You are on page 1of 7

OVR Type 1+2 surge protective devices

Single pole
Description
Type 1 and Type 1+2 surge protective devices are designed to discharge high current surges without any destruction of the installation. These surge protective devices are characterized by their capacity to withstand
impulse current with 10/350 s wave form which simulate natural lightning current.
Type 1+2 ABB surge protective devices have a high impulse current withstand capacity with ensuring a low
protection level (Up).
Type 1 and Type 1+2 SPDs can be installed at the entrance in the main switch board for a global protection
of the electrical installation.

3
OVR T1+2 15-255-7

Ordering details
Nb of Impulse Max.
poles current discharge
current
Iimp
Imax
10/350 8/20
kA
kA
1
7
70
1
15
140
1
25
60

Follow
current
interrupting
rating
Ifi

Voltage
Nominal Max. cont. Type
protection voltage operating
level
voltage
Up

Un

Uc

kA
15

kV
1.4
1.4
1.5

V
230/400
230/400
230/400

V
275
440
255

Follow current interrupting rating 7 kA


1
15
60
7
1.7
230/400 255

Main dimensions

Order code

EAN
code

Weight
Pkg
(1 pce)

3660308
OVR T1+2 7-275s P 2CTB815101R3900 513403
OVR HL 15-440s P TS 2CTB815201R0800 509802
OVR T1+2 25-255 TS 2CTB815101R0300 510884

kg
0.15
0.32
0.27

OVR T1+2 15-255-7

0.14

2CTB815101R8900 514134

mm

OVR HL 15-440s P TS

OVR T1+2 7-275s P

35

OVR T1+2 25-255 TS

Type
OVR T1+2 7-275s P
OVR HL 15-440s P TS
OVR T1+2 25-255 TS
OVR T1+2 15-255-7

OVR T1+2 15-255-7

Width
mm
17.8
35.6
35.0
17.8

inches
0.70
1.40
1.38
0.70

32 | ABB System pro M compact

1TXH000083C0202_OVR_proM.indb 32

17/09/2012 15:57:40

OVR Type 1+2 surge protective devices


Single pole
General technical data
Types
with auxiliary contact (TS)

Technology
Wiring diagram

OVR T1+2 7-275s P

Varistor

OVR T1+2

Electrical features
Standard
Type / test class
Protected lines
Types of networks
Type of current
Nominal voltage Un
Maximum continuous operating voltage Uc
Maximum impulse current Iimp (10/350)
Maximum impulse current Tot. Iimp (10/350)
Maximum discharge current Imax (8/20)
Nominal discharge current In (8/20)
Follow current interrupting rating Ifi
Voltage protection level Up at In (L-N/N-PE/L-PE)
Voltage protection level Up at 3kA (L-N/N-PE/L-PE)
TOV (Temporary overvoltage) withstand Ut
(L-N: 5s / N-PE: 200ms)
Response time
Residual current IPE
Short-circuit withstand capability Isccr
Backup protection
Fuse (gG - gL)
Circuit breaker (B or C curve)
Pluggable cartridge
Integrated thermal disconnector
State indicator
Safety reserve
Auxiliary contact
Installation
Wire range (L, N, PE)
Solid wire
Stranded wire
Stripping length (L, N, PE)
Tightening torque (L, N, PE)
Auxiliary contact (TS)
Contact complement
Minimum load
Maximum load
Connection cross-section
Miscellaneous characteristics
Stocking and operating temperature
Degree of protection
Fire resistance according to UL 94
Dimensions
height x width x depth
with auxiliary contact (TS)
height x width x depth

OVR T1+2 15-255-7


OVR HL 15-440s P TS OVR T1+2 25-255 TS
Varistor
Spark-gap + varistor
Spark-gap

OVR HL

V
V
kA
kA
kA
kA
kA
kV
kV

IEC 61643-1 / EN 61643-11


T1+T2 / I+II
T1+T2 / I+II
1
1
TNC / TNS / TT
IT / TNC / TNS / TT
AC
AC
230 / 400
230 / 400
275
440
7
15
7
15
70
100
7
5

/ / 1.4
/ / 1.4
/ / 0.8
/ / 1.2

T1+T2 / I+II
1
TNC / TNS / TT
AC
230 / 400
255
25
25
60
25
15
/ / 1.5
/ / 1.0

T1+T2 / I+II
1
TNC / TNS / TT
AC
230 / 400
255
15
15
60
15
7
/ / 1.7
/ / 0.9

V
ns
A
kA

334 /
25
50
50

440 /
25
50
50

334 /
100
10
50

650 /
100
1000
50

50
50
Yes
Yes
Yes
Yes
No

50
50
Yes
Yes
Yes
Yes
Yes

125
125
No
Yes
Yes
No
Yes

125
125
No

Yes
No
No

2.525
2.516
12.5
2

2.550
2.535
15
3.5

2.550
2.535
15
3.5

2.550
2.535
15
3.5

1 NO - 1 NC
12 V DC - 10 mA
250 VAC - 1 A
1.5

1 NO - 1 NC
12 V DC - 10 mA
250 VAC - 1 A
1.5

-40 to +80
IP20
V0

-40 to +80
IP20
V0

-40 to +80
IP20
V0

-40 to +80
IP20
V0

mm
inches

85 x 17.8 x 64.8
3.35 x 0.70 x 2.55

85 x 17.8 x 70.8
3.35 x 0.70 x 2.79

mm
inches

90 x 35.6 x 65
3.54 x 1.40 x 2.56

93 x 35 x 58
3.66 x 1.38 x 2.28

A
A

mm
mm
mm
Nm

mm
C

ABB System pro M compact | 33

1TXH000083C0202_OVR_proM.indb 33

17/09/2012 15:57:41

OVR Type 1+2 surge protective devices


TNC 230 V networks
Description
Type 1 and Type 1+2 surge protective devices are designed to discharge high current surges without any destruction of the installation. These surge protective devices are characterized by their capacity to withstand
impulse current with 10/350 s wave form which simulate natural lightning current.
Type 1+2 ABB surge protective devices have a high impulse current withstand capacity with ensuring a low
protection level (Up).
Type 1 and Type 1+2 SPDs can be installed at the entrance in the main switch board for a global protection
of the electrical installation.

Ordering details
OVR HL 3L 15-440s P TS

Nb of
poles

3
3

Impulse Max.
current discharge
current
Iimp
Imax
10/350 8/20
kA
kA
15
100
7
70

Main dimensions

Voltage
Nominal Max.
Type
protection voltage cont.
level
operating
voltage
Up
Un
Uc
kV
1.4
1.4

V
V
230/400 440
230/400 275

OVR HL 3L 15-440s P TS
OVR T1+2 3L 7-275s P

EAN
code

Weight
Pkg
(1 pce)

OVR HL 3L 15-440s P TS 2CTB815401R0400


OVR T1+2 3L 7-275s P 2CTB815101R4000

3660308
509833
513410

kg
0.94
0.48

mm

OVR HL 3L 15-440s P TS

Type

Order code

Width
mm
106.8
53.4

OVR T1+2 3L 7-275s P

inches
4.2
2.1

34 | ABB System pro M compact

1TXH000083C0202_OVR_proM.indb 34

17/09/2012 15:57:43

OVR Type 1+2 surge protective devices


TNC 230 V networks
General technical data
Types
with auxiliary contact (TS)

Technology
Wiring diagram

OVR HL 3L 15-440s P TS
Varistor

OVR T1+2 3L 7-275s P

Varistor

OVR T1+2

OVR T1+2

OVR T1+2

OVR HL

3
Electrical features
Standard
Type / test class
Protected lines
Types of networks
Type of current
Nominal voltage Un
Maximum continuous operating voltage Uc
Maximum impulse current Iimp (10/350)
Maximum impulse current Tot. Iimp (10/350)
Maximum discharge current Imax (8/20)
Nominal discharge current In (8/20)
Follow current interrupting rating Ifi
Voltage protection level Up at In (L-N/N-PE/L-PE)
Voltage protection level Up at 3kA (L-N/N-PE/L-PE)
TOV (Temporary overvoltage) withstand Ut
(L-N: 5s / N-PE: 200ms)
Response time
Residual current IPE
Short-circuit withstand capability Isccr
Backup protection
Fuse (gG - gL)
Circuit breaker (B or C curve)
Pluggable cartridge
Integrated thermal disconnector
State indicator
Safety reserve
Auxiliary contact
Installation
Wire range (L, N, PE)
Solid wire
Stranded wire
Stripping length (L, N, PE)
Tightening torque (L, N, PE)
Auxiliary contact (TS)
Contact complement
Minimum load
Maximum load
Connection cross-section
Miscellaneous characteristics
Stocking and operating temperature
Degree of protection
Fire resistance according to UL 94
Dimensions
height x width x depth
with auxiliary contact (TS)
height x width x depth

V
V
kA
kA
kA
kA
kA
kV
kV

IEC 61643-1 / EN 61643-11


T1+T2 / I+II
3
IT / TNC
AC
230 / 400
440
15
45
100
5

/ / 1.4
/ / 1.2

T1+T2 / I+II
3
TNC
AC
230 / 400
275
7
20
70
7

/ / 1.4
/ / 0.8

V
ns
A
kA

440 /
25
150
50

334 /
25
150
50

50
50
Yes
Yes
Yes
Yes
Yes

50
50
Yes
Yes
Yes
Yes
No

2.550
2.535
15
3.5

2.525
2.516
12.5
2

A
A

mm
mm
mm
Nm

1 NO - 1 NC
12 V DC - 10 mA
250 V AC - 1 A
mm 1.5

-40 to +80
IP20
V0

-40 to +80
IP20
V0

mm
inches

85 x 53.4 x 64.8
3.35 x 2.10 x 2.55

mm
inches

90 x 106.8 x 65
3.54 x 4.20 x 2.56

ABB System pro M compact | 35

1TXH000083C0202_OVR_proM.indb 35

17/09/2012 15:57:43

OVR Type 1+2 surge protective devices


TNS/TT 230 V 1Ph+N and 3Ph+N networks
Description
Type 1 and Type 1+2 surge protective devices are designed to discharge high current surges without any destruction of the installation. These surge protective devices are characterized by their capacity to withstand
impulse current with 10/350 s wave form which simulate natural lightning current.
Type 1+2 ABB surge protective devices have a high impulse current withstand capacity with ensuring a low
protection level (Up).
Type 1 and Type 1+2 SPDs can be installed at the entrance in the main switch board for a global protection
of the electrical installation.

Ordering details
OVR T1+2 1N 7-275s P

Nb of Impulse Max.
poles current discharge
current
Iimp
Imax
10/350 8/20
kA
kA
1+1 7
70
3+1 7
70
4
7
70
4
15
100

Follow
current
interrupting
rating
Ifi

Voltage
Nominal Max.
Type
protection voltage cont.
level
operating
voltage
Up
Un
Uc

kA
-

kV
1.4
1.4
0.9
1.4

V
230/400
230/400
230/400
230/400

V
275
275
275
440

Order code

OVR T1+2 1N 7-275s P


OVR T1+2 3N 7-275s P
OVR T1+2 4L 7-275s P
OVR HL 4L 15-440s P TS

OVR T1+2 3N 7-275s P

kg
0.32
0.63
0.60
1.20

2CTB815101R9000 514141

0.84

Width
mm
35.0
71.2
71.2
142.4
89.0

OVR T1+2 4L 7-275s P

OVR T1+2 3N 15-255-7

OVR HL 4L15-440s P TS

OVR T1+2 1N 7-275s P


OVR T1+2 3N 7-275s P
OVR T1+2 4L 7-275s P
OVR HL 4L15-440s P TS
OVR T1+2 3N 15-255-7

3660308
515728
515735
513427
509840

2CTB815302R1000
2CTB815502R1000
2CTB815101R4100
2CTB815503R0400

mm

OVR T1+2 1N 7-275s P

Type

Weight
Pkg
(1 pce)

Follow current interrupting rating 7 kA - 2 poles (1Ph+N)


3+1 15
60
7
1.7
230/400 255
OVR T1+2 3N 15-255-7

Main dimensions

EAN
code

inches
1.38
2.80
2.80
5.60
3.50

36 | ABB System pro M compact

1TXH000083C0202_OVR_proM.indb 36

17/09/2012 15:57:44

OVR Type 1+2 surge protective devices


TNS/TT 230 V 1Ph+N and 3Ph+N networks
General technical data
Types
with auxiliary contact (TS)

Technology
Wiring diagram

OVR T1+2 1N 7-275s P

Varistor

OVR T1+2

OVR T1+2

OVR T1+2 3N 7-275s P

Varistor

OVR T1+2

OVR T1+2

OVR T1+2

OVR T1+2

OVR T1+2 4L 7-275s P

Varistor

OVR T1+2

OVR T1+2

OVR T1+2

OVR T1+2 3N 15-255-7


OVR HL 4L 15-440s P TS
Varistor
Spark-gap

OVR T1+2

OVR T1+2

OVR HL

3
Electrical features
Standard
IEC 61643-1 / EN 61643-11
Type / test class
T1+T2 / I+II
T1+T2 / I+II
Protected lines
1+1
3+1
Types of networks
TNS / TT
TNS / TT
Type of current
AC
AC
V 230 / 400
Nominal voltage Un
230 / 400
V 275
Maximum continuous operating voltage Uc
275
kA 7
Maximum impulse current Iimp (10/350)
7
kA 15
Maximum impulse current Tot. Iimp (10/350)
30
kA 70
Maximum discharge current Imax (8/20)
70
kA 7
Nominal discharge current In (8/20)
7
kA
Follow current interrupting rating Ifi

kV 0.9 / 1.4 / 1.4


Voltage protection level Up at In (L-N/N-PE/L-PE)
0.9 / 1.4 / 1.4
kV 0.8 / 0.8 / 0.8
Voltage protection level Up at 3kA (L-N/N-PE/L-PE)
0.8 / 0.8 / 0.8
TOV (Temporary overvoltage) withstand Ut
V 334 / 1200
(L-N: 5s / N-PE: 200ms)
334 / 1200
ns 25
Response time
25
A 10
Residual current IPE
10
kA 50
Short-circuit withstand capability Isccr
50
Backup protection
A 50
Fuse (gG - gL)
50
A 50
Circuit breaker (B or C curve)
50
Pluggable cartridge
Yes
Yes
Integrated thermal disconnector
Yes
Yes
State indicator
Yes
Yes
Safety reserve
Yes
Yes
Auxiliary contact
No
No
Installation
Wire range (L, N, PE)
mm 2.525
Solid wire
2.525
mm 2.516
Stranded wire
2.516
mm 12.5
Stripping length (L, N, PE)
12.5
Nm 2
Tightening torque (L, N, PE)
2
Auxiliary contact (TS)
Contact complement

Minimum load

Maximum load

mm
Connection cross-section

Miscellaneous characteristics
C -40 to +80
Stocking and operating temperature
-40 to +80
Degree of protection
IP20
IP20
Fire resistance according to UL 94
V0
V0
Dimensions
mm 85 x 35 x 64.8
height x width x depth
85 x 71.2 x 64.8
inches 3.35 x 1.38 x 2.55
3.35 x 2.80 x 2.55
with auxiliary contact (TS)
mm
height x width x depth

inches

T1+T2 / I+II
4
TNS
AC
230 / 400
275
7
30
70
7

- / - / 1.4
- / - / 0.8

T1+T2 / I+II
4
TNS
AC
230 / 400
440
15
60
100
5

- / - / 1.4
- / - / 1.2

T1+T2 / I+II
3+1
TNS / TT
AC
230 / 400
255
15
50
60
15
7
1.7 / 1.5 / 1.7
0.9 / 0.9 / 0.9

334 / 25
200
50

440 / 25
200
50

650 / 1200
100
1000
50

50
50
Yes
Yes
Yes
Yes
No

50
50
Yes
Yes
Yes
Yes
Yes

125
125
No
Yes
No
No

2.525
2.516
12.5
2

2.550
2.535
15
3.5

2.550
2.535
15
3.5

1 NO - 1 NC
12 V DC - 10 mA
250 V AC - 1 A
1.5

-40 to +80
IP20
V0

-40 to +80
IP20
V0

-40 to +80
IP20
V0

85 x 71.2 x 64.8
3.35 x 2.80 x 2.55

85 x 89 x 70.8
3.35 x 3.50 x 2.79

90 x 142.4 x 65
3.54 x 5.60 x 2.56

ABB System pro M compact | 37

1TXH000083C0202_OVR_proM.indb 37

17/09/2012 15:57:45

OVR Type 2 surge protective devices


Single pole 57 V networks
Description
Type 2 surge protective devices are designed to protect electric installations and sensitive equipment against
indirect surges with ensuring a low protection level (Up). They are characterized by their capacity to safely
discharge current with 8/20 s wave form.

Ordering details
Nb of
poles

3
OVR T2 15-75 P

Type
1
1
2
2

Max.
discharge
current
Imax
8/20
kA

Nominal
discharge
current

Voltage
Nominal Max.
Type
protection voltage cont.
level
operating
voltage
Up
Un
Uc
kV
V
V

In
kA

2 pluggable - Uc 75 V
15
5
0.3
15
5
0.3
15
5
0.3
15
5
0.3

Main dimensions

57
57
57
57

75
75
75
75

OVR T2 15-75 P
OVR T2 15-75 P TS
OVR T2 2L 15-75 P
OVR T2 2L 15-75 P TS

OVR T2 2L 15-75 P

OVR T2 15-75 P TS

OVR T2 2L 15-75 P TS

OVR T2 15-75 P
OVR T2 15-75 P TS
OVR T2 2L 15-75 P
OVR T2 2L 15-75 P TS

EAN
code

Weight
Pkg
(1 pce)

2CTB803851R2800
2CTB803851R2700
2CTB803852R1700
2CTB803852R1600

3660308

kg

518446
518453
518484
518477

0.12
0.12
0.23
0.23

mm

OVR T2 15-75 P

Type

Order code

Width
mm
17.8
17.8
35.6
35.6

inches
0.70
0.70
1.40
1.40

38 | ABB System pro M compact

1TXH000083C0202_OVR_proM.indb 38

17/09/2012 15:57:46

You might also like