OCI/PBMVC/REV.001/010410
2
OCI/PBMVC/REV.001/010410
PRODUCT RANGE
VOLTAGE GRADE
:
CONDUCTOR
COPPER OR ALUMINIUM
CONDUCTOR SIZE
25 TO 1000 SQ MM
:
SPECIFICATION
Uo
Um
SPECIAL FEATURES
OCI CAN ALSO OFFER CABLES WITH DIFFERENT SHEATHING, SCREENING, TAPING &
ARMOURING OPTIONS AS PER CUSTOMERS SPECIFIC REQUIREMENTS. WE CAN ALSO OFFER
CABLES SUITABLE FOR SUPERIOR FIRE PERFORMANCE CHARACTERISTICS AS WELL AS WITH
LOW SMOKE & FUME (LSF or LSOH/LSZH) PROPERTIES. SPECIAL FEATURES LIKE LONGITUDINAL
WATER SEALING OF CONDUCTORS & CU SCREENS, RADIAL WATER SEALING OF CU SCREENS
AS WELL AS DIFFERENT COLOUR OF OUTER SHEATH CAN BE PROVIDED ON REQUEST.
THE CABLE DESIGN IN THIS CATALOGUE CONFORMS TO IEC 60502 PART 2 & IN MOST CASES
TO BS 6622. HOWEVER IF REQUESTED, WE CAN SEPARATELY OFFER GUARANTEED TECHNICAL
PARTICULARS FOR CABLES AS PER DIFFERENT INTERNATIONAL SPECIFICATIONS OR SPECIFIC
CUSTOMER NEEDS.
3
OCI/PBMVC/REV.001/010410
CONSTRUCTIONAL FEATURES
Conductor
We can offer cables with both copper or aluminium
conductors. Conductors upto 1000 sq mm will be circular
compacted & stranded and shall comply with IEC-60228
Class 2.
Conductor screen
This will be an extruded layer of semiconducting XLPE
applied under simultaneous triple extrusion process over
the conductor along with the insulation and the insulation
screen.
Insulation
This will be an extruded layer of insulating grade XLPE
applied over conductor screen under triple extrusion
process along with conductor screen and insulation
screen.
Insulation screen
This will be a layer of semiconducting XLPE which will be
applied by tripe extrusion process over the insulation.
Metallic screen
It will consist of a layer of copper tape applied helically
with overlap over insulation screen. Other combinations
of metallic screens as per customers requirement can also
be provided on request.
Laying-up
In case of three core cables, the three cores are laid up
with non hygroscopic fillers like polypropylene (PP) fillers
at interstices and a binder tape is applied with an
overlap. These binder tapes can be a PVC or Polyethylene,
or Polypropylene or Polyester.
4
OCI/PBMVC/REV.001/010410
Control Panel
a)
b)
c)
d)
6
OCI/PBMVC/REV.001/010410
LIST OF TABLES
CONDUCTOR TYPE
TABLE
PAGE NO.
COPPER
1 To 5
8 To 12
ALUMINIUM
6 To 10
13 To 17
COPPER
1 To 5
18 To 22
ARMOURED CABLES
ALUMINIUM
6 To 10
23 To 27
COPPER
1 To 5
28 To 32
ALUMINIUM
6 To 10
33 To 37
COPPER
ALUMINIUM
1 To 5
6 To 10
38 To 42
43 To 47
COPPER
ALUMINIUM
1 To 5
6 To 10
48 To 52
53 To 57
1 TO 17 60 To 68
7
OCI/PBMVC/REV.001/010410
3.6/6 (7.2) kV
Single Core Copper Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 3.8/6.6 kV Earthed
System)
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo = 3.6 kV and f= 50 Hz
Sustained current ratings (With both end bonding):Laid direct, ground temp. = 20 C &
Thermal resistivity of soil = 1.5 C m/W, depth
of laying = 0.8 m, laid in trefoil formation.
8.1
OCI/PBMVC/REV.001/010410
mm2
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
kg/km
mm
mm
mm
mm
kg/km
m
mm
5.9
218
2.5
1.8
1.43
17.5
510
1000
350
6.9
303
2.5
1.8
1.43
18.5
620
1000
370
8.1
408
2.5
1.8
1.43
20.0
750
1000
400
9.7
591
2.5
1.8
1.43
21.5
975
1000
430
11.4
821
2.5
1.8
1.43
23.0
1245
1000
460
12.9
1035
2.5
1.8
1.43
24.5
1490
1000
490
14.3
1277
2.5
1.8
1.43
26.0
1765
1000
520
16.0
1601
2.5
1.8
1.43
27.5
2130
1000
550
18.4
2105
2.6
1.9
1.52
30.5
2715
1000
610
20.6
2640
2.8
2.0
1.60
33.5
3340
1000
670
23.3
3383
3.0
2.1
1.69
37.0
4235
1000
740
26.3
4272
3.2
2.2
1.77
41.0
5250
500
820
30.0
5618
3.2
2.3
1.86
44.5
6650
500
890
34.2
7286
3.2
2.4
1.94
50.0
8395
500
1000
38.2
9046
3.2
2.6
2.11
54.5
10365
500
1090
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.727
0.927
0.132
0.936
1.621
0.26
0.29
0.524
0.668
0.126
0.680
1.178
0.29
0.33
0.387
0.494
0.121
0.509
0.882
0.32
0.36
0.268
0.342
0.111
0.360
0.624
0.37
0.42
0.193
0.247
0.105
0.268
0.464
0.42
0.48
0.153
0.196
0.101
0.220
0.381
0.46
0.52
0.124
0.159
0.099
0.187
0.324
0.50
0.57
0.0991
0.128
0.094
0.159
0.275
0.54
0.61
0.0754
0.098
0.092
0.134
0.232
0.59
0.67
0.0601
0.079
0.091
0.121
0.210
0.61
0.69
0.0470
0.063
0.089
0.109
0.189
0.64
0.72
0.0366
0.051
0.088
0.102
0.177
0.67
0.76
0.0283
0.042
0.084
0.094
0.163
0.75
0.85
0.0221
0.035
0.084
0.091
0.158
0.86
0.97
0.0176
0.030
0.082
0.087
0.151
0.94
1.06
140
166
196
239
285
323
361
406
469
526
590
655
731
806
873
132
157
186
227
271
308
343
387
447
504
564
635
712
789
859
8.2
8.3
163
198
238
296
361
417
473
543
641
735
845
956
1095
1241
1373
9.0
kA
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
114.40
143.00
SECTION A - TABLE 1
6/10 (12) kV
Single Core Copper Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 6.35/11kV Earthed
System)
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
2.0
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
26.3
30.0
34.2
38.2
kg/km
218
303
408
591
821
1035
1277
1601
2105
2640
3383
4272
5618
7286
9046
3.0
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
4.0
mm
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.6
5.0
mm
1.43
1.43
1.43
1.43
1.43
1.43
1.43
1.52
1.60
1.60
1.69
1.77
1.86
2.03
2.11
6.0
mm
19.5
20.5
22.0
23.5
25.0
26.5
28.0
30.0
32.5
34.5
38.0
41.0
45.0
50.5
54.5
7.0
kg/km
575
685
825
1050
1325
1580
1855
2240
2825
3420
4280
5275
6680
8445
10400
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
500
500
500
500
mm
390
410
440
470
500
530
560
600
650
690
760
820
900
1010
1090
0.0176
8.0
9.0
(B)
Electrical Parameters
1.0
ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
2.0
ohm/km
0.927
0.668
0.494
0.342
0.247
0.196
0.159
0.128
0.098
0.079
0.063
0.051
0.042
0.035
0.030
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.139
0.132
0.127
0.117
0.110
0.106
0.103
0.100
0.096
0.093
0.090
0.088
0.085
0.084
0.082
OCI/PBMVC/REV.001/010410
4.0
Impedance at 50 Hz (Approximate)
5.0
ohm/km
0.937
0.681
0.510
0.361
0.270
0.223
0.189
0.162
0.137
0.122
0.110
0.102
0.095
0.091
0.087
v/amp/km
1.623
1.180
0.883
0.625
0.468
0.386
0.327
0.281
0.237
0.211
0.191
0.177
0.165
0.158
0.151
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.21
0.23
0.25
0.29
0.32
0.35
0.38
0.42
0.47
0.51
0.57
0.63
0.71
0.81
0.89
7.0
mA/m
0.40
0.43
0.47
0.55
0.60
0.66
0.72
0.79
0.89
0.96
1.07
1.19
1.34
1.53
1.68
8.0
8.1
140
166
196
239
285
323
361
406
469
526
590
655
731
806
873
8.2
132
157
186
227
271
308
343
387
447
504
564
635
712
789
859
8.3
9.0
A
kA
163
3.58
198
5.01
238
7.15
296
10.01
361
13.59
417
17.16
473
21.45
543
26.46
641
34.32
735
42.90
845
57.20
956
71.50
1095
90.09
1241
114.40
1373
143.00
SECTION A - TABLE 2
10
8.7/15 (17.5) kV
Single Core Copper Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 8.7/15 kV Earthed
System)
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
2.0
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
26.3
30.0
34.2
38.2
kg/km
218
303
408
591
821
1035
1277
1601
2105
2640
3383
4272
5618
7286
9046
3.0
mm
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.0
mm
1.8
1.8
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
2.7
5.0
mm
1.43
1.43
1.43
1.43
1.43
1.52
1.52
1.60
1.60
1.69
1.77
1.86
1.94
2.03
2.20
6.0
mm
22.0
23.0
24.0
25.5
27.5
29.0
30.5
32.5
34.5
37.0
40.5
43.5
47.5
52.5
57.0
7.0
kg/km
655
770
910
1140
1420
1695
1975
2365
2945
3565
4440
5445
6865
8625
10620
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
500
500
500
500
500
mm
440
460
480
510
550
580
610
650
690
740
810
870
950
1050
1140
0.0176
8.0
9.0
(B)
Electrical Parameters
1.0
ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
2.0
ohm/km
0.927
0.668
0.494
0.342
0.247
0.196
0.159
0.128
0.098
0.079
0.063
0.051
0.041
0.035
0.030
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.146
0.139
0.132
0.122
0.116
0.112
0.109
0.105
0.100
0.097
0.094
0.091
0.089
0.087
0.085
OCI/PBMVC/REV.001/010410
4.0
Impedance at 50 Hz (Approximate)
5.0
ohm/km
0.938
0.682
0.511
0.363
0.273
0.226
0.193
0.166
0.140
0.125
0.113
0.104
0.098
0.094
0.090
v/amp/km
1.625
1.181
0.885
0.629
0.473
0.391
0.334
0.288
0.242
0.217
0.196
0.180
0.170
0.163
0.156
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.17
0.19
0.21
0.23
0.26
0.28
0.30
0.33
0.37
0.40
0.45
0.49
0.55
0.63
0.69
7.0
mA/m
0.46
0.52
0.57
0.63
0.71
0.77
0.82
0.90
1.01
1.09
1.23
1.34
1.50
1.72
1.89
8.0
8.1
140
166
196
239
285
323
361
406
469
526
590
655
731
806
873
8.2
132
157
186
227
271
308
343
387
447
504
564
635
712
789
859
8.3
163
198
238
296
361
417
473
543
641
735
845
956
1095
1241
1373
9.0
kA
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
114.40
143.00
SECTION A - TABLE 3
12/20 (24) kV
Single Core Copper Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 12.7/22 kV Earthed
System)
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
7.0
8.0
8.1
11
OCI/PBMVC/REV.001/010410
8.2
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
kg/km
mm
mm
mm
mm
kg/km
m
mm
6.9
303
5.5
1.8
1.43
25.0
860
1000
500
8.1
408
5.5
1.8
1.43
26.0
1005
1000
520
9.7
591
5.5
1.8
1.43
28.0
1240
1000
560
11.4
821
5.5
1.9
1.52
29.5
1540
1000
590
12.9
1035
5.5
1.9
1.52
31.0
1800
1000
620
14.3
1277
5.5
2.0
1.60
32.5
2105
1000
650
16.0
1601
5.5
2.0
1.60
34.5
2485
1000
690
18.4
2105
5.5
2.1
1.69
37.0
3090
1000
740
20.6
2640
5.5
2.2
1.77
39.5
3715
500
790
23.3
3383
5.5
2.3
1.86
43.0
4605
500
860
26.3
4272
5.5
2.4
1.94
46.0
5625
500
920
30.0
5618
5.5
2.5
2.03
50.0
7055
500
1000
34.2
7286
5.5
2.6
2.11
55.0
8840
500
1100
38.2
9046
5.5
2.7
2.20
59.5
10820
500
1190
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
0.524
0.668
0.145
0.684
1.185
0.16
0.387
0.494
0.137
0.513
0.889
0.18
0.268
0.342
0.128
0.365
0.632
0.20
0.193
0.247
0.121
0.275
0.476
0.22
0.153
0.196
0.116
0.228
0.395
0.24
0.124
0.159
0.113
0.195
0.338
0.26
0.0991
0.128
0.109
0.168
0.291
0.28
0.0754
0.098
0.104
0.143
0.248
0.31
0.0601
0.079
0.101
0.128
0.222
0.34
0.0470
0.063
0.098
0.117
0.203
0.38
0.0366
0.051
0.095
0.108
0.187
0.42
0.0283
0.041
0.092
0.101
0.175
0.46
0.0221
0.034
0.090
0.096
0.166
0.53
0.0176
0.030
0.088
0.093
0.161
0.58
mA/m
0.60
0.68
0.75
0.83
0.90
0.98
1.06
1.17
1.28
1.43
1.58
1.73
2.00
2.19
166
196
239
285
323
361
406
469
526
590
655
731
806
873
157
186
227
271
308
343
387
447
504
564
635
712
789
859
8.3
198
238
296
361
417
473
543
641
735
845
956
1095
1241
1373
9.0
kA
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
114.40
143.00
SECTION A - TABLE 4
12
18/30 (36) kV
Single Core Copper Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 19/33 kV Earthed
System)
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
2.0
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
26.3
30.0
34.2
38.2
kg/km
408
591
821
1035
1277
1601
2105
2640
3383
4272
5618
7286
9046
3.0
mm
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
4.0
mm
1.9
2.0
2.1
2.1
2.1
2.2
2.3
2.3
2.5
2.5
2.7
2.8
2.9
5.0
mm
1.52
1.60
1.69
1.69
1.69
1.77
1.86
1.86
2.03
2.03
2.20
2.28
2.37
6.0
mm
31.5
33.5
35.5
37.0
38.0
40.0
42.5
45.0
48.5
51.5
55.5
60.5
65.0
11385
7.0
8.0
9.0
(B)
Electrical Parameters
kg/km
1265
1530
1845
2120
2420
2835
3460
4090
5025
6050
7540
9365
1000
1000
1000
1000
1000
500
500
500
500
500
500
500
500
mm
630
670
710
740
760
800
850
900
970
1030
1110
1210
1300
0.0176
1.0
ohm/km
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
2.0
ohm/km
0.494
0.342
0.247
0.196
0.159
0.127
0.098
0.079
0.063
0.050
0.041
0.034
0.029
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.149
0.139
0.132
0.127
0.123
0.118
0.113
0.109
0.106
0.102
0.098
0.096
0.093
4.0
Impedance at 50 Hz (Approximate)
5.0
ohm/km
0.516
0.369
0.280
0.234
0.201
0.173
0.150
0.135
0.123
0.114
0.106
0.102
0.097
v/amp/km
0.894
0.639
0.485
0.405
0.348
0.300
0.260
0.234
0.213
0.197
0.184
0.177
0.168
OCI/PBMVC/REV.001/010410
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.14
0.15
0.17
0.18
0.20
0.21
0.23
0.25
0.28
0.30
0.34
0.38
0.42
7.0
mA/m
0.79
0.85
0.96
1.02
1.13
1.19
1.30
1.41
1.58
1.70
1.92
2.15
2.38
8.0
8.1
196
239
285
323
361
406
469
526
590
655
731
806
873
8.2
186
227
271
308
343
387
447
504
564
635
712
789
859
8.3
238
296
361
417
473
543
641
735
845
956
1095
1241
1373
9.0
kA
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
114.40
143.00
SECTION A - TABLE 5
3.6/6 (7.2) kV
Single Core Aluminium Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 3.8/6.6 kV Earthed
System)
Outer Sheath
ALUMINIUM CONDUCTOR
13
OCI/PBMVC/REV.001/010410
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
5.9
67
2.5
1.8
1.43
17.5
360
1000
350
6.9
92
2.5
1.8
1.43
18.5
410
1000
370
8.1
125
2.5
1.8
1.43
20.0
470
1000
400
9.7
182
2.5
1.8
1.43
21.5
565
1000
430
11.4
251
2.5
1.8
1.43
23.0
675
1000
460
12.9
317
2.5
1.8
1.43
24.5
775
1000
490
14.3
390
2.5
1.8
1.43
26.0
880
1000
520
16.0
493
2.5
1.8
1.43
27.5
1020
1000
550
18.4
646
2.6
1.9
1.52
30.5
1255
1000
610
20.6
803
2.8
2.0
1.60
33.5
1505
1000
670
23.3
1027
3.0
2.1
1.69
37.0
1875
1000
740
26.3
1307
3.2
2.2
1.77
41.0
2285
500
820
30.0
1721
3.2
2.3
1.86
44.5
2825
500
890
34.2
2188
3.2
2.4
1.94
50.0
3480
500
1000
38.2
2759
3.2
2.6
2.11
54.5
4225
500
1090
1.20
1.539
0.132
1.545
2.676
0.26
0.29
0.868
1.113
0.126
1.120
1.940
0.29
0.33
0.641
0.822
0.121
0.831
1.439
0.32
0.36
0.443
0.568
0.111
0.579
1.003
0.37
0.42
0.320
0.411
0.105
0.424
0.734
0.42
0.48
0.253
0.325
0.101
0.340
0.589
0.46
0.52
0.206
0.265
0.099
0.283
0.490
0.50
0.57
0.164
0.211
0.094
0.231
0.400
0.54
0.61
0.125
0.162
0.092
0.186
0.322
0.59
0.67
0.100
0.130
0.091
0.159
0.275
0.61
0.69
0.0778
0.102
0.089
0.135
0.234
0.64
0.72
0.0605
0.080
0.088
0.119
0.206
0.67
0.76
0.0469
0.064
0.084
0.106
0.184
0.75
0.85
0.0367
0.052
0.084
0.099
0.171
0.86
0.97
0.0291
0.043
0.082
0.093
0.161
0.94
1.06
108
129
152
186
221
252
281
317
367
414
470
528
599
672
743
102
122
144
176
210
240
267
303
351
397
451
512
583
658
731
A
kA
127
2.35
154
3.29
184
4.70
230
6.58
280
8.93
324
11.28
368
14.10
424
17.39
502
22.56
577
28.20
673
37.60
770
47.00
896
59.22
1033
75.20
1167
94.00
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
mm
Conductor weight (Approximate)
kg/km
Insulation thickness (Nominal)
mm
Outer sheath thickness (Nominal)
mm
Outer sheath thickness (Minimum)
mm
Cable overall diameter (Approximate)
mm
Cable weight (Approximate)
kg/km
Standard drum length (5% Tolerance)
m
Minimum bending radius of cable (During installation)
mm
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
ohm/km
AC resistance of conductor at 90 C (Approximate)
ohm/km
Reactance at 50 Hz (Approximate)
ohm/km
Impedance at 50 Hz (Approximate)
ohm/km
Voltage drop (Approximate for 3 phase system)
v/amp/km
Capacitance at 50 Hz (Approximate)
mF/km
Approximate charging current per phase at Uo = 3.6 kV and f= 50 Hz
mA/m
Sustained current ratings (With both end bonding):-
8.1
8.2
8.3
9.0
SECTION A - TABLE 6
14
6/10 (12) kV
Single Core Aluminium Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 6.35/11 kV Earthed
System)
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo = 6 kV and f= 50 Hz
Sustained current ratings (With both end bonding):Laid direct, ground temp. = 20 C & Thermal resistivity
of soil = 1.5 C m/W, depth of laying = 0.8 m,
laid in trefoil formation.
Drawn into earthenware ducts, ground temp. = 20 C
and Thermal resistivity of soil = 1.5 C m/W, depth
of laying = 0.8 m, laid in trefoil formation.
Laid in trefoil formation in air, ambient temp. = 30 C
Short circuit current rating of conductor for 1 second
8.1
OCI/PBMVC/REV.001/010410
8.2
8.3
9.0
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
kg/km
mm
mm
mm
mm
kg/km
m
mm
5.9
67
3.4
1.8
1.43
19.5
425
1000
390
6.9
92
3.4
1.8
1.43
20.5
475
1000
410
8.1
125
3.4
1.8
1.43
22.0
540
1000
440
9.7
182
3.4
1.8
1.43
23.5
640
1000
470
11.4
251
3.4
1.8
1.43
25.0
755
1000
500
12.9
317
3.4
1.8
1.43
26.5
860
1000
530
14.3
390
3.4
1.8
1.43
28.0
970
1000
560
16.0
493
3.4
1.9
1.52
30.0
1130
1000
600
18.4
646
3.4
2.0
1.60
32.5
1365
1000
650
20.6
803
3.4
2.0
1.60
34.5
1580
1000
690
23.3
1027
3.4
2.1
1.69
38.0
1925
1000
760
26.3
1307
3.4
2.2
1.77
41.0
2310
500
820
30.0
1721
3.4
2.3
1.86
45.0
2855
500
900
34.2
2188
3.4
2.5
2.03
50.5
3535
500
1010
38.2
2759
3.4
2.6
2.11
54.5
4260
500
1090
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
1.20
1.539
0.139
1.545
2.676
0.21
0.40
0.868
1.113
0.132
1.121
1.942
0.23
0.43
0.641
0.822
0.127
0.832
1.441
0.25
0.47
0.443
0.568
0.117
0.580
1.005
0.29
0.55
0.320
0.411
0.110
0.425
0.736
0.32
0.60
0.253
0.325
0.106
0.342
0.592
0.35
0.66
0.206
0.265
0.103
0.284
0.492
0.38
0.72
0.164
0.211
0.100
0.233
0.404
0.42
0.79
0.125
0.162
0.096
0.188
0.326
0.47
0.89
0.100
0.130
0.093
0.160
0.277
0.51
0.96
0.0778
0.102
0.090
0.136
0.236
0.57
1.07
0.0605
0.080
0.088
0.119
0.206
0.63
1.19
0.0469
0.064
0.085
0.106
0.184
0.71
1.34
0.0367
0.052
0.084
0.099
0.171
0.81
1.53
0.0291
0.043
0.082
0.093
0.161
0.89
1.68
108
129
152
186
221
252
281
317
367
414
470
528
599
672
743
102
122
144
176
210
240
267
303
351
397
451
512
583
658
731
A
kA
127
2.35
154
3.29
184
4.70
230
6.58
280
8.93
324
11.28
368
14.10
424
17.39
502
22.56
577
28.20
673
37.60
770
47.00
896
59.22
1033
75.20
1167
94.00
SECTION A - TABLE 7
8.7/15 (17.5) kV
Single Core Aluminium Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 8.7/15 kV Earthed
System)
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo = 8.7 kV and f= 50 Hz
Sustained current ratings (With both end bonding):Laid direct, ground temp. = 20 C & Thermal
resistivity of soil = 1.5 C m/W, depth of laying
= 0.8 m, laid in trefoil formation.
Drawn into earthenware ducts, ground temp. = 20 C
and Thermal resistivity of soil = 1.5 C m/W, depth
of laying = 0.8 m, laid in trefoil formation.
Laid in trefoil formation in air, ambient temp. = 30 C
Short circuit current rating of conductor for 1 second
8.1
8.3
9.0
15
OCI/PBMVC/REV.001/010410
8.2
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
kg/km
mm
mm
mm
mm
kg/km
m
mm
5.9
67
4.5
1.8
1.43
22.0
505
1000
440
6.9
92
4.5
1.8
1.43
23.0
560
1000
460
8.1
125
4.5
1.8
1.43
24.0
625
1000
480
9.7
182
4.5
1.8
1.43
25.5
730
1000
510
11.4
251
4.5
1.8
1.43
27.5
850
1000
550
12.9
317
4.5
1.9
1.52
29.0
975
1000
580
14.3
390
4.5
1.9
1.52
30.5
1090
1000
610
16.0
493
4.5
2.0
1.60
32.5
1255
1000
650
18.4
646
4.5
2.0
1.60
34.5
1485
1000
690
20.6
803
4.5
2.1
1.69
37.0
1725
1000
740
23.3
1027
4.5
2.2
1.77
40.5
2085
500
810
26.3
1307
4.5
2.3
1.86
43.5
2480
500
870
30.0
1721
4.5
2.4
1.94
47.5
3035
500
950
34.2
2188
4.5
2.5
2.03
52.5
3715
500
1050
38.2
2759
4.5
2.7
2.20
57.0
4480
500
1140
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
1.20
1.539
0.146
1.546
2.678
0.17
0.46
0.868
1.113
0.139
1.122
1.943
0.19
0.52
0.641
0.822
0.132
0.833
1.443
0.21
0.57
0.443
0.568
0.122
0.581
1.006
0.23
0.63
0.320
0.411
0.116
0.427
0.740
0.26
0.71
0.253
0.325
0.112
0.344
0.596
0.28
0.77
0.206
0.265
0.109
0.287
0.497
0.30
0.82
0.164
0.211
0.105
0.236
0.409
0.33
0.90
0.125
0.161
0.100
0.190
0.329
0.37
1.01
0.100
0.130
0.097
0.162
0.281
0.40
1.09
0.0778
0.102
0.094
0.139
0.241
0.45
1.23
0.0605
0.080
0.091
0.121
0.210
0.49
1.34
0.0469
0.064
0.089
0.110
0.191
0.55
1.50
0.0367
0.052
0.087
0.101
0.175
0.63
1.72
0.0291
0.043
0.085
0.095
0.165
0.69
1.89
108
129
152
186
221
252
281
317
367
414
470
528
599
672
743
102
122
144
176
210
240
267
303
351
397
451
512
583
658
731
A
kA
127
2.35
154
3.29
184
4.70
230
6.58
280
8.93
324
11.28
368
14.10
424
17.39
502
22.56
577
28.20
673
37.60
770
47.00
896
59.22
1033
75.20
1167
94.00
SECTION A - TABLE 8
16
12/20 (24) kV
Single Core Aluminium Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 12.7/22 kV Earthed
System)
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
2.0
35
mm
6.9
kg/km
92
50
70
95
120
150
185
240
300
400
500
630
800
1000
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
26.3
30.0
34.2
38.2
125
182
251
317
390
493
646
803
1027
1307
1721
2188
2759
3.0
mm
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
4.0
mm
1.8
1.8
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
2.6
2.7
5.0
mm
1.43
1.43
1.43
1.52
1.52
1.60
1.60
1.69
1.77
1.86
1.94
2.03
2.11
2.20
6.0
mm
25.0
26.0
28.0
29.5
31.0
32.5
34.5
37.0
39.5
43.0
46.0
50.0
55.0
59.5
4680
7.0
8.0
9.0
(B)
Electrical Parameters
kg/km
650
720
830
970
1085
1215
1375
1630
1880
2250
2660
3230
3925
1000
1000
1000
1000
1000
1000
1000
1000
500
500
500
500
500
500
mm
500
520
560
590
620
650
690
740
790
860
920
1000
1100
1190
0.0291
1.0
ohm/km
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
2.0
ohm/km
1.113
0.822
0.568
0.411
0.325
0.265
0.211
0.161
0.130
0.102
0.080
0.063
0.051
0.043
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.145
0.137
0.128
0.121
0.116
0.113
0.109
0.104
0.101
0.098
0.095
0.092
0.090
0.088
4.0
Impedance at 50 Hz (Approximate)
5.0
ohm/km
1.122
0.833
0.582
0.428
0.345
0.288
0.237
0.192
0.165
0.141
0.124
0.112
0.103
0.098
v/amp/km
1.943
1.443
1.008
0.741
0.598
0.499
0.410
0.333
0.286
0.244
0.215
0.194
0.178
0.170
OCI/PBMVC/REV.001/010410
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.38
0.42
0.46
0.53
0.58
7.0
mA/m
0.60
0.68
0.75
0.83
0.90
0.98
1.06
1.17
1.28
1.43
1.58
1.73
2.00
2.19
8.0
8.1
129
152
186
221
252
281
317
367
414
470
528
599
672
743
8.2
122
144
176
210
240
267
303
351
397
451
512
583
658
731
8.3
154
184
230
280
324
368
424
502
577
673
770
896
1033
1167
9.0
kA
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
SECTION A - TABLE 9
18/30 (36) kV
Single Core Aluminium Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 19/33 kV Earthed
System)
Binder Tape
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
2.0
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
26.3
30.0
34.2
38.2
kg/km
125
182
251
317
390
493
646
803
1027
1307
1721
2188
2759
3.0
mm
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
4.0
mm
1.9
2.0
2.1
2.1
2.1
2.2
2.3
2.3
2.5
2.5
2.7
2.8
2.9
5.0
mm
1.52
1.60
1.69
1.69
1.69
1.77
1.86
1.86
2.03
2.03
2.20
2.28
2.37
6.0
mm
31.5
33.5
35.5
37.0
38.0
40.0
42.5
45.0
48.5
51.5
55.5
60.5
65.0
7.0
kg/km
985
1120
1275
1405
1535
1725
2000
2250
2670
3085
3715
4455
5245
1000
1000
1000
1000
1000
500
500
500
500
500
500
500
500
mm
630
670
710
740
760
800
850
900
970
1030
1110
1210
1300
0.0291
8.0
9.0
(B)
Electrical Parameters
1.0
ohm/km
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
2.0
ohm/km
0.822
0.568
0.411
0.325
0.265
0.211
0.161
0.129
0.101
0.080
0.063
0.051
0.042
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.149
0.139
0.132
0.127
0.123
0.118
0.113
0.109
0.106
0.102
0.098
0.096
0.093
4.0
Impedance at 50 Hz (Approximate)
5.0
ohm/km
0.835
0.585
0.432
0.349
0.292
0.242
0.197
0.169
0.146
0.130
0.117
0.109
0.102
v/amp/km
1.446
1.013
0.748
0.604
0.506
0.419
0.341
0.293
0.253
0.225
0.203
0.189
0.177
17
OCI/PBMVC/REV.001/010410
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.14
0.15
0.17
0.18
0.20
0.21
0.23
0.25
0.28
0.30
0.34
0.38
0.42
7.0
mA/m
0.79
0.85
0.96
1.02
1.13
1.19
1.30
1.41
1.58
1.70
1.92
2.15
2.38
8.0
8.1
152
186
221
252
281
317
367
414
470
528
599
672
743
8.2
144
176
210
240
267
303
351
397
451
512
583
658
731
8.3
184
230
280
324
368
424
502
577
673
770
896
1033
1167
9.0
kA
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
SECTION A - TABLE 10
18
Bedding
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
3.6/6 (7.2) kV
Single Core Copper Conductor
XLPE Insulated
Aluminium Wire Armoured
To IEC 60502-2
(Suitable for 3.8/6.6 kV
Earthed System)
XLPE Insulation
Conductor Screen (Semi-conductive)
Copper Conductor
Insulation Screen (Semi-conductive)
Aluminium Wire Armour
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
(i)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
8.1
8.2
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
SINGLE CORE, 2XCWaY, Aluminium Wire Armoured Cables, 3.6/6 kV to IEC 60502-2
mm2
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
218
2.5
1.2
1.6
1.8
1.24
21.5
740
1000
323
6.9
303
2.5
1.2
1.6
1.8
1.24
22.5
855
1000
338
8.1
408
2.5
1.2
1.6
1.8
1.24
24.0
1005
1000
360
9.7
591
2.5
1.2
1.6
1.8
1.24
25.5
1245
1000
383
11.4
821
2.5
1.2
1.6
1.9
1.32
27.5
1550
1000
413
12.9
1035
2.5
1.2
1.6
1.9
1.32
29.0
1820
1000
435
14.3
1277
2.5
1.2
1.6
2.0
1.40
30.5
2120
1000
458
16.0
1601
2.5
1.2
2.0
2.0
1.40
33.0
2590
1000
495
18.4
2105
2.6
1.2
2.0
2.1
1.48
36.0
3225
1000
540
20.6
2640
2.8
1.2
2.0
2.2
1.56
38.5
3895
500
578
23.3
3383
3.0
1.2
2.0
2.3
1.64
42.5
4845
500
638
26.3
4272
3.2
1.3
2.5
2.5
1.80
47.5
6115
500
713
30.0
5618
3.2
1.4
2.5
2.6
1.88
51.5
7625
500
773
34.2
7286
3.2
1.4
2.5
2.7
1.96
56.5
9465
500
848
38.2
9046
3.2
1.5
2.5
2.9
2.12
61.0
11530
500
915
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.727
0.927
0.145
0.938
1.625
0.26
0.29
0.524
0.668
0.138
0.682
1.181
0.29
0.33
0.387
0.494
0.132
0.511
0.885
0.32
0.36
0.268
0.342
0.122
0.363
0.629
0.37
0.42
0.193
0.247
0.116
0.273
0.473
0.42
0.48
0.153
0.196
0.112
0.226
0.391
0.46
0.52
0.124
0.159
0.109
0.193
0.334
0.50
0.57
0.0991
0.128
0.106
0.166
0.288
0.54
0.61
0.0754
0.098
0.102
0.141
0.244
0.59
0.67
0.0601
0.079
0.099
0.127
0.220
0.61
0.69
0.0470
0.063
0.097
0.116
0.201
0.64
0.72
0.0366
0.050
0.097
0.109
0.189
0.67
0.76
0.0283
0.041
0.094
0.103
0.178
0.75
0.85
0.0221
0.034
0.091
0.097
0.168
0.86
0.97
0.0176
0.029
0.089
0.094
0.163
0.94
1.06
137
164
193
234
278
315
349
391
446
495
551
593
646
693
731
131
155
183
223
265
301
334
376
430
478
534
578
632
682
721
A
kA
162
3.58
196
5.01
234
7.15
291
10.01
353
13.59
406
17.16
460
21.45
524
26.46
611
34.32
692
42.90
788
57.20
873
71.50
975
90.09
1074
114.40
1156
143.00
ohm/km
ohm/km
kA
0.607
0.754
4.27
0.584
0.725
4.44
0.542
0.673
4.78
0.490
0.608
5.29
0.447
0.555
5.80
0.410
0.509
6.32
0.389
0.483
6.66
0.294
0.365
8.80
0.263
0.327
9.87
0.237
0.294
10.94
0.211
0.262
12.27
0.155
0.192
16.67
0.138
0.171
18.75
0.124
0.154
20.84
0.113
0.140
22.92
SECTION B - TABLE 1
Bedding
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
6/10 (12) kV
Single Core Copper Conductor
XLPE Insulated
Aluminium Wire Armoured
To IEC 60502-2
(Suitable for 6.35/11 kV
Earthed System)
XLPE Insulation
Conductor Screen (Semi-conductive)
Copper Conductor
Insulation Screen (Semi-conductive)
Aluminium Wire Armour
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
(i)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
8.1
8.2
19
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
SINGLE CORE, 2XCWaY, Aluminium Wire Armoured Cables, 6/10 kV to IEC 60502-2
mm2
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
218
3.4
1.2
1.6
1.8
1.24
23.5
830
1000
353
6.9
303
3.4
1.2
1.6
1.8
1.24
24.5
950
1000
368
8.1
408
3.4
1.2
1.6
1.8
1.24
26.0
1105
1000
390
9.7
591
3.4
1.2
1.6
1.9
1.32
27.5
1360
1000
413
11.4
821
3.4
1.2
1.6
1.9
1.32
29.5
1655
1000
443
12.9
1035
3.4
1.2
1.6
2.0
1.40
31.0
1940
1000
465
14.3
1277
3.4
1.2
2.0
2.1
1.48
33.5
2345
1000
503
16.0
1601
3.4
1.2
2.0
2.1
1.48
35.0
2735
1000
525
18.4
2105
3.4
1.2
2.0
2.2
1.56
38.0
3365
1000
570
20.6
2640
3.4
1.2
2.0
2.2
1.56
40.0
3995
500
600
23.3
3383
3.4
1.2
2.0
2.4
1.72
43.5
4925
500
653
26.3
4272
3.4
1.3
2.5
2.5
1.80
48.0
6155
500
720
30.0
5618
3.4
1.4
2.5
2.6
1.88
52.0
7655
500
780
34.2
7286
3.4
1.4
2.5
2.7
1.96
57.0
9510
500
855
38.2
9046
3.4
1.5
2.5
2.9
2.12
61.5
11580
500
923
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.727
0.927
0.151
0.939
1.626
0.21
0.40
0.524
0.668
0.143
0.683
1.183
0.23
0.43
0.387
0.494
0.137
0.513
0.889
0.25
0.47
0.268
0.342
0.126
0.364
0.630
0.29
0.55
0.193
0.247
0.121
0.275
0.476
0.32
0.60
0.153
0.196
0.116
0.228
0.395
0.35
0.66
0.124
0.159
0.115
0.196
0.339
0.38
0.72
0.0991
0.128
0.109
0.168
0.291
0.42
0.79
0.0754
0.098
0.106
0.144
0.249
0.47
0.89
0.0601
0.079
0.102
0.129
0.223
0.51
0.96
0.0470
0.063
0.099
0.117
0.203
0.57
1.07
0.0366
0.050
0.098
0.110
0.191
0.63
1.19
0.0283
0.041
0.094
0.103
0.178
0.71
1.34
0.0221
0.034
0.092
0.098
0.170
0.81
1.53
0.0176
0.029
0.090
0.095
0.165
0.89
1.68
137
164
193
234
278
315
349
391
446
495
551
593
646
693
731
131
155
183
223
265
301
334
376
430
478
534
578
632
682
721
A
kA
162
3.58
196
5.01
234
7.15
291
10.01
353
13.59
406
17.16
460
21.45
524
26.46
611
34.32
692
42.90
788
57.20
873
71.50
975
90.09
1074
114.40
1156
143.00
ohm/km
ohm/km
kA
0.542
0.673
4.78
0.506
0.628
5.12
0.474
0.589
5.46
0.434
0.539
5.97
0.400
0.497
6.49
0.380
0.472
6.83
0.286
0.355
9.07
0.270
0.335
9.60
0.243
0.302
10.67
0.226
0.281
11.47
0.207
0.257
12.54
0.152
0.189
17.09
0.138
0.171
18.75
0.122
0.151
21.25
0.111
0.138
23.34
SECTION B - TABLE 2
20
Bedding
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Copper Conductor
Insulation Screen (Semi-conductive)
Aluminium Wire Armour
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
(i)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
8.1
8.2
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
8.7/15 (17.5) kV
Single Core Copper Conductor
XLPE Insulated
Aluminium Wire Armoured
To IEC 60502-2
(Suitable for 8.7/15 kV Earthed
System)
SINGLE CORE, 2XCWaY, Aluminium Wire Armoured Cables, 8.7/15 kV to IEC 60502-2
mm2
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
218
4.5
1.2
1.6
1.8
1.24
26.0
935
1000
390
6.9
303
4.5
1.2
1.6
1.9
1.32
27.0
1075
1000
405
8.1
408
4.5
1.2
1.6
1.9
1.32
28.5
1230
1000
428
9.7
591
4.5
1.2
1.6
1.9
1.32
30.0
1480
1000
450
11.4
821
4.5
1.2
2.0
2.0
1.40
32.5
1880
1000
488
12.9
1035
4.5
1.2
2.0
2.1
1.48
34.5
2180
1000
518
14.3
1277
4.5
1.2
2.0
2.1
1.48
35.5
2485
1000
533
16.0
1601
4.5
1.2
2.0
2.2
1.56
37.5
2900
1000
563
18.4
2105
4.5
1.2
2.0
2.3
1.64
40.0
3540
500
600
20.6
2640
4.5
1.2
2.0
2.3
1.64
42.5
4175
500
638
23.3
3383
4.5
1.3
2.5
2.5
1.80
47.0
5300
500
705
26.3
4272
4.5
1.3
2.5
2.6
1.88
50.5
6365
500
758
30.0
5618
4.5
1.4
2.5
2.7
1.96
54.5
7895
500
818
34.2
7286
4.5
1.5
2.5
2.8
2.04
59.5
9765
500
893
38.2
9046
4.5
1.6
2.5
3.0
2.20
64.0
11870
500
960
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.727
0.927
0.157
0.940
1.628
0.17
0.46
0.524
0.668
0.149
0.684
1.185
0.19
0.52
0.387
0.494
0.143
0.514
0.890
0.21
0.57
0.268
0.342
0.132
0.367
0.636
0.23
0.63
0.193
0.247
0.127
0.278
0.482
0.26
0.71
0.153
0.196
0.123
0.231
0.400
0.28
0.77
0.124
0.159
0.118
0.198
0.343
0.30
0.82
0.0991
0.128
0.114
0.171
0.296
0.33
0.90
0.0754
0.098
0.109
0.147
0.255
0.37
1.01
0.0601
0.079
0.106
0.132
0.229
0.40
1.09
0.0470
0.063
0.104
0.122
0.211
0.45
1.23
0.0366
0.050
0.101
0.113
0.196
0.49
1.34
0.0283
0.041
0.097
0.105
0.182
0.55
1.50
0.0221
0.034
0.095
0.101
0.175
0.63
1.72
0.0176
0.029
0.092
0.096
0.166
0.69
1.89
137
164
193
234
278
315
349
391
446
495
551
593
646
693
731
131
155
183
223
265
301
334
376
430
478
534
578
632
682
721
A
kA
162
3.58
196
5.01
234
7.15
291
10.01
353
13.59
406
17.16
460
21.45
524
26.46
611
34.32
692
42.90
788
57.20
873
71.50
975
90.09
1074
114.40
1156
143.00
ohm/km
ohm/km
kA
0.474
0.589
5.46
0.447
0.555
5.80
0.422
0.524
6.15
0.389
0.483
6.66
0.294
0.365
8.80
0.278
0.345
9.34
0.263
0.327
9.87
0.249
0.309
10.40
0.226
0.281
11.47
0.211
0.262
12.27
0.155
0.192
16.67
0.145
0.180
17.92
0.130
0.161
20.00
0.115
0.143
22.50
0.107
0.133
24.17
SECTION B - TABLE 3
Bedding
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
12/20 (24) kV
Single Core Copper Conductor
XLPE Insulated
Aluminium Wire Armoured
To IEC 60502-2
(Suitable for 12.7/22 kV Earthed
System)
XLPE Insulation
Conductor Screen (Semi-conductive)
Copper Conductor
Insulation Screen (Semi-conductive)
Aluminium Wire Armour
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
(i)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
8.1
8.2
21
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
SINGLE CORE, 2XCWaY, Aluminium Wire Armoured Cables, 12/20 kV to IEC 60502-2
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
6.9
303
5.5
1.2
1.6
1.9
1.32
29.5
1190
1000
443
8.1
408
5.5
1.2
1.6
2.0
1.40
30.5
1365
1000
458
9.7
591
5.5
1.2
2.0
2.0
1.40
33.0
1710
1000
495
11.4
821
5.5
1.2
2.0
2.1
1.48
35.0
2035
1000
525
12.9
1035
5.5
1.2
2.0
2.1
1.48
36.5
2320
1000
548
14.3
1277
5.5
1.2
2.0
2.2
1.56
38.0
2645
1000
570
16.0
1601
5.5
1.2
2.0
2.2
1.56
39.5
3050
500
593
18.4
2105
5.5
1.2
2.0
2.3
1.64
42.5
3700
500
638
20.6
2640
5.5
1.3
2.5
2.4
1.72
46.0
4540
500
690
23.3
3383
5.5
1.3
2.5
2.5
1.80
49.5
5485
500
743
26.3
4272
5.5
1.4
2.5
2.6
1.88
52.5
6595
500
788
30.0
5618
5.5
1.4
2.5
2.8
2.04
56.5
8105
500
848
34.2
7286
5.5
1.5
2.5
2.9
2.12
62.0
10020
500
930
38.2
9046
5.5
1.6
2.5
3.0
2.20
66.5
12125
500
998
0.524
0.668
0.155
0.686
1.188
0.16
0.60
0.387
0.494
0.147
0.515
0.892
0.18
0.68
0.268
0.342
0.138
0.369
0.639
0.20
0.75
0.193
0.247
0.131
0.280
0.485
0.22
0.83
0.153
0.196
0.126
0.233
0.404
0.24
0.90
0.124
0.159
0.123
0.201
0.348
0.26
0.98
0.0991
0.127
0.117
0.173
0.300
0.28
1.06
0.0754
0.098
0.113
0.150
0.260
0.31
1.17
0.0601
0.079
0.111
0.136
0.236
0.34
1.28
0.0470
0.063
0.107
0.124
0.215
0.38
1.43
0.0366
0.050
0.103
0.114
0.197
0.42
1.58
0.0283
0.040
0.099
0.107
0.185
0.46
1.73
0.0221
0.034
0.097
0.103
0.178
0.53
2.00
0.0176
0.029
0.095
0.099
0.171
0.58
2.19
164
193
234
278
315
349
391
446
495
551
593
646
693
731
155
183
223
265
301
334
376
430
478
534
578
632
682
721
196
5.01
234
7.15
291
10.01
353
13.59
406
17.16
460
21.45
524
26.46
611
34.32
692
42.90
788
57.20
873
71.50
975
90.09
1074
114.40
1156
143.00
0.400
0.497
6.49
0.380
0.472
6.83
0.286
0.355
9.07
0.270
0.335
9.60
0.256
0.318
10.14
0.243
0.302
10.67
0.231
0.287
11.20
0.211
0.262
12.27
0.159
0.197
16.25
0.148
0.184
17.50
0.135
0.168
19.17
0.124
0.154
20.84
0.111
0.138
23.34
0.102
0.127
25.42
SECTION B - TABLE 4
22
Bedding
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Copper Conductor
Insulation Screen (Semi-conductive)
Aluminium Wire Armour
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
(i)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
8.1
8.2
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
18/30 (36) kV
Single Core Copper Conductor
XLPE Insulated
Aluminium Wire Armoured
To IEC 60502-2
(Suitable for 19/33 kV Earthed
System)
SINGLE CORE, 2XCWaY, Aluminium Wire Armoured Cables, 18/30 kV to IEC 60502-2
mm2
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
8.1
408
8.0
1.2
2.0
2.2
1.56
37.0
1810
1000
555
9.7
591
8.0
1.2
2.0
2.2
1.56
38.5
2085
500
578
11.4
821
8.0
1.2
2.0
2.3
1.64
40.5
2425
500
608
12.9
1035
8.0
1.2
2.0
2.3
1.64
42.0
2725
500
630
14.3
1277
8.0
1.3
2.5
2.4
1.72
45.0
3245
500
675
16.0
1601
8.0
1.3
2.5
2.5
1.80
46.5
3695
500
698
18.4
2105
8.0
1.3
2.5
2.5
1.80
49.0
4340
500
735
20.6
2640
8.0
1.4
2.5
2.6
1.88
52.0
5065
500
780
23.3
3383
8.0
1.4
2.5
2.7
1.96
55.0
6040
500
825
26.3
4272
8.0
1.5
2.5
2.8
2.04
58.5
7155
500
878
30.0
5618
8.0
1.5
2.5
2.9
2.12
62.0
8700
500
930
34.2
7286
8.0
1.6
2.5
3.1
2.28
67.5
10690
500
1013
38.2
9046
8.0
1.7
2.5
3.2
2.36
72.0
12835
500
1080
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.387
0.494
0.159
0.519
0.899
0.14
0.79
0.268
0.342
0.148
0.373
0.646
0.15
0.85
0.193
0.247
0.141
0.284
0.492
0.17
0.96
0.153
0.196
0.135
0.238
0.412
0.18
1.02
0.124
0.159
0.133
0.207
0.359
0.20
1.13
0.0991
0.127
0.127
0.180
0.312
0.21
1.19
0.0754
0.098
0.122
0.156
0.270
0.23
1.30
0.0601
0.078
0.118
0.141
0.244
0.25
1.41
0.0470
0.062
0.114
0.130
0.225
0.28
1.58
0.0366
0.050
0.110
0.121
0.210
0.30
1.70
0.0283
0.040
0.105
0.112
0.194
0.34
1.92
0.0221
0.033
0.103
0.108
0.187
0.38
2.15
0.0176
0.028
0.100
0.104
0.180
0.42
2.38
193
234
278
315
349
391
446
495
551
593
646
693
731
183
223
265
301
334
376
430
478
534
578
632
682
721
A
kA
234
7.15
291
10.01
353
13.59
406
17.16
460
21.45
524
26.46
611
34.32
692
42.90
788
57.20
873
71.50
975
90.09
1074
114.40
1156
143.00
ohm/km
ohm/km
kA
0.249
0.309
10.40
0.237
0.294
10.94
0.226
0.281
11.47
0.216
0.268
12.00
0.164
0.204
15.84
0.155
0.192
16.67
0.148
0.184
17.50
0.138
0.171
18.75
0.130
0.161
20.00
0.120
0.149
21.67
0.111
0.138
23.34
0.100
0.124
25.84
0.093
0.115
27.92
SECTION B - TABLE 5
Bedding
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Aluminium Conductor
Insulation Screen (Semi-conductive)
Aluminium Wire Armour
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
(i)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
8.1
8.2
23
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
3.6/6 (7.2) kV
Single Core Aluminium Conductor
XLPE Insulated
Aluminium Wire Armoured
To IEC 60502-2
(Suitable for 3.8/6.6 kV Earthed
System)
SINGLE CORE, A2XCWaY, Aluminium Wire Armoured Cables, 3.6/6 kV to IEC 60502-2
mm2
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
67
2.5
1.2
1.6
1.8
1.24
21.5
590
1000
323
6.9
92
2.5
1.2
1.6
1.8
1.24
22.5
645
1000
338
8.1
125
2.5
1.2
1.6
1.8
1.24
24.0
720
1000
360
9.7
182
2.5
1.2
1.6
1.8
1.24
25.5
835
1000
383
11.4
251
2.5
1.2
1.6
1.9
1.32
27.5
980
1000
413
12.9
317
2.5
1.2
1.6
1.9
1.32
29.0
1100
1000
435
14.3
390
2.5
1.2
1.6
2.0
1.40
30.5
1230
1000
458
16.0
493
2.5
1.2
2.0
2.0
1.40
33.0
1485
1000
495
18.4
646
2.6
1.2
2.0
2.1
1.48
36.0
1765
1000
540
20.6
803
2.8
1.2
2.0
2.2
1.56
38.5
2060
500
578
23.3
1027
3.0
1.2
2.0
2.3
1.64
42.5
2490
500
638
26.3
1307
3.2
1.3
2.5
2.5
1.80
47.5
3150
500
713
30.0
1721
3.2
1.4
2.5
2.6
1.88
51.5
3800
500
773
34.2
2188
3.2
1.4
2.5
2.7
1.96
56.5
4550
500
848
38.2
2759
3.2
1.5
2.5
2.9
2.12
61.0
5390
500
915
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
1.20
1.539
0.145
1.546
2.678
0.26
0.29
0.868
1.113
0.138
1.122
1.943
0.29
0.33
0.641
0.822
0.132
0.833
1.443
0.32
0.36
0.443
0.568
0.122
0.581
1.006
0.37
0.42
0.320
0.411
0.116
0.427
0.740
0.42
0.48
0.253
0.325
0.112
0.344
0.596
0.46
0.52
0.206
0.265
0.109
0.287
0.497
0.50
0.57
0.164
0.211
0.106
0.236
0.409
0.54
0.61
0.125
0.161
0.102
0.191
0.331
0.59
0.67
0.100
0.130
0.099
0.163
0.282
0.61
0.69
0.0778
0.102
0.097
0.141
0.244
0.64
0.72
0.0605
0.080
0.097
0.126
0.218
0.67
0.76
0.0469
0.063
0.094
0.113
0.196
0.75
0.85
0.0367
0.051
0.091
0.104
0.180
0.86
0.97
0.0291
0.043
0.089
0.099
0.171
0.94
1.06
107
127
150
182
217
246
274
309
355
397
448
494
549
601
648
101
121
142
174
207
235
262
297
342
383
434
482
537
592
639
A
kA
126
2.35
152
3.29
182
4.70
226
6.58
275
8.93
317
11.28
360
14.10
413
17.39
485
22.56
552
28.20
638
37.60
724
47.00
824
59.22
927
75.20
1020
94.00
ohm/km
ohm/km
kA
0.607
0.754
4.27
0.584
0.725
4.44
0.542
0.673
4.78
0.490
0.608
5.29
0.447
0.555
5.80
0.410
0.509
6.32
0.389
0.483
6.66
0.294
0.365
8.80
0.263
0.327
9.87
0.237
0.294
10.94
0.211
0.262
12.27
0.155
0.192
16.67
0.138
0.171
18.75
0.124
0.154
20.84
0.113
0.140
22.92
SECTION B - TABLE 6
24
Bedding
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Aluminium Conductor
Insulation Screen (Semi-conductive)
Aluminium Wire Armour
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
(i)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
8.1
8.2
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
6/10 (12) kV
Single Core Aluminium Conductor
XLPE Insulated
Aluminium Wire Armoured
To IEC 60502-2
(Suitable for 6.35/11 kV Earthed
System)
SINGLE CORE, A2XCWaY, Aluminium Wire Armoured Cables, 6/10 kV to IEC 60502-2
mm2
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
67
3.4
1.2
1.6
1.8
1.24
23.5
675
1000
353
6.9
92
3.4
1.2
1.6
1.8
1.24
24.5
740
1000
368
8.1
125
3.4
1.2
1.6
1.8
1.24
26.0
820
1000
390
9.7
182
3.4
1.2
1.6
1.9
1.32
27.5
950
1000
413
11.4
251
3.4
1.2
1.6
1.9
1.32
29.5
1085
1000
443
12.9
317
3.4
1.2
1.6
2.0
1.40
31.0
1220
1000
465
14.3
390
3.4
1.2
2.0
2.1
1.48
33.5
1455
1000
503
16.0
493
3.4
1.2
2.0
2.1
1.48
35.0
1625
1000
525
18.4
646
3.4
1.2
2.0
2.2
1.56
38.0
1905
1000
570
20.6
803
3.4
1.2
2.0
2.2
1.56
40.0
2155
500
600
23.3
1027
3.4
1.2
2.0
2.4
1.72
43.5
2570
500
653
26.3
1307
3.4
1.3
2.5
2.5
1.80
48.0
3190
500
720
30.0
1721
3.4
1.4
2.5
2.6
1.88
52.0
3830
500
780
34.2
2188
3.4
1.4
2.5
2.7
1.96
57.0
4600
500
855
38.2
2759
3.4
1.5
2.5
2.9
2.12
61.5
5440
500
923
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
1.20
1.539
0.151
1.546
2.678
0.21
0.40
0.868
1.113
0.143
1.122
1.943
0.23
0.43
0.641
0.822
0.137
0.833
1.443
0.25
0.47
0.443
0.568
0.126
0.582
1.008
0.29
0.55
0.320
0.411
0.121
0.428
0.741
0.32
0.60
0.253
0.325
0.116
0.345
0.598
0.35
0.66
0.206
0.265
0.115
0.289
0.501
0.38
0.72
0.164
0.211
0.109
0.237
0.410
0.42
0.79
0.125
0.161
0.106
0.193
0.334
0.47
0.89
0.100
0.130
0.102
0.165
0.286
0.51
0.96
0.0778
0.102
0.099
0.142
0.246
0.57
1.07
0.0605
0.080
0.098
0.127
0.220
0.63
1.19
0.0469
0.063
0.094
0.113
0.196
0.71
1.34
0.0367
0.051
0.092
0.105
0.182
0.81
1.53
0.0291
0.042
0.090
0.099
0.171
0.89
1.68
107
127
150
182
217
246
274
309
355
397
448
494
549
601
648
101
121
142
174
207
235
262
297
342
383
434
482
537
592
639
A
kA
126
2.35
152
3.29
182
4.70
226
6.58
275
8.93
317
11.28
360
14.10
413
17.39
485
22.56
552
28.20
638
37.60
724
47.00
824
59.22
927
75.20
1020
94.00
ohm/km
ohm/km
kA
0.542
0.673
4.78
0.506
0.628
5.12
0.474
0.589
5.46
0.434
0.539
5.97
0.400
0.497
6.49
0.380
0.472
6.83
0.286
0.355
9.07
0.270
0.335
9.60
0.243
0.302
10.67
0.226
0.281
11.47
0.207
0.257
12.54
0.152
0.189
17.09
0.138
0.171
18.75
0.122
0.151
21.25
0.111
0.138
23.34
SECTION B - TABLE 7
Bedding
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Aluminium Conductor
Insulation Screen (Semi-conductive)
Aluminium Wire Armour
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
(i)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
8.1
8.2
25
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
8.7/15 (17.5) kV
Single Core Aluminium Conductor
XLPE Insulated
Aluminium Wire Armoured
To IEC 60502-2
(Suitable for 8.7/15 kV Earthed
System)
SINGLE CORE, A2XCWaY, Aluminium Wire Armoured Cables, 8.7/15 kV to IEC 60502-2
mm2
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
67
4.5
1.2
1.6
1.8
1.24
26.0
780
1000
390
6.9
92
4.5
1.2
1.6
1.9
1.32
27.0
865
1000
405
8.1
125
4.5
1.2
1.6
1.9
1.32
28.5
945
1000
428
9.7
182
4.5
1.2
1.6
1.9
1.32
30.0
1070
1000
450
11.4
251
4.5
1.2
2.0
2.0
1.40
32.5
1310
1000
488
12.9
317
4.5
1.2
2.0
2.1
1.48
34.5
1460
1000
518
14.3
390
4.5
1.2
2.0
2.1
1.48
35.5
1595
1000
533
16.0
493
4.5
1.2
2.0
2.2
1.56
37.5
1790
1000
563
18.4
646
4.5
1.2
2.0
2.3
1.64
40.0
2080
500
600
20.6
803
4.5
1.2
2.0
2.3
1.64
42.5
2340
500
638
23.3
1027
4.5
1.3
2.5
2.5
1.80
47.0
2945
500
705
26.3
1307
4.5
1.3
2.5
2.6
1.88
50.5
3400
500
758
30.0
1721
4.5
1.4
2.5
2.7
1.96
54.5
4070
500
818
34.2
2188
4.5
1.5
2.5
2.8
2.04
59.5
4855
500
893
38.2
2759
4.5
1.6
2.5
3.0
2.20
64.0
5725
500
960
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
1.20
1.539
0.157
1.547
2.679
0.17
0.46
0.868
1.113
0.149
1.123
1.945
0.19
0.52
0.641
0.822
0.143
0.834
1.445
0.21
0.57
0.443
0.568
0.132
0.583
1.010
0.23
0.63
0.320
0.411
0.127
0.430
0.745
0.26
0.71
0.253
0.325
0.123
0.347
0.601
0.28
0.77
0.206
0.265
0.118
0.290
0.502
0.30
0.82
0.164
0.211
0.114
0.240
0.416
0.33
0.90
0.125
0.161
0.109
0.194
0.336
0.37
1.01
0.100
0.130
0.106
0.168
0.291
0.40
1.09
0.0778
0.101
0.104
0.145
0.251
0.45
1.23
0.0605
0.080
0.101
0.129
0.223
0.49
1.34
0.0469
0.063
0.097
0.116
0.201
0.55
1.50
0.0367
0.051
0.095
0.108
0.187
0.63
1.72
0.0291
0.042
0.092
0.101
0.175
0.69
1.89
107
127
150
182
217
246
274
309
355
397
448
494
549
601
648
101
121
142
174
207
235
262
297
342
383
434
482
537
592
639
A
kA
126
2.35
152
3.29
182
4.70
226
6.58
275
8.93
317
11.28
360
14.10
413
17.39
485
22.56
552
28.20
638
37.60
724
47.00
824
59.22
927
75.20
1020
94.00
ohm/km
ohm/km
kA
0.474
0.589
5.46
0.447
0.555
5.80
0.422
0.524
6.15
0.389
0.483
6.66
0.294
0.365
8.80
0.278
0.345
9.34
0.263
0.327
9.87
0.249
0.309
10.40
0.226
0.281
11.47
0.211
0.262
12.27
0.155
0.192
16.67
0.145
0.180
17.92
0.130
0.161
20.00
0.115
0.143
22.50
0.107
0.133
24.17
SECTION B - TABLE 8
26
Bedding
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Aluminium Conductor
Insulation Screen (Semi-conductive)
Aluminium Wire Armour
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
(i)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
8.1
8.2
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
12/20 (24) kV
Single Core Aluminium Conductor
XLPE Insulated
Aluminium Wire Armoured
To IEC 60502-2
(Suitable for 12.7/22 kV Earthed
System)
SINGLE CORE, A2XCWaY, Aluminium Wire Armoured Cables, 12/20 kV to IEC 60502-2
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
6.9
92
5.5
1.2
1.6
1.9
1.32
29.5
980
1000
443
8.1
125
5.5
1.2
1.6
2.0
1.40
30.5
1080
1000
458
9.7
182
5.5
1.2
2.0
2.0
1.40
33.0
1300
1000
495
11.4
251
5.5
1.2
2.0
2.1
1.48
35.0
1465
1000
525
12.9
317
5.5
1.2
2.0
2.1
1.48
36.5
1605
1000
548
14.3
390
5.5
1.2
2.0
2.2
1.56
38.0
1760
1000
570
16.0
493
5.5
1.2
2.0
2.2
1.56
39.5
1945
500
593
18.4
646
5.5
1.2
2.0
2.3
1.64
42.5
2240
500
638
20.6
803
5.5
1.3
2.5
2.4
1.72
46.0
2705
500
690
23.3
1027
5.5
1.3
2.5
2.5
1.80
49.5
3130
500
743
26.3
1307
5.5
1.4
2.5
2.6
1.88
52.5
3630
500
788
30.0
1721
5.5
1.4
2.5
2.8
2.04
56.5
4280
500
848
34.2
2188
5.5
1.5
2.5
2.9
2.12
62.0
5110
500
930
38.2
2759
5.5
1.6
2.5
3.0
2.20
66.5
5980
500
998
0.868
1.113
0.155
1.124
1.947
0.16
0.60
0.641
0.822
0.147
0.835
1.446
0.18
0.68
0.443
0.568
0.138
0.585
1.013
0.20
0.75
0.320
0.411
0.131
0.431
0.747
0.22
0.83
0.253
0.325
0.126
0.349
0.604
0.24
0.90
0.206
0.265
0.123
0.292
0.506
0.26
0.98
0.164
0.211
0.117
0.241
0.417
0.28
1.06
0.125
0.161
0.113
0.197
0.341
0.31
1.17
0.100
0.129
0.111
0.170
0.294
0.34
1.28
0.0778
0.101
0.107
0.147
0.255
0.38
1.43
0.0605
0.080
0.103
0.130
0.225
0.42
1.58
0.0469
0.063
0.099
0.117
0.203
0.46
1.73
0.0367
0.051
0.097
0.110
0.191
0.53
2.00
0.0291
0.042
0.095
0.104
0.180
0.58
2.19
127
150
182
217
246
274
309
355
397
448
494
549
601
648
121
142
174
207
235
262
297
342
383
434
482
537
592
639
152
3.29
182
4.70
226
6.58
275
8.93
317
11.28
360
14.10
413
17.39
485
22.56
552
28.20
638
37.60
724
47.00
824
59.22
927
75.20
1020
94.00
0.400
0.497
6.49
0.380
0.472
6.83
0.286
0.355
9.07
0.270
0.335
9.60
0.256
0.318
10.14
0.243
0.302
10.67
0.231
0.287
11.20
0.211
0.262
12.27
0.159
0.197
16.25
0.148
0.184
17.50
0.135
0.168
19.17
0.124
0.154
20.84
0.111
0.138
23.34
0.102
0.127
25.42
SECTION B - TABLE 9
Bedding
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Aluminium Conductor
Insulation Screen (Semi-conductive)
Aluminium Wire Armour
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
(i)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
8.1
8.2
27
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
18/30 (36) kV
Single Core Aluminium Conductor
XLPE Insulated
Aluminium Wire Armoured
To IEC 60502-2
(Suitable for 19/33 kV Earthed
System)
SINGLE CORE, A2XCWaY, Aluminium Wire Armoured Cables, 18/30 kV to IEC 60502-2
mm2
50
70
95
120
150
185
240
300
400
500
630
800
1000
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
8.1
125
8.0
1.2
2.0
2.2
1.56
37.0
1530
1000
555
9.7
182
8.0
1.2
2.0
2.2
1.56
38.5
1675
500
578
11.4
251
8.0
1.2
2.0
2.3
1.64
40.5
1855
500
608
12.9
317
8.0
1.2
2.0
2.3
1.64
42.0
2005
500
630
14.3
390
8.0
1.3
2.5
2.4
1.72
45.0
2355
500
675
16.0
493
8.0
1.3
2.5
2.5
1.80
46.5
2585
500
698
18.4
646
8.0
1.3
2.5
2.5
1.80
49.0
2880
500
735
20.6
803
8.0
1.4
2.5
2.6
1.88
52.0
3230
500
780
23.3
1027
8.0
1.4
2.5
2.7
1.96
55.0
3685
500
825
26.3
1307
8.0
1.5
2.5
2.8
2.04
58.5
4190
500
878
30.0
1721
8.0
1.5
2.5
2.9
2.12
62.0
4870
500
930
34.2
2188
8.0
1.6
2.5
3.1
2.28
67.5
5780
500
1013
38.2
2759
8.0
1.7
2.5
3.2
2.36
72.0
6695
500
1080
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.641
0.822
0.159
0.837
1.450
0.14
0.79
0.443
0.568
0.148
0.587
1.017
0.15
0.85
0.320
0.411
0.141
0.435
0.753
0.17
0.96
0.253
0.325
0.135
0.352
0.610
0.18
1.02
0.206
0.265
0.133
0.297
0.514
0.20
1.13
0.164
0.211
0.127
0.246
0.426
0.21
1.19
0.125
0.161
0.122
0.202
0.350
0.23
1.30
0.100
0.129
0.118
0.175
0.303
0.25
1.41
0.0778
0.101
0.114
0.152
0.263
0.28
1.58
0.0605
0.080
0.110
0.136
0.236
0.30
1.70
0.0469
0.063
0.105
0.122
0.211
0.34
1.92
0.0367
0.050
0.103
0.114
0.197
0.38
2.15
0.0291
0.042
0.100
0.108
0.187
0.42
2.38
150
182
217
246
274
309
355
397
448
494
549
601
648
142
174
207
235
262
297
342
383
434
482
537
592
639
A
kA
182
4.70
226
6.58
275
8.93
317
11.28
360
14.10
413
17.39
485
22.56
552
28.20
638
37.60
724
47.00
824
59.22
927
75.20
1020
94.00
ohm/km
ohm/km
kA
0.249
0.309
10.40
0.237
0.294
10.94
0.226
0.281
11.47
0.216
0.268
12.00
0.164
0.204
15.84
0.155
0.192
16.67
0.148
0.184
17.50
0.138
0.171
18.75
0.130
0.161
20.00
0.120
0.149
21.67
0.111
0.138
23.34
0.100
0.124
25.84
0.093
0.115
27.92
SECTION B - TABLE 10
28
Fillers
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Copper Conductor
Insulation Screen (Semi-conductive)
3.6/6 (7.2) kV
Three Core Copper Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 3.8/6.6 kV Earthed
System)
Binder tape
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
2.0
25
35
50
70
95
120
150
185
240
300
400
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
kg/km
665
922
1242
1800
2500
3152
3888
4875
6410
8039
10301
3.0
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
3.0
4.0
mm
2.1
2.1
2.2
2.3
2.5
2.6
2.7
2.8
3.0
3.2
3.4
5.0
mm
1.69
1.69
1.77
1.86
2.03
2.11
2.20
2.28
2.45
2.62
2.79
6.0
mm
34.5
36.5
39.0
43.0
47.0
50.5
53.5
57.5
63.5
69.5
78.0
13675
7.0
8.0
9.0
(B)
Electrical Parameters
kg/km
1560
1905
2345
3065
3965
4785
5680
6865
8755
10780
1000
1000
500
500
500
500
500
500
500
500
250
mm
518
548
585
645
705
758
803
863
953
1043
1170
0.0470
1.0
ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
2.0
ohm/km
0.927
0.668
0.494
0.342
0.247
0.196
0.160
0.128
0.099
0.080
0.064
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.119
0.113
0.108
0.100
0.095
0.092
0.090
0.087
0.084
0.083
0.082
4.0
Impedance at 50 Hz (Approximate)
5.0
ohm/km
0.935
0.677
0.506
0.356
0.265
0.217
0.184
0.155
0.130
0.115
0.104
v/amp/km
1.619
1.173
0.876
0.617
0.459
0.376
0.319
0.268
0.225
0.199
0.180
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.27
0.29
0.33
0.38
0.42
0.47
0.51
0.55
0.60
0.62
0.65
7.0
mA/m
0.31
0.33
0.37
0.43
0.48
0.53
0.58
0.62
0.68
0.70
0.74
OCI/PBMVC/REV.001/010410
8.0
8.1
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
129
153
181
221
262
298
334
377
434
489
553
8.2
112
133
158
193
231
264
297
336
390
441
501
8.3
142
170
204
253
304
351
398
455
531
606
696
9.0
kA
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
SECTION C - TABLE 1
Fillers
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Copper Conductor
Insulation Screen (Semi-conductive)
Binder tape
6/10 (12) kV
Three Core Copper Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 6.35/11 kV Earthed
System)
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
25
35
50
70
95
120
150
185
240
300
400
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
10301
2.0
kg/km
665
922
1242
1800
2500
3152
3888
4875
6410
8039
3.0
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
4.0
mm
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3.1
3.3
3.5
5.0
mm
1.77
1.86
1.94
2.03
2.11
2.20
2.28
2.37
2.54
2.71
2.88
6.0
mm
39.0
41.0
44.0
47.5
51.5
55.0
58.0
62.0
67.5
73.0
80.0
7.0
kg/km
1805
2180
2640
3380
4285
5125
6040
7250
9140
11105
13900
8.0
9.0
(B)
Electrical Parameters
500
500
500
500
500
500
500
500
500
500
250
mm
585
615
660
713
773
825
870
930
1013
1095
1200
1.0
ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
2.0
ohm/km
0.927
0.668
0.494
0.342
0.247
0.196
0.159
0.128
0.099
0.080
0.064
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.127
0.121
0.116
0.107
0.102
0.098
0.096
0.092
0.089
0.086
0.084
4.0
Impedance at 50 Hz (Approximate)
ohm/km
0.936
0.679
0.507
0.358
0.267
0.219
0.186
0.158
0.133
0.117
0.106
0.184
5.0
v/amp/km
1.621
1.176
0.878
0.620
0.462
0.379
0.322
0.274
0.230
0.203
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.21
0.23
0.26
0.29
0.33
0.36
0.39
0.42
0.48
0.52
0.58
7.0
mA/m
0.40
0.43
0.49
0.55
0.62
0.68
0.74
0.79
0.90
0.98
1.09
29
OCI/PBMVC/REV.001/010410
8.0
8.1
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
129
153
181
221
262
298
334
377
434
489
553
8.2
112
133
158
193
231
264
297
336
390
441
501
8.3
142
170
204
253
304
351
398
455
531
606
696
9.0
kA
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
SECTION C - TABLE 2
30
Fillers
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Copper Conductor
Insulation Screen (Semi-conductive)
8.7/15 (17.5) kV
Three Core Copper Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 8.7/15 kV Earthed
System)
Binder tape
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
2.0
3.0
25
35
50
70
95
120
150
185
240
300
400
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
kg/km
665
922
1242
1800
2500
3152
3888
4875
6410
8039
10301
mm
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.0
mm
2.4
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.4
3.7
5.0
mm
1.94
2.03
2.11
2.20
2.28
2.37
2.45
2.54
2.71
2.79
3.05
6.0
7.0
8.0
9.0
(B)
Electrical Parameters
mm
44.0
46.5
49.0
53.0
56.5
60.0
63.0
67.0
73.0
77.5
85.0
kg/km
2125
2515
2995
3765
4695
5560
6495
7735
9660
11630
14510
500
500
500
500
500
500
500
500
500
250
250
mm
660
698
735
795
848
900
945
1005
1095
1163
1275
0.0470
1.0
ohm/km
0.727
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
2.0
ohm/km
0.927
0.668
0.494
0.342
0.247
0.196
0.159
0.128
0.098
0.080
0.064
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.136
0.129
0.123
0.114
0.108
0.104
0.101
0.097
0.093
0.091
0.088
4.0
Impedance at 50 Hz (Approximate)
5.0
ohm/km
0.937
0.680
0.509
0.360
0.270
0.222
0.188
0.161
0.135
0.121
0.109
v/amp/km
1.623
1.178
0.882
0.624
0.468
0.385
0.326
0.279
0.234
0.210
0.189
OCI/PBMVC/REV.001/010410
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.17
0.19
0.21
0.24
0.26
0.29
0.31
0.34
0.37
0.41
0.46
7.0
mA/m
0.46
0.52
0.57
0.66
0.71
0.79
0.85
0.93
1.01
1.12
1.26
8.0
8.1
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
129
153
181
221
262
298
334
377
434
489
553
8.2
112
133
158
193
231
264
297
336
390
441
501
8.3
142
170
204
253
304
351
398
455
531
606
696
9.0
kA
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
SECTION C - TABLE 3
Fillers
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
12/20 (24) kV
Three Core Copper Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 12.7/22 kV Earthed
System)
XLPE Insulation
Conductor Screen (Semi-conductive)
Copper Conductor
Insulation Screen (Semi-conductive)
Binder tape
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
35
50
70
95
120
150
185
240
300
400
mm
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
10301
2.0
kg/km
922
1242
1800
2500
3152
3888
4875
6410
8039
3.0
mm
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
4.0
mm
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.4
3.6
3.8
5.0
mm
2.11
2.20
2.28
2.37
2.45
2.54
2.71
2.79
2.96
3.13
6.0
mm
51.5
54.0
57.5
61.5
65.0
68.0
72.0
77.5
83.0
90.0
7.0
kg/km
2865
3365
4155
5110
6000
6955
8255
10185
12225
15115
8.0
9.0
(B)
Electrical Parameters
500
500
500
500
500
500
500
250
250
250
mm
773
810
863
923
975
1020
1080
1163
1245
1350
1.0
ohm/km
0.524
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
0.0470
2.0
ohm/km
0.668
0.494
0.342
0.247
0.196
0.159
0.128
0.098
0.079
0.063
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.136
0.130
0.120
0.114
0.110
0.106
0.102
0.098
0.095
0.092
4.0
Impedance at 50 Hz (Approximate)
ohm/km
0.682
0.511
0.362
0.272
0.225
0.191
0.164
0.139
0.124
0.112
0.194
31
OCI/PBMVC/REV.001/010410
5.0
v/amp/km
1.181
0.885
0.627
0.471
0.390
0.331
0.284
0.241
0.215
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.17
0.18
0.20
0.23
0.25
0.26
0.29
0.32
0.35
0.38
7.0
mA/m
0.64
0.68
0.75
0.87
0.94
0.98
1.09
1.21
1.32
1.43
8.0
8.1
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
153
181
221
262
298
334
377
434
489
553
8.2
133
158
193
231
264
297
336
390
441
501
8.3
170
204
253
304
351
398
455
531
606
696
9.0
kA
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
SECTION C - TABLE 4
32
Fillers
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Copper Conductor
Insulation Screen (Semi-conductive)
18/30 (36) kV
Three Core Copper Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 19/33 kV Earthed
System)
Binder tape
Outer Sheath
COPPER CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
2.0
50
70
95
120
150
185
240
300
400
mm
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
kg/km
1242
1800
2500
3152
3888
4875
6410
8039
10301
3.0
mm
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
4.0
mm
3.1
3.2
3.3
3.4
3.5
3.6
3.8
4.0
4.2
5.0
mm
2.54
2.62
2.71
2.79
2.88
2.96
3.13
3.30
3.47
6.0
mm
66.0
69.5
73.5
77.0
80.0
84.0
89.5
95.0
102.0
kg/km
4410
5265
6285
7230
8235
9565
11625
13750
16760
500
500
250
250
250
250
250
250
250
mm
990
1043
1103
1155
1200
1260
1343
1425
1530
0.0470
7.0
8.0
9.0
(B)
Electrical Parameters
1.0
ohm/km
0.387
0.268
0.193
0.153
0.124
0.0991
0.0754
0.0601
2.0
ohm/km
0.494
0.342
0.247
0.196
0.159
0.128
0.098
0.079
0.063
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.143
0.132
0.126
0.121
0.117
0.112
0.107
0.104
0.100
4.0
Impedance at 50 Hz (Approximate)
5.0
ohm/km
0.514
0.367
0.277
0.230
0.197
0.170
0.145
0.131
0.118
v/amp/km
0.890
0.636
0.480
0.398
0.341
0.294
0.251
0.227
0.204
OCI/PBMVC/REV.001/010410
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.14
0.16
0.17
0.19
0.20
0.22
0.24
0.26
0.28
7.0
mA/m
0.79
0.90
0.96
1.07
1.13
1.24
1.36
1.47
1.58
8.0
8.1
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
181
221
262
298
334
377
434
489
553
8.2
158
193
231
264
297
336
390
441
501
8.3
204
253
304
351
398
455
531
606
696
9.0
kA
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
SECTION C - TABLE 5
Fillers
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Aluminium Conductor
Insulation Screen (Semi-conductive)
3.6/6 (7.2) kV
Three Core Aluminium Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 3.8/6.6 kV Earthed
System)
Binder tape
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
25
35
50
70
95
120
150
185
240
300
400
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
3126
2.0
kg/km
203
280
381
553
764
965
1186
1500
1967
2445
3.0
mm
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.6
2.8
3.0
4.0
mm
2.1
2.1
2.2
2.3
2.5
2.6
2.7
2.8
3.0
3.2
3.4
5.0
mm
1.69
1.69
1.77
1.86
2.03
2.11
2.20
2.28
2.45
2.62
2.79
6.0
mm
34.5
36.5
39.0
43.0
47.0
50.5
53.5
57.5
63.5
69.5
78.0
7.0
kg/km
1100
1260
1480
1815
2230
2595
2975
3490
4315
5185
6500
1000
1000
500
500
500
500
500
500
500
500
250
mm
518
548
585
645
705
758
803
863
953
1043
1170
8.0
9.0
(B)
Electrical Parameters
1.0
ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
2.0
ohm/km
1.539
1.113
0.822
0.568
0.411
0.325
0.265
0.211
0.162
0.130
0.102
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.119
0.113
0.108
0.100
0.095
0.092
0.090
0.087
0.084
0.083
0.082
4.0
Impedance at 50 Hz (Approximate)
ohm/km
1.544
1.119
0.829
0.577
0.422
0.338
0.280
0.228
0.182
0.154
0.131
0.227
33
OCI/PBMVC/REV.001/010410
5.0
v/amp/km
2.674
1.938
1.436
0.999
0.731
0.585
0.485
0.395
0.315
0.267
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.27
0.29
0.33
0.38
0.42
0.47
0.51
0.55
0.60
0.62
0.65
7.0
mA/m
0.31
0.33
0.37
0.43
0.48
0.53
0.58
0.62
0.68
0.70
0.74
8.0
8.1
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
100
119
140
171
203
232
260
294
340
384
438
8.2
87
103
122
150
179
205
231
262
305
346
398
8.3
110
132
158
196
236
273
309
355
415
475
552
9.0
kA
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
SECTION C - TABLE 6
34
Fillers
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Aluminium Conductor
Insulation Screen (Semi-conductive)
Binder tape
6/10 (12) kV
Three Core Aluminium Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 6.35/11 kV Earthed
System)
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
2.0
25
35
50
70
95
120
150
185
240
300
400
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
kg/km
203
280
381
553
764
965
1186
1500
1967
2445
3126
3.0
mm
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
4.0
mm
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3.1
3.3
3.5
5.0
mm
1.77
1.86
1.94
2.03
2.11
2.20
2.28
2.37
2.54
2.71
2.88
6.0
mm
39.0
41.0
44.0
47.5
51.5
55.0
58.0
62.0
67.5
73.0
80.0
kg/km
1345
1540
1780
2135
2550
2940
3340
3875
4695
5515
6725
500
500
500
500
500
500
500
500
500
500
250
mm
585
615
660
713
773
825
870
930
1013
1095
1200
0.0778
7.0
8.0
9.0
(B)
Electrical Parameters
1.0
ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
2.0
ohm/km
1.539
1.113
0.822
0.568
0.411
0.325
0.265
0.211
0.162
0.130
0.102
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.127
0.121
0.116
0.107
0.102
0.098
0.096
0.092
0.089
0.086
0.084
4.0
Impedance at 50 Hz (Approximate)
5.0
ohm/km
1.544
1.120
0.830
0.578
0.423
0.339
0.282
0.230
0.185
0.156
0.132
v/amp/km
2.674
1.940
1.438
1.001
0.733
0.587
0.488
0.398
0.320
0.270
0.229
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.21
0.23
0.26
0.29
0.33
0.36
0.39
0.42
0.48
0.52
0.58
7.0
mA/m
0.40
0.43
0.49
0.55
0.62
0.68
0.74
0.79
0.90
0.98
1.09
OCI/PBMVC/REV.001/010410
8.0
8.1
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
100
119
140
171
203
232
260
294
340
384
438
8.2
87
103
122
150
179
205
231
262
305
346
398
8.3
110
132
158
196
236
273
309
355
415
475
552
9.0
kA
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
SECTION C - TABLE 7
Fillers
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Aluminium Conductor
Insulation Screen (Semi-conductive)
Binder tape
8.7/15 (17.5) kV
Three Core Aluminium Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 8.7/15 kV Earthed
System)
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
25
35
50
70
95
120
150
185
240
300
400
mm
5.9
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
3126
2.0
kg/km
203
280
381
553
764
965
1186
1500
1967
2445
3.0
mm
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.0
mm
2.4
2.5
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.4
3.7
5.0
mm
1.94
2.03
2.11
2.20
2.28
2.37
2.45
2.54
2.71
2.79
3.05
6.0
mm
44.0
46.5
49.0
53.0
56.5
60.0
63.0
67.0
73.0
77.5
85.0
7.0
kg/km
1665
1875
2135
2520
2960
3375
3795
4360
5220
6035
7335
8.0
9.0
(B)
Electrical Parameters
500
500
500
500
500
500
500
500
500
250
250
mm
660
698
735
795
848
900
945
1005
1095
1163
1275
1.0
ohm/km
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
2.0
ohm/km
1.539
1.113
0.822
0.568
0.411
0.325
0.265
0.211
0.162
0.130
0.102
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.136
0.129
0.123
0.114
0.108
0.104
0.101
0.097
0.093
0.091
0.088
4.0
Impedance at 50 Hz (Approximate)
ohm/km
1.545
1.120
0.831
0.579
0.425
0.341
0.284
0.232
0.187
0.159
0.135
0.234
5.0
v/amp/km
2.676
1.940
1.439
1.003
0.736
0.591
0.492
0.402
0.324
0.275
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.17
0.19
0.21
0.24
0.26
0.29
0.31
0.34
0.37
0.41
0.46
7.0
mA/m
0.46
0.52
0.57
0.66
0.71
0.79
0.85
0.93
1.01
1.12
1.26
35
OCI/PBMVC/REV.001/010410
8.0
8.1
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
100
119
140
171
203
232
260
294
340
384
438
8.2
87
103
122
150
179
205
231
262
305
346
398
8.3
110
132
158
196
236
273
309
355
415
475
552
9.0
kA
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
SECTION C - TABLE 8
36
Fillers
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Aluminium Conductor
Insulation Screen (Semi-conductive)
12/20 (24) kV
Three Core Aluminium Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 12.7/22 kV Earthed
System)
Binder tape
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
2.0
35
50
70
95
120
150
185
240
300
400
mm
6.9
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
kg/km
280
381
553
764
965
1186
1500
1967
2445
3126
3.0
mm
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
4.0
mm
2.6
2.7
2.8
2.9
3.0
3.1
3.3
3.4
3.6
3.8
5.0
mm
2.11
2.20
2.28
2.37
2.45
2.54
2.71
2.79
2.96
3.13
6.0
mm
51.5
54.0
57.5
61.5
65.0
68.0
72.0
77.5
83.0
90.0
kg/km
2220
2500
2910
3375
3810
4255
4880
5745
6635
7940
500
500
500
500
500
500
500
250
250
250
mm
773
810
863
923
975
1020
1080
1163
1245
1350
0.0778
7.0
8.0
9.0
(B)
Electrical Parameters
1.0
ohm/km
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
2.0
ohm/km
1.113
0.822
0.568
0.411
0.325
0.265
0.211
0.162
0.130
0.102
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.136
0.130
0.120
0.114
0.110
0.106
0.102
0.098
0.095
0.092
4.0
Impedance at 50 Hz (Approximate)
5.0
ohm/km
1.121
0.832
0.581
0.427
0.343
0.285
0.234
0.189
0.161
0.137
v/amp/km
1.942
1.441
1.006
0.740
0.594
0.494
0.405
0.327
0.279
0.237
OCI/PBMVC/REV.001/010410
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.17
0.18
0.20
0.23
0.25
0.26
0.29
0.32
0.35
0.38
7.0
mA/m
0.64
0.68
0.75
0.87
0.94
0.98
1.09
1.21
1.32
1.43
8.0
8.1
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
119
140
171
203
232
260
294
340
384
438
8.2
103
122
150
179
205
231
262
305
346
398
8.3
132
158
196
236
273
309
355
415
475
552
9.0
kA
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
SECTION C - TABLE 9
Fillers
Metallic Copper Screen
(Copper screen can be of Cu wires + open helix Cu tape
or copper tape (The details given in below Table are for
copper tape screened cables). For copper wire screened
cables the details can be given on specific request.)
XLPE Insulation
Conductor Screen (Semi-conductive)
Aluminium Conductor
Insulation Screen (Semi-conductive)
18/30 (36) kV
Three Core Aluminium Conductor
XLPE Insulated Unarmoured
To IEC 60502-2
(Suitable for 19/33 kV Earthed
System)
Binder tape
Outer Sheath
ALUMINIUM CONDUCTOR
Sr. No.
(A)
Manufacturing Dimensions
1.0
50
70
95
120
150
185
240
300
400
mm
8.1
9.7
11.4
12.9
14.3
16.0
18.4
20.6
23.3
3126
2.0
kg/km
381
553
764
965
1186
1500
1967
2445
3.0
mm
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
4.0
mm
3.1
3.2
3.3
3.4
3.5
3.6
3.8
4.0
4.2
5.0
mm
2.54
2.62
2.71
2.79
2.88
2.96
3.13
3.30
3.47
6.0
mm
66.0
69.5
73.5
77.0
80.0
84.0
89.5
95.0
102.0
7.0
kg/km
3550
4020
4550
5040
5535
6190
7180
8160
9585
8.0
9.0
(B)
Electrical Parameters
500
500
250
250
250
250
250
250
250
mm
990
1043
1103
1155
1200
1260
1343
1425
1530
1.0
ohm/km
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
2.0
ohm/km
0.822
0.568
0.411
0.325
0.265
0.211
0.161
0.130
0.102
3.0
Reactance at 50 Hz (Approximate)
ohm/km
0.143
0.132
0.126
0.121
0.117
0.112
0.107
0.104
0.100
4.0
Impedance at 50 Hz (Approximate)
ohm/km
0.834
0.583
0.430
0.347
0.290
0.239
0.193
0.166
0.143
0.248
37
OCI/PBMVC/REV.001/010410
5.0
v/amp/km
1.445
1.010
0.745
0.601
0.502
0.414
0.334
0.288
6.0
Capacitance at 50 Hz (Approximate)
mF/km
0.14
0.16
0.17
0.19
0.20
0.22
0.24
0.26
0.28
7.0
mA/m
0.79
0.90
0.96
1.07
1.13
1.24
1.36
1.47
1.58
8.0
8.1
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
140
171
203
232
260
294
340
384
438
8.2
122
150
179
205
231
262
305
346
398
8.3
158
196
236
273
309
355
415
475
552
9.0
kA
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
SECTION C - TABLE 10
38
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
3.6/6 (7.2) kV
Three Core Copper Conductor
XLPE Insulated Steel
Wire Armoured To IEC 60502-2
(Suitable for 3.8/6.6 kV Earthed
System)
25
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
665
2.5
1.2
2.0
2.3
1.64
39.5
2960
500
474
6.9
922
2.5
1.2
2.0
2.3
1.64
42.0
3390
500
504
8.1
1242
2.5
1.3
2.5
2.5
1.80
46.0
4400
500
552
9.7
1800
2.5
1.4
2.5
2.6
1.88
50.0
5320
500
600
11.4
2500
2.5
1.4
2.5
2.7
1.96
54.0
6380
500
648
12.9
3152
2.5
1.5
2.5
2.8
2.04
57.0
7380
500
684
14.3
3888
2.5
1.5
2.5
2.9
2.12
60.5
8415
500
726
16.0
4875
2.5
1.6
2.5
3.0
2.20
64.5
9850
500
774
18.4
6410
2.6
1.7
2.5
3.2
2.36
70.5
12045
500
846
20.6
8039
2.8
1.8
3.15
3.5
2.60
78.5
15325
250
942
23.3
10301
3.0
2.0
3.15
3.8
2.84
87.5
18910
250
1050
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.727
0.927
0.119
0.935
1.619
0.27
0.31
0.524
0.668
0.113
0.677
1.173
0.29
0.33
0.387
0.494
0.108
0.506
0.876
0.33
0.37
0.268
0.342
0.100
0.356
0.617
0.38
0.43
0.193
0.247
0.095
0.265
0.459
0.42
0.48
0.153
0.196
0.092
0.217
0.376
0.47
0.53
0.124
0.160
0.090
0.184
0.319
0.51
0.58
0.0991
0.128
0.087
0.155
0.268
0.55
0.62
0.0754
0.099
0.084
0.130
0.225
0.60
0.68
0.0601
0.080
0.083
0.115
0.199
0.62
0.70
0.0470
0.064
0.082
0.104
0.180
0.65
0.74
129
154
181
220
263
298
332
374
431
482
541
112
134
158
194
232
264
296
335
387
435
492
A
kA
143
3.58
172
5.01
205
7.15
253
10.01
307
13.59
352
17.16
397
21.45
453
26.46
529
34.32
599
42.90
683
57.20
ohm/km
ohm/km
kA
1.130
1.435
6.12
1.054
1.339
6.56
0.779
0.989
8.88
0.706
0.897
9.79
0.646
0.820
10.70
0.595
0.756
11.62
0.562
0.714
12.30
0.515
0.654
13.44
0.467
0.593
14.80
0.342
0.434
20.25
0.299
0.380
23.14
SECTION D - TABLE 1
39
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
6/10 (12) kV
Three Core Copper Conductor
XLPE Insulated Steel
Wire Armoured To IEC 60502-2
(Suitable for 6.35/11 kV Earthed
System)
25
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
665
3.4
1.3
2.5
2.4
1.72
45.5
3795
500
546
6.9
922
3.4
1.3
2.5
2.5
1.80
48.0
4305
500
576
8.1
1242
3.4
1.4
2.5
2.6
1.88
51.0
4920
500
612
9.7
1800
3.4
1.4
2.5
2.7
1.96
54.5
5845
500
654
11.4
2500
3.4
1.5
2.5
2.9
2.12
58.5
6955
500
702
12.9
3152
3.4
1.6
2.5
3.0
2.20
62.0
8000
500
744
14.3
3888
3.4
1.6
2.5
3.1
2.28
65.0
9055
500
780
16.0
4875
3.4
1.7
2.5
3.2
2.36
69.5
10525
500
834
18.4
6410
3.4
1.8
3.15
3.4
2.52
76.5
13605
250
918
20.6
8039
3.4
1.9
3.15
3.6
2.68
82.0
15905
250
984
23.3
10301
3.4
2.0
3.15
3.8
2.84
89.0
19235
250
1068
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.727
0.927
0.127
0.936
1.621
0.21
0.40
0.524
0.668
0.121
0.679
1.176
0.23
0.43
0.387
0.494
0.116
0.507
0.878
0.26
0.49
0.268
0.342
0.107
0.358
0.620
0.29
0.55
0.193
0.247
0.102
0.267
0.462
0.33
0.62
0.153
0.196
0.098
0.219
0.379
0.36
0.68
0.124
0.159
0.096
0.186
0.322
0.39
0.74
0.0991
0.128
0.092
0.158
0.274
0.42
0.79
0.0754
0.099
0.089
0.133
0.230
0.48
0.90
0.0601
0.080
0.086
0.117
0.203
0.52
0.98
0.0470
0.064
0.084
0.106
0.184
0.58
1.09
129
154
181
220
263
298
332
374
431
482
541
112
134
158
194
232
264
296
335
387
435
492
A
kA
143
3.58
172
5.01
205
7.15
253
10.01
307
13.59
352
17.16
397
21.45
453
26.46
529
34.32
599
42.90
683
57.20
ohm/km
ohm/km
kA
0.799
1.015
8.66
0.741
0.941
9.34
0.690
0.876
10.02
0.633
0.804
10.93
0.584
0.742
11.84
0.542
0.688
12.75
0.515
0.654
13.44
0.474
0.602
14.58
0.348
0.442
19.89
0.324
0.411
21.33
0.290
0.368
23.87
SECTION D - TABLE 2
40
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
8.7/15 (17.5) kV
Three Core Copper Conductor
XLPE Insulated Steel Wire
Armoured To IEC 60502-2
(Suitable for 8.7/15 kV Earthed
System)
25
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
665
4.5
1.4
2.5
2.6
1.88
51.0
4405
500
612
6.9
922
4.5
1.4
2.5
2.7
1.96
53.0
4890
500
636
8.1
1242
4.5
1.5
2.5
2.8
2.04
56.0
5505
500
672
9.7
1800
4.5
1.5
2.5
2.9
2.12
59.5
6455
500
714
11.4
2500
4.5
1.6
2.5
3.0
2.20
63.5
7635
500
762
12.9
3152
4.5
1.7
2.5
3.1
2.28
67.5
8710
500
810
14.3
3888
4.5
1.7
2.5
3.2
2.36
70.5
9785
500
846
16.0
4875
4.5
1.8
3.15
3.4
2.52
76.0
12135
250
912
18.4
6410
4.5
1.9
3.15
3.6
2.68
82.0
14460
250
984
20.6
8039
4.5
2.0
3.15
3.7
2.76
87.0
16820
250
1044
23.3
10301
4.5
2.1
3.15
4.0
3.00
94.5
20190
250
1134
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.727
0.927
0.136
0.937
1.623
0.17
0.46
0.524
0.668
0.129
0.680
1.178
0.19
0.52
0.387
0.494
0.123
0.509
0.882
0.21
0.57
0.268
0.342
0.114
0.360
0.624
0.24
0.66
0.193
0.247
0.108
0.270
0.468
0.26
0.71
0.153
0.196
0.104
0.222
0.385
0.29
0.79
0.124
0.159
0.101
0.188
0.326
0.31
0.85
0.0991
0.128
0.097
0.161
0.279
0.34
0.93
0.0754
0.098
0.093
0.135
0.234
0.37
1.01
0.0601
0.080
0.091
0.121
0.210
0.41
1.12
0.0470
0.064
0.088
0.109
0.189
0.46
1.26
129
154
181
220
263
298
332
374
431
482
541
112
134
158
194
232
264
296
335
387
435
492
A
kA
143
3.58
172
5.01
205
7.15
253
10.01
307
13.59
352
17.16
397
21.45
453
26.46
529
34.32
599
42.90
683
57.20
ohm/km
ohm/km
kA
0.690
0.876
10.02
0.660
0.838
10.48
0.620
0.787
11.16
0.573
0.728
12.07
0.523
0.664
13.21
0.490
0.622
14.12
0.467
0.593
14.80
0.354
0.450
19.53
0.324
0.411
21.33
0.299
0.380
23.14
0.273
0.347
25.31
SECTION D - TABLE 3
41
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
12/20 (24) kV
Three Core Copper Conductor
XLPE Insulated Steel Wire
Armoured To IEC 60502-2
(Suitable for 12.7/22 kV Earthed
System)
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
6.9
922
5.5
1.5
2.5
2.8
2.04
58.0
5505
500
696
8.1
1242
5.5
1.6
2.5
2.9
2.12
61.0
6165
500
732
9.7
1800
5.5
1.6
2.5
3.1
2.28
65.0
7170
500
780
11.4
2500
5.5
1.7
2.5
3.2
2.36
69.0
8340
500
828
12.9
3152
5.5
1.7
3.15
3.3
2.44
73.5
10285
250
882
14.3
3888
5.5
1.8
3.15
3.4
2.52
77.0
11425
250
924
16.0
4875
5.5
1.9
3.15
3.6
2.68
81.5
13045
250
978
18.4
6410
5.5
2.0
3.15
3.7
2.76
87.0
15375
250
1044
20.6
8039
5.5
2.0
3.15
3.9
2.92
92.0
17715
250
1104
23.3
10301
5.5
2.2
3.15
4.1
3.08
99.5
21090
250
1194
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.524
0.668
0.136
0.682
1.181
0.17
0.64
0.387
0.494
0.130
0.511
0.885
0.18
0.68
0.268
0.342
0.120
0.362
0.627
0.20
0.75
0.193
0.247
0.114
0.272
0.471
0.23
0.87
0.153
0.196
0.110
0.225
0.390
0.25
0.94
0.124
0.159
0.106
0.191
0.331
0.26
0.98
0.0991
0.128
0.102
0.164
0.284
0.29
1.09
0.0754
0.098
0.098
0.139
0.241
0.32
1.21
0.0601
0.079
0.095
0.124
0.215
0.35
1.32
0.0470
0.063
0.092
0.112
0.194
0.38
1.43
154
181
220
263
298
332
374
431
482
541
134
158
194
232
264
296
335
387
435
492
A
kA
172
5.01
205
7.15
253
10.01
307
13.59
352
17.16
397
21.45
453
26.46
529
34.32
599
42.90
683
57.20
ohm/km
ohm/km
kA
0.584
0.742
11.84
0.552
0.701
12.53
0.515
0.654
13.44
0.482
0.612
14.35
0.361
0.458
19.16
0.348
0.442
19.89
0.324
0.411
21.33
0.299
0.380
23.14
0.281
0.357
24.59
0.258
0.328
26.76
SECTION D - TABLE 4
42
OCI/PBMVC/REV.001/010410
8.3
9.0
(ii)
1.0
2.0
3.0
18/30 (36) kV
Three Core Copper Conductor
XLPE Insulated Steel Wire
Armoured To IEC 60502-2
(Suitable for 19/33 kV Earthed
System)
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
8.1
1242
8.0
1.8
3.15
3.4
2.52
75.0
8800
250
900
9.7
1800
8.0
1.8
3.15
3.5
2.60
78.5
9875
250
942
11.4
2500
8.0
1.9
3.15
3.6
2.68
82.5
11150
250
990
12.9
3152
8.0
2.0
3.15
3.7
2.76
86.5
12350
250
1038
14.3
3888
8.0
2.0
3.15
3.8
2.84
89.5
13575
250
1074
16.0
4875
8.0
2.1
3.15
4.0
3.00
94.0
15210
250
1128
18.4
6410
8.0
2.2
3.15
4.1
3.08
99.0
17595
250
1188
20.6
8039
8.0
2.3
3.15
4.3
3.24
104.5
20130
250
1254
23.3
10301
8.0
2.4
3.15
4.5
3.40
112.0
23630
250
1344
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.387
0.494
0.143
0.514
0.890
0.14
0.79
0.268
0.342
0.132
0.367
0.636
0.16
0.90
0.193
0.247
0.126
0.277
0.480
0.17
0.96
0.153
0.196
0.121
0.230
0.398
0.19
1.07
0.124
0.159
0.117
0.197
0.341
0.20
1.13
0.0991
0.128
0.112
0.170
0.294
0.22
1.24
0.0754
0.098
0.107
0.145
0.251
0.24
1.36
0.0601
0.079
0.104
0.131
0.227
0.26
1.47
0.0470
0.063
0.100
0.118
0.204
0.28
1.58
181
220
263
298
332
374
431
482
541
158
194
232
264
296
335
387
435
492
A
kA
205
7.15
253
10.01
307
13.59
352
17.16
397
21.45
453
26.46
529
34.32
599
42.90
683
57.20
ohm/km
ohm/km
kA
0.354
0.450
19.53
0.336
0.427
20.61
0.319
0.405
21.70
0.304
0.386
22.78
0.290
0.368
23.87
0.277
0.352
24.95
0.258
0.328
26.76
0.242
0.307
28.57
0.225
0.286
30.74
SECTION D - TABLE 5
43
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
ALUMINIUM CONDUCTOR
Nominal Area of Conductor
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Separation sheath thickness (Nominal)
Armour wire diameter (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
Conductor
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo=3.6 kV and f = 50 Hz
Sustained current ratings:Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
Drawn into earthenware ducts, ground temp. = 20 C and Thermal resistivity of
soil = 1.5 C m/W, depth of laying = 0.8 m, laid singly
Laid singly in air, ambient temp. = 30 C
Short circuit current rating of conductor for 1 second
Armour
DC resistance at 20 C (Approximate)
AC resistance at 80 C (Approximate)
Short circuit current rating of armour for 1 second (Approximate)
3.6/6 (7.2) kV
Three Core Aluminium Conductor
XLPE Insulated Steel Wire
Armoured To IEC 60502-2
(Suitable for 3.8/6.6 kV Earthed
System)
mm2
25
35
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
203
2.5
1.2
2.0
2.3
1.64
39.5
2500
500
474
6.9
280
2.5
1.2
2.0
2.3
1.64
42.0
2745
500
504
8.1
381
2.5
1.3
2.5
2.5
1.80
46.0
3535
500
552
9.7
553
2.5
1.4
2.5
2.6
1.88
50.0
4075
500
600
11.4
764
2.5
1.4
2.5
2.7
1.96
54.0
4645
500
648
12.9
965
2.5
1.5
2.5
2.8
2.04
57.0
5195
500
684
14.3
1186
2.5
1.5
2.5
2.9
2.12
60.5
5710
500
726
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
1.20
1.539
0.119
1.544
2.674
0.27
0.31
0.868
1.113
0.113
1.119
1.938
0.29
0.33
0.641
0.822
0.108
0.829
1.436
0.33
0.37
0.443
0.568
0.100
0.577
0.999
0.38
0.43
0.320
0.411
0.095
0.422
0.731
0.42
0.48
0.253
0.325
0.092
0.338
0.585
0.47
0.53
100
119
140
171
204
232
240
300
400
16.0
1500
2.5
1.6
2.5
3.0
2.20
64.5
6475
500
774
18.4
1967
2.6
1.7
2.5
3.2
2.36
70.5
7605
500
846
20.6
2445
2.8
1.8
3.15
3.5
2.60
78.5
9730
250
942
23.3
3126
3.0
2.0
3.15
3.8
2.84
87.5
11735
250
1050
0.206
0.265
0.090
0.280
0.485
0.51
0.58
0.164
0.211
0.087
0.228
0.395
0.55
0.62
0.125
0.162
0.084
0.182
0.315
0.60
0.68
0.100
0.130
0.083
0.154
0.267
0.62
0.70
0.0778
0.102
0.082
0.131
0.227
0.65
0.74
259
293
338
380
432
87
104
123
150
180
206
231
262
304
343
393
A
kA
111
2.35
133
3.29
159
4.70
196
6.58
238
8.93
274
11.28
309
14.10
354
17.39
415
22.56
472
28.20
545
37.60
ohm/km
ohm/km
kA
1.130
1.435
6.12
1.054
1.339
6.56
0.779
0.989
8.88
0.706
0.897
9.79
0.646
0.820
10.70
0.595
0.756
11.62
0.562
0.714
12.30
0.515
0.654
13.44
0.467
0.593
14.80
0.342
0.434
20.25
0.299
0.380
23.14
SECTION D - TABLE 6
44
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
6/10 (12) kV
Three Core Aluminium Conductor
XLPE Insulated Steel Wire
Armoured To IEC 60502-2
(Suitable for 6.35/11 kV Earthed
System)
25
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
203
3.4
1.3
2.5
2.4
1.72
45.5
3335
500
546
6.9
280
3.4
1.3
2.5
2.5
1.80
48.0
3660
500
576
8.1
381
3.4
1.4
2.5
2.6
1.88
51.0
4060
500
612
9.7
553
3.4
1.4
2.5
2.7
1.96
54.5
4600
500
654
11.4
764
3.4
1.5
2.5
2.9
2.12
58.5
5220
500
702
12.9
965
3.4
1.6
2.5
3.0
2.20
62.0
5815
500
744
14.3
1186
3.4
1.6
2.5
3.1
2.28
65.0
6355
500
780
16.0
1500
3.4
1.7
2.5
3.2
2.36
69.5
7145
500
834
18.4
1967
3.4
1.8
3.15
3.4
2.52
76.5
9160
250
918
20.6
2445
3.4
1.9
3.15
3.6
2.68
82.0
10310
250
984
23.3
3126
3.4
2.0
3.15
3.8
2.84
89.0
12060
250
1068
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
1.20
1.539
0.127
1.544
2.674
0.21
0.40
0.868
1.113
0.121
1.120
1.940
0.23
0.43
0.641
0.822
0.116
0.830
1.438
0.26
0.49
0.443
0.568
0.107
0.578
1.001
0.29
0.55
0.320
0.411
0.102
0.423
0.733
0.33
0.62
0.253
0.325
0.098
0.339
0.587
0.36
0.68
0.206
0.265
0.096
0.282
0.488
0.39
0.74
0.164
0.211
0.092
0.230
0.398
0.42
0.79
0.125
0.162
0.089
0.185
0.320
0.48
0.90
0.100
0.130
0.086
0.156
0.270
0.52
0.98
0.0778
0.102
0.084
0.132
0.229
0.58
1.09
100
119
140
171
204
232
259
293
338
380
432
87
104
123
150
180
206
231
262
304
343
393
A
kA
111
2.35
133
3.29
159
4.70
196
6.58
238
8.93
274
11.28
309
14.10
354
17.39
415
22.56
472
28.20
545
37.60
ohm/km
ohm/km
kA
0.799
1.015
8.66
0.741
0.941
9.34
0.690
0.876
10.02
0.633
0.804
10.93
0.584
0.742
11.84
0.542
0.688
12.75
0.515
0.654
13.44
0.474
0.602
14.58
0.348
0.442
19.89
0.324
0.411
21.33
0.290
0.368
23.87
SECTION D - TABLE 7
8.7/15 (17.5) kV
Three Core Aluminium Conductor
XLPE Insulated Steel Wire
Armoured To IEC 60502-2
(Suitable for 8.7/15 kV Earthed
System)
45
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
25
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
203
4.5
1.4
2.5
2.6
1.88
51.0
3945
500
612
6.9
280
4.5
1.4
2.5
2.7
1.96
53.0
4250
500
636
8.1
381
4.5
1.5
2.5
2.8
2.04
56.0
4645
500
672
9.7
553
4.5
1.5
2.5
2.9
2.12
59.5
5210
500
714
11.4
764
4.5
1.6
2.5
3.0
2.20
63.5
5900
500
762
12.9
965
4.5
1.7
2.5
3.1
2.28
67.5
6520
500
810
14.3
1186
4.5
1.7
2.5
3.2
2.36
70.5
7080
500
846
16.0
1500
4.5
1.8
3.15
3.4
2.52
76.0
8755
250
912
18.4
1967
4.5
1.9
3.15
3.6
2.68
82.0
10015
250
984
20.6
2445
4.5
2.0
3.15
3.7
2.76
87.0
11230
250
1044
23.3
3126
4.5
2.1
3.15
4.0
3.00
94.5
13010
250
1134
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
1.20
1.539
0.136
1.545
2.676
0.17
0.46
0.868
1.113
0.129
1.120
1.940
0.19
0.52
0.641
0.822
0.123
0.831
1.439
0.21
0.57
0.443
0.568
0.114
0.579
1.003
0.24
0.66
0.320
0.411
0.108
0.425
0.736
0.26
0.71
0.253
0.325
0.104
0.341
0.591
0.29
0.79
0.206
0.265
0.101
0.284
0.492
0.31
0.85
0.164
0.211
0.097
0.232
0.402
0.34
0.93
0.125
0.162
0.093
0.187
0.324
0.37
1.01
0.100
0.130
0.091
0.159
0.275
0.41
1.12
0.0778
0.102
0.088
0.135
0.234
0.46
1.26
100
119
140
171
204
232
259
293
338
380
432
87
104
123
150
180
206
231
262
304
343
393
A
kA
111
2.35
133
3.29
159
4.70
196
6.58
238
8.93
274
11.28
309
14.10
354
17.39
415
22.56
472
28.20
545
37.60
ohm/km
ohm/km
kA
0.690
0.876
10.02
0.660
0.838
10.48
0.620
0.787
11.16
0.573
0.728
12.07
0.523
0.664
13.21
0.490
0.622
14.12
0.467
0.593
14.80
0.354
0.450
19.53
0.324
0.411
21.33
0.299
0.380
23.14
0.273
0.347
25.31
SECTION D - TABLE 8
46
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
ALUMINIUM CONDUCTOR
Nominal Area of Conductor
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Separation sheath thickness (Nominal)
Armour wire diameter (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
Conductor
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo=12 kV and f = 50 Hz
Sustained current ratings:Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
Drawn into earthenware ducts, ground temp. = 20 C and Thermal resistivity of
soil = 1.5 C m/W, depth of laying = 0.8 m, laid singly
Laid singly in air, ambient temp. = 30 C
Short circuit current rating of conductor for 1 second
Armour
DC resistance at 20 C (Approximate)
AC resistance at 80 C (Approximate)
Short circuit current rating of armour for 1 second (Approximate)
12/20 (24) kV
Three Core Aluminium Conductor
XLPE Insulated Steel Wire
Armoured To IEC 60502-2
(Suitable for 12.7/22 kV Earthed
System)
mm2
35
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
6.9
280
5.5
1.5
2.5
2.8
2.04
58.0
4865
500
696
8.1
381
5.5
1.6
2.5
2.9
2.12
61.0
5305
500
732
9.7
553
5.5
1.6
2.5
3.1
2.28
65.0
5925
500
780
11.4
764
5.5
1.7
2.5
3.2
2.36
69.0
6605
500
828
12.9
965
5.5
1.7
3.15
3.3
2.44
73.5
8100
250
882
14.3
1186
5.5
1.8
3.15
3.4
2.52
77.0
8725
250
924
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.868
1.113
0.136
1.121
1.942
0.17
0.64
0.641
0.822
0.130
0.832
1.441
0.18
0.68
0.443
0.568
0.120
0.581
1.006
0.20
0.75
0.320
0.411
0.114
0.427
0.740
0.23
0.87
0.253
0.325
0.110
0.343
0.594
0.25
0.94
119
140
171
204
104
123
150
A
kA
133
3.29
159
4.70
196
6.58
ohm/km
ohm/km
kA
0.584
0.742
11.84
0.552
0.701
12.53
0.515
0.654
13.44
SECTION D - TABLE 9
240
300
400
16.0
1500
5.5
1.9
3.15
3.6
2.68
81.5
9670
250
978
18.4
1967
5.5
2.0
3.15
3.7
2.76
87.0
10935
250
1044
20.6
2445
5.5
2.0
3.15
3.9
2.92
92.0
12125
250
1104
23.3
3126
5.5
2.2
3.15
4.1
3.08
99.5
13915
250
1194
0.206
0.265
0.106
0.285
0.494
0.26
0.98
0.164
0.211
0.102
0.234
0.405
0.29
1.09
0.125
0.162
0.098
0.189
0.327
0.32
1.21
0.100
0.130
0.095
0.161
0.279
0.35
1.32
0.0778
0.102
0.092
0.137
0.237
0.38
1.43
232
259
293
338
380
432
180
206
231
262
304
343
393
238
8.93
274
11.28
309
14.10
354
17.39
415
22.56
472
28.20
545
37.60
0.482
0.612
14.35
0.361
0.458
19.16
0.348
0.442
19.89
0.324
0.411
21.33
0.299
0.380
23.14
0.281
0.357
24.59
0.258
0.328
26.76
47
OCI/PBMVC/REV.001/010410
8.3
9.0
( ii )
1.0
2.0
3.0
ALUMINIUM CONDUCTOR
Nominal Area of Conductor
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Separation sheath thickness (Nominal)
Armour wire diameter (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
Conductor
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo=18 kV and f = 50 Hz
Sustained current ratings:Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
Drawn into earthenware ducts, ground temp. = 20 C and Thermal resistivity of
soil = 1.5 C m/W, depth of laying = 0.8 m, laid singly
Laid singly in air, ambient temp. = 30 C
Short circuit current rating of conductor for 1 second
Armour
DC resistance at 20 C (Approximate)
AC resistance at 80 C (Approximate)
Short circuit current rating of armour for 1 second (Approximate)
18/30 (36) kV
Three Core Aluminium Conductor
XLPE Insulated Steel Wire
Armoured To IEC 60502-2
(Suitable for 19/33 kV Earthed
System)
mm2
50
70
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
8.1
381
8.0
1.8
3.15
3.4
2.52
75.0
7940
250
900
9.7
553
8.0
1.8
3.15
3.5
2.60
78.5
8625
250
942
11.4
764
8.0
1.9
3.15
3.6
2.68
82.5
9415
250
990
12.9
965
8.0
2.0
3.15
3.7
2.76
86.5
10165
250
1038
14.3
1186
8.0
2.0
3.15
3.8
2.84
89.5
10875
250
1074
16.0
1500
8.0
2.1
3.15
4.0
3.00
94.0
11835
250
1128
18.4
1967
8.0
2.2
3.15
4.1
3.08
99.0
13150
250
1188
20.6
2445
8.0
2.3
3.15
4.3
3.24
104.5
14535
250
1254
23.3
3126
8.0
2.4
3.15
4.5
3.40
112.0
16455
250
1344
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.641
0.822
0.143
0.834
1.445
0.14
0.79
0.443
0.568
0.132
0.583
1.010
0.16
0.90
0.320
0.411
0.126
0.430
0.745
0.17
0.96
0.253
0.325
0.121
0.347
0.601
0.19
1.07
0.206
0.265
0.117
0.290
0.502
0.20
1.13
0.164
0.211
0.112
0.239
0.414
0.22
1.24
0.125
0.161
0.107
0.193
0.334
0.24
1.36
0.100
0.130
0.104
0.166
0.288
0.26
1.47
0.0778
0.102
0.100
0.143
0.248
0.28
1.58
140
171
204
232
259
293
338
380
432
123
150
180
206
231
262
304
343
393
A
kA
159
4.70
196
6.58
238
8.93
274
11.28
309
14.10
354
17.39
415
22.56
472
28.20
545
37.60
ohm/km
ohm/km
kA
0.354
0.450
19.53
0.336
0.427
20.61
0.319
0.405
21.70
0.304
0.386
22.78
0.290
0.368
23.87
0.277
0.352
24.95
0.258
0.328
26.76
0.242
0.307
28.57
0.225
0.286
30.74
SECTION D - TABLE 10
400
48
3.6/6 (7.2) kV
Three Core Copper Conductor
XLPE Insulated
Double Steel Tape Armoured
To IEC 60502-2
(Suitable for 3.8/6.6 kV Earthed
System)
3 CORE, 2XCETgY, Double Steel Taped Armoured Cables 3.6/6 kV to IEC 60502-2
OCI/PBMVC/REV.001/010410
mm2
25
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
665
2.5
1.2
0.5
2.2
1.56
37.5
2215
1000
563
6.9
922
2.5
1.2
0.5
2.3
1.64
40.0
2615
500
600
8.1
1242
2.5
1.3
0.5
2.4
1.72
43.0
3130
500
645
9.7
1800
2.5
1.4
0.5
2.5
1.80
46.5
3940
500
698
11.4
2500
2.5
1.4
0.5
2.6
1.88
50.5
4895
500
758
12.9
3152
2.5
1.5
0.5
2.7
1.96
54.0
5805
500
810
14.3
3888
2.5
1.5
0.5
2.8
2.04
57.0
6735
500
855
16.0
4875
2.5
1.6
0.5
2.9
2.12
61.0
8025
500
915
18.4
6410
2.6
1.7
0.5
3.1
2.28
67.5
10060
500
1013
20.6
8039
2.8
1.8
0.5
3.3
2.44
73.5
12235
250
1103
23.3
10301
3.0
2.0
0.8
3.6
2.68
84.0
16240
250
1260
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.727
0.927
0.119
0.935
1.619
0.27
0.31
0.524
0.668
0.113
0.677
1.173
0.29
0.33
0.387
0.494
0.108
0.506
0.876
0.33
0.37
0.268
0.342
0.100
0.356
0.617
0.38
0.43
0.193
0.247
0.095
0.265
0.459
0.42
0.48
0.153
0.196
0.092
0.217
0.376
0.47
0.53
0.124
0.160
0.090
0.184
0.319
0.51
0.58
0.0991
0.128
0.087
0.155
0.268
0.55
0.62
0.0754
0.099
0.084
0.130
0.225
0.60
0.68
0.0601
0.080
0.083
0.115
0.199
0.62
0.70
0.0470
0.064
0.082
0.104
0.180
0.65
0.74
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
129
154
181
220
263
298
332
374
431
482
541
8.2
112
134
158
194
232
264
296
335
387
435
492
8.3
9.0
A
kA
143
3.58
172
5.01
205
7.15
253
10.01
307
13.59
352
17.16
397
21.45
453
26.46
529
34.32
599
42.90
683
57.20
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Separation sheath thickness (Nominal)
Steel tape thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo=3.6 kV and f= 50 Hz
Sustained current ratings:-
8.1
SECTION E - TABLE 1
6/10 (12) kV
Three Core Copper Conductor
XLPE Insulated
Double Steel Tape Armoured
To IEC 60502-2
(Suitable for 6.35/11 kV Earthed
System)
3 CORE, 2XCETgY, Double Steel Taped Armoured Cables 6/10 kV to IEC 60502-2
49
OCI/PBMVC/REV.001/010410
mm2
25
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
665
3.4
1.3
0.5
2.3
1.64
42.0
2565
500
630
6.9
922
3.4
1.3
0.5
2.4
1.72
44.5
2980
500
668
8.1
1242
3.4
1.4
0.5
2.5
1.80
47.5
3515
500
713
9.7
1800
3.4
1.4
0.5
2.6
1.88
51.0
4325
500
765
11.4
2500
3.4
1.5
0.5
2.7
1.96
55.5
5330
500
833
12.9
3152
3.4
1.6
0.5
2.9
2.12
59.0
6265
500
885
14.3
3888
3.4
1.6
0.5
3.0
2.20
62.0
7240
500
930
16.0
4875
3.4
1.7
0.5
3.1
2.28
66.0
8560
500
990
18.4
6410
3.4
1.8
0.5
3.3
2.44
72.0
10590
500
1080
20.6
8039
3.4
1.9
0.5
3.4
2.52
77.0
12660
250
1155
23.3
10301
3.4
2.0
0.8
3.7
2.76
86.0
16520
250
1290
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.727
0.927
0.127
0.936
1.621
0.21
0.40
0.524
0.668
0.121
0.679
1.176
0.23
0.43
0.387
0.494
0.116
0.507
0.878
0.26
0.49
0.268
0.342
0.107
0.358
0.620
0.29
0.55
0.193
0.247
0.102
0.267
0.462
0.33
0.62
0.153
0.196
0.098
0.219
0.379
0.36
0.68
0.124
0.159
0.096
0.186
0.322
0.39
0.74
0.0991
0.128
0.092
0.158
0.274
0.42
0.79
0.0754
0.099
0.089
0.133
0.230
0.48
0.90
0.0601
0.080
0.086
0.117
0.203
0.52
0.98
0.0470
0.064
0.084
0.106
0.184
0.58
1.09
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m /W,
depth of laying = 0.8 m laid singly
129
154
181
220
263
298
332
374
431
482
541
8.2
112
134
158
194
232
264
296
335
387
435
492
8.3
9.0
A
kA
143
3.58
172
5.01
205
7.15
253
10.01
307
13.59
352
17.16
397
21.45
453
26.46
529
34.32
599
42.90
683
57.20
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Separation sheath thickness (Nominal)
Steel tape thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo =6 kV and f= 50 Hz
Sustained current ratings:-
8.1
SECTION E - TABLE 2
50
8.7/15 (17.5) kV
Three Core Copper Conductor
XLPE Insulated
Double Steel Tape Armoured
To IEC 60502-2
(Suitable for 8.7/15 kV Earthed
System)
3 CORE, 2XCETgY, Double Steel Taped Armoured Cables 8.7/15 kV to IEC 60502-2
OCI/PBMVC/REV.001/010410
mm2
25
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
665
4.5
1.4
0.5
2.5
1.80
47.5
3000
500
713
6.9
922
4.5
1.4
0.5
2.6
1.88
50.0
3435
500
750
8.1
1242
4.5
1.5
0.5
2.7
1.96
53.0
3990
500
795
9.7
1800
4.5
1.5
0.5
2.8
2.04
56.5
4805
500
848
11.4
2500
4.5
1.6
0.5
2.9
2.12
60.5
5835
500
908
12.9
3152
4.5
1.7
0.5
3.0
2.20
64.0
6800
500
960
14.3
3888
4.5
1.7
0.5
3.1
2.28
67.0
7795
500
1005
16.0
4875
4.5
1.8
0.5
3.3
2.44
71.5
9175
500
1073
18.4
6410
4.5
1.9
0.5
3.4
2.52
77.0
11215
250
1155
20.6
8039
4.5
2.0
0.8
3.6
2.68
83.5
14185
250
1253
23.3
10301
4.5
2.1
0.8
3.9
2.92
91.0
17330
250
1365
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.727
0.927
0.136
0.937
1.623
0.17
0.46
0.524
0.668
0.129
0.680
1.178
0.19
0.52
0.387
0.494
0.123
0.509
0.882
0.21
0.57
0.268
0.342
0.114
0.360
0.624
0.24
0.66
0.193
0.247
0.108
0.270
0.468
0.26
0.71
0.153
0.196
0.104
0.222
0.385
0.29
0.79
0.124
0.159
0.101
0.188
0.326
0.31
0.85
0.0991
0.128
0.097
0.161
0.279
0.34
0.93
0.0754
0.098
0.093
0.135
0.234
0.37
1.01
0.0601
0.080
0.091
0.121
0.210
0.41
1.12
0.0470
0.064
0.088
0.109
0.189
0.46
1.26
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
129
154
181
220
263
298
332
374
431
482
541
8.2
112
134
158
194
232
264
296
335
387
435
492
8.3
9.0
A
kA
143
3.58
172
5.01
205
7.15
253
10.01
307
13.59
352
17.16
397
21.45
453
26.46
529
34.32
599
42.90
683
57.20
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Separation sheath thickness (Nominal)
Steel tape thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo=8.7 kV and f= 50 Hz
Sustained current ratings:-
8.1
SECTION E - TABLE 3
12/20 (24) kV
Three Core Copper Conductor
XLPE Insulated
Double Steel Tape Armoured
To IEC 60502-2
(Suitable for 12.7/22 kV Earthed
System)
3 CORE, 2XCETgY, Double Steel Taped Armoured Cables 12/20 kV to IEC 60502-2
51
OCI/PBMVC/REV.001/010410
mm2
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
6.9
922
5.5
1.5
0.5
2.7
1.96
55.0
3905
500
825
8.1
1242
5.5
1.6
0.5
2.8
2.04
58.0
4460
500
870
9.7
1800
5.5
1.6
0.5
2.9
2.12
61.5
5320
500
923
11.4
2500
5.5
1.7
0.5
3.1
2.28
66.0
6410
500
990
12.9
3152
5.5
1.7
0.5
3.2
2.36
69.0
7365
500
1035
14.3
3888
5.5
1.8
0.5
3.3
2.44
72.5
8420
500
1088
16.0
4875
5.5
1.9
0.5
3.4
2.52
76.5
9800
250
1148
18.4
6410
5.5
2.0
0.8
3.6
2.68
83.5
12740
250
1253
20.6
8039
5.5
2.0
0.8
3.8
2.84
89.0
14935
250
1335
23.3
10301
5.5
2.2
0.8
4.0
3.00
96.5
18140
250
1448
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.524
0.668
0.136
0.682
1.181
0.17
0.64
0.387
0.494
0.130
0.511
0.885
0.18
0.68
0.268
0.342
0.120
0.362
0.627
0.20
0.75
0.193
0.247
0.114
0.272
0.471
0.23
0.87
0.153
0.196
0.110
0.225
0.390
0.25
0.94
0.124
0.159
0.106
0.191
0.331
0.26
0.98
0.0991
0.128
0.102
0.164
0.284
0.29
1.09
0.0754
0.098
0.098
0.139
0.241
0.32
1.21
0.0601
0.079
0.095
0.124
0.215
0.35
1.32
0.0470
0.063
0.092
0.112
0.194
0.38
1.43
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W, depth of laying =
0.8 m laid singly
154
181
220
263
298
332
374
431
482
541
8.2
134
158
194
232
264
296
335
387
435
492
8.3
9.0
A
kA
172
5.01
205
7.15
253
10.01
307
13.59
352
17.16
397
21.45
453
26.46
529
34.32
599
42.90
683
57.20
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Separation sheath thickness (Nominal)
Steel tape thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo=12 kV and f= 50 Hz
Sustained current ratings:-
8.1
SECTION E - TABLE 4
52
18/30 (36) kV
Three Core Copper Conductor
XLPE Insulated
Double Steel Tape Armoured
To IEC 60502-2
(Suitable for 19/33 kV Earthed
System)
3 CORE, 2XCETgY, Double Steel Taped Armoured Cables 18/30 kV to IEC 60502-2
OCI/PBMVC/REV.001/010410
mm2
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
8.1
1242
8.0
1.8
0.5
3.2
2.36
70.5
5800
500
1058
9.7
1800
8.0
1.8
0.5
3.3
2.44
74.0
6725
250
1110
11.4
2500
8.0
1.9
0.5
3.5
2.60
78.0
7895
250
1170
12.9
3152
8.0
2.0
0.8
3.6
2.68
83.0
9760
250
1245
14.3
3888
8.0
2.0
0.8
3.7
2.76
86.0
10865
250
1290
16.0
4875
8.0
2.1
0.8
3.9
2.92
90.5
12400
250
1358
18.4
6410
8.0
2.2
0.8
4.0
3.00
96.0
14640
250
1440
20.6
8039
8.0
2.3
0.8
4.2
3.16
101.5
16930
250
1523
23.3
10301
8.0
2.4
0.8
4.4
3.32
108.5
20210
250
1628
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.387
0.494
0.143
0.514
0.890
0.14
0.79
0.268
0.342
0.132
0.367
0.636
0.16
0.90
0.193
0.247
0.126
0.277
0.480
0.17
0.96
0.153
0.196
0.121
0.230
0.398
0.19
1.07
0.124
0.159
0.117
0.197
0.341
0.20
1.13
0.0991
0.128
0.112
0.170
0.294
0.22
1.24
0.0754
0.098
0.107
0.145
0.251
0.24
1.36
0.0601
0.079
0.104
0.131
0.227
0.26
1.47
0.0470
0.063
0.100
0.118
0.204
0.28
1.58
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
181
220
263
298
332
374
431
482
541
8.2
158
194
232
264
296
335
387
435
492
8.3
9.0
A
kA
205
7.15
253
10.01
307
13.59
352
17.16
397
21.45
453
26.46
529
34.32
599
42.90
683
57.20
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Separation sheath thickness (Nominal)
Steel tape thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo=18 kV and f= 50 Hz
Sustained current ratings:-
8.1
SECTION E - TABLE 5
3.6/6 (7.2) kV
Three Core Aluminium Conductor
XLPE Insulated
Double Steel Tape Armoured
To IEC 60502-2
(Suitable for 3.8/6.6 kV Earthed
System)
3 CORE, A2XCETgY, Double Steel Taped Armoured Cables 3.6/6 kV to IEC 60502-2
53
OCI/PBMVC/REV.001/010410
mm2
25
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
203
2.5
1.2
0.5
2.2
1.56
37.5
1755
1000
563
6.9
280
2.5
1.2
0.5
2.3
1.64
40.0
1975
500
600
8.1
381
2.5
1.3
0.5
2.4
1.72
43.0
2270
500
645
9.7
553
2.5
1.4
0.5
2.5
1.80
46.5
2695
500
698
11.4
764
2.5
1.4
0.5
2.6
1.88
50.5
3160
500
758
12.9
965
2.5
1.5
0.5
2.7
1.96
54.0
3620
500
810
14.3
1186
2.5
1.5
0.5
2.8
2.04
57.0
4030
500
855
16.0
1500
2.5
1.6
0.5
2.9
2.12
61.0
4650
500
915
18.4
1967
2.6
1.7
0.5
3.1
2.28
67.5
5620
500
1013
20.6
2445
2.8
1.8
0.5
3.3
2.44
73.5
6640
250
1103
23.3
3126
3.0
2.0
0.8
3.6
2.68
84.0
9060
250
1260
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
1.20
1.539
0.119
1.544
2.674
0.27
0.31
0.868
1.113
0.113
1.119
1.938
0.29
0.33
0.641
0.822
0.108
0.829
1.436
0.33
0.37
0.443
0.568
0.100
0.577
0.999
0.38
0.43
0.320
0.411
0.095
0.422
0.731
0.42
0.48
0.253
0.325
0.092
0.338
0.585
0.47
0.53
0.206
0.265
0.090
0.280
0.485
0.51
0.58
0.164
0.211
0.087
0.228
0.395
0.55
0.62
0.125
0.162
0.084
0.182
0.315
0.60
0.68
0.100
0.130
0.083
0.154
0.267
0.62
0.70
0.0778
0.102
0.082
0.131
0.227
0.65
0.74
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
100
119
140
171
204
232
259
293
338
380
432
8.2
87
104
123
150
180
206
231
262
304
343
393
8.3
9.0
A
kA
111
2.35
133
3.29
159
4.70
196
6.58
238
8.93
274
11.28
309
14.10
354
17.39
415
22.56
472
28.20
545
37.60
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Separation sheath thickness (Nominal)
Steel tape thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo=3.6 kV and f= 50 Hz
Sustained current ratings:-
8.1
SECTION E - TABLE 6
54
6/10 (12) kV
Three Core Aluminium Conductor
XLPE Insulated
Double Steel Tape Armoured
To IEC 60502-2
(Suitable for 6.35/11 kV Earthed
System)
3 CORE, A2XCETgY, Double Steel Taped Armoured Cables 6/10 kV to IEC 60502-2
mm2
25
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
203
3.4
1.3
0.5
2.3
1.64
42.0
2100
500
630
6.9
280
3.4
1.3
0.5
2.4
1.72
44.5
2335
500
668
8.1
381
3.4
1.4
0.5
2.5
1.80
47.5
2650
500
713
9.7
553
3.4
1.4
0.5
2.6
1.88
51.0
3080
500
765
11.4
764
3.4
1.5
0.5
2.7
1.96
55.5
3595
500
833
12.9
965
3.4
1.6
0.5
2.9
2.12
59.0
4080
500
885
14.3
1186
3.4
1.6
0.5
3.0
2.20
62.0
4535
500
930
16.0
1500
3.4
1.7
0.5
3.1
2.28
66.0
5180
500
990
18.4
1967
3.4
1.8
0.5
3.3
2.44
72.0
6145
500
1080
20.6
2445
3.4
1.9
0.5
3.4
2.52
77.0
7070
250
1155
23.3
3126
3.4
2.0
0.8
3.7
2.76
86.0
9340
250
1290
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
1.20
1.539
0.127
1.544
2.674
0.21
0.40
0.868
1.113
0.121
1.120
1.940
0.23
0.43
0.641
0.822
0.116
0.830
1.438
0.26
0.49
0.443
0.568
0.107
0.578
1.001
0.29
0.55
0.320
0.411
0.102
0.423
0.733
0.33
0.62
0.253
0.325
0.098
0.339
0.587
0.36
0.68
0.206
0.265
0.096
0.282
0.488
0.39
0.74
0.164
0.211
0.092
0.230
0.398
0.42
0.79
0.125
0.162
0.089
0.185
0.320
0.48
0.90
0.100
0.130
0.086
0.156
0.270
0.52
0.98
0.0778
0.102
0.084
0.132
0.229
0.58
1.09
OCI/PBMVC/REV.001/010410
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Separation sheath thickness (Nominal)
Steel tape thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo =6 kV and f= 50 Hz
Sustained current ratings:-
8.1
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
100
119
140
171
204
232
259
293
338
380
432
8.2
87
104
123
150
180
206
231
262
304
343
393
8.3
9.0
A
kA
111
2.35
133
3.29
159
4.70
196
6.58
238
8.93
274
11.28
309
14.10
354
17.39
415
22.56
472
28.20
545
37.60
SECTION E - TABLE 7
8.7/15 (17.5) kV
Three Core Aluminium Conductor
XLPE Insulated
Double Steel Tape Armoured
To IEC 60502-2
(Suitable for 8.7/15 kV Earthed
System)
3 CORE, A2XCETgY, Double Steel Taped Armoured Cables 8.7/15 kV to IEC 60502-2
55
OCI/PBMVC/REV.001/010410
mm2
25
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
5.9
203
4.5
1.4
0.5
2.5
1.80
47.5
2540
500
713
6.9
280
4.5
1.4
0.5
2.6
1.88
50.0
2790
500
750
8.1
381
4.5
1.5
0.5
2.7
1.96
53.0
3130
500
795
9.7
553
4.5
1.5
0.5
2.8
2.04
56.5
3555
500
848
11.4
764
4.5
1.6
0.5
2.9
2.12
60.5
4100
500
908
12.9
965
4.5
1.7
0.5
3.0
2.20
64.0
4610
500
960
14.3
1186
4.5
1.7
0.5
3.1
2.28
67.0
5090
500
1005
16.0
1500
4.5
1.8
0.5
3.3
2.44
71.5
5800
500
1073
18.4
1967
4.5
1.9
0.5
3.4
2.52
77.0
6775
250
1155
20.6
2445
4.5
2.0
0.8
3.6
2.68
83.5
8590
250
1253
23.3
3126
4.5
2.1
0.8
3.9
2.92
91.0
10155
250
1365
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
1.20
1.539
0.136
1.545
2.676
0.17
0.46
0.868
1.113
0.129
1.120
1.940
0.19
0.52
0.641
0.822
0.123
0.831
1.439
0.21
0.57
0.443
0.568
0.114
0.579
1.003
0.24
0.66
0.320
0.411
0.108
0.425
0.736
0.26
0.71
0.253
0.325
0.104
0.341
0.591
0.29
0.79
0.206
0.265
0.101
0.284
0.492
0.31
0.85
0.164
0.211
0.097
0.232
0.402
0.34
0.93
0.125
0.162
0.093
0.187
0.324
0.37
1.01
0.100
0.130
0.091
0.159
0.275
0.41
1.12
0.0778
0.102
0.088
0.135
0.234
0.46
1.26
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
100
119
140
171
204
232
259
293
338
380
432
8.2
87
104
123
150
180
206
231
262
304
343
393
8.3
9.0
A
kA
111
2.35
133
3.29
159
4.70
196
6.58
238
8.93
274
11.28
309
14.10
354
17.39
415
22.56
472
28.20
545
37.60
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Separation sheath thickness (Nominal)
Steel tape thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo=8.7 kV and f= 50 Hz
Sustained current ratings:-
8.1
SECTION E - TABLE 8
56
12/20 (24) kV
Three Core Aluminium Conductor
XLPE Insulated
Double Steel Tape Armoured
To IEC 60502-2
(Suitable for 12.7/22 kV Earthed
System)
3 CORE, A2XCETgY, Double Steel Taped Armoured Cables 12/20 kV to IEC 60502-2
OCI/PBMVC/REV.001/010410
mm2
35
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
6.9
280
5.5
1.5
0.5
2.7
1.96
55.0
3260
500
825
8.1
381
5.5
1.6
0.5
2.8
2.04
58.0
3595
500
870
9.7
553
5.5
1.6
0.5
2.9
2.12
61.5
4075
500
923
11.4
764
5.5
1.7
0.5
3.1
2.28
66.0
4675
500
990
12.9
965
5.5
1.7
0.5
3.2
2.36
69.0
5180
500
1035
14.3
1186
5.5
1.8
0.5
3.3
2.44
72.5
5720
500
1088
16.0
1500
5.5
1.9
0.5
3.4
2.52
76.5
6425
250
1148
18.4
1967
5.5
2.0
0.8
3.6
2.68
83.5
8300
250
1253
20.6
2445
5.5
2.0
0.8
3.8
2.84
89.0
9345
250
1335
23.3
3126
5.5
2.2
0.8
4.0
3.00
96.5
10965
250
1448
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.868
1.113
0.136
1.121
1.942
0.17
0.64
0.641
0.822
0.130
0.832
1.441
0.18
0.68
0.443
0.568
0.120
0.581
1.006
0.20
0.75
0.320
0.411
0.114
0.427
0.740
0.23
0.87
0.253
0.325
0.110
0.343
0.594
0.25
0.94
0.206
0.265
0.106
0.285
0.494
0.26
0.98
0.164
0.211
0.102
0.234
0.405
0.29
1.09
0.125
0.162
0.098
0.189
0.327
0.32
1.21
0.100
0.130
0.095
0.161
0.279
0.35
1.32
0.0778
0.102
0.092
0.137
0.237
0.38
1.43
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
119
140
171
204
232
259
293
338
380
432
8.2
104
123
150
180
206
231
262
304
343
393
8.3
9.0
A
kA
133
3.29
159
4.70
196
6.58
238
8.93
274
11.28
309
14.10
354
17.39
415
22.56
472
28.20
545
37.60
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Separation sheath thickness (Nominal)
Steel tape thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo=12 kV and f= 50 Hz
Sustained current ratings:-
8.1
SECTION E - TABLE 9
18/30 (36) kV
Three Core Aluminium Conductor
XLPE Insulated
Double Steel Tape Armoured
To IEC 60502-2
(Suitable for 19/33 kV Earthed
System)
3 CORE, A2XCETgY, Double Steel Taped Armoured Cables 18/30 kV to IEC 60502-2
57
OCI/PBMVC/REV.001/010410
mm2
50
70
95
120
150
185
240
300
400
mm
kg/km
mm
mm
mm
mm
mm
mm
kg/km
m
mm
8.1
381
8.0
1.8
0.5
3.2
2.36
70.5
4940
500
1058
9.7
553
8.0
1.8
0.5
3.3
2.44
74.0
5475
250
1110
11.4
764
8.0
1.9
0.5
3.5
2.60
78.0
6160
250
1170
12.9
965
8.0
2.0
0.8
3.6
2.68
83.0
7575
250
1245
14.3
1186
8.0
2.0
0.8
3.7
2.76
86.0
8165
250
1290
16.0
1500
8.0
2.1
0.8
3.9
2.92
90.5
9025
250
1358
18.4
1967
8.0
2.2
0.8
4.0
3.00
96.0
10195
250
1440
20.6
2445
8.0
2.3
0.8
4.2
3.16
101.5
11335
250
1523
23.3
3126
8.0
2.4
0.8
4.4
3.32
108.5
13035
250
1628
ohm/km
ohm/km
ohm/km
ohm/km
v/amp/km
mF/km
mA/m
0.641
0.822
0.143
0.834
1.445
0.14
0.79
0.443
0.568
0.132
0.583
1.010
0.16
0.90
0.320
0.411
0.126
0.430
0.745
0.17
0.96
0.253
0.325
0.121
0.347
0.601
0.19
1.07
0.206
0.265
0.117
0.290
0.502
0.20
1.13
0.164
0.211
0.112
0.239
0.414
0.22
1.24
0.125
0.161
0.107
0.193
0.334
0.24
1.36
0.100
0.130
0.104
0.166
0.288
0.26
1.47
0.0778
0.102
0.100
0.143
0.248
0.28
1.58
Laid direct, ground temp. = 20 C & Thermal resistivity of soil = 1.5 C m/W,
depth of laying = 0.8 m laid singly
140
171
204
232
259
293
338
380
432
8.2
123
150
180
206
231
262
304
343
393
8.3
9.0
A
kA
159
4.70
196
6.58
238
8.93
274
11.28
309
14.10
354
17.39
415
22.56
472
28.20
545
37.60
Sr. No.
(A)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
(B)
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
Manufacturing Dimensions
Conductor diameter (Approximate)
Conductor weight (Approximate)
Insulation thickness (Nominal)
Separation sheath thickness (Nominal)
Steel tape thickness (Nominal)
Outer sheath thickness (Nominal)
Outer sheath thickness (Minimum)
Cable overall diameter (Approximate)
Cable weight (Approximate)
Standard drum length (5% Tolerance)
Minimum bending radius of cable (During installation)
Electrical Parameters
DC resistance of conductor at 20 C (Maximum)
AC resistance of conductor at 90 C (Approximate)
Reactance at 50 Hz (Approximate)
Impedance at 50 Hz (Approximate)
Voltage drop (Approximate for 3 phase system)
Capacitance at 50 Hz (Approximate)
Approximate charging current per phase at Uo=18 kV and f= 50 Hz
Sustained current ratings:-
8.1
SECTION E - TABLE 10
58
Section F
59
OCI/PBMVC/REV.001/010410
60
OCI/PBMVC/REV.001/010410
200
400
600
800
0.73
0.83
0.88
0.90
0.92
0.60
0.73
0.79
0.83
0.86
0.54
0.68
0.75
0.80
0.84
0.49
0.63
0.72
0.78
0.82
0.46
0.61
0.70
0.76
0.81
0.43
0.58
0.68
0.75
0.80
0.41
0.57
0.67
0.74
0.39
0.55
0.66
0.73
10
0.37
0.54
0.65
11
0.36
0.53
0.64
12
0.35
0.52
0.64
SECTION F - TABLE 1
200
400
600
800
0.80
0.86
0.90
0.92
0.94
0.69
0.77
0.82
0.86
0.89
0.62
0.72
0.79
0.83
0.87
0.57
0.68
0.76
0.81
0.85
0.54
0.65
0.74
0.80
0.84
0.51
0.63
0.72
0.78
0.83
0.49
0.61
0.71
0.78
0.47
0.60
0.70
0.77
10
0.46
0.59
0.69
11
0.45
0.57
0.69
12
0.43
0.56
0.68
SECTION F - TABLE 2
61
OCI/PBMVC/REV.001/010410
0.8
0.9
1.5
2.5
25
1.30
1.25
1.20
1.16
1.00
0.89
0.81
0.75
35
1.30
1.25
1.21
1.16
1.00
0.89
0.81
0.75
50
1.32
1.26
1.21
1.16
1.00
0.89
0.81
0.74
70
1.33
1.27
1.22
1.17
1.00
0.89
0.81
0.74
95
1.34
1.28
1.22
1.18
1.00
0.89
0.80
0.74
120
1.34
1.28
1.22
1.18
1.00
0.88
0.80
0.74
150
1.35
1.28
1.23
1.18
1.00
0.88
0.80
0.74
185
1.35
1.29
1.23
1.18
1.00
0.88
0.80
0.74
240
1.36
1.29
1.23
1.18
1.00
0.88
0.80
0.73
300
1.36
1.30
1.24
1.19
1.00
0.88
0.80
0.73
1.37
1.30
1.24
1.19
1.00
0.88
0.79
0.73
SECTION F - TABLE 3
0.8
0.9
1.5
2.5
25
1.24
1.20
1.16
1.13
1.00
0.91
0.84
0.78
35
1.25
1.21
1.17
1.13
1.00
0.91
0.83
0.78
50
1.25
1.21
1.17
1.14
1.00
0.91
0.83
0.77
70
1.26
1.21
1.18
1.14
1.00
0.90
0.83
0.77
95
1.26
1.22
1.18
1.14
1.00
0.90
0.83
0.77
120
1.26
1.22
1.18
1.14
1.00
0.90
0.83
0.77
150
1.27
1.22
1.18
1.15
1.00
0.90
0.83
0.77
185
1.27
1.23
1.18
1.15
1.00
0.90
0.83
0.77
240
1.28
1.23
1.19
1.15
1.00
0.90
0.83
0.77
300
1.28
1.23
1.19
1.15
1.00
0.90
0.82
0.77
400
1.28
1.23
1.19
1.15
1.00
0.90
0.82
0.76
SECTION F - TABLE 4
62
OCI/PBMVC/REV.001/010410
Depth of laying
m
Three-core
cables
185 mm2
>185 mm2
0.5
1.04
1.06
1.04
0.6
1.02
1.04
1.03
0.8
1.00
1.00
1.00
1.0
0.98
0.97
0.98
1.25
0.96
0.95
0.96
1.5
0.95
0.93
0.95
1.75
0.94
0.91
0.94
2.0
0.93
0.90
0.93
2.5
0.91
0.88
0.91
3.0
0.90
0.86
0.90
SECTION F - TABLE 5
10
15
20
25
30
35
40
45
50
1.07
1.04
1.00
0.96
0.93
0.89
0.85
0.80
0.76
SECTION F - TABLE 6
63
OCI/PBMVC/REV.001/010410
200
400
600
800
0.78
0.85
0.89
0.91
0.93
0.66
0.75
0.81
0.85
0.88
0.59
0.70
0.77
0.82
0.86
0.55
0.66
0.74
0.80
0.84
0.51
0.64
0.72
0.78
0.83
0.48
0.61
0.71
0.77
0.82
0.46
0.60
0.70
0.76
0.44
0.58
0.69
0.76
10
0.43
0.57
0.68
11
0.42
0.56
0.67
12
0.40
0.55
0.67
SECTION F - TABLE 7
200
400
600
800
0.85
0.88
0.92
0.94
0.95
0.75
0.80
0.85
0.88
0.91
0.69
0.75
0.82
0.86
0.89
0.65
0.72
0.79
0.84
0.87
0.62
0.69
0.77
0.83
0.87
0.59
0.67
0.76
0.82
0.86
0.57
0.65
0.75
0.81
0.55
0.64
0.74
0.80
10
0.54
0.63
0.73
11
0.52
0.62
0.73
12
0.51
0.61
0.72
SECTION F - TABLE 8
64
OCI/PBMVC/REV.001/010410
0.8
0.9
1.5
2.5
25
1.21
1.17
1.14
1.12
1.00
0.91
0.85
0.79
35
1.21
1.18
1.15
1.12
1.00
0.91
0.84
0.79
50
1.21
1.18
1.15
1.12
1.00
0.91
0.84
0.78
70
1.22
1.19
1.15
1.12
1.00
0.91
0.84
0.78
95
1.23
1.19
1.16
1.13
1.00
0.91
0.84
0.78
120
1.23
1.20
1.16
1.13
1.00
0.91
0.84
0.78
150
1.24
1.20
1.16
1.13
1.00
0.91
0.83
0.78
185
1.24
1.20
1.17
1.13
1.00
0.91
0.83
0.78
240
1.25
1.21
1.17
1.14
1.00
0.90
0.83
0.77
300
1.25
1.21
1.17
1.14
1.00
0.90
0.83
0.77
1.25
1.21
1.17
1.14
1.00
0.90
0.83
0.77
SECTION F - TABLE 9
0.8
0.9
1.5
2.5
25
1.14
1.12
1.10
1.08
1.00
0.94
0.89
0.84
35
1.14
1.12
1.10
1.08
1.00
0.94
0.88
0.84
50
1.14
1.12
1.10
1.08
1.00
0.94
0.88
0.84
70
1.15
1.13
1.11
1.09
1.00
0.94
0.88
0.83
95
1.15
1.13
1.11
1.09
1.00
0.94
0.88
0.83
120
1.15
1.13
1.11
1.09
1.00
0.93
0.88
0.83
150
1.16
1.13
1.11
1.09
1.00
0.93
0.88
0.83
185
1.16
1.14
1.11
1.09
1.00
0.93
0.87
0.83
240
1.16
1.14
1.12
1.10
1.00
0.93
0.87
0.82
300
1.17
1.14
1.12
1.10
1.00
0.93
0.87
0.82
400
1.17
1.14
1.12
1.10
1.00
0.92
0.86
0.81
SECTION F - TABLE 10
65
OCI/PBMVC/REV.001/010410
Depth of laying
m
Three-core
cables
185 mm2
>185 mm2
0.5
1.04
1.05
1.03
0.6
1.02
1.03
1.02
0.8
1.00
1.00
1.00
1.0
0.98
0.97
0.99
1.25
0.96
0.95
0.97
1.5
0.95
0.93
0.96
1.75
0.94
0.92
0.95
2.0
0.93
0.91
0.94
2.5
0.91
0.89
0.93
3.0
0.90
0.88
0.92
SECTION F - TABLE 11
10
15
20
25
30
35
40
45
50
RATING FACTOR
1.07
1.04
1.00
0.96
0.93
0.89
0.85
0.80
0.76
SECTION F - TABLE 12
20
25
30
35
40
45
50
55
60
RATING FACTOR
1.08
1.04
1.00
0.96
0.91
0.87
0.82
0.76
0.71
SECTION F - TABLE 13
66
OCI/PBMVC/REV.001/010410
GROUP RATING FACTORS FOR GROUPS OF MORE THAN ONE MULTI-CORE CABLE IN AIR TO BE APPLIED TO THE CURRENT-CARRYING CAPACITY FOR ONE MULTI-CORE CABLE IN FREE AIR
Method of Installation
Cables on
perforated trays
Cables on ladder
supports, cleats, etc
Number of cables
3
4
Touching
1.00
0.88
0.82
0.79
0.76
0.73
1.00
0.87
0.80
0.77
0.73
0.68
1.00
0.86
0.79
0.76
0.71
0.66
Spaced
1.00
1.00
0.98
0.95
0.91
1.00
0.99
0.96
0.92
0.87
1.00
0.98
0.95
0.91
0.85
1.00
0.88
0.82
0.78
0.73
0.72
1.00
0.88
0.81
0.76
0.71
0.70
Spaced
1.00
0.91
0.89
0.88
0.87
1.00
0.91
0.88
0.87
0.85
Touching
1.00
0.87
0.82
0.80
0.79
0.78
1.00
0.86
0.80
0.78
0.76
0.73
1.00
0.85
0.79
0.76
0.73
0.70
Spaced
1.00
1.00
1.00
1.00
1.00
1.00
0.99
0.98
0.97
0.96
1.00
0.98
0.97
0.96
0.93
Touching
Cables on vertical
perforated trays
Number
of trays
Note 1: Values are given for vertical spacings between trays of 300 mm and at least 20 mm between trays and wall.
For closer spacing, the factors should be reduced.
Note 2: Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back. For closer
spacing, the factors should be reduced.
SECTION F - TABLE 14
67
OCI/PBMVC/REV.001/010410
GROUP RATING FACTORS FOR GROUPS OF MORE THAN ONE CIRCUIT OF SINGLE-CORE CABLES
- TO BE APPLIED TO THE CURRENT-CARRYING CAPACITY FOR ONE CIRCUIT OF SINGLE-CORE
CABLES IN FREE AIR
Number of
trays
Method of Installation
Number of three-phase
circuits (Note 3)
1
1.00
0.98
0.96
0.97
0.93
0.89
0.96
0.92
0.86
1.00
0.91
0.89
(Note 2)
1.00
0.90
0.86
Ladder
supports,
cleats, etc.
1.00
1.00
1.00
0.97
0.95
0.93
0.96
0.94
0.90
Perforated trays
(Note 1)
Vertical perforated
trays
(Note 1)
Spaced
Use as a
multiplier to
rating for
Three cables in
trefoil formation
Note 1: Values are given for vertical spacings between trays of 300 mm. For closer spacing, the factors should be
reduced.
Note 2: Values are given for horizontal spacing between trays of 225 mm with trays mounted back to back. For
closer spacing, the factors should be reduced.
Note 3: For circuits having more than one cable in parallel per phase, each three phase set of conductors should be
considered as a circuit for the purpose of this table.
SECTION F - TABLE 15
68
OCI/PBMVC/REV.001/010410
TYPE OF CABLE
DURING INSTALLATION
DURING TERMINATION
Unarmoured
20 x D
15 x D
Armoured
15 x D
12 X D
Unarmoured
15 x D
12 x D
Armoured (SWA)
12 x D
10 x D
15 x D
15 x D
SECTION F - TABLE 16
3.6/6
15
6/10
24
8.7/15
35
12/20
48
18/30
72
* Given test voltages are for New installation only (Reference - IEC - 60502-2)
SECTION F - TABLE 17
Copper wire screen area for Single core unarmoured cable
It is always advisable to design the cable for specific fault current as per the system requirement. However as a common
practice copper wire screen area as per the table given below may be provided for single core unarmoured cables. This
screen area is irrespective of voltage grade of the cable.
25-120
16
150-300
25
35
69
OCI/PBMVC/REV.001/010410
70
OCI/PBMVC/REV.001/010410
71
OCI/PBMVC/REV.001/010410
72
OCI/PBMVC/REV.001/010410
The short circuit ratings (r.m.s. values) of XLPE insulated cables have been calculated on the following assumptions.
1. Conductor temperature prior to short circuit
90 0C
250 0C
3. Specific gravity
a. Copper
8.89 gm/cc
b. Aluminium
2.703 gm/cc
4. Resistivity
a. Copper
17.241 X 10-6
W mm
b. Aluminium
28.264 X 10-6
W mm
The Maximum short circuit current is calculated with the following formula
K x A (kA)
t
Where lsh = r.m.s. value of short circuit current (kA)
lsh =
73
OCI/PBMVC/REV.001/010410
COPPER CONDUCTOR
74
OCI/PBMVC/REV.001/010410
ALUMINIUM CONDUCTOR
75
OCI/PBMVC/REV.001/010410
76
OCI/PBMVC/REV.001/010410
Installation
We recommend the following special guidelines, in conjunction with the standard installation instructions.
The cables should be stored in proper packed condition, in the shade and direct exposure to sun should be avoided.
As LSF (LSOH/LSZH) has lower tear strength property as compared to PVC/PE sheath, special care should be taken
during installation to avoid any damage. Even a small cut on the LSF (LSOH/LSZH) sheath could result in sheath
cracking, as it will run in longitudinal direction due to lower tear strength property of LSF (LSOH/LSZH) sheath.
Use pay-in rollers and corner rollers of non-metallic material (Nylon or Teflon) at least every 3 to 4 meters while laying
the cable.
As far as possible installation should be undercover or indoors. For outdoor installation, direct exposure to sunlight
should be avoided by using a suitable cable tray.
The cables should not be in contact with any hot surface.
The requirement of minimum bending radius should be followed as per data sheet.
Any clamping device should not be applied directly on the outer sheath. There should be some cushion (for instance
a rubber pad of approx. 3 mm thickness) between the cables outer sheath and clamps.
Maximum distance of unsupported length of cable for horizontal and vertical run should be as below:
Overall diameter of cable (mm)
0-14.9
350
450
15-19.9
400
550
20-39.9
450
600
40-59.9
700
900
60 & above
1100
1300
Re-winding
In case re-winding should be necessary, extreme caution should be taken during the process to avoid damage. The
following should be adhered to :
The winding should be done equally and uniformly with no over-riding of the coils or pinching on the sides of the drum.
The pay-off drum should have an adequate braking system to prevent the cable from coming loose on the drum.
77
OCI/PBMVC/REV.001/010410
DESCRIPTION
Copper Conductor
Aluminium Conductor
2X
XLPE Insulation
CE
Wa
Tg
PVC sheath
2Y
PE sheath
Example: 3C X 120 mm2, Copper Conductor, XLPE Insulated, copper tape screened over individual core, PVC bedding,
round wire armoured and overall PVC sheathed cable, 3.6/6 kV.
Hence cable can be denoted as : 3C x 120 mm2, 2XCEWY, 3.6/6 kV.
78
OCI/PBMVC/REV.001/010410
79
OCI/PBMVC/REV.001/010410
Category A: This category comprises those systems in which any phase conductor that comes in contact with
earth or an earth conductor is disconnected from the system within 1 min.
b)
Category B: This category comprises those systems which, under fault conditions, are operated for a short time
with one phase earthed. IEC 60183 recommends that this period should not exceed 1 h. For cables specified in
BS 6622/IEC-60502-2, a longer period, not exceeding 8 h on any occasion, can be tolerated. The total duration
of earth faults in any year should not exceed 125 h.
c)
Category C: This category comprises all systems which do not fall into categories A or B.
NOTE: In a system in which an earth fault is not automatically and promptly isolated, the extra stresses on the insulation
of cables during the earth fault might reduce the life of the cables. If the system is expected to be operated fairly often
with a permanent earth fault, it might be advisable to classify the system as category C.
The below Table gives the lowest rated voltage of cable that should be used according to the system voltage and category.
Minimum rated
voltage of cable,
Uo/U
Nominal voltage, U
Maximum sustained
voltage, Um
kV
kV
kV
6.6 or 6
7.2
A or B
3.6/6
6.6 or 6
7.2
6/10
11 or 10
12
A or B
6/10
11 or 10
12
8.7/15
15
17.5
A or B
8.7/15
15
17.5
12/20
22 or 20
24
A or B
12/20
22 or 20
24
18/30
33 or 30
36
A or B
18/30
The nominal system voltage, U, given in above Table is the nominal voltage between phases.
The maximum sustained system voltage Um, is the highest voltage between phases that can be sustained under normal
operating conditions at any time and at any point in the system. It excludes transient voltage variations, due to lightning
impulses, fault conditions and rapid disconnection of loads.
The normal system voltages shown in above Table are generally in accordance with series 1 as given in IEC 60038. For
system voltages intermediate between the values in above Table, the cable should be selected with a rated voltage not
less than the next highest value (e.g. for a 13.8 kV system of category A or B, the cable should have a rated voltage not
less than 8.7/15 kV and for a 13.8 kV system of category C, not less than 12/20 kV).
80
OCI/PBMVC/REV.001/010410