DMP catalogue
1-200 kW, 5-1000 Nm
List of contents
Introduction ................................................................. p. 3
Options ....................................................................... p. 4
Application data .......................................................... p. 5
Output data ................................................................ p. 7
Dimension drawings, IC06 ......................................... p. 31
Dimension drawings, IC17/37 .................................... p. 33
Dimension drawings, IC666 ....................................... p. 34
Dimension drawings, IC86W ...................................... p. 35
Dimensions, flanges ................................................... p. 36
Order form .................................................................. p. 37
Introduction
DMP d.c. motors are fully
laminated, 2 or 4 pole, square
frame.
Output: 1-200 kW
Torque: 5-1000 Nm
DMP motor range:
Frame size
DMP
Core
lengths
112-2
MA, LA
112-4
M, L
132-2
132-4
S, M, L, LB
160-4
180-4
A, B, C, D, E, F
=
=
=
=
=
DC motor
Motor type
Centre height in mm
Number of poles
Core length
Options
Frame size
DMP
112-2
112-4
132-2
132-4
160
180
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
o
Pulse generators
POG 9 D (1-1250 ppr)
HG650 or DG60L (1024 ppr)
Others available
o
o
o
o
o
o
o
o
o
o
o
o
Cooling forms
IC06
(IP23)
Force ventilated
IC17
(IP23)
Single pipe ventilated
IC37
(IP54)
Double pipe ventilated
IC410 (IP54)
Totally enclosed
IC416 (IP54)
Totally enclosed, fan cooled
IC666 (IP54)
Air-air cooled
IC86W (IP54)
Air-water cooled
Other cooling forms available
Protection
IP55
Mounting forms
IM1001 Horizontal foot
IM1002 Horizontal foot, two shaft ends
IM2001 Horizontal foot and flange
IM2011 Vertical foot and flange
Other mounting forms available
Application data
Standards
IEC 34 - IEC 72 etc.
Insulation
Class H
Temperature rise
Class F
Balance
IEC 34-14 grade 'N' standard.
Grade 'R' on request.
Overload capacity
180% xFLC for
15 sec. every 5 minutes
30 sec. every 30 minutes
Terminal box
Standard position: On right hand
side (facing D-end).
Mounting of terminal box on top
or left hand side on request.
DMP motors are delivered with
a large terminal box IP55 including knockout openings:
DMP 112 132
2 x 28.5 (PG 21)
2 x 20.5 (PG 13.5)
Cable entry from Drive end.
DMP 160 180
2 x 55 (PG 42)
4 x 28.5 (PG 21)
Cable entry from above or
below.
Heat exchangers
Air/water (IC86W):
Air/air (IC666):
Blower position
Standard: On top of the motor at
the non-drive end.
Other positions on request.
Blower is supplied without filter
as standard.
Filter on request.
Bearings
Grease lubricated ball bearings
as standard.
For belt drive please contact our
sales offices.
Application data
Fan blower motor data
DMP
IY (A)
112
132-2M
132-4S/M/L
3x380-420 V. 50 Hz
3x440-480 V. 60 Hz
3x500 V. 50 Hz
0.70
0.70
0.60
3x220-240 V. 50 Hz
3x250-280 V. 60 Hz
-
1.20
1.20
-
0.25
0.30
0.25
132-4LB
160-4S/M/L
3x380-420 V. 50 Hz
3x440-480 V. 60 Hz
3x500 V. 50 Hz
2.10
2.00
1.40
3x220-240 V. 50 Hz
3x250-280 V. 60 Hz
-
3.60
3.50
-
0.75
0.90
0.75
16
160-4LB
3x380-420 V. 50 Hz
3x440-480 V. 60 Hz
3x500 V. 50 Hz
2.90
2.80
2.30
3x220-240 V. 50 Hz
3x250-280 V. 60 Hz
-
5.00
5.00
-
1.30
1.50
1.30
18
180-4A/B/C/D
3x380-420 V. 50 Hz
3x440-480 V. 60 Hz
3x500 V. 50 Hz
3.00
2.90
2.70
3x220-240 V. 50 Hz
3x250-280 V. 60 Hz
-
5.20
5.00
-
1.50
1.75
1.50
18
180-4E/F
3x380-420 V. 50 Hz
3x440-480 V. 60 Hz
3x500 V. 50 Hz
5.80
5.80
4.60
3x220-240 V. 50 Hz
3x250-280 V. 60 Hz
-
10.0
10.0
-
2.70
3.00
2.70
20
Unet, fnet ()
I (A)
Pfan (kW)
Wfan (kg)
Bearings
Drive end
DMP
112
132
160
180-4A/B/C/D/E
180-4F
Non-drive end
Ball bearing
Roller bearing
6308-C3
6309-C3
6310-C3
6215-C3
6315-C3
NU 308 ECP
NU 309 ECP
NU 310 ECP
NU 2215-ECP
NU 315 ECP
6208-2RS 1-HT-C3
6307-2RS 1-HT-C3
6309-2RS 1-HT-C3
6312-2RS1-HT-C3
6312-2RS1-HT-C3
Output data
Select motor frame size against
voltage, output and speed. For
intermediate output, take the
nearest higher output listed
under the next frame size. For
intermediate speed take the
next lower speed listed within
the output required. The output
lists are based on:
Cooling forms
IC06/IC17/IC37/IC86W.
Duty cycles
Ratings: All outputs are duty
type S 1 and motors are fed
from a 3-phase fully controlled
thyristor where the form factor
is 1.05.
Field windings
All motors in the output lists
have separate excitation, the
field being shunt wound.
Compound winding can be
supplied on request.
Motors with compound winding
may have nominal data which
differ from those shown in the
output lists.
Armature voltage
For other armature voltages,
please contact our sales offices.
Stock motors
Motors indicated with the sign
in the output data lists are
available from stock and can be
delivered promptly.
The stock motors are available
according to following specification. Motor fan, standard tachogenerator and coupling can be
fitted on request.
IM 1001, IP 23, IC 17, designed for cooling air inlet at
either D or N-end (when
possible, cooling air inlet
should always be at the Dend of DMP motors).
Cylindrical roller bearing on
D-end.
Terminal box on right hand
side (facing D-end).
Balanced with half key.
Thermostats NC.
PTC thermistors.
Name plate and documents
in English.
Rating data as standard
motors but field weakening
is only allowed up to 25 %
overspeed for stock
motors.
Stock motors have a parallel /serial connection suitable for an excitation voltage of 170-180-190/340-360380 V.
Stock motors have reinforced impregnation.
Output data
Technical data
nmax
nmax
n0
J
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
n0
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
420
440
470
nb (min-1)
520
550
P
I
T
(kW) (A) (Nm)
h
(%)
Base speed
Armature voltage
Mechanical power
Armature current
Torque
Efficiency IEC
Max electrical speed
Armature resistance
Armature inductance
n2
min-1
RA (115C)
()
LA (0Hz)
(mH)
112-2MA
30 Nm
Technical data
nmax
n0
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
5000 min-1
40 min-1
0.03 kgm2
420 W
620 V
110-440 V
235 m3/h
375 Pa
90 kg
102 kg
Cat. Nr Ua (V):260
FR 154...
241-AB
400
420
440
-1
nb (min )
470
520
1000
1075
1145
1255
1440
241-BB
645
1235
1315
1400
1525
1745
241-CB
860
1570
1670
1770
1920
2180
251-CB
1010
1795
1905
2015
2185
2475
241-DB
1185
2070
2195
2320
2510
2832
241-EB*
1445
2450
2595
2740
2955
3325
231-EB
1740
2920
3085
3255
231-FB
2175
3590
3790
3995
231-GB1
2820
4590
h
P
(kW)
I
(A)
T
(Nm)
(%)
3.2
3.5
3.7
4.1
4.6
2.0
3.8
4.0
4.3
4.7
5.3
2.8
5.1
5.4
5.7
6.2
6.9
3.2
5.7
6.0
6.4
6.9
7.7
3.8
6.6
7.0
7.4
8.0
8.9
4.5
7.7
8.2
8.6
9.3
10.3
5.8
9.6
10.2
10.7
7.0
11.5
12.2
12.8
8.7
14.2
12.2
12.2
12.2
12.2
12.0
13.5
13.5
13.5
13.5
13.5
13.3
17.0
17.0
17.0
17.0
17.0
16.7
18.5
18.5
18.5
18.5
18.5
18.2
21.0
21.0
21.0
21.0
21.0
20.7
23.7
23.7
23.7
23.7
23.7
23.3
29.0
29.0
29.0
29.0
34.0
34.0
34.0
34.0
41.0
41.0
31.0
31.0
31.0
31.0
30.4
29.1
29.3
29.3
29.3
29.3
28.8
30.8
30.8
30.8
30.8
30.8
30.3
30.2
30.2
30.2
30.2
30.2
29.7
30.4
30.4
30.4
30.4
30.4
29.9
30.0
30.0
30.0
30.0
30.0
29.5
31.6
31.5
31.5
31.5
30.8
30.7
30.7
30.7
29.6
29.6
61.1
62.8
64.1
66.0
68.9
50.3
65.0
66.2
67.5
69.2
71.8
57.4
70.0
71.2
72.2
73.6
75.8
61.1
61.1
73.5
74.5
75.7
77.7
64.4
74.8
75.7
76.5
77.7
79.4
69.1
77.9
78.7
79.4
80.4
81.8
72.3
80.1
80.8
81.4
75.7
82.3
82.9
83.4
79.0
84.3
n2
RA (115C)
-1
min
()
1605
9.84
120
1960
7.78
88
2480
5.14
61
3060
4.21
49
3250
3.33
39
3835
2.42
30
3595
1.75
30
3835
1.25
15
5000
0.85
10
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
LA (0Hz)
(mH)
112-2LA
43 Nm
Technical data
nmax
n0
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
5000 min-1
40 min-1
0.04 kgm2
500 W
620 V
110-440 V
235 m3/h
375 Pa
96 kg
108 kg
Cat. Nr Ua (V):260
FR 154...
400
141-AB
655
420
440
-1
nb (min )
470
520
I
(A)
T
(Nm)
(%)
3.0
3.3
3.5
3.9
4.4
3.5
3.7
4.0
4.4
5.0
3.5
3.8
4.0
4.5
5.1
4.8
5.1
5.4
5.9
6.7
2.9
5.4
5.8
6.1
6.7
7.5
3.5
6.3
6.7
7.1
7.8
8.7
4.3
7.6
8.0
8.5
9.2
10.2
5.5
9.4
10.0
10.5
11.4
12.6
6.2
10.6
11.2
11.8
12.7
14.1
6.8
11.4
12.0
12.7
13.7
15.1
7.8
12.9
13.6
14.4
15.5
12.2
12.2
12.2
12.2
12.0
13.5
13.5
13.5
13.5
13.3
13.7
13.7
13.7
13.7
13.5
17.0
17.0
17.0
17.0
16.7
18.5
18.5
18.5
18.5
18.5
18.2
21.0
21.0
21.0
21.0
21.0
20.7
24.0
24.0
24.0
24.0
24.0
23.6
29.2
29.0
29.0
29.0
29.0
28.5
32.0
32.0
32.0
32.0
32.0
31.5
34.0
34.0
34.0
34.0
34.0
33.4
38.0
38.0
38.0
38.0
38.0
44.3
44.3
44.3
44.3
43.6
45.6
45.6
45.6
45.7
44.8
42.6
42.6
42.6
42.7
41.9
44.0
44.0
44.0
44.1
43.3
42.9
43.1
43.1
43.2
43.1
42.5
43.4
43.5
43.5
43.5
43.6
42.7
43.5
43.5
43.5
43.5
43.5
42.8
45.1
45.2
45.2
45.2
45.1
44.4
45.7
45.7
45.7
45.7
45.7
44.9
44.0
44.0
44.0
44.0
44.1
43.3
44.3
44.3
44.3
44.3
44.3
56.3
58.1
59.7
61.8
65.3
58.6
60.2
61.8
63.8
67.1
59.0
60.7
62.2
64.3
67.4
65.5
66.8
68.1
69.8
72.5
54.8
68.5
69.7
70.8
72.4
74.8
58.7
71.2
72.3
73.4
74.8
77.0
64.2
75.0
76.0
76.9
78.1
79.9
68.5
77.9
78.7
79.5
80.6
82.2
70.7
79.4
80.2
80.0
81.9
83.3
72.6
80.7
81.4
82.0
82.9
84.2
75.0
82.3
82.9
83.5
84.3
705
755
830
964
151-AB
725
780
835
915
1058
141-BB
790
850
910
1000
1153
141-CB
1040
1110
1180
1285
1472
141-DB
645
1200
1275
1355
1470
1674
141-EB
770
1390
1480
1570
1705
1933
141-FB
950
1660
1765
1865
2020
2278
141-GB*
1165
1995
2110
2230
2410
2710
131-CB*
1305
2210
2340
2470
2665
2993
141-HB
1470
2465
2610
2750
2965
3326
141-KB*
h
P
(kW)
1675
2785
2940
3100
3335
n2
RA (115C)
-1
min 115C ()
1055
11.51
164
1280
9.85
141
1275
9.52
121
1650
6.29
83
1895
5.16
67
2200
4.07
54
2610
2.97
41
3120
2.13
30
3120
1.76
25
3850
1.52
21
4340
1.22
17
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
10
LA (0Hz)
(mH)
112-4M
47 Nm
Technical data
nmax
n0
5000 min-1
40 min-1
Cat. Nr Ua (V):260
FR 153...
201-NA
Pf
0.037 kgm2
400
625 W
420
440
-1
nb (min )
Uamax
550 V
470
520
Uf
Vcool
Pr
W(foot)
W(flange)
110-440 V
270 m3/h
480 Pa
103 kg
115 kg
I
(A)
T
(Nm)
(%)
n2
RA (115C)
-1
min 115C ()
6.7
7.1
7.5
8.1
8.3
7.1
7.5
8.6
8.6
8.8
4.6
7.8
8.3
8.8
9.4
9.5
4.9
8.2
8.7
9.2
9.9
10.2
5.5
9.2
9.7
10.3
11.1
12.0
6.1
10.1
10.6
11.2
12.0
12.9
6.8
11.2
11.8
12.4
13.4
14.2
8.2
13.5
14.2
14.9
15.5
9.4
15.3
16.1
17.0
17.8
11.2
18.0
19.0
20.0
13.4
21.4
15.9
21.0
21.0
21.0
21.0
19.2
22.0
22.0
22.0
22.0
20.1
24.0
24.0
24.0
24.0
24.0
21.4
25.0
25.0
25.0
25.0
25.0
22.9
27.5
27.5
27.5
27.5
27.5
26.6
30.0
30.0
30.0
30.0
30.0
28.8
33.0
33.0
33.0
33.0
33.0
31.4
39.0
39.0
39.0
39.0
37.7
44.0
44.0
44.0
44.0
43.0
51.0
51.0
51.0
51.0
60.0
60.0
70.0
47.9
47.9
47.9
47.9
43.8
47.1
47.1
47.0
47.0
43.1
48.0
47.9
47.9
47.9
47.9
42.8
46.3
46.3
46.3
46.3
46.3
42.4
47.0
47.0
47.0
47.0
47.0
45.5
46.7
46.6
46.6
46.6
46.6
44.8
46.7
46.6
46.6
46.6
46.6
44.3
50.0
49.9
49.9
49.9
48.2
49.9
49.8
49.8
49.8
48.7
51.0
50.8
50.8
50.8
51.3
51.1
49.8
75.1
76.0
76.9
78.0
80.1
76.8
77.7
78.5
79.5
81.3
68.9
77.9
78.7
79.5
80.4
81.9
70.2
78.8
79.5
80.2
81.2
82.5
72.5
80.3
81.0
81.7
82.5
83.7
73.8
81.2
81.9
82.5
83.3
84.4
75.7
82.5
83.1
83.6
84.4
85.4
77.9
84.0
84.6
85.0
85.7
79.7
85.2
85.7
86.1
86.7
81.8
86.6
87.0
87.3
83.5
87.7
85.4
1655
1655
1655
1655
1810
1795
1795
1795
1795
1960
1890
1890
1890
1890
1890
2115
2105
2105
2105
2105
2105
2295
2435
2435
2435
2435
2435
2515
2655
2655
2655
2655
2655
2760
2920
2920
2920
2920
2920
3065
2975
2975
2975
2975
3080
3425
3425
3425
3425
3500
3855
3855
3855
3855
4460
4460
5000
1325
1405
1485
1605
1810
201-MA
1445
1530
1615
1745
1960
201-LA
920
1565
1655
1745
1890
2115
201-KA
1010
1700
1800
1900
2050
2295
201-JA
1120
1870
1980
2085
2245
2515
201-IA
1240
2060
2175
2295
2470
2760
201-HA
1390
2295
2420
2550
2745
3065
201-GA
1575
2575
2720
2860
3080
201-FA
1800
2930
3090
3250
3500
201-EA
2100
3390
3575
3760
201-DA
2495
4000
201-CA
h
P
(kW)
3055
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
11
LA (0Hz)
(mH)
3.258
40.75
2.776
35.80
2.416
31.20
2.174
26.90
1.783
22.90
1.549
19.25
1.275
15.90
0.973
12.90
0.772
10.20
0.573
7.80
0.425
5.75
0.298
4.00
112-4L
68 Nm
Technical data
nmax
n0
5000 min-1
40 min-1
Cat. Nr Ua (V):260
FR 153...
101-KA
J
0.05 kgm2
400
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
740 W
550 V
110-440 V
270 m3/h
480 Pa
110 kg
122 kg
420
440
-1
nb (min )
470
520
I
(A)
T
(Nm)
(%)
n2
RA (115C)
-1
min 115C ()
7.9
8.4
8.9
9.6
8.9
9.4
9.9
10.7
12.0
9.8
10.4
10.9
11.8
13.2
10.9
11.6
12.2
13.1
14.7
7.9
13.1
13.9
14.6
15.7
9.1
15.0
15.8
16.7
17.9
10.9
17.7
18.6
19.6
13.0
21.0
22.1
23.3
15.5
24.8
26.1
27.5
18.6
29.3
30.9
32.4
23.0
25.0
25.0
25.0
25.0
27.5
27.5
27.5
27.5
27.5
30.0
30.0
30.0
30.0
30.0
33.0
33.0
33.0
33.0
33.0
39.0
39.0
39.0
39.0
39.0
44.0
44.0
44.0
44.0
44.0
51.0
51.0
51.0
51.0
60.0
60.0
60.0
60.0
70.0
70.0
70.0
70.0
82.0
82.0
82.0
82.0
100.0
65.2
65.2
65.2
65.2
66.2
66.2
66.2
66.2
66.2
66.2
66.2
66.1
66.1
66.1
66.2
66.2
66.1
66.1
66.1
70.6
70.5
70.5
70.5
70.4
70.8
70.6
70.6
70.6
70.6
71.8
71.6
71.6
71.6
72.2
72.0
72.0
72.0
70.2
69.9
69.9
69.8
65.5
65.2
65.1
65.1
59.5
75.0
76.0
76.8
77.9
76.9
77.8
78.5
79.6
81.0
77.9
78.7
79.5
80.4
81.8
79.5
80.2
80.9
81.7
83.0
74.0
81.3
82.0
82.6
83.3
76.2
82.8
83.3
83.9
84.6
78.7
84.4
84.9
85.3
80.7
85.7
86.2
87.0
83.0
87.1
87.5
87.8
84.9
88.1
88.4
88.6
86.7
1545
1545
1545
1545
1790
1790
1790
1790
1790
1950
1950
1950
1950
1950
2145
2145
2145
2145
2145
2240
2240
2240
2240
2240
2515
2515
2515
2515
2515
2835
2835
2835
2835
3280
3280
3280
3280
4050
4050
4050
4050
5000
5000
5000
5000
5000
1160
1230
1300
1405
101-JA
1280
1355
1435
1545
1735
101-IA*
1410
1495
1575
1700
1910
101-HA
1575
1670
1760
1895
2125
101-GA
1070
1790
1880
1980
2135
101-FA*
1230
2030
2145
2255
2425
101-EA*
1445
2355
2485
2615
101-DA*
1720
2785
2935
3085
101-CA
2115
3390
3575
3755
101-BA
2705
4300
4525
4755
101-AA
h
P
(kW)
3690
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
12
LA (0Hz)
(mH)
2.679
32.75
2.196
27.90
1.908
23.45
1.569
19.40
1.195
15.70
0.947
12.40
0.708
9.50
0.526
7.00
0.368
4.85
0.251
3.10
0.149
1.75
132-2M
65 Nm
Technical data
nmax
n0
5000 min-1
40 min-1
J
0.09 kgm2
Cat. Nr Ua (V):260
FR 154...
400
241-AB
605
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
550 W
620 V
110-440 V
435 m3/h
400 Pa
132 kg
147 kg
420
440
-1
nb (min )
470
520
I
(A)
T
(Nm)
(%)
n2
RA (115C)
-1
min 115C ()
4.0
4.3
4.6
5.1
5.8
5.6
6.0
6.4
7.0
7.9
6.6
7.1
7.5
8.2
9.2
8.3
8.8
9.3
10.1
11.3
5.3
9.4
10.0
10.6
11.5
12.8
5.6
10.0
10.6
11.2
12.2
13.5
6.6
11.5
12.2
12.9
13.9
15.4
7.7
13.1
13.9
14.6
15.8
17.5
9.1
15.4
16.3
17.1
18.5
20.4
10.6
17.6
18.7
19.7
21.2
12.7
20.8
22.0
23.2
15.6
25.3
16.4
16.4
16.4
16.4
16.1
20.5
20.5
20.5
20.5
20.2
23.3
23.3
23.3
23.3
22.9
27.5
27.5
27.5
27.5
27.0
30.5
30.5
30.5
30.5
30.5
30.0
32.0
32.0
32.0
32.0
32.0
31.5
36.0
36.0
36.0
36.0
36.0
35.4
40.0
40.0
40.0
40.0
40.0
39.3
46.0
46.0
46.0
46.0
46.0
45.2
52.0
52.0
52.0
52.0
52.0
60.0
60.0
60.0
60.0
72.0
72.0
63.1
63.1
63.1
63.4
62.1
64.3
64.3
64.3
64.3
63.3
64.6
64.6
64.6
64.6
63.5
66.1
66.1
66.1
66.1
65.0
67.6
67.7
67.7
67.7
67.7
66.5
64.9
65.0
65.0
65.0
65.1
63.9
66.5
66.4
66.4
66.4
66.4
65.3
66.5
66.5
66.5
66.5
66.5
65.3
68.0
68.1
68.1
68.1
68.1
66.9
67.3
67.3
67.3
67.3
67.4
66.9
66.6
66.6
66.6
66.5
66.5
56.1
57.9
59.5
61.7
65.2
63.7
65.1
66.5
68.3
71.2
67.0
68.3
69.5
71.2
73.8
71.7
72.8
73.9
75.3
77.5
62.2
73.8
74.9
75.8
77.1
79.0
63.6
74.8
75.8
76.7
77.9
79.9
66.5
76.7
77.7
78.5
79.6
81.4
70.1
79.1
79.9
80.7
81.7
83.2
73.0
81.1
81.8
82.5
83.3
84.7
75.4
82.7
83.3
83.9
84.7
78.7
84.9
85.4
85.9
81.0
86.3
1460
1480
1480
1480
1480
1725
1725
1725
1725
1725
1950
1950
1950
1950
1950
2200
2200
2200
2200
2200
1860
1860
1860
1860
1860
1860
2650
2650
2650
2650
2650
2650
2840
2840
2840
2840
2840
2840
3160
3160
3160
3160
3160
3160
3480
3480
3480
3480
3480
3480
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
650
700
770
898
241-BB
830
885
945
1035
1186
241-CB
980
1045
1110
1210
1383
241-DB
1200
1275
1350
1465
1664
231-AB
745
1330
1415
1495
1620
1835
251-EB
830
1465
1555
1650
1785
2019
241-EB
945
1650
1750
1850
2000
2257
251-FB
1100
1880
1990
2105
2270
2554
241-FB
1280
2155
2280
2405
2595
2911
241-GB
1505
2500
2645
2790
3000
231-DB
1820
2990
3155
3320
231-EB
h
P
(kW)
2240
3640
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
13
LA (0Hz)
(mH)
8.93
132
5.73
87
4.50
68
3.18
51
2.60
43
2.37
36
1.93
30
1.51
24
1.16
19
0.92
15
0.65
11
0.47
132-4S
100 Nm
Technical data
nmax
n0
4000 min-1
40 min-1
J
0.10 kgm2
Cat. Nr Ua (V):260
FR 156...
400
341-AB
690
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
750 W
620 V
110-440 V
470 m3/h
550 Pa
115 kg
130 kg
420
440
-1
nb (min )
470
520
I
(A)
T
(Nm)
(%)
n2
RA (115C)
-1
min 115C ()
7.7
8.2
8.8
9.6
10.8
9.1
9.7
10.3
11.2
12.5
5.9
10.7
11.4
12.1
13.1
14.6
7.9
13.8
14.6
15.4
16.7
18.5
9.4
16.0
17.0
18.0
19.4
21.5
10.2
17.1
18.1
19.1
20.6
22.7
12.7
21.2
22.4
23.6
25.4
27.9
14.5
23.9
25.2
26.6
28.6
31.4
16.2
26.2
27.6
29.1
31.2
34.2
22.6
36.1
38.0
39.9
27.5
27.5
27.5
27.5
27.0
31.0
31.0
31.0
31.0
30.5
35.0
35.0
35.0
35.0
35.0
34.4
43.0
43.0
43.0
43.0
43.0
42.3
49.0
49.0
49.0
49.0
49.0
48.2
51.0
51.0
51.0
51.0
51.0
50.2
62.0
62.0
62.0
62.0
62.0
61.0
69.0
69.0
69.0
69.0
69.0
67.9
74.0
74.0
74.0
74.0
74.0
72.8
100.0
100.0
100.0
100.0
107.0
107.0
107.0
107.0
105.0
106.0
106.0
106.0
105.0
104.0
102.0
102.0
102.0
102.0
102.0
100.0
105.0
105.0
105.0
105.0
105.0
103.0
107.0
107.0
107.0
107.0
107.0
105.0
99.0
99.1
99.1
99.1
99.0
97.4
106.0
105.0
105.0
105.0
105.0
104.0
100.0
101.0
101.0
100.0
100.0
98.7
89.7
89.6
89.6
89.4
89.4
87.9
97.0
96.8
96.8
96.7
65.6
67.0
68.3
70.0
72.8
69.0
70.3
71.4
73.0
75.5
60.1
72.5
73.6
74.7
76.0
78.2
66.2
76.7
77.6
78.5
79.6
81.4
69.5
78.9
79.7
80.5
81.5
83.1
72.6
80.9
81.7
82.3
83.2
84.6
75.4
82.8
83.5
84.1
84.9
86.1
77.6
84.3
84.8
85.4
86.1
87.2
81.1
86.4
86.9
87.3
87.8
88.7
84.3
88.5
88.9
89.3
1250
1250
1250
1250
1250
1410
1410
1410
1410
1410
1750
1750
1750
1750
1750
1750
2000
2000
2000
2000
2000
2000
2160
2160
2160
2160
2160
2160
2630
2630
2630
2630
2630
2630
2920
2920
2920
2920
2920
2920
3750
3750
3750
3750
3750
3750
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
737
785
855
980
341-BB
820
875
930
1015
1155
341-CB
555
1000
1065
1130
1225
1390
341-DB
720
1260
1335
1410
1525
1720
341-EB*
835
1430
1515
1600
1730
1945
341-FB
980
1650
1745
1840
1985
2230
341-GB*
1150
1915
2025
2135
2300
2580
341-HB
1380
2270
2395
2525
2720
3040
341-KB
1725
2795
2945
3100
3335
3715
331-GB
h
P
(kW)
2220
3560
3750
3945
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
14
LA (0Hz)
(mH)
4.01
60.30
3.16
46.20
2.41
33.90
1.61
23.60
1.26
19.40
1.04
15.30
0.77
11.80
0.61
8.70
0.45
5.03
0.26
3.20
132-4M
135 Nm
Technical data
nmax
n0
4000 min-1
40 min-1
J
0.12 kgm2
Cat. Nr Ua (V):260
FR 156...
400
241-AB
730
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
830 W
620 V
110-440 V
470 m3/h
550 Pa
145 kg
160 kg
420
440
-1
nb (min )
470
520
780
830
900
1030
241-BB
515
930
985
1045
1130
1285
241-CB
605
1060
1125
1190
1285
1455
241-DB
715
1230
1300
1375
1480
1670
241-EB
845
1430
1510
1595
1720
1935
241-FB*
1015
1700
1795
1895
2040
2290
241-GB
1285
2100
2220
2335
2515
2805
241-HB*
1665
2690
2835
2980
3200
3570
231-HB
2280
3645
h
P
(kW)
I
(A)
T
(Nm)
(%)
n2
RA (115C)
-1
min
()
10.2
10.9
11.6
12.6
14.1
7.4
13.3
14.1
15.0
16.2
18.0
8.9
15.6
16.5
17.5
18.9
21.0
9.7
16.7
17.7
18.6
20.1
22.3
12.2
20.7
21.9
23.1
24.9
27.5
14.0
23.4
24.8
26.1
28.1
31.0
15.8
25.8
27.3
28.7
30.8
33.9
22.1
35.7
37.6
39.6
42.5
46.5
27.7
44.1
35.0
35.0
35.0
35.0
34.4
43.0
43.0
43.0
43.0
43.0
42.3
49.0
49.0
49.0
49.0
49.0
48.2
51.0
51.0
51.0
51.0
51.0
50.2
62.0
62.0
62.0
62.0
62.0
61.0
69.0
69.0
69.0
69.0
69.0
67.9
74.0
74.0
74.0
74.0
74.0
72.8
100.0
100.0
100.0
100.0
100.0
98.3
122.0
122.0
133.0
133.0
133.0
133.0
131.0
137.0
137.0
137.0
137.0
137.0
134.0
140.0
140.0
140.0
140.0
140.0
138.0
130.0
130.0
130.0
130.0
130.0
127.0
138.0
138.0
138.0
138.0
138.0
136.0
132.0
132.0
132.0
132.0
132.0
129.0
118.0
118.0
117.0
117.0
117.0
115.0
127.0
127.0
127.0
127.0
127.0
125.0
116.0
116.0
68.8
70.1
71.3
72.8
75.4
61.6
73.6
74.7
75.7
77.0
79.1
65.6
76.2
77.2
78.1
79.2
81.1
69.0
78.5
79.3
80.1
81.1
82.8
72.2
80.7
81.5
82.2
83.1
84.5
74.8
82.4
83.1
83.7
84.5
85.8
78.8
84.9
85.5
86.0
86.6
87.6
82.5
87.4
87.8
88.2
88.7
89.5
85.1
88.9
1200
1200
1200
1200
1200
1410
1410
1410
1410
1410
1410
1520
1520
1520
1520
1520
1520
1860
1860
1860
1860
1860
1860
2050
2050
2050
2050
2050
2050
2500
2500
2500
2500
2500
2500
3350
3350
3350
3350
3350
3350
3900
3900
3900
3900
3900
3900
4000
4000
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
15
LA (0Hz)
(mH)
2.81
42.0
1.88
29.2
1.46
23.6
1.22
18.7
0.89
14.2
0.71
10.5
0.52
7.3
0.03
4.6
0.19
2.6
132-4L
150 Nm
Technical data
nmax
n0
4000 min-1
40 min-1
J
0.14 kgm2
Cat. Nr Ua (V):260
FR 156...
400
141-AB
765
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
1000 W
620 V
110-440 V
470 m3/h
550 Pa
170 kg
185 kg
420
440
-1
nb (min )
470
P
I
T
h
(kW) (A) (Nm) (%)
520
11.8
12.6
13.3
14.4
16.1
7.7
13.6
14.4
15.3
16.5
18.4
9.0
15.5
16.5
17.4
18.8
20.8
10.7
18.2
19.3
20.3
21.9
24.2
13.0
21.9
23.1
24.4
26.3
29.0
16.2
26.7
28.2
29.7
31.9
35.1
21.6
34.9
36.8
38.7
41.5
45.5
25.7
41.0
43.2
45.4
48.6
53.2
810
860
930
1060
141-BB
495
875
925
980
1060
1200
141-CB
580
1000
1065
1125
1215
1370
141-DB
690
1170
1240
1310
1415
1590
141-EB*
825
1390
1470
1550
1675
1875
141-FB*
1045
1720
1820
1915
2060
2305
141-GB*
1365
2215
2335
2455
2635
2940
141-HB
1880
3010
3170
3330
3570
3980
38.5
38.5
38.5
38.5
37.9
43.0
43.0
43.0
43.0
43.0
42.3
48.0
48.0
48.0
48.0
48.0
47.2
55.0
55.0
55.0
55.0
55.0
54.1
65.0
65.0
65.0
65.0
65.0
63.9
77.0
77.0
77.0
77.0
77.0
75.7
98.0
98.0
98.0
98.0
98.0
96.4
114.0
114.0
114.0
114.0
114.0
112.0
148.0
148.0
148.0
148.0
145.0
149.0
149.0
149.0
149.0
149.0
146.0
148.0
148.0
148.0
148.0
148.0
145.0
148.0
148.0
148.0
148.0
148.0
146.0
150.0
150.0
150.0
150.0
150.0
148.0
148.0
148.0
148.0
148.0
148.0
145.0
151.0
151.0
151.0
151.0
151.0
148.0
131.0
130.0
130.0
130.0
130.0
128.0
72.0
73.1
74.2
75.5
77.7
63.5
74.7
75.7
76.7
77.9
79.8
66.8
76.9
77.9
78.7
79.8
81.6
70.0
79.1
79.9
80.7
81.7
83.2
72.7
81.0
81.7
82.4
83.3
84.7
77.3
84.0
84.6
85.1
85.8
86.9
81.5
86.8
87.3
87.7
88.2
89.1
84.3
88.4
88.7
89.1
89.4
90.1
n2
RA (115C)
-1
min
()
1460
1460
1460
1460
1460
1610
1610
1610
1610
1610
1610
1830
1830
1830
1830
1830
1830
2080
2080
2080
2080
2080
2080
2470
2470
2470
2470
2470
2470
3000
3000
3000
3000
3000
3000
3780
3780
3780
3780
3780
3780
4000
4000
4000
4000
4000
4000
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
16
LA (0Hz)
(mH)
2.14
35.00
1.69
29.00
1.35
23.00
1.05
17.00
0.08
13.00
0.53
90.00
0.32
60.00
0.21
3.00
132-4LB
240 Nm
Technical data
nmax
n0
5000 min-1
40 min-1
J
0.20 kgm2
Cat. Nr Ua (V):260
FR 156...
400
401-AB
465
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
1350 W
550 V
110-440 V
510 m3/h
810 Pa
220 kg
235 kg
420
440
-1
nb (min )
470
520
I
(A)
T
(Nm)
(%)
11.7
12.6
13.4
14.7
16.6
13.5
14.5
15.4
16.8
18.8
15.3
16.3
17.3
18.8
21.0
10.3
18.5
19.7
20.9
22.6
25.2
12.5
22.0
23.3
24.7
26.7
29.6
16.5
28.2
29.8
31.5
34.0
37.5
20.9
34.4
36.4
38.3
41.2
45.2
26.8
43.5
45.9
48.3
51.9
56.9
43.0
43.0
43.0
43.0
42.2
47.0
47.0
47.0
47.0
46.2
51.0
51.0
51.0
51.0
50.1
60.0
60.0
60.0
60.0
60.0
59.0
69.0
69.0
69.0
69.0
69.0
67.8
85.0
85.0
85.0
85.0
85.0
83.5
99.0
99.0
99.0
99.0
99.0
97.3
123.0
123.0
123.0
123.0
123.0
121.0
242
242
242
242
237
238
238
238
238
234
229
229
229
229
225
236
236
236
236
236
232
233
233
233
233
233
229
239
239
239
239
239
235
223
223
223
223
223
219
207
207
207
207
207
203
65.2
66.7
68.0
69.8
72.6
68.9
70.2
71.4
73.0
75.6
71.8
73.0
74.0
75.5
77.7
62.7
74.4
75.5
76.5
77.8
79.9
66.8
77.2
78.1
79.0
80.1
81.9
72.0
80.8
81.5
82.5
83.2
84.6
78.3
84.9
85.5
86.0
86.8
87.8
81.3
86.8
87.3
87.8
88.4
89.2
500
530
580
665
401-BB
545
580
620
675
770
401-CB
635
680
720
780
890
401-DB
415
750
795
845
915
1040
401-EB
515
900
955
1010
1095
1240
401-FB
660
1125
1190
1260
1360
1525
401-GB
895
1475
1560
1645
1770
1975
401-HB
h
P
(kW)
1235
2010
2120
2230
2395
2670
n2
RA (115C)
-1
min
()
920
2.74
44.5
1040
2.17
36.1
1210
1.78
28.5
1345
1.36
21.8
1645
1.03
16.0
1920
0.69
11.1
2575
0.42
7.1
3000
0.28
4.0
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
17
LA (0Hz)
(mH)
160-4S
185 Nm
Technical data
nmax
n0
3500 min-1
40 min-1
Cat. Nr Ua (V):400
FR 157...
301-RC
J
0.22 kgm2
420
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
1050 W
550 V
110-440 V
880 m3/h
980 Pa
190 kg
215 kg
440
470
-1
nb (min )
520
550
I
(A)
T
(Nm)
(%)
12.4
13.3
14.0
15.3
17.0
18.0
14.0
14.8
15.7
17.0
19.0
20.2
15.9
16.9
17.9
19.4
21.5
22.9
18.2
19.3
20.4
22.0
24.4
25.6
20.9
22.2
23.4
25.3
27.9
29.3
24.3
25.7
27.1
29.3
32.3
34.0
29.5
31.1
32.8
35.3
38.8
41.0
36.1
37.9
40.1
42.9
47.3
49.6
45.8
48.3
50.8
54.5
59.7
62.9
51.6
54.4
57.2
61.3
67.1
61.0
64.2
41
41
41
41
40
40
45
45
45
45
44
44
50
50
50
50
49
49
56
56
56
56
55
54
63
63
63
63
62
61
72
72
72
72
71
70
85
85
85
85
84
83
102
102
102
102
100
99
127
127
127
127
125
124
142
142
142
142
140
166
166
182
182
182
182
179
178
182
182
182
182
179
178
185
185
185
185
182
181
186
186
186
186
183
180
186
186
186
186
183
181
187
187
187
187
183
181
189
189
189
189
186
184
189
189
189
189
185
183
188
188
188
188
185
183
188
188
188
188
184
184
184
71.2
72.5
73.5
75.0
77.3
78.4
73.5
74.5
75.5
76.8
78.9
80.0
75.7
76.7
77.6
78.8
80.7
81.7
77.6
78.5
79.3
80.5
82.2
83.1
79.8
80.6
81.4
82.4
83.9
84.7
81.5
82.3
82.9
83.9
85.3
86.0
84.1
84.7
85.3
86.0
87.2
87.8
86.2
86.7
87.2
87.9
88.9
89.4
88.4
88.8
89.2
89.7
90.5
90.9
89.8
90.2
90.6
91.0
91.7
90.4
90.7
650
695
735
800
905
975
301-PC
735
775
825
890
1010
1080
301-NC
825
875
925
1000
1130
1205
301-MC
935
990
1045
1130
1275
1360
301-LC
1075
1135
1200
1295
1455
1550
301-KC
1245
1320
1390
1500
1680
1795
301-HC
1490
1575
1660
1785
2000
2125
301-GC*
1830
1930
2030
2180
2440
2590
301-FC
2330
2455
2580
2770
3090
3280
301-EB
2630
2770
2910
3120
3480
301-EC
h
P
(kW)
3165
3335
n2
RA (115C)
-1
min
()
980
980
980
980
980
980
1050
1050
1050
1050
1080
1080
1205
1205
1205
1205
1205
1205
1400
1400
1400
1400
1400
1400
1575
1575
1575
1575
1575
1575
1850
1850
1850
1850
1850
1850
2125
2125
2125
2125
2125
2125
2470
2470
2470
2470
2590
2590
3325
3325
3325
3325
3325
3325
3500
3500
3500
3500
3500
3500
3500
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
18
LA (0Hz)
(mH)
2.14
33.6
1.75
28.2
1.44
23.3
1.17
18.9
0.92
14.9
0.72
11.5
0.50
8.4
0.35
5.9
0.22
3.8
0.18
3.0
0.13
2.1
160-4SO
210 Nm
Technical data
nmax
n0
3500 min-1
40 min-1
Cat. Nr Ua (V):400
FR 156...
601-RC
J
0.24 kgm2
420
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
1050 W
550 V
110-440 V
880 m3/h
980 Pa
200 kg
225 kg
440
470
-1
nb (min )
520
550
I
(A)
T
(Nm)
(%)
14.8
15.7
16.7
18.0
20.1
21.2
16.4
17.4
18.4
19.9
22.0
23.3
18.7
19.8
20.9
22.6
24.9
26.3
20.9
22.2
23.4
25.3
27.9
29.5
24.4
25.8
27.3
29.4
32.4
33.8
28.5
30.1
31.7
34.1
37.6
38.6
34.1
36.0
37.9
40.7
44.7
45.1
41.1
43.4
45.6
49.0
53.8
54.1
43.2
45.5
47.9
51.4
56.3
59.2
52.5
55.3
58.1
62.3
67.6
67.5
56.4
59.4
62.4
66.9
73.2
70.0
73.7
47
47
47
47
46
46
51
51
51
51
50
50
57
57
57
57
56
55
63
63
63
63
62
61
72
72
72
72
71
69
83
83
83
83
81
78
97
97
97
97
95
90
115
115
115
115
113
107
120
120
120
120
118
117
144
144
144
144
140
132
154
154
154
154
151
189
189
208
208
208
208
205
203
207
207
207
207
204
202
211
211
211
211
207
205
210
210
210
210
206
204
213
213
213
213
210
205
214
214
214
214
210
202
215
215
215
215
212
200
213
213
213
213
209
197
204
204
204
204
201
198
213
213
213
213
207
195
204
204
204
204
200
210
210
75.4
76.4
77.3
78.6
80.5
81.5
76.9
77.9
78.7
79.5
81.7
82.6
78.9
79.8
80.5
81.6
83.0
83.9
80.3
81.1
81.9
82.8
84.3
85.1
82.3
83.1
83.7
84.6
85.9
86.6
84.1
84.8
85.3
86.1
87.3
88.0
86.0
86.5
87.0
87.7
88.7
89.4
87.7
88.2
88.6
89.2
90.1
90.6
88.7
89.1
89.5
90.0
90.8
91.2
89.7
90.1
90.5
90.9
91.6
91.9
90.5
90.8
91.1
91.6
92.2
91.6
91.8
680
720
765
830
935
1000
601-PC
755
800
845
915
1035
1105
601-NC
845
900
950
1025
1150
1225
601-MC
955
1010
1065
1150
1295
1380
601-LC
1095
1160
1220
1315
1475
1575
601-KC
1275
1345
1420
1525
1710
1825
601-HC
1515
1595
1680
1805
2020
2155
601-GC
1845
1950
2050
2200
2460
2615
601-GB
2020
2130
2240
2400
2680
2850
601-FC
2350
2480
2605
2795
3115
3315
601-EB
2640
2780
2920
3140
3490
601-EC1
h
P
(kW)
3190
3360
n2
RA (115C)
-1
min
()
1075
1.59
26.3
1180
1.36
22.1
1280
1.12
18.3
1430
0.92
14.9
1580
0.71
11.7
1800
1800
1800
1800
1825
1825
2095
2095
2095
2095
2095
2155
2545
2545
2545
2545
2545
2615
3000
0.54
9.0
0.40
6.6
0.28
4.6
0.25
4.0
3170
3170
3170
3170
3170
3315
3500
0.18
2.9
0.15
2.4
3500
0.10
1.7
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
19
LA (0Hz)
(mH)
160-4M
240 Nm
Technical data
nmax
n0
3500 min-1
40 min-1
Cat. Nr Ua (V):400
FR 157...
201-NC
J
0.25 kgm2
420
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
1250 W
550 V
110-440 V
880 m3/h
980 Pa
230 kg
245 kg
440
470
-1
nb (min )
520
550
I
(A)
T
(Nm)
(%)
15.4
16.4
17.4
18.8
21.0
22.3
17.6
18.7
19.8
21.5
23.9
25.1
20.4
21.6
22.9
24.7
27.4
28.8
23.8
25.2
26.6
28.7
31.7
33.5
28.9
30.6
32.2
34.7
38.3
40.5
35.5
37.4
39.5
42.3
46.7
48.6
45.2
47.7
50.2
53.9
59.2
62.4
50.3
53.1
55.8
59.9
65.6
69.0
60.4
63.6
66.8
71.7
78.5
73.5
77.4
81.2
87.0
50
50
50
50
50
50
56
56
56
56
55
54
63
63
63
63
62
61
72
72
72
72
71
70
85
85
85
85
84
83
102
102
102
102
100
98
127
127
127
127
125
124
140
140
140
140
138
136
166
166
166
166
163
200
200
200
200
237
237
237
237
233
232
238
238
238
238
234
230
239
239
239
239
235
231
238
238
238
238
234
232
242
242
242
242
237
235
241
241
241
241
237
232
240
240
240
240
236
234
237
237
237
237
233
230
235
235
235
235
231
241
241
240
240
72.5
73.6
74.7
76.0
78.2
79.3
74.6
75.6
76.6
77.9
79.9
80.9
77.1
78.0
78.9
80.0
81.8
82.7
79.1
79.9
80.7
81.7
83.3
84.2
82.0
82.8
83.4
84.3
85.6
86.3
84.4
85.0
85.6
86.3
87.5
88.1
86.9
87.4
87.9
88.5
89.4
89.8
88.6
89.0
89.4
89.9
90.7
91.0
89.2
89.6
90.0
90.4
91.1
91.0
91.2
91.5
91.8
620
660
700
760
860
920
201-MC
710
750
795
860
975
1040
201-LC
815
865
915
990
1115
1190
201-KC
950
1010
1065
1150
1295
1380
201-HC
1145
1210
1275
1375
1540
1640
201-GC*
1410
1485
1565
1680
1885
2000
201-FC
1800
1895
1995
2145
2390
2540
201-EB
2030
2140
2250
2420
2700
2860
201-EC*
2450
2580
2715
2910
3245
201-CB
h
P
(kW)
2920
3075
3230
3460
n2
RA (115C)
-1
min
()
925
925
925
925
925
925
1125
1125
1125
1125
1125
1125
1265
1265
1265
1265
1265
1265
1490
1490
1490
1490
1490
1490
1690
1690
1690
1690
1690
1690
2000
2000
2000
2000
2000
2000
2675
2675
2675
2675
2675
2675
2980
2980
2980
2980
2980
2980
3500
3500
3500
3500
3500
3500
3500
3500
3500
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
20
LA (0Hz)
(mH)
1.64
28.30
1.33
22.90
1.05
18.10
0.83
13.85
0.58
10.20
0.4
7.05
0.25
4.50
0.21
3.63
0.15
2.55
0.09
1.85
160-4MO
270 Nm
Technical data
nmax
n0
3500 min-1
40 min-1
Cat. Nr Ua (V):400
FR 157...
501-NC
J
0.27 kgm2
420
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
1250 W
550 V
110-440 V
880 m3/h
980 Pa
230 kg
255 kg
440
470
-1
nb (min )
520
550
I
(A)
T
(Nm)
(%)
18.1
19.2
20.3
22.0
24.4
25.8
20.4
21.7
22.9
24.7
27.4
29.0
23.9
25.3
26.8
28.9
31.9
33.6
28.0
29.6
31.2
33.7
37.1
39.1
33.6
35.5
37.4
40.3
44.3
46.6
40.6
42.9
45.2
48.5
53.3
56.1
42.5
44.9
47.2
50.7
55.6
58.5
52.0
54.8
57.6
61.8
67.8
71.2
55.8
58.8
61.8
66.3
72.6
76.3
69.5
73.2
76.9
82.4
90.1
94.6
77.9
82.0
86.0
92.2
57
57
57
57
56
55
63
63
63
63
62
61
72
72
72
72
71
70
83
83
83
83
81
80
97
97
97
97
95
94
115
115
115
115
113
112
120
120
120
120
118
117
144
144
144
144
142
140
154
154
154
154
151
150
189
189
189
189
186
184
210
210
210
210
270
270
270
270
265
263
269
269
269
269
264
261
273
273
273
273
269
265
274
274
274
274
269
266
276
276
276
276
271
268
273
273
273
273
268
265
260
260
260
260
256
253
273
273
273
273
268
265
261
261
261
261
256
253
269
269
269
269
264
261
253
253
253
253
75.9
76.9
77.8
79.0
80.9
81.9
77.7
78.7
79.5
80.6
82.3
83.2
80.1
80.9
81.6
82.6
84.1
84.9
82.1
82.9
83.5
84.4
85.7
86.4
84.3
84.9
85.4
86.2
87.4
88.0
86.3
86.9
87.4
88.0
89.1
89.6
87.1
87.6
88.0
88.6
89.5
89.9
88.6
89.0
89.4
90.0
90.7
91.1
89.4
89.8
90.1
90.7
91.3
91.7
90.7
91.0
91.3
91.7
92.3
92.6
91.6
91.8
92.1
92.4
640
680
720
780
880
940
501-MC
725
770
815
880
995
1060
501-LC
840
885
935
1010
1135
1210
501-KC
975
1035
1090
1175
1315
1405
501-HC
1165
1230
1295
1395
1560
1660
501-GC
1425
1505
1585
1700
1905
2020
501-GB
1560
1650
1730
1860
2080
2210
501-FC
1820
1915
2015
2165
2415
2560
501-EB
2050
2160
2270
2430
2710
2880
501-EC
2470
2605
2735
2935
3265
3465
501-CB
h
P
(kW)
2940
3095
3250
3480
n2
RA (115C)
-1
min
()
1035
1.28
23.6
1150
1.05
19.1
1275
0.81
15.1
1450
0.62
11.6
1680
0.45
8.5
2045
0.32
5.9
2420
0.29
4.9
2560
0.20
3.8
3110
0.18
2.9
3420
3420
3420
3420
3420
3465
3500
0.12
2.1
0.09
1.5
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
21
LA (0Hz)
(mH)
160-4L
310 Nm
Technical data
nmax
n0
3500 min-1
40 min-1
Cat. Nr Ua (V):400
FR 157...
101-LC
J
0.31 kgm2
420
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
1400 W
550 V
110-440 V
880 m3/h
980 Pa
275 kg
290 kg
440
470
-1
nb (min )
520
550
605
645
680
740
835
895
101-KC
710
750
795
860
970
1035
101-HC
860
910
960
1035
1165
1240
101-GC
1060
1120
1180
1270
1425
1515
101-FC*
1360
1435
1510
1625
1815
1930
101-EB
1540
1620
1710
1840
2050
2180
101-EC*
1860
1960
2060
2215
2470
2620
101-CB*
2220
2340
2460
2635
2935
3110
101-BB*
2815
2960
3100
3330
P
(kW)
19.6
20.9
22.1
24.0
26.6
28.1
23.0
24.4
25.8
27.9
31.0
32.7
28.2
29.8
31.5
34.0
37.5
39.7
34.7
36.6
38.7
41.6
45.9
48.3
44.4
46.9
49.4
53.1
58.4
61.6
49.6
52.3
55.1
59.1
64.9
68.2
59.6
62.8
66.1
70.9
77.7
81.9
73.1
76.9
80.9
86.7
96.4
102.0
86.4
91.0
95.5
102.0
I
(A)
63
63
63
63
62
61
72
72
72
72
71
70
85
85
85
85
84
83
102
102
102
102
100
99
127
127
127
127
125
124
140
140
140
140
138
136
166
166
166
166
163
162
200
200
200
200
200
200
234
234
234
234
h
T
(Nm)
(%)
n2
RA (115C)
-1
min
()
310
310
310
310
305
300
310
310
310
310
305
301
313
313
313
313
308
306
313
313
313
313
308
304
312
312
312
312
307
305
308
308
308
308
302
299
306
306
306
306
301
298
314
314
314
314
314
314
294
294
294
293
73.8
74.9
75.9
77.2
79.2
80.3
76.2
77.1
78.0
79.2
81.1
82.0
79.5
80.4
81.1
82.1
83.7
84.4
82.3
83.0
83.6
84.5
85.8
86.4
85.1
85.7
86.2
86.9
88.0
88.5
87.1
87.6
88.0
88.6
89.5
90.0
87.9
88.3
88.7
89.3
90.1
90.5
90.3
90.5
90.9
91.3
91.9
92.2
91.4
91.7
91.9
92.3
1000
1000
1000
1000
1000
1000
1175
1175
1175
1175
1175
1175
1330
1330
1330
1330
1330
1330
1565
1565
1565
1565
1565
1565
2105
2105
2105
2105
2105
2105
2350
2350
2350
2350
2350
2350
2815
2815
2815
2815
2815
2815
3230
3230
3230
3230
3230
3230
3500
3500
3500
3500
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
22
LA (0Hz)
(mH)
1.24
22.60
0.97
17.30
0.68
12.70
0.48
8.85
0.30
5.65
0.25
4.60
0.18
3.20
0.11
2.30
0.08
1.50
160-4LO
350 Nm
Technical data
nmax
n0
3500 min-1
40 min-1
Cat. Nr Ua (V):400
FR 157...
401-LC
J
0.33 kgm2
420
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
1400 W
550 V
110-440 V
880 m3/h
980 Pa
280 kg
305 kg
440
470
-1
nb (min )
520
550
620
660
695
755
850
910
401-KC
725
770
815
880
990
1055
401-HC
870
920
970
1045
1175
1250
401-GC
1070
1130
1190
1280
1435
1530
401-GB
1180
1250
1310
1410
1580
1680
401-FC
1370
1450
1525
1635
1825
1940
401-EB
1550
1640
1720
1850
2060
2190
401-EC1
1870
1970
2075
2225
2475
2630
401-CB
2230
2350
2465
2645
2940
3120
401-BB
2810
2960
3105
3325
P
(kW)
23.2
24.6
26.0
28.2
31.2
32.9
27.2
28.9
30.5
32.9
36.3
38.4
32.9
34.7
36.6
39.5
43.5
45.9
39.9
42.2
44.4
47.8
52.5
55.3
41.9
44.3
46.6
50.1
55.1
58.0
51.3
54.1
56.9
61.1
66.9
70.3
55.0
58.1
61.1
65.6
71.9
75.5
68.8
72.5
76.2
81.7
89.2
93.7
77.4
81.4
85.5
91.6
100.1
105.1
92.6
97.5
102.3
109.6
I
(A)
72
72
72
72
71
70
83
83
83
83
81
80
97
97
97
97
95
94
115
115
115
115
113
112
120
120
120
120
118
117
144
144
144
144
142
140
154
154
154
154
151
150
189
189
189
189
186
184
210
210
210
210
207
204
250
250
250
250
h
T
(Nm)
(%)
357
357
357
357
350
346
358
358
358
358
351
348
361
361
361
361
354
350
357
357
357
357
349
346
340
340
340
340
334
330
357
357
357
357
350
346
339
339
339
339
333
329
351
351
351
351
344
340
331
331
331
331
325
321
315
315
315
315
77.7
78.6
79.5
80.6
82.0
82.9
80.0
80.7
81.2
82.2
83.8
84.6
82.4
83.1
83.8
84.7
85.7
86.4
84.8
85.4
85.9
86.7
87.6
88.2
85.7
86.2
86.7
87.4
88.5
89.0
87.5
87.9
88.4
89.0
89.5
89.9
88.0
88.5
88.9
89.4
90.2
90.7
89.8
90.1
90.5
90.9
91.3
91.6
90.8
91.1
91.4
91.8
92.3
92.5
91.6
91.8
92.1
92.4
n2
RA (115C)
-1
min
()
990
0.95
19.6
1130
0.73
15
1310
0.53
11
1590
0.37
7.6
1900
0.33
6.6
1985
0.24
4.9
2450
0.21
4.0
2690
0.14
2.8
3480
0.1
3500
0.07
1.3
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
23
LA (0Hz)
(mH)
160-4LB
500 Nm
Technical data
nmax
n0
3500 min-1
40 min-1
Cat. Nr Ua (V):400
FR 157...
701-LC
J
0.46 kgm2
420
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
2000 W
550 V
110-440 V
880 m3/h
980 Pa
380 kg
405 kg
440
470
-1
nb (min )
520
550
410
435
460
500
570
615
701-KC
485
515
545
590
670
715
701-HC
585
620
655
705
800
850
701-GC
725
765
810
870
985
1045
701-GB
800
840
890
960
1070
1150
701-FC
935
990
1045
1120
1255
1335
701-EB
1060
1110
1170
1260
1410
1500
701-EC1
1290
1360
1430
1535
1710
1820
701-CB
1540
1625
1705
1830
2040
2165
701-BB
1945
2050
2155
2310
2570
2725
h
P
(kW)
I
(A)
T
(Nm)
(%)
21.8
23.2
24.6
26.7
29.9
31.7
25.8
27.4
29.0
31.5
35.0
37.1
31.4
33.3
35.2
38.0
42.2
44.6
38.5
40.7
43.0
46.3
51.3
54.1
40.6
43.0
45.3
48.9
53.9
56.8
49.9
52.7
55.5
59.7
65.8
69.2
53.8
56.8
59.8
64.3
70.7
74.4
67.4
71.1
74.9
80.4
88.1
92.6
76.4
80.5
84.6
90.7
99.3
104.3
91.7
96.6
101.4
108.7
118.9
124.8
72
72
72
72
71
70
83
83
83
83
81
80
97
97
97
97
95
94
115
115
115
115
113
112
120
120
120
120
118
117
144
144
144
144
142
140
154
154
154
154
151
150
189
189
189
189
186
184
210
210
210
210
207
204
250
250
250
250
246
243
508
508
508
508
500
494
509
510
510
510
501
496
514
514
514
514
505
500
508
508
508
508
499
494
487
487
487
487
479
474
509
509
509
509
500
495
487
487
487
487
478
473
500
500
500
500
492
486
473
473
473
473
465
460
450
450
450
450
442
437
72.2
73.4
74.4
75.8
78.2
79.4
75.0
76.1
77.0
78.3
80.2
81.2
78.2
79.0
79.9
81.0
82.6
83.5
81.2
81.9
82.6
83.6
85.1
85.9
82.2
82.9
83.6
84.5
85.8
86.5
84.5
85.1
85.7
86.4
87.6
88.1
85.3
85.9
86.4
87.1
88.2
88.7
87.6
88.0
88.5
89.0
89.8
90.3
89.3
89.7
90.0
90.5
91.2
91.5
90.4
90.7
91.0
91.4
91.9
92.2
n2
RA (115C)
-1
min
()
715
1.21
29
815
0.94
22.2
945
0.69
16.3
1145
0.47
11.3
1350
0.43
9.6
1430
0.30
7.3
1750
0.27
5.8
1995
0.17
4.1
2510
0.12
2745
0.09
1.9
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
2 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 15% reduction of power.
* Normally kept in stock with reinforced impregnation.
24
LA (0Hz)
(mH)
180-4A
400 Nm
Technical data
nmax
n0
4500 min-1
40 min-1
Cat. Nr Ua (V):400
FR 159...
101-RC
J
0.39 kgm2
420
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
1520 W
550 V
110-440 V
1300 m3/h
1250 Pa
290 kg
320 kg
440
470
-1
nb (min )
520
550
I
(A)
T
(Nm)
(%)
27
29
31
33
37
39
32
34
36
39
43
45
37
40
42
45
50
52
43
46
48
52
57
60
53
56
59
64
70
81
59
62
65
70
77
94
69
72
76
82
90
94
75
79
79
79
79
79
89
94
99
106
116
122
110
111
111
111
111
111
137
139
139
139
139
85
85
85
85
84
83
97
97
97
97
95
94
111
111
111
111
109
108
126
126
126
126
124
123
152
152
152
152
149
148
166
166
166
166
163
162
192
192
192
192
189
187
207
207
198
184
164
154
245
245
245
245
241
238
299
286
272
253
227
214
368
356
338
315
283
400
400
400
400
394
389
406
406
406
406
399
395
407
407
407
407
400
396
396
396
396
396
389
385
398
398
398
398
391
387
400
400
400
400
393
389
402
402
402
402
395
391
387
387
370
343
306
287
384
384
384
384
377
373
400
382
363
337
302
284
393
380
361
335
300
77.9
78.9
79.7
80.8
82.5
83.4
80.2
81.0
81.7
82.7
84.2
85.0
82.4
83.1
83.7
84.6
85.9
86.6
84.0
84.6
85.2
86.0
87.1
87.8
86.0
86.5
87.0
87.7
88.7
89.2
87.2
87.6
88.1
88.7
89.6
90.0
88.2
88.7
89.1
89.6
90.4
90.6
89.0
89.4
89.9
90.6
91.3
91.6
90.2
90.5
90.8
91.2
91.9
92.1
91.4
91.8
92.1
92.5
92.9
93.1
92.4
92.6
92.9
93.2
93.5
650
700
730
790
900
950
101-PC
750
800
840
900
1020
1090
101-NC
880
930
980
1060
1190
1260
101-LC
1040
1100
1160
1250
1400
1490
101-HC
1280
1350
1420
1530
1700
1810
101-GB
1400
1480
1560
1680
1870
1990
101-FC*
1630
1720
1810
1940
2170
2300
101-EB
1840
1930
2040
2200
2470
2620
101-DC1
2220
2340
2460
2630
2930
3110
101-CB
2640
2780
2930
3140
3500
3720
101-BB
h
P
(kW)
3330
3500
3690
3950
4400
n2
RA (115C)
-1
min
()
2300
0.73
15.7
1500
0.63
12.4
2730
0.47
9.5
3740
0.37
3910
0.26
4.8
2100
0.21
4.1
4500
0.16
3.1
1950
1950
2040
2200
2470
2620
4500
0.13
2.5
0.1
1.7
2660
2780
2930
3140
3500
3720
3390
3500
3690
3950
4400
0.06
1.3
0.04
0.8
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 15% reduction of power.
* Normally kept in stock with reinforced impregnation.
25
LA (0Hz)
(mH)
180-4B
470 Nm
Technical data
nmax
n0
4500 min-1
40 min-1
Cat. Nr Ua (V):400
FR 159...
201-RC
J
0.47 kgm2
420
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
1670 W
550 V
110-440 V
1300 m3/h
1250 Pa
330 kg
360 kg
440
470
-1
nb (min )
520
550
I
(A)
T
(Nm)
(%)
27
28
30
32
36
38
31
33
35
38
42
44
37
39
41
44
49
52
43
45
48
51
57
60
53
56
59
63
69
73
58
61
65
70
76
80
68
72
76
82
89
94
74
78
82
88
96
101
89
94
98
105
115
121
110
113
113
113
113
113
136
142
142
142
141
141
168
85
85
85
85
84
83
97
97
97
97
95
94
111
111
111
111
109
108
126
126
126
126
124
123
152
152
152
152
149
148
166
166
166
166
163
162
192
192
192
192
189
187
207
207
207
207
204
202
245
245
245
245
241
238
299
293
278
259
232
219
368
365
346
322
289
273
450
472
472
472
472
464
459
479
479
479
479
471
466
480
480
480
480
472
467
467
467
467
467
459
454
469
469
469
469
461
456
471
471
471
471
463
458
474
474
474
474
456
461
453
457
457
457
449
444
453
453
453
453
445
441
471
462
438
407
364
342
464
460
436
405
363
341
424
75.6
76.6
77.5
78.8
80.7
81.7
78.4
79.3
80.1
81.2
82.9
83.8
81.0
81.8
82.5
83.4
84.9
85.6
82.8
83.5
84.1
85.0
86.3
86.9
85.1
85.7
86.3
87.0
88.1
88.6
86.1
86.7
87.1
87.8
88.8
89.3
87.7
88.2
88.6
89.2
90.0
90.5
87.8
88.4
88.8
89.4
90.1
90.5
89.5
89.9
90.2
90.7
91.4
91.7
91.0
91.4
91.8
92.2
92.7
92.9
92.0
92.2
92.6
92.9
93.2
93.4
93.0
540
570
600
660
740
790
201-PC
625
660
700
755
855
910
201-NC
735
775
820
885
995
1060
201-LC
875
925
975
1050
1175
1255
201-HC
1075
1135
1195
1285
1440
1530
201-GB
1175
1245
1310
1410
1575
1675
201-FC*
1375
1450
1530
1640
1830
1945
201-EB
1550
1630
1710
1840
2050
2180
201-DC
1870
1970
2070
2220
2475
2630
201-CB
2230
2350
2470
2660
2960
3150
201-BB
2810
2960
3110
3340
3720
3950
201-AB1
h
P
(kW)
3800
n2
RA (115C)
-1
min
()
1800
0.81
18.7
1200
0.69
14.8
2360
0.52
11.3
3230
0.41
8.3
3390
0.28
5.8
1700
0.24
4.9
4200
0.17
3.7
2500
0.15
4500
0.11
2.1
2300
2350
2470
2660
2960
3150
2930
2960
3110
3340
3720
3950
4000
0.07
1.5
0.05
0.03
0.5
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 15% reduction of power.
* Normally kept in stock with reinforced impregnation.
26
LA (0Hz)
(mH)
180-4C
600 Nm
Technical data
nmax
n0
4500 min-1
40 min-1
Cat. Nr Ua (V):400
FR 159...
301-PC
J
0.55 kgm2
420
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
1900 W
550 V
110-440 V
1300 m3/h
1250 Pa
380 kg
410 kg
440
470
-1
nb (min )
520
550
I
(A)
T
(Nm)
(%)
31
33
35
38
43
45
38
40
42
46
51
53
44
46
49
53
58
61
54
57
60
65
71
75
60
63
67
72
79
83
70
74
78
84
93
97
77
81
83
83
82
82
93
98
103
110
121
127
115
116
116
115
115
115
142
144
144
144
144
143
167
176
185
198
101
101
101
101
99
98
117
117
117
117
115
114
132
132
132
132
130
128
159
159
159
159
156
155
174
174
174
174
171
169
201
201
201
201
198
196
218
218
211
195
173
163
258
258
258
258
254
251
315
301
286
266
238
224
386
372
354
329
295
278
450
450
450
450
613
613
613
613
603
596
621
621
621
621
611
605
601
601
601
601
590
584
603
603
603
603
593
587
607
607
607
607
597
591
610
610
610
610
599
593
591
591
571
528
469
440
587
587
587
587
576
570
610
583
553
513
458
431
598
576
547
508
454
427
521
521
521
520
75.6
76.6
77.6
78.8
80.8
81.7
78.2
79.1
80.0
81.1
82.8
83.7
80.5
81.3
82.1
83.0
84.6
85.3
83.1
83.8
84.4
85.2
86.5
87.2
84.6
85.1
85.7
86.5
87.6
88.2
86.3
86.8
87.3
88.0
89.0
89.4
86.9
87.4
88.0
88.9
90.0
90.5
88.7
89.1
89.5
90.0
90.7
91.1
90.1
90.6
91.0
91.6
92.2
92.4
91.3
91.6
92.0
92.4
92.9
93.0
92.5
92.8
92.9
93.2
490
520
550
600
675
725
301-NC
575
610
645
700
790
845
301-LC
690
730
775
835
940
1000
301-HC
850
900
950
1025
1150
1225
301-GB
940
995
1050
1130
1265
1345
301-FC
1100
1165
1225
1320
1475
1565
301-EB
1240
1310
1380
1500
1680
1790
1
301-DC *
1510
1590
1670
1795
2000
2125
301-CB1
1795
1900
2000
2150
2400
2550
301-BB *
2270
2395
2520
2710
3020
3200
301-AB
h
P
(kW)
3080
3230
3400
3640
n2
RA (115C)
-1
min
()
900
0.69
18.1
1860
0.53
13.9
2550
0.4
10.2
2690
0.28
7.1
1360
0.26
3330
0.19
4.5
1330
1330
1380
1500
1680
1790
4500
0.17
3.6
0.12
2.5
1810
1900
2000
2150
2400
2550
2310
2395
2520
2710
3020
3200
4000
0.08
1.8
0.05
1.2
0.03
0.7
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 15% reduction of power.
* Normally kept in stock with reinforced impregnation.
27
LA (0Hz)
(mH)
180-4D
700 Nm
Technical data
nmax
n0
4500 min-1
40 min-1
Cat. Nr Ua (V):400
FR 159...
401-NC
J
0.69 kgm2
420
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
2240 W
550 V
110-440 V
1300 m3/h
1250 Pa
470 kg
500 kg
440
470
-1
nb (min )
520
550
P
I
(kW) (A)
450
33
35
37
40
44
47
40
43
45
49
54
57
51
54
57
61
68
71
53
56
59
64
70
74
64
68
72
77
85
89
68
72
76
81
88
88
87
92
97
104
114
120
101
107
112
121
124
123
126
133
140
150
155
154
166
175
184
197
215
225
480
510
550
625
670
401-LC
545
580
610
660
745
800
401-HC
680
720
760
820
920
980
401-GB
760
800
845
910
1020
1085
401-FC
875
925
975
1050
1180
1255
401-EB
1000
1055
1110
1200
1340
1430
401-DC*
1210
1275
1340
1440
1610
1710
401-CB1
1445
1525
1605
1720
1925
2045
401-BB1*
1835
1930
2030
2175
2425
2575
401-AB
2470
2600
2730
2930
3250
3450
105
105
105
105
103
102
125
125
125
125
123
122
152
152
152
152
149
148
155
155
155
155
152
151
187
187
187
187
184
182
194
194
194
194
189
176
246
246
246
246
242
239
280
280
280
280
257
242
344
344
344
344
320
301
450
450
450
450
442
438
h
T
(Nm)
(%)
688
688
688
688
676
670
702
702
702
702
690
683
712
712
712
712
700
693
668
668
668
668
656
649
701
701
701
701
688
681
649
649
649
649
631
586
691
691
691
691
679
671
669
669
669
669
614
576
657
657
657
657
609
572
644
644
644
643
631
625
74.8
75.8
76.8
78.0
80.0
81.0
77.9
78.8
79.6
80.7
82.5
83.3
81.4
82.1
82.8
83.7
85.2
85.9
83.4
84.0
84.6
85.5
86.7
87.3
84.3
84.9
85.5
86.3
87.4
88.0
86.0
86.5
87.0
87.6
88.6
89.3
87.5
88.0
88.4
89.0
89.8
90.2
89.3
89.7
90.0
90.5
91.3
91.6
90.7
91.0
91.3
91.6
92.2
92.5
91.8
92.0
92.3
92.5
92.9
93.1
n2
RA (115C)
-1
min
()
1500
0.77
17.1
2210
0.55
12.6
2310
0.37
8.7
1100
0.3
7.4
2930
0.24
5.6
1300
1300
1300
1300
1340
1430
4500
0.19
4.5
0.14
3.1
1770
1770
1770
1770
1925
2045
2250
2250
2250
2250
2425
2575
4000
0.09
2.3
0.06
1.5
0.04
0.8
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 10% reduction of power.
* Normally kept in stock with reinforced impregnation.
28
LA (0Hz)
(mH)
180-4E
800 Nm
Technical data
nmax
n0
3800 min-1
40 min-1
Cat. Nr Ua (V):400
FR 159...
501-HC
J
0.81 kgm2
420
Pf
Uamax
Uf
Vcool
Pr
W(foot)
W(flange)
2400 W
550 V
110-440 V
1500 m3/h
1530 Pa
520 kg
550 kg
440
470
-1
nb (min )
520
550
570
605
635
690
775
825
501-GB
630
665
705
760
850
910
501-FC
735
780
820
870
990
1055
501-EB
835
885
930
1000
1125
1200
501-DC
1020
1075
1130
1215
1360
1445
501-CB1
1215
1280
1345
1445
1620
1725
501-BB
1545
1625
1710
1835
2040
2170
501-AB
2100
2200
2320
2480
2760
P
I
(kW) (A)
49
51
54
59
65
69
54
57
60
65
72
76
62
65
69
74
81
86
70
74
77
83
90
90
84
89
94
100
110
116
104
110
116
124
125
125
130
137
144
154
169
177
166
175
183
196
214
148
148
148
148
146
144
162
162
162
162
159
158
181
181
181
181
178
176
202
202
202
202
194
181
239
239
239
239
235
233
292
292
292
292
263
247
358
358
358
358
352
348
450
450
450
450
442
h
T
(Nm)
(%)
815
815
815
815
801
792
820
820
820
820
806
798
795
795
795
795
783
775
790
790
790
790
761
711
789
789
789
789
775
766
821
821
821
821
736
691
805
805
805
805
790
781
757
756
756
756
742
79.8
80.6
81.3
82.3
83.9
84.6
81.3
82.1
82.8
83.7
85.1
85.8
83.0
83.6
84.3
85.1
86.3
87.0
84.4
85.0
85.5
86.3
87.5
88.3
86.5
87.0
87.5
88.1
89.0
89.5
88.2
88.6
89.0
89.5
90.5
90.9
89.8
90.1
90.4
90.9
91.6
91.9
91.4
91.7
91.9
92.2
92.6
n2
RA (115C)
-1
min
()
1700
0.42
10.3
920
0.34
8.7
2450
0.27
6.6
1070
1070
1070
1070
1125
1200
3400
0.22
5.3
0.15
3.7
1450
1450
1450
1450
1620
1725
3000
0.11
2.7
0.07
1.7
3200
0.05
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 15% reduction of power.
* Normally kept in stock with reinforced impregnation.
29
LA (0Hz)
(mH)
180-4F
900-1000 Nm
Technical data
nmax
n0
3000 min-1
40 min-1
Cat. Nr Ua (V):400
FR 159...
601-BF
J
1.05 kgm2
420
Pf
Uamax
Uf
Vcool
Pr
W(foot)
2650 W
550 V
110-440 V
1900 m3/h
1400 Pa
630 kg
440
470
-1
nb (min )
520
550
P
I
(kW) (A)
610
66
69
73
79
87
92
65
69
73
79
87
86
75
79
83
90
99
104
90
95
100
108
118
124
86
91
95
103
113
119
103
109
115
123
135
142
143
151
158
170
186
195
175
184
193
207
226
237
650
680
740
830
880
601-FF
670
710
750
810
910
970
601-EF
770
810
860
920
1040
1100
601-BD
880
930
980
1050
1170
1250
601-DF
890
940
990
1070
1200
1270
601-CF
1060
1120
1180
1270
1410
1500
1
601-AF *
1310
1380
1450
1560
1740
1840
601-AD *
1850
1940
2040
2190
2430
2580
194
194
194
194
194
189
196
196
196
196
193
191
220
220
220
220
216
214
255
255
255
255
251
248
249
249
249
249
245
242
294
294
294
294
289
286
394
394
394
394
387
383
474
474
474
474
466
461
660 kg
T
(Nm)
h
(%)
n2
RA (115C)
-1
min
()
1024
1024
1024
1024
1007
996
930
930
930
930
914
904
928
928
927
927
911
902
977
977
977
977
960
950
918
918
918
918
902
892
929
929
929
929
913
903
1039
1039
1039
1039
1021
1010
905
905
904
904
888
878
82.7
83.4
84.0
84.8
86.1
86.8
81.7
82.4
83.0
83.9
85.3
86.0
83.3
83.9
84.5
85.3
86.5
87.1
86.6
87.1
87.6
88.2
89.1
89.6
84.7
85.3
85.8
86.5
87.6
88.1
86.5
87.0
87.4
88.0
88.9
89.4
89.7
90.1
90.4
90.8
91.4
91.8
91.4
91.7
91.9
92.2
92.6
92.8
1200
0.26
10.5
1050
0.29
8.5
1200
0.22
6.8
1800
0.14
5.6
1400
0.18
5.2
1700
0.13
3.8
2500
0.06
2.6
2800
0.05
1.4
1 Cooling air inlet at commutator side. Can be used with cooling air inlet at shaft side with 15% reduction of power.
* Normally kept in stock with reinforced impregnation.
30
W(flange)
LA (0Hz)
(mH)
IC06
Dimensions in mm
DMP
112-2MA
112-2LA
112-4M
112-4L
132-2M
132-4S
132-4M
132-4L
132-4LB
DMP
112-2MA
112-2LA
112-4M
112-4L
132-2M
132-4S
132-4M
132-4L
132-4LB
AA
190
45
AB
AC
AD
AE
AJ
AK
77
326
AF
AG
17
AH
220
220
220
220
285
17
17
17
17
33.5
195
195
195
195
235
175
175
175
175
208
195
195
195
195
235
77
77
77
77
89
DE
GA
112
CA
CB
CC
70
55
25
45
38 M10 80
10
41
64
38
38
38
38
42
10
10
10
10
12
41
41
41
41
45
89
60
25
AI
80
80
M10 80
80
110
132
B
373
428
373
428
BA
50
BC
336
391
336
391
BD
235
BE
514
569
514
569
50
419
374
419
469
609
335
335
335
335
298
590
545
590
640
780
HD
HE
HF
KL
10
241 451
66
250
12
60
12
491
491
491
491
569
86
290
290
290
290
314
12
60
60
60
60
80
366
482
437
482
532
642
HA
HC
261
31
BF
190
190
L
L+REO444R1 L+TDP0.2LT
594.5
805.5
811.5
649.5
860.5
866.5
594.5
805.5
811.5
649.5
860.5
866.5
695.5
650.5
695.5
745.5
885
906.5
861.5
906.5
956.5
1096
912.5
867.5
912.5
962.5
1102
W (kg)
97
103
110
117
139
122
152
177
236
IC06
Dimensions in mm
DMP
160-4S/SO
160-4M/MO
160-4L/LO
160-4LB
180-4A
180-4B
180-4C
180-4D
180-4E
180-4F
DMP
160-4S/SO
160-4M/MO
160-4L/LO
160-4LB
180-4A
180-4B
180-4C
180-4D
180-4E
180-4F
AE
285
285
285
315
AF
33.5
33.5
33.5
21.5
AG
235
235
235
300
AH
208
208
208
208
294
294
294
294
294
392
355
355
355
355
405
405
25.5
25.5
25.5
340
25.5
28.5
28.5
DE
AA
254
56
279
66
66
66
66
61
61
356 391
CA
CB
AB
108
65
28
121
195
195
195
195
195
95
50
35
21
43
28
40
AC
CC
AD
AI
235
235
235
300
AJ
89
89
89
80
265
265
265
265
270
270
340
95
95
95
95
105
105
GA
HA
80
48 M16 110
14 51.5 160
91
55
55
60
70
70
70
16
16
18
20
20
20
M16
M16
M16
M20
M20
M20
110
110
140
140
140
140
59
59
64
180
74.5
74.5
74.5
AK
439
479
BC
426
473
56
538
663.5
B
475
522
587
712
BA
561
612
677
707
720
795
66
66
66
66
66
85
499
535
616
681
741
821
HD HE HF
611
356
611
356
14 343.5
88.5
611
356
641
338
18
18
18
18
18
18
HC
364
364
364
364
364
372.5
745 109
745 109
745 109
745 109
815 109
815 117.5
32
402
402
402
402
448
444
BD
298
298
298
299
BE
631
678
743
868
305 718
305 754
305 835
305 900
349 960
349 1071
K
KL
BF
240
240
L
744
791
856
981
15
80
15
15
15
15
15
19
848.5
80
884.5
80
110 965.5
110 1030.5
110 1190.5
110 1248
955
1002
1067
1192
961
1008
1073
1198
W (kg)
206/216
246/256
291/301
398
1059.5
1095.5
1176.5
1241.5
1301.5
1459
1065.5
1101.5
1182.5
1247.5
1307.5
1465
308
348
398
488
540
650
L+REO444R1 L+TDP0.2LT
IC17/37
Dimensions in mm
DMP
112-2MA
112-2LA
112-4M
112-4L
bb
cc
110
110
110
oa
ob
oc
104
110
100
100
M6
W (kg)
90
96
103
110
7.5
116.5
116.5
116.5
116.5
146.5
145
110
110
M6
132
115
145
170
220
145
7.5
263
310
375
500
150
180
130
130
M6
190/200
230/240
275/285
380
160
7.5
7.5
7.5
7.5
7.5
10
320
356
407
472
532
660
158.5
158.5
188.5
188.5
188.5
171
200
200
200
200
200
210
145
145
145
145
145
140
145
145
145
145
145
155
M8
290
330
380
470
520
630
150
125
7.5
125
160-4S/MO
160-4M/MO
160-4L/LO
160-4LB
190
145
7.5
160
7.5
7.5
7.5
7.5
7.5
10
210
286
241
286
336
446
132-2M
132-4S
132-4M
132-4L
132-4LB
180-4A
180-4B
180-4C
180-4D
180-4E
180-4F
d
245
300
245
300
33
IC666
Dimensions in mm
DMP
132-2M
132-4S
132-4M
132-4L
132-4LB
160-4S/SO
160-4M/MO
160-4L/LO
160-4LB
616
527.5
527.5
527.5
597
475
522
587
712
56
426
473
538
663
20
656
600
600
600
600
740
740
561
612
677
707
720
795
66
66
66
66
66
85
E
80
80
80
80
110
F
10
10
10
10
12
GA
41
41
41
41
45
HA
HB
132
110
14
51.5
160
AB
AC
AD
AE
AF
AK
216
47.5
260
279
223
390
20
440
335
274
515
515
515
606
294
294
294
294
294
322
606
606
606
606
720
720
DE
56
279
66
66
66
66
66
61
356
375
CA
CB
CC
60
25
64
D
38
38
38
38
42
160-4S/SO
160-4M/MO
160-4L/LO
160-4LB
65
28
80
180-4A
180-4B
180-4C
180-4D
180-4E
180-4F
195
195
195
195
195
95
DMP
132-2M
132-4S
132-4M
132-4L
132-4LB
B
482
437
482
532
642
AA
254
180-4A
180-4B
180-4C
180-4D
180-4E
180-4F
AL
482
437
482
390
532
642
50
35
21
43
28
40
316
91
48
55
55
60
70
70
70
M10
M16
M16
M16
M16
M20
M20
M20
110
110
140
140
140
140
20
16
16
18
20
20
20
59
59
64
74.5
74.5
74.5
180
BL
647
647
647
647
772
BM
91
91
91
91
121
BP
290
290
290
290
400
BO
223
223
223
223
238
240
723
723
723
843
753
800
115
865
990
325
325
325
320
240
240
240
278
108
499
535
616
681
741
821
240
843
843
843
843
1047
1047
126.5
126.5
156.5
156.5
149
131
320
320
320
320
500
500
278
278
278
278
337
337
121
HB
HC
HD
HE
12
215
261
1089
86
12
KL
60
60
60
60
80
L
695.5
650.5
695.5
745.5
885
215
215
14
215
240
215
215
215
240
343.5 1259
88.5
15
80
744
791
856
981
310
340
385
500
18
18
18
18
18
16
240
240
240
240
280
280
364
364
364
364
364
372.5
109
109
109
109
109
117.5
15
15
15
15
15
19
80
80
110
110
110
110
848,5
884,5
965,5
1030,5
1090,5
1248
525
555
615
645
725
820
BA
50
34
BC
419
374
419
469
609
BF
190
1259
1259
1334
1356
1356
1356
1356
1451
1451
89
W (kg)
212
205
225
250
310
IC86W
Dimensions in mm
A
AA
AB
AC
AD
AE
AK
AM
216
47.5
260
279
223
195
440
230
254
56
316
335
274
240
616
278
475
522
587
712
279
66
66
66
66
66
61
356
375
294
294
294
294
294
322
295
295
295
295
292
292
656
328
328
328
328
337
337
CA
CB
CC
DE
DN
60
25
64
D
38
38
38
38
42
M10
20
E
80
80
80
80
110
160-4S/SO
160-4M/MO
160-4L/LO
160-4LB
65
28
80
48
M16
20
180-4A
180-4B
180-4C
180-4D
180-4E
180-4F
195
195
195
195
195
95
50
35
21
43
28
40
91
55
55
60
70
70
70
M16
M16
M16
M20
M20
M20
20
20
20
20
25
25
DMP
132-2M
132-4S
132-4M
132-4L
132-4LB
160-4S/SO
160-4M/MO
160-4L/LO
160-4LB
180-4A
180-4B
180-4C
180-4D
180-4E
180-4F
DMP
132-2M
132-4S
132-4M
132-4L
132-4LB
B
482
437
482
532
642
BL
791
746
791
841
951
BM
99
99
99
99
129
240
753
800
865
990
110
110
110
110
142
142
HB
12
599
160
14
180
18
18
18
18
18
16
761
761
761
761
769
769
BD
BF
110
190
426
473
538
663
110
453.5
453.5
483.5
483.5
542.5
525
499
535
616
681
741
821
HA
132
BA
BO
220
89
158
215
108
240
860
896
947
1012
1112
1240
168.5
168.5
198.5
198.5
198.5
181
240
240
240
240
280
280
121
HC
HD
HE
261
719
86
12
KL
60
60
60
60
80
L
695.5
650.5
695.5
745.5
885.5
88.5
15
80
744
791
856
981
310
340
400
500
857
857
857
857
867
867
109
109
109
109
109
117.5
15
15
15
15
15
19
80
80
110
110
110
110
848.5
884.5
965.5
1030.5
1090.5
1248
410
460
510
600
660
790
BB
314
314
314
314
344
BC
419
374
419
469
609
56
393
561
612
677
707
720
795
66
66
66
66
66
85
F
10
10
10
10
12
GA
41
41
41
41
45
110
14
51.5
110
110
140
140
140
140
16
16
18
20
20
20
59
59
64
74.5
74.5
74.5
50
35
364
364
364
364
364
372.5
W (kg)
220
200
235
260
330
Flanges
VIEW: 1
VIEW: 1B
VIEW: 2
Dimensions in mm
DMP
Flange
LA
Nj6
112
F215
F265
F265
F300
14
14
17
17
215
265
265
300
180
230
230
250
250
300
300
350
4
4
4
5
1B
1B
1B
1B
160
F350
1B
180-4A/B/C/D/E
F300
F350
F400
F500
F300
F500
41
17
17
20
41
20
1
1B
2B
2
1
2
132
180-4F
300
350
400
500
300
500
250
300
350
450
250
450
S T View
350
400
450
550
350
550
15
15
15
19
19
19
19
19
19
19
5
5
5
5
5
5
tachometer flange
36
Ordering
Fan blower
The fan blower can be mounted
on top or on either side, at the
drive end or at the non-drive
end. The location does not affect
the output of the motor (except
when specified in the tables).
The fan can be delivered with a
38
Pos 25-42:
Additional price for blower and
terminal box mounted on same
side.