Professional Documents
Culture Documents
35 kg
EnergySmartTM
Excellent MPPT Efficiency, 98%
conversion efficiency, 1000 V ,
AC power burst and an excellent
cooling concept provides high yield
and earlier return on investment.
High voltage input and reduceds
losses on the DC side. Early start up
and late stop of power production
result in maximised yield while
exact cooling minimizes energy
losses.
DC
DesignSmartTM
A large number of independently
regulated MPP trackers along with
1000 V and asymmetrical layout
options allows for endless layout
possibilities. This huge flexibility
makes installations from residential
to large scale plants possible.
DC
TrackSmartTM
Advanced Digital Tracking
algorithms with efficiency of 99.9%
creates conditions for accumulating
the most energy possible,
regardless of ambient conditions,
physical obstacles or inclination
challenges.
* ControlSmartTM
Integrated monitoring and control options through the Master
inverter and Web server allows for;
management of up to 100 inverters
from a single inverter, accumulation
of data from all inverters as well
as overview of individual inverter
parameters, from any computer.
Integrated data logging of 34
days detailed and 20 years of
accumulated data reduces the
need for additional monitoring
equipment.
* TLX Pro series only.
www.danfoss.com/solar
Description of inverter
External and internal inverter design
Insulation surveillance
DC
Switch
PV 1+
L3
PV 2+
Residual
Current
Monitor
Unit
PV 3+
L2
L1
PV 1N
PV 2-
PE
PV 3-
Communication
interface
Ethernet
MPP
Tracker
Communication
interface
RS485
S0 meter
Input
GSM Modem
(Optional)
Nomative References
Directive LVD
Directive EMC
Safety
Integrated PV load switch
TLX 6 kW
TLX 8 kW
EMC immunity
EMC emission
Utility interference
CE
Utility characteristics
S0 Energy Meter
Approvals & Certifications
Germany
Greece
Italy
Spain
Austria
Belgium
Czech Republic
France
Germany
Spain
Portugal
UK
Irradiation
sensor
interface
Temperature
sensor
input
Display/Web
server
Signalling relay
Potential free
TLX 10 kW
2006/95/EC
2004/108/EC
IEC 62109-1/IEC 62109-2
VDE 0100-712
EN 61000-6-1
EN 61000-6-2
EN 61000-6-3
EN 61000-6-4
TLX 12.5 kW
Extended Grid
faultride through
capabilities
International
inverter
TLX 15 kW
EN 61000-3-2/-3
EN 61000-3-11/-12
Yes
IEC 61727
EN 50160
EN62053-31 Annex D
For transformerless inverter
VDE 0126-1-1/A1 and VDE AR N 4105
(TLX+, TLX Pro+ only)*
Technical requirements for the connection of independent generation to the grid, Public Power Corporation (PPC)
ENEL Guida Ed. 2.1.
RD1663 (2000)
RD661 (2007)
TOR Hauptabschnitt D4, TOR Hauptabschnitt D2
Synergrid C10/11 revisie 12 mei 2009, Synergrid C10/17- revisie 8 mei 2009
Czech Energy Act (Act No. 458/2000), Article 24, Paragraph 10 part I, II, III rev09 2009
UTE NF C 15-712-1 (UNION TECHNIQUE DE LELECTRICITE, GUIDE PRATIQUE, Installations photovoltaques raccordes au rseau public
de distribution).
NF C 15-100 (Installations lectriques basse tension). Journal Officiel, Dcret no 2008-386 du 23 avril 2008 relatif aux prescriptions
techniques gnrales de conception et de fonctionnement pour le raccordement dinstallations de production aux rseaux publics
dlectricit
*Deviant from VDE 0126-1-1 section 4.7.1., the isolation resistance measurement limit is set to 200 k , in accordance with authorities
Operating Efficiency
The operating efficiency specified for VMPPmax, VDC, r and VMPPmin
TPPV/UPV
5%
10%
20%
25%
30%
50%
75%
100%
EU
420 V
88,2%
91,8%
93,6%
94,3%
94,9%
96,4%
96,6%
96,7%
95,4%
TLX 6 kW
700 V
89,6%
92,8%
94,4%
95,1%
95,8%
97,6%
97,8%
97,8%
96,5%
800 V
87,5%
91,4%
94,5%
95,3%
96,0%
97,4%
97,7%
97,9%
96,3%
420 V
88.2%
92.4%
95.0%
95.5%
95.9%
96.4%
96.4%
96.4%
95.7%
TLX 8 kW
700 V
90.9%
92.8%
96.5%
96.9%
97.2%
97.7%
97.8%
97.8%
97.0%
800 V
88.1%
92.6%
95.8%
96.5%
96.9%
97.5%
97.8%
97.9%
96.7%
420 V
87.3%
90.6%
94.4%
95.2%
95.7%
96.6%
96.9%
97.1%
95.7%
TLX 10 kW
700 V
90.4%
92.9%
96.0%
96.6%
97.0%
97.7%
97.8%
97.9%
97.0%
800 V
89.1%
92.5%
95.6%
96.3%
96.7%
97.5%
97.8%
97.9%
96.7%
420 V
89.5%
92.1%
95.2%
95.8%
96.2%
96.9%
97.0%
97.0%
96.1%
TLX 12.5 kW
700 V
800 V
92.2%
91.1%
94.1%
93.8%
96.6%
96.3%
97.1%
96.8%
97.4%
97.1%
97.9%
97.7%
97.8%
97.8%
97.8%
97.9%
97.3%
97.3%
420 V
91.1%
93.1%
95.7%
96.2%
96.5%
97.0%
96.9%
96.9%
96.4%
TLX 15 kW
700 V
93.4%
94.9%
97.0%
97.4%
97.6%
98.0%
97.8%
97.7%
97.4%
800 V
92.5%
94.6%
96.7%
97.1%
97.4%
97.8%
97.7%
97.9%
97.4%
Derating
Temperature derating
P/P
nom
Power [W]
Trip Limit
Fixed 2 V
U1
U2
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
Ambient
temperature [C]
15
30 45 60
TLX 6 kW
12 A (+2%)
TLX 8 kW
12 A (+2%)
TLX 10 kW
12 A (+2%)
TLX 12.5 kW
12 A (+2%)
TLX 15 kW
12 A (+2%)
Grid current,
per phase
9 A (+2%)
12 A (+2%)
15 A (+2%)
19A (+2%)
22 A (+2%)
6000 W
8000 W
10000 W
12500 W
15000 W
Grid power, total
(+3%)
(+3%)
(+3%)
(+3%)
(+3%)
To avoid unintentional derating due to measurement inaccuracy, the values in brackets are added
to the limits.
Nomenclature1)
Pac,r
Vac,r
Vac, min; Vac, max
Iacmax
cosphiac,r
Parameter
AC
Max./Nom. power AC
Reactive power range
Rated output voltage
AC voltage range (P-N)
Nominal current AC
Max. current AC
AC current distortion (THD%)
Power factor at 100% load
TLX Pro 8 k
6000 W
0-3.6 kVAr
8000 W
0-4.8 kVAr
3x9A
3x9A
< 4%
3 x 12 A
3 x 12 A
< 4%
6200 W
7100 Wp
8250 W
9500 Wp
260 - 800 V
345-800 V
fr
fmin, fmax
Vdc,r
Vmppmin Vmppmax
Vdcmax
Vdcstart
Vdcmin
Idcmax
TLX Pro 10 k
TLX Pro 15 k
10000 W
0-6.0 kVAr
3x 230 V
3x 230 V 20%
3 x 15 A
3 x 15 A
< 5%
> 0.99
0.8 over-excited
0.8 under-excited
10 W
<5W
50 Hz
50 5 Hz
12500 W
0-7.5 kVAr
15000 W
0-9.0 kVAr
3 x 19 A
3 x 19 A
< 5%
3 x 22 A
3 x 22 A
< 5%
10300 W
11800 Wp
700 V
430-800 V
99.9%
1000 V
250 V
250 V
12900 W
14700 Wp
15500 W
17700 Wp
358-800 V
430-800 V
2 x 12 A
2 x 12 A
3 x 12 A
3 x 12 A
20 W
97.8 %
96.5 %
97.9%
97.0%
98%
97.0%
97.3%
97.4%
3
-25..60 C
-25..45 C
-25..60 C
Change of operating point
Class III
Class II
Included
TLX+ and TLX Pro+
95% (non-condensing)
Class I
Class II
Three-phase monitoring, ROCOF
Included
Included
Included
Included
Included
Yes (class I, grounded)
Yes
DKSI.PK.22.A4.02
December 2011