LOW VOLTAGE CURRENT TRANSFORMERS

type: IMW, IMP, IMS, ISW, INSOA, IMR

Catalogue 1YMA699050-en

APPLICATION

The current transformers types IMW, IMP, IMS, ISW, INSOA are
intended for supplying measuring instruments and protective circuits
of electrical power devices with maximum operating voltage 0,72 kV
and frequency 50 Hz. These current transformers are manufactured
for secondary currents 1 A or 5 A.
The current transformers types IMR 0, IMR 1, IMR 2 are intended for
supplying measuring instruments and protective circuits of electrical
power devices with maximum operating voltage 0,72 kV and
frequency 50 Hz, particularly for fuse disconnectors of series SLM
and SRE Slim Line , size 00, 1, 2 and 3.

OPERATING CONDITIONS

The current transformers are designed for operation in indoor


equipment, in temperate (N3), tropical (T3) and marine (MU) climate
conditions. Rated longduration thermal current and limits of
deviations of these transformers correspond to extended current
range for 120%Ipn within the bounds of the ambient temperatures
from 268 K (-5C) to 333 K (+60C). Additionally the current
transformers types INSOA, IMW, IMPa, IMPb, IMSa, IMSb, IMSc can
operate within the bounds of the ambient temperatures from 248 K
(-25C) to 333 K (+60C).

The windings of the current transformers types INSOA, IMW, IMPa,


IMPb, IMSa, IMSb are closed in the housings made of slow-burning
material.
The current transformers types IMSc, IMSd and ISW as well as the
transformers of series IMR have the housings made of self extinguishing polycarbonate.
The current transformers are made for different types of primary
circuits, for busbars with cross-sectional dimensions from 205 mm
up to set of two busbars 120 10 mm.The range of primary currents
from 1 A up to 5000 A.
The secondary terminals of the current transformers types IMW, IMP,
IMS, ISW and IMR 2 can be sealed.

COMPLIANCE WITH STANDARDS

PNIEC 185 +A1:1994


IEC185: 1987 +A1: 1990
GOST 7746 89
DIN/VDE 0414Teil: 1/01.94
The current transformers types INSOA, IMW, IMPa, IMPb, IMSa,
IMSb, IMSc are approved by Polish Register of Ships and by
Germanischer Lloyd for use on ships.

WARRANTY

DESIGN

The low voltage current transformers are single-phase, low power


transformers, operating in quasi short-circuit conditions and
transforming the current flowing through the primary circuit to the
current in the secondary circuit with the observance of the
requirements relating to the accuracy of the transformation specified
in standards.

TRANSFORMERS type IMW

The factory warranty is twenty four months since the day of putting
the apparatus into operation, but not longer than thirty six months
since the date of purchase.

THE EXAMPLE OF ORDER

The low voltage current transformer type IMSc


Ipn = 600 A; Isn = 5 A; Sn = 10 VA; class 0,5; FS 5; for temperate
climate conditions.

TECHNICAL DATA

Type

Rated
power

Ipn

Secondary
current
Isn

VA

Primary
current

5
5; 7,5;
10; 15
20
5

1; 2; 3; 5;
10; 15;
20; 25
30; 50
75
100
150

IMW

200

250

300

Sn

5; 7,5;
10; 15
20
5; 7,5;
10
1 or 5

Rated current
Security
short-time
dynamic
Class of factor for
thermal
(peak)
apparat.
accuracy
Ith
Idyn
FS
kA

0,2

10

0,5 or 1

1
0,2

10

0,5 or 1

5; 7,5;
10; 15
20
5; 7,5

kV

Rated test
voltage

Weight Spacing of
(about) cerminals

Up
kV

kg

Current
terminals

mm

102
or
108

M6
or
M8

108

M8

1
0,5

10
5

10
5; 7,5;
10; 15
15
5

kA

Maximum
permissible
voltage of
transformer
Um

10

60 x lpn

150 x lpn

0,72

0,8

5
0,2
0,5 or 1
1
0,2

5; 7,5; 10;
0,5 or 1
15; 20

10
5

Note: The versions of current transformer type IMW with secondary winding parameters: 5 VA, class 0,2; 10 VA, class 0,5; 15 VA, class 1 areprefered.
2

ABB

102 or 108

114 or 127

DIMENSIONAL DRAWING IMW transformers with bus bar 20 x 5 mm

TRANSFORMERS type IMP


TECHNICAL DATA
Security
factor for
apparat.

Rated power
Type

Rated
ratio

A/A

IMPa

IMPb

100/5
100/1
150/5
150/1
200/5
200/1
250/5
250/1
300/5
300/1
150/5
150/1
200/5
200/1
250/5
250/1
300/5
300/1
400/5
400/1

Sn
class 0,2

class 0,5

class 1

VA

VA

VA

2,5

5
7,5
10

5
7,5
10

5; 7,5;
10; 15

5; 7,5;
10; 15

5 *
7,5

5; 7,5;
10; 15;
20

5; 7,5;
10; 15;
20
5; 7,5;
10; 15;
20

2,5

5
7,5
10

5
7,5
10
*

5; 7,5;
10; 15

5 *
7,5

5; 7,5;
10; 15;
20

FS

dynamic
(peak)
Idyn

kA

kA

kV

kV

kV

kg

60 x lpn

150 x lpn

0,72

10 x 20

0,8

60 x lpn

150 x lpn

0,72

10 x 30

0,5

Weight
(about)

Up

Maximal
dimens.
of cross-section
of a bus

Rated test
voltage

10

10

5; 7,5;
10; 15
5; 7,5;
10; 15;
20
5; 7,5;
10; 15;
20

short-time
thermal
Ith

Maximum
permissible
voltage of
transformer
Um

Rated current

* - for class 0,2 FS 10..


ABB

DIMENSIONAL DRAWING IMPa current transformers for cable max 20 mm or bar 20 x 10 mm


IMPb current transformers for cable max 30 mm or bar 30 x 10 mm

Supporting version

Seal wired version

For version IMPa - the length


A = 20,2 mm
For version IMPb - the length
A = 30,2 mm

TRANSFORMERS type IMS


TECHNICAL DATA

Type

Primary
current

Secondary
current

Ipn

Isn

Rated power
Sn
class 0,2 class 0,5 class 1
VA

VA

150
200

250

300

or
IMSa

400

600

5
7,5
10

500

Security
factor for
apparat.

5
7,5
10
15

5
7,5
10
15

VA

5
5
7,5
5
7,5
5
7,5
10
5
7,5
10
15
5
7,5
10
15
20
5
7,5
10
15
20

FS

Rated current
short-time
thermal
Ith

dynamic
(peak)
Idyn

Maximum
permissible
voltage of
transformer
Um

kA

kA

kV

kV

kg

60 x lpn

150 x lpn

0,72

0,45

Rated test
voltage

Weight
(about)

Up

ABB

TECHNICAL DATA

Type

Primary
current

Secondary
current

Ipn

Isn

Rated power
Sn
kl. 0,2

kl. 0,5

kl. 1

VA

VA

VA

5
7,5

5
7,5
10
5
7,5
10
5
7,5
10
15
5
7,5

10

10
15

600

5
750
IMSb
800

1000

Security
factor for
apparat.

1
lub

7,5

5
7,5
10
15
5
7,5
10
15
5
7,5
10
15
5
7,5
10
15
20

FS

dynamic
(peak)
Idyn

Maximum
permissible
voltage of
transformer
Um

Rated test
voltage

kA

kA

kV

kV

kg

60 x lpn

150 x lpn

0,72

0,7

short-time
Ith

Weight
(about)

Up

5
10
5
10
5
10
5

DIMENSIONAL DRAWING IMSa current transformers


for bus bar max 40 x 10 mm

ABB

Rated current

DIMENSIONAL DRAWING IMSb current transformers


for bus bar max 60 x 10 mm

TECHNICAL DATA

Type

Primary
current

Secondary
current

Ipn

Isn

Rated power
Sn
class 0,2 class 0,5 class 1
VA

VA

400
500
600

750

800

5
7,5
1

IMSc

1000

or

5
7,5
10

5
1200

1500

1600

2000

Security
factor for
apparat.

5
7,5
10
7,5
10
7,5
10
7,5
10

5
7,5
10
5
7,5
10
15
5
7,5
10
15
5
7,5
10
15
20
5
7,5
10
15
20
7,5
10
15
20
7,5
10
15
20
7,5
10
15
20

VA

7,5
10
7,5
10
5
7,5
10
15
5
7,5
10
15
5
7,5
10
15
5
7,5
10
15
20
5
7,5
10
15
20
7,5
10
15
20
7,5
10
15
20
7,5
10
15
20

FS

short-time
thermal
Ith

dynamic
(peak)
Idyn

Maximum
permissible
voltage of
transformer
Um

kA

kA

kV

kV

kg

60 x lpn

150 x lpn

0,72

0,9

Rated current

Rated test
voltage

Weight
(about)

Up

10
5
10
5
10
5

DIMENSIONAL DRAWING IMSc current transformers for bus bar max 80 x 10 mm

ABB

TECHNICAL DATA

Type

Primary
curent

Secondary
current

Ipn

Isn

[A]

[A]

Parameters of secondary
windings

5 VA class 0,2 FS 10
15 VA class 0,5 FS 5
30 VA class 1 FS 5
5 VA class 0,2 FS 10
15 VA class 0,5 FS 5
30 VA class 1 FS 5
15 VA class 0,2 FS 5
30 VA class 0,5 FS 5
45 VA class 1 FS 5
15 VA class 0,2 FS 5
30 VA class 0,5 FS 5
45 VA class 1 FS 5
30 VA class 0,2 FS 5
60 VA class 0,5 FS 5
60 VA class 1 FS 5
45 VA class 0,2 FS 5
60 VA class 0,5 FS 5
90 VA class 1 FS 5
60 VA class 0,2 FS 5
90 VA class 0,5 FS 5
120 VA class 1 FS 5

1500

1600

2000

1
or

IMSd

2500

3000

4000

5000

Rated current

Weight
(about)

thermal, 1-sec.

dynamic (peak)

Ith [kA]

Idyn [kA]

37,5

100

[kg]

1,3
40

105

50

125
1,5

62,5

156,5

75

187
1,6

100

250

100

250

Maximum
permissible voltage
of transformer

Test
voltage

Extended
current
range

Um [kV]

Up [kV]

ext. % x Ipn

0,72

120% x Ipn

1,8

DIMENSIONAL DRAWING IMSd current transformers for bus bar max 120 x 30 mm or 100 x 50 mm

ABB

TRANSFORMERS type ISW


TECHNICAL DATA

Type

Primary
current

Secondary
current

Ipn

Isn

class 1

VA

VA

200
250
300

2,5
2,5

2,5
2,5; 5
2,5; 5

400

5; 7,5

5; 7,5
10

5; 7,5
10

5; 7,5
10; 15

or

5; 7,5
10; 15

5; 7,5
10; 15

750

5; 7,5
10; 15

5; 7,5
10; 15
20

800

5; 7,5
10; 15

5; 7,5
10; 15
20

250
300

2,5
2,5

2,5
2,5

400

2,5; 5

2,5; 5
7,5

500

2,5; 5
7,5; 10

2,5; 5
7,5; 10

600

2,5; 5
7,5; 10

2,5; 5
7,5; 10
15

750

2,5; 5
7,5; 10
15

2,5; 5
7,5; 10
15

2,5; 5
7,5; 10
15

2,5; 5
7,5; 10
15; 20

1000

2,5; 5
7,5; 10
15; 20

2,5; 5
7,5; 10
15; 20

1200

5; 7,5;
10; 15;
20; 30

5; 7,5;
10; 15;
20; 30

1500

5; 7,5;
10; 15;
20; 30

5; 7,5;
10; 15;
20; 30

1600

5; 7,5;
10; 15;
20; 30

5; 7,5;
10; 15;
20; 30

500
600

1
ISWb

800

or
5

Sn
class 0,5

ISWa

Rated power

short-time
thermal
Ith

dynamic
(peak)
Idyn

Maximum
permissible
voltage of
transformer
Um

kA

kA

kV

kV

kg

60 x lpn

150 x lpn

0,72

0,8

60 x lpn

150 x lpn

0,72

0,8

Security
factor for
apparat.
FS

Rated current

Rated test
voltage

Weight
(about)

Up

ABB

DIMENSIONAL DRAWING ISWa current transformers


for cable max 48 mm or bus bar max 50 x 30 mm

DIMENSIONAL DRAWING ISWb current transformers


for cable max 48 mm or bus bar max 60 x 30 mm

TRANSFORMERS type INSOA


TECHNICAL DATA

Type

Rated
ratio

Rated
power
Sn
class 3

A/A

INSOA

100/5
100/1
150/5
150/1
200/5
200/1
300/5
300/1
400/5
400/1

VA

Security
factor for
apparat.
FS

Rated current
short-time
thermal
Ith

dynamic
(peak)
Idyn

Maximum
permissible
voltage of
transformer
Um

kA

kA

kV

kV

mm

kg

60 x lpn

150 x lpn

0,72

10 x 30

0,4

Weight
(about)

Up

Maximal
dimensions
of cross-section
of a bus

Rated test
voltage

4
5; 7,5
5; 7,5; 10

5; 7,5; 10
5; 7,5; 10

DIMENSIONAL DRAWING INSOA current transformers for cable max 30 mm or bus bar max 30 x 10 mm

Supporting version

ABB

Seal wired version

TRANSFORMERS type IMR0


TECHNICAL DATA

Type

Rated
primary
current
Ipn

Parameters
of secondary winding
for version A =30 mm

Parameters
of secondary winding
for version A =50 mm

[A]

power; class; FS

power; class; FS

[A]

1 VA class 3 FS 5

50
75
IMR0

Rated
Rated test Rated current
secondary
voltage
current
short-time dynamic
Isn
thermal
(peak)

2,5 VA class 3 FS 5
2,5 VA class 1 FS 5

100

2,5 VA class 1 FS 5
1 VA class 0,5 FS 5
4 VA class 3 FS 5
2,5 VA class 0,5 FS 5

150
200

[kV]

[kA]

[kA]

Maximal
cross
-section
of busbar

Weight
(about)

[mm]

[kg]

20 x 5

0,4

2,5 VA class 3 FS 5
1 VA class 3 FS 5
2,5 VA class 3 FS 5
1 VA class 0,5 FS 5
4 VA class 3 FS 5
5 VA class 1 FS 5
2,5 VA class 0,5 FS 5

5
3

60 x lpn 150 x lpn

1 or 5

4 VA class 0,5 FS 5

DIMENSIONAL DRAWING IMR0 current transformers for cable max 18 mm or bus bar max 20 x 5 mm

Version with secondary


terminals

Version with leaded cables LYc,


length approximately 20 cm

TRANSFORMERS type IMR1


TECHNICAL DATA
Rated primary
current
Type

75
100
150
200
250
300
400
10

Parameters
of secondary winding

Up

short-time
thermal

dynamic
(peak)

Maximal
cross
-section
of busbar

[A]

[kV]

[kA]

[kA]

[mm]

[kg]

1 or 5

60 x lpn

150 x lpn

20 x 10

0,6

Rated
secondary
current
Isn

Rated test
voltage

power; class; FS

1 VA class 1 FS 5
2,5 VA class 3 FS 5
1 VA class 1 FS 5
2,5 VA class 1 FS 5
2,5 VA class 0,5 FS 5
5 VA class 1 FS 5
5 VA class 0,5 FS 5
7,5 VA class 1 FS 5
5 VA class 0,5 FS 5
7,5 VA class 1 FS 5
7,5 VA class 0,5 FS 5
10 VA class 1 FS 5
10 VA class 0,5 FS 5
15 VA class 1 FS 5

Ipn
[A]

IMR1a

The current transformer type IMR 1 for A = 20,5 mm


Rated current

Mass
(about)

ABB

The current transformer type IMR 1 for A = 25,5 mm


Rated primary
current
Type

100
150
200
250
300
400
500

dynamic
(peak)

Maximal
cross
-section
of busbar

Weight
(about)

[kA]

[kA]

[mm]

[kg]

60 x lpn

150 x lpn

25 x 10

0,6

Rated
secondary
current
Isn

Rated test
voltage
Up

short-time
thermal

power; class; FS

[A]

[kV]

1 VA class 1 FS 5
2,5 VA class 3 FS 5
1 VA class 0,5 FS 5
2,5 VA class 1 FS 5
2,5 VA class 0,5 FS 5
5 VA class 1 FS 5
2,5 VA class 0,5 FS 5
5 VA class 1 FS 5
5 VA class 0,5 FS 5
7,5 VA class 1 FS 5
7,5 VA class 0,5 FS 5
10 VA class 1 FS 5
10 VA class 0,5 FS 5
15 VA class 1 FS 5

1 or 5

Ipn
[A]

IMR1b

Parameters
of secondary winding

DIMENSIONAL DRAWING IMR1a current transformers


for cable max 18 mm or bus bar max 20 x 10 mm

Version with secondary


terminals

Rated current

DIMENSIONAL DRAWING IMR1b current transformers


for cable max 23 mm or bus bar max 25 x 10 mm

Version with leaded cables LYc,


length approximately 20 cm

For version IMR 1a - the length


A = 20,5 cm.
For version IMR 1b - the length
A = 25,5 cm.

TRANSFORMERS type IMR2


TECHNICAL DATA
Rated primary
current
Type

Ipn
[A]

power; class; FS

200

5 VA class 1 FS 5

250

5 VA class 0,5 FS 5
10 VA class 1 FS 5
10 VA class 0,5 FS 5
10 VA class 1 FS 5
15 VA class 0,5 FS 5
15 VA class 1 FS 5
15 VA class 0,5 FS 5
20 VA class 1 FS 5
15 VA class 0,5 FS 5
20 VA class 1 FS 5
15 VA class 0,5 FS 5
20 VA class 1 FS 5
15 VA class 0,5 FS 5
20 VA class 1 FS 5

300
IMR2

400
500
600
630
650

ABB

Parameters
of secondary winding

Rated
secondary
current
Isn

Rated test
voltage
Up

short-time
thermal

dynamic
(peak)

Maximal
cross
-section
of busbar

[A]

[kV]

[kA]

[kA]

[mm]

[kg]

1 or 5

60 x lpn

150 x lpn

40 x 10

0,6

Rated current

Weight
(about)

11

DIMENSIONAL DRAWING IMR2 current transformers for cable max 30 mm or bus bar max 40 x 10 mm
Version with secondary
terminals

Version with leaded cables LYc,


length approximately 20 cm

Manufacturer reserves for itself the right to train the changes resulting from the technological progress.

ABB Sp. z o.o.


Power Technologies Division
ul. Leszno 59
06-300 Przasnysz, Poland
Phone: ( +48 22) 52 52 838, 51 52 831
( +48 29) 75 33 233, 75 33 240
Fax:
+48 22 51 52 659, +48 29 75 33 327
www.abb.com

1YMA699050-en Publication 04.2003