HPS2DN
Digital Reduced Voltage
Starter-New Serial
Table of Contents
Page
Subject
2
3
4
5-8
9
10-12
13-14
15
16
17-18
19-20
21-22
23-24
25-26
27-32
33-34
35-36
37-38
39-40
Starter Selection
Installation
By-pass contractor
Control terminals
Control Wiring
Wiring Diagrams
Wiring Diagrams - Communication
Wiring Diagrams Diesel Generator
Wiring Diagrams Brake motor
1Internal setting
Start and stop parameters
Motor and starter protection
Front panel and LCD Displays
Display mode and Default Parameters
Parameter setting
Start-up and Pump Control adjustments
Menu Description
Trouble shooting
Technical specification
41
42
43
44
45
46
47
48
49
Table of content
UL and cUL instructions, LR recommendations
General Technical Data
Motor and Starter Fault Occurrence Timing Table
Warranty claim sheet & Fault Inquiry
Overload Trip Time (Approximate calculation)
Block Diagram and Notes
Ordering Information
Dimensions
Safety
Read this manual carefully before operating the equipment and follow its instructions
Installation, operation and maintenance should be in strict accordance with this manual,
national codes and good practice. Installation or operation not performed in strict
accordance with these instructions will void manufacturer's warranty.
Disconnect all power inputs before servicing the soft-starter and/or the motor.
After installation, check and verify that no parts (bolts, washers, etc) have fallen into the
power Section (IP00).
Attention
1. This product was designed for compliance with IEC 947-4-2 for class A equipment.
2. HPS2 DN 8~840 are designed to meet UL requirements.
3. Utilization category is AC-53a or AC53b. Form1.
For further information, see Technical Specification
Warnings
Internal components and P.C.B's are at main potential when the HPS2-DN is connected to
main.
This voltage is extremely dangerous and will cause death or severe injury if contacted.
When HPS2 DN is connected to main, even if control voltage is disconnected and motors
is stopped, full voltage may appear on starter's output and motor's terminals.
Unit must be grounded to ensure correct operation, safety and to prevent damage.
Check that Power Factor capacitors are not connected to the output side of the soft starter.
The company reserves the right to make any improvements or modifications to its products without prior notice
Starter Selection
The HPS2DN is a highly sophisticated and reliable starter
designed for use with standard three-phase,three-wire,
squirrel cage induction motors. It provides the best method
of reducing current and torque during motor starting.
The HPS2DN starts the motor by supplying a slowly
Starter Type
FLC
18
30
45
60
75
90
110
145
175
210
250
300
370
470
570
720
840
HPS2DN
HPS2DN
HPS2DN
HPS2DN
HPS2DN
HPS2DN
HPS2DN
HPS2DN
HPS2DN
HPS2DN
HPS2DN
HPS2DN
HPS2DN
HPS2DN
HPS2DN
HPS2DN
HPS2DN
18
30
45
60
75
90
110
145
175
210
250
300
390
470
570
720
840
Control Voltage
B
Control Inputs
D
Dimensions (mm)
For exact dimensions, see Dimension Sheets.
Size
Width
Height
280
360
218
280
400
218
382
446
310
540
600
310
Depth
0
1
2
3
4
5
6
7
8
9
Installation
Prior to Installation
Check that Motor's Full Load Ampere (FLA) is lower than or
equal to the starters Full Load Current (FLC) and that Main
and Control voltages are as indicated on the front panel.
Mounting
The starter must be mounted vertically, allow sufficient
space above and below the starter for suitable airflow.
It is recommended to mount the starter directly on the
rear metal plate for better heat dissipation.
Do not mount the starter near heat sources.
Protect the starter from dust and corrosive atmospheres.
Transient Protection
of -10
(14 OF) to + 50
(122 OF). Relative noncondensedhumidity inside the enclosure should not
exceed 95%.
Starter's heat dissipation is approx. 3 x In (three times
the current in watts).
Additional Ventilation
HPS2DN
HPS2DN
ATTENTION
When Start signal is initiated and a motor is not
connected to load terminals, the Wrong Connection
protection will be activated.
WARNING
1. When main voltage is connected to the HPS2DN,
even if control voltage is disconnected, full
voltage may appear on the starter load terminals.
Therefore, for isolation purposes, it is necessary
to connect an isolating device before the starter.
2. Power factor correction capacitors must not be
installed n starters load side. When required,
install capacitors on starter's line side.
Non-ventilated enclosure
Fan, creating air circulation
Under normal operating conditions, the heat dissipated
by an electronic soft starter causes heating of the
enclosure and energy losses. The heating and losses
can be eliminated by the use of a by-pass contactor,
which by pass the HPS2DN after completion of start-
By-pass Contactor
Frame Size C
(175~250A)
HPS2DN
BY PASS
CONTACTOR
terminals.
Frame Size D
(300~840A)
L1 L2 L3
L1B
L2B
L3B
KM
265
30 45
45 30
15
260
313
Max400
7(4x)
26.5
Control Terminals
Terminals 1-3
Control Supply
Control Inputs
Stop
Terminal 4
Terminal 2
Soft stop
Terminal 5
Start
Terminal 6
Notes:
1. Motor will start only if Stop (4) and Soft Stop
(5) terminals are connected to control voltage.
2. Reset after a fault is not possible for as long as
Start command is present.
WARNING
Automatic mode may be used only if by-pass
contactor is directly controlled by the HPS2DN
of-Acceleration contact.
Terminal 7
One.
Internal Fan
Terminals
1-3
4-9
10-21
22-24
I/O Terminals
25-32
Control Terminals
Dual Adjust Reverse / Reset
Terminal 8
One.
Immediate/Shear-pin Relay
Terminals 10-11-12
Three. When
Reset
function is selected, connect
terminal 8 to control voltage (use a N.O momentary
contact) to reset the starter.
Common
Terminal 9
Control Terminals
Fault Contact
Terminals: 13-N.O.
14-N.C.
Terminals 13-14-15
15 Common.
Neutral
Terminal 20
Terminal 21
17-N.C.
Terminals 16-17-18
18 Common.
External Fault
WARNING
Only potential free contacts may be connected to
terminal 21.
Do not connect any voltage to terminal 21.Any
connection of voltage to this terminal may
disrupt soft-starter operation, and cause starter or
motor damage.
Notes:
Wires connecting between terminal 21 and terminal
19 should not exceed 1 meter in length.
Do not use External Fault when terminal 21 is not
connected to Neutral or Ground.
Terminal 19
WARNING
Only potential free contacts may be connected to
terminal 19.ntial free contacts may
Do not connect any voltage to terminal 19. Any
connection of voltage to this terminal maystarter or
disrupt soft-starter operation, and cause
motor damage.
Control Terminals
Option # 1
RS-485 Communication
Option # 4
Terminals 23-24
Terminals 28-32
T2
T1
Gnd
Out(-)
Out(+)
32 31 30 29 28
Dip. Sw. SI
Option # 3
Insulation Alarm
Terminals 25-26-27
Notes:
1. Do not use External Fault while using Insulation
Alarm option.
2. Insulation test can be performed only when main
voltage is not connected to the HPS2DN, namely
an upstream isolation device must be opened.
For correct operation of Insulation test, it is
important that the HPS2DN is properly grounded
and that the control module is properly fastened to
the power section.module is properly fastened to
3. Option # 3 and option # 4 may not be applied
together.
Thermistor input
Terminals 28-29
Ground Terminal
Terminal 30
Analogue Output
Terminals 31, 32
Dip No.
4-20 mA*
0-20 mA
0-10VDC
Dip-Sw. S1 # 1
On
On
Off
Dip-Sw. S1 # 2
On
On
Off
Dip-Sw. S1 # 3
Off
Off
On
Dip-Sw. S1 # 4
Off
Off
On
Dip-Sw. S2 # 1
On
Off
Off
Dip-Sw. S2 # 2
No use
No use
No use
* Default
Notes:
1. It is important that the HPS2DN is properly
grounded, and control module is tightly fastend
the power section.
2. Option # 4 and option # 3 may not be applied
together.
3. Use twisted shielded cable for thermistor
connection.
Control Terminals
Internal jumper-see page 13
1
Fan
Control Supply
Stop
Soft Stop
Start
E.Save/Sl. Speed/Reset
D.Adjust/Reversing/Reset
Common
1
2
4
5
6
7
8
9
10
11
Immediate Relay
12
13
14
Fault Relay
15
21
16
17
18
Option 3
Option 4
19
20
Tacho. Feedback
21
Neutral
22
Leave Open
23
(-) RS 485
24
(+) RS 485
4
5
6
7
8
9
25
26
21
27
Option 5
28
29
Thermistor Input
30
Ground
31
32
3
4
5
6
7
8
9
WARNING
Incorrect connection of terminal 19 and 21 may
disrupt soft-starter operation and cause starter
or motor damage.
21
Wiring Diagrams
1. Start, soft stop and
stop buttons, single
supply source for
Control Supply and
Control Inputs.
If Soft Stop is not
used, connect a jumper
between terminals 4-5
connect emergency
stop and /or soft stop
between terminals 1-4.
L1
N
2. Start-Stop push
buttons, Separate
sources for Control
Supply and Control
Inputs.
If Soft Stop is not
used, connect a jumper
between terminals 4-5.
Soft Stop
1
2
3
4 Soft
5 Soft Stop
6 Start
7
8
9
1
2
3
4 Soft
5 Soft Stop
6 Start
7
8
9
L1
N1
L2
N2
21
21
L1
L1
2
N
6.
2
N
3
4
L1
L1
2
N
L1
C1
3
C
9
19
C 20
21
Notes: 1. Terminal 21 may be connected to terminal 3 only if terminal 3 is at neutral or at ground potential.
2. Resetting is possible only after start signal is removed.
Wiring Diagrams
By-pass contactor
Series contactor
Bypas
Contacto
C1
L1 L2 L3
L1 L2 L3
32
31
30
29
28
27
26
25
24
23
22
9 10 11 12 13 14 15 16 17 18 19 20 21
N
M
End Of Acceleration
Contac
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
U V W
Notes:
1. It is recommended that terminals 1-3 be always
connected to Control Supply.
Note:
Wiring Diagrams
Reversing with 2 series contactors
Mechanical Interlock
2
C2
HPS2DN
C1
S
13 15
13 15
L1 L2 L3
Low
31
High
S
32
speed
speed
30
29
14 16
14 16
28
HPS2DN
24
2 3 4
5 6
7 8
22
Note:
1.
2.
3.
23
9 10 11 12 13 14 15 16 17 18 19 20 21
Initial Voltage
Current Limit
Acceleration Time
Deceleration Time
Motor FLA.
L1 L2 L3
28 29 30 31 32
27
26
25
23
9 10 11 1 2 13 14 15 16 17 18 19 20 21
22
Rs485 to
rs232 Adapter
U V W
N
Remote local
start
soft stop
WARNING
The host computer must be grounded when communicating with HPS2-DN (unless using a Lap-Top Computer).
5 6
soft stop
Remote local
start
Immediatc
Stop
soft stop
Notes: The communication (data retrieval and statistics) is active at all times!
When control signals (start, stop, etc.) are required, terminals 4 and 5 have to be wired in accordance with the
appropriate wiring diagram:
1. Maintained soft-start and stop
2. Maintained soft-start with immediate stop.
3. Soft-start/stop with immediate stop via push-button control.
Bypas
Contacto
Line
Contacor
~
Dip.
L1 L2 L3
Sw.
ON
OFF
End Of Acceleration
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
U
Star
V W
stop
L
M
N
1.
When starting from a Diesel-Gen., its voltage regulator (especially older type regulators) may be affected during the
starting process, causing rapid voltage fluctuations (~350V to ~500V systems). In these rare cases, the voltage
regulator must be upgraded consult your Diesel-Gen. Supplier.
2.
In most cases where voltage, current or frequency is unstable a special routine may be applied to overcome
the starting difficulty. Use the procedure below:One. Set Dip.Switch# 3 to On (as shown above).
Two. Insert a contact (or jumper) between Control Supply and terminal 8 (Dual Adjust. Terminal) and close
contact to operate the Generator Mode. Dual Adjust LED will light when operating in Generator Mode.
Three. Set Dual Adjust parameters to the values necessary for the application (e.g. faster acceleration, lower
current limit, etc.).
3.
When operating from Main and alternatively from Diesel Gen. Set normal starting characteristics for Main and
suitable parameters for the Diesel Gen. On Dual Adjustment setting. When starting from Main, the primary settings
(suitable for main starting) will be operative. Upon starting from Generator, close contact between Control Supply
and Terminal 8
To operate on Generator Mode.
Note: Ensure that Diesel Gen. Size is suitable (Diesel Gen. KVA is approximately at 1.35 motor KVA).
WARNING
1. Motor can not run idle and must be loaded when operating in Generator Mode, otherwise vibration may occur
during starting and stopping.
2. When using extended range, use maximum precaution to avoid motor or starter burnout.
3. Disconnect all other loads before starting for the first time to prevent damages due to voltage fluctuations.
4. Disconnect Power Factor Capacitors when operating with Diesel gen.
5. Connect terminal 21 to terminals 3 and/or 9 only if these terminals are connected to neutral or at ground potential.
6. Only potential free contacts may be connected to terminal 21. Do not connect any voltage to terminal 21. Any
connection of voltage to this terminal may disrupt soft-starter operation, and cause starter or motor damage.
C1
L1 L2 L3
32
31
30
29
28
24
23
22
ImmediatcContacto
1 2 3 4 5
C1
L1 L2 L3
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
29
28
27
26
25
24
23
22
Insulation
Alam
1 2 3 4 5
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
N
B
M
M
120 seconds.
Internal Settings
Plug to
Power unit
Transformer
Power Supply
Board
Dip Switch
Main Board
Insulation Board
Fan Control
Jumper
Communication
Board
Fan Control
Intemal Jumper
Fan
B C
EPROM
A
read-only, non-volatile memory,
containing factory set parameters
(default) that cannot be changed.
3
N
Control Supply
Continuous operation (default connection) The
internal jumper is connected to terminal A. Fan(s)
will operate continuously as long as Control
Supply is connected.
External Control - Connect the jumper to terminal B.
Connect terminal 2 to Control Supply through an
external contact. Fan(s) will operate when the
external contact closes and stop when it opens.
Automatic operation-Connect the jumper to terminal
C. Fan(s) will operate automatically for a few minutes
after start. The fan(s) will stop automatically a few
minutes after stop signal.
RAM
2.
3.
WARNING
1. The starter is supplied with the internal jumper
connected to terminal A, for continuous
operation. If changed, it is the Customer's
responsibility to operate the Fan(s).
2. Use only when by-pass contactor is utilized.
A
read/write memory containing
parameters loaded from the EEPROM
which can be changed from the keypad.
These parameters are stored only as
long as Control Supply is connected.ROM
4.
Internal Settings
Dip Switch settings
Switch Function
Switch Off
Switch On
Display Format
Minimized
Maximized
Tacho feedback
Disabled
Enabled
Main/Generator
Main
Generator
Must be Off
5-6
LCD-language
selection
See table
Disabled
Enabled
Software lock
Open
Locked
Adjustment setting.
WARNING
When operating in Generator Mode, motor must be
loaded, otherwise, vibration may occur during
starting and stopping.
Maximized mode
Minimized mode
Switch 1 On
Display only
Main parameters
Start parameters
Stop parameters
Dual adjustment
Energy save parameters
Slow speed parameters
Fault parameters
I/O programming
Communication
parameters
Statistical data
Switch 1 Off
Display only
Main parameters
Start parameters
Stop parameters
Statistical data
Language
English
French
German
Spanish
Switch 5
Off
Off
On
On
Switch 6
Off
On
Off
On
Initial Voltage
Voltagae
Torque
DOL
0
1!!
2!!
3!!
Speed
range).
Un
100%
50%
10%
Current limit
Time
Un
100%
400%
Un MotorVoltagac
Acceleration Time
speed rpm +1
Pulse Start
Intended to start high friction loads,
requiring high starting torque for a
short time.
A pulse of approx. 80% Un without
Current Limit is initiated to break
the load frees. Pulse duration is
adjustable, 0.1 1 secretary.
Un
100%
30
5 sec.
Un
Notes:
80%
+1
0.1-1sec.
sec.
Final Torque
Contact Delay
Dual Adjustment
V oltage
Peceleration
0
1!!
2!!
3!!
U%
100%
30sec
U%
100%
40%
20%
2-10
2-30sec
Energy Save
Activated when motor is lightly
loaded for extended periods of time.
Supply voltage the motor decreases
(lowering the rotating magnetic
field intensity), thus, reducing the
reactive current and copper/iron
losses.
un
In
U Starter
I Motor
0.5
ATTENTION
Note: Always use Stop Curve 0. If motor stalls quickly
instead of slowly decreasing its speed, select
Stop Curve 1, then 2 or 3 if necessary.
U%
100%
30sec
WARNING
Note: When the starter operates with a by-pass
contactor, Soft Stop initiation opens the End Of
Acceleration contact, tripping open the by-pass
contactor. Load will then be transferred to the
HPS2DN and voltage begins ramping down.
ALARM:
INSULATION LEVEL and shows the value in M .
The Fault LED flashes and the Insulation Alarm Relay
is activated.
Alarm signal will disappear automatically 60 seconds
after insulation level returns to normal. Trip does not
reset automatically.
Overload (O/L)
When insulation decreases below Trip Level set point,
the LCD displays TRIP: INSULATION LEVEL and
shows the value in Mohm. The fault LED illuminates
and Fault Relay is activated.
10
1
115
500
1%
ATTENTION
Number of Starts
Determines maximum allowable number of starts.
Range: Off, 1-10 starts.
Start Period
Time period during which Number of Starts is
being counted. Range: 1-60 min.
Start inhibit
Detrermines time period during which starting is
disabled after Too many starts trip.
Range:1-60 min
tart Inhibit
Time has elapsed. Trying to start the motor
during this time delay will result in LCD
displaying Wait Before Rst: ___ MIN.motor
Under Current
Operational when motor is running. Trips the starter
when motor current drops below set Under Current
Trip (UCT) for a time longer than Under Current Delay
(UCD).
Under Current Trip, Range: 0=Off, 20-90% of FLA
Under Current Delay. Range: 1-40 sec.
Under Voltage
Becomes operational after start signal. Trips the starter
when main voltage drops below the set Under Voltage
Trip (UVT) for a time longer than Under Voltage
Delay (UVD).
Under Voltage Trip, Range: 120-600V (phase to Neutral )
corresponding: 208-1040V (phase to phase)
Under Voltage delay, range 1-10 sec.
Note:
When voltage(phase to Neutral ) drops to zero (voltage outage) the starter will trip immediately, overriding the delay.
Phase Sequence
Becomes operational when starter is energized,
provided this protection has been activated (Fault
Enable Phase Sequence Protection, see page 31).
Trips the starter when phase sequence is wrong.
WARNING
The over temperature protection is designed to
operate under normal conditions e.g. in the event of
extended low overload,insufficient ventilatio - fan
stoppage or air flow blockage.air flow blockage
Incorrect starter selection or operation frequents
starting at max.conditions,or repeated starting under
fault conditions can cause SCRs to overheat and fail
before the heatsink reaches 85 to trip the thermal
sensors.heatsink reaches 85 to trip the thermal
External Fault
Becomes operational when starter is energized, trips
the starter when an External Contact closes for more
than 2 secretary.
WARNING
Do not use External Fault when terminal 21 is not
connected to ground.
Wrong Connections
Become operational after start signal. Trips if motor is
not properly connected to starter's Load terminals, or
when:
Internal disconnection in the motor winding is
detected.
Shorted SCR
Trips the starter in case one or more SCRs have been
shorted.
Note:
Resetting is not possible as long as Start signal exists.
Auto Reset
Under-voltage and Phase-loss, faults can be set to
Auto-Reset (see Fault Parameters page 31). The
starter will reset itself 60 sec. after voltage was fully
restored provided no start signal exists.
Note:
Auto- Resetting is not possible as long as Start signal
exists.
Front Panel
LED Arrangement
Keypad
On
Lights when Control Supply voltage is connected to the
starter.
Mode
Start
Maximized
Run
Maximized
Display Only
Main Parameters
Start Parameters
Stop Parameters
Statistical Data
Dual-Adjustment Parameters
Energy Saver and Slow Speed
Parameters
Fault Parameters
I/O Programming Parameters
Communication Parameters
S. Stop
Lights up during Soft Stop process, indicating that
motor supply voltage is ramping down.
Stop
Lights up when motor is stopped.
Select
E. Save / Slow
Lights up when nergy Save is in operation
Flashes when motor is running as Slow Speed.
D. Adj. / Rev
Lights up when Dual Adjustment is in operation.
Flashes when motor is running in the Reverse direction
at slow speed.
Fault
Store
Reset
Front Panel
LCD Arrangement
Mode pages
CURRENT LIMIT
390%
Upper line displays functions.
Lower line displays setting and measured values.
% OF MOTOR FLA
98 %
When Dip Sw.#1 is set to On (see Display Options
page 19), by pressing the Mode key all Mode pages
can be reviewed.
When Dip Sw. # 1 is set to Off, the following Mode
pages marked ** will not appear.
MAIN PARAMETERS
STOP PARAMETERS
START PARAMETERS
**
DUAL ADJUSTMENT
PARAMETERS
**
**
I/O PROGRAMMING
PARAMETERS
**
COMM.
PARAMETERS
STATISTICAL DATA
Display Mode
In this mode, parameters cannot be adjusted
Press Select
UVT
300
% OF MOTOR FLA
Displays operating current as a percentage of motor
FLA.
THERMISTOR RES.
3.1 Kohm
Displays motor thermistor resistance
When option cards are not incorporated, the LCD
displays
OPTION CARD
Not installed
OVT
480
OVD
2
Range: 120-600V
(phase to Neutral )
(phase to phase).
Corresponding: 208-1040V (phase to phase)
UVD - Under Voltage Delay. Range: 1-10 secretary.
Range: 150-750V
OVT - Over Voltage Trip.
(Phase to Neutral )
(phase to phase)
Corresponding: 260-1300V (phase to phase)
OVD - Over Voltage Delay. Range: 1-10 secretary.
Press Select
STC
0
UVD
5
PT
0
IV CL AT
30 400 10
Range: 0-9
STC - Start Curve.
(0 = standard, 1, 2, 3 = pump, 4-9 = tacho)
Range: 0-1 secretary.
PT - Pulse Start Time.
(Pulse voltage is 80% of Un.)
Range: 0-50% of Un.
IV - Initial Voltage.
Range: 100-400%
CL - Current Limit.
of motor's Full Load Ampere (FLA).
Range: 1-30 secretary.
AT - Acceleration Time.
Press Select
MST NOS SP SI CD
Press Select
FLC FLA
105 105
Press Select
UCT UCD OCT OCD
0
10
850
1
Press Select
SPC
0
Press Select
Press Select
OLT OLD
115 4
OLT - Overload Trip. Range 75-150% of motor FLA.
OLD - Overload delay. Tripping time at 500% FLA.
Range: 1-10 secretary.
DT FT
10
0
DA: IV CL AT DT
30 400 10 10
IV
CL
AT
DT
- Initial Voltage.
- Current Limit.
- Acceleration Time.
- Deceleration Time.
Press Select
DA: FLA
105
Display Mode
Press Select
ES
10
Press Select
SST
8
MSST
30
ES
Range: 0-10,
Energy Saver.
(0 min saving, 10 = max saving).
SST Slow Speed Torque. Range: 1-10
(1 = min, 10 = max.)
MSST Max. Slow Speed Time allowable operates
Range: 1-30 secretary.
time at slow speed.
IMM
Press Select
SEQ
NO
INSULAT
0.1
0.1
RST
NO
SEQ
- Phase sequence Yes / No
INSULAT - Motors Insulation Alarm & Trip levels.
Alarm level. Range: 0.2 5 Mohm.
Trip level. Range: 0.2 5 Mohm.
RST - Auto Reset for Under Voltage and Phase Loss
Yes / No.
Press Select
I7
0
I8
0
FREL
0
- Immediate Relay
Left number
Range 0-60 sec.
Right number
Range 0-60 sec.
0-On delay,
0-Off delay,
Press Select
DRV
0
BAUD
96
PAR
0
SER
248
DRV
Press Select
Display of I/O Programming parametes:
17
Terminal 7
18
Terminal 8
Dual
Slow Speed
Programming
Energy Save
Slow Speed
Reset
Programming
Adjustment
Display
(0)
(1)
(2)
Display
(0)
Reverse
(1)
Reset
(2)
Programming
Display
Fault (0)
Fault - fail safe (1)
ANALOGUE OUTPUT
Normal
Normal- Analogue output increases when current
increases.
Inverted- Analogue output decreases when current
increases.
Range: Normal, Inverted.
Fault
Condition
Exists
Fault
Fault-Fail
safe
Off
Yes or No
De-Energized
De-energized
On
No
De-energized
Energized
On
Yes
Energized
De-energized
and
keys
One. Press Mo
simultaneously, the LCD will display tore
Enable Default Parameters
Two. Press Store + Mode keys simultaneously.
CAUTION
Obtaining Default Parameters erases all previously
modified settings and requires the operator to
program FLC and FLA values again.
Parameter Settings
Press Mode
Press Select
To advance to:
Press
MAIN PARAMETERS
Press Select
Press
keys to set Starter's FLC.
(see RVS-DN ratings Page 3).
STARTER FLC
105 AMP
Press Select
Press
keys to set Under Voltage Trip Delay
Range: 1-10 sec.
UNDERVOLT. DELAY
5 sec
Press Select
Press
keys to set motor's FLA
Range: 50-100% of TARTER FLC
MOTOR FLA
105 AMP
Press Select
Press
Press Select
OVERVOLT. TRIP
480 VOLT.
Press
keys to set Under Current Trip.
Range: 0 = OFF, 20-90% of FLA
UNDERCURR. TRIP
0% OF FLA
Press Select
Press
keys to set Over Voltage Trip Delay.
Range: 1 10 sec.
Press Select
OVERVOLT. DELAY
2 SEC.
Press
keys to set under Current Trip Delay.
Range: 1-40 secretary.
UNDERCURR. DELAY
10 Secretary.
Press Select
To store selected parameters, press Store key.
Press Select
Press
keys to set Over Current Shear-pin.
Range: 200 850% of FLA
O/C SHEAR PIN
850% OF FLA
STORE ENABLE
MAIN PARAMETERS
Press Select
Press
keys to set O/C Shear-pin Delay.
Range: 0.5-5 sec.
O/C DELAY
1.5 Secretary.
Press Select
Press
keys to set Overload Trip Current.
Range: 75-150% of FLA
OVERLOAD TRIP
115% OF FLA
Press Select
DATA SAVED OK
This concludes MAIN PARAMETER settings.
Pressing Select key after Data Saved Ok returns to
the first display in this mode.
STORAGE ERROR
Press
keys to set Overload Delay
at 500% of motor FLA
Range: 1-10 sec.
OVERLOAD DELAY
4 SEC AT 5 FLA
Parameter Settings
Press Mode
Press Select
To Advance to:
Press
keys to set Acceleration Time
Range: 1-30 secretary.
START PARAMETERS
ACC. TIME
10 SEC.
Press Select
SOFT START CURVE
0 (STANDARD)
Then press
keys to set Soft Start Curve:
0 = Standard Curve
1!! = Pump Control Curve # 1
2!! = Pump Control Curve # 2
3!! = Pump Control Curve # 3
When setting Dip sw. # 2 On for Tacho Mode
Press Select, curve message changes to:
START TACHO. GAIN
0 (MIN. GAIN)
Then press
keys to set Tacho gain:
0 = Minimum gain tacho, control
1!! = Second level tacho gain
2!! = Third level tacho gain
3!! = Fourth level tacho gain
4!! = Firth level tacho gain
5!! = Sixth level tacho gain
Press Select
Press
keys to set Maximum Start Time
Range: 1-30 sec.
MAX. START TIME
30 SEC.
Press Select
Press
keys to set Number of Starts permitted
(During STARTS PERIOD below). Range: 1-10, Off.
NUMBER OF STARTS
10
Press Select
Press
keys to set Number of Starts Time Period
Range: 1-60 min.
STARTS PERIOD
30 MIN.
Press Select
Press
keys to set Start Inhibit Period
Range: 1-60 min.
STARTS INHIBIT
15 MIN.
Press Select
Press Select,
Press
keys to set Pulse Start Time.
Range: 0-1 sec. (Pulse level at 80% Un)
PULSE TIME
0 SEC.
Press
keys to set Time Delay for End of
Acceleration Contact.
Range: 0-120 sec.
RUN CONTACT DEL.
5 SEC.
Press Select
Press Select,
Press
keys to set Initial Voltage.
Range: 10-50% of Un.
INITIAL VOLTAGE
30%
Press Select,
Press
keys to set Current Limit
Range: 100-400% of motor FLA.
CURRENT LIMIT
400% OF FLA
Parameter Settings
Press Mode
Press Mode
To advance to
Press Select
Then press
keys to set Soft Stop Curve
0 = Standard
1!! = Pump Control Curve # 1
2!! = Pump Control Curve # 2
3!! = Pump Control Curve # 3
SOFT STOP CURVE
0 (STANDARD)
DUAL ADJUSTMENT
PARAMETERS
When selecting Generator Mode (Dip sw # 3 is on)
the following display appears instead of the above.
D. ADJ: GENERATOR
PARAMETERS
Press Select
Then press
keys to set DA: Initial Voltage.
Range: 10-50% of Un.
DA: INIT. VOLT.
30%
Press Select
Press Select
Then press
keys to set DA: Current Limit.
Range: 100-400% of motor's FLA.
DA: CUR. LIMIT
400% OF FLA
Press Select
Then press
keys to set DA: Acceleration Time.
Range: 1-30 sec.
DA: ACC. TIME
10 SEC.
Press Select
Then press
keys to set DA: Deceleration Time.
Range: 1-30 sec.
Then press
keys to set Deceleration Time.
Range: 1-30 sec.
DEC. TIME
10 SEC.
Press Select
Then press
Press Select
Then press
keys to set Final Torque during Soft
Stop.
Range: 0 10 (0 = min., 10 = max.)
FINAL TORQUE
0 (MIN)
Press Select
To store selected parameters, press Store key
STORE ENABLE
D.ADJ. PARAMETERS
Press Select
To store selected parameters, press Store key
STORE ENABLE
STOP PARAMETERS
This
concluded
DUAL
PARAMETERS setting.
ADJUSTMENT
Parameter Settings
Press Mode
Press Mode
Press Select
Then press
keys to set Energy Saving Level.
Range: 0-10 (0 = min., 10 = max.)
SAVING ADJUST.
0 (MIN.)
Press Select
Then press
keys to set Slow Speed Torque.
Range: 1-10 (1 = min., 10 = max.)
SLOW SPEED TORQ.
8
Press Select
Then press
keys to set Maximum Slow Speed
Time.
Range: 1-30 sec.
MAX SLOW SP TIME
30 SEC.
Press Select
To store selected parameters, press Store key
STORE ENABLE
EN. SAVE & SL. SPD
When parameters have been correctly stored, the LCD
displays:
DATA SAVED OK
FAULT PARAMETERS
Press Select
Then press
keys to set Phase Sequence trip.
Range: Yes / No
PHASE SEQ. Y/N
NO
Press Select
Then press
keys to set Insulation Alarm.
Range: Off, 0.2 5 M?
INSULATION ALARM
OFF
Press Select
Then press
keys to set Insulation Trip.
Range: Off, 0.2 5 M?
INSULATION TRIP
OFF
Press Select
Then press
keys to set Auto.Reset (for Undervoltage
and Phase-loss faults).
Range: Yes / No.
AUTO RESET
NO
Press Select
Then press
keys to set Thermistor Type.
Range: PTC, NTC.
THERMISTOR TYPE
PTC
Press Select
This concludes ENERGY SAVING / SLOW SPEED
PARAMETERS setting.
Then press
keys to set Thermistor Trip Level.
Range: Off, 0.1 10 K? , step: 0.1Kohn.
THERMISTOR TRIP
OFF
Press Select
To store selected parameters, press Store key
STORE ENABLE
FAULT PARAMETERS
When parameters have been correctly stored,
the LCD displays:
DATA SAVED OK
Parameter Settings
Press Mode
Press Mode
I/O PROGRAMMING
PARAMETERS
Press Select
Then press
keys to set Terminal # 7 function
Range: Energy Saver, Slow Speed, Reset
PROG. INPUT # 7
ENERGY SAVER
COMM. PARAMETERS
Communication is optional and operates only when
starter incorporates this feature.
Press Select
Press Select
Then press
keys to set Terminal # 8 function
Range: Dual Adjustments, Slow Speed Reverse, Reset
PROG. INPUT # 8
DUAL ADJUSTMENT
Press Select
Then press
keys to set Fault Relay function
Range: Fault, Fault - Fail Safe (Fail-Safe Logic - page 23)
FAULT RELAY TYPE
FAULT
Then press
Press Select
Then press
keys to set Communication Baud Rate.
Range: 1200-9600 bps
Press Select
BAUD RATE
9600
Then press
keys to set Immediate Relay function
Range: Immediate, Shear-Pin
IMM / S.PIN RELAY
IMMEDIATE
Press Select
Press Select
Then press
keys to set Communication Parity
Check. Range: Even / Odd
Then press
keys to set Imm / S. Pin Relay On Delay
Range: Immediate 0-60 sec. / Shear-Pin 0-5 sec.
RELAY ON DELAY
0 SEC.
Press Select
Then press
Keys to set Imm / S. Pin Relay Off Delay
Range: Immediate 0-60 sec. / Shear-Pin 0-5 sec.
PARITY CHECK
EVEN
Press Select
Then press
keys to set Communication Serial Link
Number
Range: 1-248 (for up to 32 starters on one twisted pair)
SERIAL LINK NO.
248 (OFF)
Press Select
Then press
keys to set Normal or Inverted output
Range: Normal, Inverted
ANALOG OUTPUT
NORMAL
Press Select
To store selected parameters, press Store key
STORE ENABLE
I / O PROG. PARAM.
When parameters are correctly stored, the LCD
displays
DATA SAVED OK
This concludes I/O PARAMETER setting.
Press Select
To store selected parameters press Store key
STORE ENABLE
COMM. PARAMETERS
When parameters have been correctly stored, the LCD
displays:
DATA SAVED OK
This concludes COMMUNICATION PARAMETERS
setting.
Parameter Settings
Press Mode
Service Mode
To Advance to
STATISTICAL DATA
- ****-
STORE ENABLE
DEFAULT PARAMET.
Press Select
To store selected parameters, press Store key
LAST STRT PERIOD
NO DATA
Displays last starting time in seconds.
(Time duration until motor's current reached nominal)
Press Select
Press Select
RESET STATISTICS
LAST START MAX I
NO DATA
Displays the maximum current at last start.
Press Select
HPDN SERIAL
HPDN ELECTRIC.CO.
Press Select
TOTAL # OF START
0
Displays the total numbers of starts since commissioning
or since Statistical Data was last reset.
Press Select
Read phase to phase main voltage.
VOLTAGE ADJUST.
XXX % VOLT
Press Select
LAST TRIP
NO DATA
Describes last fault.
Press Select
Reads current for factory calibration use only.
CURRENT ADJUST.
XXX% OF RVS FLC
Press Select
TRIP CURRENT
0% OF FLA
Displays the current at the last fault.
Press Select
Display goes back to Store Enable Default Parameters
STORE ENABLE
DEFAULT PARAMET.
Press Select
TOTAL # OF TRIPS
0
Displays the total numbers of trips since commencenent
or since Statistical Data was lasereset.
Press Mode to return to Display Only Mode
% OF MOTOR FLA
NOTES:
Entering Service Mode is possible only when
Stop LED is on.
A Start signal while in ervice Mode exists from
this mode.
Start-Up Procedure
Note: It is necessary to connect a motor to load
terminals otherwise
Wrong Connection
Protection is activated. Other loads such as light
bulbs, resistors, etc. may also cause
Wrong
Connection Fault.
U%
600%
400%
300%
100%
1.
50%
30%
100%
10%
t
U%
100%
400%
50%
10%
100%
20
Initial Voltage
Acceleration Time
Current Limit
Imm.Rel. ON delay
U%
100%
25
10
t
t1
t2
Standard Par.
25%
t2 = 2-30 sec
300-400%
-----
Pump Control
Choosing a suitable Pump Curve (centrifugal Pumps)
Starting Curve
1. Adjust main parameters as necessary (FLA, FLC, etc..)
2. Set Starting Curve, Acceleration Time, Current Limit, and lnitial
Voltage to their default values (curve 0, 10 sec.,400% and 30%
respectively).
3. Start the pump while watching the pressure gauge as the pump
starts and look for overshootion (Pressure Surge ) of the gaue
needle above the target pressure. In case of over pressure,
choose a peak torque reduction
Curve (Pump Control curve 1!).
4. Set Start Curve 1!, increase Acceleration Time to
15 sec. and reduce Current Limit to 350%. Start the
pump and watch the pressure gauge while the pump
starts.
5. In most cases, overshooting is reduced, if the
overshoot persists, increase Acceleration time to 25
secretary. (confirm with motor manufacturer) and try
again.
6. If the overpressure persists, increase Starting
Curve setting to 2!, or 3!, if necessary. Each
increase in Starting Curve setting will reduce the
Peak Torque, thus, reducing the overpressure and
preventing the
Pressure Surge
during start.
To
increase
starting
time
above
these
maximums,
7.
employ Special Starting (page 32) with these
Torque
DOL
0
1
2
3
Speed
Peak
Torque
Sec
techniques.
Stopping Curve
1. Adjust main parameters as necessary (FLA, FLC, etc..)
2. Set Stop Curve and Deceleration Time, to their default values (curve 0, 10
sec., respectively).
Stop the pump, watching the pressure gauge and check valve as the pump
3. stops. Look for overshooting ( Water Hammer ) of the gauge (abruptly
stops the pump and the motor).
4. Select Stop Curve 1, increase Deceleration time to 15 seconds. Stop the
pump and watch the pressure gauge and the rate of closing of the check
valve as the pump stops. Abrupt stopping of the pump and motor will
cause a loud audible noise emitted from the check valve.
5. In most cases, Water Hammer is reduced. If the Water Hammer
persists, increase the time to 25 seconds (confirm with motor
manufacturer) and try again.
Deceteration
Voltagae
0
1
2
3
6. If the Water Hammer persists, increase Stop Curve setting to 2!, or 3!.
Each increase in stop curve will reduce the abrupt stop of the pump, thus,
preventing the
Water Hammer
phenomenon.
Deceteration
Voltagae
Ft10
Ft1
Sec
Menu Description
MODE
MODE
MODE
MODE
MODE
UPON INITIATION
PARAMETERS DISPLY
PAGE 1
PAGE 2
PAGE 3
PAGE 4
% OF MOTOR FLA
MAIN PARAMETERS
START
PARAMETERS
STOP
PARAMETERS
DUAL ADJUSTMENT
PARAMETERS
SELECT
SELECT
SELECT
SELECT
SELECT
TO REVIEW ALL
PARAMETERS
PRESS
MOTOR INSULATION
52.8 Mohm
STARTER FLC
105 AMP
THERMISTOR RES.
3.1 Kohm
MOTOR FLA
105 AMP
DA: GENERATOR
PARAMETERS
FLC FLA
105 105
UNDERCURR TRIP
0% OF FLA
PULSE TIME
10 SEC
DEC. TIME
10 secretary.
UNDERCURR.
DELAY 10 SECretary.
INITIAL VOLTAGE
30%
FINAL TORQUE
0 (MIN)
OLT OLD
115 4
CURRENT LIMIT
400% OF FLA
STORE ENABLE
STOP PARAMETERS
OVERLOAD TRIP
115% OF FLA
ACC. TIME
10 secretary.
STC PT IV CL AT
0 0 30 400 10
OVERLOAD DELAY
4 SEC AT 5 FLA
MST NOS SP SI CD
30 10 30 15 5
UNDELVOLT. TRIP
300 VOLT
NUMBER OF STARTS
10
SPC DT FT
0 10 0
UNDERVOLT.
DELAY 5 Secretary
STARTS PERIOD
30 MIN.
DA: IV CL AT DT
30 400 10 10
OVERVOLT. TRIP
480 VOLT.
START INHIBIT
15 MIN.
DA: FLA
105
OVERVOLT. DELAY
2 Secretary.
ES SST MSST
10 8 30
STORE ENABLE
MAIN PARMETERS
STORE ENABLE
START PARAMETERS
17 18 FREL
0 0 0
IMM/S.PIN RELAY
IMM 0
0
ANALOG OUTPUT
NORMAL
DRV BAUD PAR SER
0
96
0 248
Ba
ck t Top
o
Back to T
op
op
THERMISTOR
PTC 3.0
Back to T
Back to T
STORE ENABLE D.
ADJ PARMETERS
op
op
Back to T
Menu Description
MODE
PAGE 5
EN. SAVE & SL. SPD
PARAMETERS
SELECT
MODE
MODE
MODE
MODE
PAGE 6
PAGE 7
PAGE 8
PAGE 9
FAULT
PARAMETERS
I/0 PROGRAMING
PARAMETERS
COMM.
PARAMETERS
STATISTICAL DATA
SELECT
SELECT
SELECT
SELECT
PRESS
-**** -
SAVING ADJUST
0(MIN)
PROG. INPUT # 7
ENERGY SAVER
DRIVE NUMBER
0
INSULATION ALARM
OFF
PROG. INPUT # 8
DAUL ADJUSTENT
BAUD RATE
9600
INSULATION TRIP
OFF
PARITY CHECK
EVEN
STORE ENABLE
EN. SAVE & SL. SPD
AUTO RESET
NO
TOTAL # OF START
0
THERMISTOR TYPE
PTC
RELAY ON DELAY
0 Secretary.
STORE ENABLE
COMM. PARAMETERS
LAST TRIP
NO DATA
THERMISTOR TRIP
OFF
TRIP CURRENT
0% OF FLA
STORE ENABLE
FAULT PARAMETERS
ANALOG OUTPUT
NORMAL
TOTAL # OF TRIPS
0
STORE ENABLE
I/O PROG. PARAM.
MODE
STORE ENABLE
DEFAULT PARAMET.
SELECT
MODE + STORE
SAVE DEFAULT
PARAMETERS &
BACK TO
PARAMETERS
DISPLAY PAGE
% OF MOTOR FLA
RESET STATISTICS
RESET + STORE
SAVE STATISTICAL
DATA & BACK TO
PAGE 9
SELECT
PROGRAM VERSION
MVSTRT .DN-311298
SELECT
VOLTAGE ADJUST.
660V(phase to Neutral)
CURRENT ADJUST.
X% OF FLC
STATISICAL DATA
-**** -
BACK TO:
STORE ENABLE
DEFAULT PARAMET.
Trouble Shooting
Upon fault motor stops, Fault LED lights and Fault Relay operates. The LCD shows TRIP: and fault description.
Upon Alarm motor continues running, Alarm Relay operates and Fault LED flashes. The LCD shows ALARM: and
fault description
(for example: ALARM: MOTOR INSULATION).
INSULATION
ALARM
(Optional) Alarms when motor insulation level decreases below set level. Alarm ceases
automatically 60 sec. after resistance able set level. Check motor and cable insulation.
INSULATION TRIP
(Optional) Trips the starter when motor's insulation level decreases below trip value.
Check motor and cable insulation level.
THERMISTOR TRIP
(Optional) Trips the starter when motor's thermistor resistance decreases below trip value.
Check thermistor and cable's resistance, check motor temperature near thermistor location.
TOO MANY
STARTS
Trips the starter if number of starts, during Start Period exceeds the preset number. Wait
until motor and starter cool down according to Start Inhibit setting.
Trips the starter if output voltage does not reach nominal at the present max. Start time.
Check FLA, FLC, and Max Start Time settings. Increase Initial Voltage, Current Limit &
Max. start time or decrease Acceleration Time as necessary.
OVERLOAD
CAUTION
Check that Megger maximum
voltage is no more than 500!.
Disconnect terminal 21 before
performing a Megger test.
Trips the starter when current exceed the Overload Trip level and thermal register has
filled up.
Check FLA, FLC and Overload settings, check motor current, wait 15 minutes to let motor
and starter cool down before restarting.
UNDER CURRENT
Trips the starter when line current drops below the preset level for the preset time.
Check Under Current Trip and Time Delay settings, check line currents through L1,
L2, L3.
UNDER VOLTAGE
Trips the starter when line voltage drops below the preset level for the preset time.
Check Under Volatge Trip and Time Delay settings, check line voltage on L1,L2,L3 toNeutral. When voltage drops to zero, the starter trips immediately with no delay.
OVER VOLTAGE
Trips the starter when line voltage increases above a preset level for a preset time.
Check Over Voltage Trip and Time Delay settings, check line voltage onL1,L2,L3 toNeutral .
Trips the starter if 1 or 2 phases are missing. Check line voltages related to terminal 21 is
connected correctly (see page 8). Check that frequency variations are between 40-65Hz.
PHASE LOSS
PHASE SEQUENCE
Trips the starter if line phase sequence is wrong. Check line phase sequence, and if wrong,
swap two wires on line side. If motor now rotates in the wrong direction, swap two wires
on load side.
Trouble Shooting
MAX SLOW SP
TIME
Trips the starter when operating at slow speed for extended period of time.
Check that operation time at Slow Speed is shorter than Max Slow Speed Time setting.
Note : Motor and starter may be overheated when operating at slow speed for an extended
period.
WRONG
CONNECTION
Trips the starter when one or more motor phases is not properly connected to starter's load
terminals or in case of internal disconnection in motor winding. If required, may be
eliminated by using Dip Sw # 3 and wiring the soft-starter in generator mode
(programming D.A. parameters accordingly*).
SHORTED SCR
Trips the starter and prevents starting if any SCR is short-circuited or when motor windings
are shorted.
Check with an ohmmeter between L1-U, L2-V, L3-W; resistance > 20 KO.
Check for no voltage on terminals U, V, W (from parallel system or an independent byp Ass).
SCRs may fail due to: * High short current not protected by proper fuses
* High voltage spikes not protected by proper external Varistors.
* Frequent starting at maximum conditions or fault conditions.
OVER
TEMPERATURE
EXTERNAL FAULT Trips the starter when a N.O contact between terminals 19-21 closes for over two seconds.
Check contact position and cause of closure.
WRONG
PARAMETERS
Parameters not transferred from RAM to EEPROM or vice versa. After replacing the
EPROM with a new software version or after power up, press Reset, than Mode and
simultaneously and save the default parameters by pressing Store and Mode
simultaneously.
(If Fault LED is on, press Reset after stored parameters).
* NOTE:
When operating in generator mode, Shorted SCR and Wrong Connection faults are not
active.
Technical Specification
General Information:
Supply voltage.............................. Line to line 230V-690V (to be specified) 10%
Frequency .................................... 50/60Hz 4Hz (dual frequency)
Control Supply.............................. 110-120V of 220-240V 10% (to be specified)
Control Inputs and Outputs .............. 110-120V of 220-240V 10% (to be specified)
Load........................................... 3 phase, 3 wire, squirrel cage induction motor
Operating temperature................... 0 to 50
Storage trmperature....................... -20 to 70
Maximum starts per hour ................. 30 seconds
Maximum starting time.................... 4 starts per hour at 400% In, Up to60 starts per hour at lower load applications
Start-Stop Parameters:
Starter FLC...................................Starter Full Load Current 18~840 Amp
Motor FLA.....................................Motor Full Load Ampere 50%-100% of starter FLC
Pump control curves.......................6 field selectable curves preventing over pressure during start and water hammer during stop
Pulse start duration........................A pulse of 80% Un for adjustable time 0-1 second, to start high friction loads.
Initial voltage................................10%-50% Un*.
Current limit..................................100%-400% of Motor FLA*
Ramp-up time................................1-30 seconds*
Ramp-down time............................1-30 seconds*
Dual adjustments...........................Secondary Start Stop characteristics for INITIAL VOLTAGE,CURRENT LIMIT,ACCELERATION TIME,DECELERATION TIME and MOTOR FLA.
Energy saving...............................Activated when motor is lightly loaded for extended periods of time
Slow speed torque.........................Maximum forque produced while motor is operating at 1/6 of nominal speed to a maximum of 30 seconds
Tacho and linear acceleration..........12 selectable curves-defines gain control to improve the tacho feedback linearity
Starting from diesel generator..........Special starting characteristics become operative via an internal dip switch.(Contact terminal 8,for dual adjustment)
Motor protection:
Too many starts .........................................Determines maximum number of starts allowable during Start Period Range 1-10 starts in start period 1-60 minutes
Start inhibit..................................................Prevents starting for a variable period of 1-60 minutes ofter TOO MANY STARTS is indicated
Long start time (stall protection)..................Starter trips if the full motor speed is not reached within the maximum start time of 1-30 seconds*
Electronic fuse (shear pin)..........................Trips starter in 1 cysle at 850% in during starting and 200%-850% in during running
Electronic overload (It)2 ...............................Adjustable between 75%-150% of motor FLA overload curve can be selected by setting trip time at 500% in,1-10 seconds
Under current..............................................Starter trips when current drops below 20%-90% ln,time delay 1-40 seconds.
Under voltage(**)........................................Starter trips when mains voltage drops below 120-600V (Phase to Neutral),time delay 1-10 seconds.
Over voltage...............................................Starter trips when mains voltage increases above 150-750V(Phase to Neutral),time delay 1-10 seconds.
Phase loss,(under/over frequency**)..........Starter trips when 1 or 2 phases fail and when frequency is 4Hz of nominal frequency.
Phase sequence.........................................Starter trips when phase sequence is incorrect.
Long slow speed time.................................Starter trips if operating at slow speed longer than 30 seconds
Wrong connection.......................................Prevents starting if the motor is incorrectly connected to the starter
Shorted SCR...............................................Prevents startion when one or more SCRs are shorted
Heatsink over temperature..........................Starter trips when heatsink temperature rises above 85
External fault...............................................Starter trips when an external contact closes for 2 seconds
Motor insulation (optional)...........................Alarm level setting 0.2-5M .Trips when motor insulation decreases below 0.2-5M setting.The thyristors must be protected against short circuit
Thyristor Protection.....................................Metal Oxide Varistors(MOVs) and snubber circuits
Analogue I/O...............................................Input of motor overheat signal Ouput of analog signals of motor current
* Special settings,
** With optional Auto Reset.
Technical Specification
Control:
Displays .....................................................LCD in 4 selectable languages and 8 LEDs
Keypad....................................................... 6 clearly defined keys for easy setting
Aux Contact Immediate ............................... 1 C/O,8A,250V A.C,2000VA(delay 0-60 secon)
Aux Contact End Of Acceleration ................. 1 C/O,8A,250V A.C,2000VA(delay 0-120 secon)
Fault Contact................................. .............1 C/O,8A,250V A.C,2000VA(selectable as trip or trip fail safe)
Insulation Alarm Contact (option)..... ............1 C/O,8A,250V A.C,2000VA
Communication (option).............................. RS 485 with Modbus/Profibus protocal for full control and supervision
Standards:
Dielectric Test................................ 2500VAC
Degree of Protection ...................... IP 20 for frame size A
IP 00 for frame sizes B, C, D, E, F
Pollution Degree ............................ 3
EMC
Emissions
Immunity
EN 55011
EN 55082-2
Safety
EN 600947-1
UL508C
CISPR 11 Class A
ESD 8KV air, IEC 801-2
Electric RF field 10 V/m, 20-1000MHz, IEC 801-3
Fast transients 2KV, IEC 801-4
Related to safety requirements.
75.................................185(W)............................10~12kg
HPS2DN90
145...............................210(W)............................13~15kg
HPS2DN175
250.............................255(W).............................25~28kg
HPS2DN300
840.............................300(W).............................51~64kg
Page
Subject
42
43
44
45
46
47
48
Ordering Information
49
Dimensions
Max.
Mot.
FLA
Term
Screw
Term
Screw
Mech.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
18
30
45
60
75
110
145
175
210
250
300
370
470
570
720
840
3x2.5 +2.5
3x6 +6
3x6 +6
3x10 +10
3x16 +16
3x50 +25
3x70 +35
3x95 +50
3x150 +70
3 x 180+90
2 x (3 x 100+ 50)
2 x (3 x 120+ 70)
2 x (3 x 185+ 95)
2 x (3 x 240+120)
3 x (3 x 185+ 95)
3 x (3 x 240+120)
M8
M8
M8
M10
M10
M10
M10
M10
M10
M10
M10
180
180
180
220
220
220
220
220
220
220
220
Motor Power
230V
400V
500V
690V
1140V
7.5
11
15
25
HPS2DN18
X+X...
7.5
15
18.5
25
45
HPS2DN30
X+X...
15
22
25
37
60
HPS2DN45
X+X...
18.5
30
37
55
90
HPS2DN60
X+X...
22
37
45
59
110
HPS2DN75 -
X+X...
25
45
55
75
135
HPS2DN90
X+X...
30
55
75
90
165
HPS2DN110 -
X+X...
37
75
90
132
225
HPS2DN145 -
X+X...
45
90
110
160
270
HPS2DN175 -
X+X...
55
110
132
200
330
HPS2DN210 -
X+X...
75
132
160
220
396
HPS2DN250 -
X+X...
90
160
200
257
480
HPS2DN300 -
X+X...
110
200
250
355
600
HPS2DN370 -
X+X...
132
250
315
450
750
HPS2DN470 -
X+X...
160
315
400
560
945
HPS2DN570 -
X+X...
200
400
500
710
1200
HPS2DN720 -
X+X...
250
450
560
800
1350
HPS2DN840 -
X+X...
Control inputs
Functions Options
Motor Power
230V
4
400V
7.5
500V
11
690V
15
1140V
25
7.5
15
18.5
25
45
HPS2DN30
10000
100A
15
22
25
37
60
HPS2DN45
12000
160A
18.5
30
37
55
90
HPS2DN60
15000
200A
22
37
45
59
110
HPS2DN75
18000
250A
25
45
55
75
135
HPS2DN90
40000
315A
30
55
75
90
165
HPS2DN110
60000
315A
37
75
90
132
225
HPS2DN145
100000
400A
45
90
110
160
270
HPS2DN175
140000
450A
55
110
132
200
330
HPS2DN210
200000
630A
75
132
160
220
396
HPS2DN250
400000
630A
90
160
200
257
480
HPS2DN300
600000
700A
110
200
250
355
600
HPS2DN370
700000
900A
132
250
315
450
750
HPS2DN470
800000
1250A
160
315
400
560
945
HPS2DN570
1200000
1500A
200
400
500
710
1200
HPS2DN720
1600000
1800A
250
450
560
800
1350
HPS2DN840
2000000
1800A
63A
Note:The above table is for maximum starting current of 500% of FLC, maximum starting time of 30 seconds and rated voltage of 440V.
Suitable adjustments to the recommended ratings may be necessary to cope with special sevice conditions such as repetitive starting
conditions,high enclosure temperature (ambient ) and forced cooling.Consult works for adyice.
1.Choose the type of starter which at least bear 5 X FLC for 30 seconds.
2
2.Choose the fust whose I t during its continous operation should not exceed the Max I t recommended.
Run
Stop
On
LED is lit.
Motor Insulation test (option) - two levels for Alarm & Trip when
installed, operates upon no main voltage
Motor Thermistor (option) - programmable PTC/NTC, With
adjustable Trip level.
* Available from software version 12/12/03
Soft Stop
Country:
Fax Number:
Serial Number:
Purchasing Date:
Sale / Installation Date:
Failure Date:
Program Version:
Press MODE + , press SELECT twice, the LCD displays the program
version.
Connection Diagram & Supply Network Type. Circle the correct main supply and add or erase parts I the drawing:
Star, Delta, with/without neutral or ground
Bypas
Contacto
S
Line
Contacor
L1 L2 L3
Fault
Insulation 30
29
28
Alarm
32
31
Run
E.O.A
27
26
25
24
23
22
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
U
V W
S
M
Application Description:
Starter FLC:
Motor FLC:
Initial Voltage:
Acceleration Time:
Last Trip:
Current Limit:
Trip Current:
Total Number Of Trips:
Where:
1,375,000
2
2
I% -OLT
%=Actual Current
OLD
(LNSECONDS)
6
100
Motor FLA
Example 1:
Example 2:
1,375,000
150 2-1152
=99sec
1,375,000
2
500 -115
Example 3:
4
6
=4sec
1,375,000
2
250 -115
10
6
=47sec
Dimensions (mm)
Block Diagram for the HPS2DN control, power and firing module, inputs and option boards.
Isolated
Inputs
Keypad
Power
supply
Led
Instruments
display
MICRO
PROCESSOR
Firing circuitry
LCD
display
SCRs
V measurements
Options:
RS 485 com.
Insulation
Tachometer in
Analogue out
Thermisrtor
Notes:
Memory
Statistics
Faults
SCRs
Preparation
for by pass
All protection
remain active
Ordering information
Example:
210
xxx
HPS2DN
Starter FLC
(1)
Main voltage
(2)
B
x
2
x
2
x
1+3
x+x...
(4)
Options
(5)
4Hz
Code name
A
Specify
230VAC
For
220~240VAC
400VAC
380~420VAC
500VAC
480~520VAC
690VAC
660~690VAC
1140VAC
1000~1200VAC
Specify
For
(terminals 1-3)
115VAC
110~120VAC
50/60Hz 4Hz
230VAC
220~240VAC 10%
Code name
Specify
(terminals 4-9)
115VAC
110~120VAC
50/60Hz 4Hz
230VAC
220~240VAC 10%
(5)Required Options
Code name
10%
For
10%
Introduction
No options
indicate,for example.1+3
(Comm+Insulation)
Insulation tester
8
9
lluminated LCD
Tachometer for special drive systems (consult factory)
Dimensions (mm)
HPS2DN175 250
235
183
125
310
218
HPS2DN17 145
280
7.5
265
30 45
45 30
382
15
117
117
25
R3.5
402
380
446
260
12
26.5
R5.5
313
Max400
13
7(4x)
11
41
300
HPS2DN310 950
205
66
237
310
25
F
540
210
L2
L3
600
572
L1
6 Hole 9X7
65
210
Dimension
14
125
125
173.5
125
173.5
34
E
HPS2DN 300...470
34
25
65
HPS2DN 570...720
41.5
40
62
HPS2DN 840
46.5
50
62.5
V T3B
U T2B