Instruction Leaflet IL0503TX0001

Effective May 2010

Ground fault protector/earth


leakage protector for J circuit
breakers and motor circuit protectors
El protector de fallas a tierra protector de fugas
a tierra para interruptores de circuito y protectores
de circuito de motores
Warning
DO NOT ATTEMPT TO INSTALL OR PERFORM
MAINTENANCE ON EQUIPMENT WHILE IT IS
ENERGIZED. DEATH OR SEVERE PERSONAL INJURY
CAN RESULT FROM CONTACT WITH ENERGIZED
EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS
PRESENT BEFORE PROCEEDING.

Advertencia
NO INTENTE INSTALAR O LLEVAR A CABO TRABAJOS
DE MANTENIMIENTO EN EL EQUIPO MIENTRAS TENGA
ENERGA. EL CONTACTO CON EQUIPO CON ENERGA
PUEDE PROVOCAR LA MUERTE O LESIONES
PERSONALES SEVERAS. ANTES DE PROCEDER,
VERIFIQUE SIEMPRE QUE NO HAYA VOLTAJE PRESENTE.

Attach Endcap.

Insert Unit into Breaker.

Coloque el cubrefalta.

Coloque la unidad en el ruptor.


Breaker Must Be in OFF
Position for Assembly.
Antes de conectar el interruptor
debe estar en la posicion
de apagado (OFF).

Figure 1.

Figure 3.

Insert Screws in Retainers.

Push Down.

Coloque los tornillos en los retenedores.

Presione hacia abajo.

Figure 2.

Figure 4.

Ground fault protector/earth


leakage protector for J circuit breakers
and motor circuit protectors

Instruction Leaflet IL0503TX0001


Effective May 2010

Test by Pushing Push-To-Trip Button.

Tighten Breaker Screws and Attach Cover.


Apriete los tornillos del interruptor y coloque la tapa.

Pruebe la unidad presionado el botn de disparo.

120144 in-lb
1416 N m)

0.25
(6.00)

Figure 5.

Figure 7.

Reset Unit and Latch Breaker.

Reset Unit and Latch Breaker.

Reinicie la unidad y cierre el interruptor.

Reinicie la unidad y cierre el interruptor.

2
1

Figure 6.

Figure 8.

Attach Accessories.
Coloque los accesorios.

To Accessory

From Accessory
Proviene de
los accesorios

Four-Pole
Cuatro-polos

Figure 9.

eaton corporation www.eaton.com

Hacia los
accesorios

Three-Pole
Tres-polos

Ground fault protector/earth


leakage protector for J circuit breakers
and motor circuit protectors

Instruction Leaflet IL0503TX0001


Effective May 2010

Test Button
Botn de prueba

Push-To-Trip Button
Botn de disparo
50%IG (or 50%In)
(Indicates 50% of Leakage
Value Has Been Reached)
50%IG (o 50%In)
(Indica que 50% del valor
defuga fue alcanzado)

Reset Button
Botn de
reinicio

Status Light (Flashes to


Indicate Proper Operation)
Luz para indicacin del estado
(Parpadea para indicar
operacin apropiada)

t(s)(ort) Adjustment
IG (or In) Adjustment

Ajuste de t(seg.)(ot)

Ajuste del IG (o In)

Figure 10.
Table 1a. J-Frame Line and Load Terminations
Wire Size

Torque

Frame Type

Wire Type

AWG

mm2

Terminal Materials

Poles

Catalog Number

Lb In

Nm

J-Frame

Cu

4-350

25-185

Stainless steel

3-4

T250FJ

180

20

J-Frame

Cu/Al

4-350

25-185

Aluminum

3-4

TA250FJ

250

28

J-Frame

Cu/Al

4-350

25-185

Copper

3-4

TC250FJ

250

28

Table 1b. Terminaciones de lnea y carga del marco J


Tamao de alambre

Torsio`n

Tipo de marco

Tipo de alambre

AWG

mm2

Material
de la terminal

Polos

Nu`mero de catalogo
`
Lb-Pulg.

Nm

Marco J

Cu

4-350

25-185

Acero inoxidable

3-4

T250FJ

180

20

Marco J

Cu/Al

4-350

25-185

Aluminio

3-4

TA250FJ

250

28

Marco J

Cu/Al

4-350

25-185

Cobre

3-4

TC250FJ

250

28

eaton corporation www.eaton.com

Ground fault protector/earth


leakage protector for J circuit breakers
and motor circuit protectors

Instruction Leaflet IL0503TX0001


Effective May 2010

5.50 [4-Pole]
(139.7)
4.13 [3-Pole]
(104.9)
1.38
(35.1)

5.50 (139.7)

0.69 (17.5)

3.57
(90.7)

2.06 (52.3)

2.05
0.63 (52.07)
(16.0)

1.25
(31.7)

1.88
(47.8)

R 0.19

3.92
(99.6)

3.92
(99.6)

5.50
(139.7)
7.00
(177.8)

4.93
(125.2)

0.28 (7.1)
0.50 (12.7)

11.25
(285.7)

1.06 (26.9)
6.97
(177.0)

3.37
(85.6)

4.25
(107.9)

RESET
TEST

11.25
(285.7)

3.57 (90.7)

3.31
(83.8)

3.69 (93.7)
3.81 (96.8)
4.78 (121.4)

2.05
(52.07)
4.09
(103.9)

0.03 (0.762)

Figure 11.

NOTICE
Phase

Before Performing Any High Voltage


Insulation Test, Refer to The Following:

Fase

Antes de realizar cualquier prueba de


aislamiento usando alta tension, favor
hacer referencia lo siguiente:

Trip the Unit Using Push-to- Trip


Button Prior to Any High Voltage Test.
Dispare la unidad usando el botn
de disparo antes de ejecutar cualquier
prueba de alta tensin.

Do Not Apply Voltage Higher than the Rated


Voltage of the Unit On Phase C.
Phase
Fase

Nunca aplique un voltaje ms alto por el


cual est capacitada la unidad en la fase C.

Figure 12.
Eaton Corporation
Electrical Sector
1111 Superior Ave.
Cleveland, OH 44114
United States
877-ETN-CARE (877-386-2273)
Eaton.com
2010 Eaton Corporation
All Rights Reserved
Printed in USA
Publication No. IL0503TX0001 / Z9927
May 2010

PowerChain Management is a registered


trademark of Eaton Corporation.
All other trademarks are property of their
respective owners.