EST3
Manual de Instalacin y Servicio
P/N 270380 Rev 7.0 10SEP07
DESARROLLADO POR
GE Security, Inc.
8985 Town Center Parkway
Bradenton, FL 34202
(941) 739-4300
NOTIFICACION DE DERECHOS
DE AUTOR
MARCAS REGISTRADAS
Revisin
17JUL96
1.0
Publicacin Inicial
31MAR97
1.5
14DEC98
2.0
21OCT99
3.0
30AUG01
4.0
29OCT01
5.0
17AUG04
6.0
21JUN07
7.0
Content
Informacin Importante
Limitaciones de responsabilidad
Este producto ha sido diseado para cumplir los
requerimientos de NFPA Standard 72; Underwriters
Laboratories, Inc., Standard 864; and Underwriters
Laboratories of Canada, Inc., Standard ULC S527. La
instalacin de acuerdo a este manual, los cdigos aplicables y
las instrucciones de la Autoridad que tenga jurisdiccin es
obligatoria. GE Security bajo ninguna circunstancia se har
responsable por ningn dao o prdida incidental o como
consecuencia de la falla de productos GE Security ms all
del costo de la reparacin o reemplazo de cualquier producto
defectuoso. se reserva el derecho de hacer mejoras y cambiar
las especificaciones de los productos en cualquier momento.
An cuando se han tomado todas las precauciones durante
la preparacin de este manual para asegurar la precisin de
su contenido, GE Security no asume ninguna responsabilidad
por errores u omisiones.
ii
Content
Permitida en Posibles
UL 864? (Y/N) configuraciones
Configuraciones
permitidas en UL 864
Si
No
Si
iii
Content
Funcin programable u
opcin
Permitida en Posibles
UL 864? (Y/N) configuraciones
Retardo de Energa AC
Configuraciones
permitidas en UL 864
No
Si
Si
Inhabilitada (0)
Inhabilitada [2]
0 a 24 horas
Inhabilitada
1 a 3 horas
1 minuto a 45 horas
Enrutado mensaje de evento
Ningun Gabinete
Habilitado
Habilitado
Inhabilitado
Inhabilitado [5]
Retardos (programados en
reglas)
0 a 240 segundos
1 a 255
1 a 255 [7]
Enviar a la activacin
Los disparadores de
activacin y restauracin
deben igualar el tipo de
mensaje
N/A
En la configuracin del
mdulo Signature esta
prohibido el codigo 18 de
personalidad [11]
Tipo dispositivo de
Alarma
Tipo de dispositivo de
jaln
Tipo de dispositivo de
jaln
Tipo de dispositivo de
calor
Tipo de dispositivo de
calor
Tipo de dispositivo de
humo
Tipo de dispositivo de
humo
Tipo de dispositivo de
flujo de agua
iv
Enviar a la restauracin
Content
Funcin programable u
opcin
Permitida en Posibles
UL 864? (Y/N) configuraciones
Configuraciones
permitidas en UL 864
Tipo dispositivo de
Alarma
Tipo de dispositivo de
jaln
Tipo de dispositivo de
jaln
Tipo de dispositivo de
calor
Tipo de dispositivo de
calor
Tipo de dispositivo de
humo
Tipo de dispositivo de
humo [9]
Tipo de dispositivo de
flujo de agua
Cuenta de activacin de
dispositivo grupo AND
1 a 255
1 a 255 [10]
Tipo dispositivo de
Alarma
Tipo de dispositivo de
jaln
Tipo de dispositivo de
jaln
Tipo de dispositivo de
calor
Tipo de dispositivo de
humo
Tipo de dispositivo de
flujo de agua
Tipo de dispositivo de
calor
Tipo de dispositivo de
humo [9]
Tipo de dispositivo de flujo
de agua
3 a 10
3 a 10 [10]
Content
Funcin programable u
opcin
Permitida en Posibles
UL 864? (Y/N) configuraciones
Configuraciones
permitidas en UL 864
Notas
[1]
[2]
[3]
[4]
[5]
[6]
[7]
Cuando se usan prioridades, los eventos de alarma ddeben tener una proridad ms alta que
eventos de problemas o supervisin.
[8]
Permitidos en grupos de alarmas zonificadas, grupos AND y grupos matriz que son usados para
iniciar la descarga de agentes extinguidores o agua excepto cuando se usa la alarma de
deteccin de humo direccionable.
[9]
Permitido unicamente en grupos de alarmas zonificadas, grupos AND y grupos matriz que no son
usados para iniciar la descarga de agentes extinguidores o agua
[10] Se requiere una cuenta mpinima de activacin del dispositivo de 2 si el grupo AND y el grupo
matriz es usaado para iniciar la descarga de agentes extinguidores o agua
[11] El cdigo 18 de personalidad es tpicamente usado cuando una condicin corta debe ser
distinguida de una condicin de alarma. Este tipo de IDC est prohibido por UL 864.
vi
Content
Organizacin
Captulo 1: Informacin general del sistema: un visin general
descriptiva de los componentes y subsistemas que
constituyen un sistema EST3.
Captulo 2: Aplicaciones de seguridad: cubre aplicaciones de
seguridad. Este captulo contiene diagramas de bloque que
muestran los componentes requeridos para crear sistemas de
seguridad especficos.
Captulo 3: Aplicaciones de control de acceso: cubre
aplicaciones de control de acceso. Al igual que el Captulo 2,
este capitulo contiene diagramas de bloque y descripciones
de sistemas especficos de control de acceso.
Captulo 4: Aplicaciones centralizadas de audio: describe el
equipo y configuracin requerida para creas audio
centralizado para las instalaciones.
Captulo 5: Instalacin: informacin de instalacin de
componentes y aplicaciones del sistema que complementan
las instrucciones proporcionadas en las hojas de instalacin
de componentes individuales.
Captulo 6: Encendido y pruebas: informacin y
procedimientos necesarios para llevar a cabo el encendido
inicial del sistema y pruebas de aceptacin.
Captulo 7: Mantenimiento preventivo: enumera puntos y
procedimientos del mantenimiento programado requerido.
Capitulo 8: Servicio y resolucin de problemas: un conjunto
integral de procedimientos y tablas para ayudar al personal
tcnico certificado a darle servicio y resolver problemas del
sistema.
Apendices A, B, y C ofrecen informacin complementaria de
direccionamiento del sistema e informacin, clculos y
compatibilidad.
vii
Content
Informacin de seguridad
Este manual utiliza importantes advertencias de seguridad
para advertir de los posibles peligros a personas o el equipo.
Las precauciones son utilizadas para indicar
la presencia de algn peligro que causar o pueda causar
dao al equipo si las instrucciones de seguridad no son
seguidas o si el peligro no es evitado.
Precaucin:
viii
Content
La biblioteca EST3
Documentos EST3
Una biblioteca de documentos y presentaciones multimedia
apoyan el sistema EST3 de seguridad de la vida. Un breve
descripcin se proporciona a continuacin.
Manual de Instalacin y Servicio EST3 (P/N 270380): Ofrece
informacin completa de como instalar y dar servicio al
hardware EST3. El manual tambin incluye informacin de
instalacin de selectos componentes de la Serie Signature.
Ayuda en lnea SDU (P/N 180653): Ofrece soporte completo en
lnea para configurar y programar un sistema usando el
programa System Definition Utility.
Manual de Operacin del Sistema EST3 (P/N 270382):
Proporciona informacin detallada de la operacin del
sistema y sus componentes.
Manual de la Aplicacin de Manejo del Humo EST3 (P/N
270913):Ofrece informacin para disear, programar y probar
un sistema de control de humo del EST3.
Listas de Compatibilidad EST3 ULI ULC (P/N 3100427): Una
lisdta de los dispositivos y accesorios que son compatibles
con EST3.
Otros documentos
Adems de los documentos en la biblioteca EST3, puede
encontrar de utilidad los siguientes documentos.
Boletn de las aplicaciones detectores de calor y humo de la
serie Signature (P/N 270145): Ofrece informacin de
aplicaciones adicionales de detectores de calor y humo de la
serie Signature.
Manual de Instalacin de Componentes de la Serie Signature
(P/N 270497): Contiene informacin detallada de montaje y
cableado de todos los dispositivos de la serie Signature.
Gua de la aplicacin de bocinas (P/N 85000-0033):
Proporciona informacin de la colocacin y distribucin de las
bocinas para indicar alarma de incendio y comunicaciones de
voz de emergencia.
Gua de la aplicaciones estroboscpicas (P/N 85000-0049):
Ofrece informacin de la colocacin y distribucin de
estroboscopios para indicar alarma de incendio.
ix
Content
Documentacin relacionada
National Fire Protection Association
1 Batterymarch Park
P.O. Box 9101
Quincy, MA 02269-9101
Content
7 Crouse Road
Scarborough, ON
Canada M1R 3A9
ADEMAS DE: Requerimientos de estados y cdigos locales de edificios y la autoridad local que
tenga jurisdiccin.
xi
Captulo 1
Informacin general del sistema
Resumen
1.1
System overview
1.2
System overview
1.3
System overview
Instalaciones
Protegidas (Local)
Auxiliar
o
Estacin Remota
o
Instalaciones Propias
Protegidas
1.4
System overview
1.5
System overview
CPU
CPU
TB2
AUDIO
A IN
CPU
TB2
AUDIO
A OUT
AUDIO AUDIO
B IN
B OUT
AUDIO
A IN
CPU
TB2
AUDIO
A OUT
AUDIO AUDIO
B IN
B OUT
AUDIO
A IN
TB2
AUDIO
A OUT
AUDIO AUDIO
B IN
B OUT
AUDIO
A IN
AUDIO
A OUT
AUDIO AUDIO
B IN
B OUT
De
INFORMACION PRIMARIA DE AUDIO
en 3-ASU
1.6
System overview
CPU
CPU
CPU
CPU
TB2
TB2
TB2
TB2
AUDIO
A IN
AUDIO
A OUT
AUDIO AUDIO
B IN
B OUT
AUDIO
A IN
AUDIO
A OUT
AUDIO AUDIO
B IN
B OUT
AUDIO
A IN
AUDIO
A OUT
AUDIO AUDIO
B IN
B OUT
AUDIO
A IN
AUDIO
A OUT
AUDIO AUDIO
B IN
B OUT
De
INFORMACION PRIMARIA DE AUDIO
conexiones en 3-ASU
Amplificadores
Los amplificadores estn diseados para alimentar una sola
zona de audio y proporcionar un circuito integral 24Vdc de
dispositivos de aviso visual. Los mdulos amplificadores
estn disponibles en versiones de 20-, 40-, y 95-watt, con
cada amplificador proporcionando un circuito de salida de
audio supervisado Clase B o A. El amplificador se puede
configurar para salida de ya sea 25 Vrms o 70 Vrms. Se
proporciona tambin un circuito de dispositivos de aviso
independiente supervisado Clase B o Clase A de 24 Vdc, 3.5
Amp (NAC) en los amplificadores de 20- y 40-watt para
impulsar los dispositivos de aviso. Adicionalmente, se pueden
agregar amplificadores de soporte automticos en una
configuracin de soporte comn conmutado.
Cada amplificador de audio tiene un demultiplexador,
haciendo que los 8 canales estn disponibles a la entrada del
amplificador, siguiendo las indicaciones de la programacin
del sistema. Cada amplificador tambin contiene sistemas de
circuitos que administran las funciones de procesamiento de
seales de rutina tales como prioridad de canales.
La salida del amplificador es un circuito de bocinas dedicado,
supervisado de 25-, 70-Vrms que cubre una zona de audio en
las instalaciones protegidas. La Figura 1-4 es un ejemplo de
un recinto con cuatro amplificadores de zona y un
amplificador de soporte. En respuesta a una alarma, los
amplificadores de audio seleccionados han sido conectados a
los canales de audio requeridos. Observe que las tres
1.7
System overview
Amplif.
Respaldo
Amplif.
Zonal
Llamada
Llamada
EVAC
Alerta
El amplificador pierde
comunicacin con el modulo
Procesador Central
Amplificadores de Soporte
En caso de una falla del amplificador (no un problema de
cableado de campo), el amplificador de soporte
1.8
System overview
Amplif.
Respaldo
Amplif.
Zonal
Llamada
Amplif.
Zonal
Amplif.
Zonal
Llamada
EVAC
Amplif.
Zonal
Alerta
Nota: El amplificador de
soporte, apoyar a un
amplificador que falla si
estaba siendo usado por
Page, EVAC o Alert. No
apoyar a un amplificador
siendo usado en un canal
Auxiliar o General.
1.9
System overview
Telfono
Bomberos
Entrada
auxiliar
Multiplexor
Seales de Audio
Unidad
reproductora
mensaje digital
Base de datos
Tono/mensaje
Seales digitales
Demultiplexar
y
decodificar
Seleccin
y supervisin
de canal
Circuito de audio
supervisado de
25/70 VRMS
Amp de
poder
EOLR
1.10
System overview
Prioridad de seal de audio
Prioridad
LLAMADA
EVAC
ALERTA
AUXILIAR
GENERAL
Llamada a Todos
EVAC
Alerta
Llamada a Todos Menos
1.11
System overview
1.12
System overview
EOLR
Generador
de
tono local
ALERTA
EOLR
Generador
de
tono local
EVAC
25/70 VRMS circuito
de audio supervisado
Amp.
Potencia
EOLR
Generador
de
tono local
LLAMADA
EOLR
Generador
de
tono local
EVAC
Modo normal
Page
Evac
Alerta
Auxiliar
General1
General2
General3
General4
Page
Evac
Alerta
Auxiliar
General1
General2
General3
General4
ALL CALL
Page a EVAC
Page
Evac
Alerta
Auxiliar
General1
General2
General3
General4
Page a ALERT
Figura 1-8: Flujo de Seal Unidad de Fuente de Audio Modo Llamada Especial
1.13
System overview
El modo All Call es usado para enviar una llamada a la totalidad de las instalaciones. Cuando se activa
el interruptor de All Call, la Unidad de Fuente de Audio se coloca en el modo all call. En esta modalidad,
lo amplificadores de audio de zona no se transfieren todos al canal de llamada. Sino que la Unidad de
Fuente de Audio redirecciona la fuente de seal de llamada a todos los canales de audio. La Figura 1-8
muestra la fuente de llamada all call a las conexiones de canales de audio en la esquina inferior
izquierda. Observe que todos lo canales reciben la misma seal. Cualquier amplificador en el sistema,
independientemente del canal de audio seleccionado, recibir la llamada. Cualquier amplificador que
estuviera previamente libre se encender y recibir la llamada.
1.14
System overview
1.15
System overview
83
82
Mensaje de evacuacin, ala oeste piso
80: Se ha reportado un incendio en el
ala este del piso 80
81
80
79
78
77
Mensaje genrico ( por omisin) Se ha
reportado una emergencia en el edificio.
Permanezca en donde se encuentra y
espere instrucciones adicionales
33
32
31
Mensaje de evacuacin ala norte piso
30: se ha reportado un incendio en el
ala norte del piso 30
30
29
28
27
1.16
System overview
Telfono de bomberos
El 3-FTCU contiene un auricular maestro de telfono que
ofrece una contrahuella de telfono anlogo para
comunicaciones de 2 vas totalmente independientes entre la
estacin de mando de incendio y los telfonos de estaciones
de Bomberos/ telfonos de enchufe instalados en ubicaciones
estratgicas en toda la instalacin protegida.
Descolgar el telfono o conectndolo en un enchufe genera
un seal de llamada entrante visual o audible en la estacin
de mando de incendio. La persona originando la llamada
escucha un tono hasta que el auricular se conecta al sistema.
El operador de la estacin de mando de incendio
manualmente conecta la llamada entrante a la contrahuella
del telfono para completar la llamada. Se pueden conectar
hasta 5 telfonos remotos a la contrahuella
simultneamente. El operador del centro de mando de
incendio tambin puede usar el circuito del telfono como
una fuente de llamada, permitiendo hacer llamados a travs
del sistema telefnico.
1.17
System overview
1.18
System overview
B1_CAB1
J5
J5
CPU
TB2
RED
OUT
IN
A
B
A
B
B1_CAB2
J5
CPU
TB2
AUDIO
A IN
B1_CAB3
J5
CPU
TB2
RED
OUT
IN
A
B
A
B
AUDIO
A IN
RED
OUT
IN
A
B
A
B
B1_CAB4
CPU
TB2
AUDIO
A IN
RED
OUT
IN
A
B
A
B
AUDIO
A IN
Flujo de envo
Flujo de recepcin
Figura 1-10: Cableado de la contrahuella de la red de datos Clase B usando cable de cobre
Nota: Como una cuestin de convencin, la contrahuella de la
red de datos Clase B debe comenzar en el modulo CPU que
no tiene cables conectados a su puerto de la Red A.
1.19
System overview
B1_CAB1
J5
J5
CPU
TB2
RED
OUT
IN
A
B
A
B
B1_CAB2
J5
CPU
TB2
AUDIO
A IN
B1_CAB3
J5
CPU
TB2
RED
OUT
IN
A
B
A
B
AUDIO
A IN
RED
OUT
IN
A
B
A
B
B1_CAB4
CPU
TB2
AUDIO
A IN
RED
OUT
IN
A
B
A
B
AUDIO
A IN
Figura 1-11: Cableado tpico de una contrahuella de una red de datos Clase A usando cable de cobre
Conexiones de descarga
Cada modulo de riel programable tiene un enchufe de
telfono modular para descargar datos directamente de la
computadora SDU. El enchufe de telfono modular en
cualquier mdulo CPU tambin puede ser usado para
descargar datos a otros mdulos de red programables en el
mismo panel a travs del bus de riel, o a otros paneles de la
red a travs de la contrahuella de la red de datos.
Adems del enchufe de telfono modular, el modulo CPU
tiene dos puertos seriales de comunicacin que pueden
usarse par descargar datos, siempre que se cumplan ambas
de las siguientes condiciones:
1.20
System overview
Conecte aqu para descargar datos a todos los tres mdulos de red
programables a travs del bus de riel (modo red) o nicamente a
este modulo de riel programable (modo de un solo paso)
N
O
N
C
N
O
TROUBLE
N
A
N
C
N
O
ALARM
N
C
B
+
B
-
S
H
A
+
SIGA1
SUP
A
-
SIGA1
S P
M W
K R
1
B
+
B
-
B
+
SIGA1
B
-
S
H
SIGA1
A
+
A
-
SIGA1
S P
M W
K R
1
B
+
B
-
SIGA1
TB1
J8
J9
J11
J10
O UT P U T M O D U LE
O UT P U T M O D U LE
J1
A
+
NET WOR K
OUT
IN
A
B
+
B
-
AUDIO
A IN
+
AUDIO
A OUT
-
AUDIO
B IN
-
AUDIO
B OUT
-
R
X
1
T
X
1
R
T
S
1
C
O
M
1
R
X
2
T
X
2
R
T
S
2
C
O
M
2
SIGA2
B
-
B
+
2
S P
M W
K R
SIGA2
A
-
SIGA2
A
+
S
H
B
-
B
+
SIGA2
B
-
B
+
2
S P
M W
K R
SIGA2
A
-
SIGA2
A
+
S
H
B
-
B
+
1.21
System overview
Conexin de descarga
de la computadora SDU
B1_CAB1
J5
B1_CAB2
J5
CPU
TB2
J5
CPU
TB2
RED
OUT
A
A
B1_CAB3
IN
AUDIO
A IN
B1_CAB4
J5
CPU
TB2
RED
OUT
IN
A
B
A
B
AUDIO
A IN
RED
OUT
IN
A
B
A
B
CPU
TB2
AUDIO
A IN
RED
OUT
A
A
IN
AUDIO
A IN
Figura 1-13: Impacto de inhabilitar la conexin terminal de la Red A en redes Clase B durante una
descarga
1.22
System overview
Conexin de descarga
de computadora SDU
B1_CAB1
J5
B1_CAB2
J5
CPU
TB2
RED
OUT
IN
A
B
A
B
B1_CAB3
J5
CPU
TB2
AUDIO
A IN
B1_CAB4
J5
CPU
TB2
RED
OUT
IN
A
B
A
B
AUDIO
A IN
RED
OUT
IN
A
B
A
B
CPU
TB2
AUDIO
A IN
RED
OUT
A
A
IN
AUDIO
A IN
Figura 1-14: Impacto de inhabilitar la conexin de terminal de la Red A en redes de Clase A durante
una descarga
1.23
System overview
Pgina de cdigo
Chino simplificado
Chino tradicional
Coreano
Hebreo
Turco
Polaco, Eslovaco
Ruso
1.24
Idiomas soportados
1251 (Cyrillic)
Ingls, Ruso
1254 (Turkish)
Ingls, Turco
System overview
Idiomas soportados
1255 (Hebrew)
Ingls, Hebreo
Holands
Ingls (UK)
X
X
X[1]
Ingls (US)
Francs Canadiense
Hebreo
Italiano
Coreano, Wansung
Medio
oriente
Canadiens
e
Asitico
Europeo
Idioma
Estados
Unidos
Mercado
X
X
Polaco
Portugus (Brasil)
Ruso
Eslovaco
X
X
Espaol (Sudamrica)
Turco
1.25
System overview
[1]
[1]
Holands
Ingls (UK)
X
X
Medio
oriente
Canadiens
e
Asitico
Europeo
Idioma
Estados
Unidos
Mercado
Ingls (US)
Francs Canadiense
Hebreo
[1]
Italiano
Coreano, Wansung
[1]
X
[1]
Portugus (Brasil)
Espaol (Sudamrica)
Turco
[1]
[1]
Ruso
[1]
[1]
Polaco
[1]
Eslovaco
[1]
[1]
Canadiens
e
Medio
oriente
Asitico
Europeo
Idioma
Estados
Unidos
Mercado
1.26
Holands
Ingls (UK)
Ingls (US)
Francs Canadiense
System overview
Medio
oriente
Italiano
Canadiens
e
Asitico
Hebreo
Europeo
Idioma
Estados
Unidos
Mercado
Coreano, Wansung
Polaco
Portugus (Brasil)
Ruso
Eslovaco
Espaol (Sudamrica)
Turco
X
X
1.27
System overview
1.28
System overview
Configuracin de la sensibilidad de la alarma
1.29
System overview
1.30
System overview
Aplicaciones de la red
Esta seccin trata del layout inicial de los gabinete de la red
asi como de las configuraciones de las aplicaciones para los
mdulos bsicos de la red.
Layout de la red
La primera tarea para el diseador del sistema es ubicar los
gabinetes del equipo a lo largo del proyecto. El objetivo de
ubicar los gabinetes es el de maximizar la cobertura de las
instalaciones por gabinete minimizando el costo del
hardware. La siguiente informacin general debe ser usada
como una gua para disear el sistema.
La cobertura por gabinete esta basada, en cierta parte en el
tipo de proyecto que se est diseando. En las instalaciones
de un edificio de muchos pisos que requiere un sistema de
comunicacin de voz de emergencia, el problema es cuntos
pisos pueden ser atendidos por un solo gabinete. En una
instalacin estilo campus, puede haber uno o mas gabinetes
por edificio, dependiendo del tamao de los edificios.
Cobertura de los gabinetes
1.31
System overview
Capacidad de sistema de 64 gabinetes por red: Requiere el
Dominio de funciones
El sistema EST3 de seguridad de la vida utiliza tecnologa de
red punto a punto. No hay un gabinete nico que est en
control de la red. La conexin de red de punto a punto
permite mltiples ubicaciones de control dentro de una sola
red. El dominio de funcin se define como el grupo de
gabinetes que son afectados cuando la funcin es activada.
Un gabinete de red puede ser parte de uno o ms grupos. Se
permiten ubicaciones mltiples de control para cualquier
grupo.
Hay tres tipos de dominio disponibles.
Local: La funcin afecta nicamente al gabinete en el que est
Grupo #3
Grupo #1
Grupo #2
1.32
System overview
Estado
gabinete
Comandos
Silencio
Silencio
alarma
problema
Simulacro
Enterado
Gabinete 1
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4
1, 2, 3, 4, 5, 6
1, 2, 3, 4
Gabinete 2
1, 2, 3, 4
N/A
N/A
N/A
N/A
N/A
Grupo 3
Reset
Gabinete 3
1, 2, 3, 4, 5, 6
N/A
N/A
N/A
N/A
N/A
Gabinete 4
1, 2, 3, 4, 5, 6
N/A
N/A
N/A
N/A
N/A
Grupo 2
Grupo 1
Gabinete
que enva
Gabinete 5
3, 4, 5, 6
N/A
N/A
N/A
N/A
N/A
Gabinete 6
3, 4, 5, 6
3, 4, 5, 6
3, 4, 5, 6
3, 4, 5, 6
1, 2, 3, 4, 5, 6
3, 4, 5, 6
Leyenda
1 a 6 = Gabinetes que reciben comandos del gabinete que enva
N/A = No aplica
Figura 1-16: Comandos de red enrutados para el dominio ilustrado en la Figura 1-15
1.33
System overview
1.34
System overview
Aplicaciones de audio
Seleccin de amplificadores
1.35
System overview
Amplificadores de respaldo
Espacio en el gabinete
Canales de audio
El sistema de audio EST3 suministra ocho (8) canales
simultneos para la distribucin de seales de audio. Las
funciones de cuatro de estos canales son fijadas por el
sistema. Estos canales son llamados por sus funciones: Canal
de Llamada por altavoz, EVAC, Alerta, y Entrada Auxiliar. Los
cuatro canales restantes son llamados canales generales del
1 al 4.
1.36
System overview
1 (La ms alta)
Micrfono local
Telfono de bomberos
3 (la ms baja)
Micrfono remoto
1.37
System overview
1.38
System overview
Alarma
Incendio
Page a
Evac
Page a
Alerta
Escaleras
All Call
Minus
All Call
Page
Page
Llamada
zonal
9. piso
Alerta
Alerta
Page
Alerta
Page
Alerta
80. piso
Alerta
Alerta
Page
Alerta
Page
Alerta
7. piso
Evac
Page
Evac
Evac
Page
Evac
6. piso
Evac
Page
Evac
Evac
Page
Page
5. piso
Evac
Page
Evac
Evac
Page
Evac
4. piso
Alerta
Alerta
Page
Alerta
Page
Alerta
3. piso
Alerta
Alerta
Page
Alerta
Page
Alerta
2. piso
Alerta
Alerta
Page
Alerta
Page
Alerta
1er. piso
Alerta
Alerta
Page
Alerta
Page
Alerta
Leyenda
Piso de incendio
Piso arriba o piso debajo de incendio
1.39
System overview
1.40
System overview
Page
Page
8. piso
Page
8. piso
Alerta
Evac
Page
7. piso
Page
7. piso
Page
Page
6. piso
Page
6. piso
Alerta
Evac
Page
5. piso
Page
5. piso
Page
Page
4.piso
Page
4.piso
Alerta
Page
3er. piso
Page
3er. piso
Page
Page
2. piso
Page
2. piso
Alerta
Page
1er. piso
Page
1er. piso
Page
Evac
Evac
Status
Status
Status
Status
Alerta
Page
Alerta
Page
Alerta
Page
Alerta
Page
Alerta
Page
5o. piso
Page
9. piso
Status
4o. piso
Page
9. piso
Evac
3er. piso
Alerta
2. piso
Page
10. piso
Page
1er. piso
Page
10. piso
6o. piso
Page
5o. piso
Page
11. piso
Alerta
Status
4o. piso
Page
11. piso
Evac
3er. piso
Alerta
2. piso
Page
12. piso
1er. piso
Page
12. piso
6o. piso
1.41
System overview
1.42
System overview
Mensajes
General
1.43
System overview
1.44
System overview
1.45
System overview
1.46
System overview
Tpico circuito
Ramal de telfono
UL/ULC Listed
47 kEOLR
Clase B
+ TB3
10 9
SIGA-CC1 con
Cdigo personalidad 6
8 7 6 5
4 3 2 1
TB2
TB1
CONTRAHUELLA OUT (+)
CONTRAHUELLA OUT (-)
A siguiente SIGA-CC1 o
UL/ULC Listed EOLR
DATA IN (+)
DATA IN (-)
A siguiente dispositivo
1.47
System overview
1.48
Chapter 2
Aplicaciones de Seguridad
Sumario
2.1
Security applications
Equipo de seguridad
Introduccin
El equipo requerido para un sistema de seguridad general se
muestra en la Figura 2-1. Discutiremos cada punto mostrado
en el diagrama, adems de los dems factores mencionados
fuera del diagrama.
Panel de control
Circuito de datos Signature
Mdulo
Controlador Signature
Dispositivos alarma
de incendio
Signature
Monitor de
Pantalla
deteclado
teclado
KPDISP
Mdulo
Modem de Comunicacin
3-MODCOM
Detector de
Movimiento
MD
Mdulo
Ciclo de Seguridad
SEC2
Dispositivos
convencionales
de seguridad
Bus SAC
Lneas telefnicas
Distribuidor
Programa KDC
Estacin central
de supervisin
SDU
Otros factores
X Suministro de energa
X Configuracin hardware
RPM
Perfil de recursos
X Programacin SDU
X
Operacin ACDB/KDC
2.2
Security applications
Equipo
El equipo usado en aplicaciones de seguridad incluye:
Panel de control
Modulo Controlador de Signature
Mdulo de Deteccin de Movimiento SIGA-MD
Modulo de Ciclo de Seguridad SIGA-SEC2
Modulo de Acceso de Seguridad 3-SAC
Bus SAC
Monitor del teclado KPDISP
Mdulo de Mdem de Comunicacin 3-MODCOM
Herramienta Administrador de Perfil de Recursos RPM
Programa de Configuracin del Monitor del teclado KDC
Control panel
Es un requerimiento de la clasificacin UL que todos los
gabinetes en un sistema que incluye funciones de seguridad
deben tener un interruptor indicador de intrusin (tamper
switch). El panel de control debe incluir un tamper switch de
gabinete 3-TAMP, 3-TAMP5, o 3-TAMPRCC.
2.3
Security applications
Bus SAC
Ya que nuestros dispositivos de seguridad y control de acceso
requieren 24 Voltios de corriente directa, sugerimos que
siempre utilice un cable de 4 alambres (dos pares trenzados)
para el bus SAC y un suministro de energa de 24 Voltios de
corriente directa.
Para los cables de datos sugerimos par trenzado no
apantallado con ms de 6 vueltas por pie, en 14 a 22 AWG
(1.50 a 0.25 mm2).
Para los cables de energa, recomendamos 14 o 16 AWG.
2.4
Security applications
2.5
Security applications
Otros factores
Ahora, cubriremos los factores adicionales mencionados en el
diagrama:
2.6
Suministro de energa
Configuracin de hardware
Programacin del SDU
Operacin de ACDB/KDC
Security applications
Suministro de energa
El KPDISP est diseado para operar en 24 voltios de
corriente directa. Por esta razn, recomendamos que incluya
energa del panel con el cable del bus SAC. Puede usar el
suministro de energa del panel 3-PPS/M, 3-BPS/M, o
3-BBC/M.
Observe que los suministros adicionales de energa deben
estar listados para la aplicacin.
Programacin SDU
Mientras que el programa KDC controla una pequea porcin
de la base de datos de seguridad, todas las dems
definiciones, configuracin y programacin para el sistema
de seguridad sucede en el SDU.
El SIGA-MD y SIGA-SEC2 son ambos tratados como mdulos
en el circuito de datos de Signature. Usted puede configurar
cada mdulo de seguridad usando el SDU.
El SDU controla la configuracin general de los mdulos
3-SAC, adems de la configuracin de todos los dispositivos
CRC o KPDISP en los buses SAC.
Los mdulos KPDISP pueden ser configurados para ejecutar
una lista de comandos especficos pre-definidos cuando
ocurre un evento especfico de seguridad o control de acceso.
Usted anota las listas de comandos en la SDU, y los asigna a
eventos KPDISP cuando configura el mdulo KPDISP.
Las particiones son grupos esenciales usados con sistemas
de seguridad. Una particin es un grupo de dispositivos que
se pretende ofrezcan seguridad para un rea dada de la
ubicacin. Las particiones se pueden armar y desarmar por
separado.
Todas las particiones son creadas y definidas en la SDU, y
cada CRC, circuito de entrada CRC, KPDISP, circuito SIGASEC2, y circuito SIGA-MD puede ser asignado a una particin.
Las particiones tambin juegan un papel en el enrutado de
mensajes del KPDISP.
2.7
Security applications
Operacin ACDB/KDC
El programa Configuracin de la Pantalla del Teclado (KDC)
corre en la PC del usuario final. Le permite crear y mantener
una base de datos de informacin acerca de los KPDISPs,
usuarios, y niveles de acceso. Esto es parte de la base de
datos de seguridad general.
Durante la instalacin del programa, el usuario importa el
perfil de recursos creado por el RPM durante la programacin
del sistema.
Una vez instalado, el usuario puede crear y revisar su base de
datos KDC. Los cambios y adiciones se transmiten va mdem
al 3-MODCOM o a travs de una conexin directa RS-232 al
CPU. Los datos son entonces enrutados al 3-SAC correcto y
unidades KPDISP.
Aplicaciones de seguridad
Los temas restantes en este captulo cubren aplicaciones de
seguridad especficas. Cada tema le da una visin general de
la aplicacin y le muestra los componentes requeridos y su
interconexin.
Cada tema tiene un diagrama de bloque y una descripcin
general de la aplicacin. Otros factores (que intervienen en los
diagramas) se discutes bajo ttulos separados en cada tema.
2.8
Security applications
Instalaciones Certificadas
Descripcin de las aplicaciones
Se puede contratar a una compaa de instalacin para
instalar sistemas de alarma contra robos que estn cubiertas
por UL bajo su Servicio de Seguimiento. La compaa
contratada emite un certificado de la clase, grado y tipo
adecuado.
Este tema no detalla los pasos requeridos para la instalacin
de certificados. Usted debe seguir UL 681 para determinar los
requerimientos exactos para una instalacin especfica. Aqu
simplemente mencionamos equipo especial EST3 que puede
ser usado en las siguientes aplicaciones:
Equipo especial
Las instalaciones de certificados requieren del uso de equipo
de ataque e intrusin especializado. A continuacin hay una
serie de breves descripciones de las partes especiales. Los
diagramas para cada aplicacin muestran las partes que se
requieren.
ATCK Kit de Ataque: un kit de cubierta de reemplazo para el
gabinete 3-RCC7. El kit suministra un tiempo de demora de
ataque de dos minutos. Incluye una cubierta de la caja roja
sobrepuesta para el gabinete. La cubierta se sujeta a los
lados del backbox usando tornillos para hoja metlica y
cuatro seguros. El kit tambin incluye tapas ciegas que
aseguran los agujeros ciegos sin utilizar.
Interruptor de Intrusin Gabinete 3-TAMPRCC: Un interruptor
2.9
Security applications
Campana
Grado A
Autorizada
Panel de control
Ciclo de intrusin
Circuito de la campana
Los cables deben estar
en un conducto de metal
sin cajas ni otras
conexiones
3-IDC8/4
3-SAC
3-MODCOM
Tamper Switch del
Gabinete 3-TAMPRCC
Kit de Ataque ATCK
KPDISP
Bus SAC
Lneas telefnicas: una lnea
con prueba de 24 horas o dos
lneas con monitores de corte
de lnea
Otros factores
Estacin
central
de supervisin
Suministro energa
Configuracin hardware
X Programacin SDU
Operacin ACDB/KDC
2.10
Security applications
Panel de Control
3-SAC
3-MODCOM
Tamper Switch del
Gabinete 3-TAMPRCC
Kit de Ataque ATCK
KPDISP
bus SAC
Lneas telefnicas: una
lnea con prueba de 24
horas o dos lneas con
monitores de corte de lnea
Otros factores
Suministro de energa
Estacin
Central de
Supervisin
Configuracin hardware
X Programacin SDU
Operacin ACDB/KDC
2.11
Security applications
Campana
Grado A
y cubierta de
campana
Bucle de Intrusin
Circuito de campana
Los cables deben estar en
un conducto de metal sin
cajas ni otras conexiones
Panel de Control
bus SAC
3-IDC8/4
3-SAC
KPDISP
Tamper Switch de
Gabinete 3-TAMPRCC
Otros factores
Suministro de energa
Configuracin hardware
Programacin SDU
Operacin ACDB/KDC
2.12
Security applications
2.13
Security applications
2.14
Security applications
2.15
Security applications
CENTRO A
SDU
CENTRO B
Sistema
EST3
Sistema
EST3
SDU
RPM
RPM
Centro A
perfil
Centro B
perfil
Lneas telefnicas
CENTRO C (HQ)
Sistema
EST3
A
D1
D2
D3
ACDB
KDC
B
D1
D2
D3
C
D1
D2
D3
Centro C
perfil
Otros factores
rbol total de
Perfil de recursos
Suministro energa
X
Configuracin hardware
Programacin SDU
Operacin ACDB/KDC
RPM
SDU
2.16
Security applications
Configuracin de hardware
Cada centro debe tener un sistema EST3. En cada sistema
EST3, por lo menos un panel debe incluir un mdulo 3MODCOM para soportar la comunicacin por mdem entre
las oficinas centrales y lose centros A y B.
Los programas KDC y ACDB se pueden comunicar con el
sistema EST3 ya sea por mdem o por conexin directa un
puerto RS-232 en el mdulo CPU.
Cada sistema incluye mdulos 3-SAC que se requieran para
soportar los sistemas de seguridad y control de acceso
implementados.
Programacin SDU
No se requiere una programacin de proyecto especial para
habilitar sistemas mltiples de seguridad y control de acceso.
Al correr la herramienta RPM, cada centro recibe el 100% de
los recursos para ese centro.
Observe que todos los perfiles deben ser enviados al centro C
central cuando el proyecto este terminado.
Operacin ACDB/KDC
En las oficinas centrales, todos los tres perfiles son
importados al programa ACDB/KDC. El resultado es un rbol
global de recursos que incluye cada dispositivo KPDISP y CRC
en cada centro.
Importar todos los perfiles a un programa ACDB/KDC genera
la base de datos global.
Cuando se hacen adiciones o cambios a la base de datos
KPDISP, las oficinas centrales pueden transmitir los cambios a
todos los centros afectados.
2.17
Security applications
2.18
SIGA-IPS
Humo
Compaa A
Particin 2
Programa
KDC
KPDISP
X Configuracin hardware
X Programacin SDU
X Operacin ACDB/KDC
Suministro energa
Otros factores
Contacto
Puerta
Contacto
Puerta
KPDISP
SIGA-I PS
Humo
Compaa C
Particin 4
Movimiento
SIGA-MD
Door
contact
SIGA-270
Est. Palanca
Programa
KDC
SIGA-SEC2
Seguridad
Movimiento
SIGA-MD
SIGA-SEC2
Seguridad
SIGA-270
Est.
Palanca
SIGA-IPS
Humo
Compaa B
Particin 3
Programa
KDC
SI GA-SEC2
Seguridad
Movimiento
SIGA-MD
Campana
Seguridad
KPDISP
SAC bus
Panel de
control
Particin 1
Bucle SIGA
Movimiento
SIGA-MD
Lnea de Telfono
Security applications
2.19
Security applications
Configuracin de hardware
El panel de control contiene los siguientes mdulos de riel:
Programacin SDU
Al programar el sistema para esta aplicacin, usted define las
particiones necesarias y asigna el numero correcto de
particiones a cada dispositivo de seguridad.
Parte del esfuerzo de programacin incluye usar la
herramienta Administrador de Perfiles de Recursos (RPM)
para crear perfiles de recursos para el dueo del centro y
para cada compaa.
Ya que ninguno de los dispositivos es compartido, cada
compaa debe recibir el 100% de los recursos de su KPDISP.
Un pequeo porcentaje puede ser apartado para uso del
dueo del centro, dependiendo de la poltica del dueo.
La programacin de mdulo 3-MODCOM determina los
parmetros del marcador y del mdem, define los receptores
y cuentas y asigna cada cuenta al receptor correcto.
Finalmente al correr la herramienta RPM, usted especfica
cules, si es que alguno de los mdulos KPDISP, pueden
ejecutar comandos del sistema de incendios. Tpicamente
este privilegio est reservado para el dueo del centro o el
personal de seguridad del centro.
Consulte el Ayuda en lnea SDU para ms informacin.
2.20
Security applications
Operacin KDC
Cada dueo de compaa debe importar el resultado del perfil
de recurso del RPM. Despus de importar esta informacin de
recursos, cada dueo de compaa puede crear su porcin de
la base de datos de seguridad, de acuerdo a las instrucciones
incluidas con el programa KDC.
Los cambios hechos a la base de datos de seguridad de la
porcin pueden ser hechos en cualquier momento y desde
cualquier ubicacin.
Nota: La funcionalidad de incendio y seguridad no puede ser
2.21
Security applications
Acceso seguro
Descripcin de la aplicacin
Acceso seguro es un tipo simplificado de aplicacin de
seguridad. La aplicaciones tpicas de acceso seguros son
operadas desde el panel de control asegurado, y utilizan
particiones sin temporizador de demora de entrada o salida.
Las aplicaciones de acceso seguro frecuentemente usan el
mdulo LCD del control panel (o mdulos dedicados de
Control/LED) para controlar las particiones de seguridad. Las
particiones puede armarse o desarmarse usando alguno de
los siguientes:
Mens LCD
Mdulos EST3 Control/LED
Interaccin con FireWorks
Anunciadores ENVOY
KPDISP
Programacin SDU
Cuando usted crea una aplicacin de acceso seguro, utilice el
SDU para crear particiones como sea necesario. Al configurar
las particiones, fije los valores Entry Delay Timer y Exit Delay
Timer en cero. Al configurar dispositivos SIGA-SEC2 y SIGAMD, fije el Delay a None.
Usted puede usar comandos del men de LCD para armar o
desarmar las particiones. Para hacerlo, usted debe marcar el
recuadro de Enable LCD Security Control Functions. Este est
localizado en la pestaa de Options del cuadro de dialogo
Configuracin del Gabinete. Marcar este recuadro hace
aparecer el men de Seguridad en la lista de Mens de
Comandos.
Usted puede usar cualquier mdulo Control/LED apropiado
para armar y desarmar las particiones. Configure los
interruptores como interruptores de contacto momentneo, y
selos para activar las listas de comandos. Programe las
listas de comandos para llevar a cabo las acciones de
armado y desarmado y controlar los LEDs.
2.22
Security applications
2.23
Chapter 3
Aplicaciones de control de acceso
Resumen
3.1
Circuito entrada 1
Circuito entrada 2
Panel de control
Controlador
Lector de Tarjeta
CRC
Bus SAC
Mdulo Control de
Acceso Seguridad
3-SAC
Mdulo
Mdem de Comunicacin
3-MODCOM
Circuito salida
Lector tarjeta
Chapa
Lneas telefnicas
Distribuidor
Programa ACDB
Estacin central
de supervisin
SDU
Otros factores
X Fuente
Suministro
de energa
energa
RPM
X Configuracin hardware
Perfil de
Recurso
X Programacin SDU
X
Operacin ACDB/KDC
Equipo
A continuacin una lista del equipo usado en una sistema de
control de acceso en red:
3.2
Bus SAC
Ya que nuestros dispositivos de control de acceso y seguridad
requieren de 24 Voltios de corriente directa, sugerimos que
3.3
3.4
Opciones CRC
Sirena CRCSND CRC
Cada CRC tiene espacio para una batera interna de 1.2 Ah,
sellada de plomo-acido. La batera suministra energa al CRC
y sus perifricos y ofrece energa de reserva local.
La batera del CRC suministra 30 minutos de energa de
reserva para funciones de control de acceso y hasta 4 horas
para funciones de seguridad. La batera no puede ser usada
para aplicaciones de incendio.
Transformador CRCXF CRC
3.5
Circuitos de entrada 1 y 2
Cada CRC soporta dos circuitos de entrada para dispositivos
como:
Contactos de puerta
Detectores de movimiento
Interruptores de solicitud de salida (REX)
Dispositivos de seguridad
Circuito de salida
Cada CRC soporta un circuito de salida en la forma de
conexiones de contacto seco N.O. y N.C. El circuito de salida
puede ser usado para dispositivos como:
Lector de tarjeta
Por lector de tarjeta, nos referimos a cualquiera de los
diferentes tipos de lectores de credencial soportados por el
CRC. Un lector de tarjeta explora una tarjeta para determinar
el numero de tarjeta y lo enva al CRC.
Un lector de tarjeta es un mdulo independiente capaz de
leer un tipo de tarjeta de acceso y transmitir el cdigo de la
tarjeta a un controlador de lector de tarjeta.
Todos el sistema electrnico esta armado en el alojamiento
del lector de tarjeta. El lector de tarjeta se conecta
directamente al CRC, el cual procesa el cdigo de la tarjeta y
otorga o niega el acceso.
Cada CRC puede soportar varios lectores de tarjetas.
Tpicamente, el CRC controlar un lector de tarjeta de entrada
y salida para la entrada. Tambin puede soportar mltiples
lectores para aplicaciones como regla de dos personas o antipassback.
3.6
Proximidad
Pin Wiegand
Tira magntica
Cdigo de barra
Teclado
Tarjeta inteligente
Biometrica
Cerradura
El CRC soporta cualquier tipo de cierre de puerta o dispositivo
de apertura. Los dispositivos comunes de cierre de puerta
son magnticos o electrnicos. Uno electrnico abre la
puerta cuando se suministra energa, mientras que el
magntico asegura la puerta mientras se suministra energa.
Mtodo de comunicacin
3.7
Otros factores
Ahora, vamos a cubrir los factores adicionales mencionados
en el diagrama:
Suministro de energa
Configuracin del hardware
Programacin del SDU
Operacin ACDB/KDC
Fuente de energa
El CRC est diseado para operar en 24 Voltios de corriente
directa. Por esta razn recomendamos que incluya energa
del panel con el cable del bus SAC. Puede usar el suministro
de energa del panel 3-PPS/M, 3-BPS/M, o 3-BBC/M..
3.8
Programacin SDU
Mientras que el programa ACDB define la base de datos de
control de acceso, todas las dems definiciones,
configuracin y programacin del sistema de control de
acceso sucede en el SDU.
El SDU controla la configuracin general de los mdulos 3SAC, adems de la configuracin de todos los dispositivos
CRC en los buses SAC.
Los mdulos CRC pueden ser configurados para ejecutar una
lista de comandos especifica y predefinida cuando ocurre un
evento especfico de control de acceso. Usted escribe las
listas de comandos en el SDU, y los asigna a eventos del CRC
cuando configura el modulo CRC.
Las particiones son grupos fundamentales usados con
sistemas de control de acceso. Para usar funciones de
control de acceso como la regla de dos personas, reunin, o
anti-passback, los CRCs deben pertenecer a misma particin.
Todas las particiones son creadas y definidas en el SDU, y
cada CRC puede ser asignado a una particin.
Para el mdulo 3-MODCOM, el SDU determina los parmetros
de marcador y mdem, define los receptores y cuentas y
asigna cada cuenta al receptor correcto. Estas
configuraciones controlan el reporte CMS y la operacin de
descarga de ACDB.
3.9
Operacin ACDB
El programa ACDB le permite crear y revisar su base de datos
de control de acceso. Los parmetros almacenados en la
base de datos identifican a los tarjeta habientes, horarios y
vacaciones y asignan privilegios de acceso.
El SDU incluye una herramienta llamada Administrador de
Perfil de Recursos (RPM). El RPM le permite crear un perfil de
recursos para cada compaa usando el sistema para
propsitos de control de acceso. Durante la configuracin del
programa ACDB, usted importa el perfil de recursos creado
por el RPM. Esto define los dispositivos del sistema para el
programa ACDB.
El ACDB corre en su computadora. Usted puede conectar la
computadora al sistema de control de acceso de dos
maneras:
3.10
Desbloqueo estndar
Desbloqueo de discapacitados
Desbloqueo manual
Desbloqueo mnimo
3.11
Anti-passback
Descripcin de la aplicacin
Anti-passback es una funcin del sistema de control de
acceso que previene el uso sucesivo de una tarjeta para
pasar a travs de cualquier puerta en la misma direccin.
Anti-passback previene que una tarjeta sea pasada a otra
persona para tener acceso no autorizado.
El CRC soporta tres formas de anti-passback:
Estricto
Registrado
Medido
El anti-passback Estricto es la forma ms restringida de antipassback. Requiere que todo el personal se firme de entrada y
de salida, negndoles el acceso a una rea cuando no lo
hacen.
El anti-passback Registrado es menos restringido que el antipassback estricto. Tambin requiere que el personal se firme
de entrada y de salida pero no niega el acceso cuando se
violan las reglas de anti-passback. Dicho acceso es registrado
como un evento anti-passback con acceso otorgado. Con el
anti-passback, registrado el personal de seguridad puede
trabajar para corregir la violaciones, pero no se niega el
acceso al personal.
El anti-passback Medido previene la reutilizacin de una
tarjeta por un periodo especfico, pero no requiere que el
personal firme la salida. Un sistema medido de anti-passback
automticamente firma a un usuario fuera de la particin
controlada despus de un periodo de tiempo especfico,
permitiendo que la tarjeta sea usada nuevamente.
Nota: El anti-passback medido no puede ser usado con una
3.12
Torniquete
de
entrada
Reja perimetral
Lector
externo
Lector
interno
Circuito lector
Circuito cerradura
INSTALACIONES
Entrada
al edificio
CRC
bus SAC
Edificio principal
Panel de control
3-SAC
Salida de
emergencia
Otros factores
Fuente de energa
X Configuracin hardware
X Programacin SDU
X Operacin ACDB/KDC
3.13
Configuracin de hardware
El panel de control debe contener un mdulo de Control de
Acceso de Seguridad 3-SAC. El mdulo 3-SAC soporta el bus
SAC. La energa para el CRC puede ser tomada del 3-PPS/M y
enrutada con las lneas de datos en un doble cable trenzado
(el bus SAC).
Programacin SDU
Si el CRC va a ser usado para anti-passback esto debe ser
configurado usando el SDU. Los dilogos de configuracin del
CRC le permiten seleccionar el tipo de anti-passback que
quiere usar:
Ninguno
Registrado
Medido
Estricto
Programacin ACDB
Con el anti-passback medido, el usuario es automticamente
desmarcado despus de un periodo de tiempo especfico.
Este periodo esta definido por el ACDB. El periodo puede ser
fijado desde 0 hasta 255 minutos (4 horas y 15 minutos).
3.14
CRC
bus SAC
Panel de control
3-SAC
CPU
Reglas programadas
para transmisin
3-MODCOM
Mensaje CMS formateado
Lnea telefnica
Otros factores
Fuente de energa
Configuracin hardware
X
Programacin SDU
Estacin
Central de
supervisin
Operacin ACDB/KDC
3.15
Programacin SDU
Reportar eventos de control de acceso al CMS depende
completamente de la programacin y la creacin de listas de
comandos. En esencia, usted debe asignar una lista de
comandos a cada evento CRC que quiera reportar. La lista de
comandos contiene los detalles del mensaje que se va a
transmitir.
A los siguientes eventos CRC les pueden ser asignados
comandos de evento:
3.16
Acceso otorgado
Acceso irregular otorgado
Acceso anti-passback otorgado
Acceso otorgado rastreo y reunin
Acceso denegado desconocido
Acceso denegado lector inhabilitado
Acceso denegado nivel de acceso inactivo
Acceso denegado fuera de horario 1
Acceso denegado fuera de horario 2
Acceso denegado particin armada
Acceso denegado no ingreso NIP
Acceso denegado NIP invalido
Acceso denegado desconexin por tiempo dos-personas
Acceso denegado anti-passback
Acceso denegado acompaante
Puerta comn
CR 1
Dueo instalacin
Panel de control
ACDB
3-SAC
Modem
3-MODCOM
CRC 1
INSTALACIN
Lobby
bus SAC
Distribuidor
Suite 101
Dueo
Instalacin
CRC 2
Compaa A
SDU
Compaa
A
ACDB
Compaa
B
CR 2
RPM
Modem
Suite 102
Otros factores
ACDB
CRC 3
Compaa B
Perfiles de Recursos
X Configuracin Hardware
X Programacin SDU
Modem
CR 3
Fuente de energa
X Operacin ACDB/KDC
3.17
Configuracin hardware
La instalacin tiene un control panel EST3 que incluye un
3-SAC y un mdulo 3-MODCOM. El 3-SAC soporta el bus SAC.
El mdulo 3-MODCOM soporta comunicacion por mdem con
el panel de control a travs de lneas telefnicas.
Programacin SDU
Como distribuidor, usted utiliza el SDU para programar el
panel de control para esta aplicacin. Parte de la tarea de
programacin es utilizar el Administrador de Perfiles de
Recursos (RPM) para crear perfiles de recursos para el dueo
de la instalacin y para cada compaa arrendataria.
Los perfiles de recursos son importados al programa de Base
de Datos de Control de Acceso (ACDB). Estos determinan
cules dispositivos puede ver y programar el usuario. Los
perfiles de recursos tambin establecen rutas de transmisin
que permiten la comunicacin por mdem al panel EST3.
Cuando un dispositivo es compartido, el RPM le permite
especificar cuanto del dispositivo esta asignado cada
compaa. Usted puede destinar recursos ya sea por
porcentajes o nmeros reales.
Es una buena idea guardar una parte de reserva, dando a
cada compaa nicamente lo que necesita. Es ms fcil
asignar recursos adicionales como se requieran que
recuperar recursos que ya estn asignados.
En nuestro ejemplo el perfil de recurso para la compaa A
podra contener CRC 1 (la puerta del vestbulo) y CRC 2 (la
puerta de la suite 101). Para la Compaa A podra optar por
asignar 80% de CRC 2 y 20% de CRC 1.
De la misma manera, el perfil de recurso para la compaa B
asignara 80% de CRC 3 y otro 20% de CRC 1.
El dueo de la instalacin necesitar acceder a las puertas
CRC 2 y CRC 3 para limpieza o inspeccin. El perfil de recurso
del dueo de la instalacin podra asignar 20% de CRC1, 10%
de CRC2 y 10% de CRC3.
Esto deja 40% de CRC1 sin asignar, y 10% de CRC2 y CRC3 sin
asignar. Los recursos no asignados se reservan para futuras
expansiones o cambios.
3.18
Operacin ACDB
El dueo de la instalacin, el dueo de la Compaa A y el
dueo de la Compaa B pueden todos usar lneas telefnicas
para comunicarse con el panel de control a travs del mdulo
3-MODCOM. Pueden descargar adiciones y cambios a los
CRCs y cargar datos de uso para varios reportes ACDB.
3.19
Salida retardada
Descripcin de la aplicacin
Las puertas de salida retardada ayudan a controlar los robos
en establecimientos comerciales. Una puerta de salida
retardada tiene lectores de tarjeta y un interruptor de
solicitud de salida (REX). Los empleados pueden firmarse de
entrada y de salida como lo haran en cualquier otra puerta.
En una emergencia los clientes deben presionar el interruptor
REX para desbloquear la puerta.
Cuando se activa el interruptor REX, el CRC suena la sirena
CRCSND y enva un evento de alarma de seguridad al panel.
Esto no desbloquea la puerta de inmediato, dando tiempo al
personal de la tienda para investigar.
El CRC espera por un intervalo de tiempo especfico antes de
desbloquear la puerta . El tiempo tpico de retardo es de 15
segundos; sin embargo, usted puede usar una retardo de
hasta 30 segundos con la aprobacin de las autoridades. La
sirena sigue sonando por un periodo especfico de tiempo, o
hasta que se restablece el CRC.
Cuando pasa el tiempo de retardo, el CRC desbloquea la
puerta y la asegura en el estado de desbloqueo. El CRC debe
ser establecido para bloquear la puerta de nuevo y silenciar la
sirena. Para establecer el CRC, el personal del establecimiento
debe usar una identificacin valida en el lector de tarjeta.
El CRC tambin activa la sirena de CRCSND si la puerta es
abierta sin firmar la tarjeta. Por ejemplo, si la puerta es
forzada para abrir desde fuera, el CRCSND se activa , aun
cuando el interruptor REX no haya sido oprimido.
Muchos cdigos requieren que las puertas con salida
retardada se desbloqueen durante una alarma de incendio, o
cuando el panel esta en problemas. Este requerimiento
permite a los ocupantes evacuar las instalaciones
inmediatamente cuando se detecta un incendio o cuando el
panel pierde su habilidad de detectar un incendio o sonar la
alarma.
La Figura 3-5 muestra una puerta de salida retardada con
lectores de tarjeta internos y externos y un interruptor de
solicitud de salida. El CRC usa un interruptor de contacto de
puerta para determinar la posicin de la puerta y una
cerradura magntica para cerrar la puerta. El interruptor de
contacto de la puerta y el interruptor REX estn conectados a
los circuitos de entrada del CRC.
3.20
CRC
CRCSND
Contacto de
puerta
Lector de
tarjeta
afuera
Chapa
magntica
Interruptor
REX
Otros factores
Suministro
Fuente de energa
energa
X
Configuracin hardware
Programacin SDU
Operacin ACDB/KDC
Configuracin de hardware
Una chapa magntica es ms comnmente usada para
aplicaciones de salida retardada, pero se puede usar
cualquier dispositivo de cierre que no tenga control manual.
Por ejemplo se puede usar una barra sin manija.
El contacto de puerta es usado para detectar la apertura no
autorizada de la puerta. El CRC activa el CRCSND y reporta un
evento de alarma de seguridad cuando la puerta es abierta
sin firmar con la tarjeta o uso de REX.
La seal de contacto de puerta tambin requiere de
rebloquear la puerta cuando el CRC es restablecido. La chapa
no puede ser restablecida hasta que se cierra la puerta.
3.21
Programacin SDU
La mayora de los cdigos requieren que usted programe
reglas que desbloquean la puerta cuando el panel entra en
alarma o cuando el panel esta en problemas.
Al configurar el CRC, fije el campo de Tiempo de Retardo en
Salida al valor (en segundos) que quiera utilizar. Defina el
circuito de entrada como sigue.
Para el circuito de entrada del contacto de la puerta:
Operacin ACDB
Cuando un empleado se firma para entrar o salir de una
puerta, el CRC desva el contacto de la puerta por un periodo
de tiempo especifico. Esto es llamado el Tiempo de Bypass, y
se especifica en el ACDB.
La duracin de la sirena de CRCSND tambin es especificada
en el ACDB, como el Temporizador de la Sirena de la Salida de
Emergencia. Esto puede ser fijado a cualquier valor entre 0 y
255 segundos.
Fijar el valor a 0 segundos inhibe efectivamente el CRCSND.
Fijar el valor a 255 segundos programa el CRC para operar el
CRCSND hasta que el CRC sea restablecido manualmente al
pasar una tarjeta por el lector de tarjeta CRC.
3.22
3.23
Cuarto Elevador
SIGA -CR
Circuitos de
habilitacin de piso
SIGA -CR
SIGA -CR
Cable de viaje
del elevador
Circuito de datos Signature
Cuarto El ctrico
bus SAC (usando doble
cable trenzado
de repuesto)
Panel de control
Controlador
Signature
CPU
3-SAC
Cabina elevador
Panel del
operador
CRC
Otros factores
Lector
tarjeta
X Fuente energa
Transformador
CRCXF
X Configuracin hardware
X Programacin SDU
X Operacin ACDB/KDC
Fuente de Energa
La figura muestra una fuente independiente de energa para
el CRC. Esto es recomendable debido a la longitud del cable
de la cabina al cuarto de electricidad.
3.24
Configuracin hardware
En esta aplicacin, no se utiliza ninguno de los circuitos de
entrada del CRC o contactos de relevador. El CRC
simplemente lee la tarjeta y pasa la solicitud de lista de
comandos al 3-SAC y CPU para procesarla.
Ya que no se utilizan el cierre CRC y los circuitos de entrada,
debe proporcionar cargas de imitacin para mantener la
supervisin correcta de las corrientes. Ver la hoja de
instalacin para los valores de carga correctos.
Programacin SDU
El programador SDU debe crear una lista de comandos para
cada combinacin de pisos deseada.
Operacin ACDB
El oficial de seguridad de las instalaciones determina qu
pisos deben ser accesibles para un nivel de acceso, y asigna
la lista de comandos correcta al evento de acceso otorgado
para ese nivel. El oficial de seguridad de las instalaciones
tambin determina que usuarios pertenecen a cada nivel de
acceso.
3.25
CRC
Contacto
de puerta
CRCSND
Lector de
tarjeta
afuera
Lector de
tarjeta
adentro
Barra
Otros factores
Fuente de energa
X
Configuracin hardware
Programacin SDU
Operacin ACDB/KDC
Configuracin de hardware
Un CRC usado para una puerta de salida de emergencia
requiere lo siguiente hardware adicional:
3.26
Programacin SDU
En el SDU, usted tendr que definir el circuito de entrada para
el contacto de la puerta como sigue:
Operacin ACDB
En el ACDB se definen dos periodos de tiempo: Tiempo de
Sirena de la Salida de Emergencia, y Tiempo de Bypass.
El Tiempo de Sirena de la Salida de Emergencia es el numero
de segundos (0 a 255) que la Sirena CRC suena cuando se
abre una puerta de salida de emergencia sin pasar la tarjeta
por el lector.
Cuando se fija en cero, la sirena est inhabilitada. Cuando se
fija en 255, la sirena suena hasta que es restablecida
manualmente. La sirena se restablece cuando un usuario
pasa una tarjeta por el lector de entrada de la puerta.
En todos los casos, pasar la tarjeta en el CRC afectado puede
silenciar la sirena.
El Tiempo de Bypass es el numero de segundos (0 a 255) que
la puerta es puenteada despus de que el usuario pasa la
tarjeta para salir.
3.27
3.28
CRC
Lector de
tarjeta
adentro
Lector de
tarjeta
afuera
Lector de
tarjeta
discapacitados
afuera
Abridor
de puerta
Chapa
Lector de
tarjeta
discapacitados
adentro
Otros factores
Fuente de energa
X
Configuracin hardware
Programacin SDU
Operacin ACDB/KDC
Configuracin hardware
Un CRC usado para una puerta de acceso de discapacitados
puede requerir del siguiente hardware adicional:
3.29
Programacin SDU
En el SDU, usted tendr que definir el tipo de dispositivo
relevador del CRC como Control de Puerta de Acceso. Este
activar el abridor de la puerta por el tiempo especificado en
el ACDB.
Operacin ACDB
El tiempo de apertura del relevador tiene que ser definido en
el ACDB. Este es el numero de segundos (0 a 255) que el CRC
activar el relevador que abre la puerta automticamente. El
tiempo por defecto es de 30 segundos.
El tiempo de desbloqueo para discapacitados tambin tiene
que ser definido en la ACDB. Este es el nmero de segundos (0
a 255) que la chapa permanecer desbloqueada. El defecto
es 20 segundos. La puerta se cerrar cuando expire el tiempo
de desbloqueo y la puerta se haya cerrado.
Estos dos tiempos se pueden fijar para permitir un tiempo de
acceso ms largo para una persona discapacitada.
3.30
3.31
CRC
Detector
pasivo
infrarrojo
Chapa
Magntica
Interruptor
solicitud
salida
Otros factores
Fuente de energa
X
Configuracin hardware
Programacin SDU
Operacin ACDB/KDC
Configuracin hardware
Los perifricos de la chapa magntica consisten de lo
siguiente:
Programacin SDU
Al programar el sistema para esta aplicacin necesitar
configurar el CRC, definiendo el tipo de dispositivo. Tambin
tendr que definir los circuitos de entrada. Para esta
aplicacin defina el circuito de entrada para el PIR como
sigue:
3.32
CRC
Lector
tarjeta de
proximidad
Lector
tarjeta cdigo
de barras
Lector
tarjeta de
proximidad
Lector
tarjeta cdigo
de barras
3.33
Lector de tarjeta
Esta aplicacin trabaja mejor con lectores de tarjeta que
soportan control LED dual. El CRC utiliza el segundo LED (o
estado de LED) para indicar al visitante que el acompaante
debe pasar su tarjeta antes de que se otorgue el acceso.
Configuracin hardware
Los lectores de proximidad y de cdigo de barras estn
conectados a las mismas terminales del CRC.
Programacin SDU
Cuando un visitante acompaado trata de entrar a un rea
controlada sin un empleado, el CRC genera un evento de
acceso denegado acompaante. Usted puede seleccionar un
lista predefinida de comandos que el CPU ejecuta en
respuesta a este evento.
Operacin ACDB
Al igual que los empleados, los visitantes deben ser asignados
un nivel de acceso usando la ACDB. El oficial de seguridad de
las instalaciones puede elegir asignar el mismo nivel de
acceso a todas las tarjetas de visitantes, o asignar diferentes
niveles de acceso a rangos de tarjetas de visitante.
3.34
Rastreo y Reunin
Descripcin de la aplicacin
La aplicacin de rastreo y reunin puede ser usada para
determinar quien ha salido del edificio en el caso de una
evacuacin.
Durante operaciones normales, el personal se registra de
entrada y de salida usando los lectores internos y externos.
Observe que el reporte de rastreo nicamente funcionar si
todos los empleados registran su entrada y su salida.
Durante una evacuacin, todos salen del edificio
inmediatamente y se dirigen a una de las estaciones de
reunin predeterminadas. En la estacin de reunin el
personal se registra usando un lector que esta conectado a
un CRC designado como estacin de reunin.
Una vez que todos se han registrado en la estacin de
reunin, el personal de seguridad utiliza el programa ACDB
para crear un reporte de rastreo. El reporte muestra una lista
del personal que entr al edificio pero que no se registro en la
estacin de reunin.
La Figura 3-11 muestra una aplicacin de rastreo y reunin
tpica. Los CRCs 2, 3, 5, y 6 son CRCs de control de acceso
normal. Los CRCs 1 y 4 son CRCs de estaciones de reunin.
La computadora ACDB debe estar ubicada en un rea segura
para que el personal de seguridad pueda crear el reporte de
rastreo despus de la evacuacin. Esta computadora se
puede conectar al sistema de control de acceso por medio de
las lneas telefnicas y un 3-MODCOM, o por conexin directa
al control panel EST3.
Nota: Las ligas entre la computadora ACDB y el panel de
3.35
Estacin reunin
Lector de tarjeta
Entrada
CRC 2
Entrada
CR afuera
CR adentro
CR afuera
CR adentro
CRC 3
CRC 1
bus SAC
Panel de control
3-SAC
3-PPS/M
MODCOM
CRC 4
CR adentro
CR afuera
CRC 6
CR adentro
CR afuera
Salida de
emergencia
CRC 5
Salida de
emergencia
Lnea telefnica
Otros factores
Reporte estacin
de reunin
Lector de tarjeta
X Fuente de energa
X Configuracin hardware
Estacin de reunin
ACDB
X Programacin SDU
X Operacin ACDB/KDC
3.36
Configuracin hardware
El panel de control debe contener los siguientes mdulos de
riel:
Programacin SDU
Cada CRC utilizado en una aplicacin de rastreo y reunin
requiere de configuraciones. Estas son realizadas en el
programa SDU, en la pestaa de Configuracin CRC.
Si el CRC es usado en una particin que tiene control de
rastreo y reunin, marque la opcin de Muster Support.
3.37
3.38
3.39
Panel de control
3-PPS/M
3-SAC
24 Vdc
bus SAC
Fuente de energa
de 24 Vdc o
transformador
CRCXF
CRC
Otros factores
Lector de
tarjeta
Chapa de
barra o
magntica
Fuente de energa
Configuracin hardware
Programacin SDU
Operacin ACDB/KDC
Fuente de energa
Use clculos de energa y carga para determinar la necesidad
de fuentes de energa remota o transformadores. Consulte el
Manual de referencia Tcnico del CRC para normas de
clculos.
La configuracin de puentes determina la fuente de energa y
uso para el CRC. Consulte la hoja de instalacin para
3.40
Configuracin de hardware
El panel de control debe contener lo siguientes mdulos de
riel:
Programacin SDU
Al configurar el sistema para esta aplicacin, usted tendr
que configurar el CRC y definir el tipo de chapa apropiada en
el SDU. Para esta aplicacin la chapa puede ser de Barra o
Magntica como sea necesario para igualar la chapa usada
realmente.
3.41
3.42
Panel de control
3-PPS/M
3-SAC
24 Vdc
bus SAC
CRC
Otros factores
X Fuente de energa
Lector de
tarjeta
X Configuracin hardware
Barra
X Programacin SDU
X
Operacin ACDB/KDC
Fuente de energa
La configuracin de puentes determina la fuente de energa y
uso para el CRC. Consulte la hoja de instalacin para
configuraciones correctas de puentes. Configure la energa de
entrada como DC. Configure la energa de salida como
intermitente.
Configuracin de hardware
El panel de control debe contener los siguientes mdulos de
riel:
3.43
Programacin SDU
Al configurar el sistema para esta aplicacin, usted tendr
que configurar el CRC y definir el tipo de chapa apropiada en
el SDU. Para esta aplicacin defina el Tipo de Chapa como
Strike.
Operacin ACDB
Observe que una CRC configurada y programada para uso de
chapas intermitentes no puede soportar un horario abierto
(un periodo en el que la chapa se mantiene abierta). Dicho
horario rpidamente drenara la batera CRC y la chapa se
cerrara.
Usted debe documentar la configuracin del CRC e incluir
esto en sus planes del proyecto. Entregue una copia de esta
documentacin al personal de seguridad que usar el ACDB
para crear y asignar horarios.
3.44
3.45
Panel de control
3-PPS/M
3-SAC
24 Vdc conecta a las
terminales CRC, pero
puentea al CRC
internamente
bus SAC
Detector
infrarrojo
pasivo
Transformador
CRCXF
CRC
Lector de
tarjeta
Barra o
chapa
magntica
Otros factores
X
Fuente de energa
Configuracin hardware
Programacin SDU
Botn de
solicitud
de salida
Operacin ACDB/KDC
3.46
Panel de control
Transformador
CRCXF
(16.5 Vac)
Fuente energa
CRC
CRC
CRC
24 Vdc
24 Vdc
24 Vdc
24 Vdc
Fuente de energa
La configuracin de puentes determina la fuente de energa y
uso para el CRC. Configure la energa de entrada como AC.
Configure la energa de salida como continua.
Si usted usa una fuente de energa adicional diferente al
CRCXF, esa fuente debe estar registrada para aplicaciones de
alarma de incendios, debe tener inhabilitada la deteccin de
defecto a tierra, y debe tener una masa del circuito que est
aislada de tierra.
Programacin SDU
Al programar el sistema para esta aplicacin, necesita
configurar el CRC y definir el tipo adecuado de chapa en el
SDU. Esta puede ser ya sea de barra o magntica.
3.47
3.48
Panel de control
3-PPS/M
bus SAC
3-SAC
+24 Vdc puentea CRC
Controlador
Signature
Detector
infrarrojo
pasivo
Fuente de
energa
remota
24 Vdc
CRC
Lector de
tarjeta
Chapa
magntica
o barra
Botn de
solicitud
de salida
Otros factores
X Fuente de energa
X Configuracin hardware
X Programacin SDU
Operacin ACDB/KDC
3.49
Panel de control
Fuente de
energa remota
24 Vdc
Fuente energa
CRC
CRC
CRC
24 Vdc
24 Vdc
24 Vdc
24 Vdc
Fuente de energa
La configuracin de puentes determina la fuente de energa y
uso para el CRC. Configure la energa de entrada como DC.
Configure la energa de salida como continua.
Observe que fuentes de energa adicionales deben estar
registradas para aplicaciones de alarma de incendios, debe
tener inhabilitada la deteccin de defecto a tierra, y debe
tener una masa del circuito que est aislada de tierra.
Configuracin de hardware
El panel de control debe contener los siguientes mdulos de
riel:
3.50
SDU programming
Al programar el sistema para esta aplicacin, necesita
configurar el CRC y definir el tipo adecuado de chapa en el
SDU. Esta puede ser ya sea de barra o magntica.
3.51
Controles remotos
Descripcin de la aplicacin
En un sistema de control de acceso, un lector de tarjeta y CRC
pueden ser usados para operar dispositivos que estn
completamente remotos del CRC. En dichos casos el CRC
simplemente genera un evento de acceso y se lo enva al 3SAC para el procesamiento por el CPU. Cualquier dispositivo
que pueda ser controlado por un panel EST3 puede ser
operado en respuesta a un evento de acceso.
Como un tpico ejemplo, la Figura 3-18 muestra como los
dispositivos de entrada a un rea de estacionamiento
asegurada pueden ser operados desde un lector de tarjeta
remoto. Observe que cualquier tipo de dispositivo de entrada
CRC puede ser usado en lugar de un lector de tarjeta.
Panel de control
3-SAC
CPU
Listas de comandos
Controlador
Signature
SAC bus
Lector de
tarjeta
CRC
Relevador
Signature
Abridor
de reja
Relevador
Signature
VCR
Relevador
Signature
Foco
Otros factores
X Fuente de energa
Configuracin hardware
CRCXF
X Programacin SDU
Operacin ACDB/KDC
3.52
Fuente de energa
Un Transformador CRCXFCRC se muestra como fuente de
energa, asumiendo que el CRC sera colocado a alguna
distancia del cuarto de electricidad y panel de control.
Si usted usa una fuente de energa adicional diferente al
CRCXF, esa fuente de energa estar registrada para
aplicaciones de alarma de incendios, debe tener inhabilitada
la deteccin de defecto a tierra, y debe tener una masa del
circuito que est aislada de tierra.
Programacin SDU
El programador SDU debe generar una lista de comandos que
especifica la activacin de los relevadores y dispositivos
correctos, los retrasos requeridos y la desactivacin de los
dispositivos.
Ya que hay una fase de restauracin de los eventos de
acceso, la lista de comandos debe incluir comandos que
apaguen los dispositivos.
3.53
3.54
Panel de control
3-SAC
bus SAC
3-PPS/M
Entrada 1
CRC 1
CR afuera
CR adentro
Cuarto controlado
CR adentro
CR afuera
CRC 2
Entrada 2
Otros factores
X Fuente de energa
X Configuracin hardware
X Programacin SDU
X Programacin ACDB/KDC
Lector de tarjeta
Esta aplicacin trabaja mejor con lectores de tarjeta que
soportan control LED dual. El CRC utiliza el segundo LED (o
estado LED) para indicar al usuario que una segunda persona
debe pasar la tarjeta para entrar o salir del rea controlada.
Configuracin hardware
El panel de control debe contener los siguientes mdulos de
riel:
Mdulo Control de Acceso de Seguridad 3-SAC
Mdulo Suministro de Energa Principal 3-PPS/M
3.55
Programacin SDU
Si el CRC ser usado para una regla de dos personas debe ser
configurado en el SDU. En la pestaa de Configuracin del
CRC, debe activarse la opcin de Regla de dos personas.
Tambin puede asignar una lista de comandos predefinida al
evento Acceso denegado desconexin por tiempo dospersonas. Esta configuracin se encuentra en la pestaa de
Lista de Comandos CRC.
3.56
Chapter 4
Aplicaciones de audio centralizado
Resumen
4.1
Equipo requerido
El sistema EST3 requiere un amplificador 3-ZA20 para cada
canal de audio que va a ser operado simultneamente. La
salida de cada amplificador es reducida de 25 Vrms al nivel
adecuado de entrada (1 Vrms) usando la interfaz de 3-ATPINT,
y luego alimentado a la entrada de los amplificadores
agrupados.
El cableado entre la salida de cada 3-ZA20 y la entrada de su
amplificador agrupado asociado debe ser un par trenzado
protegido, y puede ser configurado para la supervisin de
integridad Clase A o Clase B.
La salida de los amplificadores agrupados (contrahuella de
audio) se dirige a las reas adecuadas usando mdulos de la
Serie Signature. El mdulo SIGA-CC1, Figura 4-16, es usado
para sistemas de un solo canal y el mdulo SIGA-CC2, Figura
4-17, es usado en sistemas de dos canales.
La programacin de sistema de audio EST3 requiere que los
mdulos Signature que controlan las seales de audio sean
programados adems de la programacin requerida para los
amplificador(es) 3-ZAxx que suministran la seal de audio.
Nota: Recuerde seguir la prcticas de cableado limitadas o no
4.2
4.3
Ancho
Altura
Profundidad
Espacio en
armazn
RKU-36(B)
22.31 in
(56.7 cm)
41.06 in
(104.3 cm)
18.50 in
(47.0 cm)
36.75 in
(93.3 cm)
RKU-42(B)
22.31 in
(56.7 cm)
46.31in
(117.6 cm)
18.50 in
(47.0 cm)
42.00 in
(106.7 cm)
RKU-61(B)
22.31 in
(56.7 cm)
65.56 in
(166.5 cm)
18.50 in
(47.0 cm)
61.25 In
(155.6 cm)
RKU-70(B)
22.31 in
(56.7 cm)
74.31in
(188.7 cm)
18.50 in
(47.0 cm)
70.00 in
(177.8 cm)
RKU-77(B)
22.31 in
(56.7 cm)
81.31 in
(206.5 cm)
18.50 in
(47.0 cm)
77.00 in
(195.6 cm)
4.4
4.5
S
PRE-AMP 1
PREAMP 1
70V 25V
IN
OUT RISER
OUT PRE-AMP
IN
OUT RISER
OUT PRE-AMP
1 P1
PREAMP 2
70V 25V
1 P2
PRE-AMP 2
S
[3atpint3.c dr]
4.6
Batera de respaldo
Cuando varios ATPs
comparten una batera
comn, de debe usar un
cargador externo de
bateras.
4.7
Amplificadores de audio
Existen dos amplificadores Dukane disponibles. El Modelo
1B3125 tiene 125 watts de salida. El Modelo 1B3250 tiene una
salida de 250 watts. Ambos amplificadores operan de 120
Vac, 50/60 Hz, as como de 24 Vdc batera de respaldo. Los
amplificadores estn montados en un Gabinete de Panel
Terminal de Amplificador.
Nota: El amplificador Modelo 1B3250 debe ser cargado a no
Two F ifty
THERMAL
OVERLOAD
POWER
[C1B3250X.CDR]
4.8
Energa de salida
125 W
1 Vrms
Impedancia de entrada
75 k
Voltaje de salida
25 or 70 Vrms
120 Vac, 60 Hz
Energa de la batera
24 Vdc
Consumo de energa AC
reserva
carga completa
27 W
360 W
Consumo de energa DC
reserva
carga completa
Dimensiones (HWD)
Peso
1 Vrms
Impedancia de entrada
75 k
Voltaje de salida
25 or 70 Vrms
120 Vac, 60 Hz
Energa de la batera
24 Vdc
Consumo de energa AC
reserva
carga completa
48 W
700 W
Consumo de energa DC
reserva
carga completa
Dimensiones (HWD)
8.5 x 19 x 15 in
(21.6 x 48.3 x 38.1 cm)
Peso
55 lb (24.9 kg)
4.9
Aplicacin
Se requiere un URSM en contrahuellas de sistemas de audio
de 70 Vrms y sistemas de audio de 25 Vrms. El URSM debe
ser colocado en un gabinete de equipo conveniente al final de
las contrahuellas que tengan un fuente de energa de 24 Vdc
disponible. Los contactos de problema del URSM deben ser
supervisados con un mdulo SIGA-CT2 para indicar
informacin de problema de contrahuella de regreso a la red.
La entradas de contrahuella del URSM deben ser conectadas
a un GFD, que proporciona supervisin de fallas de tierra. El
GFD debe ser monitoreado por un modulo SIGA-CT1 para
indicar condiciones de falla de tierra de la contrahuella de
regreso a la red. El GFD y SIGA-CT1 deben ser instalados en la
misma caja y debe estar ubicados junto al panel de control de
la alarma de incendio.
Tabla 4-4: Especificaciones URSM
Voltaje
24 Vdc
Corriente de Reserva
40 mA
4.10
10 Vrms
23 Vrms
2.7 Vrms
Instalacin
El URSM requiere la mitad de una planta de montaje y debe
ser instalado en donde los pigtails de energa puedan
alcanzar la fuente de energa.
El GFD y CT1 deben estar instalados en la misma caja,
ubicada adyacente al panel de control de la alarma de
incendios. El Puente JP1 en el GFD debe ser fijado a la
posicin 2-3.
Conexiones terminal
Consulte la Figura 4-6.
Pigtail negra = (-)24 Vdc power in
Pigtail roja = (+)24 Vdc power in
TB11 a 3 = Canal 2, contactos relevadores de problema
TB14 a 6 = Canal 1, contactos relevadores de problema
TB17 = Canal 2, 70 Vrms entrada contrahuella de audio
TB18 = Canal 2, 25 Vrms entrada contrahuella de audio
TB19 = Entrada de contrahuella Telfono Bomberos, Ch 2
TB110 = Canal 2, entrada contrahuella, comn
TB111 = Canal 1, 70 Vrms entrada contrahuella de audio
TB112 = Canal 1, 25 Vrms entrada contrahuella de audio
TB113 = Entrada de contrahuella Telfono Bomberos, Ch 1
TB114 = Canal 1, entrada contrahuella, comn
Operacin
El relevador de problema se activar 4560 segundos
despus de detectar un corto circuito, un circuito abierto, o
una falla del amplificador.
4.11
++
16 15 14 13
+ +
3-2-1
JP1
IN
OUT
Circuit pair 1
GFD
7
IN
OUT
Circuit pair 2
LED1 LED2
Earth Power
GND
8
12 11 10
TB2
Trouble/GF Contacts
NC COM NO
8 7
SIGA-CT1
To earth
ground
Polarity is not
important
From UL/ULC
listed 24 VDC
fire alarm panel
4 3 2 1
UL/ULC listed
47 K ohm EOL
TB1
Data in (+)
From signature ()
controller or
previous device
UL/ULC listed
47 K ohm EOL
[2] [3]
URSM
G
10
11
12
13
14
CONT 5A RES.240AC
URSM
130102
1725S DC 24V
A410-367396-13
JAPAN 692NA
TB1
CONT 5A RES.240AC
CHANNEL 2
TROUBLE
CHANNEL 1
TROUBLE
1725S DC 24V
A410-367396-13
JAPAN 692NA
TELEPHONE
25V AUDIO
70V AUDIO
CHANNEL 2
[1] [2]
TB2
[3] Nonpower-limited
4. The GFD and CT1 must
be installed in the same
enclosure
5. Jumper J1 on the GFD
should be set to the
2-3 position
SIGA-CT2
Black
Red
4 3 2 1
TB1
[2]
[1] [2]
Data in
Wiring notes
[1] Supervised
[2] Power limited
8 7 6 5
TELEPHONE
25V AUDIO
70V AUDIO
CHANNEL 1
(+)
(+)
()
()
Data out
To next device
4.12
[1]
[2]
[3]
[4]
[5]
[6]
[3atpint2.cdr]
4.13
Cableado ATP
Do Not Use
+
TB1
S +
IN
OUT
PREAMP # 1
IN
OUT RISER
OUT RISER
WARNING
TB4
BATT.
OUT
120VAC
60HZ
10A MAX.
OUT PRE-AMP
IN
TB2
+
PREAMP # 2
OUT
S +
S +
FUSE
TB5
PWR AMP # 2
IN
OUT
S +
BATT. IN
24 VDC
40AH MAX.
AMP # 2
OUT
H
G
3AB-20A
PREAMP 2
70V 25V
WARNING
PRE-AMP 2
IMPROPE
R
CONNE
CT
ION
OF T-ERMINAL
S
+
S
+
S +
S
WILL RESULTIN A FAILURE OF POWER SUPPLY
S +
OUT
IN
PWR AMP # 1
TB3
Removable 3-AT
Cover
PINT
IN
OUT
S +
OUT PRE-AMP
1 P1
1 P2
S +
AMP # 1
PRE-AMP 1
PREAMP 1
70V 25V
S +
S +
BATT.
OUT
S +
+
[3atpint1.cdr]
Do Not Use
Figura 4-8: ATP con el 3-ATPINT instalado, vista trasera
4.14
Configuracin Puente
J1 = habilitar
J1 = inhabilitar
J2 = in
J3 = in
4.15
4.16
Entrada / Voltaje
Configuracin Puente
P1 = 1/2
P1 = 2/3
P2 = 1/2
P1 = 2/3
15K EOL
15K EOL
10
15K EOL
10
15K EOL
10
10
TB1
AUDIO
AMPLIFIER
MODULE
AUDIO
AMPLIFIER
MODULE
AUDIO
AMPLIFIER
MODULE
AUDIO
AMPLIFIER
MODULE
(Riser 1)
(Riser 2)
(Riser 3)
(BACKUP)
TB2
10
10
10
10
Shield,
if used
[3AMPCON1.CDR]
Shield,
if used
From Power
Amp Output
To Power
Amp Audio
Input
2 3
Do Not Use
2 3
+
TB1
S +
IN
OUT
PREAMP # 1
IN
OUT RISER
OUT
S +
WARNING
1 P1
TB4
BATT.
OUT
TB3
S +
OUT
IN
PWR AMP # 1
OUT PRE-AMP
IN
OUT RISER
OUT PRE-AMP
IN
PREAMP # 2
OUT
S +
S +
PWR AMP # 2
IN
OUT
S +
3AB-20A
FUSE
TB5
AMP # 2
OUT
BATT. IN
24 VDC
40AH MAX.
PRE-AMP 2
120VAC
60HZ
10A MAX.
PREAMP 2
70V 25V
1 P2
S +
AMP # 1
PRE-AMP 1
PREAMP 1
70V 25V
S +
S +
BATT.
OUT
S +
[3AMPCON1.CDR]
Do Not Use
Wiring Notes
JUMPER SETTINGS
P1 = 1/2, Pre-Amp #1 Input 70 VRMS
P1 = 2/3, Pre-Amp #1 Input 25 VRMS
P2 = 1/2, Pre-Amp #2 Input 70 VRMS
P2 = 2/3, Pre-Amp #2 Input 25 VRMS
1.
2.
3.
4.
5
4.17
FUSE 25A
LEVEL ADJUST
70.7 V
25 V
25 V
CT
8 OHM
OUTPUT
COM
BRIDGING
INPUT
COM
FUSE 6.25A SB
EARTH
24 VDC
120VAC
60HZ
N/C
TO ATP
POWER RECEPTACLE
AUDIO
RISER
OUT
Do Not Use
+
TB1
S +
IN
OUT
PREAMP # 1
OUT RISER
IN
1 P2
IN
OUT RISER
S +
OUT
IN
PWR AMP # 1
WARNING
BATT.
OUT
OUT PRE-AMP
120VAC
60HZ
10A MAX.
IN
TB2
+
PREAMP # 2
OUT
S +
S +
FUSE
TB5
PWR AMP # 2
IN
OUT
Do Not Use
S +
BATT. IN
24 VDC
40AH MAX.
AMP # 2
OUT
H
G
3AB-20A
PRE-AMP 2
TB4
3-ATPINT
PREAMP 2
70V 25V
OUT
S +
OUT PRE-AMP
TB3
1 P1
S +
AMP # 1
PRE-AMP 1
PREAMP 1
70V 25V
S +
S +
BATT.
OUT
S +
[3ATPINT6.CDR]
4.18
Figura 4-11: Tarjeta terminal de fuente de energa, con 3-ATPINT, sin cubierta
FUSE 25A
70.7 V
25 V
25 V
CT
8 OHM
OUTPUT
COM
BRIDGING
INPUT
COM
FUSE 6.25A SB
EARTH
24 VDC
120VAC
60HZ
N/C
4.19
4.20
ATP
BATTERY
INPUT
120 VAC
J3
CHARGER
DISABLE
PANEL
TROUBLE
ATP
BATTERY
INPUT
120 VAC
J3
CHARGER
DISABLE
PANEL
TROUBLE
120 VAC
BATTERY
CHARGER
AA33-10-24
+
LOAD
BATTERY TRBL
[3ATPXBCW.CDR]
1 Supervised
2 Power Limited
8 7
SIGA-CT1
Single Input Module
(Personality Code 3)
4
3 2 1
DATA IN (+)
DATA OUT(+)
DATA IN (-)
DATA OUT(-)
To Next Device
4.21
4.22
'AMP1_FAIL' 'AMP2_FAIL'
MODULES REPORT RISER TROUBLE
TO NETWORK CONTROLLER
'AMP3_FAIL'
7 6 5
7 6 5
7 6 5
3 2 1
3 2 1
3 2 1
URSM
URSM
URSM
1
RKU SERIES ENCLOSURE
ARA-1 RELAY
EOL
RELAY ACTIVATES ON
AMP 1 FAILURE
PRE-AMP OUT IN
OUT 1
AMP 1
IN
RISER 1
OUT
3-ATPINT
7 6 5
3 2 1
'AMP1_BKUP'
ATP 1
AUDIO POWER
AMPLIFIER 1
AUDIO POWER
AMPLIFIER 2
IN
ACT
RISER 2
OUT PRE-AMP AMP 2
OUT 2
OUT IN
SIGA-CR DEFINED AS
NONSUPERVISED OUTPUT
ARA-1 RELAY
RELAY ACTIVATES ON
AMP 2 FAILURE
SIGA-CR DEFINED AS
NONSUPERVISED OUTPUT
+24VDC
4
7 6 5
3 2 1
'AMP2_BKUP'
7 6 5
SIGA-CR DEFINED AS
NONSUPERVISED OUTPUT
3 2 1
'ATP1_ACT'
ARA-1 RELAY
PRE-AMP OUT IN
OUT 3
AMP 3
IN
RISER 1
OUT
3-ATPINT
RELAY ACTIVATES ON
AMP 3 FAILURE
8
7 6 5
3 2 1
'AMP3_BKUP'
ATP 2
AUDIO POWER
AMPLIFIER 3
IN
ACT
RISER 2
OUT PRE-AMP AMP 4
OUT 4
OUT IN
AUDIO POWER
AMPLIFIER 4
SIGA-CR DEFINED AS
NONSUPERVISED OUTPUT
SIGA-CR DEFINED AS
NONSUPERVISED OUTPUT
8
7 6 5
3 2 1
+24VDC
'ATP2_ACT'
BACKUP RISER
FROM 3-ZAxx
'AMP1_PRI'
1 Supervised
2 Power Limited
3 Not Power Limited
(3ATPINT5.CDR)
4.23
7 6 5
7 6 5
7 6 5
7 6 5
3 2 1
3 2 1
3 2 1
3 2 1
URSM
CH1
URSM
CH2
URSM
CH1
URSM
CH2
ARA-1 RELAY
PRE-AMP OUT IN
OUT 1
AMP 1
EOL
EOL
IN
RISER 1
OUT
3-ATPINT
ATP 1
IN
ACT
RISER 2
OUT PRE-AMP AMP 2
OUT 2
OUT IN
RELAY ACTIVATES ON
AMP 1 FAILURE
8
7 6 5
3 2 1
'AMP1_BKUP'
AUDIO POWER
AMPLIFIER 1
SIGA-CR DEFINED AS
NONSUPERVISED OUTPUT
AUDIO POWER
AMPLIFIER 2
SIGA-CR DEFINED AS
NONSUPERVISED OUTPUT
8
7 6 5
3 2 1
+24VDC
'ATP1_ACT'
ARA-1 RELAY
RELAY ACTIVATES ON
AMP 2 FAILURE
7 6 5
3 2 1
'AMP2_BKUP'
ARA-1 RELAY
RELAY ACTIVATES ON
AMP 3 FAILURE
PRE-AMP OUT IN
OUT 3
AMP 3
IN
RISER 1
OUT
3-ATPINT
ATP 2
IN
ACT
RISER 2
OUT PRE-AMP AMP 4
OUT 4
OUT IN
7 6 5
3 2 1
'AMP3_BKUP'
AUDIO POWER
AMPLIFIER 3
AUDIO POWER
AMPLIFIER 4
7 6 5
3 2 1
SIGA-CR DEFINED AS
NONSUPERVISED OUTPUT
+24VDC
'ATP2_ACT'
ARA-1 RELAY
RELAY ACTIVATES ON
AMP 4 FAILURE
BACKUP RISER
7 6 5
3 2 1
'AMP4_BKUP'
SIGA-CR DEFINED AS
NONSUPERVISED OUTPUT
PRE-AMP OUT IN
OUT 5
AMP 5
IN
RISER 1
OUT
3-ATPINT
ATP 3
IN
ACT
RISER 2
OUT PRE-AMP AMP 6
OUT 6
OUT IN
AUDIO POWER
SPARE AMP
SIGA-CR DEFINED AS
NONSUPERVISED OUTPUT
8
7 6 5
3 2 1
+24VDC
'ATP3_ACT'
ARA-1 RELAY
1 Supervised
RELAY ACTIVATES IF
AMP 2 OR AMP 4 FAILS
2 Power Limited
8
7 6 5
3 2 1
'AMP24_BKUP'
(3ATPINT4.CDR)
FROM 3-ZAxx #1
'AMP1_PRI'
FROM 3-ZAxx #2
'AMP2_PRI'
4.24
Typical
Speaker
Circuit:
Style Y (Class B)
TB3
8 7 6 5
TB2
From ATP
RISER IN (+)
RISER IN (-)
DATA IN (+)
DATA IN (-)
From Signature Controller
or Previous Device
4 3 2 1
TB1
[3bwire1.cdr]
10 9
UL/ULC Listed
47K EOL
To Next Device
4.25
From ATP
UL/ULC
Listed
47K EOL
Typical
Speaker
Circuit:
CH2 (INPUT 2)
RISER IN (+)
CH2 (INPUT 2)
RISER IN (-)
Style Y (Class B)
CH2 (INPUT 2) RISER OUT (-) To Next Device or
URSM Supervisory
TB4
TB3
8 7
4 3
6 5
2 1
TB1
TB2
[3bwire2.cdr]
10 9
14 13 12 11
URSM Supervisory
From ATP
CH1 (INPUT 1)
RISER IN (+)
CH1 (INPUT 1)
RISER IN (-)
DATA IN (+)
DATA IN (-)
From Signature Controller
or Previous Device
To Next Device
Typical
Speaker
Circuit:
Style Y (Class B)
Style Z (Class A)
Only
+
TB3
JP1
16 15 14 13
8 7
TB2
From ATP
CH1 (INPUT 1)
RISER IN (+)
CH1 (INPUT 1)
RISER IN (-)
6 5
12 11 10 9
4 3
2 1
TB1
[3bwire3.cdr]
TB4
UL/ULC
Listed
47K EOL
(Class B Only)
DATA IN (+)
DATA IN (-)
From Signature Controller
or Previous Device
To Next Device
4.26
Solucin de Problemas
El ATP detecta la prdida de energa AC o corte en el suministro
de energa que afectan los amplificadores. Tambin suministra
re4splado de batera a los amplificadores si el sistema de audio
est activo cuando ocurre una falla de energa o un corte en el
suministro. El ATP debe tener instalada una tarjeta de interfaz
3-ATPINT para poder trabajar con el sistema EST3.
El ATP entra en un estado de problema si ocurre alguno de los
siguientes eventos:
4.27
Captulo 5
Instalacin
Resumen
5.1
Instalacin
Configuracin 5.55
Conexin la impresora de impacto PT-1S 5.59
Fuente de energa de la impresora del sistema 5.61
Ajuste de los niveles de salida del amplificador 5.64
Lo que necesitar 5.64
Procedimiento de ajuste 5.64
Consideraciones de diseo 5.64
Conexin del codificador de seal CDR-3 para salida de tono
codificado 5.66
Lo que necesitar 5.67
Ajuste del aumento de la entrada auxiliar de la 3-ASU 5.67
Conexin de un modem externo para uso con la herramienta
de diagnstico remoto 5.71
Activacin del RPM y de los perfiles de distribucin 5.74
5.2
Installation
Revisin de la Instalacin
Precaucin descarga electrosttica
5.3
Instalacin
2. Torcido
No mezcle
3. Torcido/protegido
Notas superiores sobre este circuito
24VDC de poder limitado
Red de audito digitalizada
Red de comunicacin (RS-485)
25V RMS Audio poder-limitado
25V RMS Audio sin poder-limitado
70V RMS Audio poder-limitado
70V RMS Audio sin poder-limitado
Circuito Signature Data
Circuito ZAS anlogo direccionable
Cable 2 IDC tradicional
Circuito de datos perifrico RS-232
Telfono
Red de electricidad AC sin poder limitado
Cable de fibra ptica
Notas inferiores sobre este circuito
24VDC de poder limitado
Red de audito digitalizada
Red de comunicacin (RS-485)
5.4
Installation
5.5
Instalacin
Washington, PA 15301
(412) 222-7060
Belden Wire and Cable Corp.
P.O. Box 1980
Washington, IN 47375
(317) 9835200BSCC
233 Florence Street
Leominster, MA 01453
Telfono: (508) 537-9138
Fax:
(508) 537-8392
Remee Products, Inc.
186 North Main Street
Florida, NY 10921
Tabla 0-1: Nmero de partes recomendadas por los fabricantes de cables.
#14 (1.50 mm2) Par torcido
Tipo
ATLAS
FPL
218-14-1-1TP
218-14-1-1STP
218-16-1-1STP
218-16-1-1STP
218-18-1-1TP
218-18-1-1STP
FPLP
__
1762-14-1-2J
1761-16-1-2J
1762-16-1-2J
1761-18-1-2J
1762-18-1-2J
FPL
9580
9581
9572
9575
9571
9574
FPLP
__
83752
__
__
__
__
FPL
__
231402
__
241602
__
241802
FPLP
341402
__
341602
351602
341802
351802
REMEE
FPLP
NY514UH
NY514SH
NY516UH
NY516SH
NY518UH
NY518SH
WEST PENN
FPL
994
995
990
991
D9780
D975
FPLP
60993
60992
60991
60990
60980
60975
BSCC
5.6
Protegido
No protegido
Protegido
MFG
BELDEN
No protegido
No protegido
Protegido
Installation
Requisitos de instalacin
3-AADC(1)
3-IDC8/4
5.7
Instalacin
Requisitos de instalacin
3-SSDC(1)
3-SDDC(1)
G1M y G1M-RM
[1] Tambin puede utilizar los mdulos SIGA-UM y SIGA-MAB configurados como Clase B
direccionados a mdulos NAC (cdigo de identificacin 16.)
2.
Si las aplicaciones de notificacin se emplean en la lnea de datos para ms de una zona, cada
zona debe contar con aislamiento de tal forma que el defecto (culpa) por ruptura, tierra o cable a
cable no afecten ms de una zona.
3.
5.8
Installation
Circuitos comunes
Los diagramas de circuito siguientes utilizan el trmino zona
para indicar zonas de notificacin como se define en UL 864.
Zona de notificacin: Un rea cubierta por aplicaciones de
notificacin que se activan simultneamente.
La Figura 0-1 muestra una aplicacin comn del mdulo 3IDC8/4 que sostiene dos zonas de notificacin. En este
ejemplo, la energa se suministra por el riel EST3 y los cables
puente (JP1 al JP4) estn colocados como corresponde.
Tambin es posible crear una aplicacin similar que utiliza
energa elctrica externa, suministrada por un NAC 1/2 IN y
un NAC 5/6 IN. Consulte la pgina de instalacin 3-IDC8/4
para los detalles del cableado y las especificaciones
requeridas para el cable puente.
En la Figura 0-1, ambas zonas estn configuradas por
separado con circuitos NAC para mecanismos de audito y
video. NAC 1 y NAC 5 estn programados como mecanismos
de video, y NAC 2 y NAC 6 como mecanismos de audio. Esto
quiere decir que la funcin de seal de silencio puede ser
configurada para silenciar slo las bocinas.
La separacin de los mecanismos de video y audio es
opcional y puede no ser necesaria para su proyecto. Consulte
la pgina de instalacin del Genesis Signal Master para
obtener configuraciones y detalles sobre el cableado
adicionales.
5.9
Instalacin
NAC 1
Device type: Visible
Label: Zone_1_Strobes
9 10
NAC 1/2
IN
NAC 2
IDC 4
IDC 3
NAC 1
NAC 2
Device type: Audible
Label: Zone_1_Horns
ZONE1
Temporal horn/strobe
and G1M module
Normal
Temporal
horn/strobe
Active
JP1 JP2
1
2
3
1
2
3
10 k
EOLR
10 k
EOLR
ZONE 2
Temporal horn/strobe
and G1M module
1
2
3
Normal
1
2
3
Active
S
10 k
EOLR
10 k
EOLR
NAC 5/6
IN
IDC 8
IDC 7
NAC 6
NAC 5
JP3 JP4
Temporal
horn/strobe
NAC 5
Device type: Visible
Label: Zone_2_Strobes
NAC 6
Device type: Audible
Label: Zone_2_Horns
NAC 1
Tipo de mecanismo: Video
Etiqueta: Zona_1_ estroboscopios
NAC 2
Tipo de mecanismo: Audio
Etiqueta :Zona_1_ bocinas
ZONA 1
Bocina/estrobo temporal
y mdulo G1M
Normal
10k
EOLR
5.10
Activo
Bocina/estrobo
temporal
10k
EOLR
Installation
ZONA 2
Bocina/estrobo temporal
y mdulo G1M
Normal
Bocina/estrobo
temporal
Activo
10k
EOLR
10k
EOLR
NAC 5
Tipo de mecanismo: Video
Etiqueta: Zona_2_ estroboscopios
NAC 6
Tipo de mecanismo: Audio
Etiqueta :Zona_2_ bocinas
La Mdulo de
Bocina/estrobo
Sincronizacin Temporal
IM
IPHS
SIGA B+
SIGA B
SIGA A +
SIGA A -
CC1
CR
270
Zona de
Notificacin 1
IPHS
Base
Aislante
Contrahuella Auxiliar
Mdulo de Bocina/estrobo
Sincronizacin Temporal
Zona de
Notificacin 2
Mdulo de Bocina/estrobo
Sincronizacin Temporal
Zona de
Notificacin 1
IM
IPHS
CC1
Clase A
(necesaria)
Contrahuella Auxiliar
CR
270
IPHS
Base
Aislante
Mdulo de Bocina/estrobo
Sincronizacin Temporal
Zona de
Notificacin 1
5.11
Instalacin
IM
IPHS
SIGA B+
SIGA B
SIGA A+
SIGA A
CC1
CR
Notification
zone 1
270
IPHS
Isolater
base
AUX riser
Sync
module
Class A
(required)
Temporal
horn/strobe
IM
IPHS
CC1
Temporal
horn/strobe
CR
Notification
zone 2
270
IPHS
Isolater
base
AUX riser
Mdulo de Bocina/estrobo
Sincronizacin Temporal
Zona de
Notificacin 1
IM
IPHS
SIGA B+
SIGA B
SIGA A +
SIGA A -
CC1
CR
270
IPHS
Base
Aislante
Contrahuella Auxiliar
Mdulo de Bocina/estrobo
Sincronizacin Temporal
Zona de
Notificacin 2
Mdulo de Bocina/estrobo
Sincronizacin Temporal
Zona de
Notificacin 1
IM
IPHS
CC1
Clase A
(necesaria)
Contrahuella Auxiliar
CR
270
IPHS
Base
Aislante
Mdulo de Bocina/estrobo
Sincronizacin Temporal
Zona de
Notificacin 1
5.12
Installation
Figura 0-2: Cableado Signature para la sincronizacin de la seal del circuito de notificacin.
La Figura 0-3 Muestra dos NACs en un circuito de datos Signature.
Cada NAC es controlado por el mdulo SIGA-CC1S: uno para
mecanismos de audio y otro para mecanismos de video.
5.13
5.14
From
previous device
4 3 2
To
next device
AUX riser to next
device or riser monitor
8 7 6 5
Model: CC1S
Device type: Visible
Personality: (25) Auto sync output
Label: Zone_1_Strobes
Data out ()
3 2
Strobe
Strobe
10 9
Active
Normal
Temporal
horn
Data in ()
8 7 6 5
10 9
Data in (+)
Model: CC1S
Device type: Audible
Personality: (25) Auto sync output
Label: Zone_1_Horns
Active
Normal
Temporal
horn
47 k
EOLR
47 k
EOLR
Instalacin
Installation
(a la derecha)
Bocina Temporal
Bocina Temporal
Normal
Activo
47 EOLR
Estreboscopio
Estreboscopio
Normal
Activo
47 EOLR
(A la izquierda)
Mdulo Signal de Una Entrada
Modelo: CC1s
Tipo de mecanismo: Audio
Identificacin (25) salida sincronizada automtica
Etiqueta: Zona _1_ bocinas
(A la derecha)
Mdulo Signal de Una Entrada
Modelo: CC1s
Tipo de mecanismo: Video
Identificacin (25) salida sincronizada automtica
Etiqueta: Zona _1_ estreboscopios
(A la izquierda)
Del mecanismo anterior
Informacin entra (+)
Informacin entra (-)
(A la derecha)
Del mecanismo siguiente
Informacin sale (+)
Informacin sale (-)
(A la izquierda)
Contrahuella Auxiliar (+)
del mecanismo anterior (-)
(A la derecha)
Contrahuella Auxiliar para el siguiente (+)
mecanismo o monitor de contrahuella (-)
Figura 0-3: Cableado comn NAC SIGA-CC1S
5.15
Instalacin
5.16
From
previous device
4 3 2
Temporal
horn/strobe
To
next device
Model: CR
Device type: Dry contact
Personality: (8) Dry contact
Label: Zone_1_NAC_Silence
Data out ()
Relay module
4 3
8 7 6
Data in ()
8 7 6 5
10 9
Temporal horn/strobe
and G1M module
Data in (+)
Model: CC1
Device type: Visible
Personality: (5) Riser selector
Label: Zone_1_NAC
Active
Normal
47 k
EOLR
Installation
5.17
Instalacin
(a la derecha)
Bocina/ Estreboscopio Temporal
y mdulo G1M
Bocina/ Estreboscopio Temporal
Normal
Activo
47 EOLR
(A la izquierda)
Mdulo Signal de Una Entrada
Modelo: CC1s
Tipo de mecanismo: Video
Identificacin (5) selector de contrahuella
Etiqueta: Zona _1_ NAC
(A la derecha)
Mdulo de Transmisin
Modelo: CR
Tipo de mecanismo: Contacto seco
Identificacin (8) Contacto seco
Etiqueta: Zona _1_ NAC_silencio
(A la izquierda)
Del mecanismo anterior
Informacin entra (+)
Informacin entra (-)
(A la derecha)
Del mecanismo siguiente
Informacin sale (+)
Informacin sale (-)
(A la izquierda)
Contrahuella Auxiliar (+)
del mecanismo anterior (-)
(A la derecha)
Contrahuella Auxiliar para el siguiente (+)
mecanismo o monitor de contrahuella (-)
Figura 0-4: Cableado comn SIGA-CC1 NAC
5.18
Installation
5.19
5.20
Model: CR
Device type:
NSCommonAlarmOutput
Personality: (8) Dry Contact
Text 1: REMOTE_SUPPLY
Text 2: HORN_SILENCE
IN
From
previous
device
Data In (+)
Data In ()
Model: CT1
Device type: AC Power
Personality: (3) Active B
Text 1: REMOTE_SUPPLY
Text 2: AC_FAILURE
NC
COM
NO
OUT
Sense 2 COM
47 k
EOLR
[3]
WHT
8 7 6
4 3 2 1
8 7
4 3 2 1
RED
24
0V
C.
8 7 6 5
PAM-1
[2]
N.O.
BLU
ORG
Sense 1 COM
OUT
47 k
EOLR
[3]
Active
Normal
Not supervised
IN
200 mA +
AUX
Auxiliary/booster
supply [4]
4 3 2 1
10 9
To
next
device
Notes
Instalacin
Installation
(Izquierda)
Fuente Auxiliar/elevador [4]
Auxiliar +
200 mA DENTRO (IN)
Sentido 1 COM
FUERA (OUT)
DENTRO (IN)
Sentido 2 COM
FUERA (OUT)
NO
COM
NC
47 EOLR [3]
47 EOLR [3]
Modelo: CR
Tipo de mecanismo:
Salida de Alarma Comn NS
Identificador: (8) Contacto Seco
Texto 1: REMOTA_FUENTE
Texto 2: BOCINA_SILENCIO
Modelo: CT
Tipo de mecanismo: Corriente Alterna (AC)
Identificador: (3) B Activo
Texto 1: REMOTA_FUENTE
Texto 2: AC_FALLA
Del mecanismo anterior
Informacin entra (+)
Informacin entra (-)
(Centro y hacia la derecha)
Normal
Activo
WHT
ORG
PAM-1 [2]
RED
BLU
Notas
1. Todo el cableado es supervisado y de poder limitados a menos que se especifique lo contrario.
[2] Instale el PAM-1 o el regulador listado equivalente slo cuando necesite supervisar el circuito de cableado 200mA AUX
[3] Utilice el nmero de parte EO-L47
[4] Configure la operacin del Sentido 1 y del Sentido 2 para el modo Genesis Master y la funcin NAC para Continuidad.
Consulte la documentacin de la fuente auxiliar/elevador para ms detalles.
[5] Utilice un CC1S si quiere mantener la sincronizacin de seal a travs de las fuentes mltiples auxiliar/elevacin en el
mismo lazo Signature.
Modelo: CC1 o CC1s [5]
Tipo de mecanismo: Video
Identificador: (5) Selector de contrahuella
Texto 1: REMOTA_FUENTE
Texto 2: BOCINAS_ &_ESTREBOSCOPIOS
Al siguiente mecanismo
Informacin sale (+)
Informacin sale (-)
Figura 0-5: Utilizacin de una fuente auxiliar/elevadora para habilitar la capacidad de silenciar la
bocina con dos cables.
5.21
Instalacin
5.22
Installation
5.23
Instalacin
5.24
Installation
Prueba
Circuito de aplicacin de
notificacin de corriente
continua (DC)
1.
2.
3.
1.
2.
3.
Circuito de aplicacin de
notificacin de audio
5.25
Instalacin
Prueba
1.
2.
3.
Circuito de contrahuella
telefnico
5.26
2.
3.
1.
2.
3.
1.
2.
3.
Installation
Prueba
Circuitos de comunicacin
RS-485
Circuitos de comunicacin
RS232-
Tierra de Tierra
1.
2.
3.
2.
3.
1.
5.27
Instalacin
Chassis 1
12 In
(30.48 cm)
Chassis 2
12 In
(30.48 cm)
Chassis 3
12 In
(30.48 cm)
5.28
Installation
5.29
Instalacin
5.30
Installation
5.31
Instalacin
5.32
Installation
ID Contacto
SIA DCS
SIA P2 (3/1 formato de pulso)
SIA P3 (4/2 formato de pulso)
TAP (3-MODCOMP solamente)
5.33
Instalacin
Cualquier timbre
Timbre normal
Timbre distinto 2 (clase II)
Timbre distinto 3 (clase III)
Funciones
Configuracin
5.34
Installation
5.35
Instalacin
Equipo
Comunicador de Modem 3-MODCOM
ID Contacto
SIA DCS
SIA P2 (3/1 formato de pulso)
SIA P3 (4/2 formato de pulso)
5.36
Installation
Opciones de configuracin
El 3-MODCOM y 3-MODCOMP se pueden configurar como
sigue:
5.37
Instalacin
5.38
Installation
Requisitos de programacin
5.39
Instalacin
Requisitos ACDB
Compatibilidad
Versiones EST3
Protocolos de transmisin
El 3-MODCOM es capaz de transmitir mensajes en cinco
formatos o protocolos:
Identificacin de contacto
SIA DCS
SIA P2 (3/1 formato de pulso)
SIA P3 (4/2 formato de pulso)
ETIQUETA (3-MODCOMP solamente)
5.40
Installation
Proceso de Transmisin
El 3-MODCOM incluye caractersticas que proporcionan un
nivel importante de integridad en la transmisin. Las lneas
telefnicas mltiples y los nmeros de telfonos mltiples le
ayudan a asegurarse de que la llamada ser recibida por el
receptor. El mdulo 3-MODCOM sigue la secuencia de los
siguientes pasos bsicos para contactar al receptor de la
estacin de monitoreo central.
1. El 3-MODCOM aprovecha una de las lneas telefnicas y
descuelga la lnea por un mnimo de tres segundos.
5.41
Instalacin
5.42
Installation
Consideraciones de la programacin
Cuentas y receptores
Etiqueta
Descripcin
Nmero telefnico primario
Nmero telefnico secundario
Protocolo a utilizar
Nmero mximo de intentos de marcacin
Tiempo de espera entre los intentos de marcacin
5.43
Instalacin
Etiqueta
Descripcin
Receptor a utilizar
Nmero de cuenta (como fue asignado a la CMS)
Intervalos de prueba de marcacin y hora del da
comandos.
Activar: un comando que le permite ejecutar una lista de
del 3-MODCOM.
Instalacin
Precaucin: Antes de instalar, retire la energa del riel.
5.44
Installation
5.45
Instalacin
5.46
Installation
Gato lnea 2
Marcacin de 1 lnea
Segunda lnea de 2 lneas de marcacin
Lnea de modem de entrada
5.47
Instalacin
5.48
Installation
Transmisin de prueba
5.49
Instalacin
Autobs SACO
El mdulo de Control de Acceso de Seguridad 3-SACO soporta
el autobs SACO, una lnea de comunicacin RS-485. Cuando
se ha construido adecuadamente, el autobs SACO corre
grandes distancias, soporta ms descensos y es ms inmune
al ruido que la lnea RS-232.
El autobs SACO est formado por dos lneas:
Autobs SACO +
Autobs SACO
Cableado recomendado
Debido a que nuestros mecanismos de control de acceso y
seguridad requieren 24 Vdc, siempre sugerimos utilizar un
cable de cuatro alambres para el autobs SACO y una fuente
de energa de 24 Vdc.
Para los cables de informacin sugerimos un par torcido no
protegido con ms de 6 torsiones por pie de 14 a 22 AWG
(1.50 a 0.25 mm cuadrados).
Para los cables de energa, recomendamos 14 16 AWG.
5.50
Installation
5.51
Instalacin
5.52
Installation
5.53
Instalacin
CONTROL PANEL
CABINET
3-PPS(-230)
TEMP
SENS.
TB2
3-BPS(-230)
TB2
3-BPS(-230)
TB2
3-BPS(-230)
TB2
CONDUIT
8A FUSE
(P/N 46097-0110)
JUMPER
BATTERY
#1
BATTERY
#2
[3BCIN1.CDR]
5.54
Installation
Instalacin
Monte el SIGA-CC1 y el SIGA-CT1 dentro de la fuente de
elevacin como se describe en la documentacin tcnica de
la fuente de elevador y cablelos como se muestra en la
Figura 32.
Configuracin
Fuente de elevador
5.55
Instalacin
5.56
Mdulo
Propiedades
SIGA-CC1
Modelo = CC1
Tipo de Mecanismo = SalidadeAlarmaComn
Identificacin = (5) Selector de Contrahuella
Texto 1 = FUENTE_REMOTA
Texto 2 = SENTIDO_1
SIGA-CT1
Modelo = CT1
Tipo de Mecanismo = FalladeCorrienteAlterna
Identificacin = (3) Activo B
Texto 1 = FUENTE_REMOTA
Texto 2 = FALLA_CORIENTEALTERNA
NC
COM
NO
OUT
COM
47 k
EOLR
[3]
47 k
EOLR
[3]
Data In (+)
Data In ()
Model = CT1
Device type = ACFail
Personality = (3) Active B
Text 1 = REMOTE_SUPPLY
Text 2 = AC_FAILURE
Sense 2
IN
OUT
COM
Auxiliary/booster
supply
Sense 1
IN
4 3 2 1
8 7
ORG
PAM-1
[2]
N.O.
0V
WHT
BLU
C.
24
200 mA AUX
Not supervised
8 7 6 5
Active
Normal
4 3 2 1
10 9
Signature loop
to next device
Model = CC1
Device type =
CommonAlarmOutput
Personality = (5) Riser Selector
Text 1 = REMOTE_SUPPLY
Text 2 = SENSE_1
Notes
Installation
5.57
Instalacin
(Izquierda)
Fuente Auxiliar/elevador
Auxiliar +
200 mA DENTRO (IN)
Sentido 1 COM
FUERA (OUT)
DENTRO (IN)
Sentido 2 COM
FUERA (OUT)
NO
COM
NC
47 EOLR [3]
47 EOLR [3]
5.58
Installation
ALARM
POWER
PITCH
MODE
SYSTEM PRINTER
PT1-P
[CPT1SX.CDR]
5.59
Instalacin
Velocidad de impresin
232 Caracteres/Segundo
Tasas de Baudios
Cableado
Voltaje
120 Vac @ 60 Hz
Poder de Reserva
40 VA
Energa de Impresin
120 VA
SW2
SW3
SW4
SW5
SW6
SW7
SW8
OFF
(Ingls)
OFF
(Ingls)
OFF
(Ingls)
OFF
(11-pulgadas
en forma)
ON
(11-pulgadas
en forma)
OFF
(auto LF off)
ON
(8 aicos)
OFF
(habilita el
panel frontal)
5.60
Interruptor
Especificacin
de Fbrica
SW1-1
OFF
SW1-2
OFF
SW1-3
ON
ON: 8 aicos
OFF: 7 aicos
SW1-4
OFF
SW1-5
ON
SW1-6
ON
SW1-7, -8
ON,ON
Descripcin
Installation
Especificacin
de Fbrica
Descripcin
SW2-1, -2,
-3
OFF,OFF,ON
SW2-4
OFF
SW2-5
ON
SW2-6
ON
SW1-7
OFF
SW1-8
OFF
no utilizado
5.61
Instalacin
Circuito 15 Amp
UPS listado U.L. 1481
Fuente de energa ininterrumpible
Tiempo de funcionamiento
174 minutos 20%
Figura 0-10.
UPS Trouble
Contact Monitor
To 120 VAC
15 Amp Circuit
Signature Module
To 3-CPUI
ALARM
P OWE R
P IT CH
M ODE
S YS TEM P RINT ER
P T1-P
Run Time
174 minutes+ 20%
(izquierda)
Problema de UPS
Monitor de Contacto
Mdulo Signature
Al 3-CPUI
Impresora Serial PT1S
(derecha)
A 120 VAC
Circuito 15 Amp
5.62
Installation
5.63
Instalacin
Procedimiento de ajuste
1. Desconecte el cableado de campo en todos los mdulos
del amplificador divididos en zonas en el gabinete.
2. Coloque un medidor RMS a travs de las terminales del
amplificador TB2 NAC/B+ y NAC/B-.
3. Utilice el interruptor 1KHZ_TONO para encender el tono.
4. Ajuste el pote de aumento del amplificador hasta que el
medidor RMS muestre el nivel de salida configurado. (25
70 Vrms).
5. Conecte el cableado de campo del amplificador.
6. Utilice el interruptor 1KHZ_TONO nuevamente y verifique
que el nivel de salida sea el mismo. Vuelva a ajustar el
pote de aumento del amplificador si es necesario.
7. Desconecte el cableado de campo del amplificador.
8. Repita los pasos 2 al 6 para cada amplificador en el
gabinete.
9. Vuelva a conectar el cableado de campo en todos los
amplificadores en el gabinete.
Consideraciones de diseo
Su sistema de audio funcionar mejor si los tonos y mensajes
pre-grabados tienen aproximadamente el mismo volumen o
amplitud. El procedimiento para establecer una amplitud
mxima comn se denomina con frecuencia normalizacin.
Le sugerimos que normalice tus tonos y mensajes a una
amplitud mxima de 1 V pico a pico o un promedio de 0.7
Vrms.
La Unidad de Servicio de Datos no cuenta con una
herramienta para normalizar sus clips de audio, por lo que
necesitar utilizar un editor de sonido para normalizar los
5.64
Installation
5.65
Instalacin
Figura 0-11. Si usted est conectando a un puerto serial CDR3 que es compartido con la impresora PT-1S, debe conectar
ambos mecanismos utilizando un IOP3A, como se muestra en
el diagrama de cableado en este tema.
5.66
Installation
Lo que necesitar
Una versin de arranque inicial de la base de datos del
proyecto que contenga un interruptor programado para
voltear los amplificadores hacia el canal Auxiliar. Consulte
"Creacin de la versin de arranque inicial de la base de datos
del proyecto".
Un voltmetro RMS (Platija 83 o su equivalente)
5.67
Instalacin
5.68
Installation
CPU
TB2
NETWORK
OUT
IN
A
A
B
B
3-PSMON
AUXILIARY POWER
AUDIO
A IN
AUDIO
A OUT
AUDIO
B IN
AUDIO
B OUT
R
X
1
T
X
1
R
T
S
1
C
O
M
1
R
X
2
C
O
M
2
R
T
S
2
T
X
2
TB1
JB4
JB1
3
2
1
TB2
IOP3A
TB1
UP
SW1
JB2
JB3
TB3
10 k EOL
TEMPORL TONE
EARTH GRND
24 VDC
AUDIO DATA TELEPHONE PAGE
OUT
PRIMARYSECONDARY
REMOTE MIC
KEY
AUX
COMMON
AUDIO
RS232 INPUT
TB1
47 k EOL
PRINT SUPV
TRBLE OUT
3-ASU
CODED TONE
10 k EOL
SIGA-CT1
From
24 Vdc NAC signal
power source
DURATION
From Signature
controller or
previous device
CDR-3
1 2 3 4 5 6 7 8
ON
SW1
JP2
TEMP
To next
device
BELL
CODE
JP1
[CDR3_ASU.CDR]
To
24 Vdc notification
appliance circuit
5.69
Instalacin
(Izquierda)
CPU
Nota: Para aplicaciones de un solo gabinete, conecte la salida del 3-ASU a la salida de AUDIO A
TB2
Red Salida A + -, Entrada A + -; Audio A Entrada + -, Audio A Salida + -; Audio B Entrada + -, Audio B Salida + -; RX1, TX1; RTS1,
COM 1; RX2, TX2; RTS2, COM2
Informacin de audio, primario, secundario; pgina telfono, salida; MIC Remoto, llave, audio; Auxiliar
SIGA CT1
Nota: Configure el SIGA CT1 como un circuito de entrada sin pestillo con el mecanismo de Monitor.
Desde el controlador Signature o el mecanismo anterior
Al prximo mecanismo
(Centro)
3-PSMON
TB1
Energa Auxiliar
1+ -, 2 +10k
47k
10k
Desde la fuente de energa de seal NAC 24Vdc
Hacia el circuito de la aplicacin de notificacin 24Vdc
(derecha)
Conector macho DB25 a la impresora PT-1S (vista trasera)
Tono temporal
Tierra a tierra
24Vdc
Comn
Salida RS232
Supervisin de Impresin
Problema Fuera
Tono codificado
CDR-3
Nota: Consulte la hoja de instalacin DFR-3 para colocacin de SW1
Duracin
Temporal
Cdigo de campana
[CDR3_ASU.CDR]
5.70
Installation
Figura 0-12.
2. Asegure el modem a la SIGA-MP1 con los 2 lazos (corbata)
de cables.
3. Atornille el SIGA-MP1 al compartimiento back box MFCA
4. Conecte todo el cableado del modem. Consulte la
documentacin tcnica que viene con el modem para las
conexiones de cableado.
El cableado RS-232 debe mantener una separacin
mnima de 1/4-pulgadas entre el cableado
nocorriente-limitado.
5.71
Instalacin
CPU
TB2
R
X
1
T
X
1
C
O
M
1
R
T
S
1
R
X
2
T
X
2
R
T
S
2
C
O
M
2
6
7
1
3
2
Modem
8
MFCA/Modem Installation
1
2
3
4
5
6
7
8
CPU
RX1, TX1; RTS1, COM 1; RX2, TX2; TB2, RTS2, COM2
Cable serial del modem
Conector macho DB-25 (vista trasera) al conector de modem RS-232
Instalacin de MFCA/Modem
[1] Placa de montaje SIGA-MP!
[2] Tornillo cabeza de cazuela ranurado # 6-32X 3/8
[3] Arandera de cerradura #6
[4] Endosure MFCA (sensor)
5.72
Installation
5.73
Instalacin
5.74
Installation
5.75
Captulo 6
Encendido y prueba
Resumen
Encendido y prueba
Estaciones manuales 6.22
Detectores de calor no restituibles 6.22
Detectores de calor restituibles 6.22
Interruptores Waterflow 6.22
Prueba de dispositivo de notificacin 6.24
Dispositivos visuales 6.24
Bafles 6.24
Timbres y bocinas 6.24
Registro de terminacin 6.25
Encendido y prueba
Encendido y prueba
Errores de activamiento
Existen varias razones por las que pueden ocurrir errores
cuando la informacin se descarga a los controladores del
CPU. De inicio, se esperan ciertos errores debido a que la
base de datos de la red se carga por pasos. Hasta que todas
las porciones de la base de datos se ingresen
adecuadamente en la memoria, se generarn errores.
Durante la configuracin del sistema inicial, esto es de
esperarse. La mayora de estos errores se resolvern por s
mismos en la medida que contine la configuracin del
sistema.
Una segunda fuente de errores de descarga es la desigualdad
entre la configuracin de los gabinetes en la SDU y la
instalacin del equipo existente. La causa ms comn de este
error se debe tpicamente a la instalacin de un mdulo de
riel local en la posicin de riel equivocada. Otro error comn
es la instalacin de un mdulo de tipo equivocado en el riel.
La falta de identificacin de todo un gabinete tambin puede
causar este tipo de error.
Una tercera causa de error de descarga puede ocurrir
despus de que los gabinetes han sido descargados
inicialmente. Despus de las descargas inciales, todas las
descargas subsecuentes pueden realizarse mediante el
Encendido y prueba
Encendido y prueba
Causa posible
Contrasea invlida
Problema de parmetro de
medida
Problema de comunicacin de
almacenaje
# de parcela
Panel inaccesible
Sesin en proceso
Escritura protegida
Nmero de block
Diferente versin
Encendido y prueba
Introduccin
Una vez que el sistema ha sido cableado, programado y las
fallas del circuito corregidas, todos los componentes
instalados deben de probarse como un sistema, para su
operacin adecuada.
La verificacin del sistema inicial est diseado para revisar
que todos los componentes del sistema estn instalados y
operando conforme a lo planeado. Verificar que el sistema
est diseado e instalado de acuerdo con las especificaciones
requiere que todos los aspectos del sistema sean ejercidos y
se verifiquen los resultados. Cuando los resultados de la
prueba difieren de los esperados, debe de tomarse la medida
correctiva correspondiente.
Antes de comenzar la prueba, notifique a todas las reas
donde la alarma suena y apague os lugares de las
instalaciones que reciben las transmisiones de problema y
alarma porque la prueba se est efectuando.
Los registros de todas las pruebas y mantenimientos deben
de mantenerse en las instalaciones protegidas por un perodo
mnimo de 5 (cinco) aos.
Herramientas necesarias:
Encendido y prueba
Encendido y prueba
Encendido y prueba
10
Encendido y prueba
11
Encendido y prueba
12
Encendido y prueba
13
Encendido y prueba
posteriormente.
posteriormente.
14
Encendido y prueba
15
Encendido y prueba
16
Encendido y prueba
17
Encendido y prueba
18
Encendido y prueba
Mdulos de Control/exhibicin
1. Verifique que la(s) pantalla(s) est(n) asentadas
correctamente en el mdulo y asegurada(s) con los cuatro
remaches de chasquido. Verifique que el cable de cinta
entre la pantalla y su mdulo anfitrin est asentado con
firmeza por ambos lados.
Active la prueba de lmpara y verifique que todas las
lmparas funcionen como sigue:
Seleccione el botn de Men de Comando para obtener la
pantalla de Men Principal.
19
Encendido y prueba
20
Encendido y prueba
21
Encendido y prueba
22
Encendido y prueba
23
Encendido y prueba
Estaciones manuales
1. Inspeccin visual
2. Mecanismo de activacin
3. Verifique que el mensaje de tipo de mecanismo y
localidad adecuado se muestre en el mdulo LCD.
Verifique que el mecanismo inicie las respuestas de
sistema apropiadas.
4. Abra el circuito. Verifique que el mensaje de Problema de
circuito y localidad adecuado se muestre en el mdulo
LCD.
24
Encendido y prueba
Interruptores Waterflow
1. Inspeccin visual
2. Active la vlvula de prueba del irrigador. (Consulte el
procedimiento de prueba del sistema Irrigador)
3. Verifique que el mensaje de tipo de mecanismo y
localidad adecuado se muestre en el mdulo LCD.
Verifique que el mecanismo inicie las respuestas de
sistema apropiadas.
4. Abra el circuito. Verifique que el mensaje de Problema de
circuito y localidad adecuado se muestre en el mdulo
LCD.
25
Encendido y prueba
Mecanismos visuales
1. Inspeccin visual
2. Active el circuito. Verifique que todos los dispositivos de
indicacin funcionen adecuadamente.
3. Abra el circuito. Verifique que el mensaje de Problema de
circuito y localidad adecuado se muestre en el mdulo
LCD.
Bafles
1. Inspeccin visual
2. Active el circuito. Verifique que todos los dispositivos de
indicacin funcionen adecuadamente.
3. Abra el circuito. Verifique que el mensaje de Problema de
circuito y localidad adecuado se muestre en el mdulo
LCD.
Timbres y bocinas
1. Inspeccin visual
2. Active el circuito. Verifique que todos los dispositivos de
indicacin funcionen adecuadamente.
3. Abra el circuito. Verifique que el mensaje de Problema de
circuito y localidad adecuado se muestre en el mdulo
LCD.
26
Encendido y prueba
Registro de terminacin
Cuando se ha probado el sistema y se ha determinado que
funciona satisfactoriamente, haga una copia y complete el
Registro de Terminacin en las siguientes pginas y
mantngalo cerca del panel de alarma contra incendio o
entrguelo al representante del edificio.
27
Encendido y prueba
Pgina1de2
RegistrodeTerminacin
PropiedadProtegida
Nombre
Autoridadconjurisdiccin
Direccin
Direccin
Representante
Telfono
Telfono
RegistrodeInstalacindeSistema
EstesistemahasidoinstaladodeconformidadconlosestndaresestablecidosporlaNFPAabajolistadosyfueinspeccionadopor:__________
en_____________________eincluyelosmecanismoslistadosabajoyhaestadoenserviciodesde__________________
NFPA72Ao_________Ch1234567(circuletodoslosqueapliquen)
NFPA70CdigodeElectricidadNacional,Artculo760
Instruccionesdelfabricante
Otrosespecifique____________________________________________________________
RegistrodeSistemadeOperacin
Todaslascaractersticasoperativasylasfuncionesdeestesistemafueronprobadaspor_________________en____________encontrndose
operativamentecorrectasydeconformidadconlosrequisitosde:
NFPA72Ao_________Ch1234567(circuletodoslosqueapliquen)
NFPA70CdigodeElectricidadNacional,Artculo760
Instruccionesdelfabricante
Otrosespeciifique____________________________________________________________
Firma:_____________
Fecha:__________________
Organizacin:_______________________________________
ProgramadelSistema
Sistemaoficialdelfabricante
Edicininstalada:_______________
Sumadeverificacin:_________________
Fecha:____________________
Solicituddeprogramacin
Instalacindelprogramainicial:______________________________________________________________________________Fecha:____________
Edicionesyrazones:_________________________________________________________________________________________Fecha:____________
___________________________________________________________________________________________________________Fecha:____________
___________________________________________________________________________________________________________Fecha:____________
___________________________________________________________________________________________________________
Programadopor(nombre):__________________________________________________________
Fechadelaltimacertificacindefbricadelprogramador:______________________________
Edicindelprogramadeentradadedatosutilizado:_____________________________________
Mantenimiento
Frecuenciadepruebasderutinaeinspecciones,sisehanrealizadosotrasdistintasalosestndaresestablecidosporlaNFPA:______________
_____________________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________________
Lasdivergenciasdesistemasconlosestablecidosenlosestndaresson:_____________________________________________________________
_____________________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________________
_____________________________________________________________________________________________________________________________
(Firmado)porlaEstacinCentralolaCompaadeServiciodeAlarma
(Ttulo)
(Fecha)
_____________________________________________________________________________________________________________________________
(Firmado)porrepresentantedelaautoridadconjurisdiccin
28
(Ttulo)
(Fecha)
Encendido y prueba
Pgina2/2
RegistrodeTerminacin
IniciacindeCircuitosyMecanismos
ServicioySistemas
(indiquecantidad)
NFPA72Local
Silaalarmaestransmitidafueradelasinstalaciones,lugar(es)dondeserecibe:________________________
Estacionesmanuales
Combinacindedetectores
Mecanismosautomticos:
(circulelossensoresactivos)
Detectoresdehumo:________Ion______Foto
______Ion/Foto/Calor
Detectoresdeducto:________Ion______Foto
______Ion/Foto/Calor
InterruptoresWaterflow:
Otros(liste):_________________________________________________________________ _______________
Supervisindemecanismosycircuitos
Tourdeguardiaobligatoriocomprometidode______estacionestransmisorasy
estacionesintermedias
Sistemadeirrigacin
Bombadeextincinelctrica
Mecanismosupervisordevlvula
Energadelabombadeextincin
Puntosdetemperaturadeledificio
Marchadelabombadeextincin
Puntosdetemperaturadelsitiodeagua
Reversindefase
Puntosdeniveldesuministrodelsitiodeagua
Bombadeextincindemotor
Otra(s) funcionesdesupervisin
Selectorenposicinautomtica
(especifique)
Problemadelpaneldecontrol
Interruptoresdetransferencia
Marchadelmotor
NFPA72ServiciodeEmergenciadeAlarmadeVoz
#Canalesalarma/voz
Individual
Mltiple
NFPA72Auxiliar
Tipodeconexin
Energalocal
Derivada
Telfonoparalelo
_____________
Lugar/telfono#desealesrecidibas:_________________________________________________
____________________________________________________________________________________ _____________
NFPA72EstacinRemota
Alarma:____________________________________________________________________________ _____________
Supervisin:________________________________________________________________________ _____________
NFPA72Propietario
Silaalarmaestransmitidafueradelasinstalaciones,lugarytelfonodelaorganizacinquerecibe
Circuitosydispositivosdenotificacin
#decircuitosdenotificacin:
Mtododeretransmisindelaalarma:____________________________________________________ _____________
Tipoycantidaddelosdispositivosdenotificacininstalados
Timbre____Pulgadas
Sealesvisuales
Tipo:________________________________
Baffle
conaudio
Bocina
sinaudio
Otros:_______________________________________________________________________________
____ Anunciadorlocal
NFPA72EstacinCentral
Primercontratista:___________________________________________________________________________________
UbicacindelaEstacinCentral:__________________________________________________________ _____________
MtododetransmisindealarmasalaEstacinCentral
McCulloh ____Sealradiofnicade1direccin
Multiplex ____Sealradiofnicade2direcciones
____Comunicadordealarmadigital
____Otros:______________________
Circuitosdelneadesealizacin
Mtododetransmisindealarmasalcentrodecomunicacionesdeserviciocontraincendiospblico
CantidadytipodeSLCsconectados,porNFPA72Tabla36.1
1.______________________________________ 2.____________________________________________
Cantidad
Tipo
Fuentesdeenerga
Primaria(principal)
Voltajenominal:____________________________
Valuacindecorriente:______________________
Proteccindesobrecorriente:
Tipo:___________________________________
Valuacindecorriente:___________________
Lugar:__________________________________
Secundaria(suplente)
Baterasalmacenadas
ValuacinAmpHoracalculado
para____horasdeoperacindel
sistema.
Generadordedicado
Ubicacindelafuentedecombustible:
Sistemadeemergenciaosuplementepararespaldarelsuministroprimario
SistemadeemergenciadescritoenNFPA70,Artculo700
SistemasuplenterequeridoporleyydescritoenNFPA70,Artculo701
SistemasuplenteopcionaldescritoenNFPA70,Artculo702quecumpleconlasespecificacionesde
funcionamientodelosArtculos700y701
29
Captulo 7
Mantenimiento Preventivo
Resumen
Mantenimiento Preventivo
Introduccin
Antes de comenzar la prueba, notifique a todas las reas
donde suena la alarma y apague los lugares de las
instalaciones que reciben las transmisiones de problema y de
alarma mientras realiza la prueba.
Los registros de todas las pruebas y mantenimientos deben
de mantenerse en las instalaciones protegidas por un perodo
mnimo de 5 (cinco) aos.
Herramientas necesarias:
Mantenimiento Preventivo
Intervalo de
prueba
Estaciones
manuales
Semestralmente
Detectores de
calor no
restituibles
Detectores de
calor
restituibles
Detectores de
humo
Semestralmente
Semestralmente
Anualmente
Procedimiento de prueba
1.
Inspeccin visual
2.
3.
Mecanismo de activacin
4.
1.
Inspeccin visual
2.
3.
4.
1.
Inspeccin visual
2.
3.
1.
Inspeccin visual
2.
3.
4.
Verifique la sensibilidad
5.
Interruptores
Waterflow
Bimestralmente
1.
2.
Todos los
circuitos de
dispositivo de
iniciacin
Anualmente
1.
2.
3.
4.
5.
1.
Anunciadores
remotos
Anualmente
Mantenimiento Preventivo
Procedimiento de prueba
Anualmente
1.
Inspeccin visual
2.
1.
2.
Panel de
Energa
primaria
1.
2.
3.
4.
5.
1.
2.
3.
4.
5.
6.
1.
2.
Componente
Dispositivos de
notificacin
Panel de
energa
secundaria
Pruebas de
aceptacin y
reaceptacin
Pruebas de
aceptacin y
reaceptacin
Seales de
problema del
panel
Anualmente
Reloj LCD
Cada visita
Mecanismos de Semestraliniciacin de
mente
seal de
supervisin
2.
Opere la vlvula
3.
Mantenimiento Preventivo
Procedimiento de prueba
Sistema
Auxiliar de
transmisin de
seal de
alarma de
fuego fuera de
las
instalaciones
Mensual
1.
2.
3.
Sistema
remoto de
transmisin de
seal
Waterflow
fuera de las
instalaciones.
Bimestralmente
1.
2.
3.
Componente
Mantenimiento Preventivo
Mdulos
Los mdulos Signature deben de ser inspeccionados
visualmente para asegurarse de que la instalacin fsica es
segura. La prueba funcionamiento del mdulo debe realizarse
regularmente como lo requiere la AHJ.
Mantenimiento Preventivo
Mantenimiento Preventivo
Mantenimiento Preventivo
Hora
Evento
Inicio
Captulo 8
Servicio y Solucin de Problemas
Resumen
8.2
Visin general
Filosofa de mantenimiento
El sistema de seguridad de vida del EST3 consiste en asambleas
modulares utilizando tecnologa de montaje de superficie (SMT,
por sus siglas en ingls) para una fcil instalacin y
mantenimiento. SMT brinda alta confiabilidad, pero prohbe
reparaciones de campo de nivel de componentes. Por estas y
otras razones, la filosofa de mantenimiento consiste en aislar la
falla en la asamblea de tarjeta del circuito, quitar la tarjeta de
circuito defectuosa y reemplazarla con su refaccin.
El servicio y reparacin de los componentes del sistema EST3 se
concentra en los siguientes supuestos:
1. El mantenimiento lo llevarn a cabo tcnicos calificados con
un completo entendimiento del equipo del sistema y las
funciones que realizan.
2. nicamente, tcnicos de mantenimiento certificados darn
servicio al equipo.
3. Los tcnicos de mantenimiento tendrn una provisin de
refacciones listas y disponibles.
8.3
Fuente de energa
Mdulos de riel locales
Amplificadores (si no hay respaldo instalado en el sistema)
Cinta para la impresora
Mdulos de monitor
Mdulos de Control
Detectores de calor
Detectores de humo por ionizacin
Detectores de humo fotoelctricos
Base, detector
Juego de filtros del detector de ducto
Reemplazos de breakglass (vidrio que se rompe en caso de
necesario) para estaciones de palanca
Reemplazos de breakglass para estaciones de palanca
Bocina, timbre, estroboscopio y bafle
8.4
Aislamiento
Los problemas con el equipo pueden clasificarse como
problemas con un gabinete de equipo y problemas con
cableado de campo y mecanismos.
La forma ms rpida de localizar un problema de equipo es
aislar porciones del sistema en forma selectiva y observar los
resultados del aislamiento. Al aislar selectivamente porciones
ms y ms pequeas del sistema, con frecuencia se asla el
equipo que falla. Entonces, el componente sospechoso puede
reemplazarse con un componente que se sabe en buen estado
y se observan los resultados nuevamente.
Equipo de sustitucin
Advertencia: Nunca instale o retire algn mdulo mientras haya
8.5
Equipo adicional
Cuando se aade equipo al gabinete, una parte de la base de
datos de configuracin de la red, tambin, debe de cambiarse.
La medida de los cambios depende de la regla de relacin entre
el componente aadido y el equilibrio de la red. Las copias
revisadas de bases de datos deben, entonces, descargarse
mediante la Herramienta de Definicin del Sistema (SDU, por
sus siglas en ingls).
Problemas de descarga
Si con frecuencia sufre de problemas de descarga, los niveles
de seal bajos de la computadora de descarga pueden ser la
causa. El Cable de Comunicacin Protegido RS-232, No. de
Catlogo SDU-CBL, puede ser empleado para corregir
problemas de nivel de seal.
Nota: No utilice un cable de comunicacin protegido RS-232
8.6
Mdulos
Seales de riel
La figura de abajo muestra las seales que normalmente se
presentan en un par de rieles del chasis.
Nota: El controlador del panel y el mdulo de monitor de la
8.7
TX RX
TX
RX
[PSMONLED.CDR]
Voltaje
Energa de Riel
Energa auxiliar
Batera
Causa posible
1.
2.
1.
1.
2.
2.
3.
3.
8.8
Causa posible
1.
2.
3.
4.
5.
TX RX
TX
RX
[PSMONLED.CDR]
Causa posible
8.9
Causa posible
8.10
N
C
N
O
N
O
TROUBLE
C
N
A
ALARM
N
C
N
O
N
C
SUP
TB1
Rx1
Tx1
Rx2
Tx2
Rx3
Tx3
J1
A
+
NETWORK
AUDIO
OUT
A IN
A B IN B
- +
- +
-
AUDIO AUDIO
B IN
A OUT
+
- +
AUDIO
B OUT
+
R
X
1
T
X
1
R
T
S
1
C
O R
M X
1 2
T
X
2
R
T
S
2
C
O
M
2
[CPULEDS.CDR]
Normal
estado
Descripcin
RX1
Parpadear
TX1
Parpadear
RX2
Parpadear
TX2
Parpadear
RX3
Parpadear
TX3
Parpadear
8.11
5
3NETTS1.CDR
Causa posible
1.
2.
1.
2.
3.
4.
5
6.
1.
2.
Cables TX y RX reversados
CPU y tasa de baudios de mecanismo perifrico no
coincidentes
PC configurada inadecuadamente
3.
Puerto auxiliar RS-232 (TB2-1 a
4 o TB2-5 a 8) inoperante
1.
2.
3.
1.
2.
3.
4.
Cables TX y RX reversados
CPU y tasa de baudios de mecanismo perifrico no
coincidentes
Mecanismo perifrico fuera de lnea o configurado
errneamente
(+) y (-) cables reversados.
Tarjeta 3-RS485 no asentada adecuadamente.
Los circuitos de red A y B cruzados
Cable inadecuado
8.13
Causa posible
1.
2.
3.
4.
5.
1.
2.
3.
1
2.
8.14
Posibles causas
Mdulos de Control/exhibicin
La informacin en esta seccin aplica a los siguientes modelos
de mdulos de control/exhibicin:
3-12/1RY
3-2RY
3-12/2RY
3-12SG
3-12SR
3-12SY
3-12/SIGY
3-12/S1RY
3-12/AS2Y
3-24G
3-24R
3-24Y
3-6/3S3L
3-6/3S1G2Y
3-6/S1GYR
8.15
Causa posible
1.
2.
3.
4.
1.
1
2.
3.
1
2.
3.
2.
3.
Causa posible
1.
2.
3.
1.
2.
Fusible quemado
Aumento configurado muy bajo
Limitante corriente de
amplificador
1.
2.
1.
8.16
Causa posible
Mdulo en problema
Causa posible
Mdulo en problema
1.
2.
3.
4.
5.
1.
2.
3.
4.
5.
6.
8.17
Causa posible
DS1 significado
DS2 significado
Off
Sin actividad
Sin actividad
On
Lnea 1 en uso
Lnea 2 en uso
Destello bajo
Destello rpido
8.19
8.20
Componentes de Audio
Unidad de fuente de audio 3-ASU
Tabla 0-10: Solucin de problemas de la Unidad de Fuente de Audio 3-ASU
Problema
Causa posible
1.
2.
3.
4.
Micrfono defectuoso
Cronometrador para inhibir paginacin fijado por largo tiempo.
3-ASU Defectuoso
Cable de cinta entre el tablero principal del 3-ASU y la cubierta
suelto o defectuoso
5. Amplificador defectuoso
Sin salida de audio para paginar 1. Contrahuella de informacin de audio de red abierta, en corto o
Llamada a Todos de los
cableada incorrectamente.
amplificadores de red, salida
2. Contrahuella de informacin de red abierta, en corto o cableada
disponible a niveles de llamada
incorrectamente.
bajos en las terminales de
3. TB2 en el CPU suelto o cableado incorrectamente
salida.
4. 3-ASU configurada errneamente en la base de datos en la SDU
5. Amplificadores instalados incorrectamente o defectuosos.
El Audio de llamada sale
distorsionado
Mensajes incorrectos a los pisos 1. Las etiquetas de mensaje y del amplificador, y las reglas
incorrectos
incorrectas o mal etiquetadas.
Llamada telefnica inoperante
8.21
Causa posible
Causa posible
La unidad no responde
Sin actividad de LED RX o TX
La llamada desplegada en el
LCD no coincide con la llamada
conectada
8.22
DS3 DS2
DS5 DS4
TB1-IN
TB1-OUT
DS1
TB5
BACKUP
70V
25V
TB2-IN
TB2-OUT
TB6
JP2
TB3
SIGA +IN- +OUT-
+ 24V [3SIGAMP1.CDR]
Color
Descripcin
DS1
Amarillo
DS2
Amarillo
Modo de respaldo
DS3
Verde
Amplificador Activo
DS4
(Tablero hijo)
DS5
(Tablero hijo)
Rojo (destellante)
Condicin Activa
Ajuste de aumento
25 Vrms = 71VPP
70 Vrms = 200 VPP
25 Vrms = 71VPP
70 Vrms = 200 VPP
8.23
Salida 25 Vrms
Salida 70 Vrms
30 Watts
20.8
167 @ 30W
50 Watts
12.5 @ 50W
@ 30W
100 @ 50W
Causa posible
Sin salida
1.
2.
3.
4.
5.
6.
1.
2.
Low Output
1.
2.
3.
8.24
Causa posible
Sin salida
1.
2.
3.
4.
5.
6.
1.
2.
Salida baja
1.
2.
3.
8.25
Etiqueta
Fuente
Descripcin funcional
0001
Respuesta de Arranque
CPU
0002
CPU
0003
Respuesta a la Primer
Supervisin
CPU
0004
CPU
0005
CPU
0006
Respuesta de Evacuacin
CPU
0007
Respuesta de Prctica
CPU
0008
CPU
0009
Respuesta de Silencio de
Alarma
CPU
0010
CPU
0011
Restablecer Activo
CPU
0012
Restablecer Fase 1
CPU
8.26
Etiqueta
Fuente
Descripcin funcional
0013
Restablecer Fase 2
CPU
0014
Restablecer Fase 3
CPU
0015
Respuesta de Primer
Cancelacin
CPU
0016
CPU
0017
CPU
0018
CPU
0019
Prolongacin de
Restablecimiento del
Controlador de Lazo
CPU
0020
Servicio de Supervisin de
Mecanismo
CPU
0021
Problema de Usuario
CPU
0022
Incompatibilidad de Base de
Datos Ext
CPU
0023
CPU
0101
0164
Falla de Comunicacin xx
CPU
0200
0222
CPU
0261
0279
Configuracin de Tarjeta xx
Incongruente
CPU
8.27
Etiqueta
Fuente
Descripcin funcional
0281
0299
CPU
Etiqueta
Fuente
Descripcin
0676
Mecanismo no programado
3-AADC1
0676
Tarjeta 1 de Datos de
Mecanismo no programado
3-DSDC
3-SSDC1
3-SDDC1
0686
Tarjeta 2 de Datos de
Mecanismo no programado
3-DSDC
3-SSDC1
3-SDDC1
Etiqueta
Fuente
Descripcin
0001
3-SAC
0002
3-SAC
0003
Supervisin de Anunciador
3-SAC
0004
Falla de Comunicacin en el
Mdulo de Riel
3-SAC
0005
0006
3-SAC
0007
Supervisin de Cdigo
3-SAC
0008
Falla interna
3-SAC
0009
Falla de Configuracin
3-SAC
0010
3-SAC
0071
Falla de Tarea
3-SAC
0071
8.28
Etiqueta
Fuente
Descripcin
0600
Supervisin de Anunciador
General
0601
Falla Clase A
CPU
0601
Falla de Comunicacin en el
Mdulo de Riel
General
0602
CPU
0603
Supervisin de Audio
CPU
0604
Falla interna
General
0604
3-AADC1
0605
General
0605
0606
Supervisin de Cdigo
General
0607
CPU
0607
3-AADC1
N/A
0607
Falla 1 de Tarjeta de
Informacin
3-DSDC
3-SSDC1
3-SDDC1
N/A
0608
CPU
0608
Falla 2 de Tarjeta de
Informacin
3-DSDC
3-SSDC1
3-SDDC1
N/A
0609
CPU
0609
Falla de Configuracin
General
0610
CPU
0610
3-PPS/M
3-BPS/M
3-BBC/M
8.29
Etiqueta
Fuente
Descripcin
0610
Lnea de Telfono 1
3-MODCOM
0611
CPU
0611
3-PS/M
0611
Lnea de Telfono 2
3-MODCOM
0612
3-PPS/M
3-BPS/M
3-BBC/M
0612
3-MODCOM
0613
3-PPS/M
3-BPS/M
3-BBC/M
0613
3-MODCOM
0614
3-PPS/M
3-BPS/M
3-BBC/M
0614
Canal RS-232
3-MODCOM
0615
Problema de Batera
3-PPS/M
3-BPS/M
3-BBC/M
0616
Red_Clase A_Circuito
A_Falla_01_01
CPU
0617
Red_Clase A_Circuito
B_Falla_01_01
CPU
0616
Circuito 2 Sobrecargado de
Energa Auxiliar
3-PPS/M
3-BPS/M
3-BBC/M
1. Carga excesiva
2.Circuito en corto
0617
Supervisin DSP
3-MODCOM
0617
3-PPS/M
3-BPS/M
3-BBC/M
8.30
Etiqueta
Fuente
Descripcin
0618
Circuito 1 Sobrecargado de
Energa Auxiliar
3-PPS/M
3-BPS/M
3-BBC/M
1. Carga excesiva
2.Circuito en corto
0619
3-PPS/M
3-BPS/M
3-BBC/M
0620
3-ZAxx
0620
0621
Sobre corriente en el
amplificador
3-ZAxx
1.Circuito en corto
2. Configuracin de la llave de potencia
en vatios del bafle excede a la
valuacin de salida del amplificador
3. Configuracin de cable puente 70
Vrms utilizada con bafles de 25 Vrms. .
0622
3-ZAxx
0623
3-ZAxx
0624
3-ZAxx
0625
3-ZAxx
Tablero defectuoso
0626
Supervisin de fusible
3-ZAxx
0627
Supervisin PAL
3-ZAxx
0629
Solicitud de Respaldo
3-ZAxx
N/A
0630
Supervisin de Contrahuella
3-FTCU
8.31
Etiqueta
Fuente
Descripcin
0631
Interface de Usuario
3-FTCU
0632
0633
3-FTCU
0640
3-OPS
0641
3-OPS
0642
3-OPS
N/A
0652
Problemas de Supervisin de
Entrada
3-ASU
0653
3-ASU
0654
Incongruencia en el Equipo de
Audio
3-ASU
0655
3-ASU
0656
3-ASU
0658
3-ASU
0659
3-ASU
0670
3-AADC1
0670
3-DSDC
3-SSDC1
3-SDDC1
0671
3-AADC1
Falla en el cableado
0671
Tarjeta 1 de Informacin de
Lnea Abierta o en Corto
3-DSDC
3-SSDC1
3-SDDC1
Falla en el cableado
0672
Tarjeta 1 de Informacin de
Falla de Mapeo
3-DSDC
3-SSDC1
3-SDDC1
0677
Falla de Tierra
3-AADC1
Falla en el cableado
8.32
Etiqueta
Fuente
Descripcin
0677
Tarjeta 1 de Informacin de
Falla de Tierra
3-DSDC
3-SSDC1
3-SDDC1
Falla en el cableado
0678
Lnea de Reconstruccin
3-AADC1
N/A
0679
3-AADC1
N/A
0679
3-DSDC
3-SSDC1
3-SDDC1
N/A
0680
Falla Interna
3-LDSM
N/A
0681
Tarjeta 2 de Informacin de
Lnea Abierta en Corto
3-DSDC
3-SSDC1
3-SDDC1
Falla en el cableado
0682
Tarjeta 2 de Informacin de
Falla de Mapeo
3-DSDC
3-SSDC1
3-SDDC1
0687
Tarjeta 2 de Informacin de
Falla de Tierra
3-DSDC
3-SSDC1
3-SDDC1
Falla en el cableado
0689
3-DSDC
3-SSDC1
3-SDDC1
Mdulo defectuoso
0690
Configuracin Incongruente en
Ranura 1
3-DSDC
3-SSDC1
3-SDDC1
N/A
Etiqueta
Fuente
Descripcin
0615
Timbre de Entrada
3-MODCOM
0622
0650
3-ASU
0651
3-ASU
0673
Tarjeta 1 de Informacin de
Mapeo en Proceso
3-DSDC
3-SSDC1
3-SDDC1
N/A
Marcacin activa
8.33
Etiqueta
Fuente
Descripcin
0674
Tarjeta 1 de Informacin No
disponible de Mapeo
3-DSDC
3-SSDC1
3-SDDC1
0675
Alerta de Mantenimiento de
Mecanismos
3-AADC1
N/A
0675
Tarjeta 1 de Informacin de
Alerta de Mantenimiento de
Mecanismo
3-DSDC
3-SSDC1
3-SDDC1
0678
Tarjeta 1 de Informacin de
Lnea de Reconstruccin
3-DSDC
3-SSDC1
3-SDDC1
N/A
0683
Tarjeta 2 de Informacin de
Procesamiento de Mapeo
3-DSDC
3-SSDC1
3-SDDC1
N/A
0684
Tarjeta 2 de Informacin No
disponible de Mapeo
3-DSDC
3-SSDC1
3-SDDC1
0685
Tarjeta 2 de Informacin de
Alerta de Mantenimiento de
Mecanismo
3-DSDC
3-SSDC1
3-SDDC1
0688
Tarjeta 2 de Informacin de
Lnea de Reconstruccin
3-DSDC
3-SSDC1
3-SDDC1
N/A
Etiqueta
Fuente
Descripcin
0621
3-MODCOM
Etiqueta
Tipo de evento
Descripcin
SS01
Problema de
Acceso
SS02
Batera Baja
Problema de
Acceso
SS03
Pisn
Alarma de
Seguridad
SS04
Falla de Barra
Problema de
Acceso
8.34
Etiqueta
Tipo de evento
Descripcin
SS05
Falla de Lector
Problema de
Acceso
SS06
Problema de
Acceso
SS07
Supervisin de Cdigo
Problema de
Acceso
SS08
Problema de
Acceso
SS09
Falla de Comunicaciones
Problema de
Acceso
SS10
Lazo 1
Alarma de
Seguridad
(configurable)
SS11
Lazo 2
Alarma de
Seguridad
(configurable)
SS12
Falla de Tarea
Problema Local
SS15
SS32
Salida de Acceso
SS33
Salida de Acceso
SS34
Salida de Acceso
SS35
Salida de Acceso
SS36
Salida de Acceso
SS37
Salida de Acceso
SS38
Resonador CRC
Problema de
Acceso
8.35
Etiqueta
Tipo de evento
Descripcin
SS06
Problema Local
SS07
Supervisin de Cdigo
Problema Local
SS08
Problema Local
SS09
Falla de Comunicaciones
Problema Local
SS12
Supervisin de Tarea
Problema Local
SS13
Problema Local
SS14
Supervisin de Registro de
Usuario
Problema Local
N/A
SS15
Problema Local
SS16
SS32
Timbre de Entrada
Salida no
supervisada
SS33
Timbre de Salida
Salida no
supervisada
8.36
Etiqueta
Fuente
Descripcin
0002
3-ZAxx
0003
Canal_1_Relay_
Confirmacin
3-ZAxx
0004
Canal_2_Relay_
Confirmacin
3-ZAxx
0005
Canal_3_Relay_
Confirmacin
3-ZAxx
0006
Canal_4_Relay_
Confirmacin
3-ZAxx
0007
Canal_5_Relay_
Confirmacin
3-ZAxx
0008
Canal_6_Relay_
Confirmacin
3-ZAxx
0009
Canal_7_Relay_
Confirmacin
3-ZAxx
0010
Canal_8_Relay_
Confirmacin
3-ZAxx
0011
Seleccione Llamado
3-ZAxx
8.37
Operacin
8.38
Operacin
1. El sistema muestra un problema con la etiqueta del mecanismo
o con la direccin cuando el mecanismo se retira.
2. Cuando se instala un mecanismo nuevo, el mdulo del
controlador Signature vuelve a mapear el circuito, reemplazando
el S/N del mecanismo anterior con el S/N del nuevo mecanismo.
El nuevo mdulo NO es operativo. El panel presentar problema,
indicando incongruencia en el tipo de mecanismo. El programa
de Herramienta de Definicin del Sistema debe de utilizarse para
re-asignar el tipo de mecanismo y sacar al panel del problema.
3. Si un solo mdulo de direccin se reemplaza con un mdulo de
doble direccin o vice versa, una falla de mapeo se generar por
la incongruencia entre el nmero de direcciones.
8.39
8.40
8.41
8.42
Mdulos de telfono
SIGA-CC1
SIGA-CC1S
SIGA-MCC1
SIGA-MCC1S
1. Circuito de informacin
Signature
2.Circuito de energa de humo 24
Vdc
1.
8.43
8.45
8.46
8.47
8.48
8.49
8.51
8.52
Causa posible
Circuito de Informacin
Signature abierto
1.
2.
3.
4.
5.
Circuito de Informacin
Signature en corto
Errores de mapeo
La Tabla 0-28 proporciona informacin bsica sobre errores de
mapeo. Para informacin detallada sobre la identificacin y
localizacin de errores de mapeo, consulte las secciones de
EST3 Manual de Servicio e Instalacin
8.53
Posibles causas
Error de mapeo
1.
2.
3.
4.
5.
El sistema vuelve a mapear
continuamente del circuito de
informacin
1.
2.
Error de tipo de mecanismo
8.54
1.
Verde (destellando)
Comunicacin normal
Rojo (destellando)
Alarma o Activo
(ya sea en mdulos de entrada o de entrada
dual)
C
C
2
C
R
C
R
R
C
T
1
C
T
2
M
M
1
U
M
W
T
M
Causas posibles
8.55
x
x
x
x
Causas posibles
Detector no responde
correctamente
8.56
8.57
Tip: La Herramienta
de Diagnstico
Signature est en el
men de herramientas
SDU.
8.58
8.59
1. Errores de Mapeo
2. Cadenas de Mecanismos
3. Conteos de Mensaje
1. Tablas de Mecanismos
2. Tablas de Problemas
8.60
1.
2.
3.
1.
2.
3.
1.
2.
1.
1.
8.61
1.
1.
2.
Reemplace el mecanismo
Corrija la programacin del mdulo controlador
Signature
1.
2.
3.
1.
1.
2.
3.
El mapeo ha sido deshabilitado
1.
Habilite el mapeo.
1.
1.
2.
8.62
2.
Corrija el cableado.
Vuelva a mapear el circuito.
1.
2.
8.63
8.64
8.65
Pregunta Aislante
Pregunta Estado
Pregunta Mscara de
Mecanismo
8.66
Mdulo PFX
Restablece Mecanismo
Habilita Mecanismo
Deshabilita Mecanismo
Inicia Mecanismo
Relay Control
Restablece Estado de
Mecanismo
Selecciona Sensores
8.67
Causa posible
Posible solucin
Detector Defectuoso
Reemplace el Detector
Apertura de Lnea de
Mecanismo Externo
Detector Defectuoso
Reemplace el Detector
Detector Sucio
Limpie el detector
Corto en el circuito de
informacin Signature
1.
2.
Detector Sucio
Cmara de Ion Daada
1.
2.
Limpie el Detector
Reemplace el Detector
1.
2.
Detector Sucio
Cmara de Ion Daada
1.
2.
Limpie el Detector
Reemplace el Detector
1.
2.
Detector Sucio
Cmara de Ion Daada
1.
2.
Limpie el Detector
Reemplace el Detector
8.68
Causa posible
Posible solucin
Reemplace la Base
1.
2.
1.
2.
Base Daada
Reemplace la Base
Reemplace el Detector
Detector Sucio
Limpie el detector
Detector Sucio
Limpie el detector
Detector Defectuoso
Reemplace el Detector
Base Daada
Reemplace la Base
Base Daada
Reemplace la Base
Reemplace el Detector
EEPROM daado
Reemplace el Detector
EEPROM daado
Reemplace el Detector
Clase de Mecanismo
Desconocido
EEPROM daado
Reemplace el Detector
EEPROM daado
Reemplace el Detector
1.
2.
1.
2.
Detector Sucio
Limpie el detector
Detector Sucio
Limpie el detector
Base Daada
Reemplace la Base
Detector Sucio
La luz de exterior llega a la
cmara del detector
Limpie el Detector
Elimine la fuente de luz
8.69
Causa posible
Posible solucin
Relay intercambiado
EEPROM no inicializado
EEPROM no programado
adecuadamente
Reemplace el mdulo
EEPROM daado
Reemplace el mdulo
A/D Tiempo-fuera
Reemplace el mdulo
EEPROM defectuoso
Reemplace el mdulo
Falla Clase A
El voltaje en el cable de
Verifique la salida de la fuente de
suministro de energa de humo energa.
de 24 Vdc al SIGA-UM est
Verifique el cableado
fuera de rango.
RAM no programada
RAM daado
Reemplace el mdulo
8.71
8.72
Estado de DSDC
Introduccin
La funcin de estado de la DSDC se utiliza para determinar el
estado del tiempo-real de Circuito de Informacin Signature
(SDC). Esta funcin se utiliza para aislar y corregir las fallas en el
SDC. La funcin de estado DSDC es utilizada junto con la
descarga y las funciones de diagnstico del DSCS.
8.73
8.74
Funcin
Falla interna
Problema de Informacin
de la Verificacin de suma
Falla I/F
Falla de Lnea
Falla de Mapeo
Mapeo en proceso
Mapeo deshabilitado
Mecanismo Sucio
Se ha identificado un detector de
humo sucio
Alarma no configurada
Inicializacin de lnea
Mapeo Balanceado
Modo de Programacin
Falla RAM
Mapeo Pendiente
8.75
Funcin
Autnomo
Alarma Autnoma
Falla de tierra
Falla de Tierra de
Mecanismo
Delta suspendido
8.76
8.77
8.78
8.79
Descripcin
Mecanismos de
Comunicacin
Falla interna
Falla de tipo de
mecanismo
Falla
Inesperada
Un mecanismo reporta a la
direccin no configurada.
8.80
Causas posibles
Descripcin
Causas posibles
Falla de
Comunicacin
Mecanismo Faltante
Falla de apertura
Falla de Corto
Falla de
Compatibilidad
8.81
8.82
8.83
Causa posible
1.
2.
3.
4.
5.
8.84
8.85
Rojo Parpadeante
Mecanismo de sondeo
Rojo Estable
Alarma o Activo
M501
MF
M500
CF
8.86
x = Aplicable
- = No aplicable
Tabla 0-42: Solucin de problemas del detector anlogo direccional
Sntoma
Causas posibles
Detector no responde
correctamente
1.
2.
3.
Detector en problema en el
CPU/LCD
1.
2.
3.
4.
Detector incorrectamente en
alarma en el CPU/LCD
1.
2.
3.
4.
8.87
Problemas de cableado
Hay tres causas bsicas de operacin errtica relacionadas
con el cableado de un circuito Anlogo Direccional:
Resistencia de cableado excesiva
8.89
8.90
Apndice A
Direcciones del Sistema
Resumen
Direcciones de Sistema
Formato de direccin
Tip: Para determinar el
nmero de gabinete del
panel local, utilice el men
de comando LCD para
obtener el estado de todos
los puntos activos en el
panel. Cuando un nmero
de panel le sea solicitado,
ingrese 00. El panel
regresa la direccin lgica
del punto de respuesta de
arranque. Los primeros dos
nmero de la direccin
lgica son los nmeros de
gabinete.
Direcciones de sistema
Direcciones de Sistema
Direcciones LRM
La Figura 0-2, la
Direcciones de sistema
Direcciones de Sistema
Direcciones de sistema
Direcciones de Sistema
Figura 0-5: Direcciones LRM cuando se utiliza una Pantalla LCD Principal 3-LCDXL1
Direcciones de sistema
Direcciones de Sistema
Direcciones de mecanismo
La Figura 0-7 muestra las direcciones lgicas del mecanismo
que el sistema asigna a diversos mdulos de riel.
10
Apndice B
Clculos del Sistema
Resumen
B.1
System calculations
Resistencia: 90 ohms ()
Capacidad: 0.3 microfaradios ( F)
Distancia: 5,000 pies
B.2
System calculations
A 19.2 Kbaud
18
1.4
2.8
16
1.8
3.6
14
2.1
4.2
B.3
System calculations
B.4
System calculations
10
12
[WIRECALC2.CDR]
B.5
System calculations
B.6
System calculations
Tabla B-1: Mxima longitud de ramal con 0 SIGA-UMs configurados para detectores de humo de dos cables
Direcciones
detectores
Signature
Direcciones
mdulos
Signature
Distancia mxima de cable permitida usando par de cables no trenzado y sin pantalla
18 AWG
16 AWG
14 AWG
ft
ft
ft
125
7437
2267
11815
3601
18792
5728
2650
7038
2145
11180
3408
17782
5420
5175
6638
2023
10545
3214
16772
5112
76100
6238
1901
9910
3021
15762
4804
101125
5839
1780
9275
2827
14752
4497
125
7267
2215
11544
3519
18361
5597
125
125
6867
2093
10909
3325
17351
5289
2650
125
6467
1971
10275
3132
16342
4981
5175
125
6068
1849
9640
2938
15332
4673
76100
125
5668
1728
9005
2745
14322
4365
101125
125
5268
1606
8370
2551
13312
4057
2650
6697
2041
10639
3243
16921
5157
125
2650
6297
1919
10004
3049
15911
4850
2650
2650
5897
1798
9369
2856
14901
4542
5175
2650
5498
1676
8734
2662
13891
4234
76100
2650
5098
1554
8099
2469
12881
3926
101125
2650
4698
1432
7464
2275
11871
3618
5175
5906
1800
9383
2860
14923
4549
125
5175
5250
1600
8340
2542
13265
4043
2650
5175
4633
1412
7360
2243
11707
3568
5175
5175
4051
1235
6435
1961
10235
3120
76100
5175
3498
1066
5558
1694
8839
2694
101125
5175
2973
906
4723
1440
7512
2290
76100
3931
1198
6245
1903
9932
3027
125
76100
3404
1037
5407
1648
8601
2621
2650
76100
2899
883
4605
1404
7324
2232
5175
76100
2413
735
3833
1168
6096
1858
76100
76100
1945
593
3089
942
4913
1498
101125
76100
1493
455
2371
723
3771
1149
101125
2631
802
4180
1274
6649
2027
125
101125
2165
660
3439
1048
5470
1667
2650
101125
1713
522
2721
829
4328
1319
5175
101125
1274
388
2023
617
3218
981
76100
101125
847
258
1345
410
2140
652
101125
101125
431
131
685
209
1089
332
B.7
System calculations
Tabla B-2: : Mxima longitud de ramal con 1 a 5 SIGA-UMs configurados para detectores de humo de dos cables
Direcciones
detectores
Signature
Direcciones
mdulos
Signature
Distancia mxima de cable permitida usando par de cables no trenzado y sin pantalla
18 AWG
16 AWG
14 AWG
ft
ft
ft
125
6778
2066
10768
3282
17126
5220
2650
6131
1869
9741
2969
15492
4722
5175
5501
1677
8739
2664
13899
4236
76100
4885
1489
7760
2365
12342
3762
101125
4282
1305
6802
2073
10819
3298
125
5353
1632
8504
2592
13525
4122
125
125
4720
1439
7498
2286
11926
3635
2650
125
4100
1250
6513
1985
10359
3157
5175
125
3491
1064
5546
1691
8821
2689
76100
125
2893
882
4597
1401
7311
2228
101125
125
2306
703
3663
1116
5826
1776
2650
3776
1151
5999
1829
9542
2908
125
2650
3153
961
5009
1527
7966
2428
2650
2650
2539
774
4034
1230
6416
1956
5175
2650
1935
590
3075
937
4890
1491
76100
2650
1340
409
2130
649
3387
1032
101125
2650
754
230
1197
365
1905
581
5175
2491
759
3957
1206
6293
1918
125
5175
1868
569
2967
904
4720
1439
2650
5175
1254
382
1992
607
3168
966
5175
5175
648
198
1030
314
1638
499
76100
5175
50
15
80
24
126
39
101125
5175
76100
1386
422
2201
671
3501
1067
125
76100
760
232
1208
368
1921
586
2650
76100
143
44
227
69
361
110
5175
76100
76100
76100
101125
76100
101125
125
101125
2650
101125
5175
101125
76100
101125
101125
101125
B.8
System calculations
Tabla B-3: Mxima longitud de ramal con 6 a 9 SIGA-UMs configurados para detectores de humo de dos cables
Direcciones
detectores
Signature
Direcciones
mdulos
Signature
Distancia mxima de cable permitida usando par de cables no trenzado y sin pantalla
18 AWG
16 AWG
14 AWG
ft
ft
ft
m
3886
125
5045
1538
8015
2443
12748
2650
4494
1370
7139
2176
11355
3461
5175
3950
1204
6275
1913
9981
3042
76100
3414
1040
5423
1653
8625
2629
101125
2884
879
4581
1396
7286
2221
125
4106
1252
6523
1988
10375
3162
125
125
3542
1080
5627
1715
8950
2728
2650
125
2985
910
4742
1445
7542
2299
5175
125
2435
742
3868
1179
6152
1875
76100
125
1891
576
3004
916
4778
1456
101125
125
1353
412
2150
655
3419
1042
2650
2869
874
4557
1389
7248
2209
125
2650
2296
700
3648
1112
5802
1768
2650
2650
1730
527
2749
838
4372
1332
5175
2650
1170
357
1859
567
2957
901
76100
2650
617
188
979
299
1558
475
101125
2650
68
21
108
33
172
53
5175
1796
547
2853
869
4537
1383
125
5175
1214
370
1929
588
3067
935
2650
5175
638
195
1014
309
1613
492
5175
5175
69
21
109
33
173
53
76100
5175
101125
5175
76100
833
254
1323
403
2105
642
242
74
385
117
613
187
125
76100
2650
76100
5175
76100
76100
76100
101125
76100
101125
125
101125
2650
101125
5175
101125
76100
101125
B.9
System calculations
Tabla B-3: Mxima longitud de ramal con 6 a 9 SIGA-UMs configurados para detectores de humo de dos cables
Direcciones
detectores
Signature
Direcciones
mdulos
Signature
Distancia mxima de cable permitida usando par de cables no trenzado y sin pantalla
18 AWG
ft
101125
16 AWG
m
ft
14 AWG
ft
101125
10
12
[WIRECALC2.CDR]
14 AWG
16 AWG
18 AWG
Par trenzado
13,157 ft
(4,010 m)
13,888 ft
(4,233 m)
20,000 ft
(6,096 m)
5,952 ft
(1,814 m)
6,098 ft
(1,859 m)
8,621 ft
(2,628 m)
20,000 ft
(6,096 m)
20,000 ft
(6,096 m)
B.10
System calculations
Nota: En ningn caso la longitud total del lazo de un circuito
B.11
System calculations
B.12
System calculations
Lo que va a necesitar
Valores de dispositivos y cable
B.13
System calculations
Valores de la fuente de energa
Voltaje mnimo
Cada del voltaje
B.14
System calculations
NAC2
NAC3
NAC4
Factor de cargar
Voltaje medido
0.37
0.37
0.37
0.37
V/A
V
20.4
20.4
20.4
20.4
Voltaje mnimo
Mxima resistencia
16.0
16.0
16.0
16.0
ft
2
ft
[1] Total de la corrientes mximas de operacin para todos los dispositivos como se especifica para
energa DC. Ver las hojas de instalacin de dispositivos para corrientes de operacin.
[2] Esta cada de voltaje es vlida para dispositivos de notificacin regulados nicamente. Para
dispositivos no regulados, ver el Mtodo de Ecuacin, mas adelante en este tema.
[3] Utilice la resistencia de cable publicada por el fabricante expresada en ohms por pie. Para valores
tpicos, ver Tabla 4, ms adelante en este tema.
B.15
System calculations
Mtodo de ecuacin
Voltaje y corriente de operacin de dispositivos
Resistencia
1 hebra de cobre sin
recubrimiento
Resistencia
7 hebras cobre sin
recubrimiento
por pie
por metro
por pie
por metro
12
0.00193
0.00633
0.00198
0.00649
14
0.00307
0.01007
0.00314
0.01030
16
0.00489
0.01604
0.00499
0.01637
18
0.00777
0.02549
0.00795
0.02608
B.16
System calculations
B.17
System calculations
En donde:
Rmax = mxima resistencia
Rw = factor de resistencia del cable
Ejemplo: Usted est usando dispositivos de notificacin
B.18
System calculations
En donde:
59.25 X 25
13 X 30
13.0
8.0
5.2
3.2
B.19
System calculations
Las Tabla B-6 y Tabla B-7 dan las longitudes mxima de cable
permitidas para diferentes tamaos de cable y cargas. Use
Tabla B-6 al disear circuitos para amplificadores
configurados a 25 Vrms de salida. Use Tabla B-7 al disear
circuitos para amplificadores configurados a 70 Vrms de
salida.
Tabla B-6: Longitud mxima permitida a 25 Vrms, prdida de 0.5 dB
Requerimiento de carga del circuito
Calibre de
cable
15 W
20 W
30 W
40 W
95 W
120 W
ft
ft
ft
ft
ft
18 AWG
(0.75 sq mm)
190
58
142
43
95
29
71
22
16 AWG
(1.0 sq mm)
309
94
231
70
154
47
116
35
48.7
15
39
12
14 AWG
(1.5 sq mm)
475
145
356
109
237
72
178
54
75
23
59
18
12 AWG
(2.5 sq mm)
772
235
579
176
386
118
289
88
121.8
37
96
29
Arriba del
lmite max. de
corriente
ft
Arriba del
lmite max.
de corriente
Calibre de
cable
15 W
20 W
30 W
95 W
40 W
120 W
ft
ft
ft
ft
ft
ft
18 AWG
(0.75 sq mm)
1489
454
1117
340
744
227
558
170
235
72
186
57
16 AWG
(1.0 sq mm)
2420
738
1815
553
1210
369
907
276
382
116
302
92
14 AWG
(1.5 sq mm)
851
1861
567
1396
426
588.7
180
465
142
12 AWG
(2.5 sq mm)
922
2268
691
955
291
756
230
B.20
System calculations
Trenzado,
apantallado
ft
ft
ft
0.01 F
4000
1219
1724
525
5000
1524
0.02 F
8000
2438
3448
1051
10000
3048
0.03 F
12000
3658
5172
1576
15000
4572
0.04 F
16000
4877
6896
2102
20000
6096
0.05 F
20000
6096
8620
2627
25000
7620
0.01 F
2777
846
1219
372
5000
1524
0.02 F
5555
1693
2439
743
10000
3048
0.03 F
8333
2540
3658
1115
15000
4572
0.04 F
11111
3387
4878
1487
20000
6096
0.05 F
13888
4233
6097
1858
25000
7620
0.01 F
2631
802
1190
363
5000
1524
0.02 F
5263
1604
2380
725
10000
3048
0.03 F
7894
2406
3571
1088
15000
4572
0.04 F
10526
3208
4761
1451
20000
6096
0.05 F
13157
4010
5952
1814
25000
7620
18
16
14
B.21
System calculations
Gabinete de la batera
Utilice el siguiente mtodo para calcular la mnima capacidad
amperes- hora de una batera requerida para operar el panel
en ausencia de energa AC. Los clculos de batera deben
llevarse a cabo por separado para cada gabinete del sistema.
Determina la cantidad total de corriente en miliamperes
requeridos por todos los componentes que derivan energa de
la batera mientras el panel est en modo de espera.
Multiplique la cantidad total de corriente en espera por el
nmero de horas que el panel va a tener que operar en modo
de espera con energa de la batera.
Determine la cantidad de total de corriente en miliamperes
requeridos por todos los componentes que derivan energa de
la batera mientras el panel est en modo de alarma.
Multiplique la cantidad total de corriente de alarma por el
numero de minutos que el panel necesita trabajar en modo
de alarma con energa de la batera.
Sume la cantidad total de corriente en espeta y la cantidad
total de corriente en alarma y divida el resultado entre 1000
para convertir a amperes-hora. Multiplique este nmero por
1.2 para agregar un 20% de factor de seguridad a los
clculos.
EST3 esta en la lista UL para duracin de operacin con
batera como sigue:
B.22
System calculations
B.23
System calculations
KPDISP
100
35
CRC
950
940
CR-5355
72
70
CR-5365
31
25
CR-5395
24
20
CR-6005
20
20
Lector sirena
CRCSND
100 mA @ 12 V
33
150 mA @ 12 V
40
200 mA @ 12 V
42
250 mA @ 12 V
47
300 mA @ 12 V
51
35 mA @ 12 V
55
400 mA @ 12 V
58
450 mA @ 12 V
63
500 mA @ 12 V
65
100 mA @ 12 V
80
80
150 mA @ 12 V
126
126
200 mA @ 12 V
156
156
250 mA @ 12 V
187
187
300 mA @ 12 V
233
233
350 mA @ 12 V
283
283
400 mA @ 12 V
376
376
450 mA @ 12 V
436
436
500 mA @ 12 V
470
470
Barra
Chapa Magntica
Nota: Tiempo en espera = cantidad de tiempo que el dispositivo consumir corriente en espera de la
batera. No hay tiempo en espera mnimo para control de acceso.
B.24
System calculations
B.25
System calculations
Cada de voltaje real
400
450
500
550
600
650
885
800
720
665
616
880
760
666
594
532
484
444
410
990
780
660
570
498
444
399
363
333
306
800
624
520
452
400
355
320
288
266
244
1875 1350
885
650
525
435
375
333
296
266
242
222
205
1620 1140
756
558
450
378
324
286
254
228
207
190
1400
980
665
497
392
329
285
250
222
199
1240
880
584
440
352
288
253
222
197
1125
810
522
396
315
261
228
200
10
1030
730
480
360
290
240
207
B.26
70
100
150
200
250
300
350
System calculations
Tabla B-9: Longitud del cable de bus SAC para nmero de puertas vs. carga de corriente usando
cable 16 AWG
Carga (mA)
Puerta
s
70
100
150
200
250
300
350
400
450
500
550
600
650
11
946
660
440
330
264
220
12
876
600
408
300
240
13
806
559
377
273
14
756
518
350
15
705
495
330
16
672
464
304
17
629
442
18
576
414
19
570
399
20
540
380
Nota: Todas las medidas de distancia estn en pies. X significa que el 3-PPS/M no soportar a estos
dispositivos a ninguna distancia.
Tabla B-10: Longitud del cable de bus SAC para nmero de puertas vs. carga de corriente usando
cable 14 AWG
Carga (mA)
Puerta
s
70
100
150
200
250
600
650
4000 4000 4000 3000 2400 2000 1750 1500 1360 1200 1100 1000
940
900
800
740
680
620
870
750
660
600
555
510
471
960
800
700
600
544
480
436
400
376
800
675
575
500
455
405
365
335
315
870
690
582
492
438
390
348
312
756
602
511
434
378
336
301
1920 1360
904
680
544
448
384
336
1710 1215
810
612
477
405
351
10
1550 1100
740
550
440
370
310
11
1430 1012
682
506
407
341
12
1344
936
624
468
372
13
1248
858
585
429
351
300
350
400
450
500
550
B.27
System calculations
Tabla B-10: Longitud del cable de bus SAC para nmero de puertas vs. carga de corriente usando
cable 14 AWG
Carga (mA)
Puerta
s
70
100
150
200
250
300
350
400
450
500
550
600
650
14
1162
812
532
406
322
15
1095
750
510
375
16
1024
720
480
352
17
969
680
442
340
18
918
630
414
19
874
608
399
20
820
580
380
Nota: Todas las medidas de distancia estn en pies. X significa que el 3-PPS/M no soportar a estos
dispositivos a ninguna distancia.
B.28
System calculations
Memoria CPU
Use la hoja de trabajo para calcular la memoria CPU, la Tabla
B-11, para determinar si un CPU requiere memoria adicional.
Cada lnea en la hoja de trabajo es un variable del sistema y
esta referenciada por una letra de identificacin de lnea (ID).
Los IDs de lnea tambin aparecen en la columna de la
formula. El resultado de resolver la formula es colocado en la
columna de Resultados.
Ingrese los valores de cada variable en la columna # en la
misma lnea.
Reemplace las variables en la formula por el valor ingresado
en la columna # que tiene la misma letra que la formula.
Calcule la formula y anote los resultados en la columna de
Resultados.
Determine el tamao de la memoria requerido como se indica
al final de la hoja de trabajo.
Nota: La Herramienta de Definicin del Sistema le impide
B.29
System calculations
Formula
Resultado
70,000
Uso de la base
N/A
N/A
Uso de etiquetas
N/A
48+(22 x (H+K+L+N+Q+S+T))
Entre 0 y 42
2 + (E x 8)
F x 916
G x 1,776
Nmero de zonas
H x (22 + C + (J x 4) + (D x 2))
N/A
K x (14 x C + (2 x D))
L x (22 + C + (D x 2) + (M x 4))
N/A
N x (22 + C + (2 x D) + (4 x P))
N/A
Q x ((24 + C) + (2 x D) + (4 x R))
N/A
S x ((26 + C) + (2 x D) + 14))
T x (22 + C + (V x 4) + (U x 4))
N/A
N/A
W x (46 + C + (Y x 4) + (2 x D) + 8)
N/A
A+B+C+D+E+F+G+H+J+K+L+M+N+P+Q+
R+S+T+U+V+W+Y
B.30
System calculations
B.31
System calculations
B.32
B
Distancia
[ ] Pies
[ ] Km
[ ] Millas
C
Prdida de
Cable
AxB
D
Nmero de
empalmes
E
Empalmes de
contingencia
F
Prdida total de
enlaces (dB)
C+2[D+E]
Apndice C
Requisitos de Listados
Resumen
Requisitos de Listados
C.2
Requisitos de Listados
Requisitos adicionales:
C.3
Requisitos de Listados
Equipo mnimo:
Requisitos adicionales:
C.4
Requisitos de Listados
Requisitos adicionales:
C.5
Requisitos de Listados
Requisitos adicionales:
C.6
Requisitos de Listados
Requisitos adicionales:
Patentado Grado A
Norma: UL 1076
Equipo mnimo:
Requisitos adicionales:
C.7
Requisitos de Listados
Patentado Grado AA
Norma: UL 1076
Equipo mnimo:
Requisitos adicionales:
Control de acceso
Norma: UL 294
Equipo mnimo:
Alarma de interrupcin
Norma: UL 636
Equipo mnimo:
C.8
Requisitos de Listados
Requisitos adicionales:
C.9
Requisitos de Listados
C.10
Requisitos de Listados
Requisitos UL y ULC
La siguiente tabla describe los requisitos que su sistema debe
tener para cumplir con la UL o ULC.
UL
ULC
Requisito
Sistema de Seguridad
Todos los sistemas de seguridad deben especificar una estacin de armado maestra
la cual recibe todos los mensajes de eventos de seguridad. Alternativamente, el
sistema puede configurarse de tal manera que todos los mensajes estn enrutados
a todos los teclados.
Todos los gabinetes en un sistema que incluye funcionalidad de seguridad deben de
incluir interruptores de pisn.
Cuando se activan, todos los puntos de seguridad deben generar una respuesta de
mecanismo de salida apropiada. La SDU no puede garantizar la correlacin entre los
mecanismos de seguridad de entrada y de salida. El programador del sistema debe
de asegurarse de que todos los puntos estn considerados. Cuando el sistema
incluye una campana Grado A, usted debe de crear una regla general para sonar la
campana cuando se active cualquier mecanismo de seguridad.
C.11
Requisitos de Listados
UL
ULC
Requisito
C.12
Y
Glosario
accin de inicio
ACDB
activar
Afirmacin AND
alarma
verificacin de alarma
Base de datos
Cambio de estado
Canal RS-232
Canal RS-485
circuito audible
Circuito de Informacin
Signature
circuito de supervisin
Y.1
Glossary
CMS
codificador
Cdigo de identificacin
compilar
contrahuella
control de tiempo
CRC
DACT
descargar
direccin
Direccin de dispositivo
Dispositivo
Dispositivo o zona
Dominio de grupo
Dominio global
Dominio local
EEPROM
emergencia
Energa-limitada
entrada
EPROM
Y.2
Glossary
etiqueta
Fibra ptica
Funciones lgicas
Afirmaciones AND y OR
grupo
Grupo check-in
grupo de servicio
habilitar
Herramienta de Definicin de
Sistema
IDC
IDC Clase A
IDC Clase B
inhabilitar
KDC
KPDISP
Y.3
Glossary
Lista de comandos
listado
M dispositivo o zona
marcador
Ver DACT
matriz
Mecanismo S o zona
Memoria flash
mdem
NAC
NAC Clase
NAC Clase A
no silenciable
Objeto
Y.4
Glossary
patrn temporal
Prioridad de salida
Protocolo TAP
PSNI
Punto Falso
RAM
regla
respuesta
restablecer
restitucin
retardar
Salida
SDU
secuencia
secuencia de inicio
Y.5
Glossary
sensibilidad
SIGA
Abreviacin de Signature A
silenciable
Sistema local
Sistema propietario
SPM
supervisin en corto
telco
Compaa de telfonos
Temporizador de silencio de
alarma
Tiempo de marcha
zona
Y.6