Professional Documents
Culture Documents
easyelectricalengineering.blogspot.com /2012/01/classification-of-compensating-devices.html
CLASSIFICATION OF COMPENSATING DEVICES
The devices used for this purpose are classified as:
CLASSIFICATION 1
A. STATIC COMPENSATOR, using slow switching devices eg. Mechanically switched capacitor(using
CB), Switched Reactors
Static Compensation is ideal for second and minute responses. (capacitors, reactors, tapchanges).
B. DYNAMIC COMPENSATOR using fast acting switching devices having response less than 10 sec.
eg. FACTS Controllers
Dynamic Compensation is ideal for instantaneous responses. (condensers, generators)
CLASSIFICATION 2
A. passive compensation
Shunt capacitors and reactors, and series capacitors provide passive compensation.
They are either permanently connected to the transmission and distribution system, or switched.
They contribute to voltage control by modifying the network characteristics.
B. ACTIVE COMPENSATION
Synchronous condensers and SVCs provide active compensation; the reactive power
absorbed/supplied by them is automatically adjusted so as to maintain voltages of the buses to which
they are connected.
CLASSIFICATION 3
A. Sources or sinks of reactive power, such as shunt capacitors, shunt reactors, synchronous
condensers, and static Var compensators (SVCs).
B. Line reactance compensators, such as series capacitors.
C. Regulating transformers, such as tap-changing transformers and boosters.
CLASSIFICATION 4
A. TCR( Thyristor controlled Reactor) Based(variable impedance type FACTS controllers) include:
(i) Static Var Compensator (SVC), (shunt connected)
(ii) Thyrister Controlled Series Capacitor or compensator (TCSC), (series connected)
(iii) Thyristor Controlled Phase Shifting Transformer (TCPST) of Static PST (combined shunt and
series)
B. VSC ( Voltage Source Converter)based FACTS controllers are:
Coordinated control of the tap changers of all the transformers interconnecting the subsystems is
required if the general level of voltage is to be changed.
During high system load conditions, the network voltages are kept at the highest practical level to
minimize reactive power requirements and increase the effectiveness of shunt capacitors and line
charging.
During light load conditions, it is usually required to lower the network voltages to reduce line charging
and avoid under excited operation of generators.
Transformers with off-load tap-changing facilities can also help maintain satisfactory voltage profiles.
While transformers with OLTC can be used to take care of daily, hourly, and minute-by-minute
variations in system conditions, settings of off-load tap-changing transformers have to be carefully
chosen depending on long term variations due to system expansion, load growth, or seasonal
changes.
Synchronous Condensers
A synchronous condenser is a synchronous machine running without a prime mover or a mechanical
load. By controlling the field excitation, it can be made to either generate or absorb reactive power.
With a voltage regulator, it can automatically adjust the reactive power output to maintain constant
terminal voltage.
Synchronous compensators contribute to system short-circuit capacity. Their reactive power
production is not affected by the system voltage.
During power swings (electromechanical oscillations) there is an exchange of kinetic
PASSIVE REACTIVE POWER COMPENSATION
(Refer : Fundamental theory of reactive power compensation)
Fixed or mechanically switched capacitors
Shunt capacitors were first employed for power factor correction in the year 1914. The leading current
drawn by the shunt capacitors compensates the lagging current drawn by the load. The selection of
shunt capacitors depends on many factors, the most important of which is the amount of lagging
reactive power taken by the load. In the case of widely fluctuating loads, the reactive power also varies
over a wide range. Thus, a fixed capacitor bank may often lead to either over-compensation or undercompensation. Variable VAR compensation is achieved using switched capacitors. Depending on the
total VAR requirement, capacitor banks are switched into or switched out of the system. The
smoothness of control is solely dependent on the number of capacitors switching units used. The
switching is usually accomplished using relays and circuit breakers. However, these methods based on
mechanical switches and relays have the disadvantage of being sluggish and unreliable. Also they
generate high inrush currents, and require frequent maintenance.
Series Capacitors (SC)
Series compensation with capacitors is the most common strategy. Series Capacitor are installed in
series with a transmission line as shown in Fig.3, which means that all the equipment must be installed
on a platform that is fully insulated for the system voltage (both the terminals are at the line voltage).
On this platform, the main capacitor is located together with overvoltage protection circuits. The
overvoltage protection is a key design factor as the capacitor bank has to withstand the throughput
fault current, even at a severe nearby fault. The primary overvoltage protection typically involves nonlinear metal-oxide varistors, a spark gap and a fast bypass switch. Secondary protection is achieved
with ground mounted electronics acting on signals from optical current transducers in the high voltage
circuit.
A series capacitor is not just a capacitor in series with the line. For proper functioning, series
compensation requires control, protection and supervision facilities to enable it to perform as an
integrated part of a power system. Also, since the series capacitor is working at the same voltage level
as the rest of the system, it needs to be fully insulated to ground. The main circuit diagram of a state of
the art series capacitor is shown in Fig. 4. The main protective device is a varistor, usually of ZnO type,
limiting the voltage across the capacitor to safe values in conjunction with system faults giving rise to
large short circuit currents flowing through the line. A spark gap is utilized in many cases, to enable bypass of the series capacitor in situations where the varistor is not sufficient to absorb the excess
current during a fault sequence. There are various bypass solutions available today like spark gap,
high power plasma switch, power electronic device, etc.
Finally, a circuit breaker is incorporated in the scheme to enable bypassing of the series capacitor for
more extended periods of time as need may be. It is also needed for extinguishing the spark gap, or, in
the absence of a spark gap, for by-passing the varistor in conjunction with faults close to the series
capacitor (so-called internal faults).
Points..
Series capacitors are connected in series with the line conductors to compensate for the inductive
reactance of the line.
The reactive power produced by a series capacitor increases with increasing power transfer; a series
capacitor is self-regulating in this regard.
Series capacitors are self- regulating.
The reactive power supplied by series capacitors is proportional to square of the line current and is
independent of the bus voltages.
This has a favourable effect on voltage stability.
Application to EHV
Transmission System
They have been primarily
used to improve system
stability and to obtain the
desired load division among
parallel lines.
High compensation levels
also increase the complexity
of protective relaying and the
probability of subsynchronous resonance.
A practical upper limit to the degree of series compensation is about 80%.
Following are some of the key considerations in the application of series capacitor banks:
Voltage rise due to reactive current: Voltage rise of on one side of the capacitor may be excessive
when the line reactive-current flow is high, as might occur during heavy power transfers.
Bypassing and reinsertion: provision is made for bypassing the capacitor during faults and reinsertion
after fault clearing. Speed of reinsertion may be an important factor in maintaining transient stability.
Present trend is to use nonlinear resistors of zinc oxide which have the advantage that reinsertion is
essentially instantaneous.
Location: Factors influencing choice of location include cost, accessibility, fault level, protective
relaying considerations, voltage profile and effectiveness in improving power transfer capability.
The following are the usual locations considered:
Location along the line
Midpoint of the line
Line terminals
or point of the line
Benefits
Less SC Current
Better Voltage Profile
Simple Protection is needed
One or both ends of a line section on line sides in switching station.
More protection is needed
More KVar is need for same compensation compared to other locations
Location Between busbar in switching stations
POWER FLOW
Reactive current is injected
into the line to maintain
voltage magnitude.
Transmittable active power is
increased but more reactive
power is to be provided.
(Applicable for Facts also)
Application to transmission
system
Shunt capacitors are used to
compensate for the XI2 losses
in transmission system and to
ensure satisfactory voltage
levels during heavy loading
conditions.
Switching of capacitor banks
provides a convenient means of controlling transmission system
voltages.
The principal advantages of shunt capacitors are their low cost
and their flexibility of installation and operation.
The principal disadvantage of shunt capacitors is that their
reactive power output is proportional to the square of the voltage.
The reactive power output is reduced at low
voltages when it is likely to be needed most.
The following are the usual locations
considered:
Midpoint of the line
Line terminals
or point of the line
(a) Tertiary connected capacitor (b) HV capacitor
bank
REACTORS
Reactors, like capacitors, are basic to and an integral part of both distribution and transmission power
systems. Depending on their function, reactors are connected in shunt or in series with the network;
singularly (current limiting reactors, shunt reactors) or in conjunction with other basic components such
as power capacitors (shunt capacitor switching reactors, capacitor discharge reactors filter reactors).
Reactors are utilized to provide inductive reactance in power circuits for a wide variety of purposes.
These include fault current limiting, inrush current limiting for capacitors and motors, harmonic filtering,
VAR compensation, reduction of ripple currents. Reactors may be installed at any industrial,
distribution, or transmission voltage level. Shunt reactor compensation is typically required under
conditions that are the opposite of this requiring shunt capacitor compensation.
POINTS.
Shunt reactors are used to compensate for the effects of line capacitance, particularly to limit voltage
rise on open circuit or light load. They are usually required for EHV overhead lines longer than 200Km.
A shorter overhead line may also require shunt reactors if the line is supplied from a weak system (low
short-circuit capacity).
A shunt reactor of sufficient size must be permanently connected to the line to limit fundamentalfrequency temporary over voltages to about 1.5 pu for a duration of less than 1 second.
Additional shunt reactors required to maintain normal voltage under light-load conditions may be
connected to the EHV bus. During heavy loading conditions some of the reactors may have to be
disconnected.