Professional Documents
Culture Documents
1/8
TABLE OF CONTENTS
1.
Civil works..............................................................................................3
1.1.
Site preparation...................................................................................................... 3
1.2.
2.
Foundations............................................................................................................ 3
Construction works...............................................................................4
2.1.
2.2.
2.3.
2.7.
Painting.................................................................................................................... 7
2/8
1.
Civil works
1.1.
Site preparation
Approx site area is 14.350 m with access to existing main road via side road on
reserved site (see attached drawing: Site Plan). The erection of the side road
outside the site boundaries and the preparation of all needed media connections
(water, sewage, electricity, telecom, etc.) are excluded from VAMED scope of
work.
The site area is flat land .
Existing trees and bushes on the site have to be rooted out where necessary.
Main trenches for channels, (for building supplying services) potable water, fire
fighting water, electricity etc. will be excavated and backfilled with the soil placed
alongside the trenches. Electrical power supply cables will be protected with brick
layer and warning tape.
Gardening and landscaping:
Green areas around the buildings have to be covered with humus and planted with
suitable grassing and some trees. Trees and bushes have to be cultivated
according to the site-layout.
1.2.
The fence around the site has to be made of galvanized mesh 1.80 m height.
Total length according to drawings.
Site entering gates: metal, with galvanized mesh, manually operated 6 m width
(or 2x3m), H=1,8 m
1.3.
1.4.
Foundations
3/8
2.
Construction works
2.1.
Outside and inside non-bearing walls shall be built of local made hollow blockwork
(or solid concrete blocks or red bricks where applicable) min.10 cm thick, incl. all
necessary lintels, girders, columns, inside and outside plastered, ready for
painting, tiling or laying of vinyl sheet.
All walls have to be able to carry wall mounted facilities, cupboards, MT
equipment, etc. wherever necessary, acc. to the approved detailed shop drawings.
Building parts within air-conditioned areas must have fully insulated walls (double
walls 10+5+10 cm, with 5 cm insulation)
Walls must be connected with wire loops to the main structural system to avoid
possible cracks in the joints.
2.3.
Walls shall be lead shielded for X-ray protection, thickness according to standards
for X-Ray facilities (max 150 kV) authoritys approval.
2.4.
4/8
Roof
2.5.1. Structure and Substructure
Sloping roof structure shall be executed according proposed design
requirements and static calculations.
Roof truss shall be made of steel/metal. Main structural framing shall
be especially coated with aluminum-zinc coating to prevent rust.
All details according to the manufacturer's production details and
shop drawings.
2.5.2. Roofing
The roof shall be made of special coated profiled steel or aluminum
sheets, standard color acc. manufacturer (protection coat), outside
colored, support made of corrosion protected metal profiles.
The roof has to be watertight and insect tight.
All openings for ventilation with insect protection screen.
5/8
H01
H02
patient bedrooms
H03
static conductive
vinyl sheet
H04
x-ray rooms
H05
ceramic tiles,
good quality, easy
to clean
H06
various stores,
cleaners room
ceramic tiles,
good quality, easy
to clean, anti-slip
H07
toilets, showers
H08
corridors, waiting
zones in closed
areas, nurse base,
various bays
ceramic tiles,
good quality, easy
to clean, anti-slip
ceramic tiles,
good quality, antislip
H09
laboratories
H10
CSSD
WALL FINISHES
CEILING
special (antibacterial)
paint, ceramic tiles
around basins,
skirting of same
material as floor
finish min. 10 cm
high
special (antibacterial)
paint, ceramic tiles
around basins,
skirting of same
material as floor
finish min. 10 cm
high
special (antibacterial)
paint, easy cleaning,
rounded molding and
skirting of same
material as floor
finish min. 10 cm
high or vinyl sheet,
rounded molding
facing plaster board
wall, radiation
protection, latex
paint, skirting of
same material as
floor finish min. 10
cm high
special (antibacterial)
paint, ceramic tiles
around basins,
skirting of same
material as floor
finish min. 10 cm
high
latex paint, skirting of
same material as
floor finish min. 10
cm high
ceramic tiles
latex paint
special (antibacterial)
paint, ceramic tiles
around basins,
skirting of same
material as floor
finish min. 10 cm
high
latex paint
suspended plasterboard
ceiling, special
(antibacterial) paint
suspended plasterboard
ceiling, radiation
protection, latex paint
latex paint
latex paint
latex paint
6/8
N01
WALL FINISHES
CEILING
ceramic tiles
latex paint
latex paint
ceramic tiles,
heavy duty, antislip
ceramic tiles
suspended plasterboard
ceiling, latex paint
ceramic tiles,
easy to clean,
anti-slip
N02
main entrance,
dining area
natural stone,
good quality, antislip
N03
staircases,
corridors, waiting
zones in open
areas
N04
waste management
services
N05
engineering
services, cleaning /
housekeeping,
hospital medical
stores
catering
department
(kitchen), laundry /
linen services
central staff
facilities, relatives
dormitories
natural stone,
terrazzo or
ceramic tiles,
good quality, antislip
ceramic tiles,
heavy duty, antislip
ceramic tiles,
heavy duty, antislip
N06
N07
N08
N09
open walkways on
ground floor, M&E
plants
terraces
N10
sealed concrete,
anti-slip
concrete tiles,
anti-slip
ceramic tiles,
easy to clean,
anti-slip
concrete
Painting
In general, all walls, gypsum boards and ceilings must be painted with emulsion
paint, primer and final coat. The colors shall be selected by SLAF and the Project
Architect.
Washable emulsion paint in corridors up to 1,5 m high shall be provided.
7/8
Internal doors
2.8.1. Standard doors
Door leaf: standard aluminium frame, melamine filling
Door frames: steel frames, manufactured from zinc coated steel,
ready for paint finish, acc. BS
Handles: stainless steel (hygienic areas e.g. OT-dept., CSSD) and
anodized aluminium, emergency escape doors with panic handle set,
all acc. to BS and design guideline by Project Architect
Hinges: stainless steel, acc. BS
Door bumpers, stoppers: where necessary
2.8.2. Doors to Operation Theatres
Door leaf: manually operated, standard aluminium frame, stainless
steel cover
Door frames: steel frames, manufactured from zinc coated steel,
ready for paint finish, acc. BS
Handles: stainless steel, acc. to BS and design guideline by Project
Architect
Hinges: stainless steel, acc. BS
Push plates: base plates and push plates (approx.15 cm high) made
of 1mm stainless steel or 2mm aluminum plates on both sides of the
door.
2.8.3. Double wing doors, partly glazed
Door leaf: standard aluminium frame, acc. to BS
Glazing: single glazed, acc. BS
Door frames: steel frames, manufactured from zinc coated steel,
ready for paint finish, acc. BS
Handles: stainless steel (hygienic areas e.g. OT-dept., CSSD) and
anodized aluminium, emergency escape doors with panic handle set,
all acc. to BS and design guideline by Project Architect
Hinges: stainless steel, acc. BS
Door bumpers, stoppers: where necessary
2.8.4. X-ray doors
Door leaf: standard aluminium frame, melamine filling, X-ray
protection acc. BS1178
Door frames: steel frames, manufactured from zinc coated steel,
ready for paint finish, X-ray protection acc. BS1178
Handles: stainless steel, acc. to BS and design guideline by Project
Architect
Hinges: stainless steel, acc. BS
Door bumpers, stoppers: where necessary
8/8