CHILLER REPLACEMENT

CONTRACTORS GUIDE
YCAL 15 to 65 TONS
AIR COOLED SCROLL CHILLER

YLAA 70 to 175 TONS


AIR COOLED SCROLL CHILLER

YVAA 150 to 500 TONS


AIR COOLED SCREW CHILLER

YCWL 50 to 200 TONS


WATER COOLED SCROLL CHILLER

AIR-COOLED
YCAL
15 TO 40
Pages 12-23

YCAL
41 TO 65
Pages 24-29

CHILLER REPLACEMENT
CONTRACTORS GUIDE

YLAA
70 TO 90
Pages 36-43

YLAA
91 TO 130
YCAL 15 to 65 TONS
AIR COOLED SCROLL CHILLER

YLAA 70 to 175 TONS


AIR COOLED SCROLL CHILLER

Pages 44-53

YLAA
131 TO 175
Pages 54-63

YVAA
150 TO 200
Pages 68-73

YVAA
201 TO 500
Pages 74-85

YVAA 150 to 500 TONS


AIR COOLED SCREW CHILLER

YCWL 50 to 200 TONS


WATER COOLED SCROLL CHILLER

WATER COOLED
YCWL
50 TO 90
Pages 92-109

YCWL
91 TO 130
Pages 110-117

YCWL
131 TO 200
Pages 118-125

In-stock Chillers Ready for Quick Shipment

When You Need Cooling Fast!


Complete packages for quick Plug & Play installation

Unit Benefits
Air-cooled Scroll Chillers

Air-cooled Screw Chillers

Air-cooled chillers using scroll-compressor technology ranging from 15 to 175 tons. Standard feature include:

Air-cooled chillers using YORK VSD Screw technology ranging from 150 to 500 tons. Standard features include:

Voltages: 200V, 230V, 380V, 460V, 380-415V/50Hz, 575V


Chilled-water supply range: 40 - 55F; brine supply to 10F
Ambient operation between 0 - 115F
Single-point power connection reduces wiring costs
Non-fused disconnect switch simplifies installation and
servicing
Control transformer eliminates separate control wiring
Micro-computer control panel is very user-friendly
Low-noise fans reduce radiated sound
Victaulic-grooved water connections reduce installation
costs
Complies with ASHRAE Standard 90.1 on energy efficiency
Options are available upon request

Voltages: 200V, 230V, 380V, 400V, 460V, 380-415V/50Hz,


575V
Chilled-water supply range: 40 - 55F; brine supply to 15F
Ambient operation between 0 - 125F
Single-point power connection reduces wiring costs
Non-fused disconnect switch simplifies installation and
servicing
Control transformer eliminates separate control wiring
VSD increases reliability at start-up and shut-down
Micro-computer control panel is very user-friendly
Low-noise fans reduce radiated sound
Victaulic-grooved water connections reduce installation
costs
Complies with ASHRAE Standard 90.1 on energy efficiency
Options are available upon request

JOHNSON CONTROLS

Water-cooled Scroll Chillers

Water-cooled chillers using scroll-compressor technology


ranging from 50 to 200 tons. Standard features include:
Voltages: 200V, 230V, 380V, 460V, 380-415V/50Hz, 575V
Chilled-water supply range: 40 - 55F; brine supply to 15F
Single-point power connection reduces wiring costs
Non-fused disconnect switch simplifies installation and
servicing
Control transformer eliminates separate control wiring
Micro-computer control panel is very user-friendly
Complies with ASHRAE Standard 90.1 on energy
efficiency
Non-reversing heat pump function (leaving condenser
temperature control)
Options are available upon request

Need temporary cooling?

If you need cooling while we are customizing your unit,


Johnson Controls can provide a rental unit. We make
available a wide range of products including chillers,
rooftop units, air handlers, towers and peripheral
equipment. Our service includes delivery, installation,
start-up, maintenance, and financing. If interested in
this option please contact the JCI Rental Department at:

1-800-JCI-RNTL (1800-524-7685)
www.johnsoncontrols.com/rental

Need more than the standard unit?

Need Replacement Parts?

If you need a chiller quickly but need some customization


of features, Johnson Controls can make it happen.
Customization features include:
Suction-pressure readouts
Service-Isolation valves
Hot gas by-pass
Brine cooling as low as 10F
Functional witness testing
Hydronics package
Epoxy Coated Cond. Coils
Options are available upon request

Your brand HVAC parts source for air cooled, water cooled,
and absorption chillers. We are able to ship out the HVAC
parts that you need as soon as possible. If you need items
urgently (for a hospital, school or other critical application) we
can prioritize this requirement and work with our supplier for
expediting. If you have a need for replacement parts please
contact the JCI Parts Department at :

jOHNSON CONTROLS

1-800-932-1701

Ways to Reduce Your Risk, Expand Your Business and


Increase Your Profits
OPTION I
Use Variable Speed Technology to Create Chiller Replacement Opportunities
Compressor motor control via a variable frequency drive allows you as the installing contractor to give your
customer more tonnage without changing the electrical power supply. Also, emergency generator size can be
reduced when feeding chillers with variable speed compressors.
For Example: Your customer has an existing chiller that produces 165 tons at ARI conditions. The MCA for this
chiller is 374 amps and the existing wire and breaker size was installed to meet this MCA. Your customer is short
on capacity during peak hours of the day. YORK has an YVAA0248CEV that produces 225 tons with an MCA of
374. This will give you an extra 61 tons without changing out the wires or breakers.
On the other hand, if your customer doesnt have a need for additional capacity, and the installation requires electrical power component upgrades, the first cost savings when using smaller breakers, wire and conduit is substantial.

$310 Average Wire Savings

Potential For a Smaller Circuit


Breaker Frame Size

$2,100

$3,500

OPTION II
Use Energy Performance to Differentiate Your Replacement Offering
The YORK Latitude variable speed air-cooled chiller allows you as the installing contractor to offer your customers
a replacement alternative that is as much as 25% more efficient than existing chillers.
For Example: Your customer wants to replace an existing 350-ton chiller. You as the installing contractor can
offer either a standard efficiency chiller or the YORK optimized variable speed chiller. The optimized offering will
save the customer over $17,000/year*. With this level of annual savings, you can offer your customer a $21,250
additive alternate with a 1.25 year simple payback. The price premium for the optimized offering is $7,000, which
allows you to capture $14,250 of additional gross profit.
*see the next page for the Average Energy Cost (AEC) calculation

JOHNSON CONTROLS

Annual Savings / Average Energy Cost (AEC) Calculation

Input Variables:

IPLV = Integrated Part Load Value (kW/TON) = (12) / (IPLV EER)


FLT = Full Load Tons (tons)
ACL = Average Chiller Load (tons) = (FLT) x (0.58)
RATE = Commercial Energy Cost ($/kWh)
OH Average Chiller Operating Hours (hrs)
Output Functions:

AEC = (IPLV) x (ACL) x (RATE) x (OH)


Annual Savings = AEC Existing or Base Bid AEC New

Example
Input Variables:
IPLV Existing or Base Bid = 15.4 EER
IPLV New = 19.0 EER
FLT Existing or Base Bid = 350 tons
FLT New = 350 tons
RATE = $0.1016/kWh
OH = 5000 hrs
Calculations:
AEC Existing or Base Bid = (IPLV) x (ACL) x (RATE) x (OH)
AEC Existing or Base Bid = (12 / (IPLV EER)) x ((FLT) x (0.58)) x (RATE) x (OH)
AEC Existing or Base Bid = (12 / 15.4 EER) x (350 tons x 0.58) x ($0.1016/kWh) x (5000 hrs)
AEC Existing or Base Bid = $80,356.36
AEC New = (IPLV) x (ACL) x (RATE) x (OH)
AEC New = (12 / (IPLV EER)) x ((FLT) x (0.58)) x (RATE) x (OH)
AEC New = (12 / 19.0 EER) x (350 tons x 0.58) x ($0.1016/kWh) x (5000 hrs)
AEC New = $65,130.95
Annual Savings = AEC Existing or Base Bid AEC New
Annual Savings = $80,356.36 - $65,130.95
Annual Savings = $15,225.41 / year

jOHNSON CONTROLS

JOHNSON CONTROLS

YCAL

15 to 65 Tons
Air Cooled Scroll Chiller

jOHNSON CONTROLS

JOHNSON CONTROLS

YCAL Rigging
WARNING To ensure warranty coverage, this equipment must be commissioned and serviced
by an authorized Johnson Controls Service Mechanic or a qualified service person experienced in
chiller installation. Installation must comply with all applicable codes, particularly in regard to electrical wiring and other safety elements such as relief valves, HP cutout settings, design working
pressures, and ventilation requirements consistent with the amount and type of refrigerant charge.
Lethal voltages exist within the control panels. Before servicing, open and tag all disconnect
switches.
Installation Check List
The following items must be checked before placing the units in operation.
1.Inspect the unit for shipping damage.
2. Rig Unit using spreader bars.
3.Open the unit only to install water piping system. Do not remove protective covers from water connections
until piping is ready for attachment. Check water piping to ensure cleanliness.
4. Pipe unit using good piping practice (see ASHRAE handbook section 215 and 195).
5.Check to see that the unit is installed and operated within limitations (Refer to Operational and Voltage
Limitations located in Section 1 of the YCAL Operations and Maintenance Guide [Form 150.62-NM8]).
The following pages outline detailed procedures to be followed to install and startup the chiller.
Handling
These units are shipped as completely assembled units containing full operating charge, and care should be taken to
avoid damage due to rough handling.
WARNING The unit should be lifted by inserting hooks through the holes provided in the unit
base rails. Spreader bars should be used to avoid crushing the unit frame rails with lifting chains.
Inspection

EXAMPLE OF PROPER LIFTING

Immediately upon receiving the unit, it should be inspected for possible damage which may have occurred during transit. If damage is
evident, it should be noted in the carriers freight bill. A written request
for inspection by the carriers agent should be made at once. See
Instruction manual, Form 50.15-NM for more information and details.
Location and Clearances
These units are designed for outdoor installations on ground level,
rooftop, or beside a building. Location should be selected for minimum sun exposure and to insure adequate supply of fresh air for the
condenser. The units must be installed with sufficient clearances for
air entrance to the condenser coil, for air discharge away from the
condenser, and for servicing access.
In installations where winter operation is intended and show accumulations are expected, additional height must be provided to ensure
normal condenser air flow.
Clearances are listed under Dimensions in Section 1 of the YCAL
Operations and Maintenance Guide form 150.62-NM8.

jOHNSON CONTROLS

AIR COOLED SCROLL CHILLER

YCAL Style E - 15 to 65 TONS (R-410A)


BENEFITS
 Maintenance free, hermetic scroll compressor utilizes fewer moving parts to minimize breakdown
Components and circuitry designed for lower minimum circuit ampacities (MCA) to allow use of smaller
wire for reduced power wiring costs
Electronic, digital-based controls ensure reliable, solid-state monitoring and control
Units ship with full ref. charge and undergo factory pressure and operational testing to minimize field setup
time
Two refrigerant circuits on units over 35 tons allows redundant operation
Industrys only 18-month air cooled warranty that covers all parts
Wide range of options to fit any design requirement. (Acoustical treatments, Hydrokit packages etc)
UPGRADE OPTIONS
Remote Cooler
Power Options --> 200, 230, 380, 460, 575 (Not available on all models, refer to Engineering Guide):
Single Point Terminal Block, Non-fused Disconnect Switch, Circuit Breaker, Control Transformer
Control Options:
Low Ambient Kit extends operating range to 0 deg. F from +25 deg. F
Discharge Pressure Transducers and Readout Capability (standard) allows unit to sense and display
discharge pressure
Low Temperature Brine for chilling below 30 deg. F
Motor Current Module allows monitoring of compressor motor current, provides extra protection against
compressor reverse rotation, phase-loss and phase imbalance
Hot Gas Bypass for continuous, stable operation at capacities as low as 5% capacity
Service Isolation Valve - suction and discharge (ball type) isolation valves are added to unit per system;
includes a system high pressure relief valve in compliance with ASHRAE 15
Pre-coated, Post-coated Epoxy Dipped or Copper Fin condenser coils
Unit Enclosure Options:
Wire Panels (full unit-standard): coated, heavy gauge welded wire mesh mounted on exterior of unit to
prevent unauthorized access
Louvered Panels (full unit): to protect condenser coils, visually screen internal components and prevent
unauthorized access
Sound Attenuation:
Compressor Acoustic Sound Blanket
Ultra Quiet fans
Vibration Isolators - 1" spring, 2" spring or neoprene pad isolators for mounting under unit base rails

10

JOHNSON CONTROLS

AIR COOLED SCROLL CHILLER


YCAL Style E - 15 to 65 TONS

PACKAGE DESCRIPTION:

Cooler:

Shipped complete from the factory ready for field


installation and use
Fully charged with HFC-410A and initial oil charge
Baked on powder paint
Heavy gauge, formed galvanized steel base
Operational and Pressure Tested

Equipped with a heater controlled by separate


thermostat for freeze protection to 20 deg. F
Covered by closed cell foam insulation
Inlet and outlet are grooved for compatibility with
field supplied victaulic connections
Controls:

Compressors:
Suction-gas cooled, hermetic scroll compressors
Large internal volume and oil reservoir provides
greater liquid tolerance
Crankcase heaters for extra protection against
liquid migration

All controls housed in a NEMA 3R/12 cabinet with


gasket sealed, hinged & latched door
LCD, 40-character display with backlight
Color coded, sealed keypad
Standard controls permit operation from 25 to
125 deg F.

Condenser:
Low noise, direct drive, maximum efficiency fans
with corrosion resistant aluminum hub and composite blades; statically and dynamically balanced
Totally enclosed air over (TEAO) type fan motors,
current protected and permanently sealed
Seamless, internally enhanced copper fin & tube
coils arranged in staggered rows; mechanically
expanded to full-height aluminum fins
Design Working Pressure 650 PSIG
Integral subcooling included

jOHNSON CONTROLS

11

Air Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCAL0019EE46

15.4

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)

54.0
44.0
37.0
6.3
Water
0.00010
3.3

Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)

Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)

95.0
0
25.0
115.0

Electrical Data
2

1
18.6/18.6
114.0/114.0
2/1.3

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

10.0 / 2.9
14.6 / 4.3

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

1454
1481

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)

44.9
60
50

Max. Dual Element Fuse Size (Amps)


Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type

60
50
60
1
(1)#14 - #2/0
39.8
114.0
Across the Line

Notes:

Compressor kW
Total Fan kW
Total kW

17.6
1.0
18.6

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Load %
100.0
50.0

12

Operating Condition Electrical Data

Ambient (F)
95.0
70.2

Part Load Rating Data


Capacity (Tons)
15.4
9.1

Compressor kW
17.6
6.3

Unit Efficiency
10.0 / 2.9
16.0 / 4.7

JOHNSON CONTROLS

jOHNSON CONTROLS
LEFT END

44 5/16"
BASE WIDTH

8 5/16"
18 3/4"

11"

(2) 3.0 X 1.50


RIGGING HOLES
BOTH ENDS

2" VICTAULIC CONN (TYP)


LIQUID IN

BOTTOM OF PANEL

VIEW B-B

7/8" TYP.

AIR-COOLED SCROLL CHILLER


MODEL: YCAL0019EE46
NOT FOR CONSTRUCTION

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

8 5/16"
2" VICTAULIC CONN (TYP)
LIQUID OUT

TO ACCESS PANEL 16 1/4"

11 5/8"

PRODUCT DRAWING

2 1/4"

46 1/16"
45 1/4"

3 15/16"

3 1/4"
6 3/4"

13 3/4"

38 3/16"
2 1/4"

3 3/8"

CONTROL
PANEL

R-410A CHILLER

C
G

ORIGIN

6 1/8"

CONTROL
PANEL
44 3/8"
END
END CAP
WIDTH
32 1/8"

1 1/16"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 1,454, OPERATING - 1,481.
3. CENTER OF GRAVITY FROM ORIGIN: X= 58.6", Y= 22.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.

44 1/2"

15 5/8"

9 1/16"

374

FRONT VIEW

109 3/16"

74 1/2"
97 1/8"

5"

1 1/16"

COMPR
END

(2) 3.0 X 1.50


RIGGING HOLES
BOTH SIDES

340

365

A JOHNSON CONTROLS COMPANY

(2) 7.0 X 2.25


FORKLIFT HOLES
BOTH SIDES

TOP VIEW

5/8" DIA MOUNTING HOLES(TYP)

Date :
Rev. Date :
Form : 150.64-EG1
Dwg. Lev. : 03/05
Dwg. Scale : NTS

1"

17"

2 1/4"

402

MODEL: YCAL0019EE46
AHRI CAPACITY 15.4 TONS
YCAL
15 TO 40

13

Air Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCAL0022EE46

18.7

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)

54.0
44.0
44.8
4.9
Water
0.00010
3.6

Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)

Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)

95.0
0
25.0
115.0

Electrical Data
2

1
20.0/20.0
125.0/125.0
2/1.3

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

10.0 / 2.9
15.5 / 4.5

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

1567
1597

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)

48.1
60
60

Max. Dual Element Fuse Size (Amps)


Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type

60
60
60
1
(1)#14 - #2/0
42.6
125.0
Across the Line
48.1

Notes:

Compressor kW
Total Fan kW
Total kW

21.5
1.0
22.5

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Load %
100.0
50.0

14

Operating Condition Electrical Data

Ambient (F)
95.0
72.1

Part Load Rating Data


Capacity (Tons)
18.7
11.5

Compressor kW
21.5
7.2

Unit Efficiency
10.0 / 2.9
16.9 / 5.0

JOHNSON CONTROLS

jOHNSON CONTROLS
LEFT END

44 5/16"
BASE WIDTH

8 5/16"
18 3/4"

11"

(2) 3.0 X 1.50


RIGGING HOLES
BOTH ENDS

2" VICTAULIC CONN (TYP)


LIQUID IN

BOTTOM OF PANEL

VIEW B-B

7/8" TYP.

AIR-COOLED SCROLL CHILLER


MODEL: YCAL0022EE46
NOT FOR CONSTRUCTION

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

8 5/16"
2" VICTAULIC CONN (TYP)
LIQUID OUT

TO ACCESS PANEL 16 1/4"

11 5/8"

PRODUCT DRAWING

2 1/4"

46 1/16"
45 1/4"

3 15/16"

3 1/4"
6 3/4"

13 3/4"

38 3/16"
2 1/4"

3 3/8"

CONTROL
PANEL

R-410A CHILLER

C
G

ORIGIN

6 1/8"

CONTROL
PANEL
44 3/8"
END
END CAP
WIDTH
32 1/8"

1 1/16"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 1,567, OPERATING - 1,597.
3. CENTER OF GRAVITY FROM ORIGIN: X= 58.5", Y= 22.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.

44 1/2"

15 5/8"

9 1/16"

403

FRONT VIEW

109 3/16"

74 1/2"
97 1/8"

5"

1 1/16"

COMPR
END

(2) 3.0 X 1.50


RIGGING HOLES
BOTH SIDES

366

394

A JOHNSON CONTROLS COMPANY

(2) 7.0 X 2.25


FORKLIFT HOLES
BOTH SIDES

TOP VIEW

5/8" DIA MOUNTING HOLES(TYP)

Date :
Rev. Date :
Form : 150.64-EG1
Dwg. Lev. : 03/05
Dwg. Scale : NTS

1"

17"

2 1/4"

434

MODEL: YCAL0022EE46
AHRI CAPACITY 18.7 TONS
YCAL
15 TO 40

15

Air Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCAL0028EE46

25.6

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)

54.0
44.0
61.3
8.9
Water
0.00010
2.5

Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)

Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)

95.0
0
25.0
115.0

Electrical Data
2

1
23.1/26.9
150.0/187.0
2/4.0

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

10.1 / 3.0
13.4 / 3.9

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

1798
1835

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)

64.7
100
80

Max. Dual Element Fuse Size (Amps)


Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type

90
80
90
1
(1)#14 - #2/0
58.0
187.0
Across the Line

Notes:

Compressor kW
Total Fan kW
Total kW

27.5
3.0
30.5

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Load %
100.0
50.8

16

Operating Condition Electrical Data

Ambient (F)
95.0
71.9

Part Load Rating Data


Capacity (Tons)
25.6
15.7

Compressor kW
27.5
11.7

Unit Efficiency
10.1 / 3.0
14.3 / 4.2

JOHNSON CONTROLS

jOHNSON CONTROLS

15 1/2"

49 1/4"

LEFT END

44 5/16"
BASE WIDTH

19"

8 5/16"

10 3/4"

8 1/2"

AIR-COOLED SCROLL CHILLER


MODEL: YCAL0028EE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

(2) 3.0 X 1.50


RIGGING HOLES
BOTH ENDS

2" VICTAULIC CONN (TYP)


LIQUID IN

VIEW B-B
BOTTOM OF PANEL

7/8" TYP.

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

8 5/16"
2" VICTAULIC CONN (TYP)
LIQUID OUT

TO ACCESS PANEL 13 3/8"

2 1/4"

50 1/16"

3 15/16"

3 1/4"
6 3/4"

2 1/4"

3 3/8"

CONTROL
PANEL

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

17 3/4"

42 1/8"

C
G

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
1 1/16"
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
CONTROL
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
PANEL
44 3/8"
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
END CAP
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
WIDTH
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
32 1/8"
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
6 1/8"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 1,798, OPERATING - 1,835.
3. CENTER OF GRAVITY FROM ORIGIN: X= 63.1", Y= 22.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
ORIGIN
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
Y
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.

1"

17"
TOP VIEW

50 1/2"

15 5/8"

9"

Date :
Rev. Date :
Form : 150.64-EG1
Dwg. Lev. : 03/05
Dwg. Scale : NTS

FRONT VIEW

118 5/16"

105 1/16"

80 1/2"

(2) 7.0 X 2.25


FORKLIFT HOLES
BOTH SIDES

5"

1 1/16"

COMPR
END

(2) 3.0 X 1.50


RIGGING HOLES
BOTH SIDES

423

456

A JOHNSON CONTROLS COMPANY

5/8" DIA MOUNTING HOLES(TYP)

R-410A CHILLER

460
1 7/8"

495

MODEL: YCAL0028EE46
AHRI CAPACITY 25.6 TONS
YCAL
15 TO 40

17

Air Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCAL0033EE46

28.6

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)

54.0
44.0
68.4
11.0
Water
0.00010
5.2

Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)

Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)

95.0
0
25.0
115.0

Electrical Data
2

1
26.9/26.9
187.0/187.0
2/4.0

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

10.5 / 3.1
14.5 / 4.2

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

2034
2077

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)

66.7
100
80

Max. Dual Element Fuse Size (Amps)


Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type

90
80
90
1
(1)#14 - #2/0
61.8
187.0
Across the Line

Notes:

Compressor kW
Total Fan kW
Total kW

29.6
3.0
32.6

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Load %
100.0
50.0

18

Operating Condition Electrical Data

Ambient (F)
95.0
70.0

Part Load Rating Data


Capacity (Tons)
28.6
16.6

Compressor kW
29.6
11.2

Unit Efficiency
10.5 / 3.1
15.7 / 4.6

JOHNSON CONTROLS

jOHNSON CONTROLS

15 1/2"

49 1/4"

LEFT END

44 5/16"
BASE WIDTH

19"

8 5/16"

10 3/4"

8 1/2"

AIR-COOLED SCROLL CHILLER


MODEL: YCAL0033EE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

(2) 3.0 X 1.50


RIGGING HOLES
BOTH ENDS

2" VICTAULIC CONN (TYP)


LIQUID IN

VIEW B-B
BOTTOM OF PANEL

7/8" TYP.

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

8 5/16"
2" VICTAULIC CONN (TYP)
LIQUID OUT

TO ACCESS PANEL 13 3/8"

2 1/4"

50 1/16"

3 15/16"

3 1/4"
6 3/4"

2 1/4"

3 3/8"

CONTROL
PANEL

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

17 3/4"

42 1/8"

C
G

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
1 1/16"
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
CONTROL
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
PANEL
44 3/8"
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
END CAP
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
WIDTH
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
32 1/8"
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
6 1/8"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 2,034, OPERATING - 2,077.
3. CENTER OF GRAVITY FROM ORIGIN: X= 67.1", Y= 23.1" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
ORIGIN
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
Y
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.

1"

17"
TOP VIEW

50 1/2"

15 5/8"

9"

Date :
Rev. Date :
Form : 150.64-EG1
Dwg. Lev. : 03/05
Dwg. Scale : NTS

FRONT VIEW

118 5/16"

105 1/16"

80 1/2"

(2) 7.0 X 2.25


FORKLIFT HOLES
BOTH SIDES

5"

1 1/16"

COMPR
END

(2) 3.0 X 1.50


RIGGING HOLES
BOTH SIDES

516

565

A JOHNSON CONTROLS COMPANY

5/8" DIA MOUNTING HOLES(TYP)

R-410A CHILLER

475
1 7/8"

520

MODEL: YCAL0033EE46
AHRI CAPACITY 28.6 TONS
YCAL
15 TO 40

19

Air Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCAL0043EE46

37.2

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)

54.0
44.0
89.2
6.1
Water
0.00010
2.7

Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)

Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)

95.0
0
25.0
115.0

Electrical Data
2
20.0/20.0
125.0/125.0
2/3.4

1
20.0/20.0
125.0/125.0
2/3.4

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

10.1 / 3.0
14.5 / 4.2

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

2942
2967

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)

99.2
150
110

Max. Dual Element Fuse Size (Amps)


Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type

110
110
110
1
(1)#14 - #2/0
93.7
125.0
Across the Line

Notes:

Compressor kW
Total Fan kW
Total kW

38.8
5.6
44.4

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Load %
100.0
75.0
50.0
25.0
20

Operating Condition Electrical Data

Ambient (F)
95.0
83.3
69.0
55.0

Part Load Rating Data


Capacity (Tons)
37.2
30.0
21.1
11.5

Compressor kW
38.8
24.4
14.2
6.6

Unit Efficiency
10.1 / 3.0
12.0 / 3.5
14.9 / 4.4
17.3 / 5.1
JOHNSON CONTROLS

jOHNSON CONTROLS

46 15/16"

LIQUID IN

LEFT END

45 1/8"
90 1/4" BASE WIDTH

LIQUID OUT
3" VICTAULIC (TYP)

VIEW B-B
BOTTOM OF PANEL

7/8" TYP.

12 5/8"

25 3/16"
9 7/8"
15 3/4"

ELECTRICAL ACCESS
PANEL

AIR-COOLED SCROLL CHILLER


MODEL: YCAL0043EE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

47 3/4"

3 15/16"

6 3/4"
3 1/4"
C
G

15 1/16"

13 5/8"

25 3/8"

5 5/16"

18 1/2"

ORIGIN

45 1/8"

COOLER
END

1 1/16"

90 9/16"
END CAP
WIDTH

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 2,942, OPERATING - 2,967.
3. CENTER OF GRAVITY FROM ORIGIN: X= 59.6", Y= 43.6" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.

925

862

CONTROLPANEL

TOP VIEW

Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS

13 15/16"

611

569

9 13/16"

1 1/16"

COIL
END

A JOHNSON CONTROLS COMPANY

FRONT VIEW

144 13/16"

TWO LIFTING HOLES


BOTH SIDES

38"

9 13/16"

5/8" DIA MOUNTING HOLES(TYP)

MODEL: YCAL0043EE46
AHRI CAPACITY 37.2 TONS
YCAL
15 TO 40

21

Air Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCAL0046EE46

39.4

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)

54.0
44.0
94.5
5.1
Water
0.00010
3.5

Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)

Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)

95.0
0
25.0
115.0

Electrical Data
2
20.0/20.0
125.0/125.0
2/3.4

1
20.7/20.7
125.0/125.0
2/3.4

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

10.2 / 3.0
14.7 / 4.3

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

2968
3000

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)

100.8
150
110

Max. Dual Element Fuse Size (Amps)


Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type

110
110
110
1
(1)#14 - #2/0
95.1
125.0
Across the Line

Notes:

Compressor kW
Total Fan kW
Total kW

41.0
5.6
46.6

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Load %
100.0
73.2
50.0
23.2
22

Operating Condition Electrical Data

Ambient (F)
95.0
82.9
69.1
55.0

Part Load Rating Data


Capacity (Tons)
39.4
31.5
22.4
11.6

Compressor kW
41.0
25.2
14.9
6.5

Unit Efficiency
10.2 / 3.0
12.3 / 3.6
15.2 / 4.5
17.5 / 5.1
JOHNSON CONTROLS

jOHNSON CONTROLS

46 15/16"

45 1/8"

LEFT END

12 5/8"

AIR-COOLED SCROLL CHILLER


MODEL: YCAL0046EE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

15 3/4" 25 3/16"

ELECTRICAL ACCESS
PANEL

9 7/8"

LIQUID IN

90 1/4" BASE WIDTH

LIQUID OUT
3" VICTAULIC (TYP)

VIEW B-B
BOTTOM OF PANEL

7/8" TYP.

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

47 3/4"

3 15/16"

6 3/4"
3 1/4"
X

15 1/16"

13 5/8"

25 3/8"

5 5/16"

C
G

16 11/16"

ORIGIN

45 1/8"

COOLER
END

1 1/16"

90 9/16"
END CAP
WIDTH

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 2,968, OPERATING - 3,000.
3. CENTER OF GRAVITY FROM ORIGIN: X= 59.2", Y= 43.5" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.

941

875

CONTROLPANEL

TOP VIEW

Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS

13 15/16"

613

570

9 13/16"

1 1/16"

COIL
END

A JOHNSON CONTROLS COMPANY

FRONT VIEW

144 13/16"

TWO LIFTING HOLES


BOTH SIDES

38"

9 13/16"

5/8" DIA MOUNTING HOLES(TYP)

MODEL: YCAL0046EE46
AHRI CAPACITY 39.4 TONS
YCAL
15 TO 40

23

Air Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCAL0052EE46

46.2

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)

54.0
44.0
110.8
9.2
Water
0.00010
3.5

Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)

Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)

95.0
0
25.0
115.0

Electrical Data
2
23.1/23.1
150.0/150.0
2/4.0

1
23.1/23.1
150.0/150.0
2/4.0

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

10.2 / 3.0
15.1 / 4.4

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

3170
3208

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)

114.2
150
125

Max. Dual Element Fuse Size (Amps)


Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type

125
125
125
1
(1)#14 - #2/0
108.4
150.0
Across the Line

Notes:

Compressor kW
Total Fan kW
Total kW

47.9
6.7
54.6

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Load %
100.0
75.0
50.0
25.0
24

Operating Condition Electrical Data

Ambient (F)
95.0
83.4
69.5
55.0

Part Load Rating Data


Capacity (Tons)
46.2
37.3
26.6
15.1

Compressor kW
47.9
30.7
17.6
7.8

Unit Efficiency
10.2 / 3.0
12.0 / 3.5
15.2 / 4.5
19.1 / 5.6
JOHNSON CONTROLS

jOHNSON CONTROLS

61 7/8"

45 1/8"

90 1/4" BASE WIDTH


LEFT END

LIQUID OUT
3" VICTAULIC (TYP)

VIEW B-B
BOTTOM OF PANEL

7/8" TYP.

12 5/8"

25 3/16"
9 13/16"
15 3/4"

ELECTRICAL ACCESS
PANEL

LIQUID IN

AIR-COOLED SCROLL CHILLER


MODEL: YCAL0052EE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

62 5/8"

3 15/16"

6 3/4"
3 1/4"
X

15 1/16"

13 5/8"

25 3/8" B

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

C
G

18 1/2"

ORIGIN

9 13/16"

TOP VIEW

Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS

FRONT VIEW

144 13/16"

713

623

1 1/16"

COIL
END

A JOHNSON CONTROLS COMPANY

13 15/16"

9 13/16"

5/8" DIA MOUNTING HOLES(TYP)

TWO LIFTING HOLES


BOTH SIDES

CONTROL
PANEL

5 5/16"
38"

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
873
1 1/16"
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
COOLER
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
90 9/16"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
END CAP
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
WIDTH
2. WEIGHTS (LB):SHIPPING - 3,170, OPERATING - 3,208.
3. CENTER OF GRAVITY FROM ORIGIN: X= 61.9", Y= 42.2" .
45 1/8"
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
999

MODEL: YCAL0052EE46
AHRI CAPACITY 46.2 TONS

YCAL
41 TO 65

25

Air Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCAL0056EE46

56.2

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)

54.0
44.0
134.7
9.9
Water
0.00010
4.1

Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)

Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)

95.0
0
25.0
115.0

Electrical Data
2
26.9/26.9
187.0/187.0
2/4.0

1
26.9/26.9
187.0/187.0
2/4.0

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

10.1 / 3.0
14.7 / 4.3

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

3206
3244

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)

130.3
150
150

Max. Dual Element Fuse Size (Amps)


Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type

150
150
150
1
(1)#14 - #2/0
123.6
187.0
Across the Line

Notes:

Compressor kW
Total Fan kW
Total kW

60.3
6.7
67.0

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Load %
100.0
75.0
50.0
25.0
26

Operating Condition Electrical Data

Ambient (F)
95.0
83.6
69.4
55.0

Part Load Rating Data


Capacity (Tons)
56.2
45.5
32.2
18.0

Compressor kW
60.3
38.8
22.6
10.2

Unit Efficiency
10.1 / 3.0
12.0 / 3.5
14.9 / 4.4
18.1 / 5.3
JOHNSON CONTROLS

jOHNSON CONTROLS

61 7/8"

45 1/8"

90 1/4" BASE WIDTH


LEFT END

LIQUID OUT
3" VICTAULIC (TYP)

VIEW B-B
BOTTOM OF PANEL

7/8" TYP.

AIR-COOLED SCROLL CHILLER


MODEL: YCAL0056EE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

15 3/4"

12 5/8"

9 7/8"

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

25 3/16"

ELECTRICAL ACCESS
PANEL

LIQUID IN

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

62 5/8"

3 15/16"

6 3/4"
3 1/4"
X

15 1/16"

28 9/16"

25 3/8" B

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

C
G

16 11/16"

ORIGIN

9 13/16"

TOP VIEW

Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS

FRONT VIEW

144 13/16"

715

625

1 1/16"

COIL
END

A JOHNSON CONTROLS COMPANY

14"

9 13/16"

5/8" DIA MOUNTING HOLES(TYP)

TWO LIFTING HOLES


BOTH SIDES

CONTROL
PANEL

5 3/16"
38"

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
889
1 1/16"
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
COOLER
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
90 9/16"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
END CAP
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
WIDTH
2. WEIGHTS (LB):SHIPPING - 3,206, OPERATING - 3,244.
3. CENTER OF GRAVITY FROM ORIGIN: X= 61.5", Y= 42.2" .
45 1/8"
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
1,015

MODEL: YCAL0056EE46
AHRI CAPACITY 56.2 TONS

YCAL
41 TO 65

27

Air Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCAL0066EE46

66.1

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume. (gal)

54.0
44.0
158.4
8.3
Water
0.00010
4.9

Circuit
Compressor RLA
Compressor Start Current (LRA)
Fan QTY/FLA (each)

Condenser Data
Ambient Temp. (F)
Altitude (ft.)
Min. Ambient Temp. (F)
Max. Ambient Temp. (F)

95.0
0
25.0
115.0

Electrical Data
2
26.9/26.9
187.0/187.0
2/1.3

1
33.9/33.9
250.0/250.0
2/4.0

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

10.1 / 3.0
15.1 / 4.4

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

4097
4142

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Dual Element Fuse Size (Amps)

146.0
200
175

Max. Dual Element Fuse Size (Amps)


Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Total Amps
Inrush (PW) Amps
Starter Type

175
175
175
1
(1)#6 - 350
137.6
250.0
Across the Line

Notes:

Compressor kW
Total Fan kW
Total kW

72.1
6.7
78.8

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Load %
100.0
71.5
50.0
21.5
28

Operating Condition Electrical Data

Ambient (F)
95.0
82.6
69.3
55.0

Part Load Rating Data


Capacity (Tons)
66.1
52.5
37.8
18.5

Compressor kW
72.1
42.2
26.6
10.3

Unit Efficiency
10.1 / 3.0
12.9 / 3.8
15.2 / 4.5
18.5 / 5.4
JOHNSON CONTROLS

jOHNSON CONTROLS

61 7/8"

43 1/8"

90 1/4" BASE WIDTH


LEFT END

LIQUID OUT
3" VICTAULIC (TYP)

VIEW B-B
BOTTOM OF PANEL

7/8" TYP.

AIR-COOLED SCROLL CHILLER


MODEL: YCAL0066EE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

15 3/4"

12 5/8"

9 3/4"

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

25 1/16"

ELECTRICAL ACCESS
PANEL

LIQUID IN

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

62 5/8"

3 15/16"

6 3/4"
3 1/4"
X

15 1/16"

28 9/16"

25 3/8" B

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

C
G

12 13/16"

ORIGIN

9 13/16"

TOP VIEW

Date :
Rev. Date :
Form : 150.62-EG1
Dwg. Lev. : 01/02
Dwg. Scale : NTS

FRONT VIEW

153 5/8"

776

768

1 1/16"

COIL
END

A JOHNSON CONTROLS COMPANY

16"

9 13/16"

5/8" DIA MOUNTING HOLES(TYP)

TWO LIFTING HOLES


BOTH SIDES

CONTROL
PANEL

5 3/16"
38"

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
1,292
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
1 1/16"
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
COOLER
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
90 9/16"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
END CAP
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
WIDTH
2. WEIGHTS (LB):SHIPPING - 4,097, OPERATING - 4,142.
3. CENTER OF GRAVITY FROM ORIGIN: X= 59.7", Y= 44.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
43 1/8"
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
1,306

MODEL: YCAL0066EE46
AHRI CAPACITY 66.1 TONS

YCAL
41 TO 65

29

30

JOHNSON CONTROLS

YLAA

70 to 175 Tons
Air Cooled Scroll Chiller

jOHNSON CONTROLS

31

32

JOHNSON CONTROLS

YLAA RIGGING

Typical Lifting Arrangement - 8 Fan Models

Use spreader bars to avoid lifting chains hitting


the chiller.

CAUTION Never lift the chiller using


a forklift or by hooking to the top rails.
Use only the lifting holes provided.

Lifting instructions are placed on a label on the


chiller and on the shipping bag.

Typical Lifting Arrangement - 4 Fan Models

jOHNSON CONTROLS

33

AIR COOLED SCROLL CHILLER


YLAA - 70 to 175 TONS

BENEFITS
 Optimized design for R-410A refrigerant (No EPA Phase out date)
Available in 2-tiers of efficiency:

Standard Efficiency: 9.6 10.0 EER

High Efficiency: 10.1 an above EER
Best Part Load Efficiency with an IPLV as high as 15.9.
The YLAA always qualifies for LEED credit through Enhanced Refrigerant Management.

This chiller utilizes 30-50% less refrigerant than conventional scroll chiller design.
Standard ambient operation from 30 to 115-deg F
Maintenance free, hermetic scroll compressor utilizes fewer moving parts to minimize breakdown
Components and circuitry designed for lower minimum circuit ampacities (MCA) to allow use of smaller
wire for reduced power wiring costs
Electronic, digital-based controls ensure reliable, solid-state monitoring and control
Units ship evacuated with initial oil charge and undergo factory pressure and operational testing to
minimize field setup time
Two refrigerant circuits allows redundant operation.
Industrys only 18-month air cooled warranty that covers all parts
Wide range of options to fit any design requirement. (Acoustical treatments, Hydrokit packages etc)
UPGRADE OPTIONS
Remote Cooler
Power Options --> 200, 230, 380, 460, 575 (Not available on all models, refer to Engineering Guide):
Single Point Terminal Block, Terminal Block with Individual Circuit Breakers, Circuit Breaker, Non-fused
Disconnect Switch or Non-fused Disconnect Switch with Individual System Circuit Breakers
Control Options: Low Ambient Kit extends operating range to 0 deg. F from +30 deg. F
Discharge Pressure Transducers and Readout Capability allows unit to sense and display discharge
pressure
Low Temperature Brine for chilling below 30 deg. F (which includes Electronic Expansion Valve)
Motor Current Module allows monitoring of compressor motor current, provides extra protection against
compressor reverse rotation, phase-loss and phase imbalance
Hot Gas Bypass for continuous, stable operation at capacities as low as 5% capacity
Service Isolation Valve - suction and discharge (ball type) isolation valves are added to unit per system;
includes a system high pressure relief valve in compliance with ASHRAE 15
Post-coated Epoxy Dipped
Unit Enclosure Options:

Wire Panels (full unit): coated, heavy gauge welded wire mesh mounted on exterior of unit to prevent
unauthorized access

Louvered Panels (condenser coils only): louvered panels mounted over exterior condenser coil faces to
protect coils

Louvered Panels (full unit): to protect condenser coils, visually screen internal components and prevent
unauthorized access

Louvered (condensers)/Wire Panels (mechanicals): Louvered steel panels on external condenser coil
faces, heavy-gauge welded-wire mesh around base
Sound Attenuation:
Compressor Acoustic Sound Blanket
Ultra Quiet fans
Vibration Isolators - 1" spring, 2" spring or neoprene pad isolators for mounting under unit base rails

34

JOHNSON CONTROLS

AIR COOLED SCROLL CHILLER


YLAA - 70 to 175 TONS

PACKAGE DESCRIPTION:

Evaporator:

Shipped complete from the factory ready for field


installation and use
Fully charged with HFC-410A and initial oil charge
Baked on powder paint
Heavy gauge, formed galvanized steel base
Operational and Pressure Tested

Equipped with a heater controlled by separate


thermostat for freeze protection to 20 deg. F
Covered by closed cell foam insulation
Inlet and outlet are grooved for compatibility with
field supplied victaulic connections
Refrigerant Circuit:

Compressors:
Suction-gas cooled, hermetic scroll compressors
Large internal volume and oil reservoir provides
greater liquid tolerance
Crankcase heaters for extra protection against
liquid migration

Independent circuits per compressor


Each refrigerant circuit includes: liquid line shutoff
valve with charging port, low side pressure relief
device, filter-drier, solenoid valve, sight glass with
moisture indicator, thermostatic expansion valves,
and flexible, closed-cell foam insulated suction
line and suction pressure transducer.

Condenser:
Low noise, direct drive, maximum efficiency fans
with corrosion resistant aluminum hub and composite blades; statically and dynamically balanced
The fan motors are Totally Enclosed Air-Over,
current protected. They feature ball bearings that
are double-sealed and permanently lubricated.
Condenser coils are made of a single material to
avoid galvanic corrosion due to dissimilar metals.
Coils and headers are brazed as one piece.
Design Working Pressure 650 PSIG
Integral subcooling included

jOHNSON CONTROLS

Controls:
All controls housed in a NEMA 3R/12 cabinet
with gasket sealed, hinged & latched door
LCD, 40-character display with backlight
Color coded, sealed keypad
Standard controls permit operation from 30 to
115 deg F.

35

Air Cooled Scroll Chiller


Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
36

YLAA-B0070SE
6
Scroll - Hermetic
2

TR
kW
EER
EER
EER
dB(A)
ft

USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in

F
F
ft
cfm
kW

A
A
A

lb
lb
lb
in
in
in

R410A
71.8
84.8
10.2
16
16
87
3.3

Plate Heat Exchanger


5.4
Water
54
44
38.7 / 38.7
171.2
11.4
0.0001
3"

95
122.5 / 122.5
4
0
59329
6.7

460-3-60 / 414-506
160
175
175
1
#4 - 500 kcmil

3578
3623
101
116.1
88.3
94.2
JOHNSON CONTROLS

MODEL: YLAA0070SE46
NOT FOR CONSTRUCTION

Project Name :
YLAA
Location :
Engineer :
Contractor :
For :

88 5/16" - FRAME WIDTH


88 13/16" - OVERALL WIDTH

PRODUCT DRAWING

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT

81 13/16"

ORIGIN

3 1/4"

C
G

Y
X

76 5/8"

23 3/16"

UNIT0

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

732

5 5/8"

1,030

114 11/16" - FRAME LENGTH


121 11/16" - OVERALL LENGTH

23 3/16"

19 5/8"

1,087

774

46 3/8"

Date : 12/18/2012 11:37:46


Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS

46 1/2"

A JOHNSON CONTROLS COMPANY

3" OUTLET

3" INLET

CONTROL PANEL
BOTTOM DETAIL

POWER ENTRY
13" WIDE X 7" HIGH

13/16"

32 3/8"

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 3,578, OPERATING - 3,622.
3. CENTER OF GRAVITY FROM ORIGIN: X= 56.8", Y= 51.3" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

10"

jOHNSON CONTROLS
42 11/16"

5/8" DIA
MOUNTING
HOLES (TYP)

MODEL: YLAA-B0070SE
AHRI CAPACITY 71.8 TONS

YLAA
70 TO 90

37

1 1/16"

Air Cooled Scroll Chiller


Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
38

YLAA-B0080SE
6
Scroll - Hermetic
2

TR
kW
EER
EER
EER
dB(A)
ft

USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in

F
F
ft
cfm
kW

A
A
A

lb
lb
lb
in
in
in

R410A
77.7
94.4
9.9
15.4
15.4
88
3.3

Plate Heat Exchanger


6.7
Water
54
44
38.7 / 39
185.4
9
0.0001
3"

95
126.1 / 122.9
4
0
59329
6.7

460-3-60 / 414-506
173
200
200
1
#4 - 500 kcmil

3898
3954
106
116.1
88.3
94.2
JOHNSON CONTROLS

MODEL: YLAA0080SE46
NOT FOR CONSTRUCTION

Project Name :
YLAA
Location :
Engineer :
Contractor :
For :

88 5/16" - FRAME WIDTH


88 13/16" - OVERALL WIDTH

PRODUCT DRAWING

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT

81 13/16"

ORIGIN

3 1/4"

C
G

Y
X

76 5/8"

23 3/16"

UNIT0

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

750

5 5/8"

1,135

114 11/16" - FRAME LENGTH


121 11/16" - OVERALL LENGTH

23 3/16"

19 5/8"

1,246

822

46 3/8"

Date : 12/18/2012 11:39:31


Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS

46 1/2"

A JOHNSON CONTROLS COMPANY

3" OUTLET

3" INLET

CONTROL PANEL
BOTTOM DETAIL

POWER ENTRY
13" WIDE X 7" HIGH

13/16"

32 3/8"

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 3,898, OPERATING - 3,953.
3. CENTER OF GRAVITY FROM ORIGIN: X= 56.1", Y= 52.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

10"

jOHNSON CONTROLS
42 11/16"

5/8" DIA
MOUNTING
HOLES (TYP)

MODEL: YLAA-B0080SE
AHRI CAPACITY 77.7 TONS

YLAA
70 TO 90

39

1 1/4"

Air Cooled Scroll Chiller


Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
40

YLAA-B0090SE
5
Scroll - Hermetic
2

TR
kW
EER
EER
EER
dB(A)
ft

USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in

F
F
ft
cfm
kW

A
A
A

lb
lb
lb
in
in
in

R410A
83.9
103.4
9.7
15.5
15.5
88
3.3

Plate Heat Exchanger


8.8
Water
54
44
39.4 / 39.4
199.7
7
0.0001
3"

95
126.1 / 127.2
4
0
59329
6.7

460-3-60 / 414-506
192
225
225
1
#4 - 500 kcmil

4169
4241
115
116.1
88.3
94.2
JOHNSON CONTROLS

MODEL: YLAA0090SE46
NOT FOR CONSTRUCTION

Project Name :
YLAA
Location :
Engineer :
Contractor :
For :

88 5/16" - FRAME WIDTH


88 13/16" - OVERALL WIDTH

PRODUCT DRAWING

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT

81 13/16"

3" INLET

3" OUTLET

ORIGIN

3 1/4"

C
G

Y
X

76 5/8"

23 3/16"

UNIT0

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

831

5 5/8"

1,310

114 11/16" - FRAME LENGTH


121 11/16" - OVERALL LENGTH

23 3/16"

19 5/8"

1,285

816

46 3/8"

Date : 12/18/2012 11:52:29


Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS

46 1/2"

A JOHNSON CONTROLS COMPANY

3" OUTLET

3" INLET

CONTROL PANEL
BOTTOM DETAIL

POWER ENTRY
13" WIDE X 7" HIGH

13/16"

32 3/8"

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,169, OPERATING - 4,242.
3. CENTER OF GRAVITY FROM ORIGIN: X= 58.1", Y= 53.7" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

10"

jOHNSON CONTROLS
42 11/16"

5/8" DIA
MOUNTING
HOLES (TYP)

MODEL: YLAA-B0090SE
AHRI CAPACITY 83.9 TONS

YLAA
70 TO 90

41

1 1/16"

Air Cooled Scroll Chiller


Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
42

YLAA-B0091HE
4
Scroll - Hermetic
2

TR
kW
EER
EER
EER
dB(A)
ft

USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in

F
F
ft
cfm
kW

A
A
A

lb
lb
lb
in
in
in

R410A
88.2
98.3
10.8
15
14.9
88
3.3

Plate Heat Exchanger


8.8
Water
54
44
39.2 / 39.2
210.8
7.7
0.0001
3"

95
117.7 / 117.7
6
0
88993
10.1

460-3-60 / 414-506
200
250
225
1
#4 - 500 kcmil

4718
4791
115
142.7
88.3
94.2
JOHNSON CONTROLS

MODEL: YLAA0091HE46
NOT FOR CONSTRUCTION

Project Name :
YLAA
Location :
Engineer :
Contractor :
For :

88 5/16" - FRAME WIDTH


88 13/16" - OVERALL WIDTH

PRODUCT DRAWING

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT

81 13/16"
42 11/16"

ORIGIN

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,718, OPERATING - 4,791.
3. CENTER OF GRAVITY FROM ORIGIN: X= 67.8", Y= 52.1" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

3 1/4"

C
G

884

571

23 5/16"

47 3/8"

UNIT1

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

142 1/4" - FRAME LENGTH


149 5/16" - OVERALL LENGTH

69 3/4"

23 1/8"

7 11/16"

1,290

840

5 5/8"

672

534

46 3/8"

Date : 12/18/2012 11:54:27


Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS

46 1/2"

A JOHNSON CONTROLS COMPANY

3" OUTLET

3" INLET

CONTROL PANEL
BOTTOM DETAIL

POWER ENTRY
13" WIDE X 7" HIGH

13/16"

32 3/8"

jOHNSON CONTROLS
10"

5/8" DIA
MOUNTING
HOLES (TYP)

MODEL: YLAA-B0091HE
AHRI CAPACITY 88.2 TONS

YLAA
91 TO 130

43

1 1/16"

Air Cooled Scroll Chiller


Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
44

YLAA-B0100SE
5
Scroll - Hermetic
2

TR
kW
EER
EER
EER
dB(A)
ft

USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in

F
F
ft
cfm
kW

A
A
A

lb
lb
lb
in
in
in

R410A
95.8
119.1
9.7
14.3
14.3
88
3.3

Plate Heat Exchanger


8.8
Water
54
44
39.6 / 38.5
228.2
9
0.0001
3"

95
122.7 / 123.6
5
0
74161
8.4

460-3-60 / 414-506
223
250
250
1
#4 - 500 kcmil

4791
4864
112
142.7
88.3
94.2
JOHNSON CONTROLS

MODEL: YLAA0100SE46
NOT FOR CONSTRUCTION

Project Name :
YLAA
Location :
Engineer :
Contractor :
For :

88 5/16" - FRAME WIDTH


88 13/16" - OVERALL WIDTH

PRODUCT DRAWING

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT

81 13/16"
42 11/16"

ORIGIN

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,791, OPERATING - 4,863.
3. CENTER OF GRAVITY FROM ORIGIN: X= 69.6", Y= 53.5" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

3 1/4"

C
G

800

542

23 5/16"

47 3/8"

UNIT1

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

142 1/4" - FRAME LENGTH


149 5/16" - OVERALL LENGTH

69 3/4"

23 1/8"

7 11/16"

1,459

836

5 5/8"

703

520

46 3/8"

Date : 12/18/2012 12:55:43


Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS

46 1/2"

A JOHNSON CONTROLS COMPANY

3" OUTLET

3" INLET

CONTROL PANEL
BOTTOM DETAIL

POWER ENTRY
13" WIDE X 7" HIGH

13/16"

32 3/8"

jOHNSON CONTROLS
10"

5/8" DIA
MOUNTING
HOLES (TYP)

MODEL: YLAA-B0100SE
AHRI CAPACITY 95.8 TONS

YLAA
91 TO 130

45

1 1/16"

Air Cooled Scroll Chiller


Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
46

YLAA-B0101HE
5
Scroll - Hermetic
2

TR
kW
EER
EER
EER
dB(A)
ft

USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in

F
F
ft
cfm
kW

A
A
A

lb
lb
lb
in
in
in

R410A
98.5
116.1
10.2
15.4
15.4
89
3.3

Plate Heat Exchanger


8.8
Water
54
44
39.6 / 38.1
234.6
9.4
0.0001
3"

95
125.2 / 117.7
6
0
88993
10.1

460-3-60 / 414-506
227
250
250
1
#4 - 500 kcmil

4954
5026
126
142.7
88.3
94.2
JOHNSON CONTROLS

MODEL: YLAA0101HE46
NOT FOR CONSTRUCTION

Project Name :
YLAA
Location :
Engineer :
Contractor :
For :

88 5/16" - FRAME WIDTH


88 13/16" - OVERALL WIDTH

PRODUCT DRAWING

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT

81 13/16"
42 11/16"

ORIGIN

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,954, OPERATING - 5,027.
3. CENTER OF GRAVITY FROM ORIGIN: X= 69.8", Y= 53.2" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

3 1/4"

C
G

818

560

23 5/16"

47 3/8"

UNIT1

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

142 1/4" - FRAME LENGTH


149 5/16" - OVERALL LENGTH

69 3/4"

23 1/8"

7 11/16"

1,501

875

5 5/8"

728

545

46 3/8"

Date : 12/18/2012 12:58:34


Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS

46 1/2"

A JOHNSON CONTROLS COMPANY

3" OUTLET

3" INLET

CONTROL PANEL
BOTTOM DETAIL

POWER ENTRY
13" WIDE X 7" HIGH

13/16"

32 3/8"

jOHNSON CONTROLS
10"

5/8" DIA
MOUNTING
HOLES (TYP)

MODEL: YLAA-B0101HE
AHRI CAPACITY 98.5 TONS

YLAA
91 TO 130

47

1 1/16"

Air Cooled Scroll Chiller


Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
48

YLAA-B0115SE
4
Scroll - Hermetic
2

TR
kW
EER
EER
EER
dB(A)
ft

USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in

F
F
ft
cfm
kW

A
A
A

lb
lb
lb
in
in
in

R410A
113.9
140.9
9.7
14.6
14.6
88
3.3

Plate Heat Exchanger


8.8
Water
54
44
38.3 / 38.3
272.6
12.4
0.0001
3"

95
124 / 124
6
0
88993
10.1

460-3-60 / 414-506
256
300
300
1
#4 - 500 kcmil

5029
5101
119
142.7
88.3
94.2
JOHNSON CONTROLS

MODEL: YLAA0115SE46
NOT FOR CONSTRUCTION

ORIGIN

81 13/16"
42 11/16"

Project Name : New Project


Location :
Engineer :
Contractor :
For :

88 5/16" - FRAME WIDTH


88 13/16" - OVERALL WIDTH

PRODUCT DRAWING

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 5,029, OPERATING - 5,102.
3. CENTER OF GRAVITY FROM ORIGIN: X= 68", Y= 53.5" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

3 1/4"

C
G

941

582

23 5/16"

47 3/8"

UNIT0

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

142 1/4" - FRAME LENGTH


149 5/16" - OVERALL LENGTH

69 3/4"

23 1/8"

7 11/16"

1,442

866

5 5/8"

728

545

46 1/2"

Date : 12/11/2012 8:18:19


Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS

46 3/8"

A JOHNSON CONTROLS COMPANY

3" OUTLET

3" INLET

CONTROL PANEL
BOTTOM DETAIL

POWER ENTRY
13" WIDE X 7" HIGH

13/16"

32 3/8"

jOHNSON CONTROLS
10"

5/8" DIA
MOUNTING
HOLES (TYP)

MODEL: YLAA-B0115SE
AHRI CAPACITY 113.9 TONS

YLAA
91 TO 130

49

1 1/16"

Air Cooled Scroll Chiller


Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Pressure (Hemispherical Method)
Sound Pressure Measured at
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power
Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Wire Lugs Per Phase
Wire Range (Lug Size)
Weights and Dimensions
Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
50

YLAA-B0120SE
4
Scroll - Hermetic
2

TR
kW
EER
EER
EER
dB(A)
ft

USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in

F
F
ft
cfm
kW

A
A
A

lb
lb
lb
in
in
in

R410A
119.6
143.3
10
14.8
14.8
88
3.3

Plate Heat Exchanger


13.2
Water
54
44
40.6 / 40.6
285.3
8.4
0.0001
3"

95
125.1 / 125.1
6
0
88993
10.1

460-3-60 / 414-506
256
300
300
1
#4 - 500 kcmil

5183
5293
128
142.7
88.3
94.2
JOHNSON CONTROLS

MODEL: YLAA0120SE46
NOT FOR CONSTRUCTION

ORIGIN

81 13/16"
42 11/16"

Project Name : New Project


Location :
Engineer :
Contractor :
For :

88 5/16" - FRAME WIDTH


88 13/16" - OVERALL WIDTH

PRODUCT DRAWING

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 5,183, OPERATING - 5,293.
3. CENTER OF GRAVITY FROM ORIGIN: X= 69.5", Y= 53.2" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

3 1/4"

C
G

937

578

23 5/16"

47 3/8"

UNIT0

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

142 1/4" - FRAME LENGTH


149 5/16" - OVERALL LENGTH

69 3/4"

23 1/8"

7 11/16"

1,486

906

5 5/8"

789

600

46 1/2"

Date : 12/11/2012 8:21:24


Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS

46 3/8"

A JOHNSON CONTROLS COMPANY

3" OUTLET

3" INLET

CONTROL PANEL
BOTTOM DETAIL

POWER ENTRY
13" WIDE X 7" HIGH

13/16"

32 3/8"

jOHNSON CONTROLS
10"

5/8" DIA
MOUNTING
HOLES (TYP)

MODEL: YLAA-B0120SE
AHRI CAPACITY 119.6 TONS

YLAA
91 TO 130

51

1 1/16"

Air Cooled Scroll Chiller


Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Net Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Power
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Min Fluid Flow Rate
Max Fluid Flow Rate
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power

YLAA-B0136SE
6
Scroll - Hermetic
2

TR
kW
EER
EER
EER
dB(A)

USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
USGPM
USGPM

F
F
ft
cfm
kW

Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)

A
A
A
[kA]

Weights and Dimensions


Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
Software Version

lb
lb
lb
in
in
in

R410A
129.9
154.3
10.1
15.5
16.5
93

Plate Heat Exchanger


10
Water
54
44
37.2 / 39.6
310.7
13.4
0.0001
4"
120
625

95
126.9 / 113.2
8
0
120776
13.4

460-3-60 / 414-506
285
300
300
5
1
#4 - 500 kcmil

6103
6187
146
187.7
88.3
94.2
YW13.02a

Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power

52

JOHNSON CONTROLS

MODEL: YLAA0136SE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

88 1/4" - FRAME WIDTH


88 3/4" - OVERALL WIDTH

Y
C
G

23 3/16"

ORIGIN

3 5/16"

Project Name : cg ylaa


Location :
Engineer :
Contractor :
For :

4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN


ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.

3. CENTER OF GRAVITY FROM ORIGIN: X= 82.6"; Y= 51.9" .

2. WEIGHTS (LB): SHIPPING - 6,102; OPERATING - 6,186.

RECOMMENDED MINUMUM CLEARANCES:


SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THAN ONE ADJACENT WALL MAY
BE HIGHER THAN THE UNIT.

1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING


SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION.

94 3/8" - OVERALL HEIGHT


88 1/2" - FRAME HEIGHT

81 5/8"

jOHNSON CONTROLS
X

6 1/2"
69"

58"

59 13/16"

75 1/2"

UNIT1

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

186 1/4" - FRAME LENGTH

5/8" DIA
MOUNTING
HOLES (TYP)

1 3/16"

4" OUTLET

4" INLET

Date : 5/21/2013 15:16:15


Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS

5 3/8"

46 3/8"

A JOHNSON CONTROLS COMPANY

CONTROL PANEL
BOTTOM DETAIL

POWER ENTRY
13" WIDE X 7" HIGH

13/16"

32 3/8"
10"

NOTES:

MODEL: YLAAB0136SE
AHRI CAPACITY 129.9 TONS

YLAA
91 TO 130

53

Air Cooled Scroll Chiller


Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Net Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Power
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Min Fluid Flow Rate
Max Fluid Flow Rate
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power

YLAA-B0142HE
6
Scroll - Hermetic
2

TR
kW
EER
EER
EER
dB(A)

USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
USGPM
USGPM

F
F
ft
cfm
kW

Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)

A
A
A
[kA]

Weights and Dimensions


Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
Software Version

lb
lb
lb
in
in
in

R410A
132.1
152.3
10.4
14.4
16.2
96

Plate Heat Exchanger


13.2
Water
54
44
39.2 / 41.5
315.4
10
0.0001
4"
150
625

95
123.1 / 116.4
8
0
120776
13.4

460-3-60 / 414-506
285
300
300
5
1
#4 - 500 kcmil

6333
6444
157
187.7
88.3
94.2
YW13.02a

Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power

54

JOHNSON CONTROLS

MODEL: YLAA0142HE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

88 1/4" - FRAME WIDTH


88 3/4" - OVERALL WIDTH

Y
C
G

23 3/16"

ORIGIN

3 5/16"

Project Name : cg ylaa


Location :
Engineer :
Contractor :
For :

4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN


ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.

3. CENTER OF GRAVITY FROM ORIGIN: X= 83"; Y= 52.1" .

2. WEIGHTS (LB): SHIPPING - 6,334; OPERATING - 6,444.

RECOMMENDED MINUMUM CLEARANCES:


SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THAN ONE ADJACENT WALL MAY
BE HIGHER THAN THE UNIT.

1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING


SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION.

94 3/8" - OVERALL HEIGHT


88 1/2" - FRAME HEIGHT

81 5/8"

jOHNSON CONTROLS
X

6 1/2"
69"

58"

59 13/16"

75 1/2"

UNIT2

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

186 1/4" - FRAME LENGTH

5/8" DIA
MOUNTING
HOLES (TYP)

1 3/16"

4" OUTLET

4" INLET

Date : 5/21/2013 15:16:37


Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS

5 3/8"

46 3/8"

A JOHNSON CONTROLS COMPANY

CONTROL PANEL
BOTTOM DETAIL

POWER ENTRY
13" WIDE X 7" HIGH

13/16"

32 3/8"
10"

NOTES:

MODEL: YLAAB0142HE
AHRI CAPACITY 132.1 TONS

YLAA
131 TO 175

55

Air Cooled Scroll Chiller


Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Net Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Power
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Min Fluid Flow Rate
Max Fluid Flow Rate
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power

YLAA-B0156HE
5
Scroll - Hermetic
2

TR
kW
EER
EER
EER
dB(A)

USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
USGPM
USGPM

F
F
ft
cfm
kW

Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)

A
A
A
[kA]

Weights and Dimensions


Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
Software Version

lb
lb
lb
in
in
in

R410A
147.3
173.2
10.2
15.5
15.8
97

Plate Heat Exchanger


10
Water
54
44
36.9 / 38.7
351.9
16.7
0.0001
4"
120
625

95
118.8 / 117.1
10
0
150440
16.8

460-3-60 / 414-506
319
350
350
5
1
#4 - 500 kcmil

7269
7353
172
232.7
88.3
94.2
YW13.02a

Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power

56

JOHNSON CONTROLS

MODEL: YLAA0156HE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

88 1/4" - FRAME WIDTH


88 3/4" - OVERALL WIDTH

23 3/16"

ORIGIN

81 5/8"

C
G

Project Name : cg ylaa


Location :
Engineer :
Contractor :
For :

4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN


ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.

3. CENTER OF GRAVITY FROM ORIGIN: X= 95.8"; Y= 51.2" .

2. WEIGHTS (LB): SHIPPING - 7,269; OPERATING - 7,352.

RECOMMENDED MINUMUM CLEARANCES:


SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THAN ONE ADJACENT WALL MAY
BE HIGHER THAN THE UNIT.

3 5/16"

1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING


SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION.

94 3/8" - OVERALL HEIGHT


88 1/2" - FRAME HEIGHT

jOHNSON CONTROLS
X

7 11/16"
69"

58"

UNIT3

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

230 1/4" - FRAME LENGTH

43"

42 1/2"

5/8" DIA
MOUNTING
HOLES (TYP)

82 7/8"

93 5/8"

1 3/8"
4" OUTLET

4" INLET

13/16"

Date : 5/21/2013 15:16:58


Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS

46 3/8"

A JOHNSON CONTROLS COMPANY

5 3/8"

CONTROL PANEL
BOTTOM DETAIL

POWER ENTRY
13" WIDE X 7" HIGH

32 3/8"
10"

NOTES:

MODEL: YLAAB0156SE
AHRI CAPACITY 147.3 TONS

YLAA
131 TO 175

57

Air Cooled Scroll Chiller


Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Net Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Power
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Min Fluid Flow Rate
Max Fluid Flow Rate
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power

YLAA-B0170SE
6
Scroll - Hermetic
2

TR
kW
EER
EER
EER
dB(A)

USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
USGPM
USGPM

F
F
ft
cfm
kW

Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)

A
A
A
[kA]

Weights and Dimensions


Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
Software Version

lb
lb
lb
in
in
in

R410A
170.5
208.6
9.8
15.1
15.9
97

Plate Heat Exchanger


10
Water
54
44
37 / 37
407.4
22.1
0.0001
4"
120
625

95
121.3 / 121.3
10
0
150440
16.8

460-3-60 / 414-506
372
400
400
5
2
#4 - 500 kcmil

7624
7708
179
232.7
88.3
94.2
YW13.02a

Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power

58

JOHNSON CONTROLS

MODEL: YLAA0170SE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

88 1/4" - FRAME WIDTH


88 3/4" - OVERALL WIDTH

23 3/16"

ORIGIN

81 5/8"

C
G

Project Name : cg ylaa


Location :
Engineer :
Contractor :
For :

4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN


ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.

3. CENTER OF GRAVITY FROM ORIGIN: X= 97.1"; Y= 52.2" .

2. WEIGHTS (LB): SHIPPING - 7,624; OPERATING - 7,707.

RECOMMENDED MINUMUM CLEARANCES:


SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THAN ONE ADJACENT WALL MAY
BE HIGHER THAN THE UNIT.

3 5/16"

1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING


SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION.

94 3/8" - OVERALL HEIGHT


88 1/2" - FRAME HEIGHT

jOHNSON CONTROLS
X

7 11/16"
69"

58"

UNIT4

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

230 1/4" - FRAME LENGTH

43"

42 1/2"

5/8" DIA
MOUNTING
HOLES (TYP)

82 7/8"

93 5/8"

1 3/8"
4" OUTLET

4" INLET

13/16"

Date : 5/21/2013 15:17:18


Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS

46 3/8"

A JOHNSON CONTROLS COMPANY

5 3/8"

CONTROL PANEL
BOTTOM DETAIL

POWER ENTRY
13" WIDE X 7" HIGH

32 3/8"
10"

NOTES:

MODEL: YLAAB0170SE
AHRI CAPACITY 170.5 TONS

YLAA
131 TO 175

59

Air Cooled Scroll Chiller


Performance Specification
Unit Type and Size
ID
Number of Compressors
Compressor Type
Number of Compressor Circuits
Technical Data
Refrigerant Type
Net Cooling Capacity
Total Power Input
EER
IPLV
NPLV
Sound Power
Evaporator
Evaporator Type
Fluid Volume
Fluid Type
Entering Liquid Temperature
Leaving Liquid Temperature
EvaporatingTemperature
Total Flow Rate
Total Pressure Drop
Fouling Factor
Fluid Connection Diameter
Min Fluid Flow Rate
Max Fluid Flow Rate
Condenser (Air Cooled)
Ambient Air Temperature
Condensing Temperature
Number of Fans
Altitude
Total Air Flow
Total Fan Power

YLAA-B0175HE
6
Scroll - Hermetic
2

TR
kW
EER
EER
EER
dB(A)

USGAL
F
F
F
USGPM
ft H2O
h.ft.F/Btu
in
USGPM
USGPM

F
F
ft
cfm
kW

Electrical Data
Nominal Voltage / Voltage Limits
Min. Circuit Ampacity
Max. Fuse / CB Rating
Min. Fuse / CB Rating
Unit Short Circuit Current Withstand
Wire Lugs Per Phase
Wire Range (Lug Size)

A
A
A
[kA]

Weights and Dimensions


Shipping Weight
Operating Weight
Refrigerant Charge
Overall Length
Overall Width
Overall Height
Software Version

lb
lb
lb
in
in
in

R410A
176
211.1
10
15.1
16
97

Plate Heat Exchanger


14.3
Water
54
44
39.6 / 39.6
420
16.4
0.0001
4"
180
650

95
122 / 122
10
0
150440
16.8

460-3-60 / 414-506
372
400
400
5
2
#4 - 500 kcmil

7772
7891
187
232.7
88.3
94.2
YW13.02a

Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power

60

JOHNSON CONTROLS

MODEL: YLAA0175HE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

88 1/4" - FRAME WIDTH


88 3/4" - OVERALL WIDTH

23 3/16"

ORIGIN

81 5/8"

C
G

Project Name : cg ylaa


Location :
Engineer :
Contractor :
For :

4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN


ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.

3. CENTER OF GRAVITY FROM ORIGIN: X= 97.4"; Y= 52" .

2. WEIGHTS (LB): SHIPPING - 7,771; OPERATING - 7,890.

RECOMMENDED MINUMUM CLEARANCES:


SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THAN ONE ADJACENT WALL MAY
BE HIGHER THAN THE UNIT.

3 5/16"

1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING


SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION.

94 3/8" - OVERALL HEIGHT


88 1/2" - FRAME HEIGHT

jOHNSON CONTROLS
X

7 11/16"
69"

58"

UNIT5

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

230 1/4" - FRAME LENGTH

43"

42 1/2"

5/8" DIA
MOUNTING
HOLES (TYP)

82 7/8"

93 5/8"

1 3/8"
4" OUTLET

4" INLET

13/16"

Date : 5/21/2013 15:17:39


Rev. Date :
Form :
Dwg. Lev. :
Dwg. Scale : NTS

46 3/8"

A JOHNSON CONTROLS COMPANY

5 3/8"

CONTROL PANEL
BOTTOM DETAIL

POWER ENTRY
13" WIDE X 7" HIGH

32 3/8"
10"

NOTES:

MODEL: YLAAB0175HE
AHRI CAPACITY 176 TONS

YLAA
131 TO 175

61

62

JOHNSON CONTROLS

YVAA

150 to 500 Tons


Air Cooled Screw Chiller

jOHNSON CONTROLS

63

YVAA RIGGING
Lifting Unit
Container lugs should be inserted into the holes provided in the bottom of the frame rail.
Use spreader bars to avoid lifting chains hitting the chiller. Various methods of spreader bar arrangements may
be used; keeping in mind the intent is to keep the unit stable and to keep the chains from hitting the chiller and
causing damage.
WARNING Never lift the chiller using a forklift or by hooking the top rails. Use only the lifting
holes provided.
Lifting instructions are placed on a label on the chiller and on the shipping bag.

64

JOHNSON CONTROLS

Delivery and Storage


To ensure consistent quality and maximum reliability, all units are tested and inspected before leaving the factory.
Units are shipped completely assembled and containing refrigerant under pressure. Units are shipped without
export crating unless crating has been specified on the Sales Order.
If the unit is to be put into storage, prior to installation, the following precautions should be observed.
The chiller must be blocked so that the base is not permitted to sag or bow.
Ensure that all openings, such as water connections, are securely capped.
Do not store where exposed to ambient air temperatures exceeding 43C (110F).
The condensers should be covered to protect the coils and fins from potential damage and corrosion,
particularly where building work is in progress.
The unit should be stored in a location where there is minimal activity in order to limit the risk of accidental
physical damage.
To prevent inadvertent operation of the pressure relief devices the unit must not be steam cleaned.
It is recommended that the unit is periodically inspected during storage.
Inspection
Remove any transit packing and inspect the unit to ensure that all components have been delivered and that no
damage has occurred during transit. If any damage is evident, it should be noted on the carriers freight bill and a
claim entered in accordance with the instructions given on the advice note.
Major damage must be reported immediately to your local Johnson Controls representative.
Moving the Chiller
Prior to moving the unit, ensure that the installation site is suitable for installing the unit and is easily capable of supporting the weight of the unit and all associated services.
The units are designed to be lifted using shackles or safety hooks. A spreader bar or frame should be used in
order to prevent damage to the unit from the lifting chains. (Refer to Figure 4 on Page 20 of the Operations and
Maintenance Guide [Form 201.28-NM1.1 (812)] for hooks.)
Units are provided with lifting eyes in the sites of the base frame, which can be attached directly using container
lugs, shackles or safety hooks (Refer to Figure 4 on Page 20 of the Operations and Maintenance Guide [Form
201.28-NM1.1 (812)] for proper lifting illustration).
WARNING The unit must only be lifted by the base frame at the points provided. Never move the
unit on rollers, or lift the unit using a forklift truck.
Care should be taken to avoid damaging the condenser cooling fins when moving the unit.
Lifting Weights
For details of weights and weight distribution, refer to the data shipped in the chiller information packet and unit
nameplate.

jOHNSON CONTROLS

65

AIR COOLED SCREW CHILLER


YVAA - 150 to 500 TONS (R-134A)

BENEFITS
Continuous function, microprocessor controlled Variable Speed Drive (VSD) for valve less, smooth capacity
control to 10% of chiller capacity
Chiller speed matched to system requirements at off-peak conditions resulting in lower energy usage
Use of VSD reduces compressor moving parts by 50%
Soft motor start with no electrical inrush reduces components stress, heat buildup
Operating efficiencies at off-design conditions results in IPLVs as high as 19.8 EER
Standard full load power factor of 95%, maintained throughout operating range resulting in improved
energy savings
Superior acoustic operation at off-design conditions
HFC-R134a standard for long term availability and zero ODP
Wide range of options to fit any design requirement
Competitors MCA is an average of 10% higher than YORKs
Lower MCA allows for smaller wiring and smaller circuit breakers therefore lower costs
Allows for replacing chiller and increasing tonnage without replacing electrical components
Industrys only 18-month air cooled warranty that covers all parts.
UPGRADE OPTIONS
Remote Cooler
Factory mounted non-fused disconnect switch or circuit breaker
Epoxy Post Coated, Pre Coated or Post Coated for tube and fin
Seamless internally enhanced copper fin & tube coils arranged in staggered rows; mechanically bonded to
full eight aluminum fins
Evaporator Options:

1-1/2" Insulation (double thickness)

Raised Face Flange Accessory for cooler nozzles
Flow Switch Accessory: Vapor proof, SPDT, NEMA 3R switch, 150psig
Suction service isolation valve per circuit (discharge valve standard)
Unit Enclosure Options:

Wire Panels (full unit): coated, heavy gauge welded wire mesh mounted on exterior of unit to prevent
unauthorized access to refrigerant components

Louvered Panels (condenser coils only): Painted to match unit; louvered panels mounted over exterior
condenser coils faces to visually screen unit, protects coils

Louvered Panels (full unit): Painted to match unit; to protect condenser coils, visually screen internal
components and prevent unauthorized access

Louvered (condensers)/Wire Panels (mechanicals): Louvered steel panels on external condenser coil
faces, heavy-gauge welded-wire mesh around base to prevent unauthorized access
Sound Attenuation:
SilentNightTM controls to force lower sound levels on demand or per user schedule
Ultra quiet fans, compressor sound blankets and/or acoustical enclosures
Vibration Isolation: Neoprene, 1" spring isolators or 2" spring isolators

66

JOHNSON CONTROLS

AIR COOLED SCREW CHILLER


YVAA - 150 to 500 TONS

PACKAGE DESCRIPTION:

Evaporator:

Self contained, designed for outdoor installation


Baked on powder paint
Heavy gauge, formed galvanized steel base
Factory mounted control transformer
ARI-Standard 550/590-11 Rated & Certified
All exposed wiring routed through liquid-tight,
non-metallic conduit

High efficiency Hybrid falling film cooler;


refrigerant in shell and water in tubes
Removable heads to access copper tubes
Air vent and water drain connections
Heater protection to -20 deg. F ambient
Insulated with " closed cell foam
Design working pressure 150 PSIG water side
and 235 PSIG on refrigerant side

Compressors:
Reliable VSD driven semi-hermetic twin screw
High efficiency, accessible hermetic motor with
redundant overload protection
Temperature actuated body cartridge heater
Acoustically tuned discharge gas muffler
Design pressure of compressor 450 PSIG
Condenser:
Low noise, full airflow cross section fans for
maximum efficiency; statically & dynamically balanced for low vibration operation; positioned in
extended orifices for low sound
High efficiency, direct drive, 3-phase totally
enclosed fan motors with double sealed, permanently lubricated ball bearings
Condenser coils are made of a single material to
avoid galvanic corrosion due to dissimilar metals.
Coils and headers are brazed as one piece
Design Working Pressure 450 PSIG
Electrical:
Competitors MCA is an average of 10% higher
than YORKs
Lower MCA allows for smaller wiring and smaller
circuit breakers therefore lower costs
Allows for replacing chiller and increasing tonnage without replacing electrical components

jOHNSON CONTROLS

Refrigerant circuit:
Independent circuits per compressor
Computer controlled bending of refrigerant pipe
reduces over 60% of pipe brazed joints
Liquid line components include: manual shutoff
valve with charging port, removable core filterdrier, solenoid valve, sight glass with moisture
indicator, electronic expansion valves
Discharge line proided with manual compressor
shutoff service valve
External Oil separators with no moving parts, 450
PSIG design working pressure
Controls:
All controls housed in a NEMA 3R cabinet with
gasket sealed, hinged & latched door
VSD section includes dedicated inverter for each
compressor
Control display accessible without opening main
cabinet doors
LCD, 80-character display with backlight
Color coded, sealed keypad
Standard controls permit operation from 0 to
125 deg F ambient temperature

67

Air Cooled Screw Chiller


Performance Specification
Unit Tag

Qty.

Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YVAA0153BAF46

150.0

460/3/60

R134a

Pin:

BASE MODEL

POWER

CONTROLS

PIPING

COMP

EVAPORATOR

COND

CABINET

MISC

WARR

YVAA0153BAF46BA VSXX XTAXLXXXX60 44XOXXX S189W 1SXXA2B MXF PXXXX XXXX BXSX

10

15

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)

20

54.0
44.0
359.6
5.6
Water
0.00010
58.0

25

30

35

40

45

Evaporator Data (Cont.)


Min. Flow Rate (gpm)
Max. Flow Rate (gpm)

250.0
950.0

Condenser Data
Ambient Temp. Design (F)
Altitude (ft.)
Ambient Temp. Min (F)

95.0
0
0.0

Circuit

55

60

65

Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)

Electrical Data
2
109
4/3.3

1
109
4/3.3

Compressor RLA
Fan QTY/FLA (each)

50

10.1 / 3.0
15.1 / 4.4
10 %
11518
11979

Single Point
Min. Circuit Ampacity

275

Recommended Fuse/CB Rating


Max. Inverse Time CB Rating

350
350

Max. Dual Element Fuse Size (Amps)


Unit Short Circuit Withstand (STD)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Unit Power Factor
Control KVA
Starter Type

Notes:

350
30kA
2
#2 - 600 KCM
0.95
2.0
VSD

Operating Condition Electrical Data


Compressor kW
162.6
Total Fan kW
14.8
Total kW
177.4

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0

Part Load Rating Data


Capacity (Tons)
150.0
112.5
75.0
37.5

Ambient (F)
95.0
80.0
65.0
55.0

Unit Efficiency
10.1 / 3.0
13.3 / 3.9
16.3 / 4.8
17.6 / 5.2

Compressor kW
162.6
86.2
43.0
18.2

SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0153BAF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0

Ambient (F)
95.0
80.0
65.0
55.0

63
95.0
95.0
94.0
91.0

125
95.0
95.0
94.0
91.0

250
96.0
96.0
95.0
92.0

500
98.0
95.0
94.0
91.0

1K
95.0
92.0
91.0
88.0

2K
87.0
86.0
85.0
82.0

4K
83.0
82.0
81.0
78.0

8K
78.0
78.0
77.0
73.0

LWA
99.0
97.0
96.0
92.0

2K
60.0
59.0
58.0
55.0

4K
56.0
55.0
54.0
51.0

8K
51.0
51.0
50.0
46.0

dBA
72.0
70.0
69.0
65.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0153BAF46 ( Equipped with Low Sound Fans )
Load %
Ambient (F)
63
125
250
500
100.0
95.0
68.0
68.0
69.0
71.0
75.0
80.0
68.0
68.0
69.0
68.0
50.0
65.0
67.0
67.0
68.0
67.0
25.0
55.0
64.0
64.0
65.0
64.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

1K
68.0
65.0
64.0
61.0

Performance at AHRI Conditions


YVAA0153BAF46
Evaporator Data
EWT (F)
54.0
LWT (F)
44.0
Flow Rate (gpm)
359.6
Pressure Drop (ft.)
5.6
Fluid
Water
Fouling Factor
0.00010
Water Volume (gal)
58.0

Condenser Data
Ambient Temp. (F)
Altitude (ft.)

95.0
0

Performance Data
EER / COP
10.1 / 3.0
EER IPLV/COP IPLV
15.1 / 4.4
Capacity (Tons)
150.0

If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.

68

JOHNSON CONTROLS

15 1/8"

AIR-COOLED SCREW CHILLER


MODEL: YVAA0153BAF46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

POWER: SINGLE POINT WITH TERMINAL BLOCK

88 3/16"

44 1/8"

Project Name : stp


Location :
Engineer :
Contractor :
For :

26 9/16"

6" (WATER INLET)

C
G

Y
X

780

644

2,116

2,147

75 15/16"

(4) RIGGING HOLES


EACH SIDE 3 X 2

48 11/16"

6 15/16"

56 1/8"

41 1/4"

62 9/16"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

203 1/4"

71 1/4"

2,116

2,147

3/4" MOUNTING HOLES (TYP)

1,052

978

VSD / POWER PANEL

jOHNSON CONTROLS

6" (WATER OUTLET)

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 11,518, OPERATING - 11,980.
3. CENTER OF GRAVITY FROM ORIGIN: X= 101.8", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
14 1/8"

18 1/4"

47 5/16"

10 3/8"

60"

94 1/2"

4"

VIEW B-B

12"

VIEW A-A

2 15/16"

CONTROL ENTRY
3" WIDE X 11 1/2" HIGH

POWER ENTRY IS ON BOTTOM OF PANEL

1 1/2"

POWER ENTRY
10" WIDE X 13" HIGH

Date : 12/6/2012 11:43:34


Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS

A JOHNSON CONTROLS COMPANY

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

1 3/8" (TYP)

MODEL: YVAA0153BAF46
AHRI CAPACITY 150.0 TONS

YVAA
150 TO 200

69

Air Cooled Screw Chiller


Performance Specification
Unit Tag

Qty.

Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YVAA0183ABF46

175.0

460/3/60

R134a

Pin:

BASE MODEL

POWER

CONTROLS

PIPING

COMP

EVAPORATOR

COND

CABINET

MISC

WARR

YVAA0183ABF46BA VSXX XTAXLXXXX60 44XOXXX S192W 1SXXA2B MXF PXXXX XXXX BXSX

10

15

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)

20

54.0
44.0
419.5
11.4
Water
0.00010
48.0

25

30

35

40

45

Evaporator Data (Cont.)


Min. Flow Rate (gpm)
Max. Flow Rate (gpm)

200.0
750.0

Condenser Data
Ambient Temp. Design (F)
Altitude (ft.)
Ambient Temp. Min (F)

95.0
0
0.0

Circuit

55

60

65

Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)

Electrical Data
2
111
4/3.3

1
139
6/3.3

Compressor RLA
Fan QTY/FLA (each)

50

10.4 / 3.0
15.4 / 4.5
10 %
12019
12460

Single Point
Min. Circuit Ampacity

322

Recommended Fuse/CB Rating


Max. Inverse Time CB Rating

450
450

Max. Dual Element Fuse Size (Amps)


Unit Short Circuit Withstand (STD)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Unit Power Factor
Control KVA
Starter Type

Notes:

450
30kA
2
#2 - 600 KCM
0.95
2.0
VSD

Operating Condition Electrical Data


Compressor kW
184.4
Total Fan kW
17.9
Total kW
202.4

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0

Part Load Rating Data


Capacity (Tons)
175.0
131.3
87.5
43.7

Ambient (F)
95.0
80.0
65.0
55.0

Unit Efficiency
10.4 / 3.0
13.5 / 4.0
16.5 / 4.8
17.9 / 5.2

Compressor kW
184.4
97.8
49.4
22.0

SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0183ABF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0

Ambient (F)
95.0
80.0
65.0
55.0

63
96.0
96.0
94.0
91.0

125
96.0
96.0
95.0
91.0

250
97.0
97.0
95.0
92.0

500
98.0
96.0
95.0
91.0

1K
94.0
94.0
91.0
88.0

2K
88.0
87.0
86.0
82.0

4K
84.0
83.0
82.0
78.0

8K
80.0
79.0
78.0
73.0

LWA
99.0
98.0
96.0
93.0

2K
61.0
60.0
59.0
55.0

4K
57.0
56.0
55.0
51.0

8K
53.0
52.0
51.0
46.0

dBA
72.0
71.0
69.0
66.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0183ABF46 ( Equipped with Low Sound Fans )
Load %
Ambient (F)
63
125
250
500
100.0
95.0
69.0
69.0
70.0
71.0
75.0
80.0
69.0
69.0
70.0
69.0
50.0
65.0
67.0
68.0
68.0
68.0
25.0
55.0
64.0
64.0
65.0
64.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

1K
67.0
67.0
64.0
61.0

Performance at AHRI Conditions


YVAA0183ABF46
Evaporator Data
EWT (F)
54.0
LWT (F)
44.0
Flow Rate (gpm)
419.5
Pressure Drop (ft.)
11.4
Fluid
Water
Fouling Factor
0.00010
Water Volume (gal)
48.0

Condenser Data
Ambient Temp. (F)
Altitude (ft.)

95.0
0

Performance Data
EER / COP
10.4 / 3.0
EER IPLV/COP IPLV
15.4 / 4.5
Capacity (Tons)
175.0

If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.

70

JOHNSON CONTROLS

14 1/8"

AIR-COOLED SCREW CHILLER


MODEL: YVAA0183ABF46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

POWER: SINGLE POINT WITH TERMINAL BLOCK

88 3/16"

44 1/8"

Project Name : stp


Location :
Engineer :
Contractor :
For :

25 9/16"

6" (WATER INLET)

C
G

Y
X

38 3/4"

47 5/8"

1,654

1,659

247"

82 13/16"

(4) RIGGING HOLES


EACH SIDE 3 X 2

1,084

1,088

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

77 1/4"

1,084

1,729
46 3/4"

1,088

17 11/16"
1,660

3/4" MOUNTING HOLES (TYP)

42 1/16"

66 1/8"

711

704

VSD / POWER PANEL

jOHNSON CONTROLS

6" (WATER OUTLET)

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 12,019, OPERATING - 12,460.
3. CENTER OF GRAVITY FROM ORIGIN: X= 128.4", Y= 44.2".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
14 1/8"

94 1/2"

4"

VIEW B-B

12"

VIEW A-A

2 15/16"

CONTROL ENTRY
3" WIDE X 11 1/2" HIGH

POWER ENTRY IS ON BOTTOM OF PANEL

1 1/2"

POWER ENTRY
10" WIDE X 13" HIGH

Date : 12/6/2012 11:51:6


Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS

A JOHNSON CONTROLS COMPANY

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

18 1/4"

47 5/16"

10 3/8"

60"

1 1/4" (TYP)

MODEL: YVAA0183ABF46
AHRI CAPACITY 175.0 TONS

YVAA
150 TO 200

71

Air Cooled Screw Chiller


Performance Specification
Unit Tag

Qty.

Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YVAA0233BEF46

200.0

460/3/60

R134a

Pin:

BASE MODEL

POWER

CONTROLS

PIPING

COMP

EVAPORATOR

COND

CABINET

MISC

WARR

YVAA0233BEF46BA VSXX XTAXLXXXX60 44XOXXX S176W 1SXXA2B MXF PXXXX XXXX BXSX

10

15

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)

20

54.0
44.0
479.4
9.2
Water
0.00010
58.0

25

30

35

40

45

Evaporator Data (Cont.)


Min. Flow Rate (gpm)
Max. Flow Rate (gpm)

250.0
950.0

Condenser Data
Ambient Temp. Design (F)
Altitude (ft.)
Ambient Temp. Min (F)

95.0
0
0.0

Circuit

55

60

65

Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)

Electrical Data
2
135
5/3.3

1
158
7/3.3

Compressor RLA
Fan QTY/FLA (each)

50

10.5 / 3.1
15.2 / 4.5
10 %
13288
13750

Single Point
Min. Circuit Ampacity

375

Recommended Fuse/CB Rating


Max. Inverse Time CB Rating

500
500

Max. Dual Element Fuse Size (Amps)


Unit Short Circuit Withstand (STD)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Unit Power Factor
Control KVA
Starter Type

Notes:

500
30kA
2
#2 - 600 KCM
0.95
2.0
VSD

Operating Condition Electrical Data


Compressor kW
208.4
Total Fan kW
21.1
Total kW
229.4

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0

Part Load Rating Data


Capacity (Tons)
200.0
150.0
100.0
50.0

Ambient (F)
95.0
80.0
65.0
55.0

Unit Efficiency
10.5 / 3.1
13.5 / 4.0
16.2 / 4.7
17.3 / 5.1

Compressor kW
208.4
111.2
56.5
23.9

SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0213ADF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0

Ambient (F)
95.0
80.0
65.0
55.0

63
97.0
97.0
96.0
93.0

125
97.0
97.0
96.0
93.0

250
98.0
98.0
97.0
94.0

500
97.0
97.0
96.0
94.0

1K
94.0
93.0
93.0
90.0

2K
88.0
88.0
87.0
84.0

4K
84.0
84.0
83.0
80.0

8K
80.0
80.0
78.0
76.0

LWA
99.0
99.0
97.0
95.0

2K
61.0
61.0
60.0
57.0

4K
57.0
57.0
56.0
53.0

8K
53.0
53.0
51.0
49.0

dBA
72.0
72.0
70.0
68.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0213ADF46 ( Equipped with Low Sound Fans )
Load %
Ambient (F)
63
125
250
500
100.0
95.0
70.0
70.0
71.0
70.0
75.0
80.0
70.0
70.0
71.0
70.0
50.0
65.0
69.0
69.0
70.0
69.0
25.0
55.0
66.0
66.0
67.0
67.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

1K
67.0
66.0
66.0
63.0

Performance at AHRI Conditions


YVAA0213ADF46
Evaporator Data
EWT (F)
54.0
LWT (F)
44.0
Flow Rate (gpm)
479.4
Pressure Drop (ft.)
9.2
Fluid
Water
Fouling Factor
0.00010
Water Volume (gal)
58.0

Condenser Data
Ambient Temp. (F)
Altitude (ft.)

95.0
0

Performance Data
EER / COP
10.5 / 3.1
EER IPLV/COP IPLV
15.2 / 4.5
Capacity (Tons)
200.0

If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.

72

JOHNSON CONTROLS

15 1/8"

AIR-COOLED SCREW CHILLER


MODEL: YVAA0233BEF46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

POWER: SINGLE POINT WITH TERMINAL BLOCK

88 3/16"

44 1/8"

Project Name : stp


Location :
Engineer :
Contractor :
For :

26 9/16"

6" (WATER INLET)

C
G

Y
X

670

659

57 5/8"

72 5/16"

73 5/16"

670

659

38 3/4"

933

1,430

291 3/16"

76 13/16"

41 5/8"

947

1,423

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

77 5/8"

(5) RIGGING HOLES


EACH SIDE 3 X 2

51 3/4"

2,247

2,230

3/4" MOUNTING HOLES (TYP)

42 1/16"

66 1/8"

947

933

VSD / POWER PANEL

jOHNSON CONTROLS

6" (WATER OUTLET)

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 13,288, OPERATING - 13,750.
3. CENTER OF GRAVITY FROM ORIGIN: X= 134.7", Y= 44.1".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
14 1/8"

94 1/2"

4"

VIEW B-B

12"

VIEW A-A

2 15/16"

CONTROL ENTRY
3" WIDE X 11 1/2" HIGH

POWER ENTRY IS ON BOTTOM OF PANEL

1 1/2"

POWER ENTRY
10" WIDE X 13" HIGH

Date : 12/6/2012 12:52:26


Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS

A JOHNSON CONTROLS COMPANY

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

18 1/4"

47 5/16"

10 3/8"

60"

1 1/4" (TYP)

MODEL: YVAA0233BEF46
AHRI CAPACITY 200.0 TONS

YVAA
150 TO 200

73

Air Cooled Screw Chiller


Performance Specification
Unit Tag

Qty.

Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YVAA0273DGF46

250.0

460/3/60

R134a

Pin:

BASE MODEL

POWER

CONTROLS

PIPING

COMP

EVAPORATOR

COND

CABINET

MISC

WARR

YVAA0273DGF46BA VSXX XTAXLXXXX60 44XOXXX S188W 1SXXA2B MXF XXXXX XXXX BXSX

10

15

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)

20

54.0
44.0
598.3
15.2
Water
0.00010
82.0

25

30

35

40

45

Evaporator Data (Cont.)


Min. Flow Rate (gpm)
300.0
Max. Flow Rate (gpm)
1150.0
Condenser Data
Ambient Temp. Design (F)
Altitude (ft.)
Ambient Temp. Min (F)

Circuit

55

60

65

Performance Data
EER / COP
NPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)

Electrical Data
2
175
7/3.3

1
175
7/3.3

Compressor RLA
Fan QTY/FLA (each)

95.0
0
0.0

50

10.8 / 3.2
16.0 / 4.7
10 %
16275
17103

Single Point
Min. Circuit Ampacity

444

Recommended Fuse/CB Rating


Max. Inverse Time CB Rating

600
600

Max. Dual Element Fuse Size (Amps)


Unit Short Circuit Withstand (STD)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Unit Power Factor
Control KVA
Starter Type

Notes:

600
30kA
2
#2 - 600 KCM
0.95
2.0
VSD

Operating Condition Electrical Data


Compressor kW
253.5
Total Fan kW
24.2
Total kW
277.7

* Use Copper Conductors only

Load %
100.0
75.0
50.0
25.0

Part Load Rating Data


Capacity (Tons)
250.0
187.5
125.0
62.5

Ambient (F)
95.0
80.0
65.0
55.0

Unit Efficiency
10.8 / 3.2
14.0 / 4.1
17.2 / 5.0
18.9 / 5.5

Compressor kW
253.5
135.2
68.3
29.0

SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0273DGF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0

Ambient (F)
95.0
80.0
65.0
55.0

63
97.0
97.0
96.0
93.0

125
97.0
97.0
96.0
93.0

250
98.0
98.0
97.0
94.0

500
97.0
97.0
96.0
94.0

1K
94.0
93.0
93.0
90.0

2K
88.0
88.0
87.0
84.0

4K
84.0
84.0
83.0
80.0

8K
80.0
80.0
78.0
76.0

LWA
99.0
99.0
97.0
95.0

2K
63.0
62.0
61.0
58.0

4K
59.0
58.0
57.0
54.0

8K
54.0
53.0
52.0
49.0

dBA
74.0
72.0
71.0
68.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0213ADF46 ( Equipped with Low Sound Fans )
Load %
Ambient (F)
63
125
250
500
100.0
95.0
71.0
71.0
72.0
73.0
75.0
80.0
71.0
71.0
72.0
71.0
50.0
65.0
69.0
69.0
70.0
70.0
25.0
55.0
66.0
67.0
67.0
67.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

1K
70.0
67.0
66.0
63.0

Performance at AHRI Conditions


YVAA0273DGF46
Evaporator Data
EWT (F)
54.0
LWT (F)
44.0
Flow Rate (gpm)
599.8
Pressure Drop (ft.)
15.3
Fluid
Water
Fouling Factor
0.00010
Water Volume (gal)
82.0

Condenser Data
Ambient Temp. (F)
Altitude (ft.)

95.0
0

Performance Data
EER / COP
10.8 / 3.2
EER IPLV/COP IPLV
16.0 / 4.7
Capacity (Tons)
249.9

If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.

74

JOHNSON CONTROLS

44 1/8"

15 5/16"

AIR-COOLED SCREW CHILLER


MODEL: YVAA0273DGF46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

POWER: SINGLE POINT WITH TERMINAL BLOCK

88 3/16"

26 3/4"

59 1/8"

Project Name : adsfasdfa


Location :
Engineer :
Contractor :
For :

6" (WATER INLET)

C
G

1,518

1,389

1,946

2,135

83 1/4"

(6) RIGGING HOLES


EACH SIDE 3 X 2

100 5/16"

42 7/8"

60 3/16"
335 3/16"

79 13/16"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

40 3/16"

3,036

2,778

48 5/16"

1,372

1,539

3/4" MOUNTING HOLES (TYP)

60 1/4"

70 5/8"

710

14 1/8"

12 3/8"

47 1/2"

10 3/8"

60"

4"

VIEW B-B

POWER ENTRY
10" WIDE X 13" HIGH

12"

VIEW A-A

2 15/16"

CONTROL ENTRY
3" WIDE X 11 1/2" HIGH

POWER ENTRY IS ON BOTTOM OF PANEL

1 1/2"

94 11/16"

1 5/16" (TYP)

Date : 3/6/2013 8:56:2


Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS

A JOHNSON CONTROLS COMPANY

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

681

VSD / POWER PANEL

jOHNSON CONTROLS

6" (WATER OUTLET)

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 16,275, OPERATING - 17,103.
3. CENTER OF GRAVITY FROM ORIGIN: X= 168.3", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.

MODEL: YVAA0273DGF46
AHRI CAPACITY 250.0 TONS

YVAA
201 TO 500

75

Air Cooled Screw Chiller


Performance Specification
Unit Tag

Qty.

Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YVAA0343EKF46

300.0

460/3/60

R134a

Pin:

BASE MODEL

POWER

CONTROLS

PIPING

COMP

EVAPORATOR

COND

CABINET

MISC

WARR

YVAA0343EKF46BA VSXX XTAXLXXXX60 44XOXXX S179W 1SXXA2B MXF PXXXX XXXX BXSX

10

15

20

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)

54.0
44.0
719.1
11.8
Water
0.00010
113.0

25

30

35

40

45

Evaporator Data (Cont.)


Min. Flow Rate (gpm)
400.0
Max. Flow Rate (gpm)
1500.0
Condenser Data
Ambient Temp. Design (F)
Altitude (ft.)
Ambient Temp. Min (F)

Circuit

55

60

65

Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)

Electrical Data
2
209
9/3.3

1
209
9/3.3

Compressor RLA
Fan QTY/FLA (each)

95.0
0
0.0

50

10.9 / 3.2
15.5 / 4.5
10 %
19315
20175

Single Point
Min. Circuit Ampacity

533

Recommended Fuse/CB Rating


Max. Inverse Time CB Rating

700
700

Max. Dual Element Fuse Size (Amps)


Unit Short Circuit Withstand (STD)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Unit Power Factor
Control KVA
Starter Type

Notes:

700
30kA
3
#2 - 600 KCM
0.95
2.0
VSD

Operating Condition Electrical Data


Compressor kW
300.3
Total Fan kW
30.5
Total kW
330.8

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0

Part Load Rating Data


Capacity (Tons)
300.0
225.0
150.0
75.0

Ambient (F)
95.0
80.0
65.0
55.0

Unit Efficiency
10.9 / 3.2
13.9 / 4.1
16.5 / 4.8
17.8 / 5.2

Compressor kW
300.3
162.5
85.1
38.1

SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0343EKF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0

Ambient (F)
95.0
80.0
65.0
55.0

63
99.0
99.0
97.0
94.0

125
99.0
99.0
97.0
94.0

250
100.0
100.0
98.0
95.0

500
99.0
100.0
98.0
94.0

1K
98.0
98.0
95.0
92.0

2K
92.0
91.0
89.0
87.0

4K
87.0
88.0
85.0
83.0

8K
83.0
84.0
81.0
79.0

LWA
102.0
102.0
100.0
96.0

2K
65.0
64.0
62.0
60.0

4K
60.0
61.0
58.0
56.0

8K
56.0
57.0
54.0
52.0

dBA
75.0
75.0
73.0
69.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0343EKF46 ( Equipped with Low Sound Fans )
Load %
Ambient (F)
63
125
250
500
100.0
95.0
72.0
72.0
73.0
72.0
75.0
80.0
72.0
72.0
73.0
73.0
50.0
65.0
70.0
70.0
71.0
71.0
25.0
55.0
67.0
67.0
68.0
67.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

1K
71.0
71.0
68.0
65.0

Performance at AHRI Conditions


YVAA0343EKF46
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)

54.0
44.0
719.1
11.8
Water
0.00010
113.0

Condenser Data
Ambient Temp. (F)
Altitude (ft.)

95.0
0

Performance Data
EER / COP
10.9 / 3.2
EER IPLV/COP IPLV
15.5 / 4.5
Capacity (Tons)
300.0

If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.

76

JOHNSON CONTROLS

44 1/8"

15 1/2"

AIR-COOLED SCREW CHILLER


MODEL: YVAA0343EKF46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

POWER: SINGLE POINT WITH TERMINAL BLOCK

88 3/16"

29 1/2"

Project Name : stp


Location :
Engineer :
Contractor :
For :

8" (WATER INLET)

1000"

(7) RIGGING HOLES


EACH SIDE 3 X 2

C
G

423 1/8"

40 3/16"

79 13/16"

48 5/16"

1,966

1,995

3/4" MOUNTING HOLES (TYP)

60 3/16"

2,259

2,260

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

61 3/4"

2,259
97 1/2"

1,951

863
84 7/16"

2,260

1,910

863

132 3/16"

790

14 1/8"

12 3/8"

47 1/2"

10 1/4"

60"

4"

VIEW B-B

POWER ENTRY
10" WIDE X 13" HIGH

12"

VIEW A-A

2 15/16"

CONTROL ENTRY
3" WIDE X 11 1/2" HIGH

POWER ENTRY IS ON BOTTOM OF PANEL

1 1/2"

94 11/16"

1 3/8" (TYP)

Date : 12/6/2012 13:34:33


Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS

A JOHNSON CONTROLS COMPANY

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

60 1/4"

70 5/8"

801

VSD / POWER PANEL

jOHNSON CONTROLS

8" (WATER OUTLET)

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 19,316, OPERATING - 20,175.
3. CENTER OF GRAVITY FROM ORIGIN: X= 187.5", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.

MODEL: YVAA0343EKF46
AHRI CAPACITY 300.0 TONS

YVAA
201 TO 500

77

Air Cooled Screw Chiller


Performance Specification
Unit Tag

Qty.

Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YVAA0373FJF46

350.0

460/3/60

R134a

Pin:

BASE MODEL

POWER

YVAA0373FJF46BA

VSXX XTAXLXXXX60 44XOXXX S196W 1SXXA2B MXF XXXXX XXXX BXSX

10

CONTROLS

15

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)

20

54.0
44.0
837.7
11.2
Water
0.00010
96.0

PIPING

25

30

COMP

35

EVAPORATOR

40

45

Evaporator Data (Cont.)


Min. Flow Rate (gpm)
460.0
Max. Flow Rate (gpm)
1540.0
Condenser Data
Ambient Temp. Design (F)
Altitude (ft.)
Ambient Temp. Min (F)

Circuit

CABINET

50

MISC

55

WARR

60

65

Performance Data
EER / COP
NPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)

Electrical Data
2
178
7/3.3

1
327
7/3.3

Compressor RLA
Fan QTY/FLA (each)

95.0
0
0.0

COND

10.4 / 3.0
15.0 / 4.4
10 %
22346
23405

Single Point
Min. Circuit Ampacity

658

Recommended Fuse/CB Rating


Max. Inverse Time CB Rating

800
800

Max. Dual Element Fuse Size (Amps)


Unit Short Circuit Withstand (STD)
Wire Lugs Per Phase*
Wire Range (Lug Size)
Unit Power Factor
Control KVA
Starter Type

Notes:

800
30kA
2
#2 - 600 KCM
0.95
3.0
VSD

Operating Condition Electrical Data


Compressor kW
372.6
Total Fan kW
31.8
Total kW
404.4

* Use Copper Conductors only

Load %
100.0
75.0
50.0
25.0

Part Load Rating Data


Capacity (Tons)
350.0
262.5
175.0
87.5

Ambient (F)
95.0
80.0
65.0
55.0

Unit Efficiency
10.4 / 3.0
13.3 / 3.9
16.1 / 4.7
17.4 / 5.1

Compressor kW
372.6
203.4
105.5
44.4

SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0373FJF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0

Ambient (F)
95.0
80.0
65.0
55.0

63
99.0
99.0
98.0
96.0

125
99.0
100.0
98.0
96.0

250
100.0
100.0
99.0
97.0

500
103.0
100.0
98.0
97.0

1K
100.0
97.0
95.0
92.0

2K
97.0
91.0
89.0
87.0

4K
96.0
88.0
86.0
84.0

8K
85.0
83.0
83.0
81.0

LWA
105.0
102.0
100.0
98.0

2K
70.0
64.0
62.0
60.0

4K
69.0
61.0
59.0
57.0

8K
58.0
56.0
56.0
54.0

dBA
78.0
75.0
73.0
71.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0373FJF46 ( Equipped with Low Sound Fans )
Load %
Ambient (F)
63
125
250
500
100.0
95.0
72.0
72.0
73.0
76.0
75.0
80.0
72.0
73.0
73.0
73.0
50.0
65.0
71.0
71.0
72.0
71.0
25.0
55.0
69.0
69.0
70.0
70.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

1K
73.0
70.0
68.0
65.0

Performance at AHRI Conditions


YVAA0373FJF46
Evaporator Data
EWT (F)
54.0
LWT (F)
44.0
Flow Rate (gpm)
839.7
Pressure Drop (ft.)
11.3
Fluid
Water
Fouling Factor
0.00010
Water Volume (gal)
96.0

Condenser Data
Ambient Temp. (F)
Altitude (ft.)

95.0
0

Performance Data
EER / COP
10.4 / 3.0
EER IPLV/COP IPLV
15.0 / 4.4
Capacity (Tons)
349.9

If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.

78

JOHNSON CONTROLS

jOHNSON CONTROLS

88
5/16"

44 1/8"

15
13/16"

28
13/16"

94
11/16"

8" WATER INLET

AIR-COOLED SCREW CHILLER


MODEL: YVAA0373FJF46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

8" WATER OUTLET

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 22,346, OPERATING - 23,405.
3. CENTER OF GRAVITY FROM ORIGIN: X= 200.3", Y= 46.6".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.

Project Name : adsfasdfa


Location :
Engineer :
Contractor :
For :

(6) RIGGING HOLES EACH SIDE 3 X 2


133
11/16"

142
11/16"

467 1/8"

56 5/8"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

63 7/8"

78
11/16"
60 5/8"

108 1/2"

63 7/8"

10
5/16"

12
5/16"

42 1/8"

END VIEW

SECTION

12"

2 15/16"

A-A

B-B

POWER ENTRY
10" WIDE X 13" HIGH
SECTION

CONTROL ENTRY
3" WIDE X 11 1/2" HIGH

2 1/2"

2 1/2"

Date : 3/5/2013 14:21:26


Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS

A JOHNSON CONTROLS COMPANY

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

60
5/16"

70
11/16"

3/4" MOUNTING HOLES (TYP)

MODEL: YVAA0373EKF46
AHRI CAPACITY 350.0 TONS

YVAA
201 TO 500

79

Air Cooled Screw Chiller


Performance Specification
Unit Tag

Qty.

Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YVAA0443FMF46

400.0

460/3/60

R134a

Pin:

BASE MODEL

POWER

CONTROLS

PIPING

COMP

EVAPORATOR

COND

CABINET

MISC

WARR

YVAA0443FMF46BA VDXX XTAXLXXXX60 44XOXXX S172W 1SXXA2B MXF PXXXX XXXX BXSX

10

15

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)

20

54.0
44.0
958.8
14.3
Water
0.00010
96.0

Circuit

25

30

35

45

Evaporator Data (Cont.)


Min. Flow Rate (gpm)
460.0
Max. Flow Rate (gpm)
1540.0
Condenser Data
Ambient Temp. Design (F)
Altitude (ft.)
Ambient Temp. Min (F)

95.0
0
0.0

50

55

60

65

Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)

Electrical Data
2
287
12/3.3

1
287
12/3.3

Compressor RLA
Fan QTY/FLA (each)

40

10.6 / 3.1
14.8 / 4.3
10 %
25942
27001

Single Point
Min. Circuit Ampacity

398

398

Min. Non-Fused Disconnect (Amps)


Min. Dual Element Fuse Size (Amps)

600
600

600
600

Max. Dual Element Fuse Size (Amps)


Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Unit Power Factor
Control KVA
Starter Type

600
600
600
#2 - 600 KCM
0.95
3.0
VSD

600
600
600
#2 - 600 KCM
0.95

Notes:

Operating Condition Electrical Data


Compressor kW
414.4
Total Fan kW
38.0
Total kW
452.4

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0

Part Load Rating Data


Capacity (Tons)
400.0
300.0
200.0
100.0

Ambient (F)
95.0
80.0
65.0
55.0

Unit Efficiency
10.6 / 3.1
13.2 / 3.9
15.8 / 4.6
17.3 / 5.1

Compressor kW
414.4
231.7
120.9
53.3

SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0443FMF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0

Ambient (F)
95.0
80.0
65.0
55.0

63
100.0
100.0
99.0
96.0

125
100.0
100.0
99.0
96.0

250
101.0
101.0
100.0
97.0

500
102.0
102.0
100.0
98.0

1K
99.0
100.0
96.0
93.0

2K
95.0
92.0
90.0
87.0

4K
93.0
90.0
87.0
84.0

8K
88.0
85.0
85.0
82.0

LWA
104.0
104.0
101.0
98.0

2K
68.0
65.0
63.0
60.0

4K
66.0
63.0
60.0
57.0

8K
61.0
58.0
58.0
55.0

dBA
77.0
77.0
74.0
71.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0443FMF46 ( Equipped with Low Sound Fans )
Load %
Ambient (F)
63
125
250
500
100.0
95.0
73.0
73.0
74.0
75.0
75.0
80.0
73.0
73.0
74.0
75.0
50.0
65.0
72.0
72.0
73.0
73.0
25.0
55.0
69.0
69.0
70.0
71.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

1K
72.0
73.0
69.0
66.0

Performance at AHRI Conditions


YVAA0443FMF46
Evaporator Data
EWT (F)
54.0
LWT (F)
44.0
Flow Rate (gpm)
958.8
Pressure Drop (ft.)
14.3
Fluid
Water
Fouling Factor
0.00010
Water Volume (gal)
96.0

Condenser Data
Ambient Temp. (F)
Altitude (ft.)

95.0
0

Performance Data
EER / COP
10.6 / 3.1
EER IPLV/COP IPLV
14.8 / 4.3
Capacity (Tons)
400.0

If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.

80

JOHNSON CONTROLS

jOHNSON CONTROLS

88"

44 1/8"

16"

29"

95"

8" WATER INLET

AIR-COOLED SCREW CHILLER


MODEL: YVAA0443FMF46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

8" WATER OUTLET

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 25,942, OPERATING - 27,001.
3. CENTER OF GRAVITY FROM ORIGIN: X= 213.7", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.

42"

56"

Project Name : stp


Location :
Engineer :
Contractor :
For :

67"

88"

56"

143"

146"

(8) RIGGING HOLES EACH SIDE 3 X 2

287"

52"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

555"

79"

57"

51"

109"

60"

71"

12"

10"

SECTION

42"

12"

3"

END
VIEW

SECTION

A-A

B-B

POWER ENTRY
10" WIDE X 13" HIGH

CONTROL ENTRY
3" WIDE X 11 1/2" HIGH

2 1/2"

2 1/2"

Date : 12/6/2012 13:47:41


Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS

A JOHNSON CONTROLS COMPANY

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

73"

3/4" MOUNTING HOLES (TYP)

MODEL: YVAA0443FMF46
AHRI CAPACITY 400.0 TONS

YVAA
201 TO 500

81

Air Cooled Screw Chiller


Performance Specification
Unit Tag

Qty.

Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YVAA0523HMF46

450.0

460/3/60

R134a

Pin:

BASE MODEL

POWER

CONTROLS

PIPING

COMP

EVAPORATOR

COND

CABINET

MISC

WARR

YVAA0523HMF46BA VDXX XTAXLXXXX60 44XOXXX S183W 1SXXA2B MXF PXXXX XXXX BXSX

10

15

20

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)

54.0
44.0
1078.7
14.8
Water
0.00010
147.0

Circuit

25

30

35

45

Evaporator Data (Cont.)


Min. Flow Rate (gpm)
550.0
Max. Flow Rate (gpm)
1880.0
Condenser Data
Ambient Temp. Design (F)
Altitude (ft.)
Ambient Temp. Min (F)

95.0
0
0.0

50

55

60

65

Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)

Electrical Data
2
312
13/3.3

1
312
13/3.3

Compressor RLA
Fan QTY/FLA (each)

40

10.9 / 3.2
15.4 / 4.5
10 %
28427
29784

Single Point
Min. Circuit Ampacity

423

423

Min. Non-Fused Disconnect (Amps)


Min. Dual Element Fuse Size (Amps)

700
700

700
700

Max. Dual Element Fuse Size (Amps)


Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Unit Power Factor
Control KVA
Starter Type

700
700
700
#2 - 600 KCM
0.95
3.0
VSD

700
700
700
#2 - 600 KCM
0.95

Notes:

Operating Condition Electrical Data


Compressor kW
452.4
Total Fan kW
41.1
Total kW
493.6

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Load %
100.0
75.0
50.0
25.0

Part Load Rating Data


Capacity (Tons)
450.0
337.5
225.0
112.5

Ambient (F)
95.0
80.0
65.0
55.0

Unit Efficiency
10.9 / 3.2
13.7 / 4.0
16.4 / 4.8
18.2 / 5.3

Compressor kW
452.4
251.2
131.9
58.2

SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0523HMF46 ( Equipped with Low Sound Fans )
Load %
100.0
75.0
50.0
25.0

Ambient (F)
95.0
80.0
65.0
55.0

63
101.0
100.0
99.0
96.0

125
101.0
101.0
99.0
96.0

250
102.0
102.0
100.0
97.0

500
102.0
103.0
100.0
97.0

1K
101.0
100.0
96.0
93.0

2K
96.0
93.0
91.0
87.0

4K
92.0
92.0
87.0
84.0

8K
87.0
86.0
85.0
81.0

LWA
104.0
104.0
101.0
98.0

2K
69.0
66.0
64.0
60.0

4K
65.0
65.0
60.0
57.0

8K
60.0
59.0
58.0
54.0

dBA
77.0
77.0
74.0
71.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0523HMF46 ( Equipped with Low Sound Fans )
Load %
Ambient (F)
63
125
250
500
100.0
95.0
74.0
74.0
75.0
75.0
75.0
80.0
73.0
74.0
75.0
76.0
50.0
65.0
72.0
72.0
73.0
73.0
25.0
55.0
69.0
69.0
70.0
70.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

1K
74.0
73.0
69.0
66.0

Performance at AHRI Conditions


YVAA0523HMF46
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)

54.0
44.0
1078.6
14.8
Water
0.00010
147.0

Condenser Data
Ambient Temp. (F)
Altitude (ft.)

95.0
0

Performance Data
EER / COP
10.9 / 3.2
EER IPLV/COP IPLV
15.4 / 4.5
Capacity (Tons)
450.0

If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.

82

JOHNSON CONTROLS

jOHNSON CONTROLS

88"

44 1/8"

16"

30"

95"

8" WATER INLET

AIR-COOLED SCREW CHILLER


MODEL: YVAA0523HMF46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

8" WATER OUTLET

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 28,427, OPERATING - 29,784.
3. CENTER OF GRAVITY FROM ORIGIN: X= 222.4", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.

Project Name : stp


Location :
Engineer :
Contractor :
For :

79"

132"

57"

59"

78"

309"

146"
599"

52"

79"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

(8) RIGGHING HOLES EACH SIDE 3 X 2

143"

57"

51"

109"

60"

71"

12"

10"

42"

SECTION

END
END
VIEW
VIEW

SECTION

12"

3"

B-B

A-A

POWER ENTRY
10" WIDE X 13" HIGH

CONTROL ENTRY
3" WIDE X 11 1/2" HIGH

2 1/2"

2 1/2"

Date : 12/6/2012 13:57:16


Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS

A JOHNSON CONTROLS COMPANY

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

73"

3/4" MOUNTING HOLES (TYP)

MODEL: YVAA0523HMF46
AHRI CAPACITY 450.0 TONS

YVAA
201 TO 500

83

Air Cooled Screw Chiller


Performance Specification
Unit Tag

Qty.

Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YVAA0523HMG46

500.0

460/3/60

R134a

Pin:

BASE MODEL

POWER

CONTROLS

PIPING

COMP

EVAPORATOR

COND

CABINET

MISC

WARR

YVAA0523HMG46BA VDXX XTAXLXXXX60 44XOXXX S200W 1SXXA3B MXG XXXXX XXXX BXSX

10

15

20

Evaporator Data
EWT (F)
LWT (F)
Design Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)

54.0
44.0
1199.9
51.4
Water
0.00010
147.0

Circuit

25

30

35

45

Evaporator Data (Cont.)


Min. Flow Rate (gpm)
400.0
Max. Flow Rate (gpm)
1400.0
Condenser Data
Ambient Temp. Design (F)
Altitude (ft.)
Ambient Temp. Min (F)

95.0
0
0.0

50

55

60

65

Performance Data
EER / COP
IPLV
Minimum Unit Capacity
Physical Data
Rigging Wt. (lbs.)
Operating Wt. (lbs.)

Electrical Data
2
341
13/5.1

1
341
13/5.1

Compressor RLA
Fan QTY/FLA (each)

40

10.5 / 3.1
14.4 / 4.2
10 %
29365
30722

Single Point
Min. Circuit Ampacity

478

478

Min. Non-Fused Disconnect (Amps)


Min. Dual Element Fuse Size (Amps)

800
800

800
800

Max. Dual Element Fuse Size (Amps)


Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Unit Power Factor
Control KVA
Starter Type

800
800
800
#2 - 600 KCM
0.95
3.0
VSD

800
800
800
#2 - 600 KCM
0.95

Notes:

Operating Condition Electrical Data


Compressor kW
495.3
Total Fan kW
74.7
Total kW
570.0

* Use Copper Conductors only


Load %
100.0
75.0
50.0
25.0

Part Load Rating Data


Capacity (Tons)
500.0
375.0
250.0
125.0

Ambient (F)
95.0
80.0
65.0
55.0

Unit Efficiency
10.5 / 3.1
12.8 / 3.8
15.5 / 4.5
16.2 / 4.7

Compressor kW
495.3
272.8
151.9
63.4

SOUND POWER LEVELS (In Accordance with AHRI 370) Octave Band Center Frequency, Hz
YVAA0523HMG46 ( Equipped with High Airflow Fans )
Load %
100.0
75.0
50.0
25.0

Ambient (F)
95.0
80.0
65.0
55.0

63
103.0
103.0
101.0
99.0

125
117.0
117.0
115.0
113.0

250
116.0
116.0
114.0
112.0

500
110.0
110.0
107.0
105.0

1K
107.0
106.0
103.0
101.0

2K
103.0
102.0
99.0
97.0

4K
96.0
94.0
91.0
90.0

8K
90.0
89.0
87.0
85.0

LWA
113.0
112.0
110.0
108.0

2K
76.0
75.0
72.0
70.0

4K
69.0
67.0
64.0
63.0

8K
63.0
62.0
60.0
58.0

dBA
86.0
85.0
83.0
81.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0523HMG46 ( Equipped with High Airflow Fans )
Load %
Ambient (F)
63
125
250
500
100.0
95.0
76.0
90.0
89.0
83.0
75.0
80.0
76.0
90.0
89.0
83.0
50.0
65.0
74.0
88.0
87.0
80.0
25.0
55.0
72.0
86.0
85.0
78.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

1K
80.0
79.0
76.0
74.0

Performance at AHRI Conditions


YVAA0523HMG46
Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Volume (gal)

54.0
44.0
1199.9
51.4
Water
0.00010
147.0

Condenser Data
Ambient Temp. (F)
Altitude (ft.)

95.0
0

Performance Data
EER / COP
10.5 / 3.1
EER IPLV/COP IPLV
14.4 / 4.2
Capacity (Tons)
500.0

If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.

84

JOHNSON CONTROLS

jOHNSON CONTROLS

16"

AIR-COOLED SCREW CHILLER


MODEL: YVAA0523HMG46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

88"

44 1/8"

95"

8" WATER INLET

NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 29,365, OPERATING - 30,722.
3. CENTER OF GRAVITY FROM ORIGIN: X= 225.1", Y= 44.0".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.

59"

78"

146"
599"

52"

79"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

(8) RIGGHING HOLES EACH SIDE 3 X 2

143"

Project Name : examples - Small tonnage BOM


Location :
Engineer :
Contractor :
For :

79"

132"

57"

309"

528 5/16"

57"

51"

109"

73"

Date : 4/26/2013 9:55:8


Rev. Date :
Form : 201.28-EG1
Dwg. Lev. : 01/11
Dwg. Scale : NTS

60"

71"

12"

10"

3/4" MOUNTING HOLES (TYP)

END
END
VIEW
VIEW

A-A

30"

A JOHNSON CONTROLS COMPANY

42"

8" WATER OUTLET

SECTION

12"

3"

B-B

POWER ENTRY
10" WIDE X 13" HIGH
SECTION

CONTROL ENTRY
3" WIDE X 11 1/2" HIGH

2 1/2"

2 1/2"

MODEL: YVAA0523HMG46
AHRI CAPACITY 500.0 TONS

YVAA
201 TO 500

85

86

JOHNSON CONTROLS

YCWL

50 to 200 Tons
Water Cooled Scroll Chiller

jOHNSON CONTROLS

87

88

JOHNSON CONTROLS

YCWL RIGGING
Delivery and Storage
To ensure consistent quality and maximum reliability, all units are
tested and inspected before leaving the factory. Units are shipped
completely assembled and containing refrigerant under pressure.
Units are shipped without export crating unless this has been
specified on the Sales Order.
If the unit is to be put into storage, before installation, the following
precautions should be observed:
Ensure that all openings, such as water connections, are securely
capped.
Do not store where exposed to ambient air temperatures exceeding
107F (42C).
The unit should be stored in a location where there is minimal activity
to limit the risk of accidental physical damage.
To prevent inadvertent operation of the pressure relief devices the
unit must not be steam cleaned.
It is recommended that the unit is periodically inspected during
storage.
Inspection
Immediately upon receiving the unit, it should be inspected for possible damage which may have occurred during transit. If damage
is evident, it should be noted in the carriers freight bill. A written
request for inspection by the carriers agent should be made at once.
See Instruction Manual, Form 50.15-NM for more information and details.
Major damage must be reported immediately to your local Johnson Controls representative.
Moving the Unit
Before moving the unit, ensure that the installation site is suitable for installing the unit and is capable of supporting
the weight of the unit and all associated services.
The units are designed to be lifted using either lifting chains or a fork lift.
Lifting by Crane / Hoist
A spreader frame should be used to prevent damage to the unit from the lifting chains (Refer to page 34 of the
Operations and Maintenance Guide [Form 201.26-NM1]).
NOTE: The unit must only be lifted a the points provided.

jOHNSON CONTROLS

89

WATER COOLED SCROLL CHILLER


YCWL - 50 to 200 TONS

BENEFITS





IPLV as high as 25.4 EER provide cost effective operation


Designed for low acoustics without additional sound treatment
Wide range of options to fit any design requirement
HFC-410A Standard for zero ODP and low global warming potential; long service life
Multiple scroll compressors offer redundancy and accurate capacity matching
Native BACnet MSTP & Modbus communications for BAS integration

UPGRADE OPTIONS
Low temperature brine chilling to 15F
Power Options:

Single Point Power Connection to Terminal Block, Non-fused Disconnect or Circuit Breaker

Multiple Point Power Connection to Circuit Breakers for retrofit projects

Compressor Overloads to limit MCA (ideal for retrofit applications)
Heat Pump (non-reversing) option to 130F leaving condenser water temperature for energy conservation
Remote Condenser YCRL variant for remote condenser applications
Evaporator Options:

Victaulic Flange Accessory for cooler nozzles

Flow switch: Vapor proof, SPDT, NEMA 4X switch, 150 psig
Vibration Isolators - Neoprene isolators, 1" spring isolators or 2" spring isolators

90

JOHNSON CONTROLS

WATER COOLED SCROLL CHILLER


YCWL - 50 to 200 TONS

PACKAGE DESCRIPTION:

Evaporator:

Completely assembled with all piping and wiring


ready for field installation
Pressure and operational tested
Provided with HFC-410A charge and initial oil
charge
Can be provided with optional overspray coat of
Caribbean Blue enamel paint

High efficiency DX cooler, refrigerant in tubes and


chilled liquid through baffled shell
Two independent circuits per chiller
Removable heads to access copper tubes
Water vent and drain connections
Insulated with 3/4" closed cell foam
Design working pressure 150 PSIG waterside and
400 PSIG on refrigerant side

Compressors:
Reliable suction-gas cooled hermetic scrolls
High efficiency motors with redundant overload
protection
Microprocessor controlled compressor staging
regulates chiller capacity to 15% of maximum
Design Working Pressure 560 PSIG
Condenser:



Cleanable, thru-tube type with removable heads


Integral subcooling standard
Equipped with relief valves
Steel shell and copper tubes

Refrigerant Circuit:
Tandem or trio compressors per circuit
Liquid line components include: shut-off valve
with charging port, high-absorption removable
core filter-drier, solenoid valve, sight glass with
moisture indicator, thermal or electronic expansion valves (depending on options)
Entire suction line and liquid line between expansion valve and cooler insulated with flexible
closed-cell foam insulation
Controls:
All controls housed in a NEMA 1 cabinet with
gasket sealed, hinged & latched door
LCD, 40-character display with backlight
Color coded, 32-button sealed keypad

jOHNSON CONTROLS

91

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0056SE46

52.4

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
125.6
12.2
Water
0.00010
22.4

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
23.1/23.1
150.0/150.0

85.0
95.0
153.2
10.6
Water 0.0
0.00025
19.4

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

16.1 / 4.7
21.3 / 6.2

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
23.1/23.1
150.0/150.0

3515
3648

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

110.0
(1)#12 - #1
92.4
150.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

39.2
39.2

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
75.0
50.0
25.0

92

98.0
150.0
110.0

Capacity (Tons)
52.4
41.1
29.0
14.2

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
76.4
84.0
67.1
72.4
65.0
67.6

Compressor kW
39.2
26.3
15.4
7.3

Unit Efficiency
16.1 / 4.7
18.8 / 5.5
22.6 / 6.6
23.3 / 6.8

JOHNSON CONTROLS

jOHNSON CONTROLS

29"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0056SE46
NOT FOR CONSTRUCTION

8 15/16" TO RIGGING HOLES

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

15 1/2" TO COOLER CONN

4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

4 1/2" CONDENSER
64 1/2"
WATER OUTLET
VICTAULIC
CONNECTION

1 1/2" RIGGING HOLES

PRODUCT DRAWING

14 1/2"

35 1/2"

29"

17 11/16"

34 5/8"
OVERALL WIDTH

1"

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 3,515, OPERATING - 3,648.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 9.8"

9 1/16"

34"
9"

5/8" MOUNTING HOLES (TYP)

50"

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

107 3/4"

84 1/2"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

25 7/8"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

5 1/8"

5 1/2"

6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

23 1/2"

50"

909 (LB)

915 (LB)

15 1/16"

119 5/8"
101 13/16"

9 7/8"

9 7/8"

ORIGIN

A JOHNSON CONTROLS COMPANY

8 5/8"

30 3/8"

6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

909 (LB)

915 (LB)

MODEL: YCWL0056SE46
AHRI CAPACITY 52.4 TONS

YCWL
50 TO 90

93

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0064SE46

59.9

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
143.6
15.7
Water
0.00010
22.4

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
26.9/26.9
187.0/187.0

85.0
95.0
175.8
13.4
Water 0.0
0.00025
19.4

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

15.7 / 4.6
19.9 / 5.8

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
26.9/26.9
187.0/187.0

3883
4016

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

125.0
(1)#10 - 300
107.6
187.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

45.7
45.7

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
75.0
50.0
25.0

94

114.0
150.0
125.0

Capacity (Tons)
59.9
47.1
33.3
16.3

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
76.4
84.1
67.2
72.5
65.0
67.6

Compressor kW
45.7
31.1
19.1
9.2

Unit Efficiency
15.7 / 4.6
18.2 / 5.3
20.9 / 6.1
21.2 / 6.2

JOHNSON CONTROLS

jOHNSON CONTROLS

29"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0064SE46
NOT FOR CONSTRUCTION

8 15/16" TO RIGGING HOLES

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

15 1/2" TO COOLER CONN

4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

4 1/2" CONDENSER
64 1/2"
WATER OUTLET
VICTAULIC
CONNECTION

1 1/2" RIGGING HOLES

PRODUCT DRAWING

14 1/2"

35 1/2"

29"

17 11/16"

34 5/8"
OVERALL WIDTH

1"

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 3,883, OPERATING - 4,016.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 10.3"

9 1/16"

50"
34"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

5 1/8"

5 1/2"

6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

23 1/2"

9"

5/8" MOUNTING HOLES (TYP)

50"

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

107 3/4"

84 1/2"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

25 7/8"

1,042 (LB)

966 (LB)

15 1/16"

119 5/8"
101 13/16"

9 7/8"

9 7/8"

ORIGIN

A JOHNSON CONTROLS COMPANY

8 5/8"

30 3/8"

6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

1,042 (LB)

966 (LB)

MODEL: YCWL0064SE46
AHRI CAPACITY 59.9 TONS

YCWL
50 TO 90

95

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0064HE46

62.4

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
149.6
7.4
Water
0.00010
59.8

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
26.9/26.9
187.0/187.0

85.0
95.0
181.7
6.6
Water 0.0
0.00025
26.9

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

16.5 / 4.8
20.2 / 5.9

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
26.9/26.9
187.0/187.0

4533
4848

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

125.0
(1)#10 - 300
107.6
187.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

45.5
45.5

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
75.0
50.0
25.0

96

114.0
150.0
125.0

Capacity (Tons)
62.4
48.5
33.4
16.3

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
76.0
83.6
66.4
71.5
65.0
67.5

Compressor kW
45.5
31.0
18.9
9.2

Unit Efficiency
16.5 / 4.8
18.8 / 5.5
21.2 / 6.2
21.3 / 6.2

JOHNSON CONTROLS

jOHNSON CONTROLS

29"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0064HE46
NOT FOR CONSTRUCTION

67 5/8"

1"

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

11 3/4" TO COOLER CONN

4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION

1 1/2" RIGGING HOLES

12 1/4" TO RIGGING HOLES

PRODUCT DRAWING

14 1/2"

35 1/2"

29"

17 11/16"

33 13/16"
OVERALL WIDTH
23 1/2"

8 1/4"

50"

25 7/8"

34"
9"

124 3/8"

5/8" MOUNTING HOLES (TYP)

50"

101 13/16"

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

107 3/4"

85"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

1,250 (LB)

1,174 (LB)

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

5 1/8"

7 1/8"

6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,533, OPERATING - 4,848.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.2"

19 13/16"

9 7/8"

9 7/8"

ORIGIN

A JOHNSON CONTROLS COMPANY

8 3/8"

32"

6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

1,250 (LB)

1,174 (LB)

MODEL: YCWL0064HE46
AHRI CAPACITY 62.4 TONS

YCWL
50 TO 90

97

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0074SE46

67.8

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
162.5
19.9
Water
0.00010
22.4

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
30.4/30.4
225.0/225.0

85.0
95.0
200.2
16.8
Water 0.0
0.00025
19.4

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

15.2 / 4.5
20.2 / 5.9

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
26.9/26.9
187.0/187.0

4061
4194

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

150.0
(1)#10 - 300
114.6
225.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

53.6
53.6

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
72.2
50.0
22.2

98

122.0
150.0
150.0

Capacity (Tons)
67.8
52.5
38.7
16.2

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
76.0
83.5
67.8
73.2
65.0
67.3

Compressor kW
53.6
34.1
21.8
9.2

Unit Efficiency
15.2 / 4.5
18.5 / 5.4
21.2 / 6.2
21.2 / 6.2

JOHNSON CONTROLS

jOHNSON CONTROLS

29"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0074SE46
NOT FOR CONSTRUCTION

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

15 1/2" TO COOLER CONN

4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

4 1/2" CONDENSER 68 7/8"


WATER OUTLET
VICTAULIC
CONNECTION

1 1/2" RIGGING HOLES

8 15/16" TO RIGGING HOLES

PRODUCT DRAWING

14 1/2"

35 1/2"

29"

17 11/16"

33 13/16"
OVERALL WIDTH

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,061, OPERATING - 4,194.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 10.4"

23 1/2"

9 1/16"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

5 1/8"

5 1/2"

6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

1"

50"
34"
9"

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

107 3/4"

84 1/2"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

9 7/8"

9 7/8"

ORIGIN

A JOHNSON CONTROLS COMPANY

8 5/8"

30 3/8"

6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

5/8" MOUNTING HOLES (TYP) 1,106 (LB)

1,106 (LB)

50"
990 (LB)

25 7/8"

101 13/16"

125 15/16"

990 (LB)

21 3/8"

MODEL: YCWL0074SE46
AHRI CAPACITY 67.8 TONS

YCWL
50 TO 90

99

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0074HE46

72.7

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
174.4
6.0
Water
0.00010
59.8

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
30.4/30.4
225.0/225.0

85.0
95.0
212.0
8.6
Water 0.0
0.00025
26.9

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

16.3 / 4.8
20.7 / 6.1

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
26.9/26.9
187.0/187.0

4911
5406

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

150.0
(1)#10 - 300
114.6
225.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

53.4
53.4

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
72.2
50.0
22.2

100

122.0
150.0
150.0

Capacity (Tons)
72.7
54.6
38.9
16.2

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
75.0
82.3
66.4
71.5
65.0
67.1

Compressor kW
53.4
33.7
21.4
9.1

Unit Efficiency
16.3 / 4.8
19.4 / 5.7
21.9 / 6.4
21.3 / 6.2

JOHNSON CONTROLS

jOHNSON CONTROLS

14 1/2"

29"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0074HE46
NOT FOR CONSTRUCTION

74 5/8"

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

16" TO COOLER CONN

4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION

1 1/2" RIGGING HOLES

12 3/4" TO RIGGING HOLES

PRODUCT DRAWING

40"

29"

17 11/16"

33 13/16"
OVERALL WIDTH

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,911, OPERATING - 5,406.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.3"

1"

5 1/8"

7 1/8"

34"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

8 1/4"

8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

23 1/2"

50"

29"

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

107 3/4"

83"

ORIGIN
Y

9 3/8"

33 1/4"

8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

9 7/8"

9 7/8"

1,409 (LB)

1,294 (LB)

A JOHNSON CONTROLS COMPANY

5/8" MOUNTING HOLES (TYP)

50"

101 13/16"

123 5/16"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

9"

1,409 (LB)

1,294 (LB)

18 3/4"

MODEL: YCWL0074HE46
AHRI CAPACITY 72.7 TONS

YCWL
50 TO 90

101

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0084SE46

76.6

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
183.5
24.9
Water
0.00010
22.4

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
30.4/30.4
225.0/225.0

85.0
95.0
224.6
9.5
Water 0.0
0.00025
26.9

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

15.8 / 4.6
21.4 / 6.3

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
30.4/30.4
225.0/225.0

4489
4684

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

150.0
(1)#10 - 300
121.6
225.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

58.3
58.3

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
75.0
50.0
25.0

102

129.0
150.0
150.0

Capacity (Tons)
76.6
61.0
44.3
21.9

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
76.9
84.6
68.2
73.6
65.0
67.7

Compressor kW
58.3
39.7
23.5
11.1

Unit Efficiency
15.8 / 4.6
18.4 / 5.4
22.7 / 6.7
23.8 / 7.0

JOHNSON CONTROLS

jOHNSON CONTROLS

14 1/2"

29"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0084SE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

35 1/2"

29"

17 11/16"

33 13/16"
OVERALL WIDTH

68 7/8"

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

15 1/2" TO COOLER CONN

4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION

1 1/2" RIGGING HOLES

8 15/16" TO RIGGING HOLES

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,489, OPERATING - 4,684.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.6"

1"

5 1/8"

7 1/8"

34"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

8 1/4"

6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

23 1/2"

50"

84 1/2"

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

107 3/4"

X
Y

9 7/8"

A JOHNSON CONTROLS COMPANY

8 5/8"

30 3/8"

6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

1,249 (LB)

1,093 (LB) ORIGIN


9 7/8"

5/8" MOUNTING HOLES (TYP)

50"

101 13/16"

125 15/16"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

1,249 (LB)

9"

25 7/8"
1,093 (LB)

21 3/8"

MODEL: YCWL0084SE46
AHRI CAPACITY 76.6 TONS

YCWL
50 TO 90

103

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0084HE46

82.6

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
198.0
7.6
Water
0.00010
59.8

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
30.4/30.4
225.0/225.0

85.0
95.0
239.5
10.6
Water 0.0
0.00025
26.9

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

16.8 / 4.9
21.9 / 6.4

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
30.4/30.4
225.0/225.0

5089
5584

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

150.0
(1)#10 - 300
121.6
225.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

58.9
58.9

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
75.0
50.0
25.0

104

129.0
150.0
150.0

Capacity (Tons)
82.6
64.4
44.7
21.9

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
76.2
83.8
66.6
71.8
65.0
67.5

Compressor kW
58.9
39.7
23.0
11.0

Unit Efficiency
16.8 / 4.9
19.5 / 5.7
23.3 / 6.8
23.8 / 7.0

JOHNSON CONTROLS

jOHNSON CONTROLS

14 1/2"

29"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0084HE46
NOT FOR CONSTRUCTION

74 5/8"

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

16" TO COOLER CONN

4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION

1 1/2" RIGGING HOLES

12 3/4" TO RIGGING HOLES

PRODUCT DRAWING

40"

29"

17 11/16"

33 13/16"
OVERALL WIDTH

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,089, OPERATING - 5,584.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.5"

1"

5 1/8"

7 1/8"

34"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

8 1/4"

8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

23 1/2"

50"

29"

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

107 3/4"

83"

ORIGIN
Y

9 3/8"

33 1/4"

8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

9 7/8"

9 7/8"

1,474 (LB)

1,318 (LB)

A JOHNSON CONTROLS COMPANY

5/8" MOUNTING HOLES (TYP)

50"

101 13/16"

125 11/16"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

9"

1,474 (LB)

1,318 (LB)

21 1/8"

MODEL: YCWL0084HE46
AHRI CAPACITY 82.6 TONS

YCWL
50 TO 90

105

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0094SE46

85.9

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
205.8
13.2
Water
0.00010
37.3

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
42.9/42.9
250.0/250.0

85.0
95.0
250.8
11.5
Water 0.0
0.00025
85.0

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

16.2 / 4.7
21.5 / 6.3

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
30.4/30.4
225.0/225.0

5023
5338

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

200.0
(1)#10 - 300
146.6
250.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

63.8
63.8

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
72.6
50.0
22.6

106

157.0
200.0
175.0

Capacity (Tons)
85.9
66.6
47.8
21.9

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
76.0
83.6
67.2
72.5
65.0
67.4

Compressor kW
63.8
41.6
25.4
11.0

Unit Efficiency
16.2 / 4.7
19.2 / 5.6
22.5 / 6.6
23.8 / 7.0

JOHNSON CONTROLS

jOHNSON CONTROLS

29"

33 13/16"
OVERALL WIDTH

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0094SE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

14 1/2"

35 1/2"

29"

17 11/16"

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

11 3/4" TO COOLER CONN

4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION

72 1/4"

1 1/2" RIGGING HOLES

12 1/4" TO RIGGING HOLES

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,023, OPERATING - 5,338.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 10.7"

8 1/4"

23 1/2"

50"
34"
9"

125 15/16"

85"

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

107 3/4"

A JOHNSON CONTROLS COMPANY

8 3/8"

32"

6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

9 7/8"

9 7/8"

1,242 (LB) ORIGIN

5/8" MOUNTING HOLES (TYP) 1,427 (LB)

50"

101 13/16"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

1,427 (LB)

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

5 1/8"

7 1/8"

6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

1"

25 7/8"
1,242 (LB)

21 3/8"

MODEL: YCWL0094SE46
AHRI CAPACITY 85.9 TONS

YCWL
50 TO 90

107

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0094HE46

89.4

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
214.3
8.7
Water
0.00010
59.8

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
42.9/42.9
250.0/250.0

85.0
95.0
258.5
5.4
Water 0.0
0.00025
44.1

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

16.9 / 5.0
21.9 / 6.4

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
30.4/30.4
225.0/225.0

5773
6412

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

200.0
(1)#10 - 300
146.6
250.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

63.5
63.5

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
72.6
50.0
22.6

108

157.0
200.0
175.0

Capacity (Tons)
89.4
68.5
47.9
21.9

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
75.6
83.1
66.4
71.6
65.0
67.3

Compressor kW
63.5
41.1
25.1
10.9

Unit Efficiency
16.9 / 5.0
20.0 / 5.9
23.0 / 6.7
24.1 / 7.1

JOHNSON CONTROLS

jOHNSON CONTROLS

15"

30"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0094HE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

42"

29"

33 7/8"
OVERALL WIDTH
17 11/16"

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

16" TO COOLER CONN

5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
76 5/8"

1 1/2" RIGGING HOLES

12 3/4" TO RIGGING HOLES

1"

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,773, OPERATING - 6,412.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.6"

5 3/16"

8 5/8"

34"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

8 1/2"

8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

23 1/2"

50"

83"

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

108 3/4"

9 7/8"

9 3/8"

35 1/4"

8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

1,696 (LB)

1,510 (LB) ORIGIN


9 7/8"

A JOHNSON CONTROLS COMPANY

5/8" MOUNTING HOLES (TYP)

50"

101 13/16"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

1,696 (LB)

9"

27 1/2"
1,510 (LB)

17 3/16"

121 3/4"

MODEL: YCWL0094HE46
AHRI CAPACITY 89.4 TONS

YCWL
50 TO 90

109

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0104SE46

92.8

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
222.5
11.0
Water
0.00010
37.3

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
42.9/42.9
250.0/250.0

85.0
95.0
271.0
13.1
Water 0.0
0.00025
26.9

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

16.2 / 4.7
20.9 / 6.1

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
42.9/42.9
250.0/250.0

5157
5472

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

225.0
(1)#4 - 500
171.6
250.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

68.9
68.9

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
75.0
50.0
25.0

110

182.0
200.0
200.0

Capacity (Tons)
92.8
72.6
50.9
24.9

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
76.3
83.9
66.9
72.2
65.0
67.5

Compressor kW
68.9
46.5
27.6
13.2

Unit Efficiency
16.2 / 4.7
18.7 / 5.5
22.2 / 6.5
22.6 / 6.6

JOHNSON CONTROLS

jOHNSON CONTROLS

14 1/2"

29"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0104SE46
NOT FOR CONSTRUCTION

71 3/4"

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

15 1/2" TO COOLER CONN

4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION

1 1/2" RIGGING HOLES

12 1/4" TO RIGGING HOLES

PRODUCT DRAWING

38 1/2"

29"

17 11/16"

33 13/16"
OVERALL WIDTH

1"

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,157, OPERATING - 5,472.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.8"

8 1/4"

6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

34"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

5 1/8"

7 1/8"

23 1/2"

50"

9"

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

107 3/4"

85"

32"

6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

9 7/8"

9 7/8"

ORIGIN

8 3/8"

1,476 (LB)

1,260 (LB)

A JOHNSON CONTROLS COMPANY

5/8" MOUNTING HOLES (TYP)

50"

124 1/8"
101 13/16"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

1,476 (LB)

25 7/8"
1,260 (LB)

19 9/16"

MODEL: YCWL0104SE46
AHRI CAPACITY 92.8 TONS

YCWL
91 TO 130

111

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0118SE46

110.5

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
264.8
15.1
Water
0.00010
37.3

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
54.5/54.5
310.0/310.0

85.0
95.0
324.5
17.8
Water 0.0
0.00025
26.9

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

15.6 / 4.6
23.5 / 6.9

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
42.9/42.9
250.0/250.0

4983
5298

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

310.0
(1)#4 - 500
194.8
310.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

84.9
84.9

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
71.8
50.0
21.8

112

208.4
250.0
225.0

Capacity (Tons)
117.2
89.7
64.4
27.7

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
75.6
83.0
67.0
72.1
65.0
67.2

Compressor kW
83.1
49.7
29.4
11.9

Unit Efficiency
16.9 / 5.0
21.7 / 6.4
26.3 / 7.7
27.9 / 8.2

JOHNSON CONTROLS

jOHNSON CONTROLS

14 1/2"

29"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0118SE46
NOT FOR CONSTRUCTION

71 3/4"

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

15 1/2" TO COOLER CONN

4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION

1 1/2" RIGGING HOLES

12 1/4" TO RIGGING HOLES

PRODUCT DRAWING

38 1/2"

29"

17 11/16"

33 13/16"
OVERALL WIDTH

1"

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,983, OPERATING - 5,298.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.8"

8 1/4"

6 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

34"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

5 1/8"

7 1/8"

23 1/2"

50"

9"

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

107 3/4"

85"

32"

6 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

9 7/8"

9 7/8"

ORIGIN

8 3/8"

1,413 (LB)

1,236 (LB)

A JOHNSON CONTROLS COMPANY

5/8" MOUNTING HOLES (TYP)

50"

124 1/8"
101 13/16"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

1,413 (LB)

25 7/8"
1,236 (LB)

19 9/16"

MODEL: YCWL0118SE46
AHRI CAPACITY 110.5 TONS

YCWL
91 TO 130

113

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0118HE46

117.2

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
280.8
14.1
Water
0.00010
59.8

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
54.5/54.5
310.0/310.0

85.0
95.0
334.0
8.4
Water 0.0
0.00025
44.1

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

16.9 / 5.0
24.7 / 7.2

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
42.9/42.9
250.0/250.0

5733
6372

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

310.0
(1)#4 - 500
194.8
310.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

83.1
83.1

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
71.8
50.0
21.8

114

208.4
250.0
225.0

Capacity (Tons)
117.2
89.7
64.4
27.7

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
75.6
83.0
67.0
72.1
65.0
67.2

Compressor kW
83.1
49.7
29.4
11.9

Unit Efficiency
16.9 / 5.0
21.7 / 6.4
26.3 / 7.7
27.9 / 8.2

JOHNSON CONTROLS

jOHNSON CONTROLS

15"

30"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0118HE46
NOT FOR CONSTRUCTION

PRODUCT DRAWING

42"

29"

33 7/8"
OVERALL WIDTH
17 11/16"

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

16" TO COOLER CONN

5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION
76 5/8"

1 1/2" RIGGING HOLES

12 3/4" TO RIGGING HOLES

1"

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,733, OPERATING - 6,372.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.7"

5 3/16"

8 5/8"

34"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

8 1/2"

8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

23 1/2"

50"

83"

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

108 3/4"

9 7/8"

9 3/8"

35 1/4"

8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

1,681 (LB)

1,505 (LB) ORIGIN


9 7/8"

A JOHNSON CONTROLS COMPANY

5/8" MOUNTING HOLES (TYP)

50"

101 13/16"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

1,681 (LB)

9"

25 7/8"
1,505 (LB)

18 3/4"

123 5/16"

MODEL: YCWL0118HE46
AHRI CAPACITY 117.2 TONS

YCWL
91 TO 130

115

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0132SE46

127.4

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
305.3
16.5
Water
0.00010
59.8

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
54.5/54.5
310.0/310.0

85.0
95.0
372.0
14.8
Water 0.0
0.00025
35.2

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

16.1 / 4.7
23.4 / 6.9

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
54.5/54.5
310.0/310.0

5463
6027

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

310.0
(1)#4 - 500
218.0
310.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

94.7
94.7

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
75.0
50.0
25.0

116

231.6
400.0
310.0

Capacity (Tons)
127.4
100.2
70.8
34.7

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
76.5
84.1
67.2
72.4
65.0
67.5

Compressor kW
94.7
61.0
33.7
15.9

Unit Efficiency
16.1 / 4.7
19.7 / 5.8
25.2 / 7.4
26.2 / 7.7

JOHNSON CONTROLS

jOHNSON CONTROLS

29"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0132SE46
NOT FOR CONSTRUCTION

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

16" TO COOLER CONN

5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION

74 1/2"

1 1/2" RIGGING HOLES

12 3/4" TO RIGGING HOLES

PRODUCT DRAWING

14 1/2"

40"

29"

17 11/16"

33 13/16"
OVERALL WIDTH

1"

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,463, OPERATING - 6,027.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.7"

7 3/4"

8 1/8"

8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

34"
9"

123 5/16"
101 13/16"

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

108 1/4"

83"

X
Y

A JOHNSON CONTROLS COMPANY

9 3/8"

33 1/4"

8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

9 7/8"

9 7/8"

1,415 (LB) ORIGIN

1,598 (LB)
5/8" MOUNTING HOLES (TYP)

50"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

1,598 (LB)

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

5 1/4"

23 1/2"

50"

25 7/8"
1,415 (LB)

18 3/4"

MODEL: YCWL0132SE46
AHRI CAPACITY 127.4 TONS

YCWL
91 TO 130

117

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0157SE46

144.0

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
345.1
17.3
Water
0.00010
57.6

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
54.5/54.5
310.0/310.0

85.0
95.0
419.0
15.3
Water 0.0
0.00025
52.4

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

16.5 / 4.8
23.5 / 6.9

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
54.5/54.5
310.0/310.0

6163
6891

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)

231.6
400.0
250.0

Max. Circuit Breaker (Amps)


Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

250.0
() -

Notes:

Operating Condition Electrical Data


Compressor kW
Total kW

104.7
104.7

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
75.0
50.0
25.0

118

218.0
310.0
Across the Line

Capacity (Tons)
144.0
113.5
80.2
39.3

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
76.5
84.2
67.3
72.5
65.0
67.5

Compressor kW
104.7
68.1
38.0
17.9

Unit Efficiency
16.5 / 4.8
20.0 / 5.9
25.3 / 7.4
26.3 / 7.7

JOHNSON CONTROLS

MODEL: YCWL0157SE46
AHRI CAPACITY 144.0 TONS

YCWL
131 TO 200
jOHNSON CONTROLS

119

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0157HE46

148.5

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
355.9
11.6
Water
0.00010
77.0

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
54.5/54.5
310.0/310.0

85.0
95.0
422.4
12.4
Water 0.0
0.00025
59.1

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

17.1 / 5.0
24.2 / 7.1

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
54.5/54.5
310.0/310.0

6863
7807

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)

231.6
400.0
250.0

Max. Circuit Breaker (Amps)


Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

250.0
() -

Notes:

Operating Condition Electrical Data


Compressor kW
Total kW

104.3
104.3

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
75.0
50.0
25.0

120

218.0
310.0
Across the Line

Capacity (Tons)
148.5
116.8
81.4
39.9

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
76.5
84.1
66.9
72.1
65.0
67.5

Compressor kW
104.3
67.2
37.7
17.8

Unit Efficiency
17.1 / 5.0
20.9 / 6.1
25.9 / 7.6
26.9 / 7.9

JOHNSON CONTROLS

MODEL: YCWL0157HE46
AHRI CAPACITY 148.5 TONS

YCWL
131 TO 200
jOHNSON CONTROLS

121

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0177SE46

166.6

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
399.3
14.2
Water
0.00010
77.0

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
49.2/49.2/49.2
242.0/242.0/242.0

85.0
95.0
477.9
15.3
Water 0.0
0.00025
59.1

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

17.1 / 5.0
25.4 / 7.4

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
49.2/49.2
242.0/242.0

7318
8262

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

300.0
(1)#4 - 500
246.0
242.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

117.1
117.1

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
80.0
60.0
40.0
20.0

122

258.0
400.0
300.0

Capacity (Tons)
166.6
141.0
108.3
73.3
35.6

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
78.8
87.1
71.0
77.2
65.0
69.1
65.0
67.0

Compressor kW
117.1
80.8
52.8
31.0
15.2

Unit Efficiency
17.1 / 5.0
20.9 / 6.1
24.6 / 7.2
28.4 / 8.3
28.2 / 8.3

JOHNSON CONTROLS

jOHNSON CONTROLS

15"

30"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0177SE46
NOT FOR CONSTRUCTION

23 1/2"

9"

8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

16" TO COOLER CONN

5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
77 1/2"
CONNECTION

1 1/2" RIGGING HOLES

17 3/4" TO RIGGING HOLES

PRODUCT DRAWING

41"

29"

17 11/16"

34 13/16"
OVERALL WIDTH

1"

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 7,318, OPERATING - 8,262.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 62.9", Y= 11.7"

34"
9"

50"

132 3/4"

102"

5/8" MOUNTING HOLES (TYP)

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

37 5/8"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

5 3/16"

7 1/8"

50"

2,229 (LB)

1,902 (LB)

14 7/8"

143 7/16"
125 13/16"
Y

11 7/8"

36 1/4"

8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

10 3/8"

A JOHNSON CONTROLS COMPANY

2,229 (LB)

1,902 (LB) ORIGIN


10 3/8"

MODEL: YCWL0177SE46
AHRI CAPACITY 166.6 TONS

YCWL
131 TO 200

123

Water Cooled Scroll Chiller


Performance Specification
Model No.

Capacity (Tons)

Volts/Ph/Hz

Refrigerant

YCWL0198SE46

198.4

460/3/60

R410A

Evaporator Data
EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

Condenser Data
54.0
44.0
475.6
19.6
Water
0.00010
77.0

Circuit
Compressor RLA
Compressor Start Current (LRA)

EWT (F)
LWT (F)
Flow Rate (gpm)
Pressure Drop (ft.)
Fluid
Fouling Factor
Water Vol. (gal)

1
49.2/49.2/49.2
242.0/242.0/242.0

85.0
95.0
566.2
20.4
Water 0.0
0.00025
59.1

Performance Data
EER / COP
EER IPLV/COP IPLV
Physical Data

16.8 / 4.9
24.8 / 7.3

Rigging Wt. (lbs.)


Operating Wt. (lbs.)

Electrical Data
2
49.2/49.2/49.2
242.0/242.0/242.0

7673
8617

Single Point
Min. Circuit Ampacity
Min. Non-Fused Disconnect (Amps)
Min. Circuit Breaker (Amps)
Max. Circuit Breaker (Amps)
Wire Range (Lug Size) *
Grounding Wire Lug Size
Total Amps
Inrush (PW) Amps
Starter Type

Notes:

350.0
(1)#4 - 500
295.2
242.0
Across the Line

Operating Condition Electrical Data


Compressor kW
Total kW

141.9
141.9

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only

Load %
100.0
83.3
66.7
50.0
33.3
16.7

124

308.0
400.0
350.0

Capacity (Tons)
198.4
172.0
144.2
110.2
73.0
35.8

Part Load Rating Data


Cond. EWT (F)
Cond. LWT (F)
85.0
95.0
79.7
88.1
74.1
81.0
67.2
72.4
65.0
68.4
65.0
66.7

Compressor kW
141.9
106.6
76.0
50.6
31.5
15.5

Unit Efficiency
16.8 / 4.9
19.4 / 5.7
22.8 / 6.7
26.1 / 7.6
27.8 / 8.1
27.7 / 8.1

JOHNSON CONTROLS

jOHNSON CONTROLS

15"

30"

WATER-COOLED SCROLL CHILLER


MODEL: YCWL0198SE46
NOT FOR CONSTRUCTION

23 1/2"

9"

8 5/8" EVAP
LIQUID INLET
VICTAULIC
CONNECTION

Project Name : Contractors Guide


Location :
Engineer :
Contractor :
For :

16" TO COOLER CONN

5 9/16" CONDENSER
WATER INLET
VICTAULIC
CONNECTION

5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
77 1/2"
CONNECTION

1 1/2" RIGGING HOLES

17 3/4" TO RIGGING HOLES

PRODUCT DRAWING

41"

29"

17 11/16"

34 13/16"
OVERALL WIDTH

1"

NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20"
FRONT TO WALL: 36"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 7,673, OPERATING - 8,617.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 62.9", Y= 11.7"

34"
9"

143 7/16"

50"

102"

5/8" MOUNTING HOLES (TYP)

Date :
Rev. Date :
Form : 201.26-EG1
Dwg. Lev. : 10/07
Dwg. Scale : NTS

132 3/4"

125 13/16"

POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

37 5/8"

Sold To :
Cust Purch Order# :
York Contract# :
UNIT
TAG:

5 3/16"

7 1/8"

50"

2,371 (LB)

1,938 (LB)

14 7/8"
Y

11 7/8"

36 1/4"

8 5/8" EVAP
LIQUID OUTLET
VICTAULIC
CONNECTION

10 3/8"

A JOHNSON CONTROLS COMPANY

2,371 (LB)

1,938 (LB) ORIGIN


10 3/8"

MODEL: YCWL0198SE46
AHRI CAPACITY 198.4 TONS

YCWL
131 TO 200

125

126

JOHNSON CONTROLS

Printed on recycled paper


Form: 050.05-TD1 (313) Supersedes: 050.05-TD1 (309)
2008 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201 Printed in USA
www.johnsoncontrols.com