Professional Documents
Culture Documents
Feature
Figure 1 Voltage sag immunity testing has been common in the semiconductor industry for
years, where it has proved its economic value. New IEC standards for voltage dip immunity
will expand this kind of testing and certification to any other industry.
www.netaworld.org
Note that IEC 61000-4-11 and 61000-4-34 specifically forbid creating phase-to-phase sags by sagging two
phase-to-neutral voltages simultaneously, an approach that
is permitted in SEMI F47. Instead, you must create phase
shifts during your phase-to-phase sags something that sag
generators designed for these standards do automatically.
Typical suppliers of compliant sag generators include Keytek
(www.keytek.com), Power Standards Lab (www.PowerStandards.com), and Schaffner (www.schaffner.com) .
Three-Phase Testing
For three-phase EUTs, the sags are applied between
each pair of power conductors, one pair at a time. If there is
a neutral conductor, this implies that there are six different
sags at each depth-duration pair; three different phase-tophase sags, and three different phase-to-neutral sags. If there
is no neutral conductor, there are just three different sags at
each depth-duration pair in the standard; just three different
phase-to-phase sags. In all of the standards, all three phases
are never sagged at the same time.
www.netaworld.org
Figure 5 The voltage sag test engineer will insert a sag generator
between the AC source and the Equipment Under Test. Often, high
currents (200 amps) and high voltages (480 volts 3-phase) must be
handled.
sensor with a failing power supply giving an incorrect reading, causing EUT software to react inappropriately.
The second most common failure mechanism, surprisingly, occurs just after the sag has finished. All of the bulk
capacitors inside the EUT decide to recharge at once, causing a large increase in ac mains current. This increase can
trip circuit breakers, open fuses, and even destroy solid-state
rectifiers. Most design engineers correctly protect against
this inrush current during power cycling, but many do not
Spring 2008 NETA WORLD
Figure 6 Top graph shows a typical voltage sag. The next graph shows the current waveform, which was about 40 amperes peak before the sag,
but increases to 450 amperes peak after. The next graph shows the same current, this time as an rms value. Before the sag, it is about 23 amperes
rms (this equipment was rated at 30 amperes), but after the sag the current increases to 175 amperes rms typical behavior of an EUT. The final
graph shows the output of a dc supply during this sag.
www.netaworld.org
www.netaworld.org