December 2011
Thank you
Douglas M. Schanne
Assistant Director
December 2011
Based Upon
Based Upon
2003 IRC
2009 IRC
Sections in
reference to:
Sections in
reference to:
Ventilation
Exhaust
Duct Systems
Ventilation
Exhaust
Duct Systems
As amended by the
2005 Amendment
to the Connecticut
Supplement
As amended by the
pending 2011?
Amendment to the
Connecticut
Supplement
3
December 2011
Course Objectives
Course Objectives
Ventilation
Exhaust
Duct Systems
Operation
Comfort
Indoor Air Quality
Ventilation
Natural Ventilation
What Is It?
When Can We
Use Natural
Ventilation?
Section R303
R303.1
1
Minimum open
able area to the
outdoors
4% of the floor
area being
ventilated
7
December 2011
4% Example #2
4% Example #1
20 ft
Applying R303.1
Applying R303.1
20 ft
20 x 30 = 600 sq ft
4% Of Floor Area
Open able
Windows
20 x 30 = 600 sq ft
4% Of Floor Area
30 ft
4% x 600 =
.04
04 x 600 = 24 sq ft
Open
p Able
Window
30 ft
600 x 4%
%
600 x .04 = 24 sq ft
32 sq ft open able
area (vs.) minimum
of 24 sq ft
Open able window dimension of
48w x 48h = 2304 sq = 16 sq ft
2 windows x 16 sq ft = 32 sq ft
12 sq ft operable
area (vs.) minimum
of 24 sq ft
Adjoining Spaces #1
Adjoining Spaces
20 foot
Section R303.2
20 foot
Required Opening
An Adjoining Room
When or greater of the
common wall is open and
unobstructed
Opening not less than
1/10 of the floor area
10
30
Door #1
60 X 20 = 1200 sq ft
4% of area =
Door #2
30
1200 X .04 = 48 sq ft
60
Door
D
= 4 X 7 = 28 sq ft
60
Adjoining Space
56 Sq Ft
30
Adjoining Space
12
December 2011
Adjoining Spaces #2
Required Opening
Bathroom Ventilation
20 foot
Section R303.3
Bathrooms
Door #1
60 X 20 = 1200 sq ft
4% of area =
Door #2
30
1200 X .04 = 48 sq ft
Aggregate Glazing
Area
60
30
Adjoining Space
of which must be
open able
Where Required
Under
Under--floor space between the
Minimum
u net
et a
area
ea o
of ventilation
e t at o ope
openings
gs
One opening to be
15
14
16
December 2011
Ventilation Openings
3 Feet
3 Feet
Opening Exceptions
Exception #5
Natural Ventilation
Climatic conditions
Opening reduction
With approved vapor barrier
Cross ventilation provided
Space
p
used as supply
pp y
plenum
18
EXCEPTIONS
Refers over to
Section N1102.1.7 Crawl Space Walls
Mechanical ventilation
Rate of 1.0 cfm / 50 sq ft
No ventilation openings
Approved vapor retarder
Space is supplied with
conditioned air
19
20
December 2011
CT Uses Zone 5
Table N1102.1
INSULATION AND FENESTRATION REQUIREMENTS BY COMPONENT
b
CEILING
WOOD
MASS
CLIMATE FENESTRATION SKYLIGHT
GLAZED
b,e
b
ZONE
R-VALUE FRAME WALL WALL i
U-FACTOR
U-FACTOR FENESTRATION
SHGC
R-VALUE
R-VALUE
1
2
3
4 except
Marine
5 and
Marine 4
6
7 and 8
1.20
0.65j
0.50j
0.35
0.75
0.75
0.65
0.60
0.30
0.30
0.30
NR
30
30
30
38
13
13
13
13
0.35
0.60
NR
38
49
49
0.35
0.35
0.60
0.60
NR
NR
FLOOR BASEMENT
WALL
RVALUE
R-VALUE
SLAB
R-VALUE
& DEPTH
CRAWL
c
SPACE
WALL
R-VALUE
3/4
4/6
5/8
5 / 10
13
13
19
19
0
0
5 / 13f
10 / 13
0
0
0
10, 2ft
0
0
5 / 13
10 / 13
20 or 13+5h
13 / 17
30g
10 / 13
10, 2 ft
10 / 13
15 / 19
19 / 21
30g
38g
15 / 19
15 / 19
10, 4 ft
10, 4 ft
10 / 13
10 / 13
20 or 13+5
21
21
22
Vent Clearance
24
December 2011
Necessity Of Mechanical
Ventilation & Exhaust Systems
Definitions Relating To
Mechanical Ventilation & Exhaust
Mechanical System
Reference To:
25
Definitions Relating To
Mechanical Ventilation & Exhaust
Continuation
Ventilation
The natural or mechanical process of
supplying conditioned or unconditioned air
to, or removing such air from, any space
Exception #1
Applies for the use of Mechanical Ventilation
Part 1
NOTE:
Ventilation and venting are two separate
processes
27
26
28
December 2011
20
Part 2
Window
12
Application:
Room is:
Computation base
Bedroom
#2
Bath
Hallway
Bedroom #3
Bedroom
#4
Bedroom
#5
5 Bedroom Home
30
Master = 2 occupants
#2
= 1 occupant
#3
= 1 occupant
#4
= 1 occupant
#5
= 1 occupant
Total occupant load = 6 X 15 cfm = 90 cfm
90 cfm whole house mechanical ventilation is
necessary
50 cfm intermittent
20 cfm continuous
32
December 2011
Referenced Table
Second
Exhaust systems shall have the capacity to
exhaust the minimum air flow rate
As per Table M1506.3
33
Opening Locations
34
Figure R303.4.1
From 2003 IRC Commentary
35
36
December 2011
Exhaust Location
Opening Protection
Outside Opening
Protection R303.5
To be provided with
corrosion resistant
Screens, Louvers or
Grills
Minimum opening
Of inch
Maximum opening
Of inch
38
37
Underfloor Mechanical
Ventilation
Exception #4
Of Section R408.2
Vapor Retarder:
With continuous
ti
mechanical
h i l
ventilation
40
10
December 2011
Example
Exception #4 Continued
50
30
Crawl Space
Crawl
C
l Space
S
= 50 long X 30 wide =
1500 Square Ft
1500 sq ft / 50 sq ft = 30
30 X 1.0 cfm = 30 cfm
Answer:
30 cfm of Mechanical Ventilation is needed
41
42
Ventilation Openings
Each Opening Must Go
Directly to the outdoors
Horizontally
sq ft / 1000 cu ft of garage
volume
l
Natural Ventilation
Section M1307.4.1
For indoor operations
M1307.4.1.2
44
11
December 2011
Example #1
20
Garage Area
NOTE: Ceiling
height = 8 feet
30
Garage Area
Ventilation rate of
Exhaust Systems
Engineered Installations
Section M1307.4.3
Specially Engineered
Installations
47
46
48
12
December 2011
2009 IRC
50
Exhaust Duct
Section M1501.3
Not to exceed 25 feet in length
Restriction reductions
45 degree = 2.5 feet
90 degree = 5 feet
51
52
13
December 2011
Range Hoods
No termination in
Attic
Crawl Space
Inside of Building
Wall duct
53
Exception
Exception
55
54
56
14
December 2011
Downdraft Exception
Range Hoods
Exception to M1503.2
Exhaust
E h
t hood
h d systems
t
exhausting
h
ti iin excess
of 400 cubic feet per minute
Shall be provided with makeup at +/- equal rate
Makeup air systems equipped with means of
closure and automatic controls to start and operate
simultaneously with exhaust system
Maximum of 1 inch
Microwave Oven
Installation
58
Section M1504.1
Minimum of 28 gage
24 inches
59
60
15
December 2011
Minimum
Dimensions
Mechanical Ventilation
2009 IRC Section M1507
Unit is to be
As wide as the cookcook-top
Extend over the cook
cook--top
AREA TO BE VENTILATED
VENTILATION RATES
Kitchens
Bathrooms-Toilet Rooms
61
62
Chapter 16
Duct Systems
Short Break
Plenum
A chamber that forms apart of an airair-circulation
system other than the occupied space being
exhausted.
63
64
16
December 2011
Duct Construction
Section M1601.1.1
Section M1601.1.2
65
66
NFPA 255
67
68
17
December 2011
70
Acceptable Installation
Wall Cavities & Joist Spaces Criteria
Wall Studs
Fireblocking
72
18
December 2011
Underground Duct
Unacceptable
Section
Construction Materials
Concrete, Clay, Metal, Plastic
Maximum Temperature
150 degrees F. for plastic duct
74
U. L
UNDERWRITERS
LABORATORIES
LISTED
Must be
AIR DUCT
CLASS 1
Medium velocity.4,000 F
Medium positive pressure..3 in. v
Maximum negative pressure..5 in.v
75
A
U. L
CONNECTOR
FOR INSTALLATION IN LENGTH
NOT OVER 14 FT
FT.
CLASS 1
ISSUE NO. 11,000
MAXIMUM VELOCITY..4,000 FPM
MAXIMUM POSITIVE PRESSURE10 IN. H20
MAXIMUM NEGATIVE PRESSURE2 IN. H20
76
19
December 2011
Insulation Conformance
Factors
Duct wrap
Legible markings
Installed thickness
79
78
80
20
December 2011
Vibration Isolators
Installation Of Ductwork
Joints are to be
substantially air tight
Joint & Seam sealing
Tapes, Mastics, Gasketing &
other approved means
All methods to comply with
their UL rating
81
Examples
82
Connections
Meets UL 181A
UL 181 A
A--P = Pressure Sensitive Tape
UL 181 A
A--M = Mastic
UL 181 A
A--H = Heat Sensitive Tape
Meets UL 181B
UL 181 B
B--FX = Pressure Sensitive Tape
UL 181 B
B--M = Mastic
Minimum fastening of
3 sheet met screws or
rivets, equally spaced
83
84
21
December 2011
Duct Support
Do I Need To Fireblock?
Non
Non--metallic ducts
To be supported as per MFG
installation instructions
85
Insulation Installation
86
Insulation Installation
Duct Insulation
Section M1601.4.5
(Formerly M1601.3.4 of 2003 IRC)
It shall be installed in
accordance with three
separate requirements
Requirements
Vapor Retarder
Maximum permeance of 0.05
perm
Exterior Duct
System
Aluminum Foil
Minimum thickness of 2 mils
To be protected
against the elements
88
22
December 2011
Insulation Thickness
Ducts In Garages
5/8
26 Gage
89
90
Return Air
91
92
23
December 2011
Prohibited Sources
Prohibitions Continued
If Room Or Space
Exception
93
94
Prohibited Sources
Prohibitions Continued
Exception
Closet
Bathroom
Kitchen
Garage
Mechanical Room
Furnace Room
Or another dwelling
24
December 2011
Combustion Air
Oil-Fired appliances
What Is
98
Sleeping rooms
Bathrooms
Toilet Rooms
Exceptions
If solid fuel, provided it is not a conditioned space
If all air is from outdoors and enclosure uses
99
100
25
December 2011
Section M1702.2
Opening dimensions for each opening
Required Volume
102
Diagram Example #1
Opening size
FURNACE
104
26
December 2011
Diagram Example # 2
Diagram Example # 3
Vertical Ducts
Ventilation Louvers
Duct Sizing
1 sq in/4000 Btu total
input
OUTLET
Within 12 In.
In
Of Ceiling
Furnace
To be
within 12 in
of ceiling
Air Openings
OUTLET
FURNACE
Within 12 In.
Of Floor
INLET
Opening to be within
12 inches of floor
OPENINGS =
1 Sq. In./ 2,000
Btu
Of Input
INLET
105
106
Diagram Example # 1
(2003 IRC)
Ventilation Louvers
OUTLET
FURNACE
To be
within 12 in
of ceiling
6 inch
minimum
extension for
both.
To be a minimum of
2 times the required combustion air opening
INLET
Opening to be within
12 inches of floor
107
108
27
December 2011
Diagram Example # 3
Diagram Example # 2
Ventilation Rate
Ventilation Rate
1 sq in / 4000 Btu/h
6 Inches
Inlet
6 In.
Above
Insulation
Within 12
Inches Of
Outlet Ceiling
Furnace
Within 12
Inches Of
Floor
Outlet
Minimum
i i
12 Inches
Within 12
Inches
Furnace
CRAWL SPACE
Within 12 Inches
109
Inlet
Opening to outside to
be a minimum of 2xs
the required size for
combustion air
110
111
112
28
December 2011
113
115
114
116
29
December 2011
117
118
120
30
December 2011
Enclosure Clearances
B
FURNACE
FRONT
FURNACE
1 Inch
Minimum
6 INCH
MINIMUM
121
122
Example Problem
20
20
2 - 33 Dia.
Dia
Openings
2 Openings 10 x 20
40
123
30
NOTE: Ceiling 8
124
31
December 2011
Problem Continued
TOTAL INPUT:
200,000 Btu/hr
Question
Volume Of B:
4800 C
Cubic
bi F
Feett
Required Volume =
10,000 Cu.Ft.
Cu.Ft
Available Volume =
NO
125
126
Problem Continued
Problem Continued
Determine The Required Area Of Each
Outdoor Opening?
Question
Do openings between A & B meet
requirements of G2407.5.3
Required Area =
Required Area =
Actual Area =
200 Square Inches
YES
127
OK
128
32
December 2011
Contaminants
Moisture
Mold
Hazardous Products
Promoting a healthy
and safe environment
129
Questions??