You are on page 1of 2

MANUAL OVERRIDE SWITCHES

DAP-III panels have manual override switches to aid with start-up and troubleshooting.
Standard Control Board
There are six (6) switches:
Hard Power
ON/OFF
Blower
Cool 1

Data Aire, Inc.


Data Alarm Processor III (DAP III)
Quick Reference Guide

Cool 2
Reheat
Humidifier

If the panel is left in manual override mode an alarm will be activated.

MANUAL DIAGNOSTICS
The manual diagnostics mode (Menu Group 9) is primarily an aid for troubleshooting
and should be used only by a qualified technician. The panel should not be left in
diagnostic mode. To exit mode at any time, press the EXIT button and the panel will
return to its menu mode. Press EXIT button again and the DAP III will return to the
operation mode. Refer to the DAP-III Operation Manual for a step-by-step use of the
diagnostic mode.

Unit Mount

Wall Mount

230 West BlueRidge Avenue


Orange, CA 92865
Phone: (714) 921-6000
(800) 347-2473
Fax:

(714) 921-6010

www.dataaire.com
This Quick Reference Guide provides you with a quick overview of the procedures of some
basic functions of the Data Alarm Processor-III (DAP III). More complete information is available in the DAP III Operation Manual that is shipped with the unit or can be downloaded from
the Data Aire website (www.dataaire.com) or ordered from the Data Aire literature department.

GETTING STARTED
Prior to starting the control panel, check all mechanical connections (refrigerant
piping, condenser water, drain line and humidifier supply water) ensuring all have
been completed and checked.
Check the high voltage power supply. Verify it has been connected to the unit.

PROCESSOR START-UP
Open the panel, remove the protective paper from the battery and ensure
manual override switch for power is set to the ON position, see page 4.
Press the power ON button to energize the panel.
The panel will proceed through an automatic diagnostic self-test.
If there is a failure during the self-test, the display will stop scrolling and only the
message with the failure will be displayed. On any self-test failure, simply press
the SELECT to bypass the FAIL message.
On initial start-up it is not unusual to fail the RAM SIGNATURE test because
there is no stored data available.
Once the self-test is complete, the timed START DELAY will be displayed (the
start delay is programmable through Menu Group 3, Sub-Menu 3-4 in five second intervals to minimize the in rush current with multiple units).
After the start delay is complete, the unit will start and be in normal operating
mode. The blower will start upon completion of the timed start delay.
The cooling, reheat, humidifier and dehumidification functions are inhibited for
one (1) minute after the blower starts. This allows the temperature and humidity
sensors time to adjust.

MENU SELECTIONS
Menus are grouped in the DAP III from 1 to 10. Within each menu grouping there
are submenus. The grouping are:
1-STATUS & HISTORY
2-SETPOINTS
3-OPERATION

4-ALARMS
5-CONFIGURATION
6-NETWORK

7-CALIBRATION
8-SET-BACK
9-DIAGNOSTIC

10-ANALOG

(Menu 8 only displays when the unit is in RFM mode and menu 10 only displays if there is an analog module connected.)

To scroll among the menu groups use the MENU . Each menu grouping has
submenus. To access these submenus for a group use the SELECT or .
For example to see current conditions press the MENU button. The display
should read:
GROUP 1 - STATUS & HISTORY
To enter the submenus press the SELECT button. The display should read:
GROUP 1 - STATUS & HISTORY
1-1 TEMPERATURE & HUMIDITY SETPOINTS
To display the next submenu press the SELECT button. The display should
read:
1-2 LAST 24 HRS TEMPERATURE & HUMIDITY
TEMPERATURE SETPOINT IS: nnF(C)

Continuing to press the SELECT or will allow you to scroll through all the submenus options. Press MENU to see the next submenu.
To leave a menu or submenu, simply push the EXIT button and the processor will return
to the operational mode. To go from menu to menu, push the MENU or .
The DAP-III is password protected. Entering menu Group 2 and greater requires a password (units are shipped from the factory with the password set at 00).
Advance to Menu Group 2 Press MENU . If password has been entered through
sub menu 5-2, the display will read:
PASSWORD: 00
If a password has been entered and is unknown, push the SELECT button until 40 is
reached. This will allow viewing access to Menu Groups 2 10.
Menu Groups 2 5 are programmable. By pushing the SELECT or button, selections may be made and viewed.
Example: Push MENU button to advance the menu group. Display will read:
GROUP 2 - SETPOINTS
Push the SELECT button. Display will read:
2-1 CHANGE TEMPERATURE SETPOINT
Press the SELECT to display current temperature setpoint.
Press the SELECT or and the temperature setpoint will change in 1o increments.
Once the desired value is displayed, push MENU button to display the next sub-menu.
Follow the same procedure to view and/or change values in the sub menu.
To return to Group Menus, press EXIT. Press EXIT again to return to operational mode
and status display or press MENU button to advance to GROUP 3 OPERATION.
Note: Each time a MENU or button is pressed it will advance to the next menu or
selection. If the button is held down it will advance at a rapid rate. If there is no button
activity for three (3) minutes, the panel will return to its normal operating mode.
Menu Groups 5 and 6 are locked as is sub menu 4-24. No changes can be made until
unlocked. Refer to DAP-III Operation Manual or Data Aires technical assistance (800347-2473) if these menus require opening.
SENSORS
Temperature and humidity sensors are factory calibrated and the offset is recorded.
Each sensor is tagged with the calibration offset. This should be verified with the settings in Group 7 - CALIBRATION

You might also like