typical insulation of choice.
Reason: Fiberglass insulation melts at 1050 F, well
below the 2000 F temperature range of a typical
fire.
Step Seven:
If required by the tested system, verify insulation panels are
securely fastened with mechanical fasteners per the system,
instead of just friction-fitted in place.
Reason: The lower transoms and mullions
may degrade and melt during a fire situation causing
the curtain wall insulation to fall out prematurely if it
is not fastened correctly.
Step Eight:
Verify that exposed mullions, if required by the system, are
covered with the proper insulating barrier securely fastened with
mechanical fasteners per the system design.
Reason: Exposed mullions may degrade prematurely
in a fire.
Step Nine:
Verify safing clips or Z clips have been used if the system
requires it.
22
Step Ten:
Verify coating or sealant has been applied to the proper depth.
A common inspection practice is to be on site just prior to the
addition of the sealant to verify the correct application thickness
is being followed. The inspector may request samples from the
installing contractor after which the installing contractor shall
make the necessary repairs to the destructively sampled area.
A scale or caliper is sufficient for measuring the sealant depth.
Reason: Minimum sealant depths are required by
the system designs to assure the rating is met and
to prevent smoke, fumes or hot gases from seeping
into the non-fire area.
Step Eleven:
As an overview of the above steps, verify the parameters
indicated in the system are the same as those installed in the
field: (Download checklist form from the IFC web site)
A. Is the perimeter fire barrier system tested for the type
and nature of assembly, (minimum thickness of concrete,
transom spacing, etc.)?
B. Is the rating of the perimeter fire barrier system equal or
greater than the floor assembly?
C. Do the supplied products have labels from a recognized
quality assurance agency?
D. Does the field installation follow the listing?
a. Width of gap between floor edge and curtain wall at
time of installation.
b. Design detail includes vision glass if applicable.
c. Specified curtain wall spandrel insulation, (type,
thickness, density, etc.).
d. Specified spandrel panel perimeter angles, (gauge
thickness, dimensions, fastener spacing).
23
24
Step One:
Verify the documents and submitted drawings reference
legitimate fire resistive duct enclosure systems tested by
accredited testing laboratories or certified third party testing
agencies. These systems and insulation components should be
listed, labeled, published and readily available via the internet
or other means. Listings can be located in Intertek Testing
Services (formerly Omega Point Laboratories) Directory of Listed
Building Products, Materials & Assemblies and in the
Underwriters Laboratories Inc. Fire Resistance Directory.
Reason: There are generic insulating materials that
have not been tested as a fire resistive duct enclosure
system to verify their performance when installed in
a duct configuration under fire conditions. Generic insulating
materials do not meet code requirements and should not be
used for this application.
Step Two:
Verify the duct enclosure system is tested to the appropriate
Standard for the specific type of duct system. Grease duct enclosure
systems are tested per ASTM E2336, which includes a full scale
ASTM E 119 engulfment test. HVAC duct enclosure systems are
tested per ISO 6944, Type A for closed duct systems and Type B for
duct systems that contain openings. Additional evaluation of
ventilation duct enclosure systems for compliance to the
pertinent Mechanical Code can be conducted per AC 179. An
ASTM Standard for Fire Resistive Ventilation Duct Enclosure
Systems is under development, but not published at this time.
INSPECTION
GUIDELINES
INSPECTION GUIDELINES
25
Step Three:
Verify the fire resistance rating of the duct enclosure system
and corresponding firestop system are equal or greater than
the required fire resistive rating for the building construction
assembly penetrated.
Reason: The mechanical code requires the fire
resistance rating of the duct enclosure system be at
least equivalent to the surrounding building
construction. The F and T ratings for the corresponding duct
firestop system must also be at least equivalent to the duct
enclosure system and the surrounding assembly.
Step Four:
Verify the parameters indicated in the system are the same as
those installed in the field:
A.
B.
C.
26
D.
E.
F.
G.
27
Engineering Judgments
Although there are many listed systems, there
are some firestopping configurations that fall
outside the envelope of tested designs. It is
impossible to anticipate every field condition and
these situations should certainly not be ignored
by the firestop industry. Testing agencies and
manufacturers, usually handle these unusual occurrences with
the issuance of an Engineering Judgment. An Engineering
Judgment is not a substitute for a tested system, and an
available tested system should always take precedent over
a judgment. An Engineering Judgment is a solution based on
the interpolation of data done by a testing agencys qualified
technical personnel, a manufacturer, or by a knowledgeable
registered Professional Engineer or Fire Protection Engineer.
The issuer of an Engineering Judgment shall be responsible for
answering any questions pertaining to data, source or limits of
the judgment.
Judgments should be developed by following sound practice to
ensure that life safety issues are not compromised. A useful
publication for evaluating engineering judgments called
Recommended IFC Guidelines For Evaluating Firestop Systems
Engineering Judgments (EJs) is available from the International
Firestop Council.
28
Annular Space
Curtain Wall
CPM -
Engineering Judgment
Fireblocking -
Glossary
Document
Glossary
29
Glossary
Fire Resistive
Joint
Joint -
L Rating -
30
Glossary
Mullion -
Membrane -
Penetrant -
Perimeter -
Perimeter Barrier
31
Glossary
32
Safing Area
Splice -
Through Penetration
Through Penetration
Firestop
System
Transom -
T Rating -
Void -
W Rating -
References:
Navigating UL:
The
System
Approach:
UL Approved - No Such Thing (Only AHJ Approves Products/Systems)
UL Classified - Lab has used the country requirements
Firestop Systems
o First Alpha Character Signifies what is being penetrated
F = Floors
W = Walls
C = Walls and Floors
C-AJ-1079
Combination Floor or Wall
33
34
HW-D-0034
Barriers that form the join
First Two Alpha Characters identify the type of joint system
FF = Floor-to-Floor
WW = Wall-to-Wall
FW = Floor-to-Wall
HW = Head-of-Wall
HW-D-0034
Movement: Static or Dynamic
D = Dynamic (movement capabilities)
S = Static (no movement capabilities)
HW-D-0034
Joint Width
Numeric Component first digit identifies the width of the
joint system, next three are numbering
sequential system
HW-D-0034
Individual System Number
o 0000-0999 = joint <_ 2 inch
o 1000-1999 = joint > 2 inch <_ 6 inch
o 2000-2999 = joint > 6 inch <_ 12 inch
o 3000-3999 = joint > 12 inch <_ 24 inch
o 4000-4999 = joint > 24 inch
Class II:
Minimum 500 cycles @ a minimum
of 10 cycles/minute
Class III:
Minimum 100 cycles @ a minimum
of 30 cycles/minute
35
CAJ 3###
CAJ 4###
CAJ 5###
CAJ 6###
CAJ 7###
CAJ 8###
Cables
Cable Trays
Insulated Metal
Bus Duct
Metal Ducts
w/o Dampers
Mixed Multiple
CAJ 8###
WJ 8###
CAJ 7###
WJ 7###
TBD
TBD
CAJ 6###
WJ 6###
CAJ 5###
WJ 5###
CAJ 4###
WJ 4###
CAJ 3###
WJ 3###
FS500699FE
FS500699FC
FS500699FD
FS500699FD
FS500699FB
CAJ 2###
WJ 2###
CAJ 2###
Nonmetallic
TBD
TBD
FS100299WE
FS100299WC
FS100299WD
FS100299WD
FS100299WB
FS100299WA
CAJ 1###
WJ 1###
CAJ 1###
Metallic
FS500699FA
CONCRETE WALL
UL
I T S
CAJ 0###
FS500699WG
WJ 0###
CONCRETE FLOOR
Penetrants
UL
ITS
Blank Openings CAJ 0###
FS500699FG
WL 8###
WL 7###
WL 6###
WL 5###
WL 4###
WL 3###
WL 2###
WL 1###
FC 7###
FE 7###
FC 8###
FE 8###
TBD
FC 6###
FE 6###
FC 5###
FE 5###
TBD
FS100299WE
FS100299WC
FC 4###
FE 4###
FC 3###
FE 3###
FS100299WD
FS100299WD
FC 2###
FE 2###
FC 1###
FE 1###
TBD
TBD
FS100299FE
FS100299FC
FS100299FD
FS100299FD
FS100299FB
FS100299FA
WOOD OR
STEEL FRAMED FLOOR
UL
ITS
FC 0###
FS100FE 0###
299FG
FS100299WB
FS100299WA
GYPSUM WALL
UL
ITS
WL 0###
FS100299WG
FF-S/D*-0###
FF-S/D*-1###
FF-S/D*-2###
FF-S/D*-3###
FF-S/D*-4###
CEJ###F
Floor to
Floor
FW-S/D*-0###
FW-S/D*-1###
FW-S/D*-2###
FW-S/D*-3###
FW-S/D*-4###
CEJ###WF
Floor to
Wall
HW-S/D*-0###
HW-S/D*-1###
HW-S/D*-2###
HW-S/D*-3###
HW-S/D*-4###
CEJ###H
Head of
Wall
*S=Static / D=Dynamic
WW- S/D*-0###
WW-S/D*-1###
WW-S/D*-2###
WW-S/D*-3###
WW-S/D*-4###
CEJ###W
Wall to
Wall
CW-S/D*-0###
CW-S/D*-1###
CW-S/D*-2###
N/A
N/A
CEJ###P
Perimeter
Fire Barrier
Joint Width
< 2"
> 2"; < 6"
UL >6", < 12
>12", < 24"
> 24"
ITS
37
NOTES