Contents
Page
1 Introduction
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
Measurement Capabilities
Maximum Power
Secondary Voltage
Demand Calculation.
RS485 Serial Option
Pulse Output Option
Analogue Output Option (R )
Lonworks Option
Profibus Option
4
5
5
5
6
6
6
6
6
6
Introduction
RS485 Baud Rate
RS485 Parity / stop bits Selection
RS485 Modbus , JC N2 or Profibus Address
7
7
7
7
7
Introduction
Analogue set up features
Analogue Output Scaling Example
Power Factor
Phase Angle
Parameters available for analogue outputs
8
8
10
11
12
15
16
17
17
17
17
17
18
18
18
2 Communications set up
2.1
2.2
2.3
2.3.1
4 Serial Communications
4.1
4.2
4.3
4.4
4.5
4.6
4.7
19
20
21
Phase to Phase voltages on 4 wire and single phase 3 wire 21
Reactive and Apparent Power
21
Energy resolution
21
Power Factor
21
Maximum Demand
21
Total Harmonic Distortion
22
Contents
Page
8 Specification
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
8.9
8.10
8.11
8.12
Inputs
Auxiliary
Measuring Ranges
Accuracy
Reference conditions of influence quantities
Range of Use
Standards
Insulation
Environmental
RS485 Serial Communications Option
Active Energy Pulsed Output Option
Analogue Outputs Option
23
23
23
23
24
24
24
25
25
25
25
25
26
27
30
30
30
30
31
31
31
32
33
10.1
10.2
10.2.1
10.2.2
10.2.3
10.2.4
10.2.5
10.2.6
Auxiliary Supply
Output Connections
RS 485 and relay outputs
Relay connections
RS485 or additional display
Analogue or Analogue and RS485 options
LON option
Profibus Interface
34
34
34
35
35
35
35
35
35
35
36
37
38
1. Introduction
The Crompton Integra 1560/1580 is a measuring and communication instrument available with
digital, analogue or LED display interfaces. Typically, it is used in conjunction with an Integra
display unit. When a permanent display is not required, the display can be temporarily
connected for set up and system commissioning, and then disconnected. The Integra
configuration software tool running on a Windows platform may also be used for set-up. RS485
communications ports can be connected to a display or to a Modbus master. One RS485
communications port also supports Johnson Controls N2 protocol. Options include LonWorks
and Profibus interfaces.
The Integra 1560/1580 will measure and communicate many electrical parameters, including
THD values. All voltage and current measurements are RMS calculated for accurate
measurement of non sinusoidal waveforms. An option is available for metered neutral current.
Not all configurations and options described in this manual may be immediately available.
Contact your supplier for details of availability.
The Integra is available with either DIN rail or surface mounting options.
System
Single Phase 2 Wire
Single Phase 3 Wire
3 Phase 3 Wire
3 Phase 4 Wire
3 Phase 4 Wire with metered neutral
Surface Mounting
Model No.
INT-1581
INT-1582
INT-1583
INT-1584
INT-1585
The set up of the Integra 1560/1580 may be carried out by using the Crompton Integra display
unit or Integra configuration software the relevant user documentation gives more information
on :
Configuring for use with installed current transformers
Setting Potential Transformer / Voltage Transformer ratios, where required
Demand Integration Time
Resetting demand and energy
Pulsed output set up
Communications (RS485) set up
Analogue output set up
Password protection of set up screens to prevent accidental modification
If required, most set up parameters may also be manipulated directly via the Modbus interface.
If required, set up parameters may be manipulated directly via the Modbus interface. The
Integra can be powered from an auxiliary a.c. or d.c. supply that is separate from the metered
supply. Versions are available to suit 100-250V 50-60 Hz a.c./d.c. and 12-48V d.c supplies.
Some models have a black top cover. These products omit some features available on models
with red translucent top cover. Where appropriate, these features will be indicated in this
document with an symbol. The 1565/1585 is always configured with a red top cover. When
powered, a low power red light source will be visible through the back cover.
Modbus, Lonworks and Profibus are trademarks of their respective owners. All trademarks are
acknowledged.
Interfaces include:
The Analogue outputs provide a current output that indicates the value of a chosen parameter.
Not all options may be fitted to the same unit. Pre sales literature indicates valid option
combinations and ordering codes.
Connections for all interfaces are via detachable two-part screw clamp connectors, except
Profibus which provides a conventional 9 pin interface.
2 Communications set up
2.1 Introduction
Modbus, JC N2, LonWorks and Profibus communication options all require specific set up of the
internal communication parameters.
The table summarises these settings
Protocol
Baud Rate
(k baud)
Address
Notes
Modbus
JCN2
LonWorks
Profibus
Integra Display
Match network *
9.6
19.2
Do Not Change
Automatic
Match Network *
No 1
No 2
Do Not Change
Automatic
1-247
1-247
1
1-125
Automatic
* These parameters should be set to match the communications parameters of the associated
network.
For channel 1
For Channel 2
A1r
A1rt
A1rb
A1ot
A1ob
A2r
A2rt
A2rb
A2ot
A2ob
The example shows the set-up for the first analogue channel. Set-up of the second analogue
output is identical except that the screens indications are as above. At the end of the set up for
the second analogue output pressing >> will exit the set up system and enter A2rb - Reading
Bottom.
It is recommended that a 3 or 4 output unit be set up with Integra configuration software,
however setting up can be performed with a display unit only, with some limitations. Only
channels 1 and 2 may be directly set, and channels 3 and 4 are automatically configured as
detailed in the autoconfiguration section below.
3.1.1.2 Autoconfiguration on 3 channel analogue output 1563 and 1564
For a 3 output unit, if the lead channel is set to phase 1 of a measurement that is available for
all three phases, the follower channels are set up identically, including reading top, reading
bottom, output top and output bottom, their outputs corresponding to phase 2 and 3 of that
parameter. For a 3 output Integra, channel 1 is the lead channel and 2 and 3 follow.
For 1564
If channel 1 set to
V1
I1
kW1
kVA1
kvar1
Power Factor 1
Phase Angle 1
VL1-2
THD V1
THD I1
Anything else
Then 2 is set to
V2
I2
kW2
kVA2
kvar2
Power Factor 2
Phase Angle 2
VL2-3
THD V2
THD I2
kW, 0 to max kW range
V3
I3
kW3
kVA3
kvar3
Power Factor 3
Phase Angle 3
VL3-1
THD V3
THD I3
Kvar, 0 to max kvar range
INT 1560/1580 Issue 2.5
For 1563
If channel 1 set to
I1
VL1-2
THD V1
THD I1
Anything else
Then 2 is set to
I2
VL2-3
THD V2
THD I2
kW, 0 to max kW range
I3
VL3-1
THD V3
THD I3
Kvar, 0 to max kvar range
For example, if channel 1 is set to I1, reading bottom to 200A and reading top to 300A, channels
2 and 3 will be set to represent current phases 2 and 3 respectively with the same span and
offset as channel 1.
For 1564
If channel 2 set to
V1
I1
kW1
kVA1
kvar1
Power Factor 1
Phase Angle 1
VL1-2
THD V1
THD I1
Anything else
For 1563
If channel 2 set to
I1
VL1-2
THD V1
THD I1
Anything else
For example, if channel 2 is set to I1, reading bottom to 200A and reading top to 300A, channels
3 and 4 will be set to represent current phases 2 and 3 respectively with the same span and
offset as channel 1.
10
3.1.3.4 Output
The two output values specify the analogue current outputs that will represent the top and
bottom reading values. They are included to allow a 0-20mA output to be converted to 4-20mA
and to permit additional versatility where particular requirements prevail. However it is
suggested that, in most cases, these values should be set to the limits that the hardware can
cover. The range of the analogue output(s) for a particular unit is marked on the product label.
Power factor
The polarity of the power factor reading in the diagram above indicates the direction of active
power flow:
Positive PF relates to imported active power
Negative PF relates to exported active power.
When setting up the analogue output for a power factor reading, the Reading Top value must be
in one of the left-hand quadrants and the Reading Bottom value must be in one of the righthand quadrants. The analogue output range will always include unity PF (=1).
Hence, if the Reading Top value is set to 0.5, this will be a power factor of 0.5 for power
exported to an inductive load (bottom left-hand quadrant). If a Reading Bottom value of 0.5 is
specified, this will represent a power factor of 0.5 for power exported to a capacitive load
(bottom right-hand quadrant). As a power factor of +1 (for true power imported to a resistive
load) is always included in the analogue output range, the output would span 0.5 export
inductive to 0.5 export capacitive.
12
In specifying the Output Top and Output Bottom values, there are two conventions one for
European areas of influence and one for North American areas. The two conventions are:
Europe
USA
The examples below show cases where power is only imported and the load may be either
capacitive or inductive. The Reading Top and Reading Bottom values of zero ensure that the
whole range of possible (import) power factor readings is covered. The unit in the left-hand
example has an analogue output range of +1 to 1 mA and, since the Output Top value (+1 mA)
is more positive than the Output Bottom value (-1 mA), this arrangement complies with the
European convention. The right-hand example shows the North American convention.
European convention
13
European convention
In the example above, the unit has an analogue output range of 0 to 1 mA, all power is imported
and the load is inductive. The 1 mA Output range covers a reading power factor range of 0.6,
from 0.9 capacitive to 0.5 inductive. The Output to Reading correlation is as follows:
Reading
0.9 Pf
1 Pf
0.9 Pf
0.8 Pf
0.7 Pf
0.6 Pf
0.5 Pf
0 mA
0.167 mA
0.333 mA
0.500 mA
0.667 mA
0.833 mA
1 mA
1 mA
0.833 mA
0.667 mA
0.500 mA
0.333 mA
0.167 mA
0 mA
cap.
ind.
ind.
ind.
ind.
ind.
14
European convention
15
3
4 wire
3
3 wire
1
3 wire
1
2 wire
+/-
16
4 Serial Communications
4.1 Port 1 Display, Modbus or JC N2
RS485 Integra 1560/1580 digital transducers have fitted as standard one communications port.
This port can be used for either the Integra display unit, as an RS485 Modbus RTU port, or as a
Johnson Controls N2 protocol slave. Choice of reply protocol is made by the Integra on the
basis of the format of request, so that a Modbus request receives a Modbus reply, and an N2
protocol request receives an N2 protocol reply.
17
18
19
Range
Load
Compliance Voltage
0/20mA
-1/0/+1mA
0-500
0-10k
10V
10V
Parameters can be adjusted to suit the application and are not fixed to the system value. Top
and bottom readings can be adjusted and a variety of outputs achieved, for example:-
Example
Mode
0kW
50kW
100kW
Normal
Inverse
Offset
Live
0mA
1mA
0
4mA
0.5mA
0.5mA
0
12mA
1mA
0
1mA
20mA
More details of analogue output set-up are contained in section 3 of this document, the
1560/1580 Modbus guide and the Integra configurator software user guide.
20
22
8 Specification
8.1 Inputs
Nominal rated input voltage
Voltage range L
Voltage range M
57 - 139V L-N
57 - 139V L-N (114 - 278V L-L)
100 - 240V L-L
100 - 240V L-L (57 - 139V L-N)
Voltages above are expressed as RMS values and relate to sinusoidal waveforms and
corresponding instantaneous peak values. "Range Maximum" for a particular instrument refers
to the upper end of the relevant voltage range.
Max continuous input voltage
120% of range maximum.
Max short duration input voltage
2* range maximum (1s application repeated 10 times at
0s intervals)
Nominal input voltage burden
0.2VA approx. per phase
Nominal input current
1 or 5A a.c. rms
System CT primary values
Integer values up to 9999A (1 or 5 Amp secondaries)
System VT ratios
Any value up to 400kV(subject to an overall power limit
of 250 MW nominal, 360MW maximum and the 4
significant digit limitation of the display unit, where this
is used for setup)
Max continuous input current
120% of nominal
Max short duration current input
20* nominal (1s application repeated 5 times at 5 min
intervals)
Nominal input current burden
0.6VA approx. per phase
8.2 Auxiliary
Standard supply voltage
23
8.4 Accuracy
Voltage
Current
Neutral current (calculated)
Neutral current (1565/1585 only)
Frequency
Power factor
Active power (W)
Reactive power (var)
Apparent power (VA)
Active energy (Wh)
Reactive energy (varh)
Total Harmonic Distortion
Temperature coefficient
0.018%/C W, var, VA typical
Response time to step input
24
Current
0.1 .. 120% of nominal
Frequency
45 .. 66 Hz
Power Factor
1 .. 0 leading or lagging
Active power (Watt)
1 .. 144% of nominal, 360MW Max
Reactive power (var)
1 .. 144% of nominal, 360Mvar Max
Apparent power (VA)
1 .. 144% of nominal, 360MVA Max
Harmonic distortion (voltage)
Max 40% THD up to 31st harmonic
Power is only registered when voltage and current are within their respective range of use.
Power Factor is only indicated when the measured VA is over 3% of Range Maximum.
Voltage THD is only indicated when the measured voltage is over 5% of Range Maximum, and
full accuracy only when measured voltage >25% of Range Maximum.
Current THD is only registered when the measured current is over 5% of nominal, and full
accuracy only when measured current is over 20% of nominal
8.7 Standards
Terms, Definitions and Test Methods
EMC Emissions
EMC Immunity
Safety
8.8 Insulation
CT primary to voltage circuits
Relay contact to voltage circuits
RS485 to voltage circuits
Analogue to voltage circuits
Auxiliary supply to voltage circuits
CT primary to CT primary
8.9 Environmental
Operating temperature
Storage temperature
Relative humidity
Warm up time
Shock
Vibration
-20 to +60C *
-30 to +80C *
0 .. 90% non condensing
1 minute
30g in 3 planes
10 .. 15 Hz, 1.5mm amplitude peak to peak,
15Hz to 150 Hz @ 1g
* Maximum operating and storage temperatures are in the context of typical daily and seasonal
variation. This product is not designed for permanent operation or long term storage at
maximum specified temperatures.
25
Pulse duration
Pulse rate
Accuracy
Temperature coefficient
Over range
26
USA Style
27
USA Style
SINGLE-PHASE - 2 WIRE
SINGLE-PHASE - 2 WIRE
28
USA Style
SINGLE-PHASE - 3 WIRE
SINGLE-PHASE - 3 WIRE
29
12-48V
negative
100-250V
AC or DC
L+
12-48V
Positive
It is recommended that if used with a remote Integra display, a common auxiliary supply is used
for both the display and Integra. If this arrangement is not implemented then the Integra
communications parameters may be configured as detailed in the preceding section 4.3, Display
auto detect. The Integra establishes contact with a remote display in the first 5 seconds after
power up, and may not operate correctly with the display if the display is powered several
seconds after the Integra is powered, unless the communications parameters are set
appropriately.
30
Note that the return( ve) terminal for analogue outputs is common amongst all analogue
channels. The analogue return is galvanically isolated from the RS485 ground.
The polarity indicated above is correct for positive designated currents. On 1 .. 0 .. +1 mA
outputs, polarity will be reversed when the relevant parameter is below half scale. On purely
positive going configured outputs (0..20mA), it is possible that a small reverse current may be
registered when the input parameter is below reading bottom. If the application cannot tolerate
such reverse currents, fitting of an external silicon diode is suggested.
31
The service LED provides basic diagnostic information for the LON interface:
Continuously on
Continuously off
Single 1 second flash, 2 seconds off
and then continuously on after
applying auxiliary power
Repeated 1 second on followed by
2 second off
All of the above problems (with the exception of no auxiliary power) require service attention to
the Integra LON interface.
Repeated 1 second on, 1 second off
flashing
Brief flash on, off for 6 seconds,
and then continuously on
32
33
Warning
During normal operation, voltages hazardous to life may be present at some of the terminals of
this unit. Installation and servicing should be performed only by qualified, properly trained
personnel abiding by local regulations. Ensure all supplies are de-energised before attempting
connection or other procedures.
It is recommended adjustments be made with the supplies de-energised, but if this is not
possible, then extreme caution should be exercised.
Terminals should not be user accessible after installation and external installation provisions
must be sufficient to prevent hazards under fault conditions.
This unit is not intended to function as part of a system providing the sole means of fault
protection - good engineering practice dictates that any critical function be protected by at least
two independent and diverse means.
Never open circuit the secondary winding of an energised current transformer.
Auxiliary circuits (12-48V auxiliary, communications, relay and analogue outputs, where
applicable) are separated from metering inputs and 100-250V auxiliary circuits by at least basic
insulation. Such auxiliary circuit terminals are only suitable for connection to equipment which
has no user accessible live parts. The insulation for such auxiliary circuits must be rated for the
highest voltage connected to the instrument and suitable for single fault condition. The
connection at the remote end of such auxiliary circuits should not be accessible in normal use.
Depending on application, equipment connected to auxiliary circuits may vary widely. The
choice of connected equipment or combination of equipment should not diminish the level of
user protection specified.
This unit is not intended to provide safety rated isolation between the 12-48V auxiliary terminals
and communications or analogue output circuits. Galvanic isolation is provided, but one of the
12-48V inputs should be at or near earth potential.
The auxiliary supply to the unit should not be subject to excessive interference. In some
cases, a supply line filter may be required.
To protect the product against incorrect operation or permanent damage, surge transients
must be controlled. It is good EMC practice to suppress differential surges to 2kV or less at
the source. The unit has been designed to automatically recover from typical transients,
however in extreme circumstances it may be necessary to temporarily disconnect the
auxiliary supply for a period of greater than 5 seconds to restore correct operation.
Screened communication and small signal leads are recommended and may be required.
These and other connecting leads may require the fitting of RF suppression components,
such as ferrite absorbers, line filters etc., if RF fields cause problems.
INT 1560/1580 Issue 2.5
34
It is good practice to install sensitive electronic instruments that are performing critical
functions in EMC enclosures that protect against electrical interference causing a
disturbance in function.
35
11.5 Maintenance
The case should be wiped with a dry cloth only. If a cleaning agent is necessary, isopropyl
alcohol is the only recommended agent and should be used sparingly. Water should not be
used. If the case exterior or terminals should accidentally be contaminated with water, the unit
must be thoroughly dried before further service. Should it be suspected that water or other
contaminants might have entered the unit, factory inspection and refurbishment is
recommended.
In normal use, little maintenance is needed. As appropriate for service conditions, isolate
electrical power, inspect the unit and remove any dust or other foreign material present.
Periodically check all connections for freedom from corrosion and screw tightness, particularly if
vibration is present.
The front display window also acts as an insulating barrier. It is not possible to touch, by hand,
any live part, even if the window is completely missing, but if the window is perforated or
significantly damaged in any other way, repair is required.
In the unlikely event of a repair being necessary, it is recommended that the unit be returned to
the factory or nearest Crompton service centre.
36
37
38
About TE Connectivity
While TE has made every reasonable effort to ensure the accuracy of the information in this catalog, TE does not guarantee that it is error-free,
nor does TE make any other representation, warranty or guarantee that the information is accurate, correct, reliable or current. TE reserves the
right to make any adjustments to the information contained herein at any time without notice. TE expressly disclaims all implied warranties
regarding the information contained herein, including, but not limited to, any implied warranties of merchantability or fitness for a particular
purpose. The dimensions in this catalog are for reference purposes only and are subject to change without notice. Specifications are subject to
change without notice. Consult TE for the latest dimensions and design specifications. TE connectivity (logo) and TE Connectivity are
trademarks of the TE Connectivity Ltd. family of companies. Crompton is a trademark of Crompton Parkinson and is used by TE Connectivity
Ltd. under a licence. Other logos, product and Company names mentioned herein may be trademarks of their respective owners.
TE Energy innovative and economical solutions for the electrical power industry: cable accessories, connectors & fittings, insulators &
insulation, surge arresters, switching equipment, street lighting, power measurement and control.