You are on page 1of 4

Protection components

Characteristics :
pages 28301/2, 28301/3 and 28307/3
References :
page 28307/4
Scheme, dimensions :
page 28307/5

Measurement and control relays


3-phase supply control relays RM3-TR1
General

Functions

This multifunction device is designed to monitor the presence and rotational direction of the phases in a three-phase
supply, as well as overvoltage and undervoltage. Depending on the model, the detection thresholds are :
- fixed (0.9 Un and 1.1 Un), or
- adjustable (for threshold ranges see page 28307/4).
Applications
i Connection of moving equipment :
- site equipment (cranes, pumps, conveyors, etc.),
- agricultural equipment,
- refrigerated trucks.
i Protection of persons and equipment against the consequences of reverse running :
- lifting, handling, elevators, escalators, etc.

Presentation
RM3-TR1
Width 45 mm

Te RM3 TR1

Time delay function selector :


Fault detection delayed.
Fault detection extended.
2 Potentiometer for setting time delay in seconds.
R Yellow LED : indicates relay state.
U Green LED : indicates that supply to the RM3 is on.
> U Red LED : overvoltage fault.
< U Red LED : undervoltage fault.
P Red LED : phase failure or incorrect rotational direction of phases.
Following items only applicable to models with
adjustable threshold (RM3-TR110, 112 and 114) :

A1 A2
16
15 18
26
25 28

1
2
>U

<U

Overvoltage adjustment potentiometer

Undervoltage adjustment potentiometer

Operating principles
The control circuit supply voltage is applied to terminals A1-A2.
Monitoring of the 3-phase supply is performed on terminals L1, L2, L3.
In normal operation, the output relay is energised, the yellow LED is on.
The output relay is de-energised and the yellow LED goes out if the following faults are detected :
i Overvoltage or undervoltage
If the voltage being monitored goes outside the range of Un, the output relay is de-energised :
- overvoltage : the red LED > U illuminates,
- undervoltage : the red LED < U illuminates.
When the supply returns to its rated value, the relay is re-energised according to the hysteresis value (5 %) and the
corresponding indicator goes out.
A selector switch allows selection of an adjustable time delay from 0.1 to 10 s. With function
transient over and
under voltages are not taken into account. With function
all variations above or below are taken into account and
re-energisation of the relay is delayed.
i Phase failure or incorrect rotational direction of phases
The output relay is de-energised without a time delay in the event of a phase failure or incorrect rotational direction of
phases, the red LED P illuminates.
The output relay is energised and the fault indicator goes out as soon as the supply returns to normal (function
)
or after a preset time delay, (function
).
Function diagram
RM3-TR110,
TR112, TR114

RM3-TR111,
TR113, TR115

U supply A1-A2

U supply A1-A2

U1
0,95 x U1
1,05 x U2

U2

t:

time delay

Function

+ 10 %
+5%
Un
-5%
- 10 %
Voltage measured

15-18
15-16
25-28
25-26

Function

15-18
15-16

Relay

25-28
25-26

t
<t

U1 Overvoltage threshold adjustment related to potentiometer 3 setting.


U2 Undervoltage threshold adjustment related to potentiometer 4 setting.
28307/2

Te

<t

Protection components
General :
page 28307/2
References :
page 28307/4
Scheme, dimensions :
page 28307/5

Measurement and control relays


3-phase supply control relays RM3-TR1
Characteristics

Control circuit characteristics


Rated supply voltage
(Un)

c 50-60 Hz

110...130

220...240

160300

380...415

300500

Average consumption at Un

VA

2.7

2.8

Output relay and operating characteristics


Number of C/O contacts

Output relay state

De-energised on detection of overvoltage, undervoltage or on phase failure


or rotational direction of phases fault

Rated operational voltage


(switching)

400

Conventional thermal current

Rated breaking capacity

AC-15

Time delay

On overvoltage or
undervoltage fault only

Switching threshold drift

Depending on
permissible
ambient temperature

0.06 % per degree centigrade

Within the supply


voltage range
(0.851.1 Un)

0.5 %

Within the supply


voltage range
(0.851.1 Un)

0.5 %

Depending on the
rated operational
temperature

0.06 % per degree centigrade

Hysteresis

Fixed

About 5 % of the de-energisation threshold

Measuring cycle

Fixed

Operating status display

U Green LED on

Supply to device on

R Yellow LED on

Relay energised

> U Red LED on

Overvoltage

< U Red LED on

Undervoltage

P Red LED on

Incorrect rotational direction of phases or phase failure

Time delay drift

230 V- 3A, 400 V-2 A


s

ms

0.1...10

80

Control input characteristics


Nominal voltages to be monitored

c 50 Hz

220, 400, 500

c 50-60 Hz

220, 380420, 430500

Te 2 8 3 0 7 / 3

Protection components
General :
page 28307/2
Characteristics :
pages 28301/2, 28301/3 and 28307/3
Scheme, dimensions :
page 28307/5

Measurement and control relays


3-phase supply control relays RM3-TR1
References

Fixed voltage threshold relays

Adjustable
time delay

Voltage
threshold to be
monitored
%

Basic reference.
Complete with code indicating
control circuit voltage (1)

Nominal
voltage to be
monitored
V

Weight

0.1...10

220 - 50 Hz

10

RM3-TR111i
iii

0.320

400 - 50 Hz

10

RM3-TR113i
iii

0.320

500 - 50 Hz

10

RM3-TR115i
iii

0.320

kg

RM3-TR1

Adjustable voltage threshold relays


Adjustable
time delay

Voltage
threshold to be
monitored
%

Control
voltage
c 50/60 Hz
V

Reference

Nominal
voltage to be
monitored
V

Weight

0.110

220 - 50/60 Hz

Min. 160220

160300

RM3-TR110GV7

0.320

300500

RM3-TR112VS7

0.320

300500

RM3-TR114VS7

0.320

kg

Max. 220300

380420
50/60 Hz

Min. 300380
Max. 420500

430500
50/60 Hz

Min. 350430
Max. 500580

Accessory

(to be ordered separately)

Description

Reference

Sealable cover
width 45 mm

LA9-RM301

LA9-RM301
(1) Standard control voltages
Volts c 50/60 Hz
RM3-TR111
RM3-TR113
RM3-TR115
28307/4

Te

110130
FG7
FG7
FG7

220240
MU7
MU7
MU7

380415
QN7
QN7
QN7

Weight
kg
0.005

Protection components
General :
page 28307/2
Characteristics :
pages 28301/2, 28301/3 and 28307/3
References :
page 28307/4

Measurement and control relays


3-phase supply control relays RM3-TR1
Scheme, dimensions, setting-up

25
28

15
26

16

Connection and voltage values to be monitored according to


the type of RM3-TR1
RM3-TR110

L1-L2-L3

220 V-50/60 Hz

A2

A1

18

L2

L3

L1

Scheme, connection
RM3-TR1

A1 15 25 L1 L2 L3

16 18 28 26

A2

A1-A2

Supply voltage

RM3-TR111

L1-L2-L3

220 V - 50 Hz

L1, L2, L3

Voltages and supplies to be monitored


(see table opposite)

RM3-TR112

L1-L2-L3

380420 V-50/60 Hz

st

15-18
15-16

1 C/O contact of
output relay

RM3-TR113

L1-L2-L3

400 V - 50 Hz

25-28
25-26

2nd C/O contact of


output relay

RM3-TR114

L1-L2-L3

430500 V-50/60 Hz

RM3-TR115

L1-L2-L3

500 V - 50 Hz

77,5

Dimensions

100

45

Setting-up
If the 3-phase voltage to be monitored has the same value as the supply voltage, the module can be supplied by connecting
A1 and L1 on the one hand, and A2 and L3 on the other hand. However, in this case, some faults cannot be displayed:
failure of phase L1 or L3 for example.

Example of undervoltage and overvoltage to be monitored :


-

Nominal 3-phase voltage to be monitored 400 V/60 Hz


Overvoltage threshold to be monitored : 460 V
Undervoltage threshold to be monitored : 360 V
Control circuit voltage : 400 V

Te RM3 TR1
A1 A2
16
15 18
26
25 28

i Product selected : RM3-TR112VS7


i Monitoring principle :
- Supply the control circuit (A1-A2) (400 V).
- Connect the 3-phase voltage to be monitored to terminals
L1, L2, L3.
- Adjust the overvoltage to be monitored to 460 V by
means of potentiometer 3.
- Adjust the undervoltage to be monitored to 360V by
means of potentiometer 4.

1
2
>U

<U

Te 2 8 3 0 7 / 5