Professional Documents
Culture Documents
Application Bulletin
Copyright
Trademarks and
patents
Manufacturer
Contact information
Content
ii
Important information
Limitation of liability
The content of this manual is proprietary in nature and is intended solely for
distribution to authorized persons, companies, distributors or others for the sole
purpose of conducting business associated with UTC Fire & Security. The
distribution of information contained within this manual to unauthorized persons
shall constitute a violation of any distributor agreements and may result in
implementation of legal proceedings.
The Signature Series detectors have been designed to meet the requirements of
the following standards:
CAN/CSA-6.19-01
NFPA 72
UL 521
CAN/ULC-S527
NFPA 720
UL 864
CAN/ULC-S529-09
UL 268
UL 2034
CAN/ULC-S530-M91
UL 268A
UL 2075
ICES-003
Installation in accordance with this manual, applicable codes, and the instructions
of the authority having jurisdiction is mandatory. UTC Fire & Security shall not
under any circumstances be liable for any incidental or consequential damages
arising from loss of property or other damages or losses owing to the failure of
UTC Fire & Security products beyond the cost of repair or replacement of any
defective products. UTC Fire & Security reserves the right to make product
improvements and change product specifications at any time.
While every precaution has been taken during the preparation of this manual to
ensure the accuracy of its contents, UTC Fire & Security assumes no
responsibility for errors or omissions.
FCC warning
This equipment can generate and radiate radio frequency energy. If this
equipment is not installed in accordance with this manual, it may cause
interference to radio communications. This equipment was tested and found to
comply within the limits for Class A computing devices pursuant to Subpart B of
Part 15 of the FCC Rules. These rules provide reasonable protection against
such interference when this equipment is operated in a commercial environment.
If the operation of this equipment causes interference, the user must correct the
interference and incur the expense.
iii
Related documentation
National Fire Protection Association (NFPA)
1 Batterymarch Park
Quincy, MA 02168-7471
NFPA 70
NFPA 72
NFPA 720
UL 38
UL 217
UL 228
UL 268
UL 268A
UL 346
UL 464
UL 521
UL 864
UL 1481
UL 1638
UL 1971
UL 2075
CAN/ULC S-524
CAN/ULC S-527
CAN/ULC S-529-09
CAN/ULC-S530-M91
CAN/ULC S-536
CAN/ULC S-537
CAN/CSA-6.19
iv
Description
SIGA-IS
SIGA-PS, SIGA2-PS
SIGA-PHS,
SIGA2-PHS,
SIGA2-PHSB [2] [3]
SIGA-IPHS
SIGA-IPHSB [3]
SIGA-HFS, SIGA2-HFS
SIGA-HRS, SIGA2-HRS Combination 15F (8C) per minute Rate-of-Rise, and 135F (57C)
Fixed-Temperature Heat Detector
SIGA2-COS
SIGA2-COS-CA [4]
SIGA2-HCOS
SIGA2-HCOS-CA [4]
Combination 15F (8C) per minute Rate-of-Rise, 135F (57C) FixedTemperature Heat Detector with CO sensor
SIGA2-PCOS
SIGA2-PCOS-CA [4]
SIGA2-PHCOS
SIGA2-PHCOS-CA [4]
Combination Photoelectric Smoke and 135F (57C) FixedTemperature Heat Detector with CO sensor
[1] The SIGA2 detectors are backwards compatible with the SIGA detectors, providing equivalent
functionality.
[2] The difference between the SIGA-PHS device and the SIGA2-PHS(B) is that the
SIGA2-PHS(B) can report the heat and photo elements as separate event types (independent latched, or independent - nonlatched), or together (combo alarm - latched). To set the type of
reporting, refer to the SDU Help version 11.0 or later.
[3] The B models are black.
[4] Model numbers with the suffix -CA are approved by ULC.
Description
SIGA
SIGA2
SIGA-AB4G
X [1]
SIGA-TCDR
X [1]
SIGA-SB
SIGA-SB4
SIGA-IB
SIGA-IB4
SIGA-RB
SIGA-RB4
2-CORPL
CO Replacement Module
2-SPRC1
2-SPRC2
SIGA-LED
SIGA-TS4
SIGA-TSB
SIGA-TS
SIGA-DG
Detector Guard
SIGA-DGSB
SIGA-DGMF
SIGA-DH
SIGA-DMP
Signature Series smoke, heat, and carbon monoxide sensor (CO) detectors are
intelligent analog addressable devices that contain their own microprocessors
that allow them to make alarm decisions based on the information collected by
their sensors. Depending on the detector, decisions may be based on the
information gathered by up to three independent sensing elements.
Addressing: All Signature Series detectors feature electronic addressing. No
addressing switches are used.
LEDs: Signature Series detectors use LEDs to indicate the detectors condition.
SIGA detectors have two LEDs, while SIGA2 detectors have one LED. In normal
condition, a flashing green LED indicates that the control panel is performing
background supervision and a flashing red LED indicates an alarm condition. In
the event of a loss of communication in some systems, the detector operates in a
stand-alone mode. As long as it maintains circuit continuity to the control panel,
the detector indicates the stand-alone mode by the steady operation of both
LEDs in SIGA detectors or the single LED in SIGA2 detectors.
Self-diagnostics: Signature Series detectors can perform and store a
comprehensive range of self-diagnostic measurements. The detector stores
information regarding a detectors hours of operation, last maintenance date,
sensitivity values, and number of recorded alarms and troubles.
Sensitivity: The alarm sensitivity is the minimum obscuration level at which the
detector initiates an alarm condition. On some Signature Series detectors, the
alarm sensitivity level may be changed to any of five sensitivity settings using the
control panel programming. See Table 17 on page 39 for SIGA and Table 18 on
page 40 for SIGA2.
Suitability: To select which detector is best suited for a particular type of fire, see
the following.
Verification: All Signature Series smoke detectors offer alarm verification for
validating an alarm condition before the control panel processes it. When
enabled, the alarm verification tries to reset a detector that has initiated an alarm
condition. If the detector cannot be reset or if it returns to its alarm condition
within the required time window, the alarm is considered valid and the control
panel processes it.
Sloping peaked-type, if the ceiling slopes in two directions from the highest
point. Consider curved or domed ceilings as a peaked ceiling, with the slope
figured as the slope of the chord from highest to lowest point. See Sloping
peaked-typed ceilings on page 8.
Sloping shed-type, if the high point is at one side with the slope extending
toward the opposite side. See Sloping shed-typed ceilings on page 9.
Ceiling Height is the height from the floor to the ceiling of a room or space.
Design spacing spacing required for a particular installation.
Listed spacing the spacing for which a heat detector is rated.
Partitions walls extending from the floor toward the ceiling. If they are within
15% of the ceiling, consider the space separated by the partitions as separate
rooms.
Solid joists are solid structures that project down from the ceiling surface
more than 4 in. (100 mm) and are spaced at intervals of 36 in. (910 mm) or less,
center-to-center. Consider solid joists equivalent to beams for smoke detector
spacing guidelines.
SIGA
SIGA2
SIGA-HRS
SIGA2-HRS
SIGA2-HCOS
SIGA2-HCOS-CA
Fixed temperature
SIGA-HFS
SIGA2-HFS
[1] For combination heat and rate-of-rise or photo-thermal detectors, see Table 5 on page 19.
.7S
S/2
S/2 .7S
S
S/2
S/2
S/2
1. Heat detector
Since all of the area within the detectors circle of coverage is suitable for
detecting a fire, the shape and dimensions of the detector coverage square in
Figure 3 on page 7 may be modified. Note that, although the coverage square
is now a rectangle, the coverage area remains within the overall detector circle
of coverage.
4 in.
3
1.
2.
3.
4.
5.
When installed on the ceiling, locate the heat detectors a minimum of 4 in. (100
mm) from the wall. When installed on walls, locate the detector between 4 in.
(100 mm) and 12 in. (300 mm) from the ceiling, as shown Figure 4 on page 7.
Ceiling height and construction
Make spacing adjustments when installing heat detectors on other than flat
smooth ceilings or at ceiling heights 10 ft. (3 m) to 30 ft. (9.1 m) high. Table 4
below lists the reduction in spacing required when mounting detectors on ceilings
higher than 10 ft. (3 m). This reduced spacing yields the equivalent response of
detectors located on a 10 ft. (3 m) ceiling. Evaluate ceilings above 30 feet with
consideration to the best type of detection and the placement and spacing.
Table 4: Heat detector ceiling height reduction percentages
Ceiling height
Percent of listed
spacing
SIGA-HFS,
SIGA-HRS
SIGA2-HFS,
SIGA2-HRS,
SIGA2-HCOS,
SIGA2-HCOS-CA
0 to 10 ft. (0 to 3.0 m)
100
70 ft. (21.3 m)
50 ft. (15.3 m)
10 to 12 ft. (3 to 3.7 m)
91
63 ft. (19.2 m)
84
58 ft. (17.7 m)
42 ft. (12.8 m)
77
53 ft. (16.2 m)
71
49 ft. (14.9 m)
35.5ft. (10.8 m)
64
44 ft. (13.4 m)
32 ft. (9.8 m)
58
40 ft. (12.2 m)
29 ft. (8.8 m)
52
36 ft. (11.0 m)
26 ft. (7.9 m)
46
32 ft. (9.8 m)
23 ft. (7.0 m)
40
28 ft. (8.5 m)
20 ft. (6.0 m)
34
23 ft. (7.0 m)
17 ft. (5.2 m)
Note: Ceiling heights higher than 30 ft. (9.1 m) exceed the limits of the testing for the requirement
of the code.
Less than 30 degrees, space the detectors using the height at the peak.
Greater than 30 degrees, space the detectors, other than those located in the
peak, based on the average slope height or the height of the peak.
1/2 S
Less than 30, adjust the horizontal spacing according to the height of the
peak
Greater than 30, adjust the horizontal spacing according to the average
sloped ceiling height or to the height of the peak
This spacing modification for sloped shed-typed ceilings is identical for spot-type
heat detectors and smoke detectors.
4 in.
(100 mm)
3
36 in.
(910 mm)
max.
4 in.
(100 mm)
Solid joists
When spacing heat detectors at right angles to the solid joists, do not exceed
50% of the listed spacing and mount the detectors at the bottom of the joists.
Figure 7: Heat detector spacing - solid joists
1
W
> 4 in.
(100 mm) D
D. Depth
W. Spacing between joist
10
1. Ceiling
2. Detector
3. Joist
1/2 S
1/2 S
1/4 S
1
1/2 S
1/2 S
1. Heat detector
2. Joist
Exposed beams
Exposed beams may impede the flow of fixed or rate-of-rise heat detectors.
Beams are defined as solid structures extending 4 in. (100 mm) or more down
from the ceiling. Beam spacing depends on the depth of projection from the
ceiling and the center-to-center spacing between the beams. If the beams
project:
Less than or equal to 4 in. (100 mm) below the ceiling, mount the detector on
the ceiling with normal ceiling spacing. See Figure 9, item 1.
More than 4 in. (100 mm) below the ceiling, mount the detector on the ceiling.
Do not exceed 66% of the listed spacing at right angles to the beam direction.
Treat the spacing in the direction parallel to the beams separately. See
Figure 9, item 2.
Less than 12 in. (300 mm) in depth and are spaced less than 96 in. (2.44 m)
on center, mount the detectors on the bottom of the beams. See Figure 9,
item 3.
Greater than 18 in. (460 mm) below the ceiling and are more than 96 in.
(2.44m) on center, treat each bay created by the beams as a separate area.
See Figure 9, item 4.
11
4 in.
D
(100 mm)
6
5
2
W
> 4 in.
(100 mm)
6
5
8
3
> 12 in.
(300 mm)
W
< 96 in. (2.44 m)
6
5
4
> 18 in.
(460 mm)
W
> 96 in. (2.44 m)
D = Depth of beam
W = Beam spacing
1. D = 4 in. (100 mm)
2. D = > 4 in. (100 mm)
12
5.
6.
7.
8.
Ceiling Section
Heat detector
Solid beam
Side view
1. Smooth ceiling
2. Top of detector is acceptable in this area
3. Wall
4. Floor
13
For a smooth ceiling, for every point on the ceiling, locate the detector within a
horizontal measurement no greater than 0.7 times the selected spacing.
Beams and solid joists
For smoke detector spacing, solid joists are considered equivalent to beams.
For ceilings with a beam or solid joist depth less than 10 percent of the ceiling
height (0.1 H) mount the detectors on the bottom of beams.
For ceilings with a beam or solid joist depth equal to or greater than 10 percent of
the ceiling height (0.1 H) and a beam spacing equal to or greater than 40 percent
of the ceiling height (0.4 H), locate the detectors on the ceiling in each beam
pocket.
For ceilings with a beam depth equal to or greater than 10 percent of the ceiling
height (0.1 H) and a beam spacing less than 40 percent of the ceiling height
(0.4 H), locate the detectors either on the bottom of the beams or on the ceiling
at smooth ceiling spacing in the direction parallel to the beams and at one-half
smooth ceiling spacing in the direction perpendicular to the beams.
14
6
5
2
0.4 H
6
5
3
0.4 H
H = Ceiling Heights
1
2.
3.
4.
< 1.0 H
. 0.1 H and . 0.4 H
0.1 H and . 0.4 H
Side view
5. Ceiling Section
6. Heat detector
7. Solid beam
Locate the smoke detectors on the ceiling within the beam pockets.
For beam depths less than or equal to 10 percent of the ceiling height (0.1 H),
locate the detectors with smooth ceiling spacing perpendicular to the beams.
15
For beam depths greater than 10 percent of the ceiling height (0.1 H) and
beam spacing greater than or equal to 40 percent of the ceiling height (0.4 H),
locate the detectors in each beam pocket.
For beam depths greater than 10 percent of the ceiling height (0.1 H) and
beam spacing less than 40 percent of the ceiling height (0.4 H), smoke
detectors are not required in every beam pocket but must be spaced not
greater than 50 percent of smooth ceiling spacing.
3
0.1
D/H
0.1
Smoke detector
D = Beam depth; H = average ceiling height over slope
1. Upslope
2. Place the detectors with not more than three beams between detectors and not exceeding
the smooth ceiling spacing
3. Place the detectors with not more than two beams between detectors and not exceeding the
50% of the smooth ceiling spacing
16
Greater than a 1 ft. in 8 ft. (1 m in 8 m) rise, place the first row of detectors
within 36 in. (910 mm) of the high end of the ceiling. Space additional
detectors, if required, based upon the horizontal projection of the ceiling and
ceiling construction.
Less than 30, adjust the horizontal spacing according to the height of the
peak.
Greater than or equal to 30, adjust the horizontal spacing according to the
average sloped ceiling height.
CO detector locations
Selecting a suitable location is critical to the operation of CO detectors. Install the
SIGA2 CO detector in accordance with NFPA 720 Standard for the Installation of
Carbon Monoxide (CO) Detection and Warning Equipment, UL 2075 Standard for
Gas and Vapor Detectors and Sensors, CAN/CSA-6.19-01 Residential Carbon
Monoxide Alarming Devices, CSA C22.1 Canadian Electrical Code, Part 1 and
applicable codes. Base the detector location and spacing on an engineering
evaluation that considers potential sources and migration of carbon monoxide. In
this evaluation, consider the HVAC system, which can provide CO migration.
Place the wall-mounted detectors at least 5 ft. (1.5 m) up from the floor. For
ceiling mounted applications, place the detector at least 1 ft. (0.3 m) from any
wall. For combination detectors, follow the spacing requirements for each sensor.
See Combination and multisensor detector spacing on page 19.
The recommended CO detector locations are:
17
Near air conditioners, heating registers, or any other ventilation source that
may interfere with CO gas entering the detector
In a recessed area
CO detector locations
WARNING: The CO detector by itself does not provide smoke or fire protection.
For life safety and property protection from fire, use the detector with ionization
detectors, photoelectric smoke detectors, or both.
18
SIGA
SIGA2
SIGA2-HRS
SIGA2-HCOS,
SIGA2-HCOS-CA
SIGA-PHS
SIGA-IPHS
SIGA-IPHSB
SIGA2-PHS
SIGA2-PHSB
SIGA2-PHCOS
SIGA2-PHCOS-CA
For spacing information about the thermal portion of the detector, see Heat
detector spacing on page 4.
Note: If using combination detectors incorporating both fixed temperature and
rate-of-rise heat detection principles, space the detector based on the rate-ofrise.
For spacing information about the smoke portion of the detector, see Smoke
detector spacing on page 13.
Note: If using combination smoke and heat detection principles, space the
detector based on the smoke portion. For example, space combination smoke
and heat detectors with a maximum spacing of 30 ft. (9.1 m) 5% or 18 in.
(460 mm).
19
Under-floor installation
When spot-type smoke detectors are installed under raised floors, they are
subjected to high air velocities and dust levels. Install the detectors with the base
up or the base vertical (never down) as shown in Figure 14 below. This
minimizes the effects of dirt, dust, and mechanical interference from cabling.
Figure 14: Permissible smoke detector under floor mounting
1
2
A
20
1. Ceiling section
2. Smoke detector, at ceiling
3. Smoke detector, below ceiling
4. Side view
5. Plan view
21
Number of air
changes per hour
Coverage per
detector
60
30
20
15
12
10
8.6
7.5
6.7
10
22
Sense fires in areas where heat cannot reach the detector. Heat from fires in
walls, roofs, or on the opposite side of closed doors may not reach the
detector.
Detect oxygen levels, smoke, toxic gases, or flames. Use these devices as
part of a broad-based life safety program which includes a variety of
information sources pertaining to heat and smoke levels, extinguishment
systems, visual and audible devices, and other safety measures.
23
Suitability of detectors
Open wood
Optimal
Wood pyrolysis
Unsuitable
Smoldering cotton
Unsuitable
PU foam
Suitable
N-heptane
Very Suitable
Optimal
Suitability of detectors
Open wood
Optimal
Wood pyrolysis
Unsuitable
Smoldering cotton
Unsuitable
PU foam
Suitable
n-heptane
Very Suitable
Optimal
24
Suitability of SIGA-IS
Open wood
Optimal
Wood pyrolysis
Suitable
Smoldering cotton
Very suitable
PU foam
Very suitable
N-heptane
Optimal
Unsuitable
25
Suitability of detectors
Open wood
Unsuitable
Wood pyrolysis
Optimal
Smoldering cotton
Optimal
PU foam
Very suitable
N-heptane
Very suitable
Unsuitable
Suitability of detectors
Open wood
Very suitable
Wood pyrolysis
Optimal
Smoldering cotton
Optimal
PU foam
Very suitable
N-heptane
Optimal
Very suitable
26
smoldering fires such as wood pyrolysis and smoldering cotton and fast, flaming
fires such as open wood and n-Heptane fires.
Table 12: Intelligent 4D multisensor smoke detector applications
Type of fire
Suitability of SIGA-IPHS(B)
Open wood
Optimal
Wood pyrolysis
Optimal
Smoldering cotton
Optimal
PU foam
Optimal
N-heptane
Optimal
Very suitable
Cooking equipment
Welding, cutting, and industrial processes
Chemical fumes
Dust
Engine exhaust
Vibration
Excessive airflow
Lightning and power outages
Lighting fixture and other electrical equipment that may emit noise/EMF
Radio frequency transmissions
Steam and moisture
27
Detector placement
Up to 72 in. (1.83 m)
One additional detector for each full 24 in. (610 mm) of duct
opening
[1] Duct size is the greater of the width (horizontal dimension) or depth (vertical dimension)
Figure 16: Smoke detector spacing in return ducts
72 in. (1.83 m) max.
W/2
36 in.
(910 mm)
max.
W/4
D/2
W/4
D/2
72 in. (1.83 m)
36 in.
(910 mm)
max.
18 in.
(460 mm)
max.
18 in.
(460 mm)
max.
D/2
W Width
D Depth
28
Smoke detector
D/2
1
2
1. Electrical box
2. Detector
Install the SIGA-DMP in ducts that have a maximum width and maximum height
of 36 in. (910 mm).
29
SIGA-PS, SIGA-PHS
SIGA2-PS, SIGA2-PHS,
SIGA2-PHSB
SIGA-IPHS, SIGA-IPHSB
There are three possible installation configurations for the SIGA-DMP. Refer to
Figure 19 on page 31.
Option 1: Installing the SIGA-DMP to a remote LED
When mounting the SIGA-DMP in an easily accessible, clearly visible location on
the air duct, use a remote LED (model SIGA-LED) to mount the SIGA-DMP and
to indicate Normal and Alarm conditions of the smoke detector.
Option 2: Installing the SIGA-DMP to a remote relay module
When mounting the SIGA-DMP on a control relay module (model SIGA-CR), use
a remote LED (model SIGA-LED) to provide indication of normal and alarm
conditions of the smoke detector.
Option 3: Mounting the SIGA-DMP to a blank cover
When using the SIGA-LED at a remote location to provide indication of normal
and alarm conditions of the smoke detector, install a blank cover plate on the
SIGA-DMP.
30
6
4
If the distance between doorways exceeds 24 in. (610 mm), treat each
doorway separately.
Treat each group of doorway openings with an overall width greater than
20 ft. (6.1 m) as separate.
For additional information and detector location requirement for single and
double doors, see NFPA 72.
31
CO detector applications
The Signature Series Carbon Monoxide (CO) detector is an intelligent analog
device that uses a CO sensor to detect carbon monoxide. The detector then
analyzes the sensor data to determine when to initiate a life safety CO alarm. For
model numbers and descriptions, see Table 1 on page 1.
The CO detectors have the following features.
Carbon monoxide sensor. The CO sensor is designed to detect carbon
monoxide gas from any source of combustion. It is not intended to detect fire,
smoke, or any other gas.
The detector analyzes the air every eight seconds and sends a signal to the
FACP when the concentration of CO and the time of CO exposure produces
above 5% COHb (the concentration of CO in the human body,
carboxyhemoglobin), as set forth in UL 2075 and CAN/CSA-6.19-01.
LED indicator. The LED indicator displays the following states:
Stand-alone alarm: red LED indicator glows continuously; evacuate the area.
32
CO information
WARNINGS
This product is intended for use in ordinary indoor locations of family living
units. It is not designed to comply with commercial or industrial standards
such as the Occupational Safety and Health Administration (OSHA).
The detector only indicates the presence of CO gas at the detector. Carbon
monoxide gas may be present in other areas.
To reduce the risk of CO poisoning, test the detector operation when not in
use for 10 days or more.
This detector does not operate without electrical power. As fires frequently
cause power interruption, discuss further safeguards with the authority having
jurisdiction (AHJ).
Notes
Alarm time
30 3 PPM
70 5 PPM
60 to 240 Minutes
150 5 PPM
10 to 50 Minutes
400 10 PPM
4 to 15 Minutes
33
Symptoms of CO poisoning
The following symptoms related to CO poisoning should be discussed with all
occupants of the protected site.
Mild exposure: Slight headache, nausea, vomiting, fatigue (often described as
"flu-like" symptoms).
Medium exposure: Severe throbbing headache, drowsiness, confusion, fast heart
rate.
Extreme exposure: Unconsciousness, convulsions, cardiorespiratory failure,
death.
Many cases of reported CO poisoning indicate that while victims are aware they
are not well, they become so disoriented that they are unable to save themselves
by either exiting the building or calling for assistance. Young children and pets
may be the first affected.
CO sources
The CO sensor in this detector is designed to detect carbon monoxide gas from
any source of combustion. It is not intended to detect fire, smoke, or any other
gas. Potential CO sources include fuel-fired appliances (e.g., space heater,
furnace, water heater, range, oven, clothes dryer); other sources of combustion
(e.g., kerosene-burning stove or heater, or gas log fireplace); or internal
combustion engines.
In addition, excessive exhaust spillage or reverse venting of fuel-burning
appliances can produce dangerous transient levels of CO. This can be caused by
external conditions:
Temperature inversions that can trap exhaust gases near the ground
Vent pipe connections vibrating loose from dryers, furnaces, or water heaters
34
Clean all chimneys, flues, and vents annually. Keep them free of debris and
check for blockage, corrosion, rust, and cracks.
Ensure that exhaust and ventilation fans and fireplaces do not interfere with
the air supply to a furnace.
35
Installing CO detectors
WARNINGS
Use only with UL/ULC Listed control panels capable of differentiating between
alarm signals (fire, burglary, CO, etc.) and providing distinct identification for
each.
The CO detector does not operate without electrical power. As fires frequently
cause power interruption, discuss further safeguards with the local fire
protection specialist.
The CO detector by itself does not provide smoke or fire protection; use with
ionization detectors, photoelectric smoke detectors, or both.
The CO detector does not detect oxygen levels, smoke or flames. Use this
device as part of a broad-based life safety program which includes a variety
of information sources pertaining to heat and smoke levels, extinguishment
systems, visual and audible devices, and other safety measures.
Notes
Install per UL 2075 Standard for Gas and Vapor Detectors and Sensors,
NFPA 720 Standard for the Installation of Carbon Monoxide (CO) Detection
and Warning Equipment, and applicable codes and the local authority having
jurisdiction.
Do not install the CO detectors until after final construction cleanup (unless
otherwise specified by the AHJ).
The dust cover (supplied) must remain on the detector during installation.
Temporarily remove it for commissioning and replace it until just prior to
placing it into service. The dust cover is not a substitute for removing the
detector during new construction or heavy remodeling.
36
In a typical installation, place the junction boxes in the ceiling, and run the wires
from the panel to the junction box in conduit. Run the wires from the junction box
to a compatible detector base per the installation instructions for the base.
All wiring must conform to the requirements of the NFPA 70 National Electrical
Code, CSA C22.1 Canadian Electrical Code, Part 1, the applicable local codes,
and the authority having jurisdiction.
Note: Where required, to permanently disable the tamper-resist mechanism prior
to placing the detector in difficult to reach locations, break and remove the plastic
lever arm from the base.
37
Detectors required
One ceiling-mounted
detector on each side
or one wall-mounted
detector on each side
D1
5 ft. max.
(1.52 m)
Min. = 12 in.
One ceiling-mounted
detector on higher side
or one wall -mounted
detector on each side
D2
D
D1
5 ft. max.
(1.52 m max.)
Min. = D
D1
5 ft. max.
1.52 m max.
Min=D
5 ft. max.
1.52 m max.
Min=D
38
Sensitivity readings
The control system to which these detectors are connected is capable of
interrogating each detector to determine its sensitivity. The system can provide a
hardcopy of the results of sensitivity testing if a printer is installed. Table 17
below lists the acceptable smoke and heat ranges of sensitivity for SIGA smoke
and heat detectors. Table 17 below lists the acceptable smoke, heat, and CO
ranges of sensitivity for SIGA2 detectors.
Table 17: Acceptable sensitivity ranges for SIGA detectors as reported by the control
panel
Model
Detection elements
Factory-assigned
sensitivity
SIGA-IS
Ionization
1.6% obsc./ft.
SIGA-PS
Photoelectric
3.5% obsc./ft.
SIGA-PHS
Photoelectric
Fixed temperature
3.5% obsc./ft.
135F (57C)
SIGA-IPHS,
SIGA-IPHSB
Ionization, photoelectric,
Above ambient
temperature
3.5% obsc./ft.
65F (35C)
SIGA-HFS
Fixed-temperature
135F (57C)
N/A
SIGA-HRS
Rate-of-rise or
Fixed-temperature
15F/minute or
135F (57C)
N/A
[1] Settings listed in the following sequence: most, more, medium, less, least.
Notes
The prealarm points available depend on the panel with which these are used.
The prealarm actual % per foot obscuration depends on the settings for the
sensitivity level and the prealarm level.
On EST3 and QuickStart panels:
39
Table 18: Acceptable sensitivity ranges for SIGA2 detectors as reported by the control
panel
Model
Detection elements
Factory-assigned
sensitivity
SIGA2-COS
SIGA2-COS-CA
CO
70 ppm 60 to 240
minutes
N/A
SIGA2-HCOS
SIGA2-HCOS -CA
Rate-of-rise or
Fixed temperature
CO
15F/minute or
135F (57C)
70 ppm 60 to 240
minutes
N/A
SIGA2-HFS
Fixed temperature
135F (57C)
N/A
SIGA2-HRS
Rate-of-rise or
Fixed temperature
15F/minute or
135F (57C)
N/A
SIGA2-PCOS
SIGA2-PCOS-CA
Photoelectric
CO
3.5% obsc./ft.
70 ppm 60 to 240
minutes
SIGA2-PHCOS
SIGA2-PHCOS-CA
Photoelectric
Fixed temperature
CO
3.5% obsc./ft.
135F (57C)
70 ppm 60 to 240
minutes
SIGA2-PHS(B)
Photoelectric
Fixed temperature
3.5% obsc./ft.
135F (57C)
SIGA2-PS
Photoelectric
3.5% obsc./ft.
[1] Settings listed in the following sequence: most, more, medium, less, least.
40
41
3. If wired for Class A operation, verify that the detector continues to operate
first with SLC_IN disconnected, and then with SLC_OUT disconnected.
(Refer to the installation sheet for the base.)
4. Place a momentary ground fault on the signaling line circuit (SLC) to verify
operation of ground fault detection circuitry.
5. Run a system detector sensitivity report on all detectors and verify that
readings fall within acceptable limits.
6. Perform a sensor function test as described in SIGA2 sensor function test
procedures on page 45.
Routine maintenance
Detectors shall be tested on a routine basis satisfactory with the authority having
jurisdiction, typically once every 6 months.
To perform routine SIGA maintenance:
1. Verify detector operation, wiring integrity, and control panel operation
sequences specific to that detector, if any.
2. Activate smoke detectors using a chemical smoke aerosol spray (Smoke
Tester by Home Safeguard, Inc. is recommended) or smoke generator.
3. Activate rate-of-rise heat detectors using a heat gun.
4. Run a system detector sensitivity report on all detectors and verify that
readings fall within acceptable limits. Clean detectors that are too close to the
alarm threshold according to the Detector cleaning procedures on page 46.
To perform routine SIGA2 maintenance:
1. Verify detector operation, wiring integrity, and control panel operation
sequences specific to that detector, if any.
2. Perform a sensor function test on each sensor as described in SIGA2 sensor
function test procedures on page 45.
3. Run a system detector sensitivity report on all detectors and verify that
readings fall within acceptable limits. Clean detectors that are too close to the
alarm threshold according to the Detector cleaning procedures on page 46.
42
Testing
interval
Sensor
Testing procedure
SIGA-HFS,
SIGA-HRS
Semiannually
Heat
SIGA-IS
SIGA-PS,
SIGA-PHS,
SIGA-IPHS,
SIGA-IPHSB
Annually
Smoke
43
Table 20: SIGA2 recommended preventive maintenance and conventional test schedule
Model
Testing interval
SIGA2-COS
SIGA2-COS-CA
SIGA2-HCOS
SIGA2-HCOS-CA
SIGA2-PCOS
SIGA2-PCOS-CA
SIGA2-PHCOS
SIGA2-PHCOS-CA
Monthly (until
CO
January, 2012 when
it becomes an
annual test)
SIGA2-HFS
Semi-annually
SIGA2-HRS
SIGA2-HCOS
SIGA2-HCOS-CA
SIGA2-PCOS
SIGA2-PCOS-CA
SIGA2-PHCOS
SIGA2-PHCOS-CA
SIGA2-COS
Annually
SIGA2-COS-CA
(Starting January,
SIGA2-HCOS
2012)
SIGA2-HCOS-CA
SIGA2-PCOS
SIGA2-PCOS-CA
SIGA2-PHCOS
SIGA2-PHCOS-CA
CO
SIGA2-PS
SIGA2-PHS,
SIGA2-PHSB
Annually
CO
Replace CO sensor.
[1] Testing procedure as described in SIGA2 sensor function test procedures on page 45
44
45
SIGA2 detectors require opening the detector and cleaning the interior using
a vacuum cleaner and a soft brush as instructed below.
Note: In order to avoid false alarms, disable the detector being cleaned before
cleaning.
To clean the SIGA detector:
1. Disable the detector to prevent false alarms.
2. Use the conventional vacuum cleaner brush attachment to remove any visible
cobwebs etc. from the immediate area of the detector.
3. Connect the detector cleaning tool to the suction hose. See Figure 20 on
page 47.
4. Place the detector cleaning tool over the detector head for approximately one
minute.
5. After the detector has been cleaned, use the SIGA-PRO Signature
Program/Service Tool to change the maintenance date and thereby
automatically update the dirtiness level at the control panel.
Without using the SIGA-PRO Signature Program/Service Tool, it is not
possible to immediately verify the dirtiness levels after cleaning. In this case,
operate the detectors for a minimum of two hours, and then restart the loop
controller. If the detectors are cleaned properly, the maintenance indicators
return to normal condition.
6. Run the detector sensitivity routine to print a list of detector sensitivity and
compensation readings and to verify the effectiveness of the cleaning.
46
47
1.
2.
3.
4.
Mounting base
Detector base
CO sensor module (on CO detectors only)
Smoke chamber: to remove see Figure 24
on page 51
5.
6.
7.
8.
CO maintenance reports
The CO sensor module has a life span of 6 years. After 6 years, the detector
sends out an end-of-life trouble message. When this trouble message is
transmitted, replace the CO sensor module. For instructions on how to field
replace the CO sensor module, see CO sensor module on page 51.
To determine the months until end of life, request a Maintenance Report. See
Figure 22 on page 49.
48
CO maintenance alert
In addition to displaying a maintenance alert message when the photo element
dirtiness is at or above 80%, the loop controller displays a maintenance alert
when the CO sensor module is at or below 6 months until end of life. If both
elements are at or beyond these thresholds, there is only one maintenance alert.
Once the dirtiness threshold is at 100%, a dirty detector trouble message
displays for the photo element. Once there are 0 months until end of life, the
panel displays the end-of-life trouble. See CO sensor module on page 51.
49
2-SPRC1
2-SPRC2
50
1
1
2
2
1. Pry locator
CO sensor module
2-CORPL is the replacement sensor for the Signature Series CO detectors listed
in Table 22 on page 52. Replace the CO sensor module every six years or when
the control panel indicates a sensor end-of-life condition, whichever comes first.
Refer to installation sheet P/N 3101589.
Note: For proper operation, never replace the CO sensor itself without the PCB
as each board has calibration data specific to the CO sensor.
51
Name
SIGA2-COS, SIGA2-COS-CA
CO Detector
SIGA2-HCOS, SIGA2-HCOS-CA
SIGA2-PCOS, SIGA2-PCOS-CA
Use Figure 21 through Figure 25 and the instructions below to remove and
replace the sensor.
To remove the CO sensor module:
1. Remove the detector from the detector base by inserting a small screwdriver
into the tamper-resist access slot while rotating the detector
counterclockwise. See Figure 21 on page 48.
2. Push the releasing tab on the bottom of the detector toward the center, and
then twist and pull to remove the cover. See Figure 23.
3. Remove the smoke chamber or inner chamber by locating the pry indicator,
inserting a screwdriver into the pry locations and gently prying the chamber
up. See Figure 24 on page 51.
4. Lift the existing CO sensor module to remove. Do not pull on the CO sensor.
See Figure 25.
Caution: This product contains components that are sensitive to static electricity.
Use approved handling precautions to prevent damage from electrostatic
discharge.
To replace the CO sensor module:
1. Using ESD precautions, remove the replacement 2-CORPL module from its
packaging and replace the removed module.
2. If applicable, line up the smoke chamber over the CO sensor. Push the
smoke chamber down over the CO sensor until it seats into position.
3. Align the cover slots with the tabs on the detector and twist to lock.
4. Connect the detector to the detector base by rotating the detector clockwise
until it snaps into the locked position.
5. Verify that the green LED illuminates.
6. After replacing the CO sensor module, perform the CO sensor function test
required. See SIGA2 sensor function test procedures on page 45.
52
2
3
A.
B.
1.
2.
3.
4.
53
54