Specification EXH-EG-1826-H
SPECIFICATION EXH-EG-1826-H
AIR COOLED HEAT EXCHANGERS
December 1989
Page 1 of 11
Chevron
Specification EXH-EG-1826-H
CONTENTS
1.0
GENERAL............................................................................................................................3
2.0
PROPOSALS........................................................................................................................3
3.0
DOCUMENTATION............................................................................................................3
4.0
5.0
DESIGN ...............................................................................................................................4
6.0
MATERIALS........................................................................................................................7
7.0
FABRICATION....................................................................................................................8
8.0
9.0
11.0
Page 2 of 11
December 1989
Chevron
Specification EXH-EG-1826-H
1.0
GENERAL
1.1 Scope
(Addition) This specification supplements the requirements of the latest edition of API
Standard 661 (referred to hereafter as API 661) and its Appendices. An accompanying data
sheet for each unit describes further requirements for performance and construction.
1.1.1
Nomenclature.
(Exception) In order of precedence, the unit shall conform to the following documents:
2.0
3.0
PROPOSALS
2.2.1
2.2.8
(Exception) The proposal shall include a completed noise data sheet, NCM-EF-594.
DOCUMENTATION
3.1 Approval Information
3.1.1
December 1989
(Addition) In addition to the items listed in Paragraph 3.1.1 of API 661, Vendor shall
include the following information on the outline drawings.
Page 3 of 11
Chevron
Specification EXH-EG-1826-H
14.
3.1.2
(Addition) Vendor shall not start fabrication until Company has approved preliminary
or final shop drawings submitted in accordance with Paragraph 3.1.1.
3.1.4
(Addition) All proposed welding procedures and qualifications shall be submitted for
approval prior to start of fabrication.
4.0
9.
12.
GUARANTEE (EXCEPTION)
Vendor shall guarantee each unit in accordance with GAM-EG-3042.
5.0
DESIGN
5.1.6
5.1.9
Gaskets
5.1.9.2 (Addition) Where compressed asbestos gaskets are used or where gaskets are
not confined, 450F shall be given as maximum allowable temperature.
Page 4 of 11
December 1989
Chevron
Specification EXH-EG-1826-H
Type of Fin
1.
2.
3.
4.
Maximum Inlet
Fluid Temperature
Embedded
Integral
Overlapped Footed
Footed
750F
550F
250F
250F
Noise Control
5.2.2.1 (Exception) The Vendor's base proposal shall include his standard sound
level control features, if any. Unless otherwise specified, maximum sound
pressure levels at any location 3 feet from any air cooler surface shall not
exceed 85 dBA.
For the basic offering, the Vendor shall furnish the guaranteed A-weighted
sound pressure level at 3 feet from the unit. If the sound pressure level of the
basic offering exceeds 85 dBA, the Vendor shall separately quote special
designs and/or acoustic treatment that would be required for the Vendor to
guarantee 85 dBA. Details of specific designs and/or acoustic treatment shall
be furnished with the proposal.
5.2.3
5.2.5
Lubrication Facilities
5.2.5.1 (Addition) Length of lines supplying grease to bearings shall be held to the
minimum consistent with good accessibility.
December 1989
Page 5 of 11
Chevron
Specification EXH-EG-1826-H
5.2.5.2 (Addition) Gear box oil level shall be capable of being checked and oil added
if necessary without hazardous exposure of the operator or shutdown of the
equipment.
5.2.8
5.2.11.9
5.2.12 Gear Drives (Addition) All gear selection is subject to the Company's specific
review and approval.
5.2.14 Vibration Cutout Switches
5.2.14.1
5.3.4
Access Facilities
5.3.4.1 (Addition) Full platform access to fan motors, gears, vibration shutdown
switches, and piping flanges is required. Where plug access is the only
maintenance requirement, permanent supports for temporary scaffolding are
acceptable.
Page 6 of 11
December 1989
Chevron
Specification EXH-EG-1826-H
6.0
MATERIALS
6.1 General Requirements. (Addition) Materials shall comply with requirements of Data Sheet
EXH-DS-1826.
6.1.1
Carbon Steel
Low-Alloy Steel
Austenitic Stainless Steel
Ferritic Stainless Steel
SA-179 or SA-192
SA-209 or SA-213
SA-213
SA-268
Maximum
Fan Diameter
12 feet
18 feet
18 feet
18 feet is an
6.1.8.1 (Addition) Copper content of aluminum blades shall not exceed 0.4% to
exclude aluminum alloys with poor corrosion resistance.
December 1989
Page 7 of 11
Chevron
Specification EXH-EG-1826-H
6.1.8.3 (Addition) All components of the fan assembly including the nonmetallic
parts such as plastic fan blades, blade mounting bushings, variable pitch
controls shall meet the following conditions:
1. Fans in induced draft service may be shut down for extended periods,
and will then be subjected to the inlet temperature of the fluid being
cooled. They shall be suitable to be re-started from this condition.
2. During turnaround, the cooling coils will be subject to steam flow at
a temperature specified by the Company. The fans will not be
operated during or immediately following this period. Fans and other
components above the bundle in induced draft services will be subjected
to the saturation temperature of the steam.
3. For air cooled heat exchangers with provisions for air recirculation, due
consideration shall be given to the temperature to which the fans may be
subjected during abnormal operation.
7.0
FABRICATION
7.1 Welding
7.1.1
General
7.1.1.5 (Addition) Weld rod or wire shall be selected to ensure that the deposited
weld metal in the finished header will not exceed 100,000 psi tensile strength.
This shall be verified by hardness testing in accordance with Section 8.2.13.
(Addition) Carbon steel shall receive a postweld heat treatment when required by
Code or when specified by the Company.
Preheat and postweld heat treatment requirements for carbon steel shall be as follows:
Page 8 of 11
To 1-1/2 in.:
70F
Over 1-1/2 in.: 250F
1100-1200F
Per Code
December 1989
Chevron
Specification EXH-EG-1826-H
8.0
2.
3.
(Addition) Tests shall be made after any required postweld heat treatment
and before hydrostatic testing.
4.
(Exception) Any carbon steel joint with a hardness over 200 Brinell or lowalloy joint with a hardness over 215 Brinell shall be rejected.
5.
6.
(Addition) The tube side shall be hydrostatic tested to 1-1/2 times the maximum
allowable pressure at the test temperature calculated for the nominal thickness as
constructed in accordance with Code Paragraph UG-99(b).
8.3.3
(Addition) The minimum fluid temperature for hydrostatic testing shall be higher than
the Minimum Pressurizing Temperature listed on the Data Sheet EXH-DS-1826.
8.3.7
(Addition) Normal service gaskets shall be used for all hydrostatic tests.
December 1989
Page 9 of 11
Chevron
Specification EXH-EG-1826-H
8.3.8
(Addition) The purchaser's inspector shall witness the final required tests as
described above.
(Addition) In addition to the data required by the Code and API 661, the nameplate
shall give the following information:
a.
b.
c.
d.
9.0
(Exception) Company will specify coating system to be used and surface preparation
requirements. Vendor may submit alternate coating proposals for Company review
and approval.
9.1.5
Page 10 of 11
December 1989
Chevron
Specification EXH-EG-1826-H
EXH-DS-1826
DRI-EG-404
DRI-EG-1824
GAM-EG-3042
NCM-EF-594
GD-M13909
GF-M88575
GF-M99645
December 1989
Page 11 of 11