WPS100/S

EP Series

Features:

Rotate speed governor: Mechanical governor


Excitation system: self-excited
A.V.R model: R250/R438
Emergency stop switch
ATS (automatic transfer switch) receptacle
1x12V sealed for life maintenance free battery
Lockable battery isolator switch
Powder coated canopy
(Only for Soundproofed sets)
50radiator
Oil pump on the engine
Steel base frame with fork holes
Vibration isolators between the engine/alternator and
base frame
Dry type air filter
Base fuel tank for daily running
Drain points for fuel tank
Operation Manual / Specifications

Output Ratings
GeneratingSet
Model
WPS100
WPS100S

PrimePower*

StandbyPower**

100kVA/80kW
100kVA/80kW

110kVA/88kW
110kVA/88kW

Ratingsat0.8powerfactor

Dimensions and Weights

Ratings and Performance Data

Model
WPS100
WPS100S

Length (L)
mm

Width (W)
mm

Height (H)
mm

Dry Weight
kg

2317
3150

890
1150

1405
1700

1267
1852

Engine Make & Model:

Perkins 1104C-44TAG2

Alternator Brand:

Leroy somer

Alternator Model:

LSA44.2VS45

Control System:

Auto Gen

Circuit Breaker Type:

3 Pole MCCB

Frequency & Phase:

50Hz & 3PH

Engine Speed: RPM

1500

Notes:
***
*Prime
Power

Continuous
duty operation, under variable load 24/24h-10% over load

permissible
1 hour/12 hours;

**Standby
Power

Standby
duty, operation under variable load, without over load;

Fuel Tank Capacity: litres


WPS100
WPS100S
Fuel Consumption: l/hr
(100% Load)
- Prime Power
-Standby Power

Standard Reference Conditions

Note: Standard reference conditions 25C (77F) Air Inlet Temp, 100m(328

ft) A.S.L. 30% relative humidity.

Fuel
consumption data at full load with diesel fuel with specific gravity of

0.85
and conforming to BS2869: 1998, Class A2.

www.powerlinkworld.com

245
300

22.6
24.9

1/5

WPS100/S

EP Series

Engine model:1104C-44TAG2

EngineTechnicalData

No. of Cylinders / Alignment:

4 / In-line

Cycle:

4 Stroke

Bore / Stroke: mm

105/127

Induction:

Turbocharged

Cooling Method:

Water cooled

Governing Type:

Electronic

Governing Class:

ISO 8528, G3

Compression Ratio:
Displacement:

4.4L

Moment of Inertia: kg m

0.162

Weight: kg

- Dry
- Wet

Energy to Cooling Fan: kWm

12/Negative
12/65

3.5

401
N/A

165.6/165.6

External Restriction to
Cooling Airflow: Pa

N/A

Designed to operate in ambient conditions up to 50C (122F).


Contact your local PowerLink Dealer for power ratings at specific site
conditions

1500

FuelSystem

Fuel Filter Type: Replaceable Element

- Prime

93.6

- Standby

103

Recommended Fuel: Diesel Class A2


Fuel Consumption: l/hr

- Prime

1702

- Standby

1873

LubricationSystem

Oil Filter Type:


Total Oil Capacity: l
Minimum: l
Oil Type:
Oil Cooling Method:

Prime

110%
Load

100%
Load

75%
Load

50%
Load

WPS100

24.9

22.6

17.1

11.8

WPS100S

24.9

22.6

17.1

11.8

Spin-On, Full Flow


8.0
5.5
API-CC/SE or
CCMC-D1
Water

(Based on diesel fuel with a specific gravity of 0.85 and


conforming to BS2869,Class A2)

46.1
50.7

- Prime 6.8
- Standby 7.5

- Prime
- Standby

Energy to Radiator:
kWt

BMEP: kPa

7.0

kWt

12.6

Capacity without Radiator: l


Energy to Coolant and Lubricating Oil

Gross Engine Power: kW

Capacity with Radiator: l

Engine Speed: rpm

CoolingSystem

Radiator Cooling Airflow: m/min

Performance

18.23:1

Engine Electrical System:


- Voltage / Ground
- Battery Charger Amps

ExhaustSystem

AirSystems

Silencer Type:
Exhaust Outlet Size:

64mm

Silencer Noise Reduction Level:

N/A

Maximum Allowable Back


Pressure: kPa

18

Exhaust Gas Flow: m/min


- Prime
- Standby

15.2
16.3

Exhaust Gas Temperature: C


- Prime
- Standby

514
543

www.powerlinkworld.com

Air Filter Type:

Industrial

Combustion Air Flow: m/min


- Prime
- Standby
Max. Air Intake Restriction: kPa
-clean filter
-dirty filter

2 stage
cylonic/paper
element
6.01
6.27
5
8

The weights are approximate and without fuel.

2/5

WPS100/S

EP Series

Alternator model: LSA44.2VS45

Alternator Physical Data

Manufactured by:

Leroy somer

Model:

Overspeed: rpm

LSA44.2VS45

No. of Bearings:

Single

Insulation Class:

H
2/3

Wires:

12

Voltage Regulation: (Steady state)

AVR Model:

0.5%

<50

Wave Form IEC = THF:

<2%

Total Harmonic content LL/LN:

Noload<2%onload<2%

Radio Interference:

IP23
SHUNT,AREPOR
PMG
R250,R438

Excitation System:

2250min1

Wave Form NEMA = TIF:

Winding Pitch Code:

Ingress Protection Rating:

Alternator Operating Data

Radiant Heat: kW (Btu/min)

-WPS100

-WPS100S

Alternator

WPS100

Performance Data:

WPS100S

Data Item

194.4/227.9

194.4/227.9

0.35

0.35

362

362

14.1

14.1

Motor Starting
Capability* kVA
Short Circuit
Ratio** %
Reactances: Per Unit
Xd
X'd
X"d

8.5

8.5

Voltage Technical Data WPS100

Voltage

Prime:

kVA

Voltage Technical Data WPS100S

Standby:
kW

kVA

Voltage
kW

Prime:

kVA

Standby:
kW

kVA

kW

380/220V 105

84

110

88

380/220V

105

84

110

88

400/230V 105

84

110

88

400/230V

105

84

110

88

415/240V 105

84

110

88

415/240V

105

84

110

88

www.powerlinkworld.com

3/5

WPS100/S

EP Series

Control System

PLC-7420

FEATURES

Microprocessor control, with high


stability and

credibility .

Mains supply and generator operation monitoring.

Indicating operation status and fault conditions.

Multiple protections; multiple parameters


display,
such as pressure, temperature.

Manual and automatic work mode


selectable.

Real time clock for time and date


display, overall

runtime display, 99 log entries

.
Overall power output display.

Integral speed/frequency detecting,


telling status
of start, rated operation, overspeed.

Communication with PC via RS485


or RS232

interface, using MODBUS protocol.

Engine ECU is available.

Common USB cable is usable for parameter

configuration.

Multi-language is available.

PLC-920(Optional)

FEATURES

Parameter configuration via RS-232


serial

communication;

Log last 50 events & alarm information


with

measured values;

Statistics records;

Remote start/stop;

Speed sensing from alternator voltage or

magnetic pickup;

Configurable 3 inputs and 6 outputs;

ECU powers, ECU stop, STOP


or fuel solenoid

selection;

Automatic transfer switching control


and engine

control;

Adjustable start, load and stop timers.

www.powerlinkworld.com

4/5

WPS100/S

EP Series

Optional

Engine
Water Jacket
Preheater
Oil Preheater

z
z

Alternator
Winding Temperature
Measuring Instrument
Alternator Preheater
PMG
Anti-damp and
anti-corrosion
treatment
Anti-condensation
heater

z
z
z
z
z

LubricatingSystem
Oil with the
machine

GeneratorSet
z

Protection board from


hotness

z
z
z

ExhaustSystem
z

Tools with the


machine

FuelSystem

CoolingSystem
z
z

Front heat
protection
Coolant (-30C)

Low fuel level


alarm
Automatic fuel
feeding system
Fuel T-valves

Canopy
z

ControlSystem
z
z
z

Remote control
panel
PLC-920
ATS

Trailer

Voltages
z
z
z
z
z

415/240V
400/230V
380/220V
220/127V
200-115V

The following lists are optional by the needs of customers.

Minor Repair / 1000 hrs optional


No.

Part Name

Part No.

1
2

FuelFilter

26560201

Qty
6

Remark

OilFilter

2654407

AirFilter

26510380

BELT

2614B653

SEALROCKERBOXCOVER

3681A055

GASKETCYLINDERHEAD

3681E046

THERMOSTAT

4133L507

FRONTOILSEAL

2418F437

SEALREARENDOIL

2418F704

Local Distributor
If you have any question or inquiry, please contact
PowerLink sales organization or contact:
info@powerlinkworld.com
Specification may change without prior notice.
For more info, please contact PowerLink or your local
distributors.
EP Series/2013 1st Edition

www.powerlinkworld.com

5/5