Design of One Way Slab

Reference:

NSCP 2001 Volume 1


Design of Reinforced Concrete by J.C. McCormac

Dimension:
cc

20

mm

100

mm

1000 mm

Reinforcement:
main bar
=
temp bar
=

12 mm
12 mm

Material Strength:

d
=
74
mm
Loads:
Mutop
= 2.6709 kN-m
Mubot
= 3.0048 kN-m

fc'
fy
M

=
=

21
276

0.9

Loads:
W SLAB = 2.400 kPa
W DL
= 2.000 kPa
W LL
= 1.900 kPa
WU

Mpa
Mpa

= 9.390 kPa

Check if One Way Slab


s / l < 0.50
s = 1.600 m
l = 4.400 m
s
= 0.364 one way slab!
l
Solve for hmin
hmin

when fy = 415
when fy = 415
simply supported
multiply by:
one end continuous
fy
0.40 +
= 1.07
two end continuous
415
cantilever
s
hmin =
= 57.14 ok!
28
Solve fo 1 :
NSCP Section 410.3.7.3
> 0.65
a.) if fc' > 30 Mpa ;
b.) if fc' < 30 Mpa ;
1 = 0.85
( fc' - 30 )
1 = 0.85 - 0.05
7
1 = 0.914
use:
1 = 0.85 > 0.65
ok!
Solve for max :
Solve for min :
s / 20
s / 24
s / 28
s / 10

NSCP Section 410.4.3


max 0.75 bal
bal

NSCP Section 410.6.1


min

0.85 1 fc'

600

fy

600 + fy

bal 0.0377
max 0.0282

fc'

4 fy
min 0.0042

>
<

min

1.4

fy
min 0.0051

use:
min 0.0051

Main Reinforcements
m = 0.847 fc' / fy
R = Mu / bd2
reqd = m - m2 - 2Rm/fy

Top Bars
0.0644
0.5419

Bot Bars
0.0644
0.6097

units
Mpa

0.0020

0.0022

supplied

0.0051

0.0051

Asreqd = bd

375.36
113.10

375.36
113.10

mm2
mm2

b.Temp Reinf.
NSCP Section 407.13

301.30
300.00

301.30
300.00

pcs
pcs

s < 5h = 500
s < 450

As main bar
spcgreqd
Provide (spcg)

Spcg Limitations:
a. Main Reinf.
NSCP Section 407.7.5
s <

3h = 300

s < 450

Temperature / Shrinkage Reinforcements


NSCP Section 407.13
Astemp
= 0.002bh
Astemp

spcgreqd

= 565.49 mm
= 450 mm

Provide
Summary:
Top Bars
Bot Bars
Temp Bars
267853989.xls

200

mm2

12 @ 300 mm
12 @ 300 mm
12 @ 450 mm
One Way Slab

Analysis of Two-Way Slab with Beams


Reference:

NSCP 2001 Volume 1


Design of Reinforced Concrete by J.C. McCormac

A. Computation of hmin

NSCP Section 409.6.3.3

1. For m greater than 0.20 but not greater than 2.0


hmin =

ln ( 0.80 + fy / 1500 )
36 + 5 ( m - 0.20 )

> 125 mm

2. For m greater than 2.0


hmin =

ln ( 0.80 + fy / 1500 )
36 + 9

>

90 mm

where:
m
= ave. of

= ratio of flexural stiffness of beam section to flexural


stiffness of a width of slab bounded laterally by center
lines of adjacent panels on each side of the beam
ECBB
=

ECSS
ln

= length of clear span in long direction of two-way


construction, measured face to face of supports
= ratio of clear span in long to short direction of twoway slabs

B. Total Factored Static Moment for a Span


NSCP Section 413.7.2.2
u l2 ln2
Mo
=
8
where:
l1 = length of span in direction that moments are being
determined, measured c to c of supports
l2 = length of span transverse to l1, measured c to c
of supports
ln = length of span in direction that moments are being
determined, measured face to face of supports
C. Negative & Positive Factored Moments
1. Interior Spans
Negative Factored Moments
Positive Factored Moments

NSCP Section 413.7.3

= 0.65
= 0.35

2. Exterior Spans

Interior Negative
Factored Moment
Positive Factored
Moment
Exterior Negative
Factored Moment

Slab Without Beams Between


Interior Supports
Without Edge
With Edge
Beams
Beams

Exterior Edge
Unrestrained

Slabs With
Beams
Between All
Supports

0.75

0.70

0.70

0.70

0.65

0.63

0.57

0.52

0.50

0.35

0.00

0.16

0.26

0.30

0.65

D. Factored Moments in Column Strips

Exterior Edge
Fully
Restrained

NSCP Section 413.7.4

1. Interior Negative Factored Moments (%)


l2 / l1

0.50

1.00

2.00

1 l1 / l2 = 0

75

75

75

1 l1 / l2 > 1

90

75

45

267853989.xls

Two Way Slab

2. Exterior Negative Factored Moments (%)


l2 / l1
1 l1 / l2 = 0
1 l1 / l2 > 1

0.50

1.00

2.00

t = 0

100

100

100

t > 2.5

75

75

75

t = 1

100

100

100

t > 2.5

90

75

45

3. Positive Factored Moments (%)


l2 / l1

0.50

1.00

2.00

1 l1 / l2 = 0

60

60

60

1 l1 / l2 > 1

90

75

45

Note:
if:

NSCP Section 413.7.5


1 l2 / l1 > 1.0
85 % - beam
15 % - slab
1 l2 / l1 < 1.0
interpolate from 0% to 85%

where:
1
= in direction of l1
t
= ratio of torsional dtiffness of edge beam section to
flexural stiffness of a width od slab equal to span length
of beam, c to c of supports
ECBC
t
=
2ECSS
= cross-sectional constant to define torsional properties
x x3y
= 1 - 0.63
y 3

C
C

E. Slab Reinforcements

y2
x2
y1
y1 - x2
x1

NSCP Section 413.4

Spacing of reinforcement at critical sections shall


not exceed two times the slab thickness
F. Column Strip and Middle Strip
l2
`

Colum
n Strip

Middle Strip

Colum
n Strip

l1

0.25 l1 or 0.25 l2, which is smaller

267853989.xls

Two Way Slab

Design of Two-Way Slab with Beams


Reference:

NSCP 2001 Volume 1


Design of Reinforced Concrete by J.C. McCormac
Design of Concrete Structures by Arthur H. Nilson

fc'CS

21 Mpa

fc'CB

=
=

21 Mpa
276 Mpa

fy
M

0.90

W DL

4.80 kPa

W LL

2.50 kPa

250 x 400

WuDL

10.92 kPa

WuLL

=
=

4.25 kPa
15.17 kPa

=
=

12 mm
125 mm

93 mm

Wu
bar
h
deff
la
lb

W SLAB

4.00 m
b

5.00 m
300 x 500 C

D 300 x 500
B
250 x 400

0.779

3.00 kPa
5.00 m

5.00 m

4.00 m

3.00 m

A. Solve for m
Side A
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
CB

= 1.33E+09 mm4

Side B
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
CB

= 1.33E+09 mm
Side C
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
4

CB

= 3.13E+09 mm
Side D
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
4

CB

= 3.13E+09 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh / 12

CS

= 7.32E+08 mm4

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 8.14E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh / 12

CS

= 7.32E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh / 12

CS

= 5.70E+08 mm

= 1.82

= 1.64

= 4.27

= 5.49

= 3.30

hmin =

ln ( 0.80 + fy / 1500 )
36 + 5 ( m - 0.20 )

hmin = 125.00 mm
267853989.xls

> 125 mm

ECBCB
ECSCS

ECBCB
ECSCS

ln = 4.750 m
B. Check Minimum Thickness
1. For m greater than 0.20 but not greater than 2.0

ECSCS

A + B + C + D

ECBCB

1.284

ECBCB
ECSCS

2. For m greater than 2.0


hmin =

ln ( 0.80 + fy / 1500 )
36 + 9

>

90 mm

hmin = 100.00 mm
Therefore use: hmin = 100.00 mm ok!
D. Check Slab on Shear
Va
= CaWulalb

( Coefficient Method )

la/lb

by linear interpolation
Ca
0.750
0.7600

Ca
Vu

Mu(-) Mu(+)DL Mu(+)LL

Vb
Ca

= CbWulalb

1.00 0.500

0.045

0.018

0.027

= 0.7311 kN

0.779

x 0.7311

0.95 0.550

0.050

0.020

0.030

Cb

= 0.2689 kN
= 194.91 kN
= 71.70 kN
= 0.85 fc'CS(1000)(deff)

0.800

0.7100

0.90 0.600
0.85 0.660
0.80 0.710

0.055
0.060
0.065
0.069
0.074
0.077
0.081
0.084
0.086

0.022
0.024
0.026
0.028
0.030
0.032
0.034
0.035
0.037

0.034
0.037
0.041
0.045
0.049
0.053
0.058
0.062
0.066

Va
Vb
Vc
Vc

= 362.25 kN

Cb

ok!

D. Determine Design Moments


Continuous Edge
Negative Moments:
2
Ma = CaWula

0.750

0.2400

0.779
0.800

x 0.2689
0.2900

0.75
0.70
0.65
0.60
0.55
0.50
la/lb

( Coefficient Method )
by linear interpolation
Ca
0.750
0.0690

0.760
0.810
0.850
0.890
0.920
0.940

Cb

Mb
Ca

2
= CbWulb

0.779

x 0.0667

1.00 0.500

0.045

0.018

0.027

= 0.0667 kN

0.800

0.0650

0.95 0.450

0.041

0.016

0.025

Cb

= 0.0249 kN
= 13.85 kN-m
=
8.52 kN-m

0.014

0.022

0.0220
x 0.0249
0.0270

0.90
0.85
0.80
0.75
0.70
0.65

0.037

0.750
0.779
0.800

0.012
0.011
0.009
0.007
0.006
0.004

0.019
0.017
0.014
0.012
0.010
0.007

Ma
Mb

Cb

0.400
0.340
0.290
0.240
0.190
0.150

0.60 0.110

0.031
0.027
0.022
0.017
0.014
0.010

MaLL

2
= CaLLWuLLla

0.779

x 0.0268

0.55 0.080

0.007

0.003

0.006

CaDL

= 0.0268 kN

0.800

0.0260

0.50 0.060

0.006

0.002

0.004

CaLL

= 0.0427 kN

MaDL

4.01 kN-m

MaLL
MaTOT

=
=

2.48 kN-m
6.50 kN-m

MbDL
MbLL

2
= CbDLWuDLlb
2
= CbLLWuLLlb

CbDL

= 0.0102 kN

CbLL

= 0.0157 kN

MbDL

2.50 kN-m

MbLL
MbTOT

=
=

1.51 kN-m
4.01 kN-m

Positive Moments:
2
MaDL
= CaDLWuDLla

E. Design Reinforcements:
Solve fo 1 :
> 0.65
a.) if fc' > 30 Mpa ;
1

0.85 - 0.05

by linear interpolation
CaDL 0.750
0.0280

CaLL

CbLL

267853989.xls

x 0.0427
0.0410

0.779

x 0.0102

0.800

0.0110

0.750

0.0140

0.779
0.800

x 0.0157
0.0170

NSCP Section 410.3.7.3


b.) if fc' < 30 Mpa ;
1 = 0.85
( fc' - 30 )
7

ok!

NSCP Section 410.4.3


max 0.75 bal

Solve for min :


NSCP Section 410.6.1

0.85 1 fc'

600

fy

600 + fy

bal 0.0377

0.0450

0.779
0.800

by linear interpolation
CbDL 0.750
0.0090

1 = 0.914
use:
1 = 0.85 > 0.65
Solve for max :

bal

0.750

min

fc'

4 fy
min 0.0042
use:

>
<

min

1.4

fy
min 0.0051

max 0.0282
Middle Strip
Design Moments
Bar Diameter
m = 0.847 fc' / fy
R = Mu / bdeff2

min 0.0051
Short Span
Top Bars
Bot Bars
13.85
6.50
12
12
0.0644
0.0644

Long Span
Top Bars
Bot Bars
8.52
4.01
12
12
0.0644
0.0644

1.7791

0.8346

1.0946

0.5154

reqd = m - m2 - 2Rm/fy

0.0068

0.0031

0.0041

0.0019

supplied

0.0068

0.0051

0.0051

0.0051

Asreqd = bd
As main bar
spcgreqd

632.90
113.10

471.74
113.10

471.74
113.10

471.74
113.10

178.70
175.00
Top Bars

239.75
225.00
Bot Bars

239.75
225.00
Top Bars

239.75
225.00
Bot Bars

262.50
250.00

337.50
250.00

337.50
250.00

337.50
250.00

Provide (spcg)
Column Strip
spcgreqd = 3/2(spcgMID-STRIP)
Provide (spcg)

E. Temperature / Shrinkage Reinforcements:


As
= 0.002bh
b.Temp Reinf.
As
= 250.00 mm2
NSCP Section 407.13
bar = 12.00 mm
s < 5h = 625
Asbar = 113.10 mm2
spcg = 450.00 mm

267853989.xls

s < 450

Design of Two-Way Slab with Beams


Reference:

NSCP 2001 Volume 1


Design of Reinforced Concrete by J.C. McCormac
Design of Concrete Structures by Arthur H. Nilson

fc'CS

21 Mpa

fc'CB

=
=

21 Mpa
276 Mpa

fy
M

0.90

W DL

4.35 kPa

W LL

1.92 kPa

WuDL

9.45 kPa

WuLL
Wu
bar
h
deff
la
lb

=
=

3.26 kPa
12.71 kPa

=
=

12 mm
100 mm

68 mm

W SLAB

250 x 400
A

4.00 m

200 x 400 C

D 200 x 400
B
200 x 400

4.00 m

0.477
2.40 kPa
2.00 m

2.00 m

A. Solve for m
Side A
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
CB

= 1.33E+09 mm
Side B
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
4

CB

= 1.07E+09 mm
Side C
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
4

CB

= 1.07E+09 mm
Side D
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
4

CB

= 1.07E+09 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh / 12

CS

= 1.67E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 3.33E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 1.67E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 8.33E+07 mm

= 8.00

= 3.20

= 6.40

= ###

= 7.60

hmin =

ln ( 0.80 + fy / 1500 )
36 + 5 ( m - 0.20 )

> 125 mm

hmin = 125.00 mm
2. For m greater than 2.0
hmin =
hmin =
267853989.xls

ln ( 0.80 + fy / 1500 )
36 + 9
90.00 mm

>

90 mm

ECBCB
ECSCS

ECBCB
ECSCS

ln = 3.775 m
B. Check Minimum Thickness
1. For m greater than 0.20 but not greater than 2.0

ECSCS

A + B + C + D

ECBCB

2.097

ECBCB
ECSCS

Therefore use:

267853989.xls

hmin =

90.00 mm ok!

D. Check Slab on Shear


Va
= CaWulalb

( Coefficient Method )
by linear interpolation
Ca
0.750
0.7600

= CbWulalb

Vb
Ca

la/lb

= 1.0332 kN

Cb

= -0.0332 kN
Va
= 89.26 kN
Vb =
-2.87 kN
0.85
fc'CS(1000)(deff)
Vc =
Vc = 264.87 kN ok!
D. Determine Design Moments
Continuous Edge
Negative Moments:
2
Ma = CaWula

Cb

Ca
Vu

Mu(-) Mu(+)DL Mu(+)LL

1.00 0.500

0.050

0.027

0.032

0.477

x 1.0332

0.95 0.550

0.055

0.030

0.035

0.800

0.7100

0.750

0.2400

0.90 0.600
0.85 0.660
0.80 0.710

0.477
0.800

x -0.0332
0.2900

0.760
0.810
0.850
0.890
0.920
0.940

0.060
0.066
0.071
0.076
0.081
0.085
0.089
0.092
0.094

0.033
0.036
0.039
0.043
0.046
0.050
0.053
0.056
0.059

0.039
0.043
0.048
0.052
0.057
0.062
0.067
0.072
0.077

0.75
0.70
0.65
0.60
0.55
0.50
la/lb

( Coefficient Method )
by linear interpolation
Ca
0.750
0.0760

Cb

Mb
Ca

2
= CbWulb

0.477

x 0.1033

1.00 0.500

0.050

0.027

0.032

= 0.1033 kN

0.800

0.0710

0.95 0.450

0.045

0.024

0.029

Cb

= -0.0033 kN
=
4.26 kN-m
=
-0.60 kN-m

0.750
0.477
0.800

0.0240
x -0.0033
0.0290

0.90
0.85
0.80
0.75
0.70
0.65

0.022
0.019
0.016
0.013
0.011
0.009
0.007

0.026
0.023
0.020
0.016
0.014
0.011
0.009

0.60 0.110

0.040
0.034
0.029
0.024
0.019
0.015
0.011

MaLL

2
= CaLLWuLLla

0.477

x 0.0649

0.55 0.080

0.008

0.005

0.007

CaDL

= 0.0649 kN

0.800

0.0390

0.50 0.060

0.006

0.004

0.005

CaLL

= 0.0739 kN

MaDL

1.99 kN-m

MaLL
MaTOT

=
=

0.78 kN-m
2.77 kN-m

MbDL
MbLL

2
= CbDLWuDLlb
2
= CbLLWuLLlb

CbDL

= -0.0034 kN

CbLL

= -0.0059 kN

MbDL

-0.46 kN-m

MbLL
MbTOT

=
=

-0.27 kN-m
-0.73 kN-m

Ma
Mb

Cb

Positive Moments:
2
MaDL
= CaDLWuDLla

E. Design Reinforcements:
Solve fo 1 :
> 0.65
a.) if fc' > 30 Mpa ;
1

0.85 - 0.05

by linear interpolation
CaDL 0.750
0.0430

CaLL

CbLL

267853989.xls

x 0.0739
0.0480

0.477

x -0.0034

0.800

0.0160

0.750

0.0160

0.477
0.800

x -0.0059
0.0200

NSCP Section 410.3.7.3


b.) if fc' < 30 Mpa ;
1 = 0.85
( fc' - 30 )
7

ok!

NSCP Section 410.4.3


max 0.75 bal

Solve for min :


NSCP Section 410.6.1

0.85 1 fc'

600

fy

600 + fy

bal 0.0377
max 0.0282

0.0520

0.477
0.800

by linear interpolation
CbDL 0.750
0.0130

1 = 0.914
use:
1 = 0.85 > 0.65
Solve for max :

bal

0.750

0.400
0.340
0.290
0.240
0.190
0.150

min

fc'

4 fy
min 0.0042

use:
min 0.0051

>
<

min

1.4

fy
min 0.0051

REINFORCEMENTS

Short Span

Long Span

Bot Bars
2.77
12
0.0644

Discont.
Top Bars
0.92
12
0.0644

Cont.
Top Bars
-0.60
12
0.0644

Bot Bars
-0.73
12
0.0644

Discont.
Top Bars
-0.24
12
0.0644

1.0227

0.6648

0.2216

-0.1444

-0.1752

-0.0584

reqd = m - m - 2Rm/fy

0.0038

0.0025

0.0008

-0.0005

-0.0006

-0.0002

supplied

0.0051

0.0051

0.0051

0.0051

0.0051

0.0051

Asreqd = bd
As main bar
spcgreqd

344.93
113.10

344.93
113.10

344.93
113.10

344.93
113.10

344.93
113.10

344.93
113.10

327.89
200.00
Top Bars

327.89
200.00
Bot Bars

327.89
200.00
Top Bars

327.89
200.00
Top Bars

327.89
200.00
Bot Bars

327.89
200.00
Top Bars

300.00
200.00

300.00
200.00

300.00
200.00

300.00
200.00

300.00
200.00

300.00
200.00

Middle Strip
Design Moments
Bar Diameter
m = 0.847 fc' / fy
R = Mu / bdeff2
2

Provide (spcg)
Column Strip
spcgreqd = 3/2(spcgMID-STRIP)
Provide (spcg)

Cont.
Top Bars
4.26
12
0.0644

E. Temperature / Shrinkage Reinforcements:


As
= 0.002bh
b.Temp Reinf.
As
= 200.00 mm2
NSCP Section 407.13
bar = 12.00 mm
s < 5h = 500
Asbar = 113.10 mm2
spcg = 450.00 mm

267853989.xls

s < 450

Design of Two-Way Slab with Beams


Reference:

NSCP 2001 Volume 1


Design of Reinforced Concrete by J.C. McCormac
Design of Concrete Structures by Arthur H. Nilson

fc'CS

21 Mpa

fc'CB

=
=

21 Mpa
276 Mpa

fy
M

0.90

W DL

4.80 kPa

W LL

2.50 kPa

WuDL

10.92 kPa

WuLL
Wu
bar
h
deff
la
lb

=
=

4.25 kPa
15.17 kPa

=
=

12 mm
125 mm

93 mm

W SLAB

250 x 400
A
long span
3.70 m

300 x 500 C

D 300 x 500
B
250 x 400

4.00 m

4.00 m

0.932
3.00 kPa

A. Solve for m
Side A
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
CB

= 1.33E+09 mm

Side B
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
CB

= 1.33E+09 mm

Side C
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
CB

= 3.13E+09 mm

Side D
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
CB

= 3.13E+09 mm4

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 3.01E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 3.01E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 6.51E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh / 12

CS

= 3.26E+08 mm4

= 4.43

= 4.43

= 4.80

= 9.60

= 5.81

hmin =

36 + 5 ( m - 0.20 )

> 125 mm

hmin = 125.00 mm
2. For m greater than 2.0
hmin =

ln ( 0.80 + fy / 1500 )
36 + 9

hmin =
Therefore use:
267853989.xls

>

90.00 mm
hmin = 90.00 mm ok!

90 mm

ECSCS

ECBCB
ECSCS

ln ( 0.80 + fy / 1500 )

ECBCB

ln = 3.700 m
B. Check Minimum Thickness
1. For m greater than 0.20 but not greater than 2.0

ECSCS

A + B + C + D

ECBCB

1.072

ECBCB
ECSCS

D. Check Slab on Shear


Va
= CaWulalb

( Coefficient Method )
by linear interpolation
Ca
0.750
0.8800

= CbWulalb

Vb
Ca

= 0.8070 kN

Cb

= 0.1930 kN
Va
= 156.28 kN
Vb = 37.37 kN
Vc = 0.85 fc'CS(1000)(deff)
Vc = 362.25 kN ok!
D. Determine Design Moments
Continuous Edge
Negative Moments:
2
Ma = CaWula
Ca
Ma

la/lb

Cb

Ca
Vu

Mu(-) Mu(+)DL Mu(+)LL

1.00 0.710

0.071

0.033

0.035

0.932

x 0.8070

0.95 0.750

0.075

0.036

0.038

0.800

0.8600

0.750

0.1200

0.90 0.790
0.85 0.830
0.80 0.860

0.932
0.800

x 0.1930
0.1400

0.079
0.083
0.086
0.088
0.091
0.093
0.095
0.096
0.097

0.039
0.042
0.045
0.048
0.051
0.054
0.056
0.058
0.061

0.042
0.046
0.051
0.055
0.060
0.064
0.068
0.073
0.078

0.027
0.024
0.021
0.017
0.015

0.032
0.029
0.025
0.022
0.019

( Coefficient Method )
by linear interpolation
Ca
0.750
0.0880

0.75
0.70
0.65
0.60
0.55
0.50
la/lb

0.880
0.910
0.930
0.950
0.960
0.970

1.00
0.95
0.90
0.85

0.290
0.250
0.210
0.170

Cb

0.80 0.140

MaLL

2
= CaLLWuLLla

0.932

x 0.0371

0.75 0.120

0.012

0.016

CaDL

= 0.0371 kN

0.800

0.0450

0.70 0.090

0.009

0.013

CaLL

= 0.0404 kN

0.65 0.070

0.007

0.010

= 0.0807 kN
= 14.57 kN-m

0.932
0.800

Positive Moments:
2
MaDL
= CaDLWuDLla

by linear interpolation
CaDL 0.750
0.0480

MaDL

4.82 kN-m

MaLL
MaTOT

=
=

2.04 kN-m
6.86 kN-m

MbDL
MbLL

2
= CbDLWuDLlb
2
= CbLLWuLLlb

CbDL

= 0.0229 kN

CbLL

= 0.0269 kN

MbDL

3.43 kN-m

MbLL
MbTOT

=
=

1.57 kN-m
5.00 kN-m

E. Design Reinforcements:
Solve fo 1 :
> 0.65
a.) if fc' > 30 Mpa ;
1

0.85 - 0.05

CaLL

CbLL

267853989.xls

0.0550

0.60 0.050

0.006

0.008

0.932
0.800

x 0.0404
0.0510

0.55 0.040
0.50 0.030

0.004
0.003

0.006
0.005

0.932

x 0.0229

0.800

0.0150

0.750

0.0160

0.932
0.800

x 0.0269
0.0190

NSCP Section 410.3.7.3


b.) if fc' < 30 Mpa ;
1 = 0.85
( fc' - 30 )
7

ok!

NSCP Section 410.4.3


max 0.75 bal

Solve for min :


NSCP Section 410.6.1

0.85 1 fc'

600

fy

600 + fy

bal 0.0377
max 0.0282

0.750

by linear interpolation
CbDL 0.750
0.0120

1 = 0.914
use:
1 = 0.85 > 0.65
Solve for max :

bal

x 0.0807
0.0860

min

fc'

4 fy
min 0.0042

use:
min 0.0051

>
<

min

1.4

fy
min 0.0051

REINFORCEMENTS
Middle Strip
Design Moments
Bar Diameter
m = 0.847 fc' / fy
R = Mu / bdeff2

Short Span
Cont.
Top Bars
14.57
12
0.0644

Bot Bars
6.86
12
0.0644

Discont.
Top Bars
2.29
12
0.0644

Long Span
Discont.
Bot Bars
Top Bars
5.00
1.67
12
12
0.0644
0.0644

1.8720

0.8813

0.2938

0.6421

0.2140

reqd = m - m2 - 2Rm/fy

0.0072

0.0033

0.0011

0.0024

0.0008

supplied

0.0072

0.0051

0.0051

0.0051

0.0051

Asreqd = bd
As main bar
spcgreqd

668.01
113.10

471.74
113.10

471.74
113.10

471.74
113.10

471.74
113.10

169.31
150.00
Top Bars

239.75
225.00
Bot Bars

239.75
225.00
Top Bars

239.75
225.00
Bot Bars

239.75
225.00
Top Bars

225.00
225.00

337.50
250.00

337.50
250.00

337.50
250.00

337.50
250.00

Provide (spcg)
Column Strip
spcgreqd = 3/2(spcgMID-STRIP)
Provide (spcg)

E. Temperature / Shrinkage Reinforcements:


As
= 0.002bh
b.Temp Reinf.
As
= 250.00 mm2
NSCP Section 407.13
bar = 12.00 mm
s < 5h = 625
Asbar = 113.10 mm2
spcg = 450.00 mm

267853989.xls

s < 450

Design of Two-Way Slab with Beams


Reference:

NSCP 2001 Volume 1


Design of Reinforced Concrete by J.C. McCormac
Design of Concrete Structures by Arthur H. Nilson

fc'CS

21 Mpa

fc'CB

=
=

21 Mpa
276 Mpa

fy
M

0.90

W DL

4.80 kPa

W LL

2.50 kPa

WuDL

10.92 kPa

WuLL
Wu
bar
h
deff
la
lb

=
=

4.25 kPa
15.17 kPa

=
=

12 mm
125 mm

93 mm

W SLAB

250 x 400
A
5.00 m
300 x 500 C

D 300 x 500
B
250 x 400

6.00 m

short span

0.779
3.00 kPa
4.00 m

A. Solve for m
Side A
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
CB

= 1.33E+09 mm
Side B
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
4

CB

= 1.33E+09 mm
Side C
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
4

CB

= 3.13E+09 mm
Side D
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
4

CB

= 3.13E+09 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh / 12

CS

= 4.07E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 8.95E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 3.26E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 3.26E+08 mm

= 3.28

= 1.49

= 9.60

= 9.60

= 5.99

hmin =

ln ( 0.80 + fy / 1500 )
36 + 5 ( m - 0.20 )

> 125 mm

hmin = 125.00 mm
2. For m greater than 2.0
hmin =

ln ( 0.80 + fy / 1500 )
36 + 9

hmin = 100.00 mm
267853989.xls

>

90 mm

ECBCB
ECSCS

ECBCB
ECSCS

ln = 4.750 m
B. Check Minimum Thickness
1. For m greater than 0.20 but not greater than 2.0

ECSCS

A + B + C + D

ECBCB

1.284

ECBCB
ECSCS

Therefore use:

267853989.xls

hmin = 100.00 mm ok!

D. Check Slab on Shear


Va
= CaWulalb

( Coefficient Method )

Vb
Ca

= CbWulalb
= 0.5195 kN

0.779

Cb
Va
Vb
Vc
Vc

= 0.4805 kN
= 138.50 kN
= 128.11 kN
= 0.85 fc'CS(1000)(deff)
= 362.25 kN ok!

0.800
0.750

0.4400

0.779
0.800

x 0.4805
0.5100

D. Determine Design Moments


Continuous Edge
Negative Moments:
2
Mb = CbWulb
Cb
Mb

la/lb

by linear interpolation
Ca
0.750
0.5600

Cb

Ca
Vu

Mu(-) Mu(+)DL Mu(+)LL

1.00 0.290

0.027

0.032

x 0.5195

0.95 0.330

0.031

0.036

0.4900

0.90 0.380
0.85 0.430
0.80 0.490

0.035
0.040
0.045
0.051
0.058
0.065
0.073
0.081
0.089

0.040
0.045
0.051
0.056
0.063
0.070
0.077
0.085
0.092

0.033
0.031
0.028
0.025
0.022

0.035
0.032
0.029
0.026
0.023

( Coefficient Method )
by linear interpolation
Cb
0.750
0.0440

0.75
0.70
0.65
0.60
0.55
0.50
la/lb

0.560
0.620
0.690
0.760
0.810
0.860

1.00
0.95
0.90
0.85

0.710
0.670
0.620
0.570

Cb

0.80 0.510

0.071
0.067
0.062
0.057
0.051

MaLL

2
= CaLLWuLLla

0.779

x 0.0475

0.75 0.440

0.044

0.020

0.020

CaDL

= 0.0475 kN

0.800

0.0450

0.70 0.380

0.038

0.017

0.017

CaLL

= 0.0531 kN

0.65 0.310

0.031

0.014

0.014

= 0.0481 kN
= 16.45 kN-m

0.779
0.800

Positive Moments:
2
MaDL
= CaDLWuDLla

by linear interpolation
CaDL 0.750
0.0510

MaDL

7.10 kN-m

MaLL
MaTOT

=
=

3.09 kN-m
10.19 kN-m

MbDL
MbLL

2
= CbDLWuDLlb
2
= CbLLWuLLlb

CbDL

= 0.0212 kN

CbLL

= 0.0217 kN

MbDL

5.21 kN-m

MbLL
MbTOT

=
=

2.08 kN-m
7.30 kN-m

E. Design Reinforcements:
Solve fo 1 :
> 0.65
a.) if fc' > 30 Mpa ;
1

0.85 - 0.05

CaLL

CbLL

267853989.xls

0.0560

0.60 0.240

0.024

0.012

0.011

0.779
0.800

x 0.0531
0.0510

0.55 0.190
0.50 0.140

0.019
0.014

0.009
0.007

0.009
0.007

0.779

x 0.0212

0.800

0.0220

0.750

0.0200

0.779
0.800

x 0.0217
0.0230

NSCP Section 410.3.7.3


b.) if fc' < 30 Mpa ;
1 = 0.85
( fc' - 30 )
7

ok!

NSCP Section 410.4.3


max 0.75 bal

Solve for min :


NSCP Section 410.6.1

0.85 1 fc'

600

fy

600 + fy

bal 0.0377
max 0.0282

0.750

by linear interpolation
CbDL 0.750
0.0200

1 = 0.914
use:
1 = 0.85 > 0.65
Solve for max :

bal

x 0.0481
0.0510

min

fc'

4 fy
min 0.0042

use:
min 0.0051

>
<

min

1.4

fy
min 0.0051

REINFORCEMENTS
Middle Strip
Design Moments
Bar Diameter
m = 0.847 fc' / fy
R = Mu / bdeff2

Short Span
Discont.
Bot Bars
Top Bars
10.19
3.40
12
12
0.0644
0.0644

Long Span
Cont.
Top Bars
16.45
12
0.0644

Bot Bars
7.30
12
0.0644

Discont.
Top Bars
2.43
12
0.0644

1.3097

0.4366

2.1129

0.9375

0.3125

reqd = m - m2 - 2Rm/fy

0.0049

0.0016

0.0082

0.0035

0.0011

supplied

0.0051

0.0051

0.0082

0.0051

0.0051

Asreqd = bd
As main bar
spcgreqd

471.74
113.10

471.74
113.10

760.17
113.10

471.74
113.10

471.74
113.10

239.75
225.00
Bot Bars

239.75
225.00
Top Bars

148.78
125.00
Top Bars

239.75
225.00
Bot Bars

239.75
225.00
Top Bars

337.50
250.00

337.50
250.00

187.50
175.00

337.50
250.00

337.50
250.00

Provide (spcg)
Column Strip
spcgreqd = 3/2(spcgMID-STRIP)
Provide (spcg)

E. Temperature / Shrinkage Reinforcements:


As
= 0.002bh
b.Temp Reinf.
As
= 250.00 mm2
NSCP Section 407.13
bar = 12.00 mm
s < 5h = 625
Asbar = 113.10 mm2
spcg = 450.00 mm

267853989.xls

s < 450

Design of Two-Way Slab with Beams


Reference:

NSCP 2001 Volume 1


Design of Reinforced Concrete by J.C. McCormac
Design of Concrete Structures by Arthur H. Nilson

fc'CS

21 Mpa

fc'CB

=
=

21 Mpa
276 Mpa

fy
M

0.90

W DL

4.80 kPa

W LL

2.50 kPa

300 x 500

WuDL

10.92 kPa

WuLL

=
=

4.25 kPa
15.17 kPa

=
=

12 mm
125 mm

93 mm

Wu
bar
h
deff
la
lb

W SLAB

6.00 m
b

long span
6.00 m
300 x 500 C

D 300 x 500
B
300 x 500

1.000

3.00 kPa
6.00 m

6.00 m

5.70 m

A. Solve for m
Side A
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
CB

= 3.13E+09 mm4

Side B
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
CB

= 3.13E+09 mm
Side C
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
4

CB

= 3.13E+09 mm
Side D
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
4

CB

= 3.13E+09 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh / 12

CS

= 9.77E+08 mm4

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 9.77E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh / 12

CS

= 4.88E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh / 12

CS

= 9.52E+08 mm

= 3.20

= 3.20

= 6.40

= 3.28

= 4.02

hmin =

ln ( 0.80 + fy / 1500 )
36 + 5 ( m - 0.20 )

hmin = 101.79 mm
267853989.xls

> 125 mm

ECBCB
ECSCS

ECBCB
ECSCS

ln = 5.700 m
B. Check Minimum Thickness
1. For m greater than 0.20 but not greater than 2.0

ECSCS

A + B + C + D

ECBCB

1.000

ECBCB
ECSCS

2. For m greater than 2.0


hmin =

ln ( 0.80 + fy / 1500 )
36 + 9

>

90 mm

hmin = 124.64 mm
Therefore use: hmin = 124.64 mm ok!
D. Check Slab on Shear
Va
= CaWulalb

( Coefficient Method )

la/lb

by linear interpolation
Ca
1.000
0.3300

Ca
Vu

Mu(-) Mu(+)DL Mu(+)LL

Vb
Ca

= CbWulalb

1.00 0.330

0.033

0.020

0.028

= 0.3300 kN

1.000

x 0.3300

0.95 0.380

0.038

0.022

0.031

Cb

= 0.6700 kN
= 162.65 kN
= 330.23 kN
= 0.85 fc'CS(1000)(deff)

0.950

0.3800

0.90 0.430
0.85 0.490
0.80 0.550

0.043
0.049
0.055
0.061
0.068
0.074
0.080
0.085
0.089

0.025
0.029
0.032
0.036
0.040
0.044
0.048
0.052
0.056

0.035
0.040
0.044
0.049
0.054
0.059
0.065
0.070
0.076

Va
Vb
Vc
Vc

= 362.25 kN

Cb

ok!

D. Determine Design Moments


Continuous Edge
Negative Moments:
2
Ma = CaWula

1.000

0.6700

1.000
0.950

x 0.6700
0.6200

0.75
0.70
0.65
0.60
0.55
0.50
la/lb

( Coefficient Method )
by linear interpolation
Ca
1.000
0.0330

0.610
0.680
0.740
0.800
0.850
0.890

Cb

Mb
Ca

2
= CbWulb

1.000

x 0.0330

1.00 0.670

0.061

0.023

0.030

= 0.0330 kN

0.950

0.0380

0.95 0.620

0.056

0.021

0.027

Cb

= 0.0610 kN
= 16.26 kN-m
= 30.07 kN-m

0.019

0.024

0.0610
x 0.0610
0.0560

0.90
0.85
0.80
0.75
0.70
0.65

0.052

1.000
1.000
0.950

0.017
0.015
0.013
0.011
0.009
0.007

0.022
0.019
0.016
0.014
0.011
0.009

Ma
Mb

Cb

0.570
0.510
0.450
0.390
0.320
0.260

0.60 0.200

0.046
0.041
0.036
0.029
0.024
0.018

MaLL

2
= CaLLWuLLla

1.000

x 0.0360

0.55 0.150

0.014

0.005

0.007

CaDL

= 0.0360 kN

0.950

0.0320

0.50 0.110

0.010

0.004

0.005

CaLL

= 0.0490 kN

MaDL

12.77 kN-m

MaLL
MaTOT

=
=

6.77 kN-m
19.54 kN-m

MbDL
MbLL

2
= CbDLWuDLlb
2
= CbLLWuLLlb

CbDL

= 0.0130 kN

CbLL

= 0.0160 kN

MbDL

4.61 kN-m

MbLL
MbTOT

=
=

2.21 kN-m
6.82 kN-m

Positive Moments:
2
MaDL
= CaDLWuDLla

E. Design Reinforcements:
Solve fo 1 :
> 0.65
a.) if fc' > 30 Mpa ;
1

0.85 - 0.05

by linear interpolation
CaDL 1.000
0.0360

CaLL

CbLL

267853989.xls

x 0.0490
0.0440

1.000

x 0.0130

0.950

0.0150

1.000

0.0160

1.000
0.950

x 0.0160
0.0190

NSCP Section 410.3.7.3


b.) if fc' < 30 Mpa ;
1 = 0.85
( fc' - 30 )
7

ok!

NSCP Section 410.4.3


max 0.75 bal

Solve for min :


NSCP Section 410.6.1

0.85 1 fc'

600

fy

600 + fy

bal 0.0377

0.0490

1.000
0.950

by linear interpolation
CbDL 1.000
0.0130

1 = 0.914
use:
1 = 0.85 > 0.65
Solve for max :

bal

1.000

min

fc'

4 fy
min 0.0042
use:

>
<

min

1.4

fy
min 0.0051

max 0.0282

267853989.xls

min 0.0051

REINFORCEMENTS
Middle Strip
Design Moments
Bar Diameter
m = 0.847 fc' / fy
R = Mu / bdeff2

Short Span
Cont.
Top Bars
16.26
12
0.0644

Bot Bars
19.54
12
0.0644

Discont.
Top Bars
6.51
12
0.0644

Long Span
Cont.
Top Bars
Bot Bars
30.07
6.82
12
12
0.0644
0.0644

2.0895

2.5101

0.8367

3.8624

0.8764

reqd = m - m2 - 2Rm/fy

0.0081

0.0098

0.0031

0.0160

0.0033

supplied

0.0081

0.0098

0.0051

0.0160

0.0051

Asreqd = bd
As main bar
spcgreqd

751.14
113.10

915.74
113.10

471.74
113.10

1485.57
113.10

471.74
113.10

150.57
150.00
Top Bars

123.50
100.00
Bot Bars

239.75
225.00
Top Bars

76.13
75.00
Top Bars

239.75
225.00
Bot Bars

225.00
225.00

150.00
150.00

337.50
250.00

112.50
100.00

337.50
250.00

Provide (spcg)
Column Strip
spcgreqd = 3/2(spcgMID-STRIP)
Provide (spcg)

E. Temperature / Shrinkage Reinforcements:


As
= 0.002bh
b.Temp Reinf.
As
= 250.00 mm2
NSCP Section 407.13
bar = 12.00 mm
s < 5h = 625
Asbar = 113.10 mm2
spcg = 450.00 mm

267853989.xls

s < 450

Design of Two-Way Slab with Beams


Reference:

NSCP 2001 Volume 1


Design of Reinforced Concrete by J.C. McCormac
Design of Concrete Structures by Arthur H. Nilson

fc'CS

21 Mpa

fc'CB

=
=

21 Mpa
276 Mpa

fy
M

0.90

W DL

4.80 kPa

W LL

2.50 kPa

WuDL

10.92 kPa

WuLL
Wu
bar
h
deff
la
lb

=
=

4.25 kPa
15.17 kPa

=
=

12 mm
125 mm

93 mm

W SLAB

250 x 400
A

300 x 500 C

short span

D 300 x 500

B
250 x 400
5.00 m

0.779
3.00 kPa
5.00 m

4.00 m

3.00 m

A. Solve for m
Side A
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
CB

= 1.33E+09 mm
Side B
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
4

CB

= 1.33E+09 mm
Side C
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
4

CB

= 3.13E+09 mm
Side D
ECB = 4730 fc'CB
ECB = 21675.58 MPa
CB
= bh3 / 12
4

CB

= 3.13E+09 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh / 12

CS

= 4.07E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 8.14E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 7.32E+08 mm

ECS

= 4730 fc'CS

ECS

= 21675.58 MPa

CS

= bh3 / 12

CS

= 5.70E+08 mm

= 3.67

= 3.28

= 1.64

= 4.27

= 5.49

hmin =

ln ( 0.80 + fy / 1500 )
36 + 5 ( m - 0.20 )

> 125 mm

hmin = 125.00 mm
2. For m greater than 2.0
hmin =

ln ( 0.80 + fy / 1500 )
36 + 9

hmin = 100.00 mm
267853989.xls

>

90 mm

ECSCS

ECBCB
ECSCS

ECBCB
ECSCS

ln = 4.750 m
B. Check Minimum Thickness
1. For m greater than 0.20 but not greater than 2.0

ECBCB

A + B + C + D

5.00 m

1.284

ECBCB
ECSCS

Therefore use:

267853989.xls

hmin = 100.00 mm ok!

D. Check Slab on Shear


Va
= CaWulalb

( Coefficient Method )
by linear interpolation
Ca
0.750
0.8600

= CbWulalb

Vb
Ca

la/lb

= 0.8426 kN

Cb

= 0.1574 kN
Va
= 224.66 kN
Vb = 41.96 kN
Vc = 0.85 fc'CS(1000)(deff)
Vc = 362.25 kN ok!
D. Determine Design Moments
Continuous Edge
Negative Moments:
2
Ma = CaWula

Cb

Ca
Vu

Mu(-) Mu(+)DL Mu(+)LL

1.00 0.670

0.061

0.023

0.030

0.779

x 0.8426

0.95 0.710

0.065

0.024

0.032

0.800

0.8300

0.750

0.1400

0.90 0.750
0.85 0.790
0.80 0.830

0.779
0.800

x 0.1574
0.1700

0.860
0.890
0.920
0.940
0.950
0.970

0.068
0.072
0.075
0.078
0.081
0.083
0.085
0.086
0.088

0.026
0.028
0.029
0.031
0.033
0.034
0.036
0.037
0.038

0.036
0.039
0.042
0.046
0.050
0.054
0.059
0.063
0.067

0.75
0.70
0.65
0.60
0.55
0.50
la/lb

( Coefficient Method )
by linear interpolation
Ca
0.750
0.0780

Cb

Mb
Ca

2
= CbWulb

0.779

x 0.0763

1.00 0.330

0.033

0.020

0.028

= 0.0763 kN

0.800

0.0750

0.95 0.290

0.029

0.017

0.025

Cb

= 0.0157 kN
= 15.84 kN-m
=
5.39 kN-m

0.750
0.779
0.800

0.0140
x 0.0157
0.0170

0.90
0.85
0.80
0.75
0.70
0.65

0.015
0.013
0.010
0.007
0.006
0.005
0.004

0.022
0.020
0.017
0.013
0.011
0.009
0.007

0.60 0.060

0.025
0.021
0.017
0.014
0.011
0.008
0.006

MaLL

2
= CaLLWuLLla

0.779

x 0.0298

0.55 0.050

0.005

0.003

0.006

CaDL

= 0.0298 kN

0.800

0.0290

0.50 0.030

0.003

0.002

0.004

CaLL

= 0.0437 kN

MaDL

4.46 kN-m

MaLL
MaTOT

=
=

2.54 kN-m
7.00 kN-m

MbDL
MbLL

2
= CbDLWuDLlb
2
= CbLLWuLLlb

CbDL

= 0.0087 kN

CbLL

= 0.0153 kN

MbDL

2.15 kN-m

MbLL
MbTOT

=
=

1.47 kN-m
3.62 kN-m

Ma
Mb

Cb

Positive Moments:
2
MaDL
= CaDLWuDLla

E. Design Reinforcements:
Solve fo 1 :
> 0.65
a.) if fc' > 30 Mpa ;
1

0.85 - 0.05

by linear interpolation
CaDL 0.750
0.0310

CaLL

CbLL

267853989.xls

x 0.0437
0.0420

0.779

x 0.0087

0.800

0.0100

0.750

0.0130

0.779
0.800

x 0.0153
0.0170

NSCP Section 410.3.7.3


b.) if fc' < 30 Mpa ;
1 = 0.85
( fc' - 30 )
7

ok!

NSCP Section 410.4.3


max 0.75 bal

Solve for min :


NSCP Section 410.6.1

0.85 1 fc'

600

fy

600 + fy

bal 0.0377
max 0.0282

0.0460

0.779
0.800

by linear interpolation
CbDL 0.750
0.0070

1 = 0.914
use:
1 = 0.85 > 0.65
Solve for max :

bal

0.750

0.250
0.210
0.170
0.140
0.110
0.080

min

fc'

4 fy
min 0.0042

use:
min 0.0051

>
<

min

1.4

fy
min 0.0051

REINFORCEMENTS
Middle Strip
Design Moments
Bar Diameter
m = 0.847 fc' / fy
R = Mu / bdeff2

Short Span
Cont.
Top Bars
Bot Bars
15.84
7.00
12
12
0.0644
0.0644

Long Span
Cont.
Top Bars
5.39
12
0.0644

Bot Bars
3.62
12
0.0644

Discont.
Top Bars
1.21
12
0.0644

2.0347

0.8996

0.6920

0.4652

0.1551

reqd = m - m2 - 2Rm/fy

0.0079

0.0033

0.0026

0.0017

0.0006

supplied

0.0079

0.0051

0.0051

0.0051

0.0051

Asreqd = bd
As main bar
spcgreqd

730.06
113.10

471.74
113.10

471.74
113.10

471.74
113.10

471.74
113.10

154.91
150.00
Top Bars

239.75
225.00
Bot Bars

239.75
225.00
Top Bars

239.75
225.00
Bot Bars

239.75
225.00
Top Bars

225.00
225.00

337.50
250.00

337.50
250.00

337.50
250.00

337.50
250.00

Provide (spcg)
Column Strip
spcgreqd = 3/2(spcgMID-STRIP)
Provide (spcg)

E. Temperature / Shrinkage Reinforcements:


As
= 0.002bh
b.Temp Reinf.
As
= 250.00 mm2
NSCP Section 407.13
bar = 12.00 mm
s < 5h = 625
Asbar = 113.10 mm2
spcg = 450.00 mm

267853989.xls

s < 450