TCE CONSULTING ENGINEERS LIMITED

SHEET 1 OF 1

30421008-3OQ00002-P0C

I/O LIST FOR SEQUENCE OF EVENTS RECORDER

SAUDI ELECTRICITY COMPANY


EASTERN OPERATING AREA
Dammam, Saudi Arabia
GENERATION EXPANSION OF RAFHA POWER PLANT
(CONTRACT NO : 30421008/00)

I/O LIST FOR SEQUENCE OF EVENTS RECORDER

DOCUMENT NO : 30421008-3OQ-00002-P0C
JUNE 2005

ENGINEERING CONSULTANT
TCE CONSULTING ENGINEERS LIMITED
73/1, ST.MARK'S ROAD
BANGALORE 560001
INDIA

CONTRACTOR:
AL-TOUKHI COMPANY FOR INDUSTRY & TRADING
P.O.BOX 497, RIYADH 11411, KINGDOM OF SAUDI ARABIA
TEL.00966-1-4633660 : FAX.00966-1-4631150

P0C 02.06.2005

AE

SR

REV NO. DATE

PREPARED BY

CHECKED BY

275181139.xls
SECTION :cover sheet

CLEARED BY

APPROVED BY

SHEET 1 OF 35

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31

Alarm
code

Tag No
A.
63-1 GT
63-2 GT
63-1 OLTC
63-2 OLTC
49-1 OGT
49-2 OGT
49-1 WGT
49-2 WGT
71 GT
63 PRGT
COOLER
FAILURE
87 GT
87 GT
87 GT
87 GTG
51N GGT
87 OA
87 OA
87 OA
87 GT FDR
87 GT FDR
87 GT FDR
51 GT
51 GT
51 GT
2/50 BF
50 BF
86 A401
74/86
74/TC-1
74/TC-2

List of Digital Signals for SOER


Generator Transformer of Unit-1-T601
T601 Buchholz relay alarm operated
T601 Buchholz relay Trip operated
OLTC of T601 Buchholz relay alarm operated
OLTC of T601 Buchholz relay Trip operated
T601 Oil temperature high - Alarm
T601 Oil temperature very high - Trip
T601 Winding Temperature high - Alarm
T601 Winding Temperature very high - Trip
T601 Low Oil Level - Trip
T601 Pressure Relief Device operated - Trip
T601 Cooling System failed - Trip
T601 87GT Differential protection PH-A operated
T601 87GT Differential protection PH-B operated
T601 87GT Differential protection PH-C operated
T601 Restricted Ground Differential protection operated
T601 Ground Over Current backup protection operated
T601 Overall Unit Differential Protection PH-A operated
T601 Overall Unit Differential Protection PH-B operated
T601 Overall Unit Differential Protection PH-C operated
T601 33kV side Feeder Differential protection PH-A operated
T601 33kV side Feeder Differential protection PH-B operated
T601 33kV side Feeder Differential protection PH-C operated
T601 phase fault back up over current protection PH-A operated
T601 phase fault back up over current protection PH-B operated
T601 phase fault back up over current protection PH-C operated
T601 33kV Side Breaker Failure protection Timer operated - I stage-Alarm
T601 33kV Side Breaker failure relay operated - II stage
T601 33kV Side Breaker Lockout relay operated
T601 33kV Side Breaker Lockout relay supervision relay operated
T601 33kV Side Trip Coil-1 Supervision relay operated
T601 33kV Side Trip Coil-2 Supervision relay operated

2 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62

Alarm
code

Tag No
74/DC
27

List of Digital Signals for SOER


DC Supply Failure/Supervision relay operated
T601 Tap changer device fail alarm
OLTC pressure relief device operated
OLTC protection relay operated
OLTC Low oil level alarm
Transformer membrane failure alarm
Cooling system failed alarm
Transformer low oil level alarm
Maintenance switch open
74DC
DC circuit supervision relay (74DC)in the ckt of 86-1
74DC
DC circuit supervision relay (74DC)in the ckt of 86-2
Primary protection SOE common +ve open
Backup protection SOE common +ve open
Mechanical protection SOE common +ve open
86-1 Trip opened at FT
86-2 Trip opened at FT
86-3 Trip opened at FT
87GT
Relay 87GT faulty
50/51
Relay 50/51 GT faulty
87OA
Overall differential relay 87OA faulty
87 GT FDR Feeder differential relay 87GT FDR faulty
B.
Generator Transformer of Unit-2
63-1 GT
T602 Buchholz relay alarm operated
63-1 OLTC OLTC of T602 Buchholz relay alarm operated
63-2 OLTC OLTC of T602 Buchholz relay Trip operated
63-OLTC OLTC of T602 Buchholz relay Trip operated
49-1 OGT T602 Oil temperature high - Alarm
49-2 OGT T602 Oil temperature very high - Trip
49-1 WGT T602 Winding Temperature high - Alarm
49-2 WGT T602 Winding Temperature very high - Trip
71 GT
T602 Low Oil Level - Trip
63 PRGT T602 Pressure Relief Device operated - Trip

3 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94

Alarm
code

Tag No
COOLER
FAILURE
87 GT
87 GT
87 GT
87 GTG
51N GGT
87 OA
87 OA
87 OA
87 GT FDR
87 GT FDR
87 GT FDR
51 GT
51 GT
51 GT
2/50 BF
50 BF
86 A401
74/86
74/TC-1
74/TC-2
74/DC
27

74DC
74DC

List of Digital Signals for SOER


T602 Cooling System failed - Trip
T602 87GT Differential protection PH-A operated
T602 87GT Differential protection PH-B operated
T602 87GT Differential protection PH-C operated
T602 Restricted Ground Differential protection operated
T602 Ground Over Current backup protection operated
T602 Overall Unit Differential Protection PH-A operated
T602 Overall Unit Differential Protection PH-B operated
T602 Overall Unit Differential Protection PH-C operated
T602 33kV side Feeder Differential protection PH-A operated
T602 33kV side Feeder Differential protection PH-B operated
T602 33kV side Feeder Differential protection PH-C operated
T602 phase fault back up over current protection PH-A operated
T602 phase fault back up over current protection PH-B operated
T602 phase fault back up over current protection PH-C operated
T602 33kV Side Breaker Failure protection Timer operated - I stage-Alarm
T602 33kV Side Breaker failure relay operated - II stage
T602 33kV Side Breaker Lockout relay operated
T601 33kV Side Breaker Lockout relay supervision relay operated
T602 33kV Side Trip Coil-1 Supervision relay operated
T602 33kV Side Trip Coil-2 Supervision relay operated - Trip Coil-2 faulty
DC Supply Failure/Supervision relay operated
T602 Tap changer device fail alarm
OLTC pressure relief device operated
OLTC protection relay operated
OLTC Low oil level alarm
Transformer membrane failure alarm
Cooling system failed alarm
Transformer low oil level alarm
Maintenance switch open
DC circuit supervision relay (74DC)in the ckt of 86-1
DC circuit supervision relay (74DC)in the ckt of 86-2

4 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125

Alarm
code

Tag No

List of Digital Signals for SOER


Primary protection SOE common +ve open
Backup protection SOE common +ve open
Mechanical protection SOE common +ve open
86-1 Trip opened at FT
86-2 Trip opened at FT
86-3 Trip opened at FT
87GT
Relay 87GT faulty
50/51
Relay 50/51 GT faulty
87OA
Overall differential relay 87OA faulty
87 GT FDR Feeder differential relay 87GT FDR faulty
C.
63-1 GT
63-2 GT
63-1 OLTC
63-2 OLTC
49-1 OGT
49-2 OGT
49-1 WGT
49-2 WGT
71 GT
63 PRGT
COOLER
FAILURE
87 GT
87 GT
87 GT
87 GTG
51N GGT
87 OA
87 OA
87 OA
87 GT FDR
87 GT FDR

Generator Transformer of Future Unit


T603 Buchholz relay alarm operated
T603 Buchholz relay Trip operated
OLTC of T603 Buchholz relay alarm operated
OLTC of T603 Buchholz relay Trip operated
T603 Oil temperature high - Alarm
T603 Oil temperature very high - Trip
T603 Winding Temperature high - Alarm
T603 Winding Temperature very high - Trip
T603 Low Oil Level - Trip
T603 Pressure Relief Device operated - Trip
T603 Cooling System failed - Trip
T603 87GT Differential protection PH-A operated
T603 87GT Differential protection PH-B operated
T603 87GT Differential protection PH-C operated
T603 Restricted Ground Differential protection operated
T603 Ground Over Current backup protection operated
T603 Overall Unit Differential Protection PH-A operated
T603 Overall Unit Differential Protection PH-B operated
T603 Overall Unit Differential Protection PH-C operated
T603 33kV side Feeder Differential protection PH-A operated
T603 33kV side Feeder Differential protection PH-B operated

5 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157

Alarm
code

Tag No
87 GT FDR
51 GT
51 GT
51 GT
2/50 BF
50 BF
86 A401
74/86
74/TC-1
74/TC-2
74/DC
27

List of Digital Signals for SOER


T603 33kV side Feeder Differential protection PH-C operated
T603 phase fault back up over current protection PH-A operated
T603 phase fault back up over current protection PH-B operated
T603 phase fault back up over current protection PH-C operated
T603 33kV Side Breaker Failure protection Timer operated - I stage-Alarm
T603 33kV Side Breaker failure relay operated - II stage
T603 33kV Side Breaker Lockout relay operated
T601 33kV Side Breaker Lockout relay supervision relay operated
T603 33kV Side Trip Coil-1 Supervision relay operated
T603 33kV Side Trip Coil-2 Supervision relay operated
DC Supply Failure/Supervision relay operated
T603 Tap changer device fail alarm
OLTC pressure relief device operated
OLTC protection relay operated
OLTC Low oil level alarm
Transformer membrane failure alarm
Cooling system failed alarm
Transformer low oil level alarm
Maintenance switch open
74DC
DC circuit supervision relay (74DC)in the ckt of 86-1
74DC
DC circuit supervision relay (74DC)in the ckt of 86-2
Primary protection SOE common +ve open
Backup protection SOE common +ve open
Mechanical protection SOE common +ve open
86-1 Trip opened at FT
86-2 Trip opened at FT
86-3 Trip opened at FT
87GT
Relay 87GT faulty
Relay 50/51 GT faulty
50/51
87OA
Overall differential relay 87OA faulty
87 GT FDR Feeder differential relay 87GT FDR faulty
D
Unit Auxiliary Transformer UAT 301
49-1WUAT Unit Auxiliary Transformer Winding Temperature high - Alarm

6 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
158
159
160
161
162
163
164

Alarm
code

Tag No
49-2WUAT
51G UAT
51G UAT
50/51 UAT
50/51 UAT
50/51 UAT
50/51 UAT

165

50/51

166

50/51

167
168
169
170
171
172
173
174
175
176

50/51
51N
50/51N
86-A201
74/86
74/TC
74/DC
86-UAT
74/86/UAT

177
178
179
180
181
182
183
184
185

E
74/TC

F
49-1WUAT
49-2WUAT
51G UAT
50/51 UAT
50/51 UAT
50/51 UAT

List of Digital Signals for SOER


Unit Auxiliary Transformer Winding Temperature very high -Trip
Unit Auxiliary Transformer Ground Over Current protection operated
Unit Auxiliary Transformer Ground Over Current relay faulty
Unit Auxiliary Transformer HV Side over current protection Phase -A operated
Unit Auxiliary Transformer HV Side over current protection Phase -B operated
Unit Auxiliary Transformer HV Side over current protection Phase -C operated
Unit Auxiliary Transformer HV Side over current relay faulty
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-A
operated
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-B
operated
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-C
operated
Unit Auxiliary Transformer UAT301 Inverse Ground fault protection operated
Unit Auxiliary Transformer LV side O/C, E/F relay faulty
Unit Auxiliary Transformer UAT301 Breaker Lockout relay operated
Unit Auxiliary Transformer UAT301 Breaker Lockout relay supervision relay operated
Unit Auxiliary Transformer UAT301 Breaker Trip Coil Supervision relay operated
Unit Auxiliary Transformer UAT301 Breaker DC Supply Failure relay operated
Unit Auxiliary Transformer Lockout relay operated
Unit Auxiliary Transformer Lockout relay supervision relay operated
Unit Auxiliary Transformer maintenance contact open
Unit Auxiliary Transformer UAT 301 LV side Breaker(A201)
Unit Auxiliary Transformer Breaker Trip Coil Supervision relay operated
Unit Auxiliary Transformer Breaker Status
Unit Auxiliary Transformer Breaker Operating Mechanism failed
Unit Auxiliary Transformer UAT 302
Unit Auxiliary Transformer Winding Temperature high - Alarm
Unit Auxiliary Transformer Winding Temperature very high -Trip
Unit Auxiliary Transformer Ground Over Current protection operated
Unit Auxiliary Transformer HV Side over current protection Phase -A operated
Unit Auxiliary Transformer HV Side over current protection Phase -B operated
Unit Auxiliary Transformer HV Side over current protection Phase -C operated

7 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
186

Alarm
code

Tag No
50/51 UAT

187

50/51

188

50/51

189
190
191
192
193
194
195
196
197
198

50/51
51N
50/51N
86-A202
74/86
74/TC
74/DC
86-UAT
74/86/UAT

199
200
201

G
74/TC

202
203
204
205
206
207
208
209

H
49-1WUAT
49-2WUAT
51G UAT
51G UAT
50/51 UAT
50/51 UAT
50/51 UAT
50/51 UAT

210

50/51

211

50/51

List of Digital Signals for SOER


Unit Auxiliary Transformer HV Side over current relay faulty
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-A
operated
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-B
operated
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-C
operated
Unit Auxiliary Transformer UAT302 Inverse Ground fault protection operated
Unit Auxiliary Transformer LV side O/C, E/F relay faulty
Unit Auxiliary Transformer UAT302 Breaker Lockout relay operated
Unit Auxiliary Transformer UAT302 Breaker Lockout relay supervision relay operated
Unit Auxiliary Transformer UAT302 Breaker Trip Coil Supervision relay operated
Unit Auxiliary Transformer UAT302 Breaker DC Supply Failure relay operated
Unit Auxiliary Transformer Lockout relay operated
Unit Auxiliary Transformer Lockout relay supervision relay operated
Unit Auxiliary Transformer maintenance contact open
Unit Auxiliary Transformer UAT 302 LV side Breaker(A201)
Unit Auxiliary Transformer Breaker Trip Coil Supervision relay operated
Unit Auxiliary Transformer Breaker Status
Unit Auxiliary Transformer Breaker Operating Mechanism failed
Unit Auxiliary Transformer (Future Unit)
Unit Auxiliary Transformer Winding Temperature high - Alarm
Unit Auxiliary Transformer Winding Temperature very high -Trip
Unit Auxiliary Transformer Ground Over Current protection operated
Unit Auxiliary Transformer Ground Over Current relay faulty
Unit Auxiliary Transformer HV Side over current protection Phase -A operated
Unit Auxiliary Transformer HV Side over current protection Phase -B operated
Unit Auxiliary Transformer HV Side over current protection Phase -C operated
Unit Auxiliary Transformer HV Side over current relay faulty
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-A
operated
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-B
operated

8 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240

Alarm
code

Tag No
50/51
51N
50/51N
86-A203
74/86
74/TC
74/DC
86-UAT
74/86/UAT
I
74/TC

List of Digital Signals for SOER


Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-C
operated
Unit Auxiliary Transformer UAT303 Inverse Ground fault protection operated
Unit Auxiliary Transformer LV side O/C, E/F relay faulty
Unit Auxiliary Transformer UAT303 Breaker Lockout relay operated
Unit Auxiliary Transformer UAT303 Breaker Lockout relay supervision relay operated
Unit Auxiliary Transformer UAT303 Breaker Trip Coil Supervision relay operated
Unit Auxiliary Transformer UAT303 Breaker DC Supply Failure relay operated
Unit Auxiliary Transformer Lockout relay operated
Unit Auxiliary Transformer Lockout relay supervision relay operated
Unit Auxiliary Transformer maintenance contact open
Unit Auxiliary Transformer UAT 303 LV side Breaker(A201)

Unit Auxiliary Transformer Breaker Trip Coil Supervision relay operated


Unit Auxiliary Transformer Breaker Status
Unit Auxiliary Transformer Breaker Operating Mechanism failed
J
Station Auxiliary Transformer SAT T201
63-1 SAT Station Aux.Transformer T201 Buchholz relay alarm operated
63-2 SAT Station Aux.Transformer T201 Buchholz relay Trip operated
49-1 OSAT Station Aux.Transformer T201 Oil temperature high - Alarm
49-2 OSAT Station Aux.Transformer T201 Oil temperature very high - Trip
49-1 WSAT Station Aux.Transformer T201 Winding Temperature high - Alarm
49-2 WSAT Station Aux.Transformer T201 Winding Temperature very high - Trip
71 SAT
Station Aux.Transformer T201 Low Oil Level - Alarm
63 P SAT Station Aux.Transformer T201 Pressure Relief Device operated - Trip
51G LV
Station Aux.Transformer T201 Neutral Ground Fault protection operated
51G LV
Station Aux.Transformer T201 Neutral Ground Fault relay faulty
50/51
Station Aux.Transformer T201 HV BKR INST/ Inverse Time O/C Phase-A operated
50/51
Station Aux.Transformer T201 HV BKR INST/ Inverse Time O/C Phase-B operated
50/51
Station Aux.Transformer T201 HV BKR INST/ Inverse Time O/C Phase-C operated
50N/51N
50/51N
50G

Station Aux.Transformer T201 HV BKR INST/ Inverse Time Ground fault protection operated
Station Aux.Transformer T201 HV BKR INST/ Inverse Time O/C, E/F relay faulty.
Station Aux.Transformer T201 HV BKR CBCT protection operated

9 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271

Alarm
code

Tag No
86 B209
74/86
86 A101
74/86
74 TC
74 DC
51
51
51
51N
51/51N

List of Digital Signals for SOER


Station Aux.Transformer T201 HV BKR Lockout relay operated
Station Aux.Transformer T201 HV BKR Lockout relay supervision relay operated
Station Aux.Transformer T201 LV BKR Lockout relay operated
Station Aux.Transformer T201 LV BKR Lockout relay supervision relay operated
Station Aux.Transformer T201 LV BKR Trip coil supervision relay operated
Station Aux.Transformer T201 LV BKR DC supply supervision relay operated
Station Aux.Transformer T201 LV BKR inverse time O/C Phase -A operated
Station Aux.Transformer T201 LV BKR inverse time O/C Phase -B operated
Station Aux.Transformer T201 LV BKR inverse time O/C Phase -C operated
Station Aux.Transformer T201 LV BKR inverse time earthfault relay operated
Station Aux.Transformer T201 LV BKR inverse time O/C, E/F relay faulty
Maintenance switch open
K
Station Auxiliary Transformer SAT T202
63-1 SAT Station Aux.Transformer T202 Buchholz relay alarm operated
63-2 SAT Station Aux.Transformer T202 Buchholz relay Trip operated
49-1 OSAT Station Aux.Transformer T202 Oil temperature high - Alarm
49-2 OSAT Station Aux.Transformer T202 Oil temperature very high - Trip
49-1 WSAT Station Aux.Transformer T202 Winding Temperature high - Alarm
49-2 WSAT Station Aux.Transformer T202 Winding Temperature very high - Trip
71 SAT
Station Aux.Transformer T202 Low Oil Level - Alarm
63 P SAT Station Aux.Transformer T202 Pressure Relief Device operated - Trip
51G LV
Station Aux.Transformer T202 Neutral Ground Fault protection operated
51G LV
Station Aux.Transformer T202 Neutral Ground Fault relay faulty
50/51
Station Aux.Transformer T202 HV BKR INST/ Inverse Time O/C Phase-A operated
50/51
Station Aux.Transformer T202 HV BKR INST/ Inverse Time O/C Phase-B operated
50/51
Station Aux.Transformer T202 HV BKR INST/ Inverse Time O/C Phase-C operated
50N/51N
50/51N
50G
86 B213
74/86
86 A102

Station Aux.Transformer T202 HV BKR INST/ Inverse Time Ground fault protection operated
Station Aux.Transformer T202 HV BKR INST/ Inverse Time O/C, E/F relay faulty.
Station Aux.Transformer T202 HV BKR CBCT protection operated
Station Aux.Transformer T202 HV BKR Lockout relay operated
Station Aux.Transformer T202 HV BKR Lockout relay supervision relay operated
Station Aux.Transformer T202 LV BKR Lockout relay operated

10 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302

Alarm
code

Tag No
74/86
74 TC
74 DC
51
51
51
51N
51/51N

List of Digital Signals for SOER


Station Aux.Transformer T202 LV BKR Lockout relay supervision relay operated
Station Aux.Transformer T202 LV BKR Trip coil supervision relay operated
Station Aux.Transformer T202 LV BKR DC supply supervision relay operated
Station Aux.Transformer T202 LV BKR inverse time O/C Phase -A operated
Station Aux.Transformer T202 LV BKR inverse time O/C Phase -B operated
Station Aux.Transformer T202 LV BKR inverse time O/C Phase -C operated
Station Aux.Transformer T202 LV BKR inverse time earthfault relay operated
Station Aux.Transformer T202 LV BKR inverse time O/C, E/F relay faulty
Maintenance switch open
L
Station Auxiliary Transformer SAT T203(Future)
63-1 SAT Station Aux.Transformer T203 Buchholz relay alarm operated
63-2 SAT Station Aux.Transformer T203 Buchholz relay Trip operated
49-1 OSAT Station Aux.Transformer T203 Oil temperature high - Alarm
49-2 OSAT Station Aux.Transformer T203 Oil temperature very high - Trip
49-1 WSAT Station Aux.Transformer T203 Winding Temperature high - Alarm
49-2 WSAT Station Aux.Transformer T203 Winding Temperature very high - Trip
71 SAT
Station Aux.Transformer T203 Low Oil Level - Alarm
63 P SAT Station Aux.Transformer T203 Pressure Relief Device operated - Trip
51G LV
Station Aux.Transformer T203 Neutral Ground Fault protection operated
51G LV
Station Aux.Transformer T203 Neutral Ground Fault relay faulty
50/51
Station Aux.Transformer T203 HV BKR INST/ Inverse Time O/C Phase-A operated
50/51
Station Aux.Transformer T203 HV BKR INST/ Inverse Time O/C Phase-B operated
50/51
Station Aux.Transformer T203 HV BKR INST/ Inverse Time O/C Phase-C operated
50N/51N
50/51N
50G
86 B213
74/86
86 A102
74/86
74 TC
74 DC

Station Aux.Transformer T203 HV BKR INST/ Inverse Time Ground fault protection operated
Station Aux.Transformer T203 HV BKR INST/ Inverse Time O/C, E/F relay faulty.
Station Aux.Transformer T203 HV BKR CBCT protection operated
Station Aux.Transformer T203 HV BKR Lockout relay operated
Station Aux.Transformer T203 HV BKR Lockout relay supervision relay operated
Station Aux.Transformer T203 LV BKR Lockout relay operated
Station Aux.Transformer T203 LV BKR Lockout relay supervision relay operated
Station Aux.Transformer T203 LV BKR Trip coil supervision relay operated
Station Aux.Transformer T203 LV BKR DC supply supervision relay operated

11 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
303
304
305
306
307
308

Alarm
code

Tag No
51
51
51
51N
51/51N

309
310
311
312
313
314
315
316
317
318
319
320

M
63-1 ST
63-2 ST
49-1 OST
49-2 OST
49-1 WST
49-2 WST
71 ST
63 PST
63 OLTC
27
50N/51N
87REF LV

321

50/51P

322

50/51P

323

50/51P

324
325
326
327
328
329

50/51S
50N/51NP
50N/51NS
87T T401
87T T401
87T T401

List of Digital Signals for SOER


Station Aux.Transformer T203 LV BKR inverse time O/C Phase -A operated
Station Aux.Transformer T203 LV BKR inverse time O/C Phase -B operated
Station Aux.Transformer T203 LV BKR inverse time O/C Phase -C operated
Station Aux.Transformer T203 LV BKR inverse time earthfault relay operated
Station Aux.Transformer T203 LV BKR inverse time O/C, E/F relay faulty
Maintenance switch open
Station Transformer ST T401
Station Transformer T401 Buchholz relay alarm operated
Station Transformer T401 Buchholz relay Trip operated
Station Transformer T401 Oil temperature high - Alarm
Station Transformer T401 Oil temperature very high - Trip
Station Transformer T401 Winding Temperature high - Alarm
Station Transformer T401 Winding Temperature very high - Trip
Station Transformer T401 Low Oil Level - Alarm
Station Transformer T401 Pressure Relief Device operated - Trip
Station Transformer T401 OLTC Buchholz trip
Station Transformer T401 Tap changer device failure alarm
Station Transformer T401 Neutral Ground fault protection operated
Station Transformer T401 REF protection operated
Station Transformer T401 HV BKR INST/Inverse Time Over current primary
protection(Phase A) operated
Station Transformer T401 HV BKR INST/Inverse Time Over current primary
protection(Phase B) operated
Station Transformer T401 HV BKR INST/Inverse Time Over current primary
protection(Phase C) operated
Station Transformer T401 HV BKR INST/Inverse Time Over current secondary protection
operated
Station Transformer T401 HV BKR Ground fault primary protection operated
Station Transformer T401 HV BKR Ground fault secondary protection operated
Station Transformer T401 Differential Protection(Phase-A) operated
Station Transformer T401 Differential Protection(Phase-B) operated
Station Transformer T401 Differential Protection(Phase-C) operated

12 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360

Alarm
code

Tag No
2/50 BF
50 BF
86-1 T401
86-2 T401
86-3 T401
74/86-1
74/86-2
74/86-3
74 TC-1
74 TC-2
86-1 B413
86-2 B413
74/86-1
74/86-2
74 DC-1
74 DC-2
67
67
67
67N
86 A204
74/86
74 TC-1
74 TC-2
74 DC-1
74 DC-2

List of Digital Signals for SOER


Station Transformer T401 HV side Breaker failure protection Timer operated -I stage Alarm
Station Transformer T401 HV side Breaker failure relay operated -II stage
Station Transformer T401 Lockout relay-1 operated
Station Transformer T401 Lockout relay-2 operated
Station Transformer T401 Lockout relay-3 operated
Station Transformer T401 Lockout relay-1 supervision relay operated
Station Transformer T401 Lockout relay-2 supervision relay operated
Station Transformer T401 Lockout relay-3 supervision relay operated
Station Transformer T401 HV BKRTrip Coil-1 Supervision relay operated
Station Transformer T401 HV BKRTrip Coil-2 Supervision relay operated
Station Transformer T401 HV BKR Lockout relay -1 operated
Station Transformer T401 HV BKR Lockout relay -2 operated
Station Transformer T401 HV BKR Lockout relay-1 supervision relay operated
Station Transformer T401 HV BKR Lockout relay-2 supervision relay operated
Station Transformer T401 HV BKR DC supply-1 supervision operated
Station Transformer T401 HV BKR DC supply-2 supervision operated
Station Transformer T401 LV BKR Directional Over current protection(Phase-A) operated
Station Transformer T401 LV BKR Directional Over current protection(Phase-B) operated
Station Transformer T401 LV BKR Directional Over current protection(Phase-C) operated
Station Transformer T401 LV BKR Directional earth fault protection operated
Station Transformer T401 LV BKR Lockout relay operated
Station Transformer T401 LV BKR Lockout relay supervision relay operated
Station Transformer T401 LV BKR tripcoil-1 supervision operated
Station Transformer T401 LV BKR tripcoil-2 supervision operated
Station Transformer T401 LV BKR DC supply-1 supervision operated
Station Transformer T401 LV BKR DC supply-2 supervision operated
OLTC pressure relief device operated
OLTC protection relay operated
OLTC Low oil level alarm
Transformer membrane failure alarm
Maintenance switch open
Station Transformer ST 402

13 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
361
362
363
364
365
366
367
368
369
370
371
372

Alarm
code

Tag No
63-1 ST
63-2 ST
49-1 OST
49-2 OST
49-1 WST
49-2 WST
71 ST
63 PST
63 OLTC
27
50N/51N
87REF LV

373

50/51P

374

50/51P

375

50/51P

376
377
378
379
380
381
382
383
384
385
386
387
388
389

50/51S
50N/51NP
50N/51NS
87T T402
87T T402
87T T402
2/50 BF
50 BF
86-1 T402
86-2 T402
86-3 T402
74/86-1
74/86-2
74/86-3

List of Digital Signals for SOER


Remarks
Station Transformer T402 Buchholz relay alarm operated
Station Transformer T402 Buchholz relay Trip operated
Station Transformer T402 Oil temperature high - Alarm
Station Transformer T402 Oil temperature very high - Trip
Station Transformer T402 Winding Temperature high - Alarm
Station Transformer T402 Winding Temperature very high - Trip
Station Transformer T402 Low Oil Level - Alarm
Station Transformer T402 Pressure Relief Device operated - Trip
Station Transformer T402 OLTC Buchholz trip
Station Transformer T402 Tap changer device failure alarm
Station Transformer T402 Neutral Ground Over Current protection operated
Station Transformer T402 REF protection operated
Station Transformer T402 HV BKR INST/Inverse Time Over current primary
protection(Phase A) operated
Station Transformer T402 HV BKR INST/Inverse Time Over current primary
protection(Phase B) operated
Station Transformer T402 HV BKR INST/Inverse Time Over current primary
protection(Phase C) operated
Station Transformer T402 HV BKR IDMT/Inverse Time Over current secondary protection
operated
Station Transformer T402 HV BKR Ground fault Overcurrent primary protection operated
Station Transformer T402 HV BKR Ground fault Overcurrent secondary protection operated
Station Transformer T402 Differential Protection(Phase-A) operated
Station Transformer T402 Differential Protection(Phase-B) operated
Station Transformer T402 Differential Protection(Phase-C) operated
Station Transformer T402 HV side Breaker failure protection Timer operated -I stage Alarm
Station Transformer T402 HV side Breaker failure relay operated -Iistage
Station Transformer T402 Lockout relay-1 operated
Station Transformer T402 Lockout relay-2 operated
Station Transformer T402 Lockout relay-3 operated
Station Transformer T402 Lockout relay-1 supervision relay operated
Station Transformer T402 Lockout relay-2 supervision relay operated
Station Transformer T402 Lockout relay-3 supervision relay operated

14 of 35

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421

Alarm
code

Tag No
74 TC-1
74 TC-2
86-1 B422
86-2 B422
74/86-1
74/86-2
74 DC-1
74 DC-2
67
67
67
67N
86 A204
74/86
74 TC-1
74 TC-2
74 DC-1
74 DC-2

O
63-1 IT
63-2 IT
49-1 OIT
49-2 OIT
49-1 WIT
49-2 WIT
71 IT
63 PIT
51N

List of Digital Signals for SOER


Station Transformer T402 HV BKRTrip Coil-1 Supervision relay operated
Station Transformer T402 HV BKRTrip Coil-2 Supervision relay operated
Station Transformer T402 HV BKR Lockout relay -1 operated
Station Transformer T402 HV BKR Lockout relay -2 operated
Station Transformer T402 HV BKR Lockout relay-1 supervision relay operated
Station Transformer T402 HV BKR Lockout relay-2 supervision relay operated
Station Transformer T402 HV BKR DC supply-1 supervision operated
Station Transformer T402 HV BKR DC supply-2 supervision operated
Station Transformer T402 LV BKR Directional Over current protection(Phase-A) operated
Station Transformer T402 LV BKR Directional Over current protection(Phase-B) operated
Station Transformer T402 LV BKR Directional Over current protection(Phase-C) operated
Station Transformer T402 LV BKR Directional earth fault protection operated
Station Transformer T402 LV BKR Lockout relay operated
Station Transformer T402 LV BKR Lockout relay supervision relay operated
Station Transformer T402 LV BKR tripcoil-1 supervision operated
Station Transformer T402 LV BKR tripcoil-2 supervision operated
Station Transformer T402 LV BKR DC supply-1 supervision operated
Station Transformer T402 LV BKR DC supply-2 supervision operated
OLTC pressure relief device operated
OLTC protection relay operated
OLTC Low oil level alarm
Transformer membrane failure alarm
Maintenance switch open
Interbus Transformer T-501
Interbus Transformer T501 Buchholz relay alarm operated
Interbus Transformer T501 Buchholz relay Trip operated
Interbus Transformer T501 Oil temperature high - Alarm
Interbus Transformer T501 Oil temperature very high - Trip
Interbus Transformer T501 Winding Temperature high - Alarm
Interbus Transformer T501 Winding Temperature very high - Trip
Interbus Transformer T501 Low Oil Level - Alarm
Interbus Transformer T501 Pressure Relief Device operated - Trip
Interbus Transformer T501 33kV side Neutral Ground Over Current protection operated

15 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
422
423
424
425
426
427

Alarm
code

Tag No
51N
87REF HV
87REF LV
87 T
87 T
87 T

428

50/51

429

50/51

430
431
432
433
434
435
436
437
438
439
440
441
442
443
444

50/51
50N/51N
2/50 BF
50 BF
86-1 B411
86-2 B411
74/86
74/86
74 TC-1
74 TC-1
74 DC-1
74 DC-2

445
446
447
448
449
450

P
63-1 IT
63-2 IT
49-1 OIT
49-2 OIT
49-1 WIT
49-2 WIT

List of Digital Signals for SOER


Remarks
Interbus Transformer T501 13.8kV side Neutral ground over current protection operated
Interbus Transformer T501 33kV Side Restricted earth fault protection operated
Interbus Transformer T501 13.8kV Side Restricted earth fault protection operated
Interbus Transformer T501 Differential Protection Phase-A operated (87T)
Interbus Transformer T501 Differential Protection Phase-B operated (87T)
Interbus Transformer T501 Differential Protection Phase-C operated (87T)
Interbus Transformer T501 33kV Side INST/Inverse Time Over current protection Phase-A
operated
Interbus Transformer T501 33kV Side INST/Inverse Time Over current protection Phase-B
operated
Interbus Transformer T501 33kV Side INST/Inverse Time Over current protection Phase-C
operated
Interbus Transformer T501 33kV Side INST/Inverse Time Ground fault protection operated
Interbus Transformer T501 33kV side Breaker failure Protection Timer operated -I stage Alarm
Interbus Transformer T501 33kV side Breaker failure relay operated -IIstage
Interbus Transformer T501 33kV Side Breaker Lockout relay-1 operated
Interbus Transformer T501 33kV Side Breaker Lockout relay-2 operated
Interbus Transformer T501 33kV Side Breaker Lockout relay supervision relay-1 operated
Interbus Transformer T501 33kV Side Breaker Lockout relay supervision relay-2 operated
Interbus Transformer T501 33kV Side BreakerTrip Coil-1 Supervision relay operated
Interbus Transformer T501 33kV Side BreakerTrip Coil-2 Supervision relay operated
Interbus Transformer T501 33kV Side DC Supply -1 Failure/Supervision relay operated
Interbus Transformer T502 33kV Side DC Supply -2 Failure/Supervision relay operated
Transformer membrane failure alarm
Maintenance switch open
Cooling failure alarm
Interbus Transformer T-502
Interbus Transformer T502 Buchholz relay alarm operated
Interbus Transformer T502 Buchholz relay Trip operated
Interbus Transformer T502 Oil temperature high - Alarm
Interbus Transformer T502 Oil temperature very high - Trip
Interbus Transformer T502 Winding Temperature high - Alarm
Interbus Transformer T502 Winding Temperature very high - Trip

16 of 35

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
451
452
453
454
455
456
457
458
459

Alarm
code

Tag No
71 IT
63 PIT
51N
51N
87REF HV
87REF LV
87 T
87 T
87 T

460

50/51

461

50/51

462
463
464
465
466
467
468
469
470
471
472
473
474
475
476

50/51
50N/51N
2/50 BF
50 BF
86-1 B423
86-2 B423
74/86
74/86
74 TC-1
74 TC-1
74 DC-1
74 DC-2

477
478
479

Q
63-1 IT
63-2 IT
49-1 OIT

List of Digital Signals for SOER


Remarks
Interbus Transformer T502 Low Oil Level - Alarm
Interbus Transformer T502 Pressure Relief Device operated - Trip
Interbus Transformer T502 33kV side Neutral Ground Over Current protection operated
Interbus Transformer T502 13.8kV side Neutral ground over current protection operated
Interbus Transformer T502 33kV Side Restricted earth fault protection operated
Interbus Transformer T502 13.8kV Side Restricted earth fault protection operated
Interbus Transformer T502 Differential Protection Phase-A operated (87T)
Interbus Transformer T502 Differential Protection Phase-B operated (87T)
Interbus Transformer T502 Differential Protection Phase-C operated (87T)
Interbus Transformer T502 33kV Side INST/Inverse Time Over current protection Phase-A
operated
Interbus Transformer T502 33kV Side INST/Inverse Time Over current protection Phase-B
operated
Interbus Transformer T502 33kV Side INST/Inverse Time Over current protection Phase-C
operated
Interbus Transformer T502 33kV Side INST/Inverse Time Ground fault protection operated
Interbus Transformer T502 33kV side Breaker failure Protection Timer operated -I stage Alarm
Interbus Transformer T502 33kV side Breaker failure relay operated -IIstage
Interbus Transformer T502 33kV Side Breaker Lockout relay-1 operated
Interbus Transformer T502 33kV Side Breaker Lockout relay-2 operated
Interbus Transformer T502 33kV Side Breaker Lockout relay supervision relay-1 operated
Interbus Transformer T502 33kV Side Breaker Lockout relay supervision relay-2 operated
Interbus Transformer T502 33kV Side BreakerTrip Coil-1 Supervision relay operated
Interbus Transformer T502 33kV Side BreakerTrip Coil-2 Supervision relay operated
Interbus Transformer T502 33kV Side DC Supply -1 Failure/Supervision relay operated
Interbus Transformer T502 33kV Side DC Supply -2 Failure/Supervision relay operated
Transformer membrane failure alarm
Maintenance switch open
Cooling failure alarm
Interbus Transformer T-503
Interbus Transformer T503 Buchholz relay alarm operated
Interbus Transformer T503 Buchholz relay Trip operated
Interbus Transformer T503 Oil temperature high - Alarm

17 of 35

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
480
481
482
483
484
485
486
487
488
489
490
491

Alarm
code

Tag No
49-2 OIT
49-1 WIT
49-2 WIT
71 IT
63 PIT
51N
51N
87REF HV
87REF LV
87 T
87 T
87 T

492

50/51

493

50/51

494
495
496
497
498
499
500
501
502
503
504
505
506
507
508

50/51
50N/51N
2/50 BF
50 BF
86-1 B424
86-2 B424
74/86
74/86
74 TC-1
74 TC-1
74 DC-1
74 DC-2

List of Digital Signals for SOER


Remarks
Interbus Transformer T503 Oil temperature very high - Trip
Interbus Transformer T503 Winding Temperature high - Alarm
Interbus Transformer T503 Winding Temperature very high - Trip
Interbus Transformer T503 Low Oil Level - Alarm
Interbus Transformer T503 Pressure Relief Device operated - Trip
Interbus Transformer T503 33kV side Neutral Ground Over Current protection operated
Interbus Transformer T503 13.8kV side Neutral ground over current protection operated
Interbus Transformer T503 33kV Side Restricted earth fault protection operated
Interbus Transformer T503 13.8kV Side Restricted earth fault protection operated
Interbus Transformer T503 Differential Protection Phase-A operated (87T)
Interbus Transformer T503 Differential Protection Phase-B operated (87T)
Interbus Transformer T503 Differential Protection Phase-C operated (87T)
Interbus Transformer T503 33kV Side INST/Inverse Time Over current protection Phase-A
operated
Interbus Transformer T503 33kV Side INST/Inverse Time Over current protection Phase-B
operated
Interbus Transformer T503 33kV Side INST/Inverse Time Over current protection Phase-C
operated
Interbus Transformer T503 33kV Side INST/Inverse Time Ground fault protection operated
Interbus Transformer T503 33kV side Breaker failure Protection Timer operated -I stage Alarm
Interbus Transformer T503 33kV side Breaker failure relay operated -IIstage
Interbus Transformer T503 33kV Side Breaker Lockout relay-1 operated
Interbus Transformer T503 33kV Side Breaker Lockout relay-2 operated
Interbus Transformer T503 33kV Side Breaker Lockout relay supervision relay-1 operated
Interbus Transformer T503 33kV Side Breaker Lockout relay supervision relay-2 operated
Interbus Transformer T503 33kV Side BreakerTrip Coil-1 Supervision relay operated
Interbus Transformer T503 33kV Side BreakerTrip Coil-2 Supervision relay operated
Interbus Transformer T503 33kV Side DC Supply -1 Failure/Supervision relay operated
Interbus Transformer T503 33kV Side DC Supply -2 Failure/Supervision relay operated
Transformer membrane failure alarm
Maintenance switch open
Cooling failure alarm
Interbus Transformer (Future)

18 of 35

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
509
510
511
512
513
514
515
516
517
518
519
520
521
522
523

Alarm
code

Tag No
63-1 IT
63-2 IT
49-1 OIT
49-2 OIT
49-1 WIT
49-2 WIT
71 IT
63 PIT
51N
51N
87REF HV
87REF LV
87 T
87 T
87 T

524

50/51

525

50/51

526
527
528
529
530
531
532
533
534
535
536
537
538

50/51
50N/51N
2/50 BF
50 BF
86-1 B412
86-2 B412
74/86
74/86
74 TC-1
74 TC-1
74 DC-1
74 DC-2

List of Digital Signals for SOER


Remarks
Interbus Transformer T504 Buchholz relay alarm operated
Interbus Transformer T504 Buchholz relay Trip operated
Interbus Transformer T504 Oil temperature high - Alarm
Interbus Transformer T504 Oil temperature very high - Trip
Interbus Transformer T504 Winding Temperature high - Alarm
Interbus Transformer T504 Winding Temperature very high - Trip
Interbus Transformer T504 Low Oil Level - Alarm
Interbus Transformer T504 Pressure Relief Device operated - Trip
Interbus Transformer T504 33kV side Neutral Ground Over Current protection operated
Interbus Transformer T504 13.8kV side Neutral ground over current protection operated
Interbus Transformer T504 33kV Side Restricted earth fault protection operated
Interbus Transformer T504 13.8kV Side Restricted earth fault protection operated
Interbus Transformer T504 Differential Protection Phase-A operated (87T)
Interbus Transformer T504 Differential Protection Phase-B operated (87T)
Interbus Transformer T504 Differential Protection Phase-C operated (87T)
Interbus Transformer T504 33kV Side INST/Inverse Time Over current protection Phase-A
operated
Interbus Transformer T504 33kV Side INST/Inverse Time Over current protection Phase-B
operated
Interbus Transformer T504 33kV Side INST/Inverse Time Over current protection Phase-C
operated
Interbus Transformer T504 33kV Side INST/Inverse Time Ground fault protection operated
Interbus Transformer T504 33kV side Breaker failure Protection Timer operated -I stage Alarm
Interbus Transformer T504 33kV side Breaker failure relay operated -IIstage
Interbus Transformer T504 33kV Side Breaker Lockout relay-1 operated
Interbus Transformer T504 33kV Side Breaker Lockout relay-2 operated
Interbus Transformer T504 33kV Side Breaker Lockout relay supervision relay-1 operated
Interbus Transformer T504 33kV Side Breaker Lockout relay supervision relay-2 operated
Interbus Transformer T504 33kV Side BreakerTrip Coil-1 Supervision relay operated
Interbus Transformer T504 33kV Side BreakerTrip Coil-2 Supervision relay operated
Interbus Transformer T504 33kV Side DC Supply -1 Failure/Supervision relay operated
Interbus Transformer T504 33kV Side DC Supply -2 Failure/Supervision relay operated
Transformer membrane failure alarm

19 of 35

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
539
540
541

Alarm
code

Tag No

S
542

87 FDR-1

543

87 FDR-1

544

87 FDR-1

545

87 FDR-2

546

87 FDR-2

547

87 FDR-2

548

67

549

67

550

67

551

67N

552

67

553

67

554

67

555

67N

List of Digital Signals for SOER


Remarks
Maintenance switch open
Cooling failure alarm
BFR circuit supervision (74 DC-1) operated
33kV Switchgear
33kV Tie feeder Differential protection phase -A operated (breaker at new 33kV Switchgear
side)
33kV Tie feeder Differential protection phase -B operated (breaker at new 33kV Switchgear
side)
33kV Tie feeder Differential protection phase -C operated (breaker at new 33kV Switchgear
side)
33kV Tie feeder Differential protection phase-A operated (breaker at existing 33kV
Switchgear side)
33kV Tie feeder Differential protection phase-B operated (breaker at existing 33kV
Switchgear side)
33kV Tie feeder Differential protection phase-C operated (breaker at existing 33kV
Switchgear side)
33kV Tie feeder Directional overcurrent protection Phase-A operated (breaker at new 33kV
Switchgear side)
33kV Tie feeder Directional overcurrent protection Phase-B operated (breaker at new 33kV
Switchgear side)
33kV Tie feeder Directional overcurrent protection Phase-C operated (breaker at new 33kV
Switchgear side)
33kV Tie feeder Directional ground fault overcurrent protection operated (breaker at new
33kV Switchgear side)
33kV Tie feeder Directional overcurrent protection phase-A operated (breaker at existing
33kV Switchgear side)
33kV Tie feeder Directional overcurrent protection phase-A operated (breaker at existing
33kV Switchgear side)
33kV Tie feeder Directional overcurrent protection phase-A operated (breaker at existing
33kV Switchgear side)
33kV Tie feeder Directional ground fault overcurrent protection operated (breaker at existing
33kV Switchgear side)

20 of 35

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No

Alarm
code

Tag No

556

2/50 BF

557

50 BF

558

2/50 BF

559
560
561

50 BF
86 FDR-1
86 FDR-2

562
563
564
565
566
567
568
569
570
571
572
573
574

List of Digital Signals for SOER


Remarks
33kV Tie feeder bkr.failure protection timer operated- Istage Alarm (breaker at new 33kV
Switchgear side)
33kV Tie feeder bkr.failure protection relay operated-IIstage (breaker at new 33kV
Switchgear side)
33kV Tie feeder bkr.failure protection timer operated- Istage Alarm (breaker at existing 33kV
Switchgear side)
33kV Tie feeder bkr.failure protection relay operated-IIstage (breaker at existing 33kV
Switchgear side)
33kV Tie feeder breaker lockout relay operted (breaker at new 33kV Switchgear side)
33kV Tie feeder breaker lockout relay operated (breaker at existing 33kV Switchgear side)

33kV Tie feeder breaker Lockout relay supervision relay operated (breaker at new 33kV
74/86 FDR-1 Switchgear side)
33kV Tie feeder breaker Lockout relay supervision relay operated (breaker at existing 33kV
74/86 FDR-2 Switchgear side)
33kV Tie feeder breaker trip coil-1 supervision relay operated (breaker at new 33kV
74 TC-1
Switchgear side)
33kV Tie feeder breaker trip coil-2 supervision relay operarted (breaker at new 33kV
74 TC-2
Switchgear side)
33kV Tie feeder breaker DC supply failure-1 relay operarted (breaker at new 33kV
74 DC-1
Switchgear side)
33kV Tie feeder breaker DC supply failure-2 relay operarted (breaker at new 33kV
74 DC-2
Switchgear side)
33kV Tie feeder breaker trip coil-1 supervision relay operated (breaker at existing 33kV
74 TC-1
Switchgear side)
33kV Tie feeder breaker trip coil-2 supervision relay operarted (breaker at existing 33kV
74 TC-2
Switchgear side)
33kV Tie feeder breaker DC supply failure-1 relay operarted (breaker at existing 33kV
74 DC-1
Switchgear side)
33kV Tie feeder breaker DC supply failure-2 relay operarted (breaker at existing 33kV
74 DC-2
Switchgear side)
87 B1
33kV Switchgear Bus Section-1 Busbar protection phase-A operated (87B1)
87 B1
33kV Switchgear Bus Section-1 Busbar protection phase-B operated (87B1)
87 B1
33kV Switchgear Bus Section-1 Busbar protection phase-C operated (87B1)

21 of 35

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
575

Alarm
code

Tag No
86 B1

List of Digital Signals for SOER


33kV Switchgear Bus Section-1 Busbar protection lockout relay operated

576

74/86

33kV Switchgear Bus Section-1 Busbar protection lockout relay supervision relay operated
33kV SWGR Bus-1 BB protection CT supervision with shorting lockout Relay (95BX)
operated
33kV Switchgear Bus Section-2 Busbar protection Phase A operated (87B2)
33kV Switchgear Bus Section-2 Busbar protection Phase B operated (87B2)
33kV Switchgear Bus Section-2 Busbar protection Phase C operated (87B2)
33kV Switchgear Bus Section-2 Busbar protection lockout relay operated

577
578
579
580
581

95BX
87 B2
87 B2
87 B2
86 B2

582

74/86

583

95BX

33kV Switchgear Bus Section-2 Busbar protection lockout relay supervision relay operated
33kV SWGR Bus-2 BB protection CT supervision with shorting lockout Relay (95BX)
operated

584

87 CH-1

33kV Switchgear Bus Section-1 Busbar protection check zone Phase A operated (87CH-1)

585

87 CH-1

33kV Switchgear Bus Section-1 Busbar protection check zone Phase B operated (87CH-1)

586
587

87 CH-1
86 CH-1

588

74/86

589

95BX

33kV Switchgear Bus Section-1 Busbar protection check zone Phase C operated (87CH-1)
33kV Switchgear Bus Section-1 Busbar protection check zone lockout relay operated
33kV Switchgear Bus Section-1 Busbar protection check zone lockout relay supervision
relay operated
33kV SWGR Bus-1 BB protection check zone CT supervision with shorting lockout Relay
(95BX) operated

590

87 CH-2

33kV Switchgear Bus Section-2 Busbar protection check zone Phase A operated (87CH-2)

591

87 CH-2

33kV Switchgear Bus Section-2 Busbar protection check zone Phase B operated (87CH-2)

592
593

87 CH-2
86 CH-2

594

74/86

33kV Switchgear Bus Section-2 Busbar protection check zone Phase C operated (87CH-2)
33kV Switchgear Bus Section-2 Busbar protection check zone lockout relay operated
33kV Switchgear Bus Section-2 Busbar protection check zone lockout relay supervision
relay operated

22 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
595
596
597
598
599
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616
617
618
619
620
621
622
623
624
625
626

Alarm
code

Tag No
95BX
51
51
51
51N
86 A403
74/86
74 TC-1
74 TC-2
T
87 B1
87 B1
87 B1
87 B2
87 B2
87 B2
51
51
51
51N
95B1
95B1
95B1
95B2
95B2
95B2
95BX1
95BX2
86B1
86B2
74/86B1
74/86B2
86 A208

List of Digital Signals for SOER


33kV SWGR Bus-2 BB protection check zone CT shorting lockout Relay (95BX) operated
33kV Bus Section breaker Inverse time over current protection phase-A operated (51)
33kV Bus Section breaker Inverse time over current protection phase-B operated (51)
33kV Bus Section breaker Inverse time over current protection phase-C operated (51)
33kV Bus Section breaker inverse time Ground fault protection operated
33kV Bus section breaker Lockout relay operated
33kV Bus section breaker Lockout relay supervision relay operated
33kV Bus section breaker Trip coil-1 supervision relay operated.
33kV Bus Section breaker trip coil-2 supervision relay operated
4.16kV Switchgear
4.16kV Switchgear Bus Section-1 Busbar protection Phase-A operated
4.16kV Switchgear Bus Section-1 Busbar protection Phase-B operated
4.16kV Switchgear Bus Section-1 Busbar protection Phase-C operated
4.16kV Switchgear Bus Section-2 Busbar protection Phase-A operated
4.16kV Switchgear Bus Section-2 Busbar protection Phase-B operated
4.16kV Switchgear Bus Section-2 Busbar protection Phase-C operated
4.16kV Bus Section breaker Inverse time over current protection Phase-A operated
4.16kV Bus Section breaker Inverse time over current protection Phase-B operated
4.16kV Bus Section breaker Inverse time over current protection Phase-C operated
4.16kV Bus Section breaker Ground fault protection operated
4.16kV SWGR Busbar-1 CT supervision relay(95B1) phase-A operated
4.16kV SWGR Busbar-1 CT supervision relay(95B1) phase-B operated
4.16kV SWGR Busbar-1 CT supervision relay(95B1) phase-C operated
4.16kV SWGR Busbar-2 CT supervision relay(95B2) phase-A operated
4.16kV SWGR Busbar-2 CT supervision relay(95B2) phase-B operated
4.16kV SWGR Busbar-2 CT supervision relay(95B2) phase-C operated
4.16kV SWGR Bus-1 BB protection CT shorting lockout Relay (95BX1) operated
4.16kV SWGR Bus-2 BB protection CT shorting lockout Relay (95BX2) operated
4.16 SWGR BB-1 Protection lock relay operated
4.16 SWGR BB-2 Protection lock relay operated
4.16 SWGR BB-1 lock relay coil supervision 74/86B1 operated.
4.16 SWGR BB-2 lock relay coil supervision 74/86B2 operated.
4.16kV Bus section breaker Lockout relay operated

23 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
627
628
629
630
631
632
633

Alarm
code

Tag No
74/86
74 DC-1
74 DC-2
74 TC-1
74 TC-2
27
27

List of Digital Signals for SOER


4.16kV Bus section breaker Lockout supervision relay operated
4.16kV Bus section breaker DC supply-1 failure relay operated.
4.16kV Bus section breaker DC supply-2 failure relay operated.
4.16kV Bus Section breaker trip coil-1 supervision relay operated
4.16kV Bus Section breaker trip coil-2 supervision relay operated
4.16 kV SWGR Bus-1 UV trip lockout relay(27/UV) operated
4.16 kV SWGR Bus-2 UV trip lockout relay(27/UV) operated

634
635
636
637
638
639
640
641
642
643
644
645
646
647
648

STM
50M/51M
50M/51M
50M/51M
50M/51M
50G
86M
74 TC-1
74 TC-2
74/86
49-1B
49-2B
49A
WTI A
WTI TRIP

GTG-1 Starting motor protection relay operated


GTG-1 starting motor feeder O/C Phase-A operated
GTG-1 starting motor feeder O/C Phase-B operated
GTG-1 starting motor feeder O/C Phase-C operated
GTG-1 starting motor feeder O/C relay faulty
GTG-1 starting motor feeder CBCT fault protection operated
GTG-1 starting motor feeder breaker lockout relay operated
GTG-1 starting motor feeder breaker trip coil-1supervision relay operated
GTG-1 starting motor feeder breaker trip coil-2 supervision relay operated
GTG-1 starting motor feeder breaker lockout relay supervision relay operated
GTG-1 starting motor bearing temperature high alarm
GTG-1 starting motor bearing temperature very high trip
GTG-1 starting motor cooler failure
GTG-1 starting motor winding temperature high alarm
GTG-1 starting motor winding temperature very high trip

649
650
651
652
653
654
655
656
657

STM
50M/51M
50M/51M
50M/51M
50M/51M
50G
86M
74 TC-1
74 TC-2

GTG-2 Starting motor protection relay operated


GTG-2 starting motor feeder O/C Phase-A operated
GTG-2 starting motor feeder O/C Phase-B operated
GTG-2 starting motor feeder O/C Phase-C operated
GTG-2 starting motor feeder O/C relay faulty
GTG-2 starting motor feeder CBCT fault protection operated
GTG-2 starting motor feeder breaker lockout relay operated
GTG-2 starting motor feeder breaker trip coil-1supervision relay operated
GTG-2 starting motor feeder breaker trip coil-2 supervision relay operated

24 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
658
659
660
661
662
663
664
665
666
667
668
669
670
671
672
673
674
675
676
677
678
679
680
681
682
683
684
685
686
687
688

Alarm
code

Tag No
74/86
49-1B
49-2B
49A
WTI A
WTI TRIP

List of Digital Signals for SOER


GTG-2 starting motor feeder breaker lockout relay supervision relay operated
GTG-2 starting motor bearing temperature high alarm
GTG-2 starting motor bearing temperature very high trip
GTG-2 starting motor cooler failure
GTG-2 starting motor winding temperature high alarm
GTG-2 starting motor winding temperature very high trip

STM
50M/51M
50M/51M
50M/51M
50M/51M
50G
86M
74 TC-1
74 TC-2
74/86
49-1B
49-2B
49A
WTI A
WTI TRIP
U
51
51
51
51N
51
86 A103
74/86
74 DC
74 TC
27

Future GTG Starting motor protection relay operated


Future GTG starting motor feeder O/C Phase-A operated
Future GTG starting motor feeder O/C Phase-B operated
Future GTG starting motor feeder O/C Phase-C operated
Future GTG starting motor feeder O/C relay faulty
Future GTG starting motor feeder CBCT fault protection operated
Future GTG starting motor feeder breaker lockout relay operated
Future GTG starting motor feeder breaker trip coil-1supervision relay operated
Future GTG starting motor feeder breaker trip coil-2 supervision relay operated
Future GTG starting motor feeder breaker lockout relay supervision relay operated
Future GTG starting motor bearing temperature high alarm
Future GTG starting motor bearing temperature very high trip
Future GTG starting motor cooler failure
Future GTG starting motor winding temperature high alarm
Future GTG starting motor winding temperature very high trip
480V Station Switchgear
480V Bus Section breaker Inverse time O/C Phase-A operated
480V Bus Section breaker Inverse time O/C Phase-B operated
480V Bus Section breaker Inverse time O/C Phase-C operated
480V Bus Section breaker Inverse time E/F relay operated
480V Bus Section breaker Inverse time O/C, E/F Relay faulty
480V Bus section breaker Lockout relay operated
480V Bus section breaker Lockout relay Supervision relay operated
480V Bus section breaker DC supply failure relay operated
480V Bus Section breaker trip circuit supervision relay operated
480V Bus Section-1 UV trip lockout relay(27/UV) operated

25 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
689
690
691
692
693
694
695
696
697
698
699
700
701
702
703
704
705
706
707
708
709
710
711
712
713
714
715
716
717

Alarm
code

Tag No
27
V
50/51
51N
86 A201
74/86
74 DC
74 TC
W
50/51
51N
86 A202
74/86
74 DC
74 TC
X
50/51
51N
86 A203
74/86
74 DC
74 TC
Y
1
2
3
4
5
6
7
8
9
10

List of Digital Signals for SOER


480V Bus Section-2 UV trip lockout relay(27/UV) operated
480V Unit Switchgear of Unit-1
Unit Switchgear INST./ Inverse Time Over current protection operated
Unit Switchgear Ground fault protection operated
Unit Switchgear Breaker Lockout relay operated
Unit Switchgear Breaker Lockout relay Supervision relay operated
Unit Switchgear DC Supply Failure relay operated
Unit switchgear breaker trip circuit supervision relay operated
480V Unit Switchgear of Unit-2
Unit Switchgear INST./ Inverse Time Over current protection operated
Unit Switchgear Ground fault protection operated
Unit Switchgear Breaker Lockout relay operated
Unit Switchgear Breaker Lockout relay Supervision relay operated
Unit Switchgear DC Supply Failure relay operated
Unit switchgear breaker trip circuit supervision relay operated
480V Unit Switchgear of Future Unit
Unit Switchgear INST./ Inverse Time Over current protection operated
Unit Switchgear Ground fault protection operated
Unit Switchgear Breaker Lockout relay operated
Unit Switchgear Breaker Lockout relay Supervision relay operated
Unit Switchgear DC Supply Failure relay operated
Unit switchgear breaker trip circuit supervision relay operated
Fuel oil System
Unloading pump1 Trip
Unloading pump2 Trip
Unloading pump3 Trip
Unloading pump4 Trip
Unloading pump5 Trip(Future)
Unloading pump6 Trip(Future)
Forwarding pump1 Trip
Forwarding pump2 Trip
Forwarding pump3 Trip
Forwarding pump4 Trip

26 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
718
719
720
721
722
723
724
725
726
727
728
729
730
731
732
733
734
735
736
737
738
739
740
741
742
743
744
745
746
747

Alarm
code

Tag No
11
12
13
14
15
16
17
18
19
20
21
22
Z
1
2
3
4

5
6
7
AA
1
2
3
4
5
6
AB
59/81G1-1
59/81G1-2

List of Digital Signals for SOER


Level switch High High DFO Tank#1(FOS-10-LSHH-01)
Level switch High DFO Tank#1(FOS-10-LSH-02)
Level switch Low DFO Tank#1(FOS-10-LSL-03)
Level switch Low Low DFO Tank#1(FOS-10-LSLL-04)
Level switch High High DFO Tank#2(FOS-10-LSHH-05)
Level switch High DFO Tank#2(FOS-10-LSH-06)
Level switch Low DFO Tank#2(FOS-10-LSL-07)
Level switch Low Low DFO Tank#2(FOS-10-LSLL-08)
Spare
Spare
Spare
Spare
Fire Alarm System
Fire Alarm area-1(Switchgear room)
Fire Alarm area-2(Battery room)
Fire Alarm area-3(GT building)
Fire Alarm area-4( Transformer area)
i) Gen.Transformer 1&2
ii) InterbusTransformer 1
iii) InterbusTransformer 2&3
Fire Alarm area-5(Fuel Tank area)
Fire Alarm area-6(Control Room)
Spare
Compressor System
Compressor-1 Trip
Compressor-2 Trip
Compressor-3 Trip
Spare
Spare
Spare
GTG-1
Over Fluxing 1st step - Set 1
Over Fluxing 2nd step - Set 1

27 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
748
749
750
751
752
753
754
755
756
757
758
759
760
761
762
763
764
765
766
767
768
769
770
771
772
773
774
775
776
777
778
779

Alarm
code

Tag No
59/81G2-1
59/81G2-2
27G1-1
27G1-2
32G-1
32G-2
40G-1
40G-2
46G1-1
46G1-2
46G1-1
46G1-2
49G-1
51V2
59G2-1
59G2-2
64F-1
74DR
81 U2-1
81 U2-2
81 U2-3
87G1
64G1
64G2
50/27G1
21G2
60VTS1
60VTS2
50BF1
AC
59/81G1-1
59/81G1-2
59/81G2-1

List of Digital Signals for SOER


Over Fluxing 1st step- Set 2
Over Fluxing 2nd step- Set 2
Under voltage 1st step - Set 1
Under voltage 2nd step- Set 1
Reverse power -Set 1
Reverse power- Set 2
Loss of excitation- Set 1
Loss of excitation- Set 2
Negative phase sequence 1st step- Set 1
Negative phase sequence 2 nd step- Set 1
Negative phase sequence 1st step - Set 2
Negative phase sequence 2 nd step - Set 2
Over load 1st step- Speedtronic
Inverse time Over current -Set2
Over voltage 1st step - Set 2
Over voltage 2 nd step- Set 2
Rotor earth fault
Rotating diode fault
Under frequency 1st step- Set2
Under frequency 2 nd step- Set2
Under frequency 3 rd step- Set2
Differential current- Set 1
Stator earth fault 95%- Set 1
Stator earth fault 100% - Set 2
Inadvertance energization - Set 1
Generator under impedance - Set 2
Voltage transformer supervision (T43) - Set 1
Voltage transformer supervision (T44) - Set 2
Unit breaker 52G fault- Set 1
GTG-2
Over Fluxing 1st step - Set 1
Over Fluxing 2nd step - Set 1
Over Fluxing 1st step- Set 2

28 of 35

Remarks

Trip When 52L opened

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
780
781
782
783
784
785
786
787
788
789
790
791
792
793
794
795
796
797
798
799
800
801
802
803
804
805
806
807
808
809
810
811

Alarm
code

Tag No
59/81G2-2
27G1-1
27G1-2
32G-1
32G-2
40G-1
40G-2
46G1-1
46G1-2
46G1-1
46G1-2
49G-1
51V2
59G2-1
59G2-2
64F-1
74DR
81 U2-1
81 U2-2
81 U2-3
87G1
64G1
64G2
50/27G1
21G2
60VTS1
60VTS2
50BF1
AD
59/81G1-1
59/81G1-2
59/81G2-1
59/81G2-2

List of Digital Signals for SOER


Over Fluxing 2nd step- Set 2
Under voltage 1st step - Set 1
Under voltage 2nd step- Set 1
Reverse power -Set 1
Reverse power- Set 2
Loss of excitation- Set 1
Loss of excitation- Set 2
Negative phase sequence 1st step- Set 1
Negative phase sequence 2 nd step- Set 1
Negative phase sequence 1st step - Set 2
Negative phase sequence 2 nd step - Set 2
Over load 1st step- Speedtronic
Inverse time Over current -Set2
Over voltage 1st step - Set 2
Over voltage 2 nd step- Set 2
Rotor earth fault
Rotating diode fault
Under frequency 1st step- Set2
Under frequency 2 nd step- Set2
Under frequency 3 rd step- Set2
Differential current- Set 1
Stator earth fault 95%- Set 1
Stator earth fault 100% - Set 2
Inadvertance energization - Set 1
Generator under impedance - Set 2
Voltage transformer supervision (T43) - Set 1
Voltage transformer supervision (T44) - Set 2
Unit breaker 52G fault- Set 1
Future GTG
Over Fluxing 1st step - Set 1
Over Fluxing 2nd step - Set 1
Over Fluxing 1st step- Set 2
Over Fluxing 2nd step- Set 2

29 of 35

Remarks

Trip When 52L opened

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
812
813
814
815
816
817
818
819
820
821
822
823
824
825
826
827
828
829
830
831
832
833
834
835
836
837
838
839
840
841
842
843

Alarm
code

Tag No
27G1-1
27G1-2
32G-1
32G-2
40G-1
40G-2
46G1-1
46G1-2
46G1-1
46G1-2
49G-1
51V2
59G2-1
59G2-2
64F-1
74DR
81 U2-1
81 U2-2
81 U2-3
87G1
64G1
64G2
50/27G1
21G2
60VTS1
60VTS2
50BF1
AE
94GB1
94GB2
94LB1
94LB2
52G SF6 FLT

List of Digital Signals for SOER


Under voltage 1st step - Set 1
Under voltage 2nd step- Set 1
Reverse power -Set 1
Reverse power- Set 2
Loss of excitation- Set 1
Loss of excitation- Set 2
Negative phase sequence 1st step- Set 1
Negative phase sequence 2 nd step- Set 1
Negative phase sequence 1st step - Set 2
Negative phase sequence 2 nd step - Set 2
Over load 1st step- Speedtronic
Inverse time Over current -Set2
Over voltage 1st step - Set 2
Over voltage 2 nd step- Set 2
Rotor earth fault
Rotating diode fault
Under frequency 1st step- Set2
Under frequency 2 nd step- Set2
Under frequency 3 rd step- Set2
Differential current- Set 1
Stator earth fault 95%- Set 1
Stator earth fault 100% - Set 2
Inadvertance energization - Set 1
Generator under impedance - Set 2
Voltage transformer supervision (T43) - Set 1
Voltage transformer supervision (T44) - Set 2
Unit breaker 52G fault- Set 1
GENERATOR SWITCHGEAR(GTG-1)
Generator breaker alarm (grouped alarm)
Generator breaker fault (grouped fault)
Line breaker alarm (grouped alarm)
Line breaker fault (grouped fault)
52G SF6 alarm

30 of 35

Remarks

Trip When 52L opened

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
844
845
846
847
848
849
850
851
852
853
854
855
856
857
858
859
860
861
862
863
864
865
866
867
868
869
870
871
872
873
874

Alarm
code

Tag No
List of Digital Signals for SOER
52G SF6 FLT 52G SF6 Trip
Breaker Status
74/TC-1
CB Trip coil -1 supervision operated
74/TC-2
CB Trip coil -2 supervision operated
CB Operating Mechanism failed
50BF
Breaker failure relay operated
86BF
Lock out relay 86BF operated
74/86
Lock out relay 86BF supervision relay operated
AF
GENERATOR SWITCHGEAR(GTG-2)
94GB1
Generator breaker alarm (grouped alarm)
94GB2
Generator breaker fault (grouped fault)
94LB1
Line breaker alarm (grouped alarm)
94LB2
Line breaker fault (grouped fault)
52G SF6 FLT 52G SF6 alarm
52G SF6 FLT 52G SF6 Trip
Breaker Status
74/TC-1
CB Trip coil -1 supervision operated
74/TC-2
CB Trip coil -2 supervision operated
CB Operating Mechanism failed
50BF
Breaker failure relay operated
86BF
Lock out relay 86BF operated
74/86
Lock out relay 86BF supervision relay operated
AG
GENERATOR SWITCHGEAR(Future)
94GB1
Generator breaker alarm (grouped alarm)
94GB2
Generator breaker fault (grouped fault)
94LB1
Line breaker alarm (grouped alarm)
94LB2
Line breaker fault (grouped fault)
52G SF6 FLT 52G SF6 alarm
52G SF6 FLT 52G SF6 Trip
Breaker Status
74/TC-1
CB Trip coil -1 supervision operated
74/TC-2
CB Trip coil -2 supervision operated
CB Operating Mechanism failed

31 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
875
876
877
878
879
880
881
882
883
884
885
886
887
888
889
890
891
892
893
894
895
896
897
898
899
900
901
902
903
904

Alarm
code

Tag No
50BF
86BF
74/86
AH
26TEX - 1
26TEX - 2
76G1-1
76G1-2
30TEX
74RB-1
74RB-2
74RB-1/2
94VT- EX1
94VT- EX2
59F
AI
26TEX - 1
26TEX - 2
76G1-1
76G1-2
30TEX
74RB-1
74RB-2
74RB-1/2
94VT- EX1
94VT- EX2
59F
AJ
26TEX - 1
26TEX - 2
76G1-1
76G1-2
30TEX

List of Digital Signals for SOER


Breaker failure relay operated
Lock out relay 86BF operated
Lock out relay 86BF supervision relay operated
EXCITATION-GTG-1
Excitation transformer Over heating 1st step
Excitation transformer Over heating 2nd step
Excitation over current 1st step-Set1
Excitation over current 2nd step-Set2
MV excitation transformer bleeding fuse fault
N1 excitation brige fuse fault
N2 excitation brige fuse fault
N1 & 2 excitation brige fuse fault
Excitation CB position
Excitation CB trip
Exciter Overvoltage
EXCITATION-GTG-2
Excitation transformer Over heating 1st step
Excitation transformer Over heating 2nd step
Excitation over current 1st step-Set1
Excitation over current 2nd step-Set2
MV excitation transformer bleeding fuse fault
N1 excitation brige fuse fault
N2 excitation brige fuse fault
N1 & 2 excitation brige fuse fault
Excitation CB position
Excitation CB trip
Exciter Overvoltage
EXCITATION-FutureGTG
Excitation transformer Over heating 1st step
Excitation transformer Over heating 2nd step
Excitation over current 1st step-Set1
Excitation over current 2nd step-Set2
MV excitation transformer bleeding fuse fault

32 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
905
906
907
908
909
910
911
912
913
914
915
916
917
918
919
920
921
922
923
924
925
926
927
928
929
930
931
932
933
934
935
936

Alarm
code

Tag No
74RB-1
74RB-2
74RB-1/2
94VT- EX1
94VT- EX2
59F
AK
94 GPM
74GT/52GT
94AVR1
94AVR2
94NUM
94VTM-1
94VTM-2
94VTM-1/2
94VTP1
94VTP2
94VTC
94VTS1/2
94VTP3
30-F43
30-F44
30-F42
NGT alarm
NGT trip
94UAT-1
94UAT-2
64B1
94HV

List of Digital Signals for SOER


N1 excitation brige fuse fault
N2 excitation brige fuse fault
N1 & 2 excitation brige fuse fault
Excitation CB position
Excitation CB trip
Exciter Overvoltage
MISCELLANEOUS-GTG-1
General watchdog of generator protection module
Gas Turbine fault inducing generator trip
Watchdog AVR 1 - Transfer from AVR1 to AVR 2 auto channel
Watchog AVR 2 - Transfer from AVR 2 to AVR1 auto channel
Watchdog AVR 1/2- Transfer from AVR 1/2 to manu channel
Regulation VT, MCB's open - Transfer from AVR1 to AVR2 auto channel
Regulation VT, MCB's open - Transfer from AVR2 to AVR1 auto channel
Regulation VT, MCB's open - Transfer from AVR1/2 to manu channel
Protection VT, MCB's open
Protection VT, MCB's open
Metering VT, MCB's open
52G Synchro VT, MCB's open
Protection VT, MCB's open (64B)
Voltage transformer F43 fuse bleeding fault
Voltage transformer F44 fuse bleeding fault
UAT fuse bleeding fault
NGT Over heating alarm
NGT Over heating trip
UAT Circuit breaker position for alarm
UAT Circuit breaker trip
MV Bus duct/Cable earthing detection Set-1
33KV protection trip
Power house ventilation system start
Power house ventilation system stop
Power house ventilation system common alarm
unit fuel drain pit level Hi alarm

33 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
937
938
939
940
941
942
943
944
945
946
947
948
949
950
951
952
953
954
955
956
957
958
959
960
961
962
963
964
965
966
967

Alarm
code

Tag No

List of Digital Signals for SOER


unit fuel drain pit level Hi Hi alarm
AL
MISCELLANEOUS-GTG-2
94 GPM
General watchdog of generator protection module
74GT/52GT Gas Turbine fault inducing generator trip
94AVR1
Watchdog AVR 1 - Transfer from AVR1 to AVR 2 auto channel
94AVR2
Watchog AVR 2 - Transfer from AVR 2 to AVR1 auto channel
94NUM
Watchdog AVR 1/2- Transfer from AVR 1/2 to manu channel
94VTM-1 Regulation VT, MCB's open - Transfer from AVR1 to AVR2 auto channel
94VTM-2 Regulation VT, MCB's open - Transfer from AVR2 to AVR1 auto channel
94VTM-1/2 Regulation VT, MCB's open - Transfer from AVR1/2 to manu channel
94VTP1
Protection VT, MCB's open
94VTP2
Protection VT, MCB's open
94VTC
Metering VT, MCB's open
94VTS1/2 52G Synchro VT, MCB's open
94VTP3
Protection VT, MCB's open (64B)
30-F43
Voltage transformer F43 fuse bleeding fault
30-F44
Voltage transformer F44 fuse bleeding fault
30-F42
UAT fuse bleeding fault
NGT alarm NGT Over heating alarm
NGT trip
NGT Over heating trip
94UAT-1
UAT Circuit breaker position for alarm
94UAT-2
UAT Circuit breaker trip
64B1
MV Bus duct/Cable earthing detection Set-1
94HV
33KV protection trip
Power house ventilation system start
Power house ventilation system stop
Power house ventilation system common alarm
unit fuel drain pit level Hi alarm
unit fuel drain pit level Hi Hi alarm
AM
MISCELLANEOUS-Future GTG
94 GPM
General watchdog of generator protection module
74GT/52GT Gas Turbine fault inducing generator trip
94AVR1
Watchdog AVR 1 - Transfer from AVR1 to AVR 2 auto channel

34 of 35

Remarks

Annexure-1: SOER Signals for Rafha Power Plant

Sl.No
968
969
970
971
972
973
974
975
976
977
978
979
980
981
982
983
984
985
986
987
988
989
990
991

Alarm
code

Tag No
94AVR2
94NUM
94VTM-1
94VTM-2
94VTM-1/2
94VTP1
94VTP2
94VTC
94VTS1/2
94VTP3
30-F43
30-F44
30-F42
NGT alarm
NGT trip
94UAT-1
94UAT-2
64B1
94HV

List of Digital Signals for SOER


Watchog AVR 2 - Transfer from AVR 2 to AVR1 auto channel
Watchdog AVR 1/2- Transfer from AVR 1/2 to manu channel
Regulation VT, MCB's open - Transfer from AVR1 to AVR2 auto channel
Regulation VT, MCB's open - Transfer from AVR2 to AVR1 auto channel
Regulation VT, MCB's open - Transfer from AVR1/2 to manu channel
Protection VT, MCB's open
Protection VT, MCB's open
Metering VT, MCB's open
52G Synchro VT, MCB's open
Protection VT, MCB's open (64B)
Voltage transformer F43 fuse bleeding fault
Voltage transformer F44 fuse bleeding fault
UAT fuse bleeding fault
NGT Over heating alarm
NGT Over heating trip
UAT Circuit breaker position for alarm
UAT Circuit breaker trip
MV Bus duct/Cable earthing detection Set-1
33KV protection trip
Power house ventilation system start
Power house ventilation system stop
Power house ventilation system common alarm
unit fuel drain pit level Hi alarm
unit fuel drain pit level Hi Hi alarm

Remarks

NOTE : Minimum 20% spare points shall be provided in each equipment monitored points and Minimum points.

35 of 35