APPLICATION DATA
AD353-126
Rev 1
November 2005
Column Feed
FT
Base Temperature
X
Q = Cp F
TC
TT
COLUMN
SP
PV
QC
CO
Base Level
X
_
TT
Design
LC
Bottoms
Base Level Controller
TT
REBOILER
FT
LT
Q = c p m(TS TR )
where: Q = heat transfer rate
cp = specific heat
m = mass flow rate
TS = supply temperature
TR = return temperature
The engineering equation must have consistent
engineering units, for example, if flow is in units of
lbs/min, heat transfer should be in BTU/min. If,
instead, heat transfer is in units of BTU/hr, the
engineering equation must include a units conversion
constant (60 minutes/hour) to yield the correct
results. As another example, if the flow is in volume
units such as gallons/minute (GPM), a density
AD353-126
Transmitter Ranges:
Hot oil flow: 0 to 500 GPM
Hot oil supply temp: 100 to 200 F
Hot oil return temp: 100 to 200 F
For the design conditions shown above, the
engineering equation is modified as follows:
AD353-126
Application Support
Other Application Data sheets in this series can be
found at the Siemens public Internet site. Detailed
information about the function blocks mentioned in
this publication can be found in the Users Manual for
each controller.
Procidia, i|pac, i|config, and 352Plus are trademarks of Siemens Energy & Automation, Inc. Other trademarks are the property of their
respective owners. All product designations may be trademarks or product names of Siemens Energy & Automation, Inc. or other supplier
companies whose use by third parties for their own purposes could violate the rights of the owners.
Siemens Energy & Automation, Inc. assumes no liability for errors or omissions in this document or for the application and use of information
in this document. The information herein is subject to change without notice.
Siemens Energy & Automation, Inc. is not responsible for changes to product functionality after the publication of this document. Customers
are urged to consult with a Siemens Energy & Automation, Inc. sales representative to confirm the applicability of the information in this
document to the product they purchased.
Control circuits are provided only to assist customers in developing individual applications. Before implementing any control circuit, it should
be thoroughly tested under all process conditions.
Copyright 2005, Siemens Energy & Automation, Inc.