VACi 12 / 17.5 / 24 kV IEC Vacuum Circuit Brreakers
Table of contents
Safety ................................................................................................................................. 5
1.1
1.2
Receiving............................................................................................................................................... 30
Handling ................................................................................................................................................ 30
Storage .................................................................................................................................................. 30
Lifting of Circuit Breakers ...................................................................................................................... 31
W-VACi Circuit Breaker Weights .......................................................................................................... 31
Photographic Description ...................................................................................................................... 32
Inspection .........................................................................................................................34
4.1 Inspection .............................................................................................................................................. 34
4.2 Frequency of Inspection ........................................................................................................................ 34
4.3 Inspection Process ................................................................................................................................ 34
4.4 Vacuum Interrupter Integrity Test ......................................................................................................... 34
4.5 Insulation Inspection ............................................................................................................................. 34
4.6 Main Circuit Resistance Check ............................................................................................................. 35
Mechanism Inspection Check ......................................................................................................................... 35
4.7 Torque specifications ............................................................................................................................ 35
4.8 Troubleshooting Chart .......................................................................................................................... 37
Operation ..........................................................................................................................43
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
Renewal parts...................................................................................................................57
7.1
7.2
7.3
7.4
General .................................................................................................................................................. 57
Ordering Instructions ............................................................................................................................. 57
Standard accessories ........................................................................................................................... 57
Optional accessories ............................................................................................................................. 60
Appendix ..........................................................................................................................62
8.1
8.2
Safety
1.1
Safety precautions
WARNING
WARNING indicates a hazard with a medium
level of risk which, if not avoided, may result in
death or serious bodily injury
CAUTION
CAUTION indicates a hazard with a low level of risk
which, if not avoided, could result in minor or
moderate injury or property damage only.
1.2
Safety practices
WARNING
Product Summary
2.1
2.2
Technology Parameters
2.3
Item
Unit
Voltage (Ur)
kV
Normal Current(Ir)
630
800
1250
1600
2000
630
800
1250
1600
2000
630
800
1250
1600
2000
1250
1600
2000
12kV W-VACi
Short-Time Withstand
Current(Ik)
kA
25
25
25
25
25
26.3
26.3
26.3
26.3
26.3
31.5
31.5
31.5
31.5
31.5
40
40
40
kA
25
25
25
25
25
26.3
26.3
26.3
26.3
26.3
31.5
31.5
31.5
31.5
31.5
40
40
40
sec
Frequency(fr)
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
50/60
100/10
79/82
4
100/
104
100/
104
12
12
12
12
Hz
50/60
50/60
50/60
50/60
50/60
kA
63/
65
63/
65
63/
65
63/
65
63/
65
66/65
66/-
66/-
66/-
66/-
79/82
79/82
79/82
79/82
ms
ms
35
35
35
20
15
35
35
35
20
15
20
20
20
20
15
15
15
15
DO Resistance
45
45
45
35
30
45
45
45
35
30
35
35
35
35
30
30
30
30
Closing Time
ms
30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70 30~70
ms
40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60 40~60
Fixed Resistance
Opening Time
m/s
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
0.7~
1.3
Opening Speed1
m/s
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
1.0~
1.7
29-35
29-35
29-35
29-35
29-35
29-35
29-35
29-35
29-35
29-35
29-35
29-35
29-35
29-35
29-35
29-35
29-35
29-35
Cable-Charging Breaking
Current (C2)
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
400
400
400
400
mm
150
150
150
210
210
150
150
150
210
210
150
150
150
210
210
210
210
210
mm
205
275
275
310
310
205
275
275
310
310
275
275
275
310
310
310
310
310
Mechanical Endurance2
Cycle
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
Electrical Endurance
Cycle
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
Closing Speed
Rated
Insulation
Level
Rated Lighting
Impulse
Withstand
Voltage(Up)
Rated Power
Frequency
Withstand
Voltage(Ud)
kV
28
28
28
28
kV
75
75
75
75
Operating Sequence
O-0.3s-CO-15s-CO
Classification
E2-M2-S1
1:
2.4
Voltage (Ur)
kV
Normal Current(Ir)
630
800
1250
1600
2000
630
800
1250
1600
2000
1250
1600
2000
Short-Time Withstand
Current(Ik)
kA
25
25
25
25
25
31.5
31.5
31.5
31.5
31.5
40
40
40
kA
25
25
25
25
25
31.5
31.5
31.5
31.5
31.5
40
40
40
sec
Frequency(fr)
Hz
50/6
0
50/6
0
50/6
0
50/6
0
50/6
0
50/6
0
50/6
0
50/6
0
50/6
0
50/6
0
50/6
0
50/6
0
50/60
kA
63/
65
63/
65
63/
65
63/
65
63/
65
79/8
2
79/8
2
79/8
2
79/8
2
79/8
2
100/10
4
100/
104
100/
104
ms
ms
Fixed Resistance1
35
35
35
20
15
20
20
20
20
15
15
15
15
DO Resistance1
45
45
45
35
30
35
35
35
35
30
30
30
30
Closing Time
ms
30~7
0
30~7
0
30~7
0
30~7
0
30~7
0
30~7
0
30~7
0
30~7
0
30~7
0
30~7
0
30~7
0
30~7
0
30~7
0
Opening Time
ms
40~6
0
40~6
0
40~6
0
40~6
0
40~6
0
40~6
0
40~6
0
40~6
0
40~6
0
40~6
0
40~6
0
40~6
0
40~6
0
Closing Speed1
m/s
0.7~1
.3
0.7~1
.3
0.7~1
.3
0.7~1
.3
0.7~1.
3
0.7~1
.3
0.7~1
.3
0.7~1.
3
0.7~1
.3
0.7~1.
3
0.7~1
.3
0.7~1
.3
0.7~1.
3
Opening Speed1
m/s
1.0~1
.7
1.0~1
.7
1.0~1
.7
1.0~1
.7
1.0~1.
7
1.0~1
.7
1.0~1
.7
1.0~1.
7
1.0~1
.7
1.0~1.
7
1.0~1
.7
1.0~1
.7
1.0~1.
7
2935
2935
2935
2935
2935
2935
2935
2935
2935
2935
2935
2935
2935
Cable-Charging Breaking
Current (C2)
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
400
400
mm
150
150
150
210
210
150
150
150
210
210
210
210
210
mm
205
275
275
310
310
275
275
275
310
310
310
310
310
Mechanical Endurance
Cycle
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
Electrical Endurance
Cycle
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
10k
Rated
Insulation
Level
1:
17.5kV W-VACi
Item
Rated Power
Frequency
Withstand
Voltage(Ud)
Rated Lighting
Impulse
Withstand
Voltage(Up)
17.5
17.5
17.5
kV
38
38
38
kV
95
95
95
Operating Sequence
O-0.3s-CO-15s-CO
Classification
E2-M2-S1
2.5
Voltage (Ur)
kV
24
Normal Current(Ir)
800
1600
2000
2500
Short-Time Withstand
Current(Ik)
kA
20
25
25
25
kA
20
25
25
25
sec
24
Frequency(fr)
Hz
50/60
50/60
50/60
50/60
kA
50/52
63/65
63/65
63/65
ms
ms
Fixed Resistance
31.5
31.5
31.5
31.5
DO Resistance1
30
30
30
30
Closing Time
ms
30~70
30~70
30~70
30~70
ms
40~60
40~60
40~60
40~60
m/s
0.7~1.3
0.7~1.3
0.7~1.3
0.7~1.3
Opening Speed
m/s
1.0~1.7
1.0~1.7
1.0~1.7
1.0~1.7
D.C. Component of
Breaking Current(Idc)
30
30
30
30
Cable-Charging Breaking
Current (C2)
31.5
31.5
31.5
31.5
mm
210
275
275
275
mm
310
310
310
310
Mechanical Endurance
Cycle
10k
20k
20k
20k
Electrical Endurance
Cycle
10k
20k
20k
20k
kV
60
60
60
60
kV
125
125
125
125
Opening Time
1
Closing Speed
Rated
Insulation
Level
1:
24kV W-VACi
Item
Rated Power
Frequency
Withstand
Voltage(Ud)
Rated
Lighting
Impulse
Withstand
Voltage(Up)
Operating Sequence
O-0.3s-CO-15s-CO
Classification
E2-M2-S1
2.6
Operating Conditions
W-VACi breakers are designed for switchgear mounted in indoor areas under normal service conditions (ambient air
temperature, altitude, humidity, etc.) as laid out is IEC60694 clause 2.1.1.
Table 2-1: Operating Conditions
Ambient Temperature:
Maximum = +40C
Minimum = -5C
Altitude:
Do not exceed 1000m
For applications above 1000 m de-rating is required
Service Site:
The environment shall be free of water, flame, and/or explosive hazard.
No chemical corrosive gases, and/or intensive vibration.
2.7
Breaker Description
12kV/17.5kV/24 kV
W-VACi or W-VACiR
20/25/26.3/31.5/40/50
630/800/1250/1600/2000
150/210/275
10
2.8
Frame Description:
Example:
12 W 1
Frame 1
Voltage (kV)
12
17.5
24
Continuous
current
(A)
Interrupting
current
(kA)
Pole
Spacing
(mm)
Upper to
Lower
terminal
spacing
(mm)
Withdrawable
Breaker Frame
Withdrawable
Breaker Frame
Page Number
Fixed
Breaker
Frame
Fixed
Breaker
Frame Page
Number
630
25
150
205
12W-1
12
12F-1
21
800
25
150
275
12W-2
13
12F-2
22
1250
25
150
275
12W-2
13
12F-2
22
1600
25
210
310
12W-3
14
12F-3
23
2000
25
210
310
12W-3
14
12F-3
23
630
26.3
150
205
12W-1
12
12F-1
21
800
26.3
150
275
12W-2
13
12F-2
22
1250
26.3
150
275
12W-2
13
12F-2
22
1600
26.3
210
310
12W-3
14
12F-3
23
2000
26.3
210
310
12W-3
14
12F-3
23
630
31.5
150
275
12W-2
13
12F-2
22
800
31.5
150
275
12W-2
13
12F-2
22
1250
31.5
150
275
12W-2
13
12F-2
22
1600
31.5
210
310
12W-3
14
12F-3
23
2000
31.5
210
310
12W-3
14
12F-3
23
1250
40
210
310
12W-3
14
12F-3
23
1600
40
210
310
12W-3
14
12F-3
23
2000
40
210
310
12W-3
14
12F-3
23
630
800
1250
1600
2000
25
25
25
25
25
150
150
150
210
210
205
275
275
310
310
17.5W-1
17.5W-2
17.5W-2
17.5W-3
17.5W-3
15
16
16
17
17
17.5F-1
17.5F-2
17.5F-2
17.5F-3
17.5F-3
24
25
25
26
26
630
800
1250
1600
2000
31.5
31.5
31.5
31.5
31.5
150
150
150
210
210
275
275
275
310
310
17.5W-2
17.5W-2
17.5W-2
17.5W-3
17.5W-3
16
16
16
17
17
17.5F-2
17.5F-2
17.5F-2
17.5F-3
17.5F-3
25
25
25
26
26
1250
1600
2000
40
40
40
210
210
210
310
310
310
17.5W-3
17.5W-3
17.5W-3
17
17
17
17.5F-3
17.5F-3
17.5F-3
26
26
26
800
1600
2000
2500
20
25
25
25
210
275
275
275
310
310
310
310
24W-1
24W-2
24W-2
24W-3
18
19
19
20
24F-1
24F-2
24F-2
24F-3
27
28
28
29
11
Applicable Ratings
Voltage
12
Breaking
Current
Normal
Current
12kV
25kA
630A
12kV
26.3kA
630A
Applicable Ratings
Voltage
12kV
Breaking
Current
Normal Current
25kA
630A
800A
NA
26.3kA
630A
800A
NA
31.5kA
630A
800A
1250A
13
Applicable Ratings
Voltage
12kV
Breaking
Current
Normal Current
25kA
NA
26.3kA
NA
31.5kA
NA
40kA
1
2
14
1250A
1600A
2000A
1600A
2000A
1600A1
1
1600A
2
2
2000A2
2
2000A
Applicable Ratings
Voltage
Breaking
Current
Normal
Current
17.5kV
25kA
630A
15
Applicable Ratings
Voltage
17.5kV
16
Breaking
Current
Normal Current
25kA
630A
800A
NA
31.5kA
630A
800A
1250A
Applicable Ratings
Voltage
17.5kV
Breaking
Current
Normal Current
25kA
NA
31.5kA
NA
40kA
1250A
1600A
2000A
1600A
2000A2
1600A
2000A2
17
Applicable Ratings
18
Voltage
Breaking
Current
Normal
Current
24kV
20kA
800A
Applicable Ratings
Voltage
Breaking
Current
Normal Current
24kV
25kA
1600A1
2000A2
19
Applicable Ratings
20
Voltage
Breaking
Current
Normal
Current
24kV
25kA
2500A
Applicable Ratings
Voltage
12kV
Breaking
Current
Normal
Current
25kA
630A
26.3kA
630A
21
Applicable Ratings
22
Voltage
Breaking
Current
25kA
630A
800A
NA
12kV
26.3kA
630A
800A
NA
31.5kA
630A
800A
1250A
Normal Current
Applicable Ratings
Voltage
12kV
Breaking
Current
Normal Current
25kA
NA
26.3kA
NA
31.5kA
NA
40kA
1250A
2000A
1600A
2000A
1600A
2000A2
2000A
1600A
1600A
2
2
23
Applicable Ratings
24
Voltage
Breaking
Current
Normal
Current
17.5kV
25kA
630A
Applicable Ratings
Voltage
17.5kV
Breaking
Current
Normal Current
25kA
630A
800A
NA
31.5kA
630A
800A
1250A
25
Applicable Ratings
Voltage
17.5kV
Breaking
Current
Normal Current
25kA
NA
31.5kA
40kA
26
NA
1250A
2000A
2000A2
2000A
1600A
1600A
1
1600A
Applicable Ratings
Voltage
Breaking
Current
Normal
Current
24kV
20kA
800A
27
Applicable Ratings
28
Voltage
Breaking
Current
Normal Current
24kV
25kA
1600A1
2000A2
Applicable Ratings
Voltage
Breaking
Current
Normal
Current
24kV
25kA
2500A
29
3.1
Storage
Receiving
3.2
3.3
Handling
WARNING
Do not use a lifting device as a platform for
performing inspection or repair on the circuit
breaker, nor for operating the contacts or
charging the springs. The breaker may fall,
causing severe personal injury. Always use a
suitable workbench capable of supporting the
breaker.
The circuit breaker shipping containers are designed to
be handled either by use of a rope sling and overhead
lifting device or by a fork truck. If containers must be
moved, it is preferable to use one of the above
methods, roller conveyors, or individual pipe rollers.
After inspecting for potential shipping damage, the
breaker should be returned to its original shipping
container until it is ready to be installed.
When a circuit breaker is ready for installation, a
removable lifting bar in conjunction with an overhead
lifter or portable floor lifter can be used to move the
breaker. If the circuit breaker is to be lifted, the lifting
bar must be positioned over the circuit breaker and the
bar must be inserted into the circuit breaker side
openings with the lifting hole toward the interrupters.
Once the lifting bar is securely seated in the lifting
holes, the circuit breaker can be carefully lifted and
moved.
30
3.4
3.5
Withdrawable
Fixed
800A
1250A
1600A
2000A
25kA
83
90
91
129
129
26.3kA
83
90
91
129
129
31.5kA
92
93
94
129
129
40kA
N/A
N/A
131
131
131
25kA
110
122
122
172
172
26.3kA
110
122
122
172
172
31.5kA
123
123
124
173
173
40kA
N/A
N/A
173
173
173
1600A
2000A
2500A
20kA
104
N/A
N/A
N/A
25kA
156
157
158
159
20kA
142
N/A
N/A
N/A
25kA
232
233
234
235
Fixed
*3kg.
Withdrawable
630A
800A
1250A
1600A
2000A
25kA
84
91
92
130
130
31.5kA
93
93
93
131
131
40kA
N/A
N/A
132
132
132
25kA
111
123
124
173
173
31.5kA
124
124
125
174
174
40kA
N/A
N/A
174
174
174
Withdrawable
Fixed
*3kg.
*3kg.
31
3.6
Photographic Description
2
9
3
4
10
5
11
6
7
12
7
1
10
4
11
5
6
32
7. Charging Motor
8. Integral Charging Handle
9. Manual Close Button
10. Closed / Open Indicator
11. Manual Open Button
W-VACi
W
with210 mm Pole Spacing
Breaker
B
W-V
VACi with275 mm
m Pole Spaccing
Bre
eaker
Finge
er Cluster
Heat Sinkk
Encapsulated Pole
Unit
Racking in
Assemblyy
Wheel
Rack
king in Assembly
Inspection
4.1
Inspection
WARNING
WARNING
Do not work on a breaker in the "service"
position.
Do not work on a breaker with secondary
disconnects engaged.
Do not work on a breaker with springs
charged or contacts closed.
4.2
Frequency of Inspection
4.3
Inspection Process
4.4
WARNING
After the high potential test is conducted, an
electrical charge may be retained by the vacuum
interrupters. Failure to discharge this residual
electrostatic charge could result in an electrical
shock. Follow safety procedures for this type of
test.
4.5
Insulation Inspection
Breaker
Testing Voltage
12kV
28kV
17.5kV
38kV
24kV
50kV
34
4.6
The resistance
e of the main circuit
c
can be measured
m
as
follows: Ensurre the breaker is in closed sta
atus, deliver
100A current to
t the main circ
cuit, and measure the
resistance with the help of a test machine. The results
cannot exceed
d the value in the
t Table 4-2. When
W
conducting thiis test with a withdrawable
w
bre
eaker, DO
NOT attach th
he test clamp to
o the springs. Use
U Fig. 4-1
as reference.
Table 4-2: Resistance
e chart of Main Circuit
C
Breaking Cu
urrent
Fix
xed
D.O.
Resistance ()
25kA
35
5
4
45
26.3kA
35
5
4
45
31.5kA
20
0
3
35
40kA
15
5
3
30
Whe
en testing circuiit resistance: cllamp directly onto
the finger cluster be
etween the sprrings as shown.
Fig. 4-1: Finger Cluster Warning
W
4.7
To
orque spec
cifications
T
Table
4-3: Torqu
ue Specification
ns
Nominal size
e and
pitch
Newton Mete
ers (Nm)
M5 x 0.80
M6 x 1.00
10
M7 x 1.00
18
M8 x 1.25
25
M10 x 1.50
50
M12 x 1.75
88
M14 x 2.00
141
Section
Inspection Item
Criteria
Inspection Method
Corrective Action
Insulation
Drive insulator,
barriers, and standoff insulators
No dirt and no
cracking
Visual inspection
Main circuit to
ground
Withstand
AC High Potential
Test
Withstand
AC High Potential
Test
Control circuit to
ground
Withstand
AC High Potential
Test
Vacuum Interrupters
Adequate vacuum
Proceed with
integrity check
Primary disconnects
No burning or
damage or spring
discoloration
Visual inspection
Replace if burned,
damaged, eroded or
discolored
Wiring
Securely tied in
proper place
Visual inspection
Repair or tie as
necessary
Terminals
Tight
Visual inspection
Tighten or replace if
necessary
Motor
Smooth, normal
operation
Functional Test
Replace brushes or
motor
Tightness of
hardware
No loose or missing
parts
Tighten or replace
parts
Dust or foreign
object
No dust or foreign
object
Visual check
Clean as necessary
Lubrication
Smooth operation
and no excessive
wear
Deformation or
Excessive Wear
No excessive
deformation or wear
Visual and
operational
Manual Operation
Smooth operation
Manual charging,
closing, and tripping
Correct per
troubleshooting chart
6.9
Insulation Integrity
Power Elements
Operating
Mechanism
36
4.8
Troubleshooting Chart
Symptom
Inspection area
Probable cause
Fail to Close
No control power
fuse blown or switch off
Secondary disconnect is not connected
Closing-spring
not charged
Motor Circuit
Closing-spring
charged but breaker
does not close
Mechanical Interlock
37
Symptom
Inspection area
Probable cause
Undesirable Close
Shunt closing release circuit is energized
Control Circuit
Auxiliary switch does not switch properly
Undesirable Close
Fail to Trip
Mechanism
Vacuum Interrupter
Undesirable Trip
Shunt trip circuit is energized
Control Circuit
Auxiliary switch does not switch properly
Trip latch is damaged
Undesirable Trip
Mechanism
38
Installation
n checks and
unctionall Tests
Fu
W
WARNING
Before plac
cing the circuit breaker in service,
s
follow the installation prrocedure given below
carefully. Not
N following the
t procedure
e can lead
to a failure
e to uncover damage that may
m have
resulted in faulty breake
er operation.
Fig. 5-1: Pu
ull the round handle down
CAUTION
C
Any wiring instructions
i
pre
esented in this document
must be folllowed preciselyy. Failure to do
o so could
cause perm
manent equipme
ent damage.
5.1
Iniitial Inspec
ction and
Op
peration
Before attemp
pting to put the circuit breakerr in service, it
should be exa
amined carefully and operated
d manually
and electrically three times. It is highly reco
ommended
that Section 3 (Receiving, ha
andling & stora
age) and
erations) are
Section 5 (circcuit breaker description & ope
closely review
wed before procceeding with installation
into switchgea
ar.
5.2
Ma
anual Operration Che
eck
Fig. 5-3: Tu
urn the handle clockwise
c
Fig. 5-4:
5
Close manu
ually
Fig. 5
5-5: Open manu
ually
5.3
ameplate
Na
CAUTION
N
Exam
mine the inside
e of the cell beffore inserting or
mounting the breakker for excessivve dirt or anyth
hing
that might interfere with the breakker travel or
insta
allation.
WARNING
Extreme caution must
m
be exerc
cised to ensure
uits are not energized while
that primary circu
cks are perforrmed in the bre
eaker
chec
com
mpartment. Failure to do so may
m result in
pers
sonal injury orr death.
5.4
Va
acuum Inte
errupter Inttegrity
Ch
heck
5.5
Ins
sulation
The primary in
nsulation for the
e vacuum interrrupters
need to be checked. Refer to
o the procedure
e in Table
4-1. This can be done by clo
osing the circuitt breaker
and performin
ng a power freq
quency voltage test.
5.6
Ma
ain Circuit Resistanc
ce Check
Check the ma
ain circuit resisttance. The resistance
should not excceed the permiissible values. Record the
obtained value
es for future reference. Refer to Table 4-2
for value limits
s and procedurre.
pring of
Note: Do not apply test current to the sp
g. 4-1 for
main contactt finger cluster. Refer to Fig
finger clusterr location. Dam
mage can occ
cur if this
process is no
ot followed co
orrectly.
5.7
Ele
ectrical Op
perations Check
C
5.8
Ra
acking han
ndle
Fig.
F 5-8: Inserted
d racking Handlle
5.9
Circuit Break
ker Interac
ction
gear
with Switchg
5.10
5.12
5.11
Electromagnetic interlock
5.13
3
4
Fig. 5-9: Pull the round handle down
7
Fig. 5-10: Secondary Disconnect Interlock
42
Operation
HEAT SINK
6.1
VACUUM
INTERRUPTER
(Internal)
BOTTOM
CONDUCTOR
6.2
TOP
CONDUCTOR
PUSH ROD
ASSEMBLY
Fig. 6-1: Encapsulated Pole Unit (EPU) Structure
Electrical Circuit
6.3
Operating Mechanism
1
WARNING
Keep hands and fingers away from the breaker's
internal parts while the breaker contacts are
closed or the closing springs are charged. The
breaker contacts may open or the closing
springs may discharge causing a serious injury.
Discharge the springs and open the breaker
before performing any breaker inspection or
repair.
The operating mechanism uses stored energy from the
closing spring (Fig. 6-2). The closing unit has one
shunt closing release and the opening unit is
composed of one or more shunt opening release
coil(s). Both have auxiliary switches and indicating
devices which are all installed in the circuit breaker
frame. Closing and opening buttons, the manual
charging handle, spring charging state indicator, and
closed/open indicators are all front accessible.
2
3
5
6
7
8
9
6. Close Button
7. Charging Handle
8. Optional Shunt Opening Release Location
9. Open Button
43
Closing Spring
Gearrs
2
3
4
Closing Spring
Signaling
Contacts
6.4
Fig
g. 6-4: Universall Mechanism As
ssembly (UMA) Left
Side View
Ch
harging
The energy re
equired for a cirrcuit breaker closing is
provided by ch
harging a closing spring using
g a charging
motor or manu
ually charging with
w the charging handle.
When electrically charging, the
t output shafft of the
motor actuates a gear drive system. When
n manually
g
driving syystem is actuate
ed through a
charging, the gear
pinion gear that is attached to
t the charging
g handle.
d, the indicator will display CH
HARGED
Once charged
and the motorr cutting switch will break the power
supply of the charging
c
motorr. The circuit breaker
b
is
now ready for closing.
6.5
Closing
The closing op
peration is acco
omplished by either
e
manually presssing the CLOS
SE button or by
b remote
operation to actuate the shunt opening rele
ease coil.
Once closed, the indicator will
w read CLOSED and the
p
supply to the motor is returned. At
circuit for the power
the same time
e the counter is
s actuated to pe
erform the
counting functtion and the driiving linkage acctuates the
main auxiliaryy switch to transsfer states of th
he other
switches and sensors
s
betwe
een on and off. The 4 states
of the mechan
nism can be se
een in Figures 6-6
6 through
Figure6-9 on the
t following pa
age.
Fig. 6-5: M
Manual Charging
g Process
11
2
7
4
5
6
8
9
3
4
5
6
11
2
7
8
9
10
10
Fig. 6-6: Breaker Open and Closing Spring
Discharged
2
11
4
3
5
6
8
7
9
2
11
4
7
10
Fig. 6-8: Breaker Open and Closing Spring Charged
1-Closing Spring
2-Closing Spring Lever
3-Spring Release D Shaft
4-Close Roller
5-Cam
5
6
8
9
10
Fig. 6-9: Breaker Closed and Closing Spring Charged
6-Cam Shaft
7-Main Roller
8-Trip bar D Shaft
9-Trip Latch
10-Drive Shaft
11-Spring Release Latch
45
6.6
Opening
6.7
Control Schemes
6.8
Value
Rated
Voltage
Rated
Voltage
Voltage
Range
Time for
Charging (S)
Ua (DC)
24-48-60-110-125-220-250 V
Ua (AC)
110-120-220-230 V
85%-110% rated voltage
15
Item
Rated
Voltage
Rated
Voltage
Rated
CurrentA
Voltage
Range*
Value
Ua (DC)
24-48-60-110-125-220-250 V
Ua (AC)
110-120-220-230 V
10
Item
Rated
Voltage
Rated
Voltage
Operating
Limits
Value
Ua (DC)
24-48-60-110-125-220-250 V
Ua (AC)
110-120-220-230 V
Item
Rated
Voltage
Rated
Voltage
Operating
Limits
Continuous
Power(Pc)
Value
Ua (DC)
24-48-60-110-125-220-250 V
Ua (AC)
110-120-220-230 V
85-110% Ua
DC=5 W
AC=5 UA
1
Insulation voltage for all electronic parts is 2000 V 50/60 Hz
(for 1 min.)
46
47
48
49
50
51
52
53
54
55
56
Renewal parts
7.1
General
7.2
Ordering Instructions
7.3
Standard accessories
Table 7-1 Standard Accessories
65A7002G01
48 VDC / 4.4A
65A7002G02
60 VDC / 4.3A
65A7002G13
65A7002G04
65A7002G06
65A7002G10
65A7002G12
Attributes
Ua (DC)
57
24-48-60-110-125-220-250 V
Ua (AC)
110-120-220-230 V
Operating Limits
70110% Ua (DC)
85110% Ua (AC)
Insulating voltage
65A7004G01
48 VDC / 4.4A
65A7004G02
60 VDC / 4.3A
65A7004G13
65A7004G04
65A7004G06
65A7004G10
65A7004G12
Attributes
Ua (DC)
24-48-60-110-125-220-250 V
Ua (AC)
110-120-220-230 V
Operating Limits
70110% Ua (DC)
85110% Ua (AC)
Insulating voltage
65A7013G01
48 VDC / 3.6A
65A7013G02
60 VDC / 2.8A
65A7013G13
65A7013G04
65A7013G06
65A7013G10
65A7013G12
Attributes
90 Watt 0.8A
Ua (DC)
24-48-60-110-125-220-250 V
Ua (AC)
110-120-220-230 V
Operating Limits
85110% Ua
Insulating voltage
Breaker Au
uxiliary Contac
cts (S1 & S2)
Standard circuit breakers contain a 10A / 10B auxiliary switch. 6A / 6B
B contacts are used by the circuit
breaker, the
erefore 4A / 4B
B contacts are available
a
for the
e end user.
24 VDC
V
/ 10.0A
48 VDC
V
/ 6.0A
60 VDC
V
/ 5.0A
110-12
25 VDC / 2.9A
65A7009G02
220-25
50 VDC / 1.7A
110-120 VAC / 14.5A
220-23
30 VAC / 9.5A
Attributes
A
Insula
ating voltage
Closing Sp
pring Signaling
g Contact (LS
S1)
This device is used to sign
nal whether the
e operating mechanisms clossing spring is charged or disch
harged.
e signaling of th
he state of the closing spring..
It uses a miicro-switch thatt allows remote
24 VDC
V
/ 4.0A
48 VDC
V
/ 2.5A
60 VDC
V
/ 2.0A
110-12
25 VDC / 0.9A
65A7014G01
220-25
50 VDC / 0.4A
110-12
20 VAC / 9.5A
220-23
30 VAC / 5.0A
Attributes
A
Insula
ating voltage
Position Co
ontacts (S8 & S9)
Fitted in the
e levering-in asssembly, these contacts are u
used to identify if the circuit brreaker is in the
service, test, or disconneccted position.
24 VDC
V
/ 10.0A
48 VDC
V
/ 7.0A
60 VDC
V
/ 6.0A
110-12
25 VDC / 3.7A
65A7012G01
220-25
50 VDC / 0.9A
110-12
20 VAC / 5.0A
220-23
30 VAC / 2.5A
A
Attributes
Insulating voltage
Racking Ha
andle
This device is used to man
nually rack the circuit breakerr into the switch
hgear. One unit of this device
e can
be used for all of the circu
uit breakers on a particular site
e.
Racking Handle
65A7023G01
7.4
Optional accessories
Table 7-2 Optional Accessories
65A7003G01
48 VDC / 4.4A
65A7003G02
60 VDC / 4.3A
65A7003G13
65A7003G04
65A7003G06
65A7003G10
65A7003G12
Attributes
Ua (DC)
24-48-60-110-125-220-250 V
Ua (AC)
110-120-220-230 V
Operating Limits
70110% Ua (DC)
85110% Ua (AC)
Insulating voltage
65A7019G01
48 VDC
65A7019G02
60 VDC
65A7019G13
110-125 VDC
65A7019G04
220-250 VDC
65A7019G06
110-120 VAC
65A7019G10
220-230 VAC
65A7019G12
Attributes
Ua (DC)
24-48-60-110-125-220-250 V
Ua (AC)
110-120-220-230 V
Operating Limits
85110% Ua
DC= 5 W
AC= 5 VA
Insulating voltage
65A7006G01
48 VDC
65A7006G02
60 VDC
65A7006G13
110-125 VDC
65A7006G04
220-250 VDC
65A7006G06
110-120 VAC
65A7006G10
220-230 VAC
65A7006G12
Attributes
Ua (DC)
24-48-60-110-125-220-250 V
Ua (AC)
110-120-220-230 V
Operating Limits
Insulating voltage
61
Appendix
Use the following charts to verify that the circuit breaker is in the correct operational status and that the received circuit
breaker has the exact same equipment as ordered.
8.1
Breaker Type:
List
Explanation
Result
Reference
Section
3.2
Operate manually-charged/close/open
4.3
4.5
4.6
4.2
Operate electrical-charge/close/open
4.7
3.2
5.2.2
Signature: ____________________
Date_________________________
8.2
Customer Name:
Customer PO :
Date of Delivery
Eaton Order:
Quantity:
YYYY_______ MM______ DD_____
Type
W-VACiR Fixed
W-VACi Withdrawable
12
17.5
24
630
800
1250
1600
2000
20
25
26.3
31.5
40
150
210
275
Short Circuit
Breaking Current
(kA)
Pole To Pole (mm)*
Distance
2500
Shunt Opening
Release (Ua)
24VD
C
48VD
C
60VD
C
110V
DC
125V
DC
220V
DC
250V
DC
110V
AC
120V
AC
220V
AC
230V
AC
Shunt Opening
Release #2 (Ua)
24VD
C
48VD
C
60VD
C
110V
DC
125V
DC
220V
DC
250V
DC
110V
AC
120V
AC
220V
AC
230V
AC
Shunt Closing
Release (Ua)
24VD
C
48VD
C
60VD
C
110V
DC
125V
DC
220V
DC
250V
DC
110V
AC
120V
AC
220V
AC
230V
AC
Charging Motor(Ua)
24VD
C
48VD
C
60VD
C
110V
DC
125V
DC
220V
DC
250V
DC
110V
AC
120V
AC
220V
AC
230V
AC
Under-Voltage
Release
24VD
C
48VD
C
60VD
C
110V
DC
125V
DC
220V
DC
250V
DC
110V
AC
120V
AC
220V
AC
230V
AC
Mechanism
Electromagnet
Interlock
24VD
C
48VD
C
60VD
C
110V
DC
125V
DC
220V
DC
250V
DC
110V
AC
120V
AC
220V
AC
230V
AC
Additional Equipment
Racking Handle
63
PowerCha
ain solutions he
elp enterprises
achieve su
ustainable and competitive
advantage
es through proa
active
management of the powe
er system as a
strategic, integrated
i
asse
et throughout
its life cyclle, resulting in enhanced
safety, gre
eater reliability and energy
efficiency. For more inforrmation, visit
al.
www.eaton.com/electrica
Eu
urope, Middle East an
nd Africa
Ea
aton Electric B.V.
P.O
O. Box 23
7550 AA Hengelo
The Netherlands
el.: +31 74 246 4012
Te
Fa
ax: +31 74 246 4601
Se
ecretariaatCSsystems@
@eaton.com
ww
ww.eatonelectrical.com
m
Asiia Pacific
Eatton Electrical Sector Asia
A
Pacific
Hea
adquarters
No..3 Lane 280 Linhong Road
R
Cha
angning District
Sha
anghai 200335, P.R.C
China
Tel.: +86 21 5200 0099
Faxx: +86 21 5200 0200
ww
ww.eatonelectrical.com
m.cn
So
outh America
Ea
aton Ltda.
Av
v. Pierre Simon de Lap
place, 751
Co
ond. Techno Park Via
An
nhanguera,
Km
m 104,5
Ca
ampinas - SP - 13069--320 - Brasil
Te
el.: +55 19 2117 0000
eatonelectricalbrasil@ea
aton.com
ww.eaton.com.br
ww
Norrth America
Eatton Corporation
Ele
ectrical Sector
00 Cherrington Parkwa
ay
100
Moon Township, PA 1510
08
Uniited States
877
7-ETN-CARE (877-386
6-2273)
ww
ww.eaton.com