Professional Documents
Culture Documents
CHAPTER
1
BASIC PRINCIPLES
1.1
Maintenance requirements
The consequences of equipment or plant failure.
Protection systems must not interfere with or limit the normal
operation of the system but must continuously monitor the system to detect
electrical failure or abnormal electrical conditions.
Further important aspects in the design of the power system are:
Incorporation of features aimed at preventing failures, and
Provisions for mitigating the effects of failure when it occurs.
Modern power system design employs both recourse as dictated by
the economics of any particular situation. Notable advances continue to
be made toward greater reliability. However also, increasingly greater
reliance is being placed on electric power. Consequently, even though the
probability of failure is decreased, the tolerance of the possible harm to the
service is also decreased.
The type of electrical failure that causes greatest concern is the
short-circuit, or fault as it is usually called, but there are other abnormal
operating conditions peculiar to certain elements of the system that also
require attention. Some of the features of design and operation aimed at
preventing electrical failure are:
Provision of adequate insulation
Coordination of insulation strength with the capabilities of
lightning surge arresters
Use of overhead ground wires and low tower-footing resistance
Design for mechanical strength to reduce exposure, and to
minimise the likelihood of failure caused by animals, birds,
insects, dirt, sleet, bushfires, etc.
Proper operation and maintenance practice.
Some of the features of design and operation for mitigating the effects
of failure are:
Features that mitigate the immediate effects of an electrical failure
1. Design to limit the magnitude of short-circuit current
(a) By avoiding too large concentrations of generating
capacity
(b) By using current-limiting impedance
2. Design to withstand mechanical stresses and heating owing
to short-circuit currents
3. Time-delay undervoltage devices on circuit breakers to
prevent dropping loads during momentary voltage dips
4. Ground-fault neutralisers.
BASIC PRINCIPLES
1.2
1.2.2 Generators
Generators appear in a number of sizes ranging from less than 1 MW
(typically in a cogeneration plant) to 600 MW or more in a large fossil
fuelled station. Generated voltages are generally constrained in the range
of 6.6 kV to 33 kV due to design limitations in the generator insulation
systems. This means that step-up transformers are generally needed to
connect the generator to the transmission system. Important parameters
in the design of protection for the system and the generator are the generator
impedances.
A distinction is made for two conditions, namely the direct and
quadrature axis which cover the positions when the axis of the rotor poles
are in phase with the machine poles, or 90 electrical degrees out of phase.
Fault currents (resulting from a short-circuit on the power system) are
mainly reactive and as they cause drops in the direct axis voltage, we use
the direct axis impedances for fault calculations.
The impedance of the generator varies with time following inception
of a fault, due to the inductive nature of the generator electrical circuit.
The value depends on the time that has elapsed from the inception of a
short-circuit. Impedances in three time zones are specified for calculation
of currents and voltages:
Subtransient impedance (X d )determines the level for
short-circuit current during the first 1 to 3 cycles after short-circuit
inception.
Transient impedance (Xd)determines the level of current that
a particular generator will contribute to a short-circuit during
the transient period between 3 to 20 cycles.
Synchronous impedance (Xd)determines the steady state value
of short-circuit current after the transient period.
BASIC PRINCIPLES
1.2.3 Transformers
Power transformers of various sizes are located throughout the power
system. Step-up transformers convert the generator voltage to levels
suitable for the transmission system which transmits bulk power to the
load centres. Depending on the size of the system, transmission voltages
will range from 132 kV to 500 kV. Step-down transformers reduce the
voltages at the bulk load centres to typically 66 kV or 33 kV for distribution
through a subtransmission network which supplies the high voltage
distribution system. The distributions system is typically 33, 22 or 11 kV
and supplies distribution substations that transform the voltage to the
customer level.
1.2.4 Lines
Impedances, for calculation of fault currents, are the most important line
parameter for protection purposes. These are usually calculated in resistive
and reactive ohms at system frequency and are expressed in the form R + jx
or ZQ. The R term is the resistance per phase and the jx term is obtained
from the basic equation of the type
jx = k log10
F Separation of conductors I
GH k Radius of conductor JK
1
1.3
SWITCHING ARRANGEMENTS
BASIC PRINCIPLES
10
11
BASIC PRINCIPLES
Feeder 1
A
G2
is left with generator 2 disconnected. The mesh layout is flexible and uses
less CBs than the double switched arrangement. There are no particular
12
1.3.4 1 CB Switching
A more elaborate system than the mesh system is the 1 CB arrangement
(Fig. 1.4).
This arrangement uses more CBs than the mesh arrangement but
gives better reliability for faults in the transmission lines or generation
plant. Again, provided current transformers and voltage transformers are
carefully located the protection arrangements is straight forward.
13
BASIC PRINCIPLES
giving rise to artificial earth fault current in the relay circuits. Special
operating procedures may be required to overcome this problem.
1.4
14
1.5
Low voltage
switchgear
High voltage
switchgear
Power transformer
High voltage
switchgear
Transmission line
Observation:
Circuit breakers are located in close proximity to each power
system element. This provision makes it possible to disconnect
only a faulty element. Occasionally, a breaker between two
adjacent elements may be omitted, in which event both elements
must be disconnected for a failure in either one.
A separate zone of protection is established around each system
element. The significance of this is that any failure occurring
within a given zone will cause the tripping (i.e., opening) of all
circuit breakers within that zone, and only those breakers.
It will become evident that, for failures within the region where
two adjacent protective zones overlap, more breakers will be
tripped than the minimum necessary to disconnect the faulty
element. However, if there were no overlap, a failure in a region
between zones would not lie in either zone, and therefore no
BASIC PRINCIPLES
15
16
BASIC PRINCIPLES
17
1.6
18
Z1B
Z2B
Z3B
End Zone
Zone 1
Zone 2
Zone 1
X
Y
=
=
=
=
=
19
BASIC PRINCIPLES
2. Unit Protection
These are schemes that respond to fault conditions lying within a
clearly defined zone. They utilise information from two or occasionally
more points in a system. In most cases a unit protection system involves
the measurement of quantities at each end of the zone, and the transmission
of information between the equipment at zone boundaries. Examples of
unit protection are differential current relays where the current entering a
zone is compared with that which leaves it. Also phase comparison carrier
protection is another example.
1.7
ZONES OF PROTECTION
Protected zone
C
R
Protected
zone
Back up
zone
20
Standby protection
zone
Line
Voltage
transformer
X
1.8
COMMON TERMINOLOGIES
21
BASIC PRINCIPLES
Load power
Phase-earth
Phase-phase
Two phase-earth
Three phase
Time