Analog Input Module, 16-Bit, 8 Isolated Inputs

IC200ALG240
September 2010

GFK-1522F

Product Description

Module Characteristics

Analog Input Module IC200ALG240 is an intelligent module that accepts


input signals from up to 8 analog devices and provides input data with 16
bits of resolution.

Channels
Module ID
Isolation:
User input to logic (optical)
and to frame ground,
Group to Group
Channel to channel
LED indicators

FLD
PWR OK

ANALOG INPUT
VOLT/CURR ISO
1234567

16BIT
8CH

Backplane current
consumption
External power supply:
Range
Current consumption
Thermal derating
Diagnostics

814

In current mode, a separate power supply may be required for isolated


inputs. Module features include:

250VAC continuous; 1500VAC for 1 minute


Not applicable
250VAC continuous; 1500VAC for 1 minute
FLD PWR LED indicates the presence of both logic
power and user power. OK LED indicates module
status.
5V output: 15mA maximum.
3.3V output: 120mA maximum
+19.5 to +30VDC including ripple
100mA maximum plus load currents
None
High/Low Limit, Over/Under-range, Open Wire, Loss
of Field Power Supply, Non-volatile memory fault

Input Characteristics

Eight isolated 4-20mA current input channels


Sixteen-bit converter resolution
Open wire detection
High-accuracy factory calibration

Input operating range


Accuracy at 25 degrees C
Temperature coefficient

The following additional features are software-configurable:

Eight inputs
FFFF9802

Per-channel selection of 4-20mA current or +/10V voltage inputs


Selectable input filter to reject normal mode AC pickup noise
Selection of default/hold last state operation
Per-channel selection of default values
Per-channel selection of under-range and over-range diagnostics
levels
Per-channel selection of alarm levels
Per-channel scaling

Analog Resolution (1 LSB)


Channel data update rate
Channel-to-channel
crosstalk rejection
Input default
Field input DC resistance
Field input filter

Host Interface
Diagnostics

Normal mode (power line


frequency) rejection
Field Input Ranges

The module reports over/under range, open wire, loss of field power
supply, and high/low alarm diagnostics.

Maximum field input


(without damage)

The module provides eight words of analog input data.

LED Indicators
The green FLD PWR LED indicates the presence of both backplane
power and field power for the analog field-side circuits. The absence of
either backplane or field power turns off the FLD PWR LED.
The OK LED indicates module status:
On green indicates normal operation
Flashing green indicates boot mode or update
Flashing amber indicates self-diagnostic error
Off indicates no 3.3V backplane power

Preinstallation Check
Carefully inspect all shipping containers for damage. If any equipment is
damaged, notify the delivery service immediately. Save the damaged
shipping container for inspection by the delivery service. After unpacking
the equipment, record all serial numbers. Save the shipping containers
and packing material in case it is necessary to transport or ship any part
of the system.

Current mode: +1 to 20mA


Voltage mode: +/-10VDC
+/- 0.1% maximum of full scale
Current mode: 45ppm/C typical, 90 ppm/C
maximum
Voltage mode: 30ppm/C typical, 60 ppm/C
maximum
Current mode: 381 nA nominal
Voltage mode: 381 V nominal
Approximately 20 mS max. @ 50 Hz filter frequency
Approximately 16.7 mS max. @ 60 Hz filter frequency
70dB minimum
Configurable
Current mode:150 Ohms
Voltage mode:760 KOhms
Type: Digital w/programmable notches at 50 or 60 Hz
3 dB Corner Frequency: 10Hz 25%
35 dB minimum
Current mode: Approximately 0 mA to +25 mA
Voltage mode: Approximately 12.5 V to +12.5 V
Current mode: 35 mA continuous
Voltage mode: 17.5 V continuous

Analog Input Module, 16-Bit, 8 Isolated Inputs


IC200ALG240
September 2010

GFK-1522F

Compatibility

Operating Notes

Firmware version 1.24 is compatible with all hardware versions of the


ALG240.

This module is compatible with:

PLC CPU firmware version 1.20 or later.

Profibus NIU PBI001Firmware version 1.10 or later. Version 2.01 or


above is required to perform software configuration.

DeviceNet NIU DBI001 Firmware version 1.10 or later. The


DeviceNet NIU does not support software configuration. Therefore,
analog modules used with a DeviceNet NIU must be autoconfigured
and use their default configuration settings, which severely limits
their functionality.

When a Loss of IO Module fault is logged for the module, the CPU
or NIU will use the Default/Hold Last State setting from the Module
Parameters tab of the module configuration to determine what value
should be reported to the reference tables.

Ethernet NIU EBI001 all versions.


Genius NIU GBI001 Firmware version 1.10 or later. Version 2.0 or
above is required to perform software configuration.

Product Version Information


Rev
IC200ALG240-FD
IC200ALG240-GD
IC200ALG240-GC

IC200ALG240-FC
BXIOAI8215-FC
IC200ALG240-EC
BXIOAI8215-EC
IC200ALG240-EB

Date

The Field Power LED does not always reflect the actual state of field
power. It remains off regardless of whether field power is on or off in
the following circumstances:
Backplane power is off.
The module has encountered a fatal error and is flashing an
error code on the OK LED.

If the hot insertion of a module is done improperly, operation of other


modules on the same backplane may be disrupted. See Installing a
Module on a Carrier in the VersaMax Modules Manual, GFK-1504.

Problems Resolved for Revision 1.24


Description

September 2010 Firmware version 1.24


Upgrade 44A752313-G03
August 2009

Changed manufacturing location. No


changes to compatibility, functionality or
performance.

October 2008

Updated Power Supply OK signal


circuitry.

Restrictions and Open Issues

September 2007 Firmware version 1.20


Upgrade 44A752313-G02
July 2005

Improvement to latching mechanism.

IC200ALG240-DB
BXIOAI8215-DB

April 2004

Changed to V0 plastic for module


housing.

IC200ALG240-CB
BXIOAI8215-CB

January 2004

IC200ALG240-BB
BXIOAI8215-BB

May 2003

Additional faults may be logged when a new configuration


containing parameter changes such as the Alarm High limit or
Alarm Low limit in the hardware configuration of an analog module
is stored followed by a Clear All operation. The additional faults are
logged against the previous configuration. This issue is observed
when Machine Edition is connected to Versamax CPUs
(IC200CPU001, IC200CPU002, IC200CPU005 and
IC200CPUE05) and does not occur with Versamax NIUs
(IC200GBI001, IC200EBI001, IC200PBI001, and IC200DBI001).

When more than 20 faults are sent to a GBC70 within a single


Genius scan, under rare conditions one fault or fault contact may
not be reported by the GBC70. This has been observed when
simultaneous open wire condition occurs in all eight channels of
IC200ALG240 module or if several I/O modules in a GNIU rack
generate multiple faults simultaneously. This issue has only been
observed when the GBC70 was in a rack with an RX7i CPU.

When 45 or more faults are sent to a GBC70 within a single


Genius scan, a few faults or fault contacts may not be reported by
the GBC70. This is most likely to be caused by the sudden loss of
numerous blocks at each bus controller in the system. The
resulting PLC diagnostics and diagnostic contacts may be
incorrect.

ATEX approval for Group 2 Category 3


applications.
Firmware version 1.10
Upgrade 44A752313-G01
Enhanced error detection

June 2001

When more than eight faults occur in a Versamax Intelligent


Analog I/O modules scan, it does not report all faults and fault
contacts to the CPU.
This issue is resolved in release 1.24.

BXIOAI8215-EB

IC200ALG240-AA
BXIOAI8215-AA

Default/Hold Last State Configuration: If there is an error on a


specific input channel, the module will always report the Channel
Default value from the Input Parameters tab of the module
configuration.

Firmware version 1.00


Initial product release

Analog Input Module, 16-Bit, 8 Isolated Inputs


IC200ALG240
September 2010

GFK-1522F

Diagnostics

Wiring Connections for Carriers with Two Rows of Terminals

Over-Range: The module reports an Over Range fault if an input value


is greater than approximately +12.5 volts or 25mA.

Shield Connections

Under-Range: The module reports an Under Range fault if an input


value is approximately 0mA on an current channel or 12.5 volts on a
voltage channel.

V
A

Open Wire: The module reports an Open Wire fault on current inputs if
the configuration of the low end of the range is greater than or equal to
approximately 2.0mA, but the input is not detecting current.

1
1

Loss of Field Power Supply: The module reports a Loss of Field Power
fault if field power is not present (also indicated by the FLD PWR LED).
Inputs default as specified by the configuration.

2
V

13

The module is calibrated at the factory. For most applications, no further


calibration is required. It is possible to perform recalibration by changing
a modules scaling so its scaled data agrees with metered values.

Connection

B1
B2
B3
B4
B5
B6
B7
B8
B9
B10
B11
B12
B13
B14
B15
B16
B17
B18

Shield Termination
VIN5IIN5VINIIN5+
Shield Termination
VIN6IIN6VINIIN6+
Shield Termination
VIN7IIN7VINIIN7+
Shield Termination
VIN8IIN8VINIIN8+
No connection
No connection

7
7
I

8
8
AI6

10

10
V

AI3

11
11

12
12

13

14

13

14
V

AI7

AI4

15
15

16
16

17
17

18
18

AI8

10

11

12

AI3

13

14

16

18

10

11

12

AI7

AI5

I
2

17

V
6

AI8
15

AI6

AI1

I
2

18

17

16

Cable Shield Connections


If the module is installed on a Terminal-style I/O Carrier or a Compact
Terminal-style I/O Carrier, the cable shield can be connected directly to
the carrier.

Field Wiring Terminals


Number

AI4
15

AI2
7

Connection

AI2

6
V

I
14

Calibration

Shield Termination
VIN1IIN1VINIIN1+
Shield Termination
VIN2IIN2VINIIN2+
Shield Termination
VIN3IIN3VINIIN3+
Shield Termination
VIN4IIN4VINIIN4+
DCDC+

5
5

AI5

Low Limit: The module reports a Low Alarm fault if an input value is
less than or equal to the value specified by the Alarm Low configuration
parameter.

A1
A2
A3
A4
A5
A6
A7
A8
A9
A10
A11
A12
A13
A14
A15
A16
A17
A18

4
4

Wiring Connections for Carriers with Three Rows of Terminals

High Limit: The module reports a High Alarm fault if an input value is
greater than or equal to the value specified by the Alarm High
configuration parameter.

Number

AI1

If the module is installed on a Connector-style I/O Carrier, the cable


shield can be connected directly to an Interposing Terminal. A shielded
interposing cable (shielded cables are available separately) must be
used between the Connector-style I/O Carrier and the Interposing
Terminal. An Auxiliary I/O Terminal can be added to the Interposing
Terminal if additional shield connections are required.

Installation in Hazardous Locations

A 24 volt power supply must be connected to A17 and A18 to operate the
module. The power wiring does not require shielding. Current inputs are
applied with positive current flow into VININn+ and out of IINn-. Both
negative terminals IINn- and VINn- of the channel should be connected
together for best accuracy on current ranges. Voltage inputs are applied
between VININn+ and VINn- with positive to VININn+.

EQUIPMENT LABELED WITH REFERENCE TO CLASS I,


GROUPS A, B, C & D, DIV. 2 HAZARDOUS LOCATIONS IS
SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C,
D OR NON-HAZARDOUS LOCATIONS ONLY

WARNING - EXPLOSION HAZARD - SUBSTITUTION OF


COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I,
DIVISION 2;

WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS


LOCATIONS, TURN OFF POWER BEFORE REPLACING OR
WIRING MODULES; AND

WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT


EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR
THE AREA IS KNOWN TO BE NONHAZARDOUS.

Analog Input Module, 16-Bit, 8 Isolated Inputs


IC200ALG240
September 2010

GFK-1522F

Table of Configurable Features

Description of Configurable Features

The default parameters of this module can be used in many


applications. The module can be software-configured when it is
installed in a PLC system, or an I/O Station controlled by a Network
Interface Unit that supports software configuration, as listed on the
previous page.

Channel Active: Each channel can be configured as either active or


inactive. If a channel is inactive, it is not scanned and the module returns
a value of 0.

The module is configured at startup. After configuration, the module


begins providing signals from the voltage or current output devices
connected to it to the CPU or NIU.

Low Alarm Limit and High Alarm Limit: Each input channel can have
a low alarm limit and a high alarm limit. If an input reaches one of its
limits, the module reports the actual value and sends the appropriate
diagnostic input bit. Alarms do not stop the process or change the value
of the input.
Alarm limits can be set anywhere over the dynamic range of the signal.
The range for each is 32,768 to +32,767. The high alarm limit must be
greater than the low alarm limit. If alarm reporting is not wanted, alarm
limits can be set beyond the dynamic range of the signal so they will
never be activated.
Scaling: The module converts electrical signals (either current or
voltage, as configured) into digital output values for the CPU or NIU. By
default, the module converts this data from 1 millivolt or 1 microamp
internal units for convenience in scaling and comparing to actual meter
measurements.

Parameter

Description

Analog
Input Data
Reference
Analog
Input Data
Length
Line
Frequency

Starting offset for the modules


analog input data.
Word length of the modules
analog input data.
Specifies the line filter
frequency.

Report Faults Enables or disables Fault


Reporting for the entire Module.
%AI Default / Specifies whether the module will
Hold Last go to the specified channel
State
defaults (see below) or hold their
last states if power or
communications are lost.
Current / Specifies whether the channel will
Voltage be a voltage or current input.
If the Channel type is Current, the
range is 4 to 20mA.
If Channel type is Voltage, the
range is 10 to +10V.
Channel
Specifies if the channel should
Active
input data received from the
CPU or NIU. If a channel is
inactive space is still allocated
for it.
Span Low Actual current (in microAmps) or
voltage (in milliVolts) to be scaled
from low engineering units value.

The modules default scaling can be changed to tailor the data for a
specific application. Typically, engineering units represent millivolts or
microamps. But they may also represent physical units such as degrees
or centimeters per second. When reconfiguring scaling, it is important to
be sure that the chosen Engineering Units values would not result in
Over-range or Under-range output levels.
The scaling for each channel can be configured independently. Scaling is
configured by selecting corresponding low and high Engineering Units
values and low and high Span values for two points.
During operation, the module will use the straight line defined by these
two pairs of configured scaling values to convert internal values to current
or voltage signal levels that represent appropriate engineering units.
Fault Reporting: By default, the module is configured for fault reporting.
The module reports faults as soon as they are detected. Once a fault has
been reported, the same fault is not reported again until the fault has
been cleared. Fault reporting can be disabled via configuration. If
disabled, faults are not reported.

Choices
user selectable

08

60 Hz

50 Hz, 60 Hz

Enabled

Enabled,
Disabled

Default

Default /Hold

I (Current)

I (Current),
V (Voltage)

Active

Inactive (off),
Active (on)

4,000 A

0 to 25,000 A
10,000 to
+10,000mV
0 to 25,000 A
10,000 to
+10,000mV

Span High Actual current in microAmps or


voltage in millivolts to be scaled
from the high engineering units
value.
Engineering The engineering units value that is
Low
considered equivalent to the low
span (actual) value.

20,000 A

Engineering The engineering units value that is


High
considered equivalent to the high
span (actual) value.
Alarm Low The low alarm limit for the
channel, in engineering units.

20000

4000

-32768 to +32767

Alarm High The high alarm limit for the


channel, in engineering units.

20000

-32768 to +32767

-32768 to +32767

Default

Default

The value to be input when the


module is in a default condition.

4000

0 to 25,000 A
10,000 to
+10,000mV
0 to 25,000 A
10,000 to
+10,000mV