Professional Documents
Culture Documents
WhichDataCenterStandard
ShouldIFollow
PhilIsaak,PE,P.Eng.,RCDD,DCDC
President,MasterInstructor
IsaakTechnologiesInc.
www.isaaktech.com
Standards WhoarethesePeople
PowerStandards
Distribution&Grounding
NetworkStandards
Protocols
ITHardwareManufacturers
MediaStandards
CablingManufacturers
Design&InstallationStandards
EndUsers,Contractors,
Consultants,Manufacturers
www.isaaktech.com
12pages
ANSI/TIA942A(2012)
TelecommunicationsInfrastructureStandard
forDataCenters
118pages
ANSI/BICSI0022011
DataCenterDesignandImplementation
BestPractices
392pages
www.isaaktech.com
ForProfitPrivatelyHeld
NOT aStandard
OpenIndustryStandard
NOT VendorNeutral
OpenIndustryStandard
VendorNeutral
ANSICertifiedStandardRequirements
Openness: Participationshallbeopento
allpersonswhoaredirectlyandmaterially
affectedbytheactivityinquestion.
LackofDominance:Thestandardsdevelopment
processshallnotbedominatedbyanysingleinterest
category,individualororganization.
Balance:Participantsfromdiverseinterestcategories
shallbesoughtwiththeobjectiveofachievingbalance.
www.isaaktech.com
BICSISubjectMatterExperts
Morethan150subjectmatterexpertsfromaround
theworldparticipatedindevelopingthestandard.
Expertise:
Perspectives:
DataCenterManagers
DataCenterOperators
Consultants
Contractors
RiskAssessors
Manufacturers
CommissioningAgents
www.isaaktech.com
FacilityEngineers/Architects
ITEngineers/Architects
SystemAdministrators
Telecommunications
Security
FireProtection
ProjectManagers
DesignGuidevs Benchmarking
ANSI/BICSI0022011
Providesareferenceofcommonterminologyanddesignpracticesa
frameworkfordeterminingtherecommendedfacilityandtechnology
redundancytomeettheoperationalrequirements,achieveITobjectives
andtodevelopoptimumdesign&implementationsolutions
UptimeTiers
Onlydatacenterbenchmarkingsystemdevelopedbyandfordata
centerowners,notachecklist,designmenu,orcookbook
Source:UptimeInstitute:TierClassificationSystem&OperationalSustainabilitypresentedby
DanaSmith,DirectorofDevelopment,UptimeInstituteatBICSIAndino 2012
www.isaaktech.com
UptimeBenchmarks
UptimeInstitute
ScheduledOutages/Year
TierI
TierII TierIII
TierIV
2x12hrs
1x12hrs
None
None
AveFailures/Year(4hrs/failure)
1.2
1.0
1.0
1.0
AveAnnualDowntimeHours
28.8
22
1.6
0.8
99.67%
99.75%
99.98%
99.99%
Availability
**Basisisontop10%ofsitesasdeterminedbyUptimeInstituteBenchmarking**
www.isaaktech.com
ComparingtheStandards
TIA942Achapters (normative)
Datacenterdesignoverview
Datacentercablingsysteminfrastructure
Datacentertelecommunicationsspaces&relatedtopologies
Datacentercablingsystems
Datacentercablingpathways
Datacenterredundancy
TIA942Aannexes (informative)
Cablingdesignconsiderations
Accessproviderinformation
Coordinationofequipmentplanswithotherengineers
Datacenterspaceconsiderations
Datacentersiteselectionandbuildingdesignconsiderations
Datacenterinfrastructuretiers
Datacenterdesignexamples
www.isaaktech.com
ComparingtheStandards
BICSI002sections
Spaceplanning
Siteselection
Architectural
Structural
Electricalsystems
Mechanical
Fireprotection
BICSI002annexes
Designprocess
Reliabilityandavailability
www.isaaktech.com
Security
Buildingautomationsystems
Telecommunications
Informationtechnology
Commissioning
Datacentermaintenance
ComprehensiveDataCenterStandard
ANSI/BICSI
0022011
www.isaaktech.com
MethodologytoDefineReliability
DefineOperational
Requirements
Annual
Planned
Downtime
Operational
Level
> 400hrs
100 400hrs
50 99hrs
0 49hrs
0hrs
www.isaaktech.com
MethodologytoDefineReliability
DefineOperational
Requirements
www.isaaktech.com
DefineAvailability
Requirements
Minutes
Numberof9s
>5,000
>99%
500 5,000
99% 99.9%
50 500
99.9% 99.99%
5 50
99.99% 99.999%
0.5 5
99.999% 99.9999%
MethodologytoDefineReliability
DefineOperational
Requirements
DefineAvailability
Requirements
DefineImpactof
Downtime
Description
Localinscope,affectingonlyasinglefunctionoroperation,resultinginaminor
disruptionordelayinachievingnoncriticalorganizationalobjectives.
Classification
Isolated
Localinscope,affectingonlyasinglesite,orresultinginaminordisruptionordelay
inachievingkeyorganizationalobjectives.
Minor
Regionalinscope,affectingaportionoftheenterpriseorresultinginamoderate
disruptionordelayinachievingkeyorganizationalobjectives.
Major
Multiregionalinscope,affectingamajorportionoftheenterpriseorresultingina
majordisruptionordelayinachievingkeyorganizationalobjectives.
Severe
Affectingthequalityofservicedeliveryacrosstheentireenterprise,orresultingin
asignificantdisruptionordelayinachievingkeyorganizationalobjectives.
Catastrophic
www.isaaktech.com
MethodologytoDefineReliability
DefineOperational
Requirements
DefineAvailability
Requirements
Recommended
Performance
Identified
Class0
Class1
Class2
Class3
Class4
www.isaaktech.com
DefineImpactof
Downtime
Class0/1SinglePath
Alternate Power
Source
Transfer
Switchgear
Utility
NChiller,Pumps
&Condenser
Electrical Distribution
Static
Bypass
UPS
Pipingandvalve
redundancynot
required.
Mechanical
Switchgear
Maint.
Bypass
WAN
Carrier
NCRAH
Modules
PDU
Edge
Internet
Critical
Loads
Non-Critical
Loads
Mechanical
Loads
Edge
WAN
Core
Aggregation
RPPA
Access
Switch
Large
Frame
Processing
Power
Circuit
Server 1
A1
Server n
A
NAS
Disk
Array
POU
APSU
www.isaaktech.com
Disk
Array
BPSU
2013IsaakTechnologiesInc.
Class2RedundantComponents
Alternate Power
Source
Transfer
Switchgear
Alternate Power
Source
Utility
N+1Chillers,Pumps
&Condensers
Electrical Distribution
Static
Bypass
UPS
Mechanical
Switchgear
UPS
Pipingandvalve
redundancynotrequired
outsidecomputerroom.
WAN
Carrier
PDU
Maint.
Bypass
Non-Critical
Loads
Critical
Loads
Edge
WAN
Mechanical
Loads
RefertoChillerPiping
andValveRedundancy
sectionforcomputer
roomrecommendations
Edge
Internet
NCRAH
Modules
Core
+1CRAHModule
MorethanN+1
redundancyis
recommendedasthe
numberofmodulesto
meetNincreases
Aggregation
RPPA
Access
Switch
Power
Power
Circuit
Circuit
A1
A2
Server 1
Server n
POU
POU
APSU
www.isaaktech.com
Large
Frame
Processing
NAS
Disk
Array
Disk
Array
BPSU
2013IsaakTechnologiesInc.
Class3ConcurrentMaintainability
Alternate Power
Source
Utility
Switchgear
Switchgear
Electrical Distribution
Electrical Distribution
Static
Bypass
Mechanical
Switchgear
UPS
Alternate Power
Source
Mechanical
Switchgear
N+1Chillers,Pumps
&Condensers
Mechanical
Loads
UPS
Maint.
Bypass
WAN
Carrier 1
Mechanical
Loads
Alternate Switchboard
Carrier 1
Mechanical
Switchboard
Mechanical
Switchboard
PDU
Pipingandvalve
redundancynotrequired,
butrecommended,
outsidecomputerroom.
WAN
Carrier 2
Edge1
WAN
PDU
Critical
Fans/Pumps
Carrier 2
Edge2
Internet
Edge1
Internet
Edge2
WAN
Core1
Core2
Non-Critical
Loads
Critical
Loads
Non-Critical
Loads
PDUB1
PDUA1
RefertoChillerPiping
andValveRedundancy
sectionforcomputer
roomrecommendations
Access
Switch 1
Large
Frame
Processing
Access
Switch 2
Server 1
RPPB1
RPPA1
NAS
Disk
Array
Server n
SAN
Switch2
SAN
Switch1
Power
Power
Power
Power
Circuit
Circuit
Circuit
Circuit
RPPA11
RPPA12
RPPB11
RPPB12
STSA
STSB
A
POU
POU
APSU
Disk
Array1
Disk
Array n
BPSU
www.isaaktech.com
NCRAH
Modules
Aggregation2
Aggregation1
2013IsaakTechnologiesInc.
+1CRAHModule
MorethanN+1
redundancyis
recommendedasthe
numberofmodulesto
meetNincreases
Class4FaultTolerant
Utility
Alternate Power
Source
Switchgear
Alternate Power
Source
Utility
Switchgear
Alternate Power
Source
Electrical Distribution
Electrical Distribution
Mechanical
Switchgear
UPS
UPS
Static
Bypass
Alternate Power
Source
N+2Chillers,Pumps
&Condensers
Mechanical
Switchgear
UPS
Mechanical
Loads
UPS
Static
Bypass
Maint.
Bypass
Pipingandvalve
redundancyrequired
outsidecomputerroom.
Maint.
Bypass
WAN
Carrier 1
Mechanical
Switchgear
Mechanical
Switchgear
WAN
Carrier 2
Carrier 1
PDU
Carrier 2
PDU
Critical
Fans/Pumps
Non-Critical
Loads
Edge1
WAN
Critical
Loads
RPP1
PanelA
PDUA2
PDUB1
PanelB
RPP2
PanelA
Edge2
WAN
RefertoChillerPiping
andValveRedundancy
sectionforcomputer
roomrecommendations
Core1
Non-Critical
Loads
Core2
Aggregation2
Aggregation1
PDUA1
NCRAH
Modules
Edge2
Internet
Edge1
Internet
PDUB2
PanelB
Access
Switch 1
Large
Frame
Processing
Access
Switch 2
Server 1
NAS
Disk
Array
Server n
Power
Power
Power
Power
Circuit
Circuit
Circuit
Circuit
RPP1A1
RPP1B1
RPP2A1
RPP2B1
SAN
Switch2
SAN
Switch1
STSA
STSB
A
POU
POU
Disk
Array1
APSU
BPSU
www.isaaktech.com
+2CRAHModule
MorethanN+2
redundancyis
recommendedasthe
numberofmodulesto
meetNincreases
2013IsaakTechnologiesInc.
Disk
Array n
EndtoEndReliability
Applications
Systems
Network
CablingInfrastructure
Facility
Applications
DataProcessing&
StorageSystems
Network
CablingInfrastructure
Facility
www.isaaktech.com
DC125DataCenterDesignCourse
4DayCourse
InDepthReview
ofStandard
PrepareforDCDCExam
DataCenterDesignConsultant
ContactFiberOpto AsiaPte Ltdforcoursedates
andlocationsavailableinSouthEastAsia
www.isaaktech.com
BICSIDataCenterDocuments
ANSI/BICSI0022011
DataCenterDesignand
ImplementationBestPractices
BICSIInternationalStandards
SupplementalInformation001
MethodologyforSelectingDataCenter
DesignClassUtilizingPerformanceCriteria
AvailablefromBICSI
www.bicsi.org/standards
www.isaaktech.com