SPARK DETECTOR
EV 395
TECHNICAL INFORMATION
EDS srl - Via Ca' Nova Zampieri 6 - 37057 S. G. Lupatoto - VERONA - ITALY - Tel. +39-045-547529 - Fax +39-045-8750065
email: eds@eds.eu - Web: www.eds.eu
EV 395 SPARK
DETECTOR
The EV395 Spark Detector is suitable for a really quick
detection of sparks that can be conducted in the pipes of
silos or storehouses that contain flammable materials like
wood sawdust, ecc.
The extreme quickness of the response of this detector
can prevent the starting of a fire causing great damages to
things and people.
1 - MOUNTING INSTRUCTIONS
1.1 - The detector can be used as a standalone detector
(reccomended) or with its EV521 control unit designed
specifically for this usage. The EV521 can control two
EV395 detectors. This Contro Unit is equipped with a
stabilized power supply, Test circuits, timers and 4
output relays. Moreover the Control Unit contains very
quick circuits so that the response time results very short.
2 - OPERATION
2.1 - With reference to fig. 5 about a 2 detectors installation,
if a burning spark passes through the first detector's field of
view, the EV395 detector gets in alarm condition, its output
relay immediately activates and remains activated for a time
duration equal to the one set with P2 trimmer between 0 and
10 seconds. The output contact of this relay will be used to
drive VL1 electrovalve that will activate the water spraying
by the SS1 noozle for a first extinguishing attempt.
2.2 - If the spark has been extinguished, the system returns to
normal operation, otherwise the spark, continuing its ride, wil
enter in the field of view of the second EV395 detector.
This will activate its output relay. The contact of this relay will
drive VL2 electrovalve that will activate the water spraying
by the SS2 noozle for a second extinguishing attempt.
4 - NOZZLE POSITIONING
4.1 - The spaying noozle has the function of extinguishing
the spark.
Its position must be calculated taking in account the
times detailed in the previous chapter and the speed of
the fluid or materials flowing in the pipe.
For a calculation of the mean value, a simple Physics
formula can be used:
S = vt
where :
S= covered lenght in meters
v= speed of the fluid in the pipe m/s
3.1 - The times to evalauate during the designing process of a t= response time of the security system
spark detection system are the following:
The fluid speed has to be measured in place.
T1 - response time of EV395 detector
Normally the following speed is measured:
T2 - response time of the detector's output relay
T3 - acquisition time of EV521 Control Unit and response wood industry : 20-30 m/s
time of its relay
textile industry : 10-20 m/s
T4 - response time of extinguishing electrovalve VL
T5 - filling time of the part of pipe goig from the For other applications a measurement is required.
electrovalve to the noozle SS and time of water cone So the calculation is simple knowing the 3 parameters
generation
of the formula.
3 - RESPONSE TIME
5 - MAINTENANCE
5.1 - The Spark Detector must be periodically cleaned.
The detector has to be unmounted from its brackets or
fixing and its viewing window has to be washed with a
cloth dampened with water and little soap. No type of
alchool or solvent should be used.. This operation has
to be done periodically according to the type of fluid.
The fluid flowing in the pipe normally keeps the
window clean by rubbing. The normal dust quantity that
settles on the viewing window do not have any influence
on the detector's operation because the infrared radiation
passes through the dust.
5.2 - Periodically check the mechanical parts of the
system.
If an automatic shutter or a fluid deviation device is
used, it is necessary to periodically verify its
operation and to lubrificate the moving parts.
5.3 - Periodically verify the operation and tightness of
the water interception electrovalve. A tightening defect
can cause a flooding of the pipe resulting in damages.
distance
distanza
[m]
30
tempo diresponse
risposta
System
del sistema 0,25s
time 0.25 sec
25
20
15
zona
consigliata
Suggested
area
10
dousare
not use
non
velocit
fluid
delspeed
fluido
0
0
10
15
20
25
30
[m/s]
fig.1
5
Relay
Fig. 1
NC
RELE'
RELAY
EV395
NA
C
1
fig.2
TEST
Electrical Connections Diagram
6
24Vcc,ca
Pipe
Spraying Nozzle
electrovalve
pressure gauge
electrovalve
pressure gauge
water supply pipe
EV395 Detector
nozzle
EV395 Detector
nozzle
automatic shutter
Silo
5.0
viewing window
finestra di visione
DS581A
162.0
56.0
pipe surface
parete della tubazione
bracket
staffa
fig.5
fig.6
9
Spark Detector
EV 395
TECHNICAL INFORMATION
ADVANTAGES
APPLICATIONS
wood industry:
sawdust
shavings
textile industry:
cotton
all other fibres
food industry:
cereals
If the transporting pipe has not a cylindric shape, for example squared
or rectangular, it can be necessary to use two opposed detectors, to
avoid dead zones external to the viewing range of the detector.
The detector's box is made of fusion light alloy with IP67 protection,
and so the internal electronics are protected from dust, shocks and
from ambient conditions, that can be also corrosive, permitting to
use the detector outdoor for a long time without any problem.
The EV395 detector is able to reveal sparks that cross its viewing
range even if they have a great velocity (up to 100 km/h).
The detector is equipped with an optical head sensible to infrared
radiation, that has a viewing range of more than 90 degrees (solid
angle) and a suitable electronic circuit that provides the
amplification and managing of the signal.
When the EV395 detector intercepts a spark it provides the
powering of a relay suitable to switch on optical and acoustic
alarms. Moreover a fire extinguishing system ( splinker ) can be
activated.
For the former function it is suggested to use our EV 521 control
unit that has a great using flexibility.
If the pipes have a large diameter (over 0,5 m.) several EV395
detectors can be used to obtain a better security level .
If a water spraying automatic extinguishing system is also
present,the spark extinguishing can be verified.
10
TECHNICAL DATA
power supply: 24 V cc or ac
power consumption: 20 mA (no alarm) - 50 mA (alarm)
optical viewing solid angle: 90 degrees
max detecting distance: about 50 cm
sensitivity regulation
regulation of relay powering time: 1-10 sec
pins to connect a remote test button
alarm LED
output relay: 6A/24V
fusion light alloy metal box
protection index: P67
dimentions: 140x135x85
weight: 0,7 Kg
water feed
pipe
water cone
electrovalve
transporting
pipe
pressure meter
nozzle
shutter
SILO