Chvac - Full Commercial HVAC Loads Calculation Program

Design Consortium (Pvt) Ltd


Colombo 08, Sri Lanka, CO 00800

Elite Software Development, Inc.


DCSL
Page 1

Building Summary Loads


Building peaks in June at 4pm.

Bldg Load
Descriptions
Roof
Wall
Glass
Floor Slab

Area
Quan

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

0
63
45
0

0
0
0
0

0,00
0,00
0,00
0,00

0
0
0
0

0
914
16 364
0

0
914
16 364
0

0,00
2,27
40,62
0,00

0,00

17 278

17 278

42,88

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

0,00
0,00
0,00
0,00
0,00
0,00
0,00
0,00
0,00
0,00
0,00
0,00
0,00
0,00
0,00
0,00
0,00
0,00
0,00

0
0
0
1 323
0
0
0
6 456
0
297
0
0
0
0
0
0
0
0
0

2 835
7 350
0
2 058
390
0
0
1 907
0
84
0
312
0
0
0
0
0
0
0

2 835
7 350
0
3 381
390
0
0
8 363
0
381
0
312
0
0
0
0
0
0
0

7,04
18,24
0,00
8,39
0,97
0,00
0,00
20,76
0,00
0,95
0,00
0,78
0,00
0,00
0,00
0,00
0,00
0,00
0,00

0,00

8 076

32 215

40 291

100,00

Skin Loads
Lighting
Equipment
Pool Latent
People
Partition
Cool. Pret.
Heat. Pret.
Cool. Vent.
Heat. Vent.
Cool. Infil.
Heat. Infil.
Draw-Thru Fan
Blow-Thru Fan
Reserve Cap.
Reheat Cap.
Supply Duct
Return Duct
Misc. Supply
Misc. Return

2 700
7 000
0
28
28
0
0
194
0
8
0
0
0
0
0
0
0
0
0

Building Totals

Building
Summary

Sen
Loss

%Tot
Loss

Lat
Gain

Sen
Gain

Net
Gain

%Net
Gain

Ventilation
Infiltration
Pretreated Air
Room Loads
Plenum Loads
Fan/Duct/Misc Loads

0
0
0
0
0
0

0,00
0,00
0,00
0,00
0,00
0,00

6 456
297
0
1 323
0
0

1 907
84
0
29 912
0
312

8 363
381
0
31 235
0
312

20,76
0,95
0,00
77,52
0,00
0,78

Building Totals

0,00

8 076

32 215

40 291

100,00

Check Figures
Total Building Supply Air (based on a 11 TD):
Total Building Vent. Air (8,65% of Supply):
Total Conditioned Air Space:
Supply Air Per Unit Area:
Area Per Cooling Capacity:
Cooling Capacity Per Area:
Heating Capacity Per Area:
Total Heating Required With Outside Air:
Total Cooling With Outside Air:

2 242 L/s
194 L/s
180
12,4549
4,4675
0,2238
0,00

Sq.m
L/s/Sq.m
Sq.m/kW
kW/Sq.m
Watts/Sq.m

0,00 kW
40,29 kW

15,7 Sq.m/Ton
0,0636 Tons/Sq.m

11,46 Tons

Chvac - Full Commercial HVAC Loads Calculation Program


Design Consortium (Pvt) Ltd
Colombo 08, Sri Lanka, CO 00800

Elite Software Development, Inc.


DCSL
Page 2

Air System #1 () Psychrometric Analysis


System Load Analysis

Latent

Leaving Coil Condition


Draw-Thru Fan
Misc Load on Supply Side
Supply Air Duct
Room Loads
Sensible Reserve

Grams

Sensible

Temp

L/s

312
0
0
29 996
0

13,000
0,113
0,000
0,000
10,887
0,000

23
0
0
2 219
0

30 308
0
0
0
1 907
0

24,000
0,000
0,000
0,000
0,692
0,000

2 242

32 215

24,692

2 242

9,084
0

0,000

1 620

0,244

Room Condition
Return Air Duct
Return Air Plenum
Misc Load on Return Side
Vent Air 194 L/s
Blow-Thru Fan

1 620

9,329

0
6 456

0,000
0,974

Entering Coil Condition

8 076

10,303

General Psychrometric Equations Used In Analysis:


PR
TSH
TLH
GTH

=
=
=
=

TSH
TLH

=
=

(Barometric pressure of site / Standard ASHRAE pressure of 1010,387)


PR x
1,23 x L/s x (DB entering - DB leaving)
PR x
2,96 x L/s x (g/kg entering - g/kg leaving)
PR x
1,20 x L/s x (Enthalpy entering - Enthalpy leaving)
0,999
0,999

x
x

1,23
2,96

x
x

2 242
2 242

x(
x(

24,7
10,3

13,0
9,1

)=
)=

SUM
=
GTH
=
0,999
Total System Load

1,20

2 242

x(

51,1

36,1

)=
=

32 215
8 077
---------40 292
40 453
40 291

Watts
Watts
Watts
Watts
Watts

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling L/s
Heating L/s
Steam Req.

=
=
=

40 453 / (
0 /(
0 /

6,00
0,00
970

x
x

4 179
4 179

Entering Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

=
=
=

1,6 L/s
0,0 L/s
0,00 kg./hr

Entering Heating Coil Conditions


24,69
18,11
53,08
51,14 kJ/kg

Leaving Cooling Coil Conditions


Dry bulb temperature:
Wet bulb temperature:
Relative humidity:
Enthalpy:

)
)

Dry bulb temperature:

24,00

Leaving Heating Coil Conditions


13,00
12,75
97,33
36,09 kJ/kg

Dry bulb temperature:

24,00

Chvac - Full Commercial HVAC Loads Calculation Program


Design Consortium (Pvt) Ltd
Colombo 08, Sri Lanka, CO 00800

Elite Software Development, Inc.


DCSL
Page 3

Air System #1 () Psychrometric Chart


RC
LC
SD
DTF
RE
SM
PRE
MIX

Room Condition
Leaving Coil Condition
Supply Duct Temperature Rise
Draw Through Fan Sensible Gain
Reserve or Reheat Sensible Gain
Supply Side Miscellaneous Sensible Gain
Pretreated Air Condition
Mixed Air Condition

OC
EC
RD
BTF
PL
MR
HRV
RML

Outdoor Condition
Entering Coil Condition
Return Duct Temperature Rise
Blow Through Fan Sensible Gain
Return Air Plenum Sensible Gain
Return Side Miscellaneous Gain
Heat Recovery Ventilator Condition
Return Miscellaneous Latent Gain