The Basics of Large Dry-Type Transformers

Advertisement

Keith Lane | Electrical Construction and Maintenance


Tweet

Recommend

Jun 1, 2007
COMMENTS 0
Make an Energy Transformation

What you need to know when selecting a transformer for a critical electrical distribution system

Advertisement

Like all of the electrical distribution equipment serving critical systems,


transformers are a key component. That's why it's crucial to evaluate your
decision from every angle before choosing a unit. To help you narrow the playing field,
let's take a look at some of the most important factors to consider when specifying or
purchasing primary dry-type transformers, which typically feed a large industrial plant,
data center, or other critical facility.

Tip of the Week: Voltage Drop and the NEC


(NFPA 70)
Tip of the Week: Use NFPA 70E to Guide Your
Safety Program
Curing Customer Confusion, Part 1
Tip of the Week: Properly Allocate Your Motor
Maintenance Resources

1. Capacity The kVA rating of the transformer.


2. Voltage rating Primary and secondary voltage of the transformer.

Photo Galleries

3. Insulation system The sum of the maximum ambient temperature, plus

Announcing EC&M's
2015 Top 10 Electrical Design Firms

the
average winding temperature rise, plus the differential between the average
winding temperature rise and the highest temperature of the winding.

4. Core and coils Wound cores or stacked laminations (copper or aluminum

It's that time of year again -- when EC&M unveils the


highly anticipated 2015 Top 40 electrical design firms in
the country, ranked specifically by electrical design
revenue.

conductors).
5. Winding insulation system Open-wound, vacuum pressure impregnation,

vacuum pressure encapsulated, encapsulated, and cast coil.

Join the Discussion on EC&M Talk


Hot Topics
@

Comments

New Topics

@ 01096922100

@ 0235682820
last reply by marvill201 in Electrical Talk Pics &
Videos

0235699066 !! 01060037840

!!

!!

last reply by marvill201 in Electrical Talk Pics &


Videos

!! 01060037840
Photo
1.
This
12,470V
to
480V,
3-phase
vacuum
pressure
encapsulated
(VPE)
transformer
serving
a
large
data
center
is
dual
rated

!! 0235699066

last reply by marvill201 in Electrical Talk Pics &


Videos

++ 01060037840

+" !

++ 0235699066

last reply by marvill201 in Electrical Talk Pics &


Videos

-- 0235682820 !! 01096922100

--

last reply by marvill201 in Electrical Talk Pics &


Videos

EC&M White Papers

6/7/2015 10:56 PM

The Basics of Large Dry-Type Transformers | content content from Elec...

2 of 5

http://ecmweb.com/content/basics-large-dry-type-transformers

at
2,000kVA
and
fan
assisted
to
2,666kVA.
The
right-hand
side
of
the
enclosure
contains
the
mediumvoltage
switches,
the
middle
section
is
the
transformer,
and
the
far
left
section
contains
the
secondary
480V
breakers.

Workplace Electrical
Safety: What the New
Language Means for
You
The recent changes to
NFPA 70E and CSA Z462
have the potential if not the intent to change the way we
approach workplace electrical safety programs....

More

VIEW MORE WHITE PAPERS

EC&M Webinars
ON-DEMAND:
Understanding Your
Options: AFCI
Protection and the
2014 NEC 5
Thursday, June 12,
2014
The 2014 National Electrical Code has expanded the
options to provide Arc Fault protection for branch circuits
More

VIEW MORE WEBINARS

EC&M TV
New Certification
Announcement from
NFPA

Large dry-type distribution transformers are typically fed by medium-voltage power


systems (12.47kV, 13.3kV, or 13.8kV) and feature a secondary voltage rating of 480V,
3-phase (Photo 1). Some of the larger common sizes of dry-type transformers available
today include 500kVA, 750kVA, 1,000kVA, 1,500kVA, 2,000kVA, 2,500kVA, 3,000kVA,
3,750kVA, 5,000kVA, and 7,500kVA.

...

More

BROWSE ALL VIDEOS

Sponsored by
Advertisement

EC&M Learning Center

Understanding the 2014 NEC,


Volume 1 (Articles 90 to 480)
This resource has proven itself in the
field and in the exam room. This latest
edition will provide you with a rock-solid
foundation...

Understanding NEC Requirements


for Grounding vs Bonding
One of the most confusing areas of the
trade continues to be grounding and
bonding, which is why this book needs to
be in the hands...

Changes to The NEC 2014


Photo
2.
Two
45kVA
open
wound
dry-type
transformers
in
a
stacked
configuration.

Don't let the scale of the code changes


intimidate you, this book will get you up
to speed on the most essential...

BROWSE ALL TITLES

As noted above, there are several different construction methods used in the manufacture
of dry-type transformers, resulting in various designs that make installation in many
different environments possible. The key difference in the design of these units is in the
insulation of the windings. Dry-type transformers can have their windings insulated in a
number of different ways.

6/7/2015 10:56 PM

The Basics of Large Dry-Type Transformers | content content from Elec...

3 of 5

http://ecmweb.com/content/basics-large-dry-type-transformers

Open wound

The standard dry-type transformer follows a dip-and-bake construction method.


This is accomplished by preheating the conductor coils and then, when heated,
dipping them in varnish at an elevated temperature. The coils are then baked to
cure the varnish (Photo 2).
Vacuum pressure impregnation (VPI)

This technique applies the varnish coating in interchanging cycles of pressure and
vacuum. The VPI process uses polyester resin. The coils are then cured in an oven.
The VPI process is better than the standard dry-type transformer because it
includes pressure in addition to vacuum. This process allows better penetration of
the varnish in the transformer coil. These units offer an increased resistance to
corona.

Sign-up to receive our free newsletters


eTrain - (Bi-Weekly) View Sample
Product NewsWire - (Monthly) View
Sample
ElectricalZone - (Weekly) View Sample
MRO Insider - (Bi-Weekly) View Sample
PQ NewsBeat - (Bi-Weekly) View
Sample
Illumination Insider - (Bi-Weekly) View
Sample
CodeWatch - (Bi-Weekly) View Sample

Vacuum pressure encapsulated (VPE)

G-Biz - (Varies) View Sample

This method is usually superior to the VPI process. Several dip processes are added
to the construction process to encapsulate the coil assembly after which the
coatings are cured in the oven. These transformers feature better protection from
harsh and wet environments than their VPI type counterparts (Photo 1).

Electrical Testing - (Monthly) View


Sample

Encapsulated (sealed)

Encapsulated transformers are standard open-wound distribution transformers


encased in an electrical-grade silica and epoxy, and totally enclosed in a heavy-duty
style enclosure.

E-MAIL*
COUNTRY*

Enter your email above to receive messages about


offerings by Penton, its brands, affiliates and/or
third-party partners, consistent with Pentons Privacy
Policy.

Cast coil (molded epoxy sealing)

These units incorporate coils encapsulated in epoxy by a molding process. The


transformer coils are solidly cast in resin under a vacuum in a mold. The
manufacturing process locks the windings in a strong epoxy resin with high
dielectric strength, protecting the transformer from severe operating environments
(Figure).

Connect With Us

A
typical
cast
coil
transformer
consists
of
the
low-voltage
bus
(1),
clamp
bolts
(2),
high-voltage
bus
(3),
low-voltage
winding
(4),
core
(5),
high-voltage
winding
(6),
tap
(7),
tap
terminals
(8),
transformer
base
(9),
lifting
channels
(10),
air
channel
(11),
high-voltage
winding
conductors
(12),
and
low-voltage

6/7/2015 10:56 PM

The Basics of Large Dry-Type Transformers | content content from Elec...

http://ecmweb.com/content/basics-large-dry-type-transformers

conductors
(13).

Each of the winding insulations noted above is specifically suited for particular
environments. Therefore, it's important for you to understand where best to use each
type. For example, it costs approximately 50% more to specify a cast coil transformer over
a VPE or VPI type unit. Therefore, your final selection can have a significant impact on
the overall cost of a project.
When improved resistance to corona (i.e., electrical discharges caused by the field
intensity exceeding the dielectric strength of the insulation) and increased mechanical
strength of the windings are required, you should use a VPI-type transformer.
Use a cast coil transformer when additional coil strength and protection is needed, such
as in unforgiving environments like chemical process plants, construction material
factories, and for outdoor installations. These types of harsh environments include
substances that can devastate the windings of other dry-type transformers, including salt,
dust, caustic gases, moisture, and metal particles. Additionally, cast coil transformers
have improved abilities to withstand heavy electrical surges, such as recurring but shortduration overloads experienced by transformers serving industrial processes. Cast coil
transformers typically have the same increased levels of BIL as oil-filled transformers,
while still providing ample protection of the transformer coils. Cast coil transformers are
also being used in some harsh locations that were previously thought best served by
liquid-filled transformers.
The engineer has a choice between a VPI/VPE transformer or cast coil transformer for
critical environments and harsh environments. The cast coil is typically accepted as the
best transformer in these types of environments. Some manufacturers, however, indicate
that the cast resin in the cast coil transformers can be detrimental to the life of the
transformer. The coefficient of expansion of the epoxy is less than the copper windings.
The cyclical expansion and contraction with the heating and cooling of the coils can
eventually crack the resin. These manufacturers indicate that the epoxy encapsulation in
the VPI transformer can better deal with this expansion and contraction; therefore, if
offers longer life. In the end, the final choice is left to the design engineer.
In addition to the capacities noted earlier, the electrical design engineer can specify a
fan-assisted transformer that can add significant capacity to the rating of the transformer.
For a cast coil transformer, the addition of the fans to cool the transformer during heavy
loading can add another 50% to the rating of the transformer. For a VPE or VPI
transformer, an additional 33% kVA capacity can be added to the rating of the
transformer. For instance, a standard cast coil dry-type transformer rated for 3,000kVA
can have a second rating when fan assisted to 4,500kVA (a 50% increase in the standard
rating). On the other hand, a VPE or VPI transformer rated 2,500kVA can have a second
rating when fan assisted to 3,333kVA (a 33% increase in the standard rating).
Remember: When using the fan-assist rating of a transformer, you are relying on moving
parts to supply the rated capacity. For critical installations, you may only want to rely on
the fan-assist rating for unusual overloads that may occur under certain operations,
including:
1. The extra current required to recharge UPS batteries after the UPS system has

been

used during a power outage before the generators begin to come online.
2. Planned maintenance bypass

that placed a short-term condition of extra load on a

specific transformer.
3. Other short-term overloads of the electrical distribution system.

For critical environments where uptime is essential, a system that relies on the
fan-assisted rating for normal operation may reduce overall system reliability.
The electrical design engineer must always evaluate cost implications and system
reliability when designing electrical distribution systems. This type of evaluation becomes
even more important in critical environments. The transformer is only one component in
complex electrical distribution systems. As you can see, the design engineer must be
armed with the most accurate information in order to make the proper transformer
selection.
Lane is a registered professional engineer, licensed electrical administrator, RCDD/NTS
specialist, TPM, LC, LEED A.P. and serves as director/vice president engineering for

4 of 5

6/7/2015 10:56 PM

The Basics of Large Dry-Type Transformers | content content from Elec...

5 of 5

http://ecmweb.com/content/basics-large-dry-type-transformers

SASCO Design/Build Electrical Contractors and Consultants in Cerritos, Calif., San


Francisco, and Woodinville, Wash.

Recommend

Tweet

Please Log In or Register to post comments.

Related Articles
Mounting a Dry-Type Transformer
How to Select the Right Energy-Efficient Dry Type Transformer
Unconventional Transformer Connections Part 3
Using Single-Phase Transformers to Create 3-Phase Systems
Transformer Secondary Conductors

Ecmweb.com
NEC

Design

Ops & Maintenance

Contractor

Safety

Site Features

EC&M Corporate

Author Guidelines

Privacy Policy

RSS

Terms of Service

Sitemap

About Us

Site Archive

Advertise

Subscribe

Contact Us

View Mobile Site

Power Quality

Training

Basics

Products

Search ecmweb.com

Subscribe to the print magazine

Follow Us

Related EC&M Sites


Electrical Wholesaling Electrical Marketing Transmission & Distribution World

Advertisement

Copyright 2015 Penton

6/7/2015 10:56 PM

You might also like