General
Specifications
UT35A/UT32A
Digital Indicating Controllers
GS 05P01D31-01EN
[Style: S5]
n Overview
n Features
UT35A
UT32A
Number
of analog
input
points
Number
of analog
output
points (*1)
Number
of contact
input
points
Number of
contact
output
points (*3)
-0
-1
-2
1
1
1
1
1
1 (*2)
2
4
7
3
5
8
-0
-1
-2
1
1
1
1
1
1 (*2)
2
2
4
3
3
5
UT35A
UT32A
*1:
*2:
*3:
n Functional Specifications
Control Specifications
*4:
*5:
GS 05P01D31-01EN
1st Edition Nov.30, 2009 (KP)
4th Edition Mar. 11, 2011 (KP)
<<Contents>> <<Index>>
(2) Control Computation Function
(a) Target setting point and the number of PID parameter groups
Respectively, four sets of target setpoints, alarm
setpoints, and PID parameters can be set.
(b) Selecting the PID parameter group
The following PID parameter groups can be selected.
Target setpoint number (SPNO) (The PID number
can be set arbitrarily.)
Measured input zone PID
Target setpoint zone PID
Reached target setpoint zone PID
(c) Auto-tuning
Tuning results can be selected from two options,
Normal or Stable.
Tuning output limit can be set. (It cannot be used in
heating/cooling control.)
(d) Super function: Overshoot-suppressing function
(e) Super 2 function: Hunting-suppressing function
(f) STOP preset output function
(g) Input ERROR preset output function
(h) MANUAL preset output function
Alarm Functions
Alarm output
action
Number of alarm
settings
Number of alarm
output points
Contact input
Tight shut
function
Rate-of-change
limiter of output
Output
deadband
0.1 to 999.9%
1 to 6000 sec. or OFF (using manual reset)
1 to 6000 sec. or OFF
0.0 to 100.0% of measured input range width
Other alarms
Types of Alarm
Output alarm
Alarm Functions
Setpoint alarm
Contact output
AUTO/MANUAL switching
REMOTE/LOCAL switching (only model with
communication option)
STOP/START switching
Switching to AUTO
Switching to MANUAL
Switching to REMOTE (only model with
communication option)
Switching to LOCAL (only model with
communication option)
AUTO-TUNING START/STOP switching
LCD backlight ON/OFF switching
Message interrupt displays 1 through 4
SP number specification
PID number specification
Manual preset output number specification
Alarms 1 through 4
Status output
Measured value
alarm
Deviation alarm
Rate-of-change
alarm
Number of basic
command types
Number of
commands
13
73
UT35A
Up to 7
Up to 8
UT32A
Up to 4
Up to 5
Remark
Load, AND, OR, Timer,
Counter, etc.
Comparison, reverse, addition/
subtraction/multiplication/
division, logic operation, high/
low limiter, etc.
Internal device
Special device
Types of device
Input relay
Output relay
M relay (bit data)
DAT register (data)
P register (parameter)
K register (constant)
Special relay (bit data)
Number of points
7 (max)
8 (max)
256
28
10
30
12
GS 05P01D31-01EN
<<Contents>> <<Index>>
Communication Function
Function
Modbus/TCP
Modbus
(RTU/ASCII)
PROFIBUS-DP
Used for communication
between PLCs and
remote I/O, enabling highspeed data transmission.
CC-Link
DeviceNet
Method
Interface
Targets
Max connection
Server
Ethernet
2 connections
Gateway
Ethernet
+RS-485
Slave
RS-485
Slave
RS-485
Modbus master
function
RS-485
UT55A/UT52A/
UT35A/UT32A/
UP55A/UP35A
Slave
RS-485
Modbus master
function
RS-485
UT55A/UT52A/
UT35A/UT32A/
UP55A/UP35A
Slave
RS-485
Modbus master
RS-485
function
UT55A/UT52A/
UT35A/UT32A/
UP55A/UP35A
Communication
Data
31 units
31 units
Number of nodes:
126
31 Units
(Main Controller
is included.)
Number of nodes:
42 (Remote device)
31 Units
(Main Controller
PV, SP, OUT,
is included.)
ALM etc
Number of nodes:
64
31 Units
(Main Controller
is included.)
Physical interface
Ethernet
Standard : IEEE802.3 (10BASE-T, 100BASE-TX)
Max segment length : 100m
Max. Connecting Configguration : Cascade Max. 4 level (10BASE-T), Max. 2 level (100BASE-TX)
RS-485
Standard : EIA RS-485
Communication method : Two-wire harf-duplex or four-wire harf-duplex, start-stop synchoronization,
and non-procedural
Baud rate : 600,1200,2400,4800,9600,19200 or 38400bps Peer to peer communication is only 19200bps
Maximum communication distance : 1200m
Terminating resistor : 220 (External)
PROFIBUS-DP Standard : Field bus (IEC61158)
Corresponding version : DP V0
Baud rate : 9.6k, 19.2k, 45.45k, 93.75k, 187.5k, 0.5M, 1.5M, 3M, 6M, 12M, AUTO (*3)
Communication distance : 1200m (9.6k to 93.75k)
1000m (187.5k)
400m (0.5M) 200m (1.5M)
100m (3M to 12M)
*3:
AUTO automatically sets the baud rate to that of the host controller (PROFIBUS-DP master).
CC-Link
DeviceNet
GS 05P01D31-01EN
<<Contents>> <<Index>>
n Hardware Specifications
Display Specifications
PV display
5-digit, 14-segment active color LCD (white/red)
Character height: 21.5 mm for UT35A and 13.0 mm
for UT32A
Data display
5-digit, 11-segment color LCD (orange)
Bar graph display
12-segment color LCD (orange)
Thermocouple
0.0 to 400.0C
-200.0 to 750.0F
0.0 to 1800.0C
32 to 3300F
S
R
0.0 to 1700.0C
0.0 to 1700.0C
32 to 3100F
32 to 3100F
-200.0 to 1300.0C
-300.0 to 2400.0F
E
L
-270.0 to 1000.0C
-200.0 to 900.0C
-200.0 to 400.0C
-450.0 to 1800.0F
-300.0 to 1600.0F
-300.0 to 750.0F
0.0 to 400.0C
-200.0 to 1000.0F
0.0 to 2300.0C
32 to 4200F
W (*2)
Resistance-temperature
detector (RTD) 3-wire
Instrument range
C
F
-270.0 to 1370.0C -450.0 to 2500.0F
-270.0 to 1000.0C -450.0 to 2300.0F
-200.0 to 500.0C
-200.0 to 1000.0F
-200.0 to 1200.0C -300.0 to 2300.0F
-270.0 to 400.0C
-450.0 to 750.0F
Platinel
0.0 to 1390.0C
2
32.0 to 2500.0F
32 to 3400F
W97
Re3-W75 0.0 to 2000.0C
Re25
32 to 3600F
JPt100
-200.0 to 500.0C
Pt100
Standard
signal
DC voltage
DC current
-300.0 to 1000.0F
-300.0 to 1560.0F
-300.0 to 1000.0F
Accuracy
0.1% of instrument
range 1 digit for 0C
or more
0.2% of instrument
range 1 digit for less
than 0C
However, 2% of
instrument range
1 digit for less than
-200C of thermocouple
K 1% of instrument
range 1 digit for less
than -200C of thermocouple T
0.15% of instrument
range 1 digit for 400C
or more
5% of instrument
range 1 digit for less
than 400C
0.15% of instrument
range 1 digit
0.1% of instrument
range 1 digit
0.25% of instrument
range 1 digit for less
than 0C
0.1% of instrument
range 1 digit for 0C
or more
0.2% of instrument
range 1 digit for less
than 0C
However, 1.5% of
instrument range 1 digit
for less than -200.0C of
thermocouple E
0.2% of instrument
range 1 digit
0.1% of instrument
range 1 digit
0.5% of instrument
range 1 digit for 800C
or more
Accuracy not guaranteed for less than 800C
*1:
*2:
E988
Applicable standards: JIS, IEC and DIN (ITS-90) for thermocouples and resistance-temperature detectors (RTD)
Input sampling period: Synchronized to control period
Burnout detection
Upscale and downscale of function, and OFF can
be specified for the standard signal of thermocouple and resistance-temperature detector (RTD).
For integrated signal input, 0.1 V or 0.4 mA or less
is judged as a burnout.
Input bias current: 0.05 A (for thermocouple and
resistance-temperature detector (RTD))
Resistance-temperature detector (RTD) measured
current: About 0.16 mA
Input resistance
1 M or more for thermocouple/mV input
About 1 M for voltage input
About 250 for current input (with built-in shunt
resistance)
Allowable signal source resistance
250 or less for thermocouple/mV input
Effect of signal source resistance: 0.1 V/ or less
2 k or less for DC voltage input
Effect of signal source resistance: about
0.01%/100
Allowable wiring resistance
Up to 150 per line for resistance-temperature
detector (RTD) input (conductor resistance
between the three lines shall be equal)
Effect of wiring resistance: 0.1C/10
Allowable input voltage/current
10 V DC for thermocouple/mV/mA or resistance temperature detector (RTD) input
20 V DC for V input
40 mA DC for mA input
Noise reduction ratio
40 dB or more (at 50/60 Hz) in normal mode
120 dB or more (at 50/60 Hz) in common mode
Reference junction compensation error
1.0C (15 to 35C)
1.5C (-10 to 5C and 35 to 50C)
0.2% of instrument
range 1 digit
0.1% of instrument
range 1 digit (*1)
0.1% of instrument
range 1 digit
0.1% of instrument
range 1 digit (*1)
0.1% of instrument
range 1 digit
0.400 to 2.0000 V
1.000 to 5.000 V
4.00 to 20.00 mA
0.000 to 2.000 V
0.00 to 10.00 V
-10.00 to 20.00 mV
0.00 to 20.00 mA
0.1% of instrument
range 1 digit
The accuracy is that in the standard operating conditions: 23 2C, 55 10%RH, and power frequency at
50/60 Hz.
GS 05P01D31-01EN
<<Contents>> <<Index>>
Number of points
Control output (heating-side output): 1 point
(standard), which is shared with transmission
output
Cooling-side output: 1 point, which is
shared with transmission output
Output functions
Current output or voltage pulse output
Current output
4 to 20 mA DC or 0 to 20 mA DC/load resistance
600 or less
Current output accuracy
0.1% of span (however, 5% of span for 1 mA
or less)
The accuracy is that in the standard operating
conditions: 23 2C, 55 10%RH, and power
frequency at 50/60 Hz
Voltage pulse output
Application: time proportional output
ON voltage: 12 V or more/load resistance of 600
or more
OFF voltage: 0.1 V DC or less
Time resolution: 10 ms or 0.1% of output value,
whichever is larger
1s
(Response time at 63% of transmission output when a
change is made stepwise in the range between 10 and
90% of input span)
GS 05P01D31-01EN
<<Contents>> <<Index>>
Safety:
Compliant with IEC/EN61010-1 (CE), approved by
CAN/CSA C22.2 No. 61010-1 (CSA), approved by
UL61010-1.
Installation category: CAT. II
Pollution degree: 2
Measurement category: I (CAT. I)
Rated measurement input voltage: Max. 10 V DC
Rated transient overvoltage: 1500 V (*)
*:
This is a reference safety standard value for measurement category I of IEC/EN/CSA/UL61010-1. This value is
not necessarily a guarantee of instrument performance.
EMC standards:
Compliant with
CE marking
EN 61326-1 Class A, Table 2 (For use in industrial
locations),
EN 61326-2-3
EN 55011 Class A, Group 1
EN 61000-3-2 Class A
EN 61000-3-3
C-tick mark
EN 55011 Class A, Group 1
The instrument continues to operate at a measure
ment accuracy of within 20% of the range during
testing.
RoHS regulation: Compliant
Power supply
Rated voltage: 100 to 240 V AC (+10%/-15%), 50/60 Hz
24 V AC/DC (+10%/-15%) (When the
/DC option is specified)
Power consumption: UT35A: 18 VA (For the /DC
option. DC: 9 VA, AC: 14 VA)
UT32A: 15 VA (For the /DC
option. DC: 7 VA, AC: 11 VA)
Storage: Nonvolatile memory
Allowable power interruption time: 20 ms (at 100 V AC)
Withstanding voltage
2300 V AC for 1 minute between primary and
secondary terminals
1500 V AC for 1 minute between primary terminals
500 V AC for 1 minute between secondary
terminals
(Primary terminals = Power (*) and relay output
terminals, Secondary terminals = Analog I/O signal
terminals, contact input terminals, communication
terminals, and functional grounding terminals.)
*:
Insulation resistance
Between power supply terminals and a grounding
terminal: 20 M or more at 500 V DC
Isolation specifications
PV (universal) input terminal
Control and transmission (analog) output terminal
(not isolated between the analog output terminals)
Valve position (feedback) input terminal
Control relay (c-contact or 2 a-contact) output terminal
Alarm-1 relay (a-contact) output terminal
Alarm-2 relay (a-contact) output terminal
Alarm-3 relay (a-contact) output terminal
Position proportional relay output terminal
Internal
circuits
Power
supply
Environmental Conditions
Normal operating conditions
Ambient temperature: -10 to 50C (-10 to 40C for
side-by-side mounting of controllers)
For the CC-Link option, 0 to 50 C (0 to 40 C for
side-by-side close mounting)
Ambient humidity: 20 to 90% RH (no condensation)
Magnetic field: 400 A/m or less
Continuous vibration (at 5 to 9 Hz) Half amplitude of
1.5 mm or less
(at 9 to 150 Hz) 4.9 m/s2 or less, 1 oct/min for 90 minutes each in the three axis directions
Rapid vibration: 14.7 m/s2, 15 s or less
Impact: 98 m/s2 or less, 11 msec.
Installation altitude: 2,000 m or less above sea level
Warm-up time: 30 minutes or more after the power is
turned on
Start-up time within 10 s
GS 05P01D31-01EN
<<Contents>> <<Index>>
n Block Diagram
Single Loop Control
Equipped as standard
Equipped as standard.
Contact inputs
PV input
PV
DI1
Input type
IN
Input unit
UNIT
Input range/scale
RH, RL
SDP
DI2
SH, SL
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameters Setting Software Users Manual.
PV input bias
BS
PV input filter
FL
Communication
SPNO
RT
REMOTE
RBS
SP
Target setpoints 1 to 4
LOCAL
R/L
PV display
SP limiter
SPH, SPL
SP ramp rate
UPR, DNR
TMU
SP display
Control computation
CNT
Output limiter
EPO
OH, OL
Normal
ALG
MPON
Manual operation
Output limiter
OH, OL
OLMT
MAN
AUTO
A/M
Preset output
PO
STOP
RUN
STOP (ON)/RUN (OFF) switch
S/R
OT
Equipped as standard
Equipped as standard
Alarm
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software Users Manual.
For optional suffix code /HA
LPS
Relay
OUT
RET
AL1
Alarm 2
(PV low limit)
Alarm 1
(PV high limit)
OUT
Alarm 3
(PV high limit)
24 V loop
power supply
AL2
HAL1
HAL2
Heater break
alarm 1
Heater break
alarm 2
AL3
Current
Terminal
Parameter
Function
Analog signal
Contact signal
GS 05P01D31-01EN
<<Contents>> <<Index>>
n Terminal Arrangement
Terminal Arrangement for UT35A Single Loop Control
OUT
Control output
Relay contact output
NC
101
NO
102
COM
103
(Equipped
PV input
PV as standard)
TC input
RTD input
A 201
202
203
202
204
203
E4-terminal area
OUT2
Cooling NO
-side
101
OUT
Heating NO
-side
102
101
-112
501
-512
401
-412
COM
103
101
501
401
102
502
103
ALM
(Equipped
as standard)
AL3
Common
Alarm-2 output
( PV low limit)
Common
Alarm-1 output
(PV high limit)
AL2
AL1
Common
UT
104
105
301
201
302
202
503
303
203
104
504
304
204
105
505
305
205
106
506
306
206
107
507
407
207
108
508
408
208
109
509
409
110
510
410
111
511
411
211
112
512
412
212
210
110
111
112
Allowable range:
(24
100-240 V AC (10%)
(free voltage)
50/60 Hz shared
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12V)
110
111
112
Feedback input
100%
HIGH
(direct)
507
LOW
(reverse)
508
205
206
511
COM
509
0% 512
+ 510
511
- 512
Control output
207
208
0-20 mA DC,
4-20 mA DC
207
14.5-18.0 V DC
(Max. 21 mA DC)
208
207
208
Default: 4-20 mA DC
Contact input
DI (Equipped as standard)
VALV
No-voltage
contact
UT Transistor
210 DI2
contact
210
211 DI1
211
Common
212 COM
212
510
RET/OUT2
108
206
109
E3-terminal area
Power supply
N
E1-terminal area
201
-212
107
14.5-18.0 V DC
(Max. 21 mA DC)
301
-306
106
206
B 203
Contact output
4-20 mA DC or
0-20 mA DC
b 202
203
Retransmission output
UT
+5V
DI2
+5V
DI1
COM
HAL2 508
Common
COM 509
511
512
GS 05P01D31-01EN
<<Contents>> <<Index>>
E4-terminal area E1-terminal area
101
-112
501
-512
401
-412
301
-306
201
-212
101
501
401
301
201
102
502
302
202
E1-Terminal Area
301-306
Contact input
103
503
303
203
504
304
204
Common
301 COM
Transistor contact
301
105
505
305
205
302 DI11
302
506
306
206
303 DI12
303
304 DI13
304
305 DI14
305
306 DI15
306
507
407
207
508
408
208
109
509
409
110
510
410
210
111
511
411
211
112
512
412
212
E3-terminal area
COM
DI11
DI12
DI13
DI14
DI15
UT
UT
+5V
+5V
+5V
+5V
+5V
UT Transistor contact
UT
COM
301 COM
301
+5V
DI11
302
302 DI11
+5V
DI12
303
303 DI12
No-voltage
contact
Common
Factory default: No function
Factory default: No function
COM 506
Common
Contact output
106
107
E4-Terminal Area
104
108
501-506
21.6-28.0 V DC
(Max. 30 mA DC)
+ 505
LPS24
506
Function can be
assigned to the
terminals with no
function.
COM 306
E3-Terminal Area
401-412
(Suffix code:
Type 3=1)
SDA(-) 408
SG
ETHR
10BASE-T/100BASE-TX
RJ45 connector
409
RDB(+) 410
Color
Amber
Lit
100M bps
RS-485
10M bps
Unlit
RDA(-) 411
Color
Green
Lit
Linked
Blink
Active
Unlit
Link failure
RSB(+) 407
RSA(-) 408
SG
390
Data
CHK line
RDY
RxD/TxD-P
220
If the UT is located at the end
RxD/TxD-N of a segment for the
Data
ERR line
3
4
PROF
PROFIBUS
communication wiring,
terminating resistors are
Pin Signal name
Description
separately needed.
1 VP
+5V bus power
These are to be prepared by
users. (390 : 2 pcs. 220 :
Data signal
2 RxD/TxD-P
(positive data receive/transmit) 1 pc., or an active
terminator.)
Data signal
390
DGND
RxD/TxD-N
DGND
Signal ground
SHIELD
Shield ground
LED
CHK
(red)
Lit
User profile error
Normal
RDY Communicating
(green) successfully
ERR
(red)
Not connected, or
communication
failure (flashing)
L ERR
L RUN
5
Pin Signal name
Normal
No power, or
Communication
failure
Normal
RSB(+) 407
RSA(-) 408
SG
409
Description
FG
SLD
Flame ground
2
3
DG
Shield
DB
DA
RX/TX + signal
CHK
(red)
RS-485
110
DB
CC-L
DA
LED
Unlit
409
Lit
User profile error/
Address error
If the UT is located at
the end of a segment
for the CC-Link
communication wiring,
terminating resistors
are separately needed.
These are to be
prepared by users.
(110 : 1 pc.)
Unlit
Normal
Normal
RSA(-) 408
SG
409
CAN_L
If the UT is located at
the end of a segment
for the DeviceNet
communication wiring,
terminating resistors
are separately needed.
These are to be
prepared by users.
(121 : 1 pc.)
MNS
5
Pin Signal name
Description
V+
CAN_H
DRAIN
Shield/Drain wire
CAN_L
CHK
(red)
RSB(+) 407
121
CHK
LED
RS-485
DNET
CAN_H
No carrier
L RUN Normal
detected/
(green) Communicating successfully Communication
timeout
V-
RX/TX - signal
DeviceNet power supply common
Lit/flashing
Unlit
Normal
MNS
(green Critical link failure (red, lit).
No electricity
/red) Connection timeout (red, flashing)
At power-on/Communication
faulted (green/red, flashing)
GS 05P01D31-01EN
RS-485
RSB(+) 407
RSA(-) 408
SG
409
10
<<Contents>> <<Index>>
Terminal Arrangement for UT32A Single Loop Control
Control output
Relay contact output
NC
101
NO
102
COM
103
OUT
Factory default:
PV input type is
undefined.
OUT
Heating NO
-side
102
COM
103
AL3
Common
Alarm-2 output
(PV low limit)
AL2
Common
Alarm-1 output
(PV high limit)
AL1
Common
203
101
301
201
102
302
202
103
303
203
104
304
204
105
14.5-18.0 V DC
(Max. 21 mA DC)
206
105
305
205
106
306
206
107
307
207
108
308
208
109
309
110
310
111
311
211
112
312
212
205
206
Control output
207
208
Default: Undefined
0-20 mA DC,
4-20 mA DC
207
14.5-18.0 V DC
(Max. 21 mA DC)
208
207
208
Default: 4-20 mA DC
210
Contact input
DI (Equipped as standard)
External contact input
108
109
110
111
110
100%
101
LOW
(reverse)
102
311
COM
103
0% 312
Current (mA)
310
input
311
312
When feedback input is current
No-voltage
contact
UT Transistor
contact
210 DI2
210
211 DI1
211
Common
212 COM
212
310
Feedback input
111
VALV
112
112
Feedback input
HIGH
(direct)
Allowable range:
100-240 V AC (10%)
(free voltage)
50/60 Hz shared
UT
+5V
DI2
+5V
DI1
COM
HAL2 308
Common
COM 309
311
312
E1-Terminal Area
301-306
RET/OUT2
107
RS-485
206
106
Power supply
N
202
201
-212
UT
203
204
301
-312
ALM (Equipped
as standard)
104
4-20 mA DC or
0-20 mA DC
b 202
B 203
E1-terminal area
A 201
101
-112
Contact output
Retransmission output
Default:
PV retransmission
RTD input
202
PV (Equipped
as standard)
TC input
203
OUT2
PV input
(Suffix code:
Type 2=1)
21.6-28.0 V DC
(Max. 30 mA DC)
SDA(-) 302
305
LPS24
306
303
SG
RDB(+) 304
RDA(-) 305
UT
301 COM
Transistor
contact
301
302 DI11
302
303 DI12
303
COM
DI11
DI12
UT
+5V
+5V
Function can be
assigned to the
terminals with no
function.
COM 306
Common
RSB(+) 301
RSA(-) 302
SG
21.6-28.0 V DC
(Max. 30 mA DC)
305
RS485/LPS24
306
303
GS 05P01D31-01EN
11
<<Contents>> <<Index>>
65
Bracket
20
96
91.6
96
Unit: mm
Terminal cover (option)
94.6
105.2
11
Bracket
1 to 10 mm (panel thickness)
Side-by-side close mounting
[(N-1)96+92] +0.8
0
General mounting
92 +0.8
0
117 min.
145
min.
(53)
92+0.8
0
92+0.8
0
(25)
UT32A
11
Unit: mm
65
Bracket
20
96
91.6
94.6
105.2
48
Bracket
1 to 10 mm (panel thickness)
Side-by-side close mounting
[(N-1)48+45] +0.6
0
General mounting
92 0
+0.8
70 min.
145
min.
(53)
92 +0.8
0
45+0.6
0
(25)
Normal tolerance:
(value of JIS B 0401-1998 tolerance class IT18)/2
12
<<Contents>> <<Index>>
Optional
suffix
code
Suffix code
UT35A
Type 1:
Basic control
-0
-1
-2
0
1
2
Type 2:
Functions
Type 3:
Open networks
0
1
2
3
4
5
-1
-2
-3
-4
0
1
-00
*1:
*2:
*3:
*4:
/LP
/HA
/DC
/CT
Optional
suffix
code
Suffix code
UT32A
Type 1:
Basic control
-0
-1
-2
0
1
2
Type 2:
Functions
Type 3:
Open networks
Description
Digital Indicating Controller (provided with retransmission output or 15 V DC loop power
supply, 2 DIs, and 3 DOs) (Power supply: 100-240 V AC)
Standard type
Position proportional type
Heating/cooling type
None
RS-485 communication (Max. 38.4 kbps, 2-wire/4-wire) (*2)
2 additional DIs and 2 additional DOs
None
-1
-2
-3
-4
Case color
Fixed code
0
1
-00
*3:
*4:
English, German, French, and Spanish can be displayed as the guide display.
The /LP option can be specified in the combination of Type 2 code (any of "0" or "1") and Type 3 code (any of "0" or "1".)
The /HA option can be specified when the Type 1 code is "-0" or "-2."
When the /CT option is specified, the UT35A does not conform to the safety standards (UL and CSA) and CE marking.
Model
*1:
*2:
Description
/LP
/HA
/DC
/CT
English
German
French
Spanish
White (Light gray)
Black (Light charcoal gray)
Always "-00"
24 V DC loop power supply (*2)
Heater break alarm (*3)
Power supply 24 V AC/DC
Coating (*4)
English, German, French, and Spanish can be displayed as the guide display.
The /LP option can be specified in the combination of Type 1 code (any of "-0" or "-1") and Type 2 code (any of "0" or "1.") Additionally, when the Type 2 code is "1", the RS-485 communication is 2-wire system.
The /HA option can be specified when the Type 1 code is "-0" or "-2."
When the /CT option is specified, the UT32A does not conform to the safety standards (UL and CSA) and CE marking.
Suffix code
-00
Description
Parameter Setting Software
n Standard accessories
n Accessory
Model
Name
Terminal cover
UTAP001
UTAP002
Users Manual
(CD-ROM)
UTAP003
Description
For UT35A
For UT32A
GS 05P01D31-01EN