Request for Quotation (RFQ) No: ----------Date of issue:


Closing Date and Time
Contact details for Clarifications

Tuesday, June 16, 2015


Friday, June 19, 2015
10:00 AM
Mr. Liu (liuhb@sinotec.org.cn)
33-A ; Block-G ; Gulberg-III ; Lahore
Tel: +92-42-35881238-9
Fax: +92-42-35881241

1. INVITATION FOR QUOTATION


Quotations are hereby invited for the supply of a Transformers as per below requirement:
No.

Description

Qty

1
2
3
4

300 KVA Transformer (Oil Type)

5
1
1
1

400 KVA Transformer (Oil Type)


300 KVA Transformer (Dry Type)
400 KVA Transformer (Dry Type)

Rate (PKR)

Amount
(PKR)

2. QUOTATION REQUIREMENTS

The subject equipment is required at our on-going projects in Punjab and the technical data sheets are
attached also.

The price should include the detailed design and approval

The price should include supervision during Installation and commissioning

3. PRICING QUOTATION

Price needs to be provided EX-Works , with details on price elements that are subject to change in
future should be clearly indicated.

Price should include additional cost elements such as freight, insurance until acceptance, duty , taxes
(GST ect.) where applicable, etc.
Pakistan Office: 33-A, Block-G, Gulberg-III, Lahore Tel: +92 42 35881238-9 Fax: +92 42 35881241


SINOTEC

Payment Terms and Conditions.

Delivery Schedule

C O. ,

LT D

NOTE: No goods and/or services should be delivered without an official Purchase order.

SPECIFICATION - 300 KVA (Oil Type)


Rated kVA Voltage Ratio

300

Basic Insulation Level (BIL)

Frequency / Phases Vector

11000 /
50 Hz

Group
Type of Cooling

400 Y
/

Dyn 11 ONAN A

Insulation Class Ambient

40

0C

Temperature

Top Oil

Temperature Rise at Rated kVA

Average

60
65

Tapping Voltages (%)

0C

LV

LI - AC 3 HV
LI 75 AC 28

1.25,2.5,3.75,5.0

HV Terminals LV Terminals

1.25,2.5,3.75,5.0

Service Altitude Above Sea Level

Type of Tank

Type

1000 meter Sealed

Winding

0C

Indoor /Outdoor

PERFORMANCE
No Load Losses at Principle Tap Position

0.75 kW

Load Losses at Principle Tap Position & Rated Current

5.6 kW

Impedance

4.00 %

Regulation at Unity Power Factor & Rated Current

1.93 %

Regulation at 0.8 Power Factor & Rated Current

3.63 %

Efficiency at Unity Power Factor & 100% Rated Current

97.93 %

Efficiency at Unity Power Factor & 50% Rated Current

98.59 %

COMPONENTS & ACCESSORIES


Off Circuit Tap Changer

Pressure Relief Device (without contacts) (Elmek, Turkey)

Oil Filling Hole and Plug

Thermometer for Oil Temperature with maximum Temperature


Oil Level Indicator

indicator (without contacts) (Elmek, Turkey)

Oil Drain Valve


HT/ LT Cable Box
Lifting Lugs
Transport Eyes
Earthing Terminals
Rating & Diagram Plate (Stainless Steel)

Pakistan Office: 33-A, Block-G, Gulberg-III, Lahore Tel: +92 42 35881238-9 Fax: +92 42 35881241


SINOTEC

C O. ,

LT D

SPECIFICATION FOR
400 KVA (Oil Type)
Rated kVA

400

Basic Insulation Level

LV

LI

AC
Voltage Ratio

11000

Frequency / Phases

50

400

Hz

(BIL)

HV

LI

75

AC

1.25,2.5,3.75,5.0

Tapping Voltages (%)


Vector Group

Dyn 11

Type of Cooling

ONAN

HV Terminals

Insulation Class

LV Terminals

Ambient Temperature

40

Top Oil

60

Winding

65

1.25,2.5,3.75,5.0

Service Altitude Above Sea Level

1000 meter

Type of Tank

Sealed

Type

Indoor /Outdoor

Temperature Rise at Rated kVA


C

Average

PERFORMANCE
No Load Losses at Principle Tap Position

0.95 kW

Load Losses at Principle Tap Position & Rated Current

6.6 kW

Impedance

4.00%

Regulation at Unity Power Factor & Rated Current

1.72%

Regulation at 0.8 Power Factor & Rated Current

3.52%

Efficiency at Unity Power Factor & 100% Rated Current

98.15%

Efficiency at Unity Power Factor & 50% Rated Current

98.72%

COMPONENTS
ACCESSORIES

&

Off Circuit Tap Changer

Pressure Relief Device (without contacts) (Elmek, Turkey)

Oil Filling Hole and Plug

Thermometer for Oil Temperature with maximum

Oil

Temperature indicator (without contacts) (Elmek, Turkey)

Level

Indicator
Oil Drain Valve

Double Float Buchholz Relay (Elmek,


Turkey)

HT/ LT Cable Box


Lifting Lugs
Transport Eyes
Earthing Terminals
Rating

&

Diagram

Plate

(Stainless Steel)

Remarks :
1)

Transformer shall be offered with first filling of oil. Transformer Oil shall be in accordance with IEC-60296

2)

Transformer shall be manufactured and tested as per IEC 600-76 Standard.

Pakistan Office: 33-A, Block-G, Gulberg-III, Lahore Tel: +92 42 35881238-9 Fax: +92 42 35881241

28


SINOTEC

C O. ,

LT D

SPECIFICATIONS 300 KVA (Dry Type)


1

IEC Standard

IEC 60076-11

Structure

Indoor Type (With Enclosure)

Rated Power

Cooling

Rated frequency

Hz

50

Rated primary voltage

KV

11

Rated Primary Insulation Level

KV

12

Applied Voltage to Industrial frequency

Basic Insulation Level

KV

75

10

Power Frequency (AC)

KV

28

11

Off- circuit tapping (No Load)

12

Secondary Voltage at No Load (Line-

400

230.9

kVA

300
AN / AF

11 KV at 50 Hz

1.25 , 2.5 , 3.75 , 5.0 ,

Line)
13

Line to Neutral Voltage

15

Applied

Secondary

to

Industrial

0.400KV at 50 Hz

frequency
16

Vector group

Dyn 11

17

Noise level

dB

18

No Load losses

kW

0.90

19

Load losses at Rated kVA (Winding

kW

3.8

4%

50 dB

Temp: 115 C)
20

% Impedance

22

Maximum ambient temperature

oC

50 C

23

Winding temperature rise

oC

80 C

24

Maximum Hot Spot Temperature

98 K

25

Maximum Altitude

Meter

1000 Meter above Sea Level

26

HV winding tempreature class

27

LV winding tempreature class

28

Temperature of insulation system

29

Conductor material (HV/LV)

Copper
Off Circuit Tap Changer
Caution Plate
Rating & Diagram Plate (Stainless
Steel)

30

Components and Accessories

Roller
Wheels

Lifting Lugs

Earthing

Pakistan Office: 33-A, Block-G, Gulberg-III, Lahore Tel: +92 42 35881238-9 Fax: +92 42 35881241


SINOTEC

C O. ,

LT D

Terminals
Enclosure

with

IP 20

Remarks :
1

Transformer shall be manufactured and tested as per IEC 600-76 Standard.

SPECIFICATIONS 400 KVA (Dry Type)


1

IEC Standard

IEC 60076-11

Structure

Indoor Type (With Enclosure)

Rated Power

Cooling

Rated frequency

Hz

50

Rated primary voltage

KV

11

Rated Primary Insulation Level

KV

12

Applied Voltage to Industrial frequency

Basic Insulation Level

KV

75

10

Power Frequency (AC)

KV

28

11

Off- circuit tapping (No Load)

12

Secondary Voltage at No Load (Line-

400

230.9

kVA

400
AN / AF

11 KV at 50 Hz

1.25 , 2.5 , 3.75 , 5.0 ,

Line)
13

Line to Neutral Voltage

15

Applied

Secondary

to

Industrial

0.400KV at 50 Hz

frequency
16

Vector group

Dyn 11

17

Noise level

dB

18

No Load losses

kW

1.00

19

Load losses at Rated kVA (Winding

kW

4.4

4%

50 dB

Temp: 115 C)
20

% Impedance

22

Maximum ambient temperature

oC

50 C

23

Winding temperature rise

oC

80 C

24

Maximum Hot Spot Temperature

98 K

25

Maximum Altitude

Meter

1000 Meter above Sea Level

26

HV winding tempreature class

27

LV winding tempreature class

28

Temperature of insulation system

29

Conductor material (HV/LV)

Copper
Off Circuit Tap Changer
Caution Plate
Rating & Diagram Plate (Stainless

Pakistan Office: 33-A, Block-G, Gulberg-III, Lahore Tel: +92 42 35881238-9 Fax: +92 42 35881241


SINOTEC

C O. ,

LT D

Steel)
30

Components and Accessories

Roller
Wheels

Lifting Lugs

Earthing
Terminals
Enclosure

with

IP 20
Remarks :
1

Transformer shall be manufactured and tested as per IEC 600-76 Standard.

Pakistan Office: 33-A, Block-G, Gulberg-III, Lahore Tel: +92 42 35881238-9 Fax: +92 42 35881241