DOC. NO.

CU-47000-0202
REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235

A.1

CT sizing calculation for 400kV Existing Bus-Bar Protection

A.1.1

Applicable CT and core Numbers:

A.1.2

A.1.3

Feeder Detail

CT Ratio

CT No

Core

Ref. Drawing No.

400kV

2000/1

400-6-CT
400-7-CT

765/400kV Unnao substation SLD:CU-470000001,Rev.00

System Parameter (As per Specification,Vol-II General Technical Requirement 071806-47ES-0200 Rev.0 Cl.6.1)
Variable

Value

Unit

Vn

420

kV

Nominal Voltage

Ispec

40

kA

Primary Short Circuit Current

fn

50

Hz

X/R

30

Maximum duration of short circuit current


System supply Frequency
X/R ratio of system

CT Parameter (As per Specification ,Vol-III Instrument Transformer 071806-47ES-7230 Rev.0.Cl.2.11.2)


IPN

2000

ISN
RCT

A.1.4

Description

Rated Primary Current

Rated Secondary Current

CT Resistance at 75oC

Relay Parameter (As per the attached Annexure 1)


IR

Rated Input Current of Relay used

Sr

10

VA

Maximum Protective relay Burden(Burden & CT requirement of RADSS relays)

tm

15

ms

Busbar Protection Relay Operating time(As per Annexure-I)

tCB

40

ms

Circuit Breaker Operating time(As per Annexure-I)

Page 1

DOC. NO. CU-47000-0202


REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235
A.1.5

Secondary Lead Parameter


IL

100

AL

mm2

rL

A.1.6

Single way length of leads


Cross sectional area of leads

3.746

km

No of runs of cable connected to CT secondary


AC resistance of 6 Sq.mm Cu, lead at 75oC

Details of Relay Proposed

Relay Type

Rated Current,IR

Bus Diffrential Protection (ABB-RADSS)

: 1A

Short time current carrying capacity,Ith


(relay)

100 X IR for 1s

= 100 X 1 A for 1s
= 100A

Maximum relay input current during through fault, If

for 1sec

IPSC/IPN X ISN
= 40000/2000 X 1
= 20.00A

A.1.7

<100A [Ith(relay)]

Formula and Requirements-Metering


The following formulae and requirements are applied

Rated Symmetrical Short Circuit Current factor(Kssc)


KSSC

As per IEC 44-6(Cl.3.15)


= IPSC/IPN
= 40 X 1000/2000
= 20.00

Standard Value of KSSC

= 20

As per IEC 44-6(Cl.4.1)

Primary Time Constant(TP)


For the System Close in Fault

X/R= 30
L/R= 30/(2X3.14X50)

Therefore Primary Time Constant(TP) at system fault

0.096sec

Page 2

DOC. NO. CU-47000-0202


REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235

= 95.54msec
Standard Value of TP

= 120

As per IEC 44-6(Cl.4.3)

Duty Cycle(C-O)
Single Energisation

= C-t'-O

where
t' = Duration of first current flow
t'= tm+tCB
= 55ms
Selected Duty Cycle

Say 80 mSec

C-80ms-O

Resistive Burden(External Burden)


RI = (2.IL.rL/1000)

Two way lead resistance

( IL=100 Mtr Longest distance of CT cabling as per Layout)


= (2X100X3.746/1000)
=

Rr = Sr/Ir2

Relay burden on CT

= 10/1^2
=

Rb = RI+Rr
=

Page 3

Considered uniform for CT

DOC. NO. CU-47000-0202


REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235

Standard Value of Rb

Vk>= 0.5 x If x (RCT+RI)

Knee Point Voltage

>= 0.5*20*(5+0.75)
>= 57.49 V

Rated Equivalent Rated Secondary e.m.f

Eal

= Kssc x Ktd x (RCT + Rb) x ISN

(-t'/TP)
)+1
Ktd = Ktf = 2 x pi x f x TP x ( 1 - e

2 x 3.14 x 50 x (0.12) x (1-e(-0.08/0.12)) + 1

Ktd = Ktf = 19.334

Eal

= Kssc X Ktd X (Rct + Rb) X Isn


20 x 1.019x (5 + 12.75) x 1

Eal

= 6863.73 V

As Equivalent Rated Secondary e.m.f is greater than Knee Point Voltage, CT is capable of supplying Eal to the relay circuit.

Rated Secondary
Current(ISN)

Rated Frequency(fn)

Rated Short Time


Thermal Current(Ith)

Duration of Short Time


Thermal Current(Ith)

Rated Dynamic
Current(Idyn)

Class as per IEC

Symmetrical Short Circuit


Current Factor

Primary Time Constant

Specified duty Cycle

Resistive Burden

Equi. Limiting Sec. e.m.f

Results
Rated Primary Current at
Tap(IPN)

A.1.8

(A)

(A)

(Hz)

(kA)

(sec)

(kA)

(-)

(-)

(ms)

(-)

()

(V)

2000

50

40kA

100

TPX

20

120

C-80ms-O

6864V

Page 4

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01

B.1

CT sizing calculation for 400kV Transformer Differential Protection(87TA)-Low Impedace Protection

B.1.1

Applicable CT and core Numbers:


Feeder Detail

B.1.2

B.1.3

B.1.4

B.1.5

CT Ratio

CT No

Core No.

ICT-1

1600/1

400-6-CTT

ICT-2

1600/1

400-7-CTT

Ref. Drawing No.


765/400kV Unnao substation SLD:CU-47000-0001,Rev.00

System Parameter (As per Specification,Vol-II General Technical Requirement 071806-47ES-0200 Rev.0 Cl.6.1)
Variable

Value

Unit

Description

Vn

420

kV

Nominal Voltage

Ispec

40

kA

Primary Short Circuit Current

fn

50

Hz

X/R

30

Maximum duration of short circuit current


System supply Frequency
X/R ratio of system

CT Parameter (As per Specification ,Vol-III Instrument Transformer 071806-47ES-7230 Rev.0.Cl.2.11.2)


IPN

1600

ISN
RCT

Rated Primary Current

Rated Secondary Current

CT Resistance at 75oC

Relay Parameter (As per the attached Annexure 1)


IR

Rated Input Current of Relay used

Sr

0.1

VA

Maximum Protective relay Burden(Burden & CT requirement of Micom relays)

tm

30

ms

Transformer Differential Relay Operating time(As per Annexure-I)

IS

0.02

Minimum Setting of Relay

tCB

40

ms

Minimum Setting of Relay

Single way length of leads

Secondary Lead Parameter


IL

350

AL

mm2

3.746

km

rL

Cross sectional area of leads


No of runs of cable connected to CT secondary
AC resistance of 6 Sq.mm Cu, lead at 75oC

Page 5

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B
B.1.6 Transformer Parameter

B.1.7

DOC. NO. CU-47000-0202


REV. 01

--

1000

MVA

VP

Transformer MVA Rating

765

kV

Primary Voltage Rating

VS

400

kV

Secondary Voltage Rating

--

14

Percentage Impedance(As per T/Specification,Vol-III 017806-47ES-7130 Rev.o


Cl.2.8.1,page 3 & GTP)

Details of Relay Proposed

Relay Type

: Transformer differential, Micom P633

Rated Current,IR

: 1A

Short time current carrying capacity,Ith (relay)

: 100 X IR for 1s
= 100 X 1 A for 1s
= 100A

Maximum relay input current during through fault, I f:

for 1sec
Source feed considered from 765 KV
side and fault current taken as per
calculations at Sl. No.1.8 (b) below

IPSC/IPN X ISN
= 10310/1600 X 1
<100A [Ith(relay)]

= 6.44A

Full load Current,IL

= MVA/(-/3 x VP)
= 1000 X 1000/1.732 X 400
= 1443A

B.1.8
1

Through Fault Current


Through Fault MVA of Transformer

: MVA Rating/% Impedance


= 1000 X 100/14
= 7142.86MVA

Through Fault Current on Secondary side of Transformer I PSC(MV):

Fault-MVA/(-/3 XVP)
= 7142.86/(1.732*400)
= 10.31kA

Page 6

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B
B.1.9 Formula and Requirements

DOC. NO. CU-47000-0202


REV. 01

The following formulae and requirements are applied


1

Rated Symmetrical Short Circuit Current factor(Kssc)

As per IEC 44-6(Cl.3.15)

KSSC

= Ispec/IPN
= 40 X 1000/1600
= 25.00

Standard Value of KSSC

= 25

As per IEC 44-6(Cl.4.1)

Primary Time Constant(TP)


For the System Close in Fault

X/R= 30
L/R= 30/(2X3.14X50)

Therefore, Primary Time Constant(T P) at system fault

0.096sec
= 95.54msec

Standard Value of TP

= 120

As per IEC 44-6(Cl.4.3)

Duty Cycle(C-O)
Single Energisation

= C-t'-O

where
t' = Duration of first current flow
t'= tm + tCB
= 70ms
Selected Duty Cycle

(say 80 ms)

C-80ms-O

Resistive Burden(External Burden)


RI = (2.IL.rL/1000)

Two way lead resistance

( IL=350 Mtr Longest distance of CT cabling as per Layout)


= (2*350*3.746/1000)
= 2.62W

Rr = Sr/Ir2

Relay burden on CT

= 0.1/1^2
= 0.10W

Page 7

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01
Rb = RI+Rr
= 2.722W

Standard Value of Rb

= 5.00W

Vk>= K X (RCT+RI)

Knee Point Voltage

Condition 1

Condition 2

As per IEC 44-6(Cl.4.5)

Applicable
If x (X/R)

<= 500 x ISN

6.44 X 30

<= 500 X 1

193.3125

<= 500

Not Applicable
500 x ISN

< If x (X/R)

<

1200

500 X 1

< 25 X 30

<

1200

< 193.3125

<

1200

500

As Condition 2 is satisfied K,
K= 0.14 x If x (X/R)
0.14 X 6.44 X 30
= 27.06

Vk>= K x (RCT+RI)
>= 27.06*(5+2.62)
>= 206.26V

Vk = 250.00V

Rated Equivalent Rated Secondary e.m.f

Eal

= Kssc x Ktd x (RCT + Rb) x ISN

(-t'/TP)
)+1
Ktd = Ktf = 2 x pi x f x TP x ( 1 - e

2*3.14*50*(0.12)*(1-EXP(-0.08/0.12))+1

Page 8

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01
Ktd = Ktf = 19.33

Eal

= Kssc X Ktd X (Rct + Rb) X Isn

Eal

= 4833.61V

25*19.33*(5+5)*1

As Equivalent Rated Secondary e.m.f is greater than Knee Point Voltage, CT is capable of supplying Eal to the relay circuit.

Rated Primary
Current at
Tap(IPN)

Rated
Secondary
Current(ISN)

Rated
Frequency(fn)

Rated Short
Time Thermal
Current(Ith)

Duration of
Short Time
Thermal
Current(Ith)

Rated Dynamic
Current(Idyn)

Class as per
IEC

Symmetrical
Short Circuit
Current Factor

Primary Time
Constant

Specified duty
Cycle

Resistive
Burden

Equi. Limiting
Sec. e.m.f

B.2.10 Results

(A)
1600

(A)
1

(Hz)
50

(kA)
40kA

(sec)
1

(kA)
100

(-)
TPX

(-)
25

(ms)
120

(-)
C-80ms-O

()

(V)
4834V

Page 9

DOC. NO. CU-47000-0202


REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

B.2

CT sizing calculation for 400kV Transformer Differential Protection(87TB)-Low Impedace Protection

B.2.1

Applicable CT and core Numbers:

B.2.2

B.2.3

B.2.4

B.2.5

Feeder Detail

CT Ratio

CT No

Core

ICT-1

1600/1

400-6-CT

ICT-2

1600/1

400-7-CT

Ref. Drawing No.


765/400kV Unnao substation SLD:CU-47000-0001,Rev.00

System Parameter (As per Specification,Vol-II General Technical Requirement 071806-47ES-0200 Rev.0 Cl.6.1)
Variable

Value

Unit

Vn

420

kV

Nominal Voltage

Ispec

40

kA

Primary Short Circuit Current

fn

50

Hz

X/R

30

Description

Maximum duration of short circuit current


System supply Frequency
X/R ratio of system

CT Parameter (As per Specification ,Vol-III Instrument Transformer 071806-47ES-7230 Rev.0.Cl.2.11.2)


IPN

1600

ISN
RCT

Rated Primary Current

Rated Secondary Current

CT Resistance at 75oC

Rated Input Current of BCU used

Relay Parameter (As per the attached Annexure 1)


IR

Sr

0.2

VA

Maximum Protective relay Burden(Burden & CT requirement of Micom relays)

tm

30

ms

Transformer Differential Relay Operating time(As per Annexure-I)

IS

0.02

Minimum Setting of Relay

tCB

40

ms

Minimum Setting of Relay

Single way length of leads

Secondary Lead Parameter


IL

100

AL

mm2

rL

3.746

km

Cross sectional area of leads


No of runs of cable connected to CT secondary
AC resistance of 6 Sq.mm Cu, lead at 75oC

Page 10

DOC. NO. CU-47000-0202


REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B
B.2.6

B.2.7

Transformer Parameter
--

1000

MVA

VP

765

kV

Transformer MVA Rating


Primary Voltage Rating

VS

400

kV

Secondary Voltage Rating

--

14

Percentage Impedance(As per T/Specification,Vol-III 017806-47ES-7130 Rev.o


Cl.2.8.1,page 3 & GTP)

Details of Relay Proposed

Relay Type

: Transformer differential, MicomP643

Rated Current,IR

: 1A

Short time current carrying capacity,Ith (relay)

: 100 X IR for 1s
= 100 X 1 A for 1s
= 100A

Maximum relay input current during through fault, I f:

for 1sec
Source feed considered from 765 KV
side and fault current taken as per
calculations at Sl. No.1.8 (b) below

IPSC/IPN X ISN
= 10310/1600 X 1
= 6.44A

Full load Current,IL

<100A [Ith(relay)]

= MVA/(-/3 x VP)
= 1000 X 1000/1.732 X 400
= 1443A

B.2.8
1

Through Fault Current


Through Fault MVA of Transformer

: MVA Rating/% Impedance


= 1000 X 100/14
= 7142.86MVA

Through Fault Current on Secondary side of


Transformer IPSC(MV):

= Fault-MVA/(-/3 XVP)
= 7142.86/(1.732*400)
= 10.31kA

Page 11

DOC. NO. CU-47000-0202


REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B
B.2.9

Formula and Requirements-Metering


The following formulae and requirements are applied

Rated Symmetrical Short Circuit Current factor(Ksec)

As per IEC 44-6(Cl.3.15)

KSSC

= Ispec/IPN
= 40 X 1000/1600
= 25.00

Standard Value of KSSC

= 25

Primary Time Constant(TP)


For the System Close in Fault

X/R= 30
L/R= 30/(2X3.14X50)

Therefore Primary Time Constant(TP) at system fault

0.096sec
= 95.54msec

Standard Value of TP

= 120

Duty Cycle(C-O)
Single Energisation

= C-t'-O

where
t' = Duration of first current flow
t'= tm + tCB
= 70ms
Selected Duty Cycle

(say 80 ms)

C-80ms-O

Resistive Burden(External Burden)


RI = (2.IL.rL/1000)

Two way lead resistance

( IL=100 Mtr Longest distance of CT cabling as per Layout)


= (2X100X3.746/1000)
=

Rr = Sr/Ir2

Relay burden on CT

= 0.2/1^2
=

Page 12

DOC. NO. CU-47000-0202


REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B
Rb = RI+Rr
=

Standard Value of Rb

As per IEC 44-6(Cl.4.5)

Vk>= K X (RCT+RI)

Knee Point Voltage

Condition 1
If <= 5 <= X/R < 40

K = 0.04 x If x (X/R+24.25) + 0.06 x (X/R+177)

Condition 2
If <= 5, 40 <= X/R < 120

K = 12 x If +16

Condition 3
5 < If <= 10, 5<= X/R < 40

K = 0.14 x If x (-X/R-15) + 0.44 x (X/R+202.5)

Condition 4
5 < If <= 10, 40<= X/R < 120

K = -7.38 x If + 112

Condition 5
5 < If <= 20, 5<= X/R < 40

K = 0.06 x If x (X/R-52.5) + 1.1 x (-X/R+74.9)

Condition 6
10 < If <= 20, 40 <= X/R < 120

K = -0.81 x If + 45

Now If =6.44 and X/R = 30, Hence "Condition 5 is considered", Therefore:

K = 0.06 x x (X/R-52.5) + 1.1 x (-X/R+74.9)


57.13

Vk>= K X (RCT+RI)
328.45V

Vk = 350.00V

Rated Equivalent Rated Secondary e.m.f

Page 13

DOC. NO. CU-47000-0202


REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

Eal

= Kssc x Ktd x (RCT + Rb) x ISN

(-t'/TP)
)+1
Ktd = Ktf = 2 x pi x f x TP x ( 1 - e

2 x 3.14 x 50 x (0.12) x (1-e(-0.08/0.12)) + 1

Ktd = Ktf = 19.334

Eal

= Kssc X Ktd X (Rct + Rb) X Isn


25 x 19.334 x (5+5) x 1

Eal

= 4833.610738713

As Equivalent Rated Secondary e.m.f is greater than Knee Point Voltage, CT is capable of supplying Eal to the relay circuit.

Rated
Secondary
Current(ISN)

Rated
Frequency(fn)

Rated Short
Time Thermal
Current(Ith)

Duration of
Short Time
Thermal
Current(Ith)

Rated Dynamic
Current(Idyn)

Class as per
IEC

Symmetrical
Short Circuit
Current Factor

Primary Time
Constant

Specified duty
Cycle

Resistive
Burden

Equi. Limiting
Sec. e.m.f

Results
Rated Primary
Current at
Tap(IPN)

B.2.10

(A)
1600

(A)
1

(Hz)
50

(kA)
40kA

(sec)
1

(kA)
100

(-)
TPX

(-)
25

(ms)
120

(-)
C-80ms-O

()

(V)
4834V

Page 14

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01

C.1

CT sizing calculation for 400kV Metering Core

C.1.1

Applicable CT and core Numbers:


Feeder Detail
CT Ratio
ICT-1
1600/1
ICT-2
1600/1
ICT-1
1600/1
ICT-2

C.1.2

X/R

C.1.4

C.1.5

C.1.6

C.1.7

400-6-CT

Core No.
3
3
2
2

Ref. Drawing No.


765/400kV Unnao substation SLD:CU-470000001,Rev.00
This is as per discussion had on 12th October
2010, with the view to connect this core for Circuit
Breaker Control Switching Scheme

System Parameter (As per Specification,Vol-II General Technical Requirement 071806-47ES-0200 Rev.0 Cl.6.1)
Variable
Value
Unit
Description
Vn
400
kV
Nominal Voltage
Ispec
40
kA
Primary Short Circuit Current
t
fn

C.1.3

1600/1

CT No
400-3-CTT
400-6-CTT
400-3-CT

50
30

Hz
-

Maximum duration of short circuit current


System supply Frequency
X/R ratio of system

CT Parameter (As per Specification ,Vol-III Instrument Transformer 071806-47ES-7230 Rev.0.Cl.2.11.2)


IPN
1600
A
Rated Primary Current
ISN

Rated Secondary Current

RCT

CT Resistance at 75oC

SN

10

VA

Rated Burden

Instrument Parameter (As per the attached Annexure 1)


IM
1
A

Rated Input Current of BCU used

Sr

0.15

VA

FS

Instrument Security Factor

SM1

VA

Rated Burden of Meter -1

SM2

VA

Rated Burden of Meter -2

Single way length of leads

Secondary Lead Parameter


IL
530
AL
6

Maximum burden of Bay Control Unit(As per Annexure-I)

mm2
-

Cross sectional area of leads


No of runs of cable connected to CT secondary

rL

3.746

W/km

AC resistance of 6 Sq.mm Cu, lead at 75 oC

Transformer Parameter
-VP

1000

MVA

Transformer MVA Rating

765

kV

Primary Voltage Rating

VS

400

kV

--

14

Secondary Voltage Rating


Percentage Impedance(As per Specification,Vol-III 01780647ES-7130 Rev.o Cl.2.8.1,page 3)

Formula and Requirements-Metering

Page 15

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B
1

DOC. NO. CU-47000-0202


REV. 01

Resitive Burden
Slead

(2.IL.RL/1000)*ISN2

ST

Slead +Sr + SM1+ SM2

Two way lead burden in VA


( IL=530 Mtr Longest distance of CT cabling as per Layout)
3.97VA

6.12VA
2

Instrument Secuirty Factor


SCT

RCT *ISN2
= 5*12
= 4.00VA

FS'

FsX(SN+SCT)/(ST+SCT)
= 6.92
20 X ISN

Rated short time carrying capactiy of Bay Control Unit =


=
=
ISN X FS'

1 X 6.92
= 6.92

20*1
20A
< 20A

Hence, ISF adopted is <= 5

Rated
Secondary
Current(ISN)

Rated
Frequency(fn)

Rated Short
Time Thermal
Current(Ith)

Duration of
Short Time
Thermal
Current(Ith)

Rated Dynamic
Current(Idyn)

Rated Burden

Instrument
Security Factor

Class of
accuracy

RCT

Results
Rated Primary
Current at
Tap(IPN)

C.1.8

(A)
1600

(A)
1

(Hz)
50

(kA)
40kA

(sec)
1

(kA)
100

(VA)
10

(-)
<=5

(-)
0.2

(W)
5

Page 16

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01

D.1

CT sizing calculation for 400kV Over Current and Earth Fault Protection

D.1.1

Applicable CT and core Numbers:

D.1.2

D.1.3

D.1.4

D.1.5

Feeder Detail

CT Ratio

CT No

Core

Ref. Drawing No.

ICT-1

1600/1

400-6-CTT

ICT-2

1600/2

400-7-CTT

765/400kV Unnao substation SLD:CU-470000001,Rev.00

System Parameter (As per Specification,Vol-II General Technical Requirement 071806-47ES-0200 Rev.0 Cl.6.1)
Variable

Value

Unit

Vn

420

kV

Nominal Voltage

Ispec

40

kA

Primary Short Circuit Current

fn

50

Hz

X/R

30

Description

Maximum duration of short circuit current


System supply Frequency
X/R ratio of system

CT Parameter (As per Specification ,Vol-III Instrument Transformer 071806-47ES-7230 Rev.0.Cl.2.11.2)


IPN

1600

ISN
RCT

Rated Primary Current

Rated Secondary Current

CT Resistance at 75oC

Relay Parameter (As per the attached Annexure 1)


IR

Rated Input Current of Relay used

Sr

0.04

VA

Over Current Protection Relay Burden(Burden & CT Requirement of


Micom Relays)

Single way length of leads

Secondary Lead Parameter


IL

530

AL

mm2

rL

3.746

km

Cross sectional area of leads


No of runs of cable connected to CT secondary
AC resistance of 6 Sq.mm Cu, lead at 75 oC

Page 17

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B
D.1.6

D.1.7

DOC. NO. CU-47000-0202


REV. 01

Transformer Parameter
--

1000

MVA

VP

Transformer MVA Rating

765

kV

Primary Voltage Rating

VS

400

kV

Secondary Voltage Rating

--

14

Percentage Impedance(As per Specification,Vol-III 017806-47ES-7130


Rev.o Cl.2.8.1,page 3)

Details of Relay Proposed

Relay Type

: Backup over current Earth fault Protection Micom-P141

Rated Current,IR
Short time current carrying capacity,Ith
(relay)

: 1A

: 100 X IR for 1s
= 100 X 1 A for 1s
= 100A

Maximum relay Secondary Input Current during through fault, I f :

for 1sec

IPSC/IPN X ISN
= 40000/1600 X 1
= 25.00A

D.1.8
1

<100A [Ith(relay)]

Through Fault Current


Through Fault MVA of Transformer

: MVA Rating/% Impedance


= 1000 X 100/14
= 7142.86MVA

Fault-MVA/(-/3 XVP)

Through Fault Current on Secondary side of Transformer I PSC(HV):

= 7142.86/(1.732*400)
= 10.31kA

D.1.9

Formula and Requirements-Backup over current Earth fault Protection


The following formulae and requirements are applied

Resistive Burden
RI = (2.IL.rL/1000)

Two way lead resistance

( IL=530 Mtr Longest distance of CT cabling as per Layout)


= (2 X 530 X 3.746 / 1000)

Page 18

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01
=

Rr = Sr/Ir2

Relay burden on CT

= 0.04/1^2
=

VA Burden and Accuracy class of CT in VA


Scal = ISN2*(Rl + Rr)
=

Sreq >= Scal

SCT = ISN2*RCT
=

Protection Class of CT
Protection Class

5P20

(The 5P20 class CT shall comply within composite error of (+/-) 5% for 20 times the rated CT current flow at rated burden.)
Accuracy Limit at Rated Burden, ALFr

= 20

Rated Burden of CT, VAr

= 30.00VA

Actual Buden

= 4.01VA

Accuracy Limit at Rated Burden, ALFr

= ALFr * (VAr + SCT)/(Sreq + SCT)


78

Ohm

Accuracy Limit Current referred to


the secondary of the CT for 5P20

= Accuracy Limit at Rated Burden, ALFr * Ir


78A

Page 19

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01

The CT secondary current during


= Ipsc/IP X Is

max system fault condition

= (10.31 X 1000)/1600 X 1
= 6.44A

Since the maximum fault current seen by the CT is less than the Accuracy Limit Current
We infer that the composite error will be within the limit. Hence 5P20 class, 30VA CT is adequate.

Rated
Frequency(fn)

Rated Short
Time Thermal
Current(Ith)

Duration of
Short Time
Thermal
Current(Ith)

Rated Dynamic
Current(Idyn)

Class as per
IEC

Rated Burden

(A)
1600

(A)
1

(Hz)
50

(kA)
40kA

(sec)
1

(kA)
100

(-)
5P20

(VA)
30

Page 20

RCT

Rated
Secondary
Current(ISN)

Results
Rated Primary
Current at
Tap(IPN)

D.1.10

()
5

DOC. NO. CU-47000-0202


REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

D.2

CT sizing calculation for 400kV LBB, Over current and Earth Fault Protection

D.2.1

Applicable CT and core Numbers:

D.2.2

D.2.3

D.2.4

Feeder Detail

CT Ratio

CT No

Core

ICT-1

1600/1

400-6-CT

ICT-2

1600/2

400-7-CT

Ref. Drawing No.


765/400kV Unnao substation SLD:CU-47000-0001,Rev.00

System Parameter (As per Specification,Vol-II General Technical Requirement 071806-47ES-0200 Rev.0 Cl.6.1)
Variable

Value

Unit

Description

Vn

420

kV

Nominal Voltage

Ispec

40

kA

Primary Short Circuit Current

fn

50

Hz

X/R

30

Maximum duration of short circuit current


System supply Frequency
X/R ratio of system

CT Parameter (As per Specification ,Vol-III Instrument Transformer 071806-47ES-7230 Rev.0.Cl.2.11.2)


IPN

1600

Rated Primary Current

ISN

Rated Secondary Current

RCT

CT Resistance at 75oC

Relay Parameter (As per the attached Annexure 1)


IR

Rated Input Current of BCU used

Sr

0.04

VA

Over Current Protection Relay Burden(Burden & CT Requirement of Micom


Relays)

Page 21

DOC. NO. CU-47000-0202


REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

D.2.5

Secondary Lead Parameter


IL

100

AL

mm2

3.746

km

AC resistance of 6 Sq.mm Cu, lead at 75 oC

--

1000

MVA

Transformer MVA Rating

VP

765

kV

Primary Voltage Rating

VS

400

kV

Secondary Voltage Rating

--

14

Percentage Impedance(As per Specification,Vol-III 017806-47ES-7130


Rev.o Cl.2.8.1,page 3)

rL

D.2.6

D.2.7

Cross sectional area of leads


No of runs of cable connected to CT secondary

Transformer Parameter

Details of Relay Proposed

Relay Type

Rated Current,IR
Short time current carrying capacity,Ith
(relay)

Single way length of leads

Breaker Failure, Backup Over Current & Earth fault Protection Micom: P821/141
: 1A
: 100 X IR for 1s
= 100 X 1 A for 1s
= 100A

Maximum relay input current during through fault, I f

for 1sec

IPSC/IPN X ISN
= 40000/1600 X 1
= 25.00A

Page 22

<100A [Ith(relay)]

DOC. NO. CU-47000-0202


REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

D.2.8
1

Through Fault Current


Through Fault MVA of Transformer

: MVA Rating/% Impedance


= 1000 X 100/14
= 7142.86MVA

Through Fault Current on Seconary


side of Transformer If(MV):

Fault MVA/(-/3 XVP)


= 7142.86/(1.732*400)
=

D.2.9

10.31kA

Formula and Requirements-Backup over current Earth fault Protection


The following formulae and requirements are applied

Resistive Burden
RI = (2.IL.rL/1000)

Two way lead resistance

( IL=530 Mtr Longest distance of CT cabling as per Layout)


= (2X350X3.746/1000)
=

Rr = Sr/Ir2
= 0.04/1^2
=

VA Burden and Accuracy class of CT in VA

Page 23

Relay burden on CT

DOC. NO. CU-47000-0202


REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B
Scal = ISN2*(Rl + Rr)
=

Sreq >= Scal

SCT = ISN2*RCT
=

Protection Class of CT
Protection Class

5P20

Accuracy Limit at Rated Burden, ALFr

20

Rated Burden of CT, VAr

30.00VA

Actual Buden

0.79VA

Accuracy Limit at Rated Burden, ALFr

ALFr * (VAr + SCT)/(Sreq + SCT)


174 VA

Accuracy Limit Current referred to


the secondary of the CT for 5P20

Accuracy Limit at Rated Burden, ALFr * Ir


174A

The CT secondary current during


max system fault condition

Ipsc/IP X Is

Page 24

DOC. NO. CU-47000-0202


REV. 01

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B
=

(10.31 X 1000)/1600 X 1

6.44A

Based on Through Fault Current at D.2.8-(2)

Since the maximum fault current seen by the CT is less than the Accuracy Limit Current
We infer that the composite error will be within the limit. Hence 5P20 class, 30VA CT is adequate.

Rated Secondary
Current(ISN)

Rated Frequency(fn)

Rated Short Time


Thermal Current(Ith)

Duration of Short Time


Thermal Current(Ith)

Rated Dynamic
Current(Idyn)

Class as per IEC

Rated Burden

RCT

Results
Rated Primary Current at
Tap(IPN)

D.2.10

(A)

(A)

(Hz)

(kA)

(sec)

(kA)

(-)

(VA)

()

1600

50

40kA

100

5P20

30

Page 25

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01

E.1

CT sizing calculation for 400kV TEE-Protection

E.1.1

Applicable CT and core Numbers:

E.1.2

E.1.3

E.1.4

Feeder Detail

CT Ratio

CT No

ICT-1

3000/1

400-6-CTT

ICT-2

3000/1

400-7-CTT

ICT-1

3000/1

400-6-CT

ICT-2

3000/1

400-7-CT

Core

Ref. Drawing No.

765/400kV Unnao substation SLD:CU-47000-0001,Rev.00

System Parameter (As per Specification,Vol-II General Technical Requirement 071806-47ES-0200 Rev.0 Cl.6.1)
Variable

Value

Unit

Description

Vn

420

kV

Nominal Voltage

Ispec

40

kA

Primary Short Circuit Current

fn

50

Hz

X/R

30

Maximum duration of short circuit current


System supply Frequency
X/R ratio of system

CT Parameter (As per Specification ,Vol-III Instrument Transformer 071806-47ES-7230 Rev.0.Cl.2.11.2)


IPN

3000

Rated Primary Current

ISN

Rated Secondary Current

RCT

6.8

CT Resistance at 75oC

Relay Parameter (As per the attached Annexure 1)


IR

Rated Input Current of BCU used

Sr

0.025

VA

Maximum Protective relay Burden(Burden & CT requirement of Micom relays)

tm

30

ms

Transformer Differential Relay Operating time(As per Annexure-I)

IS

0.1

tcb

40

ms

Minimum Setting of Relay


Circuit Breaker Operating Time

Page 26

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B
E.1.5

Secondary Lead Parameter


IL

530

AL

mm2

3.746

km

AC resistance of 6 Sq.mm Cu, lead at 75oC

Transformer MVA Rating

rL

E.1.6

E.1.7

DOC. NO. CU-47000-0202


REV. 01

Single way length of leads


Cross sectional area of leads
No of runs of cable connected to CT secondary

Transformer Parameter
--

1000

MVA

VP

765

kV

Primary Voltage Rating

VS

400

kV

Secondary Voltage Rating

--

14

Percentage Impedance(As per Specification,Vol-III 017806-47ES-7130 Rev.o


Cl.2.8.1,page 3)

Details of Relay Proposed

Relay Type

: Connection Diffrential, Micom P122

Rated Current,IR
Short time current carrying capacity,Ith
(relay)

: 1A

: 100 X IR for 1s
= 100 X 1 A for 1s
= 100A

Maximum reay input current during through fault, If

= IPSC/IPN

for 1sec

X ISN

= 40000/3000 X 1
= 13.33A

Full load Current,IL

<100A [Ith(relay)]

= MVA/(-/3 x VP)
= 1000 X 1000/1.732 X 400
= 1443A

E.1.9

Formula and Requirements-Metering


The following formulae and requirements are applied

Rated Symmetrical Short Circuit Current factor(Ksec)


KSSC

As per IEC 44-6(Cl.3.15)


= IPSC/IPN

Page 27

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01
= 40000 X 1000/3000
= 13.33

Standard Value of KSSC

= 17.5

As per IEC 44-6(Cl.4.1)

Primary Time Constant(TP)


For the System Close in Fault

X/R= 30
L/R= 30/(2X3.14X50)

Therefore Primary Time Constant(TP) at system fault

0.096sec
= 95.54msec

Standard Value of TP

= 120

As per IEC 44-6(Cl.4.3)

Duty Cycle(C-O)
Single Energisation

= C-t'-O

where
t' = Duration of first current flow
t'= tm +

tcb

= 70ms
Selected Duty Cycle

(Say 80 ms)

= C-80ms-O

Resistive Burden(External Burden)


RI = (2.IL.rL/1000)

Two way lead resistance

( IL=530. Mtr Longest distance of CT cabling as per Layout)


= (2X530X3.746/1000)
=

Rr = Sr/Ir2

Relay burden on CT

= 0..025/1^2
=

Rb = RI+Rr
=

Page 28

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01

Standard Value of Rb

As per IEC 44-6(Cl.4.5)

Stabilising Voltage
>= If x (Rl + RCT) x ((0.007 x X/R) + 1.05)

Vs

>= 13.33 X (3.97 + 6.8) X ((0.007 X 30) + 1.05)


>= 180.95V

Knee Point Voltage

Vk

>= 4 X Vs
>= 4 X 151
>= 604

Adopted Vk

= 630V

Calculation of stabilizing resistor

Relay setting Voltage

Vs

= 180.95V

Relay setting Current

Is

= 0.1

Relay Burden

Sr

= 0.025

Relay Resistance

Rrelay

= 2.5

Stabilising Resistor

= (Vs/Is) - Rrelay
= 1807 ohms

Rated Equivalent Rated Secondary e.m.f

Eal
Ktd = Ktf =

= Kssc x Ktd x (RCT + Rb) x ISN


2 x pi x f x TP x ( 1 - e(-t'/TP)) + 1

2 x 3.14 x 50 x (120/1000) x (1-e(-0.08/0.12)) + 1

Page 29

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01
Ktd = Ktf =

38.632

Eal

= 15 x 38.632 x (6.8 + 5) x 1

Eal

7978V

As Equivalent Rated Secondary e.m.f is greater than Knee Point Voltage, CT is capable of supplying Eal to the relay circuit.

Rated Primary
Current at
Tap(IPN)

Rated
Secondary
Current(ISN)

Rated
Frequency(fn)

Rated Short
Time Thermal
Current(Ith)

Duration of
Short Time
Thermal
Current(Ith)

Rated Dynamic
Current(Idyn)

Class as per
IEC

Symmetrical
Short Circuit
Current Factor

Primary Time
Constant

Specified duty
Cycle

Resistive
Burden

Equi. Limiting
Sec. e.m.f

E.1.10 Results

(A)
3000

(A)
1

(Hz)
50

(kA)
40kA

(sec)
1

(kA)
100

(-)
TPX

(-)
17.5

(ms)
120

(-)
C-80ms-O

()

(V)
7978V

Page 30

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01
400KV CT PARAMETERS FOR 765KV UNNAO SUBSTATION

DESCRIPTION
7235-1B-400kV Bus
Protection Type
Relay Type
Ratio
Accuracy class
Burden(ohm for TPX & VA for 5P20,
Metering)
Primary Time Constant (ms)
Kssc
Duty Cycle
RCT (ohm)
Equivalent Limiting Scondary e.m.f (V)
Ie (mA) at above Voltage offered

CORE 1

CORE 2

CORE 3

CORE 4

Bus-Bar Protection

Metering*

ABB-RADSS
2000:1
TPX

CORE 5

BCU
1600:1
0.2

LBB, O/C and E/F


Protection
Micom-P141/821
1600:1
5P20

Transformer Diffrential
Protection
Micom-P643
1600:1
TPX

15

10

30

120
20
C - 0.08sec - O

NA
NA
NA

NA
NA
NA

120
25
C - 0.08sec - O

120
17.5
C - 0.08sec - O

5.5
5142
<=30

5
NA
NA

5
NA
NA

5
3089
<=30

6.8
3645
<=20

TEE Protection
Micom-P122
3000:1
TPX

NOTE * : This is as per discussion had on 12th October 2010, with the view to connect this core for Circuit Breaker Control Switching Scheme
7235-2B-400kV ICT
Metering

O/C and E/F Protection

TEE Protection

2000:1
5P20

Transformer Diffrential
Protection
Micom-P633
1600:1
TPX

BCU+Energy Meter
1600:1
0.2

Micom-P141
1600:1
5P20

Micom-P122
3000:1
TPX

30

10

30

NA
NA
NA

120
25
C - 0.08sec - O

NA
NA
NA

NA
NA
NA

120
17.5
C - 0.08sec - O

5
NA
NA

5
3089
<=30

5
NA
NA

5
NA
NA

6.8
3645
<=20

Protection Type

Spare

Relay Type
Ratio
Accuracy class
Burden(ohm for TPX & VA for 5P20,
Metering)
Primary Time Constant (ms)
Kssc
Duty Cycle
RCT (ohm)
Equivalent Limiting Scondary e.m.f (V)
Ie (mA) at above Voltage offered

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01
CROMPTON GREAVES LTD
ENGINEERING PROJECT DIVISION-GURGAON

Project
Client
Consultant
Title
Sl. No
C1.
1

3
4
5
6
7
8

C2.

765KV Substation at UNNAO


Uttar Pradesh Power Transmission Corporation Limited
SNC-Lavalin
Compliance Statement for 400kV CT-Sizing with reference to SNC mail dated 5/10/2010 & Conference call on 6/10/2010.
Description
CGL Reply
Subject: General
The pages of the document are not numbered hence it is not possible to comment with
Noted & Complied
page reference.The same may be numbered.
CT Sizing calculation format of 765kv CTs for Unnao s/s may be follozed to maintain
similarly of the CTs sizing document.For calculation refer to 765kv CT calculation refer
Noted & Complied
to 765kv CT CALCULATION AND FOLLOW iec 44-6 recommendation for calculation
of Eal.Please indicate le (Ma) at this voltage.
For LBB protection 40kA must be considered (It must cover bushing faults
too).Calculation may be revised accordingly
Please confirm that existing BB Protection CTs have 2000/1 CTR.
To cover Bushing faults,design CT based on 40kA,KSSC=40kA/1600=25
Recalculate duty cycle with relay operating time of 80ms and CB operating time of
40ms .The duty cycle will be C-80 O.
For over current protection 40kA must be considered and recalculate accordingly.
A copy of page regarding 765kV CT summary of Unnao s/s is attached.For 400kV CT
similar summary sheet may be prepared after arriving at the final parameter by doing
calculations following the 765kV CT calculation format.

Noted & Complied


Noted & Complied
Noted & Complied
Noted & Complied
Noted & Complied
Noted & Complied

Subject: 400kV ICT CT, 7235-2B, 400-6-CTT & 400-7-CTT


Core1: Modify core no1(spare core) to 5P20 with 40VA power-5P Class,30VA,ALF=20 Noted & Complied
Core2: The different parameters shall be as follows
.Symmetrical SC current factor should be taken 25 instead of 7.5
.Primary time constant-120ms instead of 100ms.
.Specified duty cycle-C-80-O instead of 100ms

Noted & Complied

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01
CROMPTON GREAVES LTD
ENGINEERING PROJECT DIVISION-GURGAON

Project
Client
Consultant
Title
Sl. No

C3.

765KV Substation at UNNAO


Uttar Pradesh Power Transmission Corporation Limited
SNC-Lavalin
Compliance Statement for 400kV CT-Sizing with reference to SNC mail dated 5/10/2010 & Conference call on 6/10/2010.
Description
Core3: Meeting core should be of 1600/1 CTR
.The rated burden should be 10 instead of 30.
.Separate column to be added for Rct

CGL Reply
Noted & Complied

Core4: Separate column to be added forRct

Noted & Complied

Core5: CTR not mentioned , it should be 3000/1


.Rated secondary current written as 420A should be corrected as 1Amp.
.Symmetrical S.C current factor should be 17.5 instead of 15
.Primary time constant should 120ms instead of 100ms
.Specified duty cycle-C-80-O SHOULD BE TACKEN.

Noted & Complied

Subject: 400kV Bus CT, 7235-1B, 400-6-CT & 400-7-CT


Core1: should be used for TEE protection

As per PSLD-CU-47000-0058,
Core 1 is used for B/B Protection
Core 5 is used for TEE-Protection

.CTR not mentioned should be 3000/1 and secondary ampere should be 1Amp
instead of 420Amp
.Symmetrical S.C current factor should be 17.5 instead of 15
.Primary time constant should 120ms instead of 100ms
.Specified duty cycle-C-80-O instead of C-100-O.
.Break operating time tcb should be taken on 40ms in place of 45ms.

Noted and Complied for Core 5

PROJECT: 765kV UNNAO SUBSTATION


TITLE: 400kV CT SIZING
ITEM CODE 7235-1B/2B

DOC. NO. CU-47000-0202


REV. 01
CROMPTON GREAVES LTD
ENGINEERING PROJECT DIVISION-GURGAON

Project
Client
Consultant
Title
Sl. No

765KV Substation at UNNAO


Uttar Pradesh Power Transmission Corporation Limited
SNC-Lavalin
Compliance Statement for 400kV CT-Sizing with reference to SNC mail dated 5/10/2010 & Conference call on 6/10/2010.
Description

CGL Reply

Core2: Should be used for differential protection

As per PSLD-CU-47000-0058,
Core 2 is Spare - as per the discussion with
UPPTCL dated 12/10/2010 this core will be
0.2(Metering)-sizing is same as the core 3 of
400-6/7-CTT, with the view to connect this
core for Circuit Breaker Control Switching
Scheme
Core 4 is used for Transformer Diff. Protection

.CTR should be 1600/1 instead of 2000/1


. Symmetrical SC current factor should be taken 25 instead of 7.5
.Primary time constant should 120ms instead of 100ms
.Specified duty cycle-C-80-O instead of C-100-O.
.Resistive burden should be 5 instead of 2.

Noted and Complied for Core 4

Core3: Column of Rct should be added

Noted & Complied

Core4&5: Should be used for existing protection circuit ,the ratio of 2000/1

Please refer the reply for core 1 & core 2